2 @& TEST 2 BUILD
: = KNOW YOUR MATERIAL )
We NADL Acres Lorton,
Report No, +12B:2023/08571 gt
ULR No. C1043423000008313F i
TEST REPORT ON NON DESTRUCTIVE TESTING
REBOUND HAMMER
Customer Name & Address DEC Infasteeture and Projet (nda Pvt, Ld
Customer reference No. + Nil, Dated 13-05-2023
TRF No. & Date + TRB Fild23-24/TRFOD60, Dated 13-05-2008
Project” : MMA-21 CTRLS Data Center, Ambattur, Chennai
‘Test Conducted at (Site Location) : Ambattur
“Testing Commenced & Completedon———:-15-05.2023
‘est Method + 18516 (pa 5 /see 42020
Grade of Concrete” : M30
Age of Concete™ : More than 39 Days
Test Conducted + Rehound Hammer Test
we
si a Wentification | Rebound | Rebound | Compressive
No. seston structural member] _gttmmer | Hammer | srength Avg
(N/mm")
Tir For Deck Sa
RCSuB | Verieat 905 | 42 44,
' | pe- 1 Grid (F-H) (3-5) a ne. ai
> | 1th Foor Deck Sab [ coanirEa 4
pao | resin — | verieacvoy | 3s 3662
Requirements as per IS 516 (part Sisec 4), Clause 8.2
x by ultrasonic pulse velocity method is 3.50 kms for grades < M25, and 3.75 kms for above
* As furmished by the customer
Notes
1) above test eport results relates onl tsb saquplesmembers ested at site
2)This test epon shall not be reproduceyQQQHLLA APS without the writen approval ofthis laboratory
Rus
aul Motbory
(RK Bharadwa)
‘est witnessed bv: 1) Mr Roit Rams (DEC-QC).2) Mr. Subash T(CTRLS-QC)
steneneeneeveesaneee END OF REPORT *etteesennerensenee
Page No: 01 of 01