Professional Documents
Culture Documents
33-SFA-2022 Ramesh Natrajan - Ver17 - 13 June 2022
33-SFA-2022 Ramesh Natrajan - Ver17 - 13 June 2022
Depending on the level of water in the tank, the water pressure at the outlet
shall change if the valves of both the tanks are kept open in a similar manner.
When it comes to comparing this with a battery, if the current drawn from
two batteries of different sizes (different capacities) are the same, then the
voltage (pressure) shall reduce as the level decreases. It is obvious that the
bigger capacity battery shall last for a longer time.
A Comparison
Water Tanks Battery Cells
Valve opening in the water tank is the same for both tanks – irrespective of
the size of the water tank A load of 40W bulb
Thus, it is clear, from the comparison above, that the pressure in both water
tanks being the same, due to the same height of water in both the tanks, with
both the water outlet valves being uniformly open – the bigger tank has a
larger capacity. It can dispense water for a longer period.
Similar to the case of water – explained above – the larger capacity cell shall
have a greater capacity to give out electricity than a smaller capacity battery
cell.
Series Connection
To increase the pressure of water, we can add tanks one above the other so
that the height of the water is more, and there is more pressure at the outlet
valve.
In the case of battery cells connected similarly, in series, the voltage shall
become additive. The voltage drop shall be gradual for a fixed load, in the
case of a higher voltage battery, when compared to the drop in voltage of the
lower voltage battery.
Parallel Connection:
To increase the ability of water tanks to dispense water for a longer period of
time, without the need for higher pressure, we can keep tanks side by side,
instead of one above the other. In this case, the pressure shall be the same as
for a single 'tank'.
In the case of battery cells connected in parallel – similar to the water tanks –
the voltage shall remain constant at 2 Volts which is the voltage of one cell.
However, the load can draw current for a longer duration since the capacity
has increased. The capacity of the battery shall be the sum of the capacities of
the number of cells connected in parallel.
Ohm’s Law
Ohm's law states that the voltage between two points is directly proportional
to the current or electricity passing through the resistance & directly
proportional to the resistance of the conducting circuit.
The formula is expressed as V = IR
Thus, it expresses the relation between Voltage (V), Current (I) and
Resistance (R).
If there are two circuits connected to the same voltage, i.e. say we have a
similar cell connected to the load, the current drawn by the load can be
greater in that circuit of lower resistance.
As you can see in the illustration above – the tanks are of the same size, with
the level of water in the tanks being equal. Hence the pressure at the outlet is
equal.
However, the discharge of water from one tank is through a small pipe, i.e.
high resistance. In the other tank, the discharge is through a larger diameter
pipe, i.e. low resistance to the flow of water.
Obviously, the current of water flow shall be more from the tank, which has a
larger diameter pipe, where the resistance to the flow of water is low.
In this sketch of batteries, we have two cells of the same voltage. One cell is
connected to a high resistance circuit and the ammeter shows a low current
flowing through it. The other cell connected to a circuit of low resistance
shows a higher current passing through the circuit.
Now see the sketch below: -
The pressure from one tank is more in comparison to the pressure from the
other tank. Since the resistance is the same, the flow shall be more from the
tank having higher pressure.
In the case of batteries, we observe that the heater load being the same; more
power shall be delivered by batteries of higher voltage compared to a battery
of lower voltage.
Please see the following sketch for a better understanding of the concept
being explained:
In the above figure, we have shown two tanks having water drain pipes at
different levels. Since the drain pipe is fixed at a lower level in one tank, the
water available for use in this tank is more than the water available for use in
the other tank, where the drain pipe is fixed at a higher level. This is despite
the fact that both the tanks are of the same size, with the top level of the water
being the same, such that the pressure is the same.
The varying level of drain pipes ensures that the flow of water is restricted,
such that water will not flow out of the tank once it has dropped to a
particular level.
This cut off point decided by the placement of the drain is the cut off pressure
point. Irrespective of the rate of flow of water, which can be adjusted by
keeping the valve fully open, or partially open, or equally open, in both the
tanks, the cut off of water supply shall be maintained, based on set level,
depending on the location of the outlet in the tank.
A low cut off ensures good output, i.e., output for a longer duration provided
other parameters are constant for both the tanks. A higher cut off means less
output.
In the case of a battery, a similar working can be obtained by setting the cut
off voltage. The cut-off voltage is the low voltage set point up to which a
load can draw current from the battery during the discharge operation. It is
therefore preferred to set a battery voltage cut off to as low a level as
permitted by the battery manufacturer whenever one is designing a circuit, for
best performance, as regards back up from a battery.
INTRODUCTION TO
BATTERIES
A battery is a device which stores power. This power is used to run different
loads. The chemicals in the device, transform themselves, as they deliver the
power to the load.
Basically, speaking there are two types of batteries – Primary & Secondary.
Primary batteries are those batteries, wherein a certain defined quantity of
chemicals, are available. Once this quantity is spent, over a period of time, as
electrical energy to power a device – the battery has to be discarded.
Secondary batteries are those batteries, which can be used repeatedly, for a
defined period. These batteries can be connected to a load and discharged,
and then charged again for further discharge. The number of such cycles, of
charge and discharge, is determined by the manufacturer. This cycle life is
based on the output power, that the battery has to deliver and the defining
factor is the amount of materials that the device contains. Battery life is
defined as the number of cycles, or, number of years, depending on its
application. Examples of secondary batteries commonly used, are the
batteries, used in motorcycles, cars, buses, trucks, UPS systems, home
inverters, street lighting, railway signaling, telecom applications, battery
operated scrubbers, golf carts, material handling applications etc. etc.
To summarize – a secondary battery can be defined as an electrochemical
device, which converts chemical energy to electrical energy, by a reversible
reaction.
There are various types of secondary batteries viz. nickel cadmium, lead acid,
nickel metal hydride, lithium ion, etc. etc.
We shall try and concentrate on the topic of lead acid batteries, with
references to other battery types restricted, to comparison only, as and when
required.
Lead acid batteries have been around for a very long time and are considered
a proven technology, which is rugged and safe to use. The battery as
developed, in the initial stages has fundamentally remained the same, but
developments over the years have culminated into the emergence of batteries
with tubular plates, for industrial applications, which need a long life.
Subsequent developments have resulted in Valve Regulated Batteries
popularly known as Sealed Maintenance Free Batteries.
The manufacture of lead acid batteries is, highly process oriented, requiring a
basic knowledge of metallurgy, chemical engineering and mechanical
engineering as well as electrical engineering. The entire process from raw
material stage to final inspection, after the assembly of battery, needs 2 to 3
weeks conventionally.
The following flow charts outline the process of an automotive battery and an
inverter battery manufacture.
You would have noticed that the process of manufacture of an "Inverter
Battery", which has tubular positive plates, is a little different from the
process of manufacturing of an "Automotive Battery".
The battery designer adapts the product and ensures that the battery is made
to suit the application.
To elaborate further – the automotive battery has to be compact, lightweight
and be suitable for cranking applications.
An industrial stationary battery has to have a long life and give power to the
load over a defined duration, on a consistent basis, without delivering surge
high current like in a engine starting application. Such stationary batteries
need not be compact and can be heavy. Their being of low maintenance
characteristics or no maintenance type, can however be an advantage.
An industrial traction battery has to be as compact as possible, and shall need
to be rugged enough to work as a prime mover of the electric vehicle, with a
capability to undergo, at least one charge / discharge cycles every day. The
variety of cells, which are required to be made in different sizes, to meet the
varying demands of material handling vehicle manufacturers, is another
matter altogether, in the case of industrial traction batteries.
Attached are pictures showing the various types of lead acid batteries. The
design characteristics are related to the application. The applications of
various lead acid batteries and the target market details are also given.
MACHINES FOR BATTERY
MANUFACTURE
I t is clear from the process flow chart of batteries that lead and oxide of
lead are the main raw materials required for the manufacture of batteries.
The other components, which can be purchased from various vendors, viz.,
battery separators, tubular bags, plastic containers & covers, vent plugs etc.,
are easily available. The chemicals to be used in the process of paste mix
manufacture, as well as sulphuric acid, can also be sourced from reputed
vendors. These components and speciality chemicals are usually not made by
the battery manufacturer.
The process being quite cumbersome, the manufacture involves different
sections/departments, carrying out varied activities over quite a long duration.
Hence, a lot of machines are required, as mentioned in the process flow chart.
As with any industry, it is possible to do a lot of automation and thereby
reduce labour, increase productivity as well as production, optimise costs,
improve quality, have consistency in the product etc. etc. However, the
degree of automation is dictated by the individual manufacturer's market
demands and one's capacity to invest in high value raw materials.
The battery industry also has some manufacturers who do certain operations,
manually or in a semi-automatic manner. This enables the setup of battery
production as a SSI unit.
The photographs of various machines required for the production of battery
plates, assembly and charging, are as shown.
Battery Charger
ELIND - India
The machines mentioned cover the major processes. The jigs, fixtures, online
test equipments etc., required for fitting on machines shall depend on the type
of batteries to be manufactured. Other related equipments to be installed,
which shall include demineralised water plant, test equipments, compressors,
material handling equipments, effluent treatment plant etc. etc. shall depend
on the proposed plant capacity.
The list provides data to the extent possible. The detail of machine
manufacturers covers only some machine manufacturers in India who are
amongst the many other reputed manufacturers and who supply proven
machines and is not an exhaustive list.
Large scale manufacturers of batteries install lead smelting plants to recycle
scrap batteries and manufacture Lead Alloy. They also produce Pure Lead
from this alloying facility to process it further as Lead Oxide. Pure Lead is
converted to Lead Oxide by processing it in Ball Mills or Barton Pots.
India has a lot of vendors of equipments who make good quality machines to
produce Lead Alloys & Lead Oxide.
INVERTER BATTERIES
B atteries of the lead acid kind popularly used in home inverter batteries
are of two kinds – sealed maintenance free type or the flooded
electrolyte type.
The major difference at the customer’s end i.e. at the point of use, is that, the
flooded electrolyte type battery can be maintained by water topping up,
whereas the sealed maintenance free batteries cannot be maintained.
Before we proceed further – let us first understand the working of an inverter
coupled to the battery.
A lead acid battery has a series of positive plates and a series of negative
plates, inside. These are the electrodes.
They are the reason, why power is delivered from the battery, through the
inverter, to the load. The inverter converts DC power to AC power, in case of
a power outage.
During this period, the active material of the positive plates converts to
PbSO4, from their active state of PbO2. At the same time the active material
of the negative plates which is in the form of sponge lead, converts itself to
PbSO4.
Once this chemical transformation has taken place completely, the ability of
the electrodes to deliver power is over.
The battery needs to be recharged, by connecting it to a charger. The inverter
unit consists of a suitable charger, which starts working, as soon as AC power
is available.
The charger unit draws A.C. power from the electric mains, and converts it to
DC power, and gives it to the battery. A chemical transformation of PbSO4 to
PbO2 in the case of positive plates, and sponge Pb in the case of negative
plates, now takes place.
The discharged plates are now charged, for delivery of power to the load, in
case of the next outage of power.
This cycle of charge / discharge, with the accompanying chemical
transformation continues, depending on product and maintenance quality of
course, within the manufacturer’s design specifications.
The chemical reaction explained above is depicted as follows:
Material Particulars Charged Discharged
Positive PbO2 PbSO4
Negative Pb PbSO4
Electrolyte Dil. H2SO4 Very Dil. H2SO4
We shall now address the various questions, which a battery inverter user
usually has, one by one.
Why do inverter batteries bulge?
The major cause of bulging of batteries is due to undercharge.
The lead sulphate formed on both the positive & negative plates, during
discharge, occupies more space, than the original materials of the plates, viz.
lead dioxide & sponge lead.
If a battery is left in a undercharged state, due to a fault in the inverter, or due
to the charger being of smaller capacity w.r.t. battery requirement, or battery
being of a large capacity, the battery plates shall not get sufficiently charged.
The solution to this problem is to ensure that the battery coupled to an
inverter, is of correct capacity, as per the recommendation of the inverter
manufacturer.
An overcapacity battery coupled to a under capacity charger, can end up with
undercharged batteries, which, seemingly bulge and leave the customer
dissatisfied, as regards power back up duration.
The person buying the inverter must never suggest to the dealer, to supply a
higher capacity battery, for longer duration of power back up, without
understanding the ability of the charger, to charge the battery from its fully
discharged state.
Why do inverter batteries need top up water?
This query is relevant to flooded electrolyte batteries, which can be
maintained by the user.
The electrolyte in a lead acid battery is dilute sulphuric acid, which has the
water component drying OFF, due to high ambient, or in certain cases, due to
overcharge of the batteries. This water component needs to be replenished
periodically.
At times, when a customer negotiates too much on the price, the dealer ends
up supplying a lower capacity battery, or an automotive battery instead of a
tubular battery, to ensure that his margins are safeguarded. The voltage of the
battery, he ensures to be, as per inverter requirements. Such a compromise,
on the part of system dealer, ends up with overcharge of the battery. An
inverter having a charger of say 15 Amps capacity to charge a 12V 120Ah
battery, ends up charging a 12V 60Ah or 12V 80Ah battery, at a current of 15
Amps, which is very high for the 60 Ah or 80Ah battery, This shall surely
heat up the lower capacity smaller battery, necessitating more frequent water
topping up.
A fault in the charger of the inverter, with the charger not tapering down the
current, as the battery picks up charge, or not cutting off charging, as soon as
the battery is fully charged, can be another possible reason for batteries
needing more top up water, or needing top up water frequently.
Why does the back up of an inverter battery reduce?
The back up of an inverter battery depends on the load connected and the
capacity of the battery.
More the load – lesser will be the backup duration.
Lower the battery capacity – lesser will be the backup duration.
Ensure that the load on the system is not increased over a period of time, to
draw a false conclusion that the backup was better earlier, and, has reduced
over a period of time.
A natural reduction in backup over a long period of usage, despite load
remaining constant, is acceptable as the battery ages.
However do check tightness of battery cable connections and ensure that
petroleum jelly is applied to the terminals periodically, during routine
maintenance, so that loose contact is not the cause of this reduced back up
duration.
Why does water or acid bubble out of the top of inverter batteries?
The most commonly observed cause of water coming out of the top of
inverter batteries is overfilling of water during top up.
Another possible reason is overcharging due to use of smaller capacity
battery, or, a bigger capacity charger, or, a fault in the charger.
Why do inverter batteries – sometimes explode?
Batteries on charge release hydrogen gas, which needs to escape through the
vent holes of the vent plugs, in the case of flooded electrolyte batteries.
If the vent holes are covered due to dust or any material kept on top of the
battery, the buildup of gases inside the battery increases the pressure on the
battery container, leading to an explosion.
Another possible reason for explosion is a metallic contact, which causes
shorting of the positive and negative terminals of the battery. It is necessary
to ensure that only insulated spanners or tools are used whilst working on
batteries. Accidental shorting of terminals, or any metallic item coming in
contact with exposed terminals of the battery, can cause an explosion.
Loose contact in the terminals, which can cause a spark, is to be avoided.
When a battery is on charge – explosive hydrogen gases evolved, can come
out through the vent holes. A spark due to loose contact can ignite and be the
cause of a fire or explosion. These are of course rare occurrences and are not
very common with low voltage systems of home inverter.
To summarize the above
1) Avoid overfilling.
2) Ensure proper charging – no under charging
3) Keep terminals clean and tightly connected.
4) Periodically check whether the batteries are being overcharged and correct
such a fault, if any.
5) Ensure that the load connected, to the batteries, is as per recommendation.
6) Clean the vent plugs during routine maintenance, to ensure that the vent
holes are not clogged.
Finally but most importantly – do buy inverter and batteries from a dealer
who gives you the system, as per the manufacturer’s recommendations.
Please note that an inverter meant for sealed maintenance batteries, has the
charger settings, which are different from the settings, meant for flooded
electrolyte batteries. Do not interchange a sealed maintenance free battery
with a flooded electrolyte battery or vice versa, when you need to change the
batteries of an inverter. This can be done only after changing the charger
settings in the inverter.
UPS RELIABILITY
R eliability of a UPS system or Home Inverter system is a matter of
concern to the user, more so if the UPS is meant to supply power in
cases of emergency to highly critical and sensitive loads.
To ensure the reliability of power availability, at times of power outage from
the utility, maintenance of the UPS system, which includes batteries, is an
absolute must. The maintenance must not be restricted to breakdown
maintenance. The maintenance, in fact, must be preventive & predictive in
nature.
The schedule for preventive maintenance must be followed strictly, with a
special focus on batteries, considering that batteries are the component
needing a top up with water, corrosion resistant coating at contact points of
the terminals, cleaning of the battery top as well as vent holes of the vent
plugs etc. etc. The UPS per se, though it is complex electronic equipment, has
no moving parts other than cooling fans if the fans are provided. Ensuring
cleanliness of the UPS, using a cloth for wiping and a blower to blow off
accumulated dust, is usually sufficient.
The preventive maintenance of UPS and batteries must be assigned to
qualified personnel, with greater stress, on battery maintenance.
In any case, the UPS cannot be generally repaired, reset, or attended to, at the
site, in case of problems in the UPS. It has to be usually done by the factory,
or by factory trained personnel, in a service workshop. As long as a UPS
manufacturer has the spares available in the city of operation and has an
authorised service centre, the user has an assurance as regards UPS.
Diagnosis of battery related issues and the promptness with which battery
problems can be sorted out, as and when there are back up related issues, or a
failure of UPS, is, therefore, the only matter of concern for the UPS user.
The UPS vendor must have,
r An accessible and responsive service organisation.
r Battery service experts who shall attend to calls promptly.
r Technical ability and expertise to handle service needs of UPS and battery.
r A team offering periodic preventive maintenance, on a regular basis, in a
defined manner.
r A scheme offering Annual Maintenance Contracts.
r A trained team, with quick response capability.
Distributors and dealers of UPS systems, who do not have the capability to
solve problems at the site, are unsuitable for this work. Such vendors are
unable to meet the needs of the customer, who invest in high end costly UPS
systems. The customer, who is the end user, must be wary of such agencies
and buy a UPS system or Home Inverter system based on the above
guidelines.
The positive of one battery is connected to the negative of another battery and
as per sketch.
3 batteries of 12V 100Ah connected in series shall deliver 36V 100Ah.
12V + 12V + 12V = 36 Volts
The capacity of one battery is 100Ah and due to the series connection,
capacity of 3 batteries shall be remaining the same 100Ah.
Whenever batteries are connected in parallel, the capacity is additive and
voltage is constant.
The positive of one battery is connected to the positive of another
battery and the negative of one battery is connected to the negative of another
battery as per sketch.
3 batteries of 12V 100Ah connected in parallel shall deliver 12V 300Ah.
100 Ah + 100Ah + 100Ah = 300 Ah
The voltage of one battery is 12V and due to parallel connection, the voltage
of 3 batteries shall remain the same 12 Volts.
At times batteries are connected in a complex combination of series and
parallel connection. This is uncommon but done especially in cases where
high Ah capacities are required.
For the sake of understanding the method of calculation, we shall see how
such a connection is done using sets of 3 nos. of 12V 100Ah batteries.
In such cases, care must be taken to ensure that discharging and recharging is
uniform in all strings of batteries.
It is possible to check the D.C. current using a clamp meter. The current can
be kept constant in parallel strings by keeping the length and cross section of
the cables constant. This ensures that the resistance being the same, the
current is uniformly distributed. Alternatively – the introduction of electronic
controls in the circuit to monitor and vary the current of parallel strings is
possible. However, this shall entail additional costs.
BATTERY CHARGERS
A charger is a device which returns the charge to a discharged battery.
As such, a lead-acid battery needs to be charged after manufacture and later
on during regular use. Charging done after assembly of the battery at the time
of commissioning of battery for use is referred to as commissioning charge or
initial charging. Subsequent charging after discharge is known as recharging.
The devices used for initial charging at the manufacturer's factory or the
distributor/dealer's premises are usually rectifiers or chargers which use
utility AC power. These chargers are of constant current DC output type or,
at times constant voltage chargers.
The recharge of the battery is carried out by various methods – depending on
the application. Automotive batteries, including the ones used for
motorcycles, are charged using the vehicle's alternator. Home inverters &
UPS batteries of the stationary type are charged using a float/boost charger
which is a component inside the inverter.
Batteries coupled to solar photovoltaic systems are charged by solar panels
through a charge controller, which is also a part of the inverter. The charge
controller limits the input charge to the battery as the battery gets charged.
The solar panels draw energy from the Sun in this case.
Batteries used in E-Rickshaws or electric vehicles or scrubbers, sweepers &
golf carts are referred to as Deep Cycle Batteries and these batteries are
charged after every cycle of use. Since such batteries are fully discharged,
they need to be recharged using onboard chargers or external chargers having
output DC current, which reduces as the battery voltage increases.
Traction batteries, i.e. batteries used in industries for motive power
applications, are charged using chargers having substantial output current at
the start, which tapers down to an equalising charge current as the battery
reaches a full state of charge.
In the charging process, AC power is converted to DC power and then
supplied to the battery or a bank of batteries. This process oxidises the lead
sulphate of the positives to lead dioxide and reduces the lead sulphate of the
negatives to sponge lead by a simultaneous redox reaction. Simultaneously
the density of the electrolyte increases. The electrolyte being sulphuric acid, a
noticeable rise in specific gravity of the electrolyte is observed as and when a
battery is charged. The specific gravity is measured using a hydrometer.
We shall now discuss the various methods of charging batteries for a better
understanding of the terms used in industry parlance.
a) Constant Current Method.
b) Constant Voltage Method.
c) Modified Constant Voltage Method.
d) Taper Charging.
e) Trickle Charging.
f) Float Charging.
g) Equalising Charge.
a) Constant Current Charging:
Constant current charging is often used to charge all types of lead-acid
batteries at the manufacturer's premises, where the Ah input is a critical factor
that is monitored and recorded as a quality parameter. Constant current
charging is also used invariably in the laboratory because of the convenience
of calculating ampere-hour input and because constant current charging is
required to determine Ah and Wh efficiency. Constant current charging at
very low currents is often resorted to at site to decrease the sulfation in
batteries which have been over-discharged and/or under charged.
b) Constant Voltage Charging :
In this method of charging, the charging is done with the voltage maintained
at a constant defined value per cell. The value of the initial or starting current
of a completely discharged battery, when put on charge, often exceeds the
normal and usually high rate of charging. During the charge, as the battery
picks up a charge and the voltage of the battery slowly increases and reaches
the gassing voltage, the current is set to automatically reduce to a value much
below that of the high starting rate. In such chargers, the end of the charge
currents are set very low and are always lower than the finishing rate current
of the constant current chargers.
c) Modified Constant Voltage Charging :
Modified constant voltage charging is used for stationary batteries used in
UPS applications, home inverters and telecom application batteries wherein
the charger or rectifier is always connected to the battery. In this case, the
charger has an upper current limit. The charge current is continuously fed till
the battery reaches a defined voltage. After the battery has reached the
defined voltage, the charger current starts reducing as the voltage rises and
the battery gets fully charged. Once the battery is fully charged, the battery is
maintained within a range of voltage known as float voltage so that it is ready
for discharge in a fully charged state.
The modified constant voltage charge, with constant and high starting
currents and lower finishing current rates, is also used for traction and
monobloc deep cycling batteries. These batteries are rated for discharge at the
5 hr. rate to a depth of 80%. The recharge current of these batteries is
adjusted so that the charging is completed in a 6 to 8 hrs. duration for
batteries used in temperate climate conditions. The recharge current of these
batteries is adjusted so that the charging is completed in 12 to 14 hrs. period
for batteries used in tropical climatic conditions. The charger is set for the
constant potential in a range of 2.35 V to 2.40 V per cell, which is the gassing
voltage, and the starting current is settable in a range of 12 to 20 A per 100
Ah of the rated 5-h ampere-hour capacity. The initial current is maintained
constant until the average cell voltage in the battery reaches 2.35 V to 2.40 V
per cell. The current drops at constant voltage, tapering down to the finishing
rate of 3 A to 5 A per 100 ah, which is then maintained for a period of 3 to 6
hrs. using a settable timer. The time of charge is selected such that Ah input
which goes into the battery, is around 10 % to 20% more than the ampere-
hour output of the previous discharge. The charging time can be increased or
reduced by setting the initial current limit rate in such chargers.
d) Taper Charging:
Taper charging is similar to the modified constant voltage charging method.
However, in this case, the charger has fewer controls and thereby costs less.
Hence there is a possibility of more gassing during the recharge along with an
increase in cell temperature. The degree of the gassing and temperature rise
shall depend on the current taper profile and is thus a characteristic of the
charger design. Battery life can be affected in such chargers due to the
increase in battery temperature and gassing if the chargers are not selected
appropriately.
The end of the charge is often related to a fixed voltage rather than a fixed
current. Modified constant voltage charging methods with initial currents
based on battery Ah capacity is to be selected based on ambient temperatures
at the place of use to have a good battery performance and life.
e) Trickle Charging:
A trickle charge is a continuous constant current charge at a low rate. The
charge current is usually 1% of the battery Ah capacity. The trickle charges
current is used to maintain the battery in a fully charged condition. A trickle
charger delivers a current significant enough to compensate for self-discharge
losses as well as to restore the energy to a battery discharged during
intermittent use of the battery. This method is usually resorted to for SLI
batteries when the battery is removed from the vehicle in a service station or
when the battery is idle for long periods duly disconnected from its regular
charging source. It is also used for Genset batteries. In the case of Genset, the
trickle charger is permanently connected to the battery so that the battery
remains fully charged always and can respond to emergency situations.
f) Float Charging :
Float charging is a low-rate charge current which is fed to a battery. This sort
of charging is done to maintain the battery in a state of readiness for
discharge as and when demanded by the load. A float charger keeps the
battery in a fully charged condition. This method of charging is used mainly
for stationary batteries. The float voltage for a flooded electrolyte vented
battery is usually 2.16 V to 2.20 V per cell. The float voltage for a lead-acid
VRLA/SMF battery is usually2.20 V to 2.25 V per cell. The float charger
ensures that the voltage of the battery is continuously maintained within the
defined parameters of the set voltage range.
g) Equalising Charge :
It is commonly believed that whilst a battery is being `float charged’, it will
have consistent voltages and specific gravities and shall be in a fully charged
condition. This shall necessarily not be the case always, especially in
batteries having tall plates. A phenomenon known as acid stratification can
take place, leading to an uneven current distribution between the plates of the
cell. Stratification is the separation of electrolytes into distinct layers of
differing densities. The density of the electrolyte at the bottom of the cell
shall be higher than the density of the electrolyte at the top of the cell.
The resultant uneven current distribution and the varying `acid strength’ can
cause variation in cell plate characteristics. There can be a gradual discharge
of portions in the plates located in the low current density areas. Initially, the
overall cell voltage remains at the correct float level and no variations are
seen when the cell is new.
This partial discharge in some areas of the cell plates causes sulphation. The
degradation of cell quality due to sulphation worsens with time. The battery's
internal resistance gets affected, causing considerable variations in individual
cell voltages as well as specific gravity. The only corrective action possible to
rectify any such battery or cell is an equalising charge.
Such a battery should be periodically equalised by charging with a constant
current which is 4 to 6 percent of the ampere-hour capacity at the 10 hour rate
in the case of stationary batteries.
Batteries must be fully recharged prior to equalising. The recharge prior to
equalising charge should continue until such time as the specific gravity and
voltage readings of individual cells have reached a maximum value and have
ceased to rise for a period of three consecutive hourly readings.
In the case of traction batteries also, equalising is required. Traction batteries
are not connected to a charger when in use and are not on float charge.
Traction batteries are fully discharged to 80% depth of discharge almost on a
daily basis. These batteries need an equalising charge periodically. Battery
manufacturers usually recommend the equalising charge current rate as 3 to 5
percent of the ampere-hour capacity at the 5 hour rate. Traction batteries are
also to be equalised after a full recharge.
The purpose of equalising is attaining the constancy of voltages and specific
gravities. The actual value of voltage is not an important factor at this point in
time. It is recommended that equalising charges be carried out as per the
manufacturer's advice..
CAPACITY RATING OF
BATTERIES
T his test is done to determine the capacity of the battery, to deliver the
current in amperes which a battery has to deliver, for the defined period,
as per its rating, in line with manufacturer's specification. This capacity is
usually mentioned on the battery. The manufacturer usually specifies the
battery in conformance with industry standards, providing the following
details:
1) Battery voltage in volts.
2) Battery capacity in ampere hours.
3) Battery rating as C10 or 10 hr.
4) Battery serial number.
5) Month and year of manufacture.
6) Make or brand name of the battery.
Let us take the case of a tubular inverter battery used in homes.
Suppose we have a 12 V 100 Ah battery rated at 10 hr. rate; the battery is
expected to deliver 10 amperes constant current for 10 hrs. to an end voltage
of 10.5 Volts.
The battery behaves differently at various rates of discharge, i.e. it lasts
longer at lower currents of discharge and lasts for a lesser period at higher
currents of discharge.
As per the standards IS 13369:1992, the latest amendment in the year 2003,
the accepted performance of a battery for various rates of discharge is as
follows:
Capacity expected
Rate Of Discharge End Voltage
as %age of C10 Capacity
C10 100 % 1.80 Volts
C5 83.3 % 1.80 Volts
C3 71.7 % 1.80 Volts
C1 50.0 % 1.75 Volts
What this means is that, in the case of a 12V 100 Ah battery, we can expect
performance in line with I.S. standards as below:-
Capacity No. Of To End Voltage Discharge
Rating Hours Per Cell Current
C10 10 hrs. 1.80 V 10 Amps --
& not 20
C5 5 hrs. 1.80 V 16.66 Amps.
Amps.
& not 33
C3 3 hrs. 1.80 V 23.90 Amps.
Amps.
& not 100
C1 1 hr. 1.75 V 50.00 Amps.
Amps.
Using the above logic, it is clear that a 12 V 100 Ah battery can be classified
as a 12V 120 Ah battery by the battery manufacturer since the same battery
lasts longer when discharged at lower currents.
12V 100Ah C10 rated battery delivers 10 A for 10 hours
(12V 100Ah @C10)
12V 100Ah C10 rated battery delivers 06 A for 20 hours
(12V 120Ah @C20)
The battery is the same. It has been rated differently. Thus, it is clear that
discharge rate w.r.t. time is not a linear relationship.
ELECTRIC VEHICLES &
BATTERIES
E lectric vehicles are the latest trend, with a reported 8.5 lakh plus
vehicles on Indian roads, as on December 2021.
The major vehicles are of course two wheelers and three wheelers, which are
being used to ferry passengers. Cargo carrying three wheelers and Passenger
E-cars together account for the balance 8% of the approx. total volume.
Concerns about air pollution and climate change are forcing the adoption of
electric vehicles as the cleaner and environment-friendly means of
transportation.
In India, the central government has introduced the Faster Adoption and
Manufacturing of Electrical Vehicle Scheme, popularly known by the
acronym FAME. The government has also reduced GST on electric vehicles,
as well as charging infrastructure, to promote the development of charging
stations.
The Government of India has also approved a Production Linked Incentive
scheme to encourage the setting up of manufacturing facilities for advanced
Chemistry Cells in India. Similar PLI schemes have been announced for
Automobiles and Auto Components for electric vehicles.
With the increase in the cost of petrol and diesel, many fleet management
companies are considering the option of converting to electric vehicles,
especially for the last mile delivery requirements.
The running cost of electric two wheelers is substantially lower, approx. one
fourth to one fifth of the cost. This is in comparison to the cost of running a
two wheeler on petrol.
The acceptance of electric vehicles as the future, from an economic
standpoint, as well as the requirement to save the environment, is now a
given. The general population and the various heads of state all over the
world are in consensus on this matter.
The adoption of this technology, however, imposes certain challenges in
terms of charging infrastructure, high prices of the vehicles, availability of
good batteries at economical prices, safety related issues pertaining to
batteries - which at times crop up in the case of lithium ion batteries,
recycling and disposal of scrap batteries, standardisation of charging sockets,
educating and training of the users, development of battery management
systems which are easy to use, and, of course, mileage.
Fortunately, all these challenges are being addressed effectively and in a fast
manner due to a time frame being imposed for an all-electric vehicle
scenario. The battery industry is also gearing up to meet the various
challenges head on in a successful manner.
As of now, Lithium Ion batteries are popular & mostly used in electric
vehicles. These batteries are very costly and constitute 40% to 50% of the
cost of electric vehicles. With the increase in demand for electric vehicles, the
requirement for batteries is set to skyrocket. In fact, another application,
which also uses Lithium Ion batteries, is the renewable energy segment.
Lithium Ion batteries are widely used in consumer electronics, but EV
batteries are bigger batteries and hence more complex.
As and when bigger batteries or systems of higher voltages and higher
currents are required, the quality of Lithium Ion batteries becomes more
critical. In fact, Battery Management Systems have an important role to play
when Lithium Ion batteries are used in Electric Vehicles.
The reason for this is that Lithium Ion batteries are prone to thermal runaway
problems, leading to an explosion of batteries and resulting in fire. These
may be due to either or a combination of reasons viz. electrical, thermal,
mechanical abuse or internal short circuit.
Storage of Lithium Ion batteries is again a challenge. The following care
needs to be taken:
1) Lithium Ion batteries need to be stored in a well-ventilated area.
2) Adequate provision needs to be made for firefighting in case of a fire.
3) Personnel must be trained for the careful handling of batteries.
4) Monitoring of stores, using CCTV cameras, is a must.
5) Sensitive sensors to detect smoke & fire, complete with alarms, have to be
installed.
6) Adequate fire insurance, with all safeguards in place, has to be ensured.
7) Employing trained personnel to handle fire & emergency situations is also
important.
It is advisable to store Lithium Ion batteries in a segregated area and away
from other inflammable materials.
As far as fire extinguishers are concerned, experience has shown that Halon
and CO2 are effective, though there is a limited understanding in this matter
as of now. In case of fire due to Lithium Ion batteries, sand has been
effectively used to cover the battery to allow a controlled burn out. Water,
when added, has been found to make the fire worse.
As regards Lithium Ion batteries, there are mainly four types
1) Lithium Iron Phosphate
2) Lithium Nickel Manganese Cobalt (LiNMC)
3) Lithium Nickel Cobalt Aluminum Oxide (NCA)
4) Lithium Cobalt Oxide (LCO)
The Lithium Iron Phosphate and Lithium Nickel Manganese Cobalt are
popular for use in Electric Vehicles. Lithium Cobalt Oxide (LCO) batteries
are used mainly in portable electric products like mobile phones, cameras,
laptops and toys. Lithium Nickel Cobalt Aluminum Oxide (NCA) are used in
medical devices like ventilators, dialysis systems, anaesthesia machines and
limited industrial applications.
Though Lithium Ion is popular and presently used for electric vehicles, there
is a lot of R & D going on simultaneously to explore better technologies.
This is, all the more so, especially due to the non-availability of Lithium in
sufficiently large quantities in India, a feeling of discomfort due to incidents
of some vehicles catching fire, lack of clarity as regards recyclability and
disposal.
There are a few startups segregating used lithium batteries and working on
these cells to give it a second life. The second life, of course, shall be with a
reduced capacity, for sale, accordingly.
Below is a chart comparing the lead acid battery to two variants of Lithium
Ion batteries from an academic point of view.
The question on the mind of many people, including the minds of
manufacturers of lead acid batteries, is whether it is the end of the road for
Lead Acid Batteries and whether Lithium Ion shall replace Lead Acid
Batteries in various applications. Well, I do not think it is possible to totally
displace Lead Acid Batteries for the following reasons: -
1) Safety
The major cause of concern for all battery users is safety. Lead Acid Batteries
have a proven track record and are very safe to use. Lithium Ion Batteries
are relatively unsafe, with cases of the explosion of batteries and incidents
of fire being more frequent, in the case of Lithium Ion Batteries. Fires due
to Lithium Ion Batteries, generate toxic gases. Moreover, putting off these
fires is difficult too.
2) Availability of Lithium & Cobalt
Lithium mines exist in Argentina, Bolivia and Chile, with some quantities in
U.S.A., Australia & China. Cobalt required for making Lithium Ion
Batteries is mainly found in Congo. Importing Lithium & Cobalt or
Lithium Ion Cells for assembly from abroad is akin to importing petroleum
products for petrol & diesel vehicles from oil rich nations. Lead on the
other hand, being recyclable, is easily available.
3) Recyclability & Disposal
Though the claims of a longer life compared to Lead Acid Batteries may
imply that Lithium Ion Batteries shall need to be replaced after a lot of use,
and thereby less frequently, it is still frightening to imagine the colossal
waste that shall be generated in the future, if an effective mechanism to
recycle & dispose of the scrap batteries is not devised, by then. Moreover,
such recyclers must be available with efficient and environmentally safe
technologies, all over the world, in various locations so that recycling is
feasible and practical.
4) Cost
The cost of Lithium metal is high and further increasing, thereby making it
prohibitively costly for certain applications. The difference in cost w.r.t
Lead Acid Batteries is such that, a lot of users shall prefer Lead Acid
Batteries if given a choice, despite the shorter life and cumbersome
maintenance requirements that Lead Acid Batteries entail. Some
applications, like large size material handling equipments and high
capacity die loaders, may accept Lead Acid Batteries.
5) Reparability
Due to the ease of repair of lead acid battery, familiarity of the product and
the rebate available on scrap battery – the acceptance of the technology of
Lead Acid Batteries continues, despite the purported advantages of
Lithium Ion Batteries, in terms of quick recharge, remote assistance and
longer life characteristics.
6) Retrofit Options
A lot of vehicles with internal combustion engines and a lot of electric
vehicles, as well as material handling equipments with lead acid batteries,
are not going to be scrapped, at least for 10 years from now, or, say 10
years from the date of sale. Hence lead acid batteries shall need to be made
for these customers, who shall not opt for any retrofit on their vehicles, to
replace Lead Acid Batteries with Lithium Ion Batteries since such a
retrofit, is likely to be very costly & cumbersome.
7) Power Demand Situation
The growth of the renewable energy sector has put a lot of focus on Solar
Energy and there is an ongoing effort to reduce the use of thermal and
nuclear power plants. This means that the requirement of storage of power
shall increase. Solar energy, which can be directly used through roof top
panels, is limited to day time use. If the energy harnessed from the Sun has
to be used at night, we need to store the power. For this, one needs
batteries. Lead Acid Batteries are proven, robust, safe and inexpensive
compared to Lithium Ion. As long as the design of the Lead Acid Batteries
meant for solar applications are done properly – maintenance is also not an
issue. It has been observed that Lead Acid Batteries are designed
adequately well, last for over 10 to 12 years in solar photovoltaic
applications.
There are many more similar reasons. Considering the few reasons stated
above, we can surmise that the Lead Acid Battery industry shall survive the
advance of Lithium Ion Battery or any other similar types of batteries, into its
domain. The growth of the renewable energy segment, which is inevitable
due to the need for the preservation of the environment, shall become a
dominant reason for the demand for batteries. Lead Acid Batteries shall
therefore survive but needs technology upgradation.
The areas of improvement in Lead Acid Batteries on which the future
generation can probably work are
1) Development of software adapted to the battery industry needs. This shall
reduce inventory, which is a major area of investment of borrowed funds,
with scope for reduction of battery cost. Reduction in interest cost on
working capital is necessary.
2) Another area with scope for reduction of battery cost is in electric power
consumption. We observe high power consumption in battery industries,
in the department of charging of batteries. Development of software that
shows the efficiency of charger, and recommends usage in terms of
optimisation, and gives alerts in case of inefficient usage, shall benefit the
battery industry.
3) Development of an App with real time data of buyers and sellers. This App
shall be useful, especially for new manufacturers of components as well
as entrepreneurs setting up a new battery manufacturing industry. This
shall also promote exports by giving wider exposure to manufacturers
based in India.
4) Improving the efficiency of batteries by developing additives, which give
exponential benefits in terms of life & capacity.
5) Cost reduction in manufacturing by simple & economic automation of
plant and machinery.
6) Development of a digital probe to measure the specific gravity of
electrolyte at an economic cost is another necessity.
7) Development of Battery Management System suitable for Lead Acid
Batteries, tailored for Electric Vehicle Applications & Stationary Battery
Installations.
8) Development of battery chargers with much higher efficiencies than the
presently available chargers.
9) Development of a method to refine & reuse the dilute sulphuric acid
coming out from various processes.
10) Development of an effective and low cost effluent and acid fume
treatment plant for small scale industries.
11) Development of an acid recirculating charging system suitable for small
scale industries.
GOOD… BETTER… BEST LEAD
ACID BATTERY
A good lead acid battery is one that sufficiently meets customer
expectations by being suitable for that specific application in all respects.
Hence an automotive battery is expected to be as light as possible but
powerful enough to crank the automotive engine for a defined number of
times, repeatedly at times, for an expected life period of 2 to 4 years.
A stationary monobloc battery with tubular positive plates designed for home
inverters is expected to be as compact as possible, with a life expectancy of 3
to 5 years.
A stationary 2 Volt cell with tubular positive plates, designed for use,
coupled to UPS systems in large industries, power stations or telecom
systems etc., is expected to work for long durations at times of power
outages. These batteries are expected to last for 10 to 12 years and actually
last for 15 to 18 years and even more at times.
A stationary 2 Volt cell with tubular positive plates, designed for use,
coupled to a solar photovoltaic system and installed in a remote location is
expected to work with minimal or no maintenance for a period of 10 to 15
years, depending on ambient conditions and depth of discharge. These
batteries are usually charged by solar photovoltaic cells and designed for
quick charge acceptance as well as use for up to 5 days of continuous
discharge without a recharge. Monobloc stationary tubular plate batteries
used in solar applications are expected to deliver a minimum of 5 years of
useful life.
A motorcycle battery, made using ultra-thin battery plates, is made such that
it delivers power to meet the demanding needs of today's hi-tech two
wheelers. The batteries used in two wheelers nowadays are expected to even
crank the engine since quite a few two wheelers are designed with push
button self-start technology. The power delivered by motorcycle batteries,
which literally fit in the palm of a hand, is to be experienced to be believed.
A motive power battery, known in industry parlance as a traction battery, is
used to power material handling vehicles, which are used in airports, large
industries, railway stations, docks etc. etc. These batteries being the prime
movers, are discharged on a daily basis and recharged for use on the
following day. These batteries at times act as a counterweight and are very
heavy. They are made rugged since they are cycled on a daily basis usually.
Batteries meant for scrubbers, sweepers, electric vehicles, boom lifts, cranes
and recreation vehicles are also deep cycling batteries and these are designed
to be rugged but light weight.
The different types of lead acid batteries used with specific requirements for
varying applications have to be designed
r with differing sp. gr. of operations
r with varying pitch of assembly
r with separators of differing thicknesses
r with abundant or limited electrolyte volume, depending on battery size
limitations
r with alloy of lead having calcium or antimony or selenium etc., depending
on expected performance characteristics
r with paste density variation
r with fine tuning of certain processes etc. etc. etc.
Thus, you see that lead acid batteries used for different applications have
minor changes in processes, or materials used, or in design characteristics.
Once a good battery has been designed and the product has been validated in
the field, after a proper review of the design, it is necessary to freeze the
design, material specifications and process to have a consistent product.
The consistency of the product, which has been accepted by the user as an
acceptable and good product, as well as the after sales technical and service
support, is what helps a manufacturer build his brand value for a bigger
market.
The customer ultimately decides, based on user experience, as to which is the
BEST battery in the market.