Download as pdf or txt
Download as pdf or txt
You are on page 1of 61

Magnetic Circuit Theory and

Transformers IV
EC2220 – El3ctrical Machines and Power Systems

Anuradha Kumarasinghe
Department of Electrical and Electronic Engineering

Department of Electrical & Electronic Engineering 1


Transformers – Part II

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 63
Transformers

• As discussed before, transformers are of 2 main types:


• Step-Up:
• The secondary winding has more turns than that of the primary winding.
• The voltage at the secondary shall be higher than the primary voltage.
• Step up transformers are used to increase transmission voltage to reduce transmission
losses.
• They can be found in generating stations.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 64
Transformers

• As discussed before, transformers are of 2 main types:


• Step-Down:
• The number of turns in the secondary side of the transformer is lesser than that of the
number of windings in the primary side.
• The voltage at the secondary is lower than that of the primary voltage.
• These transformers are used to reduce the voltage at the distribution side of the power
system

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 65
Theory of Operation of Single-Phase Real
Transformers
• All flux do not link with each other. At either coil, some flux is lost due to leakage.
• These are called Primary Leakage, 𝜙𝐿1 , and Secondary Leakage, 𝜙𝐿2 .
• The flux that does link is called Mutual Flux, 𝜙𝑀 .
• Therefore, at either winding, we can say the total average flux is equal to the mutual
flux plus the leakage.

𝜙1 = 𝜙𝑀 + 𝜙𝐿1

𝜙2 = 𝜙𝑀 + 𝜙𝐿2

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 66
Theory of Operation of Single-Phase Real
Transformers
• Along with the leakage losses, a practical transformer also has no-load losses.
• This draws a no-load current, 𝐼0 , from the primary side even with no load or current
on the secondary side.
• This current is made of 2 parts,
• Magnetization Current, 𝐼𝜇 , used to magnetize the core.
• Core-Loss Current, 𝐼𝑤 , due to hysteresis and eddy currents.
• The Magnetization Current, 𝐼𝜇 , is in phase and proportional to the flux. magnetization current
eka flux ekata
• Core-Loss Current, 𝐼𝑤 , is in phase with the voltage. samanupathika saha
ema dishavatama
pavathi

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 67
Theory of Operation of Single-Phase Real
Transformers
• The Magnetization Current, 𝐼𝜇 , is in phase and proportional to the flux.
• The Core-Loss Current, 𝐼𝑤 , is in phase with the voltage.
• Therefore, we can find the no-load current as:
• Here, 𝜃 is the phase angle difference.
• Also, Power factor, 𝑝𝑓 = cos 𝜃.

electrical circuit ekaka vagema mevageth P.F.


ekak laba gatha hakiya E(voltage ) vs flux
graph ekata anuva core loss crruent eka saha
magnetization crrunt eka adimen apata no-load
current eka kaba gatha hakiya E saha no-load
current eka athara konaya P.F eka lesa lab
gath hakiya

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 68
The Equivalent Circuit of a Transformer

• The flux leakage at either end gives raise to leakage reactance, 𝑋1 and 𝑋2 .
• This reactance, as well as the resistances in the coils, 𝑅1 and 𝑅2 , given raise to an
impedance at either winding.
• This impedance causes a voltage drop in the electrical circuit in each side.
• Let's take a look at the Primary side. resistances
leakage reactance in the coils
• 𝑉1 is the supply voltage.
• 𝐸1 is the voltage across the primary winding.
• There is a loss due to the impedance detailed.
𝐸1 = 𝑉1 − 𝐼1 𝑅1 + 𝑗𝐼1 𝑋1

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 69
The Equivalent Circuit of a Transformer

• The primary side current, 𝐼1 , has 2 parts.


• The current supplied to the secondary side, 𝐼2′ .
• The current used up due to losses, 𝐼0 . This is also called the no-load current.
• The permeability of the core is not infinite.
• This means that some current in used to magnetize the core, incurring more losses,
𝑋0 . This used current is called Magnetization Current, 𝐼𝜇 .
• Also, as discussed earlier, hysteresis and eddy currents also incur losses, 𝑅0 . The
current to make up for this is the Core-Loss Current, 𝐼𝑤 .

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 70
The Equivalent Circuit of a Transformer

• These losses can be calculated as:


𝐸1 𝐸1
𝑋0 = and 𝑅0 =
𝐼𝜇 𝐼𝑤

These losses are represented parallel to the windings.

Hysteresis and
eddy currents also
Magnetize the core, incur losses,
incurring more losses,

Magnetization Current,
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering Core-Loss Current,
71
The Equivalent Circuit of a Transformer

• Current 𝐼2′ passes through the primary winding with voltage 𝐸1 .


• This induces 𝐸2 voltage on the secondary side with current 𝐼2 .

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 72
The Equivalent Circuit of a Transformer

• Applying a similar technique to the secondary side, we can obtain an equivalent


circuit for the transformer.
• Since all losses are accounted for in the circuit, we can treat the actual transformer
part as ideal.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering smae parts
73
The Equivalent Circuit of a Transformer

• But let’s get rid of the transformation altogether.


• Moving to the secondary side, we need to know the transformation ratio, 𝐾.
𝐸1 N1 𝐼2
𝐾= = =
𝐸2 𝑁2 𝐼1
• Similar to the primary side,
the impedance on the winding,
𝑅2 and 𝑋2 , need to be account for.
• The circuit on the secondary
side is:

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 74
The Equivalent Circuit of a Transformer with
Referring Primary Side
𝐸1 N1 𝐼2
𝐾= = =
𝐸2 𝑁2 𝐼1
• Let's write primary side terms as 𝐸2′ and 𝐼2′ .

𝐸2′ N1 𝐼2
𝐾= = = ′
𝐸2 𝑁2 𝐼2
• Looking from the primary side, the voltage drop due to the secondary side can be
written as 𝐾𝐼2 𝑍2 .
• But we know, 𝐼2 = 𝐾𝐼2′ .
𝐾𝐼2 𝑍2 = 𝐾𝐾𝐼2′ 𝑍2 = 𝐾 2 𝐼2′ 𝑍2
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 75
The Equivalent Circuit of a Transformer with
Referring Primary Side
𝐾𝐼2 𝑍2 = 𝐾𝐾𝐼2′ 𝑍2 = 𝐾 2 𝐼2′ 𝑍2
• Let’s assume,
𝑍2′ = 𝐾 2 𝑍2
• Similarly,
𝑅2′ = 𝐾 2 𝑅2 , 𝑋2′ = 𝐾 2 𝑋2

• The secondary voltage and current is therefore written as:

𝐼2
𝑉2′ = 𝐾𝑉2 and 𝐼2′ =
𝐾

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 76
The Equivalent Circuit of a Transformer with
Referring Primary Side
• A similar transformation is now done for any load, 𝑍𝐿 on the secondary side.
𝑍𝐿′ = 𝐾 2 𝑍𝐿
• We can now draw the full equivalent circuit as referred from the primary side.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 77
The Equivalent Circuit of a Transformer with
Referring Secondary Side
• Using the same technique, it is also possible to draw the full equivalent circuit as
referred from the secondary side.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 78
Determining the Values of Components in the
Transformer Model
• To figure out the internal parameters of a transformer, it is possible to carry out 2
types of tests.
• Open-Circuit Test
• Short Circuit Test
• These tests would allow us to determine parameters including:
• Transformer Efficiency
• Voltage Regulation
• Circuit Constants
• Both tests are done without a load

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 79
Open-Circuit Test

• Open circuit testing can be used to:


• Determine the no-load current, 𝐼0 , of a transformer.
• The associated losses.
• Usually, the low voltage coil of the transformer is tested.
• The equipment used:
• Wattmeter
• Ammeter
• Voltmeter
• An AC supply of the nominal
voltage and frequency
of the transformer.
• An important fact is that the secondary side is left open.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 80
Open-Circuit Test - Process

• The supply AC is started at a low value and increased until the rated voltage of the
transformer is reached.
• Take care not the touch the high voltage side of the transformer as this will carry a
large voltage. It must remain open circuit.
• Obtain the following reading:
• Wattmeter reading, 𝑊0
• Ammeter reading, 𝐼0
• Voltmeter reading, 𝑉1
• The obtained values are as a result
of the core losses and the copper
losses on the primary side.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 81
Open-Circuit Test - Process

• However, at no-load, the copper losses are a negligible amount.


• Thus, 𝑊𝑜 can be taken as the core loss, 𝑃𝑖 .
𝑃𝑖 = 𝑉1 𝐼0 cos 𝜃
• With no load power factor, 𝑝𝑓 = cos 𝜃 .
• The Core-loss current, 𝐼𝑤 , is:
𝑃𝑖
𝐼𝑤 =
𝑉1
𝐼𝑤 = 𝐼0 cos 𝜃

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 82
Open-Circuit Test - Process

• The Magnetization Current, 𝐼𝜇 ,


𝐼𝜇 = 𝐼0 sin 𝜃

𝐼𝜇 = 𝐼02 − 𝐼𝑤
2

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 83
Open-Circuit Test - Process

• We now know the currents, 𝐼𝑤 and 𝐼𝜇 , and the voltage across, 𝑉1 .


• It is therefore possible to find the magnetization reactance, 𝑋0 , and the Core-Loss
resistance, 𝑅0 .

𝑉1
𝑋0 =
𝐼𝜇

𝑉1
𝑅0 =
𝐼𝑤

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 84
Short-Circuit Test

• In the earlier test, the copper losses were neglected as they are very low at no load.
• The short circuit test allows us to find the copper losses at full load.
• This will also tell us the efficiency of the transformer.
• The equivalent resistance, leakage
reactance and impedance can also
be found.
• Obtain the following reading:
• Wattmeter reading, 𝑊𝑠𝑐
• Ammeter reading, 𝐼𝑠𝑐
• Voltmeter reading, 𝑉𝑠𝑐
• The meters are connected as shown.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 85
Short-Circuit Test - Process

• For the short circuit test, the high voltage is the supply side.
• The low voltage side is shorted with a thick strip of material.
• The high voltage side is connected to a variable supply, set to 5% to 10% of the rated
voltage of the transformer.
• The voltage is then increased until the ammeter reads the rated coil current of the
high voltage coil.
• Since the output is shorted, the voltage in the core, and therefore the flux generated
is low.
• Therefore, the core losses are low and negligible.
• The power input seen is due to the copper losses.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 86
Short-Circuit Test - Process

• The copper losses, 𝑃𝑐 , in the transformer is therefore,


𝑃𝑐 = 𝑊𝑠𝑐
• Also, the equivalent resistance, referred from the high voltage side, 𝑅2 , is:
𝑊𝑠𝑐
𝑅𝑒𝑞 = 2
𝐼𝑠𝑐
• The equivalent impedance, referred from the high voltage side, 𝑍2 , is:
𝑉𝑠𝑐
𝑍𝑒𝑞 =
𝐼𝑠𝑐

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 87
Short-Circuit Test - Process

• The equivalent leakage reactance, referred from the high voltage side, 𝑋2 , is:
2 2
𝑋𝑒𝑞 = 𝑍𝑒𝑞 − 𝑅𝑒𝑞

• The short circuit power factor, 𝑝𝑓, can also be found.


𝑊𝑠𝑐
𝑝𝑓 = cos 𝜃 =
𝑉𝑠𝑐 𝐼𝑠𝑐
• Since we are taking all the measurements from the high voltage side, all the values,
𝑅𝑒𝑞 , 𝑋𝑒𝑞 and 𝑍𝑒𝑞 , are as referred to from this side.
• The equivalent circuit obtained from this test is as shown below.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 88
Short-Circuit Test - Process

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 89
Transformer Efficiency

• Non-Ideal transformers have 2 types of losses as discussed.


• This means that the power output is less than the power sent in.
• This lost power is turned into heat and is dissipated through various means.
• Therefore, it is important to know the efficiency, 𝜂, of a transformer.
Output KW
𝜂=
Input KW

Output KW
𝜂=
Output KW + Losses

Output KW
𝜂=
Output KW + (Copper Losses + Core Losses)

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 90
Transformer Efficiency

Output KW
𝜂=
Output KW + (Copper Losses + Core Losses)

• Copper losses depend on the square of the current and therefore change with
load. Core losses are constant regardless of load.
• Let’s take an example transformer of ratio 250: 500𝑉.
• A short circuit test is done with the high voltage side shorted. Results: 20𝑉, 12𝐴, 100𝑊
• An open circuit test is done on low voltage side. Results: 250𝑉, 1𝐴, 80𝑊
• Let’s find the efficiency of the transformers when the output is 10𝐴, 500𝑉, 𝑝𝑓 =
0.8 lagging.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 91
Transformer Efficiency

• From short circuit test we know,


𝑉𝑠𝑐 = 20
𝐼𝑠𝑐 = 12
𝑊𝑠𝑐 = 100
• This 𝑊𝑠𝑐 is a measure of power loss due to copper loss.
• During operation, 𝐼2 = 10.
• Therefore, copper loss at operation,
2 2
𝐼2 10
𝑃𝑐 = 𝑊𝑠𝑐 = × 100 = 69.44𝑊
𝐼𝑠𝑐 12

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 92
Transformer Efficiency

• From open circuit test we know, that the core losses, 𝑃𝑖 = 80𝑊.
• The power output during operation, 𝑃, can be found.
𝑃 = 𝑉2 𝐼2 cos 𝜃 = 500 × 10 × 0.8 = 4000𝑊

• Therefore, the efficiency of the transformer can be found.


Output KW
𝜂=
Output KW + (Copper Losses + Core Losses)

4000
𝜂= = 0.964
4000 + (69.44 + 80)

• Therefore, the transformer has an efficiency of 96.4%.


Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 93
Voltage Regulation of Transformer

• The voltage ratio between the primary and secondary coil are known.
• Thus, when there is an open circuit on the secondary side, there is no current
flow on this side, 𝐼𝐿 = 0.
• Therefore, the voltage on the secondary side is equal to what is obtained by the
voltage ratio.
• However, when a load is applied on the secondary side, there is now a current
flow.
• Thus, due to the internal resistance and leakage reactance of the winding, there is
going to be a voltage drop at the terminals of the secondary side.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 94
Voltage Regulation of Transformer

• Voltage regulation is the amount of change seen in this voltage when there is no
load to when there is a full load.
• Voltage regulation is the percentage of change seen in this voltage when there is
no load to when there is a full load.
• The voltage regulation can be expressed with 2 references, the no-load voltage,
𝑉𝑛𝑙 , or the full load voltage, 𝑉𝑓𝑙 .

𝑉𝑛𝑙 − 𝑉𝑓𝑙
Regulation = %
𝑉𝑛𝑙
𝑉𝑛𝑙 − 𝑉𝑓𝑙
Regulation = %
𝑉𝑓𝑙
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 95
Three-Phase Transformers

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 96
Three-Phase Transformers

• The worlds power grid relies completely on 3 phase transformers.


• The 3 phases can be sent through 3 individual single-phase transformers in a bank
or, more commonly, through a single 3 phase transformer.
• The single unit design is more common because:
• It is a smaller design with less weight and cost.
• It is easier transport.
• It is more efficient.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 97
Three-Phase Transformers

• One downside is that all 3 phases will go down if a single phase develops a
problem in the transformer.
• Because there are now 3 phase lines, their connection to the transformer can be
in either Wye or Delta form, or a combination.
• This is called Three-Phase Transformer Configuration.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 98
Three-Phase Transformers

• As expected, a 3-phase transformer will have 3 primary coils and 3 secondary


coils.
• However, the core would be shared. The core is either Shell type or Core type.

• The connection between the 3 windings would be according to the transformer


configuration.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 99
Three-Phase Transformers

• As discussed, each side of a 3-phare transformer can be either a


Wye or Delta connection.
• A few more obscure configurations exists but will not be
discussed here.
• Thus, in total, 4 different configurations exist.
• Wye-Wye (Y-Y)
• Delta-Delta (Δ-Δ)
• Wye-Delta (Y-Δ)
• Delta-Wye (Δ-Y)

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 100
Three-Phase Transformers

• In literature, the primary sides phases are labeled as 𝐴, 𝐵 and 𝐶,


while the secondary side is labeled as 𝑎, 𝑏, and 𝑐.
• The configuration can also be labeled as D, or Y for the primary
side and d or y on the secondary side.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 101
Wye Connection

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 102
Delta Connection

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 103
Wye-Wye Three-Phase Transformer (Y-Y)

• Wye-Wye connection is generally used for small, high-voltage transformers.


• Because of Wye connection, number of required turns per phase is reduced (as
phase voltage in star connection is 1/√3 times of line voltage only).
• Thus, the amount of insulation required is also reduced.
• The ratio of line voltages on the primary side and
the secondary side is equal to the transformation
ratio of the transformers.
• Line voltages on both sides are in phase with
each other.
• This connection can be used only if the
connected load is balanced.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 104
Delta-Delta Three-Phase Transformer (𝚫 - 𝚫)

• This connection is generally used for large, low-voltage transformers.


• Number of required phase per turns is relatively greater than that for a Wye-
Wye connection.
• The ratio of line voltages on the primary and the secondary side is equal to the
transformation ratio of the transformers.
• This connection can be used even for unbalanced
loading.
• Another advantage of this type of connection is
that even if one transformer is disabled, system
can continue to operate in open delta connection
but with reduced available capacity.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 105
Wye-Delta Three-Phase Transformer (Y- 𝚫)

• The primary winding is Wye connected with a grounded neutral and the
secondary winding is Delta connected.
• This connection is mainly used in step down transformer at the substation end
of the transmission line.
• The ratio of secondary to primary line
voltage is 1/√3 times the transformation ratio.
• There is 30° shift between the primary and
secondary line voltages.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 106
Delta-Wye Three-Phase Transformer (𝚫 -𝐘)

• The primary winding is connected in Delta and the secondary winding is


connected in Wye with neutral grounded.
• Thus, it can be used to provide 3-phase 4-wire service.
• This type of connection is mainly used in step-up transformer at the beginning of
transmission line.
• The ratio of secondary to primary line voltage
is √3 times the transformation ratio.
• There is 30° shift between the primary and
secondary line voltages.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 107
Three-Phase Transformer Configuration

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 108
Three-Phase Transformer Configuration

• As detailed, depending on the configuration, the voltage ratio would be affected


by some factor in addition to the turns-ratio.
• These are as summarized below, 𝑛 being the turns-ratio:
Primary - Secondary Line Voltage change Line Current change
Configuration Primary => Secondary Primary => Secondary
𝐼𝐿
Wye-Wye 𝑉𝐿 ⇒ 𝑛𝑉𝐿 𝐼𝐿 ⇒
𝑛
𝐼𝐿
Delta-Delta 𝑉𝐿 ⇒ 𝑛𝑉𝐿 𝐼𝐿 ⇒
𝑛
𝑛𝑉𝐿 𝐼𝐿
Wye-Delta 𝑉𝐿 ⇒ 𝐼𝐿 ⇒ 3
3 𝑛
𝐼𝐿
Delta-Wye 𝑉𝐿 ⇒ 3𝑛𝑉𝐿 𝐼𝐿 ⇒
3𝑛
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 109
Apparent Power Rating of a Transformer

• The current flow in the transformer windings depend on the voltage rating as
well as the power rating.
• This current flow incurs losses due to heating and overheating could damage
coils and insulations. Overall life of the transformer could be reduced.
• The power rating of a transformer is given in Apparent Power (VA). This is
provided in the “Name plate”
• This value can change, for the same set up, based on attached cooling apparatus.
• Commonly, windings are immersed in oil that is cooled by forced air or using a
heat exchange.
• These cooling methods would generally increase the rating by ~33%.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 110
Apparent Power Rating of a Transformer

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 111
Per Unit System

• The power is transferred through the transformer core as magnetic flux.


• Therefore, there are various losses and resistances to deal with.
• An Equivalent circuit for a transformer is as shown.
• To make calculations easier, it is possible to get an approximate circuit by
referring the impedances to one side.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 112
Per Unit System

• However, in power flow calculation and fault analysis, it is possible to represent a


transformer by a single leakage reactance.
• Transformer phase shift, resistance and magnetizing reactance are neglected.
• However, because the voltages on either side are different, it is necessary to
normalize the system.
• This is done with the use of the Per Unit system.

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 113
Per Unit System

• The presence of transformers in the system complicates models and


calculations.
• The system had varying voltage and current levels.
• A way to simplify things is the Per Units system (pu).
• System parameters are expressed as a fraction of a predefined base value.
• This applies to Voltage, Current, Power and Impedance.
• Essentially,
Actual Value
Per Unit Value =
Predefined Base Value
• pu is used throughout in power systems.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 114
Per Unit System

• For example, let’s say parameter 𝑋 = 240 units and the base for this parameter
is 220 units. What is the per unit equivalent of 𝑋?

Actual Value
Per Unit Value =
Predefined Base Value

240
Per Unit Value = = 1.1𝑝𝑢
220

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 115
Per Unit System

• Generally, the Voltage base (𝑉𝑏𝑎𝑠𝑒 ) and Apparent Power base (𝑆𝑏𝑎𝑠𝑒 ) are known
for a system.
• Also, to note,
𝑆𝑏𝑎𝑠𝑒 = 𝑃𝑏𝑎𝑠𝑒 = 𝑄𝑏𝑎𝑠𝑒
• Therefore,
𝑆𝑎𝑐𝑡𝑢𝑎𝑙 𝑃𝑎𝑐𝑡𝑢𝑎𝑙 + 𝑗𝑄𝑎𝑐𝑡𝑢𝑎𝑙 𝑃𝑎𝑐𝑡𝑢𝑎𝑙 𝑄𝑎𝑐𝑡𝑢𝑎𝑙
𝑆𝑝𝑢 = = = +𝑗
𝑆𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒
• The current base (𝐼𝑏𝑎𝑠𝑒 ) and impedance base (𝑍𝑏𝑎𝑠𝑒 ) can be found,
2
𝑆𝑏𝑎𝑠𝑒 𝑉𝑏𝑎𝑠𝑒 1
𝐼𝑏𝑎𝑠𝑒 = 𝑍𝑏𝑎𝑠𝑒 = 𝑌𝑏𝑎𝑠𝑒 =
𝑉𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒 𝑍𝑏𝑎𝑠𝑒

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 116
Per Unit System

• Therefore, base values or 𝑆𝑏𝑎𝑠𝑒 and 𝑉𝑏𝑎𝑠𝑒 are selected, Other base values, 𝐼𝑏𝑎𝑠𝑒,
𝑍𝑏𝑎𝑠𝑒, 𝑌𝑏𝑎𝑠𝑒 can be determined.
• When there is a transformer present, the power through is constant.
• Therefore, 𝑆𝑏𝑎𝑠𝑒 is constant throughout the system.
• However, 𝑉𝑏𝑎𝑠𝑒 changes between the primary and secondary sides of the
transformer.
0.2+j0.5Ω 10+j50Ω
• Take the example system below. +
220/2.2k
+

_ _

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 117
Per Unit System

• 𝑆𝑏𝑎𝑠𝑒 is to be taken as 10𝑘𝑉𝐴 and 𝑉𝑏𝑎𝑠𝑒 can be selected.


Quantity Primary Secondary
𝑆𝑏𝑎𝑠𝑒 10𝑘𝑉𝐴 10𝑘𝑉𝐴
𝑉𝑏𝑎𝑠𝑒 220𝑉 2.2𝑘𝑉

• 𝐼𝑏𝑎𝑠𝑒 and 𝑍𝑏𝑎𝑠𝑒 can then be calculated.


Quantity Primary Secondary
𝑆𝑏𝑎𝑠𝑒 10𝑘 𝑆𝑏𝑎𝑠𝑒 10𝑘
𝐼𝑏𝑎𝑠𝑒 = = 45.45A = = 4.55A
𝑉𝑏𝑎𝑠𝑒 220 𝑉𝑏𝑎𝑠𝑒 2.2𝑘
2 2
𝑉𝑏𝑎𝑠𝑒 2202 𝑉𝑏𝑎𝑠𝑒 2.2𝑘 2
𝑍 = of Electrical
= 4.84Ω = = 484Ω
Department of𝑏𝑎𝑠𝑒 𝑆Department
Electrical & Electronic Engineering
𝑏𝑎𝑠𝑒 10𝑘 and Electronic Engineering
𝑆𝑏𝑎𝑠𝑒 10𝑘 118
Per Unit System
Quantity Primary Secondary
𝑆𝑏𝑎𝑠𝑒 10𝑘𝑉𝐴 10𝑘𝑉𝐴
𝑉𝑏𝑎𝑠𝑒 220𝑉 2.2𝑘𝑉
• Thus, the pu values for each can be found. 𝐼𝑏𝑎𝑠𝑒 45.45A 4.55A
𝑍𝑏𝑎𝑠𝑒 4.84Ω 484Ω
• The primary and secondary side operating voltages,
𝑉𝑝,𝑎𝑐𝑡 𝑉𝑠,𝑎𝑐𝑡
𝑉𝑝,𝑝𝑢 = 𝑉𝑠,𝑝𝑢 =
220𝑉 2.2𝑘𝑉
• The primary and secondary side currents,
𝐼𝑝,𝑎𝑐𝑡 𝐼𝑠,𝑎𝑐𝑡
𝐼𝑝,𝑝𝑢 = 𝐼𝑠,𝑝𝑢 =
45.45A 4.55Ω

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 119
Per Unit System
Quantity Primary Secondary
𝑆𝑏𝑎𝑠𝑒 10𝑘𝑉𝐴 10𝑘𝑉𝐴
𝑉𝑏𝑎𝑠𝑒 220𝑉 2.2𝑘𝑉
𝐼𝑏𝑎𝑠𝑒 45.45A 4.55A
𝑍𝑏𝑎𝑠𝑒 4.84Ω 484Ω
• The impedances,
0.2+𝑗0.5 10+𝑗50
𝑍𝑝 = = 0.04 + 𝑗0.10 𝑍𝑠 = = 0.02 + 𝑗0.10
4.84 484

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 120
Per Unit System

• The impedance base for equipment is derived from its rated power and the
rated voltage.
• A system can consist of multiple machines with varying power and voltage
ratings.
• This makes in necessary to change between bases.
• We know that,
𝑜𝑙𝑑
𝑋𝑎𝑐𝑡
𝑋𝑝𝑢 = 𝑜𝑙𝑑
𝑋𝑏𝑎𝑠𝑒
• Thus,
𝑋𝑎𝑐𝑡 = 𝑋𝑝𝑢𝑜𝑙𝑑 × 𝑋 𝑜𝑙𝑑 = 𝑋 𝑛𝑒𝑤 × 𝑋 𝑛𝑒𝑤
𝑏𝑎𝑠𝑒 𝑝𝑢 𝑏𝑎𝑠𝑒

Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 121
Per Unit System
𝑜𝑙𝑑 × 𝑋 𝑜𝑙𝑑 = 𝑋 𝑛𝑒𝑤 × 𝑋 𝑛𝑒𝑤
𝑋𝑎𝑐𝑡 = 𝑋𝑝𝑢 𝑏𝑎𝑠𝑒 𝑝𝑢 𝑏𝑎𝑠𝑒

𝑜𝑙𝑑 𝑜𝑙𝑑
𝑛𝑒𝑤 𝑜𝑙𝑑 𝑆𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 𝑜𝑙𝑑 𝑉𝑏𝑎𝑠𝑒
𝑆𝑝𝑢 = 𝑆𝑝𝑢 × 𝑛𝑒𝑤 𝑉𝑝𝑢 = 𝑉𝑝𝑢 × 𝑛𝑒𝑤
𝑆𝑏𝑎𝑠𝑒 𝑉𝑏𝑎𝑠𝑒

• Also, since,
2
𝑉𝑏𝑎𝑠𝑒
𝑍𝑏𝑎𝑠𝑒 =
𝑆𝑏𝑎𝑠𝑒

𝑜𝑙𝑑 2 𝑛𝑒𝑤
𝑛𝑒𝑤 = 𝑍 𝑜𝑙𝑑 ×
𝑉𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒
𝑍𝑝𝑢 𝑝𝑢 𝑛𝑒𝑤 × 𝑜𝑙𝑑
𝑉𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 122

You might also like