4hr Generator Test 030224

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

EC.02.05.

07 EP 10: The 36-month diesel-powered emergency generator


EP’s 10 test uses a dynamic or static load that is at least 30% of the
Frequency – Every 3 Years (Triennial) nameplate rating of the generator or meets the manufacturer’s
Testing of the emergency generator for (4) continuous hours recommended prime movers' exhaust gas temperature.
Volts Volts Volts Amps Amps Amps Hour Oil
Time KW Hz NFAP 110-2010,
RPM Chapter 8Oil Fuel Water Amb. Exaust
1 2 3 1 2 3 Meter Temp. Press. Press. Temp. Temp. Temp.
Warm Up 423 482 481 97 100 90 75 60.1 1800 614.8 176 73 25 70 70
Start 9:30 am 481 484 480 346 327 342 280 60.1 1800 614.9 180 69 50 75 102
9:45 480 484 481 350 320 335 277 60.1 1800 615.1 180 69 70 100 120
10:00 AM 481 485 481 344 324 333 287 60.1 1800 615.2 180 69 75 102 125
10:15 481 484 481 357 324 336 278 60.1 1800 615.4 180 69 75 102 127
10:30 482 483 481 349 347 315 267 60.1 1800 615.7 180 69 75 105 128
10:45 482 483 481 320 322 309 262 60.1 1800 615.8 180 67 75 106 130
11:00 AM 482 483 481 310 322 307 266 60.1 1800 615.9 180 67 75 103 127
11:15 482 483 481 349 349 334 305 60.1 1800 616.0 180 67 75 103 130
11:30 482 483 481 367 371 337 301 60.1 1800 616.0 180 67 75 104 130
11:45 482 483 481 291 290 277 245 60.1 1800 616.5 180 67 75 103 130
12:00 PM 482 483 481 390 401 386 304 60.1 1800 616.7 180 67 75 106 132
12:15 482 483 481 378 376 370 302 60.1 1800 616.8 180 67 75 107 121
12:30 482 483 481 315 290 303 249 60.1 1800 617.2 180 67 75 107 130
12:45 481 484 481 295 292 297 247 60.1 1800 617.4 180 67 75 108 135
1:00 PM 482 481 481 325 322 310 260 60.1 1800 618.1 180 67 75 110 132
1:15 482 483 481 319 314 300 253 60.1 1800 618.5 180 67 75 110 130
1:30 482 483 481 341 336 304 275 60.1 1800 618.7 180 67 75 110 132
CL Dwn 1:45 482 483 481 0 0 0 0 60.1 1800 618.8 176 70 75 100 120
Remarks:

Job Name: Engine Model: C27 S/N: AFR02595 Generator Model: CAT0027VDB S/N: SR$B
KW Rating: 800 KVA Rating: 1000 Phase: 60Hz RPM: 1800 Volts: 480
Date: Test Start Time: Test Finish Time: Test Location:
Tested By: PETER MINAQUI
3/2/24 9:30 AM 1:45 PM 333 East 38th Street NY, NY 10016

INSPECTORS NAME:________________________________ INSPECTORS SIGNATURE:________________________________ Date:____________________