Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

DISTRIBUTION

SEL-751A Feeder Protection Relay

The SEL-751A is the right solution for industrial


and utility feeder protection, with arc-flash
detection, flexible I/O, advanced communications,
and easy mounting options.

SEL

Key Features Synchrophasor Measurements to Increase Asset Utilization


Validate system load flow and fault models via instantaneous voltage
Complete Feeder Protection
angles. Use system-state measurements to increase stable system loading
Maximize control scheme flexibility with time- and instantaneous- through reduced margin requirements.
overcurrent, reclosing control, synchronism check, overvoltage,
undervoltage, and frequency elements.

Arc-Flash Detection
Reduce arc-flash incident energy with fast detection and tripping. Combine
light-sensing technology with fast overcurrent protection to provide high * *
speed without false tripping. R*

Over-/
*
Convenient Controls Underfrequency
32
Use the four programmable pushbuttons on the front for quick, Directional

50 *
Power
personalized control. PAF
Arc-Flash
Easy Communications Overcurrent

Choose from single or dual, copper or fiber-optic Ethernet or serial com-


munications and several protocols, including MIRRORED BITS® and IEC 61850.
Pick multiple Modbus® TCP or Modbus serial sessions for custom configura- 50 * 25
*
NAF
tion of your application. Use DNP3 Serial or DNP3 LAN/WAN protocol. Arc-Flash Neutral
Overcurrent
*
Rugged Design * 79
AFD Arc-Flash Detector
Rely on the industry’s widest ambient operating temperature range,
—40° to +85°C (—40° to +185°F). * *
27 59
Easy Installation
Easily install into existing locations using available retrofit kits and
mounting adapters, with no cutting or drilling. BRM LGC DFR SER RTU SBM
Breaker Wear SELOGIC® Event Reports Sequential Remote Station Battery
Flexible Design Monitor Events Recorder Terminal Unit Monitor

Choose from many installation and integration options, with a small form 52PB MET 85
PMU HMI
RIO
factor and slide-in expansion cards. Trip/Close High-Accuracy SEL MIRRORED BITS® Synchrophasors Operator
Pushbuttons Metering Interface

Reclosing Control Load Data Adaptive


LDP Profiling 50/51 Overcurrent
Apply the programmable four-shot autoreclosing function with synchro- * Optional Functions

nism and voltage check logic to match a variety of reclosing practices. 4 2 1


Sequence coordination logic coordinates with downstream reclosers.
EIA-232 Ethernet IRIG-B
EIA-485 (Copper or Fiber-Optic)

100 Tel: +1.509.332.1890 | Fax: +1.509.332.7990 | www.selinc.com


DISTRIBUTION

SEL-751A Feeder Protection Relay


Applications Hardware Specifications
v Customize front-panel pushbutton operation and LEDs, or use default Phase Current Inputs
breaker trip/close functions.
Nominal Current INOM 1 A or 5 A
v Personalize LCD messages using event-driven display point settings.
Burden 0.01 VA @ 1 A; 0.10 VA @ 5 A
v Create an integrated control system with a variety of I/O and
communications options. +WV\QV]W][ v1NOM
v Use comprehensive reporting to understand events, schedule ;MKWVL<PMZUIT v1NOM
maintenance, detect unfavorable trends, modify loads, and satisfy Neutral/Ground Current Input
information requirements of supervisory systems.
Nominal Current INNOM 2.5 mA, 50 mA, 1 A or 5 A
v Include RTD inputs as part of system integration or to bias protection.
Burden 0.01 VA @ 1 A; 0.10 VA @ 5 A
v Mitigate arc-flash hazards in metal-clad switchgear.
+WV\QV]W][ v16NOM
v Analyze overcurrent protection system performance using built-in
Sequential Events Recorder (SER). ;MKWVL<PMZUIT v16NOM
v Control autoreclosing with synchronism and voltage check logic. Optional Phase Voltage Input
v Protect small generators, including distributed generation intercon- Rated Operating Voltage 100—250 Vac
nections.
Rated Continuous Voltage 300 Vac
v View synchronous phasors from any location to measure system state
10 Second Thermal 600 Vac
using standard synchrophasor SEL Fast Messages.
Burden 0.1 VA at 300 Vac
Optional Features Four-wire wye or open-delta voltage connections
v Communications. Power Supply Ratings
— DNP3, Modbus TCP, IEC 61850 110—250 Vdc, 110—240 Vac (—20% to +10%)
— Rear EIA-232 or EIA-485
24/48 Vdc 20—60 Vdc
— DeviceNet™ communications card
40 VA (ac) or 15 W (dc) total burden
— Ethernet, single or dual port, copper or fiber-optic
— Fiber-optic serial Hazardous Location Ratings

Zo
I
v Voltage input card. UL Class I, Zone 2 approved
!

ss

ne
Cla
v Voltage input card with four arc-flash detection inputs. ATEX

2
v Enhanced voltage input card with monitoring package. CSA Hazardous Location
APPROVED
v I/O expansion card. Optoisolated Control Input Ranges
— Four digital inputs (DI) and four digital outputs (DO) 24, 48, 110, 125, 220, or 250 Vdc or Vac
— Four digital inputs (DI), four digital outputs (DO) with fast, Control inputs are externally wetted
high-current interrupting capability
— Four digital outputs (DO), three digital inputs (DI), and one analog 2 inputs standard
output (AO) Contact Outputs
— Four analog inputs (AI) and four analog outputs (AO) Operating Voltage 240 Vac/250 Vdc
— Eight analog inputs (AI)
Rated Insulation Voltage 300 Vac/300 Vdc
— Eight digital inputs (DI)
3 outputs standard
— Three ac voltage inputs or five voltage inputs
— Ten RTD inputs Operating Temperature
v Conformal coating. —40° to +85°C (—40° to +185°F)
Related Products Arc-Flash Detection
SEL-2725 Five-Port Ethernet Switch ...................................................................... 334
Arc-Flash
SEL-3010 Event Messenger .......................................................................................346 Overcurrent
Fault
SEL-4388 MIRRORED BITS Tester .................................................................................. 426 Current

Easily mounted point sensors


Price detect light from the arc
flash in confined areas.
Budgetary Retail, Quantity 1: $950
Arc
(Base price is shown for planning purposes and is subject to change. Flash
Contact your SEL sales representative today for a quote on Arc-Flash Light Sensors
configurations and quantities to meet your needs.) (up to four)
Bare-fiber sensors detect light from the arc
flash over the entire length of the fiber loop.
This type of sensor is used for large areas,
such as busbars.

Combined light-sensing technology with fast overcurrent protection


provides high-speed, arc-flash detection without false tripping.

Tel: +1.509.332.1890 | Fax: +1.509.332.7990 | www.selinc.com 101


DISTRIBUTION

SEL-751A Feeder Protection Relay


Rear View Side View

i4160b
i3970c
Ethernet, fiber serial, IRIG-B, EIA-232 communications, 4 DO/3 DI/1 AO,
and voltage option.

Rear View Side View

i4162b
i4159a
Ethernet, fiber serial, EIA-485 communications, 8 DI, RTD, and 4 AI/4 AO option.

102 Tel: +1.509.332.1890 | Fax: +1.509.332.7990 | www.selinc.com


DISTRIBUTION

SEL-751A Feeder Protection Relay


Rear View Side View

i4246a
Dual-port, fiber-optic Ethernet, DeviceNet™, fast hybrid 4 DI/4 DO, and
enhanced-voltage options with monitoring package.

Dimensions

Visit www.selinc.com for more detailed information and configuration options.

Tel: +1.509.332.1890 | Fax: +1.509.332.7990 | www.selinc.com 103

You might also like