LOAD SPECIFICATIONS:
1. Design Loads:
1.1 Dead Loads Computation
1.1.1. Residential Building (2nd floor)
• Slab (250mm) stone concrete fill 250*0.02354 (Refer to Table 204-2 NSCP 2015) = 5.89
kPa
• Acoustic fiber board as ceiling (Refer to Table 204-2 NSCP 2015) = 0.05 kPa
• Ceramic tile on 13mm mortar bed (Refer to Table 204-2 NSCP 2015) = 0.77 kPa
• Electrical and Plumbing Materials (Assumed) = 0.3 kPa
• 6” CHB fully grouted using 19.6 kN/m3 density of unit, plastered in both sides, 2.7m high
(exterior walls)
(Refer to Table 204-2 NSCP 2015)
(2.82kPa + 2(0.24)kPa) = 3.3 kPa
• 4” CHB fully grouted using 19.6 kN/m3 density of unit, plastered in both sides,
2.7m high (interior walls or partition)
(Refer to Table 204-2 NSCP 2015)
(2.82kPa + 2(0.24)kPa) = 3.3 kPa