Technical Calculations Temperature Maintenance MTM105/20

Pipe Group Group1 BURSA KIRCAALİ MEYDAN YANGIN HATLARI HEAT TRACE SİSTEMİ

Please note Total Heater Qty relates to the installed quantity. An allowance of 0.5m/1.6ft is included in bill of material for termination of cable.
There is no additional allowance for MI cables as these are supplied terminated.
Line Pipe Reference Pipe Pipe Insul Maintain Heat Product Reference Cable Trace Spiral Spiral Installed In-Rush Heater Qty Total Heater Max In- Max Circuit Run Load
No Size Length Thick Loss Output Type Ratio Pitch Power Current for Equip Qty Rush Length
Temp Current @
10°C

(mm) (m) (mm) (°C) (W/m) (W/m) (m) (m) (W/m) (A/m) (m) (m) (A/ph) (m) (kW)

1 DN25 25 1 25 5 5,0 11FSM2-CT 11,0 SST 1,000 0,000 11,0 0,000 0,0 1,0 0,0 0,0 0,01
2 DN32 32 1 25 5 5,9 11FSM2-CT 11,0 SST 1,000 0,000 11,0 0,000 0,0 1,0 0,0 0,0 0,01
3 DN38 32 1 25 5 5,9 11FSM2-CT 11,0 SST 1,000 0,000 11,0 0,000 0,0 1,0 0,0 0,0 0,01
4 DN50 50 1 25 5 7,6 11FSM2-CT 11,0 SST 1,000 0,000 11,0 0,000 0,0 1,0 0,0 0,0 0,01
5 DN63 63 1 25 5 8,8 11FSM2-CT 11,0 SST 1,000 0,000 11,0 0,000 0,0 1,0 0,0 0,0 0,01
6 DN75 75 1 25 5 10,3 11FSM2-CT 11,0 SST 1,000 0,000 11,0 0,000 0,0 1,0 0,0 0,0 0,01
7 DN100 100 1 25 5 12,7 17FSM2-CT 17,0 SST 1,000 0,000 17,0 0,000 0,0 1,0 0,0 0,0 0,02
8 DN150 150 1 25 5 17,7 31FSR2-CT 33,1 SST 1,000 0,000 33,1 0,000 0,0 1,0 0,0 0,0 0,03
9 DN200 200 1 25 5 22,3 31FSR2-CT 33,1 SST 1,000 0,000 33,1 0,000 0,0 1,0 0,0 0,0 0,03
10 DN250 250 1 25 5 27,3 31FSR2-CT 33,1 SST 1,000 0,000 33,1 0,000 0,0 1,0 0,0 0,0 0,03
Group Total 0,0 0,18

Enquiry Total 0,0 0,18

Date Printed: 28 Mayıs 2020 Perşembe Page 2 of


5
Maximum Pipe Temperature Graphs MTM105/20
Pipe Group Group1 BURSA KIRCAALİ MEYDAN YANGIN HATLARI HEAT TRACE SİSTEMİ

Line No : 1 Pipe Reference : DN25 Line No : 2 Pipe Reference : DN32


Heat Loss / Cable Output (W/m) Heat Loss / Cable Output (W/m)
30 30

20
47°C 20
46°C
10 10

0 0
0 10 20 30 40 50 60 0 10 20 30 40 50 60
Pipe Temperature (°C) Pipe Temperature (°C)

Line No : 3 Pipe Reference : DN38 Line No : 4 Pipe Reference : DN50


Heat Loss / Cable Output (W/m) Heat Loss / Cable Output (W/m)
30 40

20
46°C 30 44°C
20

10
10

0 0
0 10 20 30 40 50 60 0 10 20 30 40 50
Pipe Temperature (°C) Pipe Temperature (°C)

Line No : 5 Pipe Reference : DN63 Line No : 6 Pipe Reference : DN75


Heat Loss / Cable Output (W/m) Heat Loss / Cable Output (W/m)
40 50

30 43°C 40
42°C
30
20
20
10
10

0 0
0 10 20 30 40 50 0 10 20 30 40 50
Pipe Temperature (°C) Pipe Temperature (°C)

Line No : 7 Pipe Reference : DN100 Line No : 8 Pipe Reference : DN150


Heat Loss / Cable Output (W/m) Heat Loss / Cable Output (W/m)
60 90
80
50

40
43°C 70
60
49°C
50
30
40
20 30
20
10
10
0 0
0 10 20 30 40 50 0 10 20 30 40 50 60
Pipe Temperature (°C) Pipe Temperature (°C)
Cable Output @ Min Cable Output @ Max
Heat Loss @ Min Ambient Heat Loss @ Max Ambient Max Pipe Temperature
Tolerance Tolerance

Date Printed: 28 Mayıs 2020 Perşembe


Page 3 of 5
Maximum Pipe Temperature Graphs (Continued) MTM105/20
Pipe Group Group1 BURSA KIRCAALİ MEYDAN YANGIN HATLARI HEAT TRACE SİSTEMİ

Line No : 9 Pipe Reference : DN200 Line No : 10 Pipe Reference : DN250


Heat Loss / Cable Output (W/m) Heat Loss / Cable Output (W/m)
120 120

100

80
46°C 100

80
44°C
60 60

40 40

20 20

0 0
0 10 20 30 40 50 60 0 10 20 30 40 50
Pipe Temperature (°C) Pipe Temperature (°C)

Cable Output @ Min Cable Output @ Max


Heat Loss @ Min Ambient Heat Loss @ Max Ambient Max Pipe Temperature
Tolerance Tolerance

Date Printed: 28 Mayıs 2020 Perşembe