Professional Documents
Culture Documents
Magnetic Circuit Theory and Transformers IV
Magnetic Circuit Theory and Transformers IV
Transformers IV
EC2220 – El3ctrical Machines and Power Systems
Anuradha Kumarasinghe
Department of Electrical and Electronic Engineering
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 63
Transformers
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 64
Transformers
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 65
Theory of Operation of Single-Phase Real
Transformers
• All flux do not link with each other. At either coil, some flux is lost due to leakage.
• These are called Primary Leakage, 𝜙𝐿1 , and Secondary Leakage, 𝜙𝐿2 .
• The flux that does link is called Mutual Flux, 𝜙𝑀 .
• Therefore, at either winding, we can say the total average flux is equal to the mutual
flux plus the leakage.
𝜙1 = 𝜙𝑀 + 𝜙𝐿1
𝜙2 = 𝜙𝑀 + 𝜙𝐿2
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 66
Theory of Operation of Single-Phase Real
Transformers
• Along with the leakage losses, a practical transformer also has no-load losses.
• This draws a no-load current, 𝐼0 , from the primary side even with no load or current
on the secondary side.
• This current is made of 2 parts,
• Magnetization Current, 𝐼𝜇 , used to magnetize the core.
• Core-Loss Current, 𝐼𝑤 , due to hysteresis and eddy currents.
• The Magnetization Current, 𝐼𝜇 , is in phase and proportional to the flux. magnetization current
eka flux ekata
• Core-Loss Current, 𝐼𝑤 , is in phase with the voltage. samanupathika saha
ema dishavatama
pavathi
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 67
Theory of Operation of Single-Phase Real
Transformers
• The Magnetization Current, 𝐼𝜇 , is in phase and proportional to the flux.
• The Core-Loss Current, 𝐼𝑤 , is in phase with the voltage.
• Therefore, we can find the no-load current as:
• Here, 𝜃 is the phase angle difference.
• Also, Power factor, 𝑝𝑓 = cos 𝜃.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 68
The Equivalent Circuit of a Transformer
• The flux leakage at either end gives raise to leakage reactance, 𝑋1 and 𝑋2 .
• This reactance, as well as the resistances in the coils, 𝑅1 and 𝑅2 , given raise to an
impedance at either winding.
• This impedance causes a voltage drop in the electrical circuit in each side.
• Let's take a look at the Primary side. resistances
leakage reactance in the coils
• 𝑉1 is the supply voltage.
• 𝐸1 is the voltage across the primary winding.
• There is a loss due to the impedance detailed.
𝐸1 = 𝑉1 − 𝐼1 𝑅1 + 𝑗𝐼1 𝑋1
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 69
The Equivalent Circuit of a Transformer
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 70
The Equivalent Circuit of a Transformer
Hysteresis and
eddy currents also
Magnetize the core, incur losses,
incurring more losses,
Magnetization Current,
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering Core-Loss Current,
71
The Equivalent Circuit of a Transformer
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 72
The Equivalent Circuit of a Transformer
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering smae parts
73
The Equivalent Circuit of a Transformer
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 74
The Equivalent Circuit of a Transformer with
Referring Primary Side
𝐸1 N1 𝐼2
𝐾= = =
𝐸2 𝑁2 𝐼1
• Let's write primary side terms as 𝐸2′ and 𝐼2′ .
𝐸2′ N1 𝐼2
𝐾= = = ′
𝐸2 𝑁2 𝐼2
• Looking from the primary side, the voltage drop due to the secondary side can be
written as 𝐾𝐼2 𝑍2 .
• But we know, 𝐼2 = 𝐾𝐼2′ .
𝐾𝐼2 𝑍2 = 𝐾𝐾𝐼2′ 𝑍2 = 𝐾 2 𝐼2′ 𝑍2
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 75
The Equivalent Circuit of a Transformer with
Referring Primary Side
𝐾𝐼2 𝑍2 = 𝐾𝐾𝐼2′ 𝑍2 = 𝐾 2 𝐼2′ 𝑍2
• Let’s assume,
𝑍2′ = 𝐾 2 𝑍2
• Similarly,
𝑅2′ = 𝐾 2 𝑅2 , 𝑋2′ = 𝐾 2 𝑋2
𝐼2
𝑉2′ = 𝐾𝑉2 and 𝐼2′ =
𝐾
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 76
The Equivalent Circuit of a Transformer with
Referring Primary Side
• A similar transformation is now done for any load, 𝑍𝐿 on the secondary side.
𝑍𝐿′ = 𝐾 2 𝑍𝐿
• We can now draw the full equivalent circuit as referred from the primary side.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 77
The Equivalent Circuit of a Transformer with
Referring Secondary Side
• Using the same technique, it is also possible to draw the full equivalent circuit as
referred from the secondary side.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 78
Determining the Values of Components in the
Transformer Model
• To figure out the internal parameters of a transformer, it is possible to carry out 2
types of tests.
• Open-Circuit Test
• Short Circuit Test
• These tests would allow us to determine parameters including:
• Transformer Efficiency
• Voltage Regulation
• Circuit Constants
• Both tests are done without a load
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 79
Open-Circuit Test
• The supply AC is started at a low value and increased until the rated voltage of the
transformer is reached.
• Take care not the touch the high voltage side of the transformer as this will carry a
large voltage. It must remain open circuit.
• Obtain the following reading:
• Wattmeter reading, 𝑊0
• Ammeter reading, 𝐼0
• Voltmeter reading, 𝑉1
• The obtained values are as a result
of the core losses and the copper
losses on the primary side.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 81
Open-Circuit Test - Process
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 82
Open-Circuit Test - Process
𝐼𝜇 = 𝐼02 − 𝐼𝑤
2
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 83
Open-Circuit Test - Process
𝑉1
𝑋0 =
𝐼𝜇
𝑉1
𝑅0 =
𝐼𝑤
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 84
Short-Circuit Test
• In the earlier test, the copper losses were neglected as they are very low at no load.
• The short circuit test allows us to find the copper losses at full load.
• This will also tell us the efficiency of the transformer.
• The equivalent resistance, leakage
reactance and impedance can also
be found.
• Obtain the following reading:
• Wattmeter reading, 𝑊𝑠𝑐
• Ammeter reading, 𝐼𝑠𝑐
• Voltmeter reading, 𝑉𝑠𝑐
• The meters are connected as shown.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 85
Short-Circuit Test - Process
• For the short circuit test, the high voltage is the supply side.
• The low voltage side is shorted with a thick strip of material.
• The high voltage side is connected to a variable supply, set to 5% to 10% of the rated
voltage of the transformer.
• The voltage is then increased until the ammeter reads the rated coil current of the
high voltage coil.
• Since the output is shorted, the voltage in the core, and therefore the flux generated
is low.
• Therefore, the core losses are low and negligible.
• The power input seen is due to the copper losses.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 86
Short-Circuit Test - Process
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 87
Short-Circuit Test - Process
• The equivalent leakage reactance, referred from the high voltage side, 𝑋2 , is:
2 2
𝑋𝑒𝑞 = 𝑍𝑒𝑞 − 𝑅𝑒𝑞
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 88
Short-Circuit Test - Process
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 89
Transformer Efficiency
Output KW
𝜂=
Output KW + Losses
Output KW
𝜂=
Output KW + (Copper Losses + Core Losses)
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 90
Transformer Efficiency
Output KW
𝜂=
Output KW + (Copper Losses + Core Losses)
• Copper losses depend on the square of the current and therefore change with
load. Core losses are constant regardless of load.
• Let’s take an example transformer of ratio 250: 500𝑉.
• A short circuit test is done with the high voltage side shorted. Results: 20𝑉, 12𝐴, 100𝑊
• An open circuit test is done on low voltage side. Results: 250𝑉, 1𝐴, 80𝑊
• Let’s find the efficiency of the transformers when the output is 10𝐴, 500𝑉, 𝑝𝑓 =
0.8 lagging.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 91
Transformer Efficiency
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 92
Transformer Efficiency
• From open circuit test we know, that the core losses, 𝑃𝑖 = 80𝑊.
• The power output during operation, 𝑃, can be found.
𝑃 = 𝑉2 𝐼2 cos 𝜃 = 500 × 10 × 0.8 = 4000𝑊
4000
𝜂= = 0.964
4000 + (69.44 + 80)
• The voltage ratio between the primary and secondary coil are known.
• Thus, when there is an open circuit on the secondary side, there is no current
flow on this side, 𝐼𝐿 = 0.
• Therefore, the voltage on the secondary side is equal to what is obtained by the
voltage ratio.
• However, when a load is applied on the secondary side, there is now a current
flow.
• Thus, due to the internal resistance and leakage reactance of the winding, there is
going to be a voltage drop at the terminals of the secondary side.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 94
Voltage Regulation of Transformer
• Voltage regulation is the amount of change seen in this voltage when there is no
load to when there is a full load.
• Voltage regulation is the percentage of change seen in this voltage when there is
no load to when there is a full load.
• The voltage regulation can be expressed with 2 references, the no-load voltage,
𝑉𝑛𝑙 , or the full load voltage, 𝑉𝑓𝑙 .
𝑉𝑛𝑙 − 𝑉𝑓𝑙
Regulation = %
𝑉𝑛𝑙
𝑉𝑛𝑙 − 𝑉𝑓𝑙
Regulation = %
𝑉𝑓𝑙
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 95
Three-Phase Transformers
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 96
Three-Phase Transformers
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 97
Three-Phase Transformers
• One downside is that all 3 phases will go down if a single phase develops a
problem in the transformer.
• Because there are now 3 phase lines, their connection to the transformer can be
in either Wye or Delta form, or a combination.
• This is called Three-Phase Transformer Configuration.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 98
Three-Phase Transformers
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 100
Three-Phase Transformers
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 101
Wye Connection
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 102
Delta Connection
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 103
Wye-Wye Three-Phase Transformer (Y-Y)
• The primary winding is Wye connected with a grounded neutral and the
secondary winding is Delta connected.
• This connection is mainly used in step down transformer at the substation end
of the transmission line.
• The ratio of secondary to primary line
voltage is 1/√3 times the transformation ratio.
• There is 30° shift between the primary and
secondary line voltages.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 106
Delta-Wye Three-Phase Transformer (𝚫 -𝐘)
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 107
Three-Phase Transformer Configuration
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 108
Three-Phase Transformer Configuration
• The current flow in the transformer windings depend on the voltage rating as
well as the power rating.
• This current flow incurs losses due to heating and overheating could damage
coils and insulations. Overall life of the transformer could be reduced.
• The power rating of a transformer is given in Apparent Power (VA). This is
provided in the “Name plate”
• This value can change, for the same set up, based on attached cooling apparatus.
• Commonly, windings are immersed in oil that is cooled by forced air or using a
heat exchange.
• These cooling methods would generally increase the rating by ~33%.
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 110
Apparent Power Rating of a Transformer
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 111
Per Unit System
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 112
Per Unit System
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 113
Per Unit System
• For example, let’s say parameter 𝑋 = 240 units and the base for this parameter
is 220 units. What is the per unit equivalent of 𝑋?
Actual Value
Per Unit Value =
Predefined Base Value
240
Per Unit Value = = 1.1𝑝𝑢
220
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 115
Per Unit System
• Generally, the Voltage base (𝑉𝑏𝑎𝑠𝑒 ) and Apparent Power base (𝑆𝑏𝑎𝑠𝑒 ) are known
for a system.
• Also, to note,
𝑆𝑏𝑎𝑠𝑒 = 𝑃𝑏𝑎𝑠𝑒 = 𝑄𝑏𝑎𝑠𝑒
• Therefore,
𝑆𝑎𝑐𝑡𝑢𝑎𝑙 𝑃𝑎𝑐𝑡𝑢𝑎𝑙 + 𝑗𝑄𝑎𝑐𝑡𝑢𝑎𝑙 𝑃𝑎𝑐𝑡𝑢𝑎𝑙 𝑄𝑎𝑐𝑡𝑢𝑎𝑙
𝑆𝑝𝑢 = = = +𝑗
𝑆𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒
• The current base (𝐼𝑏𝑎𝑠𝑒 ) and impedance base (𝑍𝑏𝑎𝑠𝑒 ) can be found,
2
𝑆𝑏𝑎𝑠𝑒 𝑉𝑏𝑎𝑠𝑒 1
𝐼𝑏𝑎𝑠𝑒 = 𝑍𝑏𝑎𝑠𝑒 = 𝑌𝑏𝑎𝑠𝑒 =
𝑉𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒 𝑍𝑏𝑎𝑠𝑒
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 116
Per Unit System
• Therefore, base values or 𝑆𝑏𝑎𝑠𝑒 and 𝑉𝑏𝑎𝑠𝑒 are selected, Other base values, 𝐼𝑏𝑎𝑠𝑒,
𝑍𝑏𝑎𝑠𝑒, 𝑌𝑏𝑎𝑠𝑒 can be determined.
• When there is a transformer present, the power through is constant.
• Therefore, 𝑆𝑏𝑎𝑠𝑒 is constant throughout the system.
• However, 𝑉𝑏𝑎𝑠𝑒 changes between the primary and secondary sides of the
transformer.
0.2+j0.5Ω 10+j50Ω
• Take the example system below. +
220/2.2k
+
_ _
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 117
Per Unit System
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 119
Per Unit System
Quantity Primary Secondary
𝑆𝑏𝑎𝑠𝑒 10𝑘𝑉𝐴 10𝑘𝑉𝐴
𝑉𝑏𝑎𝑠𝑒 220𝑉 2.2𝑘𝑉
𝐼𝑏𝑎𝑠𝑒 45.45A 4.55A
𝑍𝑏𝑎𝑠𝑒 4.84Ω 484Ω
• The impedances,
0.2+𝑗0.5 10+𝑗50
𝑍𝑝 = = 0.04 + 𝑗0.10 𝑍𝑠 = = 0.02 + 𝑗0.10
4.84 484
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 120
Per Unit System
• The impedance base for equipment is derived from its rated power and the
rated voltage.
• A system can consist of multiple machines with varying power and voltage
ratings.
• This makes in necessary to change between bases.
• We know that,
𝑜𝑙𝑑
𝑋𝑎𝑐𝑡
𝑋𝑝𝑢 = 𝑜𝑙𝑑
𝑋𝑏𝑎𝑠𝑒
• Thus,
𝑋𝑎𝑐𝑡 = 𝑋𝑝𝑢𝑜𝑙𝑑 × 𝑋 𝑜𝑙𝑑 = 𝑋 𝑛𝑒𝑤 × 𝑋 𝑛𝑒𝑤
𝑏𝑎𝑠𝑒 𝑝𝑢 𝑏𝑎𝑠𝑒
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 121
Per Unit System
𝑜𝑙𝑑 × 𝑋 𝑜𝑙𝑑 = 𝑋 𝑛𝑒𝑤 × 𝑋 𝑛𝑒𝑤
𝑋𝑎𝑐𝑡 = 𝑋𝑝𝑢 𝑏𝑎𝑠𝑒 𝑝𝑢 𝑏𝑎𝑠𝑒
𝑜𝑙𝑑 𝑜𝑙𝑑
𝑛𝑒𝑤 𝑜𝑙𝑑 𝑆𝑏𝑎𝑠𝑒 𝑛𝑒𝑤 𝑜𝑙𝑑 𝑉𝑏𝑎𝑠𝑒
𝑆𝑝𝑢 = 𝑆𝑝𝑢 × 𝑛𝑒𝑤 𝑉𝑝𝑢 = 𝑉𝑝𝑢 × 𝑛𝑒𝑤
𝑆𝑏𝑎𝑠𝑒 𝑉𝑏𝑎𝑠𝑒
• Also, since,
2
𝑉𝑏𝑎𝑠𝑒
𝑍𝑏𝑎𝑠𝑒 =
𝑆𝑏𝑎𝑠𝑒
𝑜𝑙𝑑 2 𝑛𝑒𝑤
𝑛𝑒𝑤 = 𝑍 𝑜𝑙𝑑 ×
𝑉𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒
𝑍𝑝𝑢 𝑝𝑢 𝑛𝑒𝑤 × 𝑜𝑙𝑑
𝑉𝑏𝑎𝑠𝑒 𝑆𝑏𝑎𝑠𝑒
Department
Department of Electrical & Electronic of Electrical and Electronic Engineering
Engineering 122