Manual Calculation of Lighting

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 18

Luminaire Type Lamp Type Power Luminous Flux Code

Batten Luminaire LED 40 1200 Batten


Utilization Factor

Luminaire Code Housing Column1


Ba Batten Luminaire 40W
Column1

Column1

Batten Luminaire

Room index
0.50
0.60
0.80
1.00
1.25
1.50
2.00
2.50
3.00
4.00
5.00
Reflectance
Column2 Column3 Column4 Column5 Column6 Column7 Column8 Column9
Ceiling 0.80 0.80 0.70 0.70 0.70 0.70 0.50
Column2 Column3 Column4 Column5 Column6 Column7 Column8 Column9
Wall 0.50 0.50 0.50 0.50 0.50 0.30 0.30
Column2 Column3 Column4 Column5 Column6 Column7 Column8 Column9
Working Plane 0.30 0.10 0.30 0.20 0.10 0.10 0.10
A B C D E F G

Column2 Column3 Column4 Column5 Column6 Column7 Column8 Column9


0.4 0.38 0.38 0.37 0.36 0.29 0.27
0.4 0.38 0.38 0.37 0.36 0.29 0.27
0.5 0.47 0.47 0.46 0.44 0.37 0.34
0.58 0.53 0.54 0.53 0.51 0.43 0.4
0.65 0.6 0.62 0.59 0.57 0.5 0.46
0.72 0.65 0.67 0.65 0.62 0.55 0.5
0.81 0.72 0.76 0.72 0.69 0.63 0.57
0.87 0.77 0.82 0.78 0.74 0.68 0.62
0.92 0.81 0.86 0.81 0.77 0.72 0.66
0.98 0.85 0.92 0.86 0.81 0.77 0.71
1.02 0.88 0.96 0.9 0.84 0.8 0.74
e
Column10 Column11 Column12 Column13
0.50 0.30 0.30 0.00
Column10 Column11 Column12 Column13
0.10 0.30 0.10 0.00
Column10 Column11 Column12 Column13
0.10 0.10 0.10 0.00
H I K L

Column10 Column11 Column12 Column13


0.22 0.25 0.21 0.17
0.22 0.25 0.21 0.17
0.29 0.31 0.27 0.22
0.35 0.36 0.32 0.27
0.41 0.42 0.38 0.31
0.45 0.46 0.42 0.35
0.53 0.52 0.49 0.41
0.58 0.57 0.54 0.46
0.62 0.6 0.57 0.49
0.67 0.65 0.62 0.53
0.71 0.68 0.65 0.56
PROJECT:
LIGHTING CALCULATION SHEET

Date: 3/6/2024
Design Key: Notes: Reflectance Factor:

Luminaire Maintenance Factor – LMF 0.94 1. Lamp Lumen Maintenance Factor – LLMF Ceiling 0.70 Standard Ceiling
As with conventional source lamps LED output will depreciate
Room condition Luminaire Cleaning Time Wall 0.50 Standard Wall
over time.
Clean 1 Year Clean 2. Luminaire Maintenance Factor – LMF Working Plane 0.30 Standard Floor
Room Surface Maintenance Factor - RMF 0.95 It indicate annual luminaires cleaning time
Room condition Luminaire Cleaning Time 3. Room Surface Maintenance Factor - RMF Light loss facto 0.80
Clean 1 Year Room Clean It indicate annual luminaires cleaning time & Type of Luminaire
Direct
Luminaire Type 4. Lamp Survival Factor - LSF
Luminaires
Lamp Survival Factor - LSF 1 It indicate failure factor of LED Lamp - Usually equal 1
Lamp Lumen Maintenance Factor - LLMF 0.9

Maintaince Factor - MF 0.8037

Linear Interpolation
Q'ty
Lamp Working LTG Q'ty E(lux) E(lux)
E Room Lighting Fixture type Mantainance Luminous Manua
No. Room height height Hm(m) X (m) Y (m) S (m2) U Factor Q'ty Put in LGT lay-out Manua Put in Code SHR x1 x2 y1 y2 y
(Lux) Index (Phillips Light Reference) Factor Flux l
(m) (m) Cal. Room l Room
Decide
A FACTORY { GROUND FLOOR } ceiling X Y

1 TOILET (F) Y 200 2.5 0.00 2.5 3.6 9.8 35.1 1.05 Batten Luminaire 40W 0.556 0.8037 1,200 17 18 2 9 0 220 Batten 0.575 1 1.25 0.54 0.62 0.556

2 TOILET (M) Y 200 2.5 0.00 2.5 3.6 3.5 12.7 0.71 Batten Luminaire 40W 0.4295 0.8037 1,200 8 4 2 2 0 104 Batten 0.505 1 0.8 0.38 0.47 0.4295

3 ELECTRICAL ROOM Y 200 2.9 0.80 2.1 9.0 7.7 69.7 1.98 Batten Luminaire 40W 0.7564 0.8037 1,200 24 25 5 5 0 209 Batten 0.811 2 2 0.67 0.76 0.7564

4 BOILER ROOM Y 200 2.9 0.80 2.1 8.4 13.2 110.5 2.44 Batten Luminaire 40W 0.8128 0.8037 1,200 36 20 4 5 0 114 Batten 0.834 2 2.5 0.76 0.82 0.8128

5 COMPRESSOR ROOM Y 200 3.3 0.80 2.5 5.5 5.9 32.8 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 15 15 3 5 0 205 Batten 0.584 1 1.25 0.54 0.62 0.5816

6 PUMP ROOM _1 Y 200 2.9 0.80 2.1 6.8 7.8 52.6 1.72 Batten Luminaire 40W 0.7096 0.8037 1,200 20 20 4 5 0 208 Batten 0.772 2 2 0.67 0.76 0.7096

7 SLUDGE ROOM Y 200 2.9 0.80 2.1 4.5 4.0 18.0 1.01 Batten Luminaire 40W 0.5432 0.8037 1,200 9 12 3 4 0 279 Batten 0.673 1 1.25 0.54 0.62 0.5432

8 FILTER MACHINE ROOM Y 200 2.9 0.80 2.1 5.0 4.0 20.0 1.06 Batten Luminaire 40W 0.5592 0.8037 1,200 10 12 3 4 0 259 Batten 0.673 1 1.25 0.54 0.62 0.5592

9 RO SYSTEM ROOM Y 200 2.9 0.80 2.1 7.8 6.0 46.8 1.61 Batten Luminaire 40W 0.6898 0.8037 1,200 18 20 4 5 0 227 Batten 0.768 2 2 0.67 0.76 0.6898

10 FAN ROOM Y 200 2.9 0.80 2.1 7.3 3.5 25.6 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 12 12 3 4 0 211 Batten 0.695 1 1.25 0.54 0.62 0.5816

11 OPERATION ROOM Y 200 2.9 0.80 2.1 7.0 3.5 24.5 1.11 Batten Luminaire 40W 0.5752 0.8037 1,200 12 12 3 4 0 217 Batten 0.68 1 1.25 0.54 0.62 0.5752

12 PHARMACY Y 200 2.9 0.80 2.1 4.0 3.5 14.0 0.89 Batten Luminaire 40W 0.5015 0.8037 1,200 8 4 2 2 0 111 Batten 0.63 1 1 0.47 0.54 0.5015

13 2nd QC Y 700 2.9 0.80 2.1 5.7 26.9 152.9 2.23 Batten Luminaire 40W 0.7876 0.8037 1,200 177 50 5 10 0 199 Batten 0.443 2 2.5 0.76 0.82 0.7876

14 FINAL QC Y 700 2.5 0.80 1.7 11.8 10.3 121.0 3.23 Batten Luminaire 40W 0.8738 0.8037 1,200 126 25 5 5 0 139 Batten 0.576 3 4 0.86 0.92 0.8738

15 PACKING Y 550 2.5 0.80 1.7 11.8 4.8 57.2 2.02 Batten Luminaire 40W 0.7624 0.8037 1,200 54 15 5 3 0 154 Batten 0.605 2 2.5 0.76 0.82 0.7624

16 PRODUCTION WAREHOUSE Y 300 2.5 0.80 1.7 11.8 11.2 132.3 3.38 Batten Luminaire 40W 0.8828 0.8037 1,200 59 28 7 4 0 144 Batten 0.881 3 4 0.86 0.92 0.8828

17 FABRIC WAREHOUSE Y 300 2.9 0.80 2.1 20.0 30.0 600.0 5.71 Batten Luminaire 40W 0.96 0.8037 1,200 244 63 7 9 0 78 Batten 0.747 5 ### 0.96 ### Err:502

18 CAD ROOM Y 500 2.5 0.80 1.7 11.5 2.3 26.2 1.12 Batten Luminaire 40W 0.5784 0.8037 1,200 30 8 4 2 0 136 Batten 0.55 1 1.25 0.54 0.62 0.5784

19 CUTTING AREA Y 550 2.1 0.80 1.3 48.4 26.6 1288.7 13.21 Batten Luminaire 40W 0.96 0.8037 1,200 957 216 24 9 0 124 Batten 0.893 5 ### 0.96 ### Err:502

20 LINE IMPORT Y 550 2.9 0.80 2.1 10.0 22.5 225.0 3.30 Batten Luminaire 40W 0.878 0.8037 1,200 183 50 5 10 0 151 Batten 0.528 3 4 0.86 0.92 0.878

page 5 of 18
PROJECT:
LIGHTING CALCULATION SHEET

Date: 3/6/2024
Design Key: Notes: Reflectance Factor:

Luminaire Maintenance Factor – LMF 0.94 1. Lamp Lumen Maintenance Factor – LLMF Ceiling 0.70 Standard Ceiling
As with conventional source lamps LED output will depreciate
Room condition Luminaire Cleaning Time Wall 0.50 Standard Wall
over time.
Clean 1 Year Clean 2. Luminaire Maintenance Factor – LMF Working Plane 0.30 Standard Floor
Room Surface Maintenance Factor - RMF 0.95 It indicate annual luminaires cleaning time
Room condition Luminaire Cleaning Time 3. Room Surface Maintenance Factor - RMF Light loss facto 0.80
Clean 1 Year Room Clean It indicate annual luminaires cleaning time & Type of Luminaire
Direct
Luminaire Type 4. Lamp Survival Factor - LSF
Luminaires
Lamp Survival Factor - LSF 1 It indicate failure factor of LED Lamp - Usually equal 1
Lamp Lumen Maintenance Factor - LLMF 0.9

Maintaince Factor - MF 0.8037

Linear Interpolation
Q'ty
Lamp Working LTG Q'ty E(lux) E(lux)
E Room Lighting Fixture type Mantainance Luminous Manua
No. Room height height Hm(m) X (m) Y (m) S (m2) U Factor Q'ty Put in LGT lay-out Manua Put in Code SHR x1 x2 y1 y2 y
(Lux) Index (Phillips Light Reference) Factor Flux l
(m) (m) Cal. Room l Room
Decide
21 GENERATOR ROOM Y 200 2.9 0.80 2.1 8.3 10.3 85.6 2.19 Batten Luminaire 40W 0.7828 0.8037 1,200 29 11 4 8 0 78 Batten 0.818 2 2.5 0.76 0.82 0.7828

22 BAR TACK Y 600 2.1 0.80 1.3 5.6 26.9 149.8 3.55 Batten Luminaire 40W 0.893 0.8037 1,200 131 32 5 27 0 147 Batten 0.823 3 4 0.86 0.92 0.893

23 IRON Y 500 2.1 0.80 1.3 7.7 26.9 205.9 4.59 Batten Luminaire 40W 0.9436 0.8037 1,200 142 34 6 24 0 120 Batten 0.926 4 5 0.92 0.96 0.9436

24 PUMP ROOM _2 Y 200 2.9 0.80 2.1 4.7 5.2 24.5 1.18 Batten Luminaire 40W 0.5976 0.8037 1,200 11 9 3 3 0 169 Batten 0.711 1 1.25 0.54 0.62 0.5976

25 KNIFE BAND AREA Y 200 2.9 0.80 2.1 10.2 2.8 28.6 1.05 Batten Luminaire 40W 0.556 0.8037 1,200 14 5 5 1 0 75 Batten 0.681 1 1.25 0.54 0.62 0.556

26 BET @LINE IMPORT & MACHNE INTERLY 200 2.9 0.80 2.1 1.5 25.3 38.0 0.67 Batten Luminaire 40W 0.4115 0.8037 1,200 24 11 1 11 0 92 Batten 0.599 1 0.8 0.38 0.47 0.4115

27 CORRIDOR (GL_@4 & E _ K) Y 200 2.9 0.80 2.1 51.4 3.0 154.2 1.35 Batten Luminaire 40W 0.64 0.8037 1,200 63 17 17 1 0 54 Batten 0.745 1 1.5 0.62 0.67 0.64

28 CORRIDOR (GL_@4 & K _ Bet Q&R) Y 200 2.9 0.80 2.1 51.7 1.7 87.8 0.78 Batten Luminaire 40W 0.461 0.8037 1,200 50 19 19 1 0 77 Batten 0.631 1 0.8 0.38 0.47 0.461

29 CORRIDOR (GL_@4 & Bet Q&R _ S) Y 200 2.9 0.80 2.1 11.8 3.0 35.3 1.14 Batten Luminaire 40W 0.5848 0.8037 1,200 16 8 4 2 0 102 Batten 0.707 1 1.25 0.54 0.62 0.5848

30 CORRIDOR (GL_@S&T) Y 200 2.9 0.80 2.1 3.8 3.2 12.2 0.83 Batten Luminaire 40W 0.4805 0.8037 1,200 7 4 2 2 0 122 Batten 0.629 1 1 0.47 0.54 0.4805

31 CORRIDOR (GL_@S&T) Y 200 2.9 0.80 2.1 4.6 24.7 113.1 1.84 Batten Luminaire 40W 0.7312 0.8037 1,200 41 18 2 9 0 90 Batten 0.791 2 2 0.67 0.76 0.7312

32 CORRIDOR (GL_@1 & K _ S) Y 200 2.9 0.80 2.1 65.4 1.7 111.1 0.79 Batten Luminaire 40W 0.4655 0.8037 1,200 62 72 24 3 0 233 Batten 0.638 1 0.8 0.38 0.47 0.4655

CANTEEN { GROUND FLOOR }

33 LOCKER 1 Y 200 2.9 0.80 2.1 17.5 2.1 37.1 0.90 Batten Luminaire 40W 0.505 0.8037 1,200 20 5 5 1 0 52 Batten 0.649 1 1 0.47 0.54 0.505

34 CANTEEN Y 150 2.9 0.80 2.1 18.5 40.1 742.9 6.03 Batten Luminaire 40W 0.96 0.8037 1,200 151 55 5 11 0 55 Batten 1.056 5 ### 0.96 ### Err:502

35 CORRIDOR Y 200 3.5 0.80 2.7 3.0 10.3 30.8 0.86 Batten Luminaire 40W 0.491 0.8037 1,200 17 6 2 3 0 74 Batten 0.499 1 1 0.47 0.54 0.491

36 LOCKER 2 Y 200 2.9 0.80 2.1 15.4 4.7 73.1 1.73 Batten Luminaire 40W 0.7114 0.8037 1,200 27 27 9 3 0 203 Batten 0.784 2 2 0.67 0.76 0.7114

FACTORY { FIRST FLOOR }

1 TOILET (F) GL@A Y 200 2.5 0.00 2.5 3.4 9.5 32.2 1.00 Batten Luminaire 40W 0.54 0.8037 1,200 16 16 2 8 0 207 Batten 0.567 1 1.25 0.54 0.62 0.54

page 6 of 18
PROJECT:
LIGHTING CALCULATION SHEET

Date: 3/6/2024
Design Key: Notes: Reflectance Factor:

Luminaire Maintenance Factor – LMF 0.94 1. Lamp Lumen Maintenance Factor – LLMF Ceiling 0.70 Standard Ceiling
As with conventional source lamps LED output will depreciate
Room condition Luminaire Cleaning Time Wall 0.50 Standard Wall
over time.
Clean 1 Year Clean 2. Luminaire Maintenance Factor – LMF Working Plane 0.30 Standard Floor
Room Surface Maintenance Factor - RMF 0.95 It indicate annual luminaires cleaning time
Room condition Luminaire Cleaning Time 3. Room Surface Maintenance Factor - RMF Light loss facto 0.80
Clean 1 Year Room Clean It indicate annual luminaires cleaning time & Type of Luminaire
Direct
Luminaire Type 4. Lamp Survival Factor - LSF
Luminaires
Lamp Survival Factor - LSF 1 It indicate failure factor of LED Lamp - Usually equal 1
Lamp Lumen Maintenance Factor - LLMF 0.9

Maintaince Factor - MF 0.8037

Linear Interpolation
Q'ty
Lamp Working LTG Q'ty E(lux) E(lux)
E Room Lighting Fixture type Mantainance Luminous Manua
No. Room height height Hm(m) X (m) Y (m) S (m2) U Factor Q'ty Put in LGT lay-out Manua Put in Code SHR x1 x2 y1 y2 y
(Lux) Index (Phillips Light Reference) Factor Flux l
(m) (m) Cal. Room l Room
Decide
2 TOILET (M) GL@A Y 200 2.5 0.00 2.5 3.4 3.2 10.7 0.65 Batten Luminaire 40W 0.4025 0.8037 1,200 7 8 2 4 0 232 Batten 0.494 1 0.8 0.38 0.47 0.4025

3 PRODUCTION WAREHOUSE Y 300 3.5 0.80 2.7 16.4 24.0 393.6 3.58 Batten Luminaire 40W 0.8948 0.8037 1,200 172 80 10 8 0 140 Batten 0.556 3 4 0.86 0.92 0.8948

4 PACKING Y 550 2.5 0.80 1.7 7.8 23.5 182.9 3.44 Batten Luminaire 40W 0.8864 0.8037 1,200 148 78 6 13 0 292 Batten 0.654 3 4 0.86 0.92 0.8864

5 DRY ROOM & PRODUCTION STORAGE Y 300 2.5 0.80 1.7 23.1 23.5 544.8 6.86 Batten Luminaire 40W 0.96 0.8037 1,200 221 98 14 7 0 133 Batten 0.924 5 ### 0.96 ### Err:502

6 FINAL QC Y 700 3.5 0.80 2.7 4.3 24.0 103.6 1.36 Batten Luminaire 40W 0.642 0.8037 1,200 147 32 4 8 0 153 Batten 0.311 1 1.5 0.62 0.67 0.642

7 IRON Y 500 2.1 0.80 1.3 5.9 24.0 140.5 3.62 Batten Luminaire 40W 0.8972 0.8037 1,200 102 25 4 26 0 123 Batten 0.903 3 4 0.86 0.92 0.8972

8 2nd QC Y 700 3.5 0.80 2.7 4.8 24.0 116.1 1.49 Batten Luminaire 40W 0.668 0.8037 1,200 158 56 4 14 0 249 Batten 0.317 1 1.5 0.62 0.67 0.668

9 BAR TACK Y 600 2.1 0.80 1.3 5.3 24.0 127.7 3.35 Batten Luminaire 40W 0.881 0.8037 1,200 113 28 5 23 0 149 Batten 0.818 3 4 0.86 0.92 0.881

10 SEWING Y 600 2.1 0.80 1.3 50.9 24.0 1221.3 12.54 Batten Luminaire 40W 0.96 0.8037 1,200 990 233 20 12 0 141 Batten 0.854 5 ### 0.96 ### Err:502

11 STORE 1 Y 200 3.5 0.80 2.7 9.5 10.2 97.3 1.83 Batten Luminaire 40W 0.7294 0.8037 1,200 35 12 4 3 0 69 Batten 0.617 2 2 0.67 0.76 0.7294

12 STORE 2 Y 200 3.5 0.80 2.7 9.5 10.2 97.3 1.83 Batten Luminaire 40W 0.7294 0.8037 1,200 35 12 4 3 0 69 Batten 0.617 2 2 0.67 0.76 0.7294

13 TOILET (F) GL@T Y 200 2.5 0.00 2.5 3.6 9.8 34.9 1.05 Batten Luminaire 40W 0.556 0.8037 1,200 17 18 2 9 0 221 Batten 0.573 1 1.25 0.54 0.62 0.556

14 TOILET (M) GL@T Y 200 2.5 0.00 2.5 3.6 3.5 12.3 0.70 Batten Luminaire 40W 0.425 0.8037 1,200 8 4 2 2 0 106 Batten 0.497 1 0.8 0.38 0.47 0.425

15 CORRIDOR (GL_@1 & B_T) Y 200 3.4 0.80 2.6 144.3 3.0 433.0 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 193 57 57 1 0 59 Batten 0.576 1 1.25 0.54 0.62 0.5816

16 CORRIDOR (GL_@4 & B_S) Y 200 3.4 0.80 2.6 141.8 3.0 425.4 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 190 55 55 1 0 58 Batten 0.575 1 1.25 0.54 0.62 0.5816

17 CORRIDOR (GL_@1_2 & A_B) Y 200 3.4 0.80 2.6 7.9 10.5 83.3 1.74 Batten Luminaire 40W 0.7132 0.8037 1,200 31 16 4 4 0 106 Batten 0.63 2 2 0.67 0.76 0.7132

18 CORRIDOR (GL_@2_4 & A_B) Y 200 3.4 0.80 2.6 4.3 16.5 70.9 1.31 Batten Luminaire 40W 0.632 0.8037 1,200 30 12 2 6 0 83 Batten 0.591 1 1.5 0.62 0.67 0.632

19 CORRIDOR (GL_@1_4 & Q_R) Y 200 3.4 0.80 2.6 7.1 20.4 144.8 2.02 Batten Luminaire 40W 0.7624 0.8037 1,200 50 52 4 13 0 211 Batten 0.654 2 2.5 0.76 0.82 0.7624

20 CORRIDOR (GL_@4 & Q_S) Y 200 3.4 0.80 2.6 16.6 3.6 59.3 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 27 5 5 1 0 38 Batten 0.57 1 1.25 0.54 0.62 0.5816

21 CORRIDOR (GL_@1_4 & S_T) Y 200 3.4 0.80 2.6 3.0 23.4 70.3 1.02 Batten Luminaire 40W 0.5464 0.8037 1,200 34 16 2 8 0 96 Batten 0.553 1 1.25 0.54 0.62 0.5464

22 CORRIDOR (GL_@1_2 & S_T) Y 200 3.4 0.80 2.6 3.8 5.7 21.7 0.88 Batten Luminaire 40W 0.498 0.8037 1,200 12 4 2 2 0 71 Batten 0.517 1 1 0.47 0.54 0.498

page 7 of 18
PROJECT:
LIGHTING CALCULATION SHEET

Date: 3/6/2024
Design Key: Notes: Reflectance Factor:

Luminaire Maintenance Factor – LMF 0.94 1. Lamp Lumen Maintenance Factor – LLMF Ceiling 0.70 Standard Ceiling
As with conventional source lamps LED output will depreciate
Room condition Luminaire Cleaning Time Wall 0.50 Standard Wall
over time.
Clean 1 Year Clean 2. Luminaire Maintenance Factor – LMF Working Plane 0.30 Standard Floor
Room Surface Maintenance Factor - RMF 0.95 It indicate annual luminaires cleaning time
Room condition Luminaire Cleaning Time 3. Room Surface Maintenance Factor - RMF Light loss facto 0.80
Clean 1 Year Room Clean It indicate annual luminaires cleaning time & Type of Luminaire
Direct
Luminaire Type 4. Lamp Survival Factor - LSF
Luminaires
Lamp Survival Factor - LSF 1 It indicate failure factor of LED Lamp - Usually equal 1
Lamp Lumen Maintenance Factor - LLMF 0.9

Maintaince Factor - MF 0.8037

Linear Interpolation
Q'ty
Lamp Working LTG Q'ty E(lux) E(lux)
E Room Lighting Fixture type Mantainance Luminous Manua
No. Room height height Hm(m) X (m) Y (m) S (m2) U Factor Q'ty Put in LGT lay-out Manua Put in Code SHR x1 x2 y1 y2 y
(Lux) Index (Phillips Light Reference) Factor Flux l
(m) (m) Cal. Room l Room
Decide

CANTEEN { FIRST FLOOR }

23 LOCKER 1 Y 200 3.5 0.80 2.7 17.5 2.1 37.1 0.70 Batten Luminaire 40W 0.425 0.8037 1,200 23 5 5 1 0 44 Batten 0.47 1 0.8 0.38 0.47 0.425

24 CANTEEN Y 150 3.5 0.80 2.7 18.5 40.1 742.9 4.69 Batten Luminaire 40W 0.96 0.8037 1,200 151 55 5 11 0 55 Batten 0.821 4 5 0.92 0.96 0.9476

25 CORRIDOR Y 200 3.5 0.80 2.7 3.0 10.3 30.8 0.86 Batten Luminaire 40W 0.491 0.8037 1,200 17 6 2 3 0 74 Batten 0.499 1 1 0.47 0.54 0.491

26 LOCKER 2 Y 200 3.5 0.80 2.7 15.4 4.7 73.1 1.34 Batten Luminaire 40W 0.638 0.8037 1,200 30 36 9 4 0 242 Batten 0.578 1 1.5 0.62 0.67 0.638

FACTORY { SECOND FLOOR }

1 TOILET (F) GL@A Y 200 2.5 0.00 2.5 3.4 11.3 38.3 1.04 Batten Luminaire 40W 0.5528 0.8037 1,200 18 10 2 5 0 111 Batten 0.583 1 1.25 0.54 0.62 0.5528

page 8 of 18
PROJECT:
LIGHTING CALCULATION SHEET

Date: 3/6/2024
Design Key: Notes: Reflectance Factor:

Luminaire Maintenance Factor – LMF 0.94 1. Lamp Lumen Maintenance Factor – LLMF Ceiling 0.70 Standard Ceiling
As with conventional source lamps LED output will depreciate
Room condition Luminaire Cleaning Time Wall 0.50 Standard Wall
over time.
Clean 1 Year Clean 2. Luminaire Maintenance Factor – LMF Working Plane 0.30 Standard Floor
Room Surface Maintenance Factor - RMF 0.95 It indicate annual luminaires cleaning time
Room condition Luminaire Cleaning Time 3. Room Surface Maintenance Factor - RMF Light loss facto 0.80
Clean 1 Year Room Clean It indicate annual luminaires cleaning time & Type of Luminaire
Direct
Luminaire Type 4. Lamp Survival Factor - LSF
Luminaires
Lamp Survival Factor - LSF 1 It indicate failure factor of LED Lamp - Usually equal 1
Lamp Lumen Maintenance Factor - LLMF 0.9

Maintaince Factor - MF 0.8037

Linear Interpolation
Q'ty
Lamp Working LTG Q'ty E(lux) E(lux)
E Room Lighting Fixture type Mantainance Luminous Manua
No. Room height height Hm(m) X (m) Y (m) S (m2) U Factor Q'ty Put in LGT lay-out Manua Put in Code SHR x1 x2 y1 y2 y
(Lux) Index (Phillips Light Reference) Factor Flux l
(m) (m) Cal. Room l Room
Decide
2 TOILET (M) GL@A Y 200 2.5 0.00 2.5 3.4 3.2 10.7 0.65 Batten Luminaire 40W 0.4025 0.8037 1,200 7 8 2 4 0 232 Batten 0.494 1 0.8 0.38 0.47 0.4025

3 PRODUCTION WAREHOUSE Y 300 3.5 0.80 2.7 16.4 24.0 393.6 3.58 Batten Luminaire 40W 0.8948 0.8037 1,200 172 80 10 8 0 140 Batten 0.556 3 4 0.86 0.92 0.8948

4 PACKING Y 550 2.5 0.80 1.7 7.8 23.5 182.9 3.44 Batten Luminaire 40W 0.8864 0.8037 1,200 148 78 6 13 0 292 Batten 0.654 3 4 0.86 0.92 0.8864

5 DRY ROOM & PRODUCTION STORAGE Y 300 2.5 0.80 1.7 23.1 23.5 544.8 6.86 Batten Luminaire 40W 0.96 0.8037 1,200 221 98 14 7 0 133 Batten 0.924 5 ### 0.96 ### Err:502

6 FINAL QC Y 700 3.5 0.80 2.7 4.3 24.0 103.6 1.36 Batten Luminaire 40W 0.642 0.8037 1,200 147 32 4 8 0 153 Batten 0.311 1 1.5 0.62 0.67 0.642

7 IRON Y 500 2.1 0.80 1.3 5.9 24.0 140.5 3.62 Batten Luminaire 40W 0.8972 0.8037 1,200 102 25 4 26 0 123 Batten 0.903 3 4 0.86 0.92 0.8972

8 2nd QC Y 700 3.5 0.80 2.7 4.8 24.0 116.1 1.49 Batten Luminaire 40W 0.668 0.8037 1,200 158 56 4 14 0 249 Batten 0.317 1 1.5 0.62 0.67 0.668

9 BAR TACK Y 600 2.1 0.80 1.3 5.3 24.0 127.7 3.35 Batten Luminaire 40W 0.881 0.8037 1,200 113 28 5 23 0 149 Batten 0.818 3 4 0.86 0.92 0.881

10 SEWING Y 600 2.1 0.80 1.3 50.9 24.0 1221.3 12.54 Batten Luminaire 40W 0.96 0.8037 1,200 990 217 18 55 0 132 Batten 0.854 5 ### 0.96 ### Err:502

11 SAMPLE Y 200 3.5 0.80 2.7 9.5 10.2 97.3 1.83 Batten Luminaire 40W 0.7294 0.8037 1,200 35 12 4 3 0 69 Batten 0.617 2 2 0.67 0.76 0.7294

12 MAINTENANCE Y 200 3.5 0.80 2.7 9.5 10.2 97.3 1.83 Batten Luminaire 40W 0.7294 0.8037 1,200 35 12 4 3 0 69 Batten 0.617 2 2 0.67 0.76 0.7294

13 TOILET (F) GL@T Y 200 2.5 0.00 2.5 3.6 11.6 41.4 1.09 Batten Luminaire 40W 0.5688 0.8037 1,200 19 10 2 5 0 106 Batten 0.59 1 1.25 0.54 0.62 0.5688

14 TOILET (M) GL@T Y 200 2.5 0.00 2.5 3.6 3.4 12.3 0.70 Batten Luminaire 40W 0.425 0.8037 1,200 8 4 2 2 0 107 Batten 0.495 1 0.8 0.38 0.47 0.425

15 CORRIDOR (GL_@1 & B_T) Y 200 3.4 0.80 2.6 144.3 3.0 433.0 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 193 57 57 1 0 59 Batten 0.576 1 1.25 0.54 0.62 0.5816

16 CORRIDOR (GL_@4 & B_S) Y 200 3.4 0.80 2.6 141.8 3.0 426.8 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 191 55 55 1 0 58 Batten 0.575 1 1.25 0.54 0.62 0.5816

17 CORRIDOR (GL_@1_2 & A_B) Y 200 3.4 0.80 2.6 7.9 8.7 68.9 1.60 Batten Luminaire 40W 0.688 0.8037 1,200 26 12 4 3 0 92 Batten 0.626 2 2 0.67 0.76 0.688

18 CORRIDOR (GL_@2_4 & A_B) Y 200 3.4 0.80 2.6 4.3 18.3 78.7 1.34 Batten Luminaire 40W 0.638 0.8037 1,200 32 14 2 7 0 88 Batten 0.603 1 1.5 0.62 0.67 0.638

19 CORRIDOR (GL_@1_4 & Q_R) Y 200 3.4 0.80 2.6 7.1 20.4 144.8 2.02 Batten Luminaire 40W 0.7624 0.8037 1,200 50 52 4 13 0 211 Batten 0.654 2 2.5 0.76 0.82 0.7624

20 CORRIDOR (GL_@4 & Q_S) Y 200 3.4 0.80 2.6 16.6 3.6 59.3 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 27 5 5 1 0 38 Batten 0.57 1 1.25 0.54 0.62 0.5816

21 CORRIDOR (GL_@1_4 & S_T) Y 200 3.4 0.80 2.6 3.0 23.4 70.3 1.02 Batten Luminaire 40W 0.5464 0.8037 1,200 34 16 2 8 0 96 Batten 0.553 1 1.25 0.54 0.62 0.5464

22 CORRIDOR (GL_@1_2 & S_T) Y 200 3.4 0.80 2.6 3.8 3.9 15.0 0.74 Batten Luminaire 40W 0.443 0.8037 1,200 9 2 2 1 0 46 Batten 0.496 1 0.8 0.38 0.47 0.443

page 9 of 18
PROJECT:
LIGHTING CALCULATION SHEET

Date: 3/6/2024
Design Key: Notes: Reflectance Factor:

Luminaire Maintenance Factor – LMF 0.94 1. Lamp Lumen Maintenance Factor – LLMF Ceiling 0.70 Standard Ceiling
As with conventional source lamps LED output will depreciate
Room condition Luminaire Cleaning Time Wall 0.50 Standard Wall
over time.
Clean 1 Year Clean 2. Luminaire Maintenance Factor – LMF Working Plane 0.30 Standard Floor
Room Surface Maintenance Factor - RMF 0.95 It indicate annual luminaires cleaning time
Room condition Luminaire Cleaning Time 3. Room Surface Maintenance Factor - RMF Light loss facto 0.80
Clean 1 Year Room Clean It indicate annual luminaires cleaning time & Type of Luminaire
Direct
Luminaire Type 4. Lamp Survival Factor - LSF
Luminaires
Lamp Survival Factor - LSF 1 It indicate failure factor of LED Lamp - Usually equal 1
Lamp Lumen Maintenance Factor - LLMF 0.9

Maintaince Factor - MF 0.8037

Linear Interpolation
Q'ty
Lamp Working LTG Q'ty E(lux) E(lux)
E Room Lighting Fixture type Mantainance Luminous Manua
No. Room height height Hm(m) X (m) Y (m) S (m2) U Factor Q'ty Put in LGT lay-out Manua Put in Code SHR x1 x2 y1 y2 y
(Lux) Index (Phillips Light Reference) Factor Flux l
(m) (m) Cal. Room l Room
Decide

CANTEEN { SEDOND FLOOR }

23 LOCKER 1 Y 200 3.5 0.80 2.7 17.5 2.1 37.1 0.70 Batten Luminaire 40W 0.425 0.8037 1,200 23 5 5 1 0 44 Batten 0.47 1 0.8 0.38 0.47 0.425

24 CANTEEN Y 150 3.5 0.80 2.7 18.5 40.1 742.9 4.69 Batten Luminaire 40W 0.96 0.8037 1,200 151 55 5 11 0 55 Batten 0.821 4 5 0.92 0.96 0.9476

page 10 of 18
PROJECT:
LIGHTING CALCULATION SHEET

Date: 3/6/2024
Design Key: Notes: Reflectance Factor:

Luminaire Maintenance Factor – LMF 0.94 1. Lamp Lumen Maintenance Factor – LLMF Ceiling 0.70 Standard Ceiling
As with conventional source lamps LED output will depreciate
Room condition Luminaire Cleaning Time Wall 0.50 Standard Wall
over time.
Clean 1 Year Clean 2. Luminaire Maintenance Factor – LMF Working Plane 0.30 Standard Floor
Room Surface Maintenance Factor - RMF 0.95 It indicate annual luminaires cleaning time
Room condition Luminaire Cleaning Time 3. Room Surface Maintenance Factor - RMF Light loss facto 0.80
Clean 1 Year Room Clean It indicate annual luminaires cleaning time & Type of Luminaire
Direct
Luminaire Type 4. Lamp Survival Factor - LSF
Luminaires
Lamp Survival Factor - LSF 1 It indicate failure factor of LED Lamp - Usually equal 1
Lamp Lumen Maintenance Factor - LLMF 0.9

Maintaince Factor - MF 0.8037

Q'ty
Lamp Working Lighting Fixture type LTG Q'ty E(lux)
E Room Mantainance Luminous Manua E(lux)
No. Room height height Hm(m) X (m) Y (m) S (m2) (Phillips Light U Factor Q'ty Put in LGT lay-out Put in Code
(Lux) Index Factor Flux l Manual
(m) (m) Reference) Cal. Room Room
Decide
A FACTORY { GROUND FLOOR } ceiling X Y

1 TOILET (F) Y 200 2.5 0.00 2.5 3.6 11.3 41.1 1.10 Batten Luminaire 40W 0.572 0.8037 1,200 19 10 2 5 0 107 Batten

2 TOILET (M) Y 200 2.5 0.00 2.5 3.6 3.5 12.7 0.71 Batten Luminaire 40W 0.4295 0.8037 1,200 8 4 2 2 0 104 Batten

3 ELECTRICAL ROOM Y 200 2.9 0.80 2.1 9.0 7.7 69.7 1.98 Batten Luminaire 40W 0.7564 0.8037 1,200 24 25 5 5 0 209 Batten

4 BOILER ROOM Y 200 2.9 0.80 2.1 8.4 13.2 110.5 2.44 Batten Luminaire 40W 0.8128 0.8037 1,200 36 20 4 5 0 114 Batten

5 COMPRESSOR ROOM Y 200 3.3 0.80 2.5 5.5 5.9 32.8 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 15 6 3 2 0 82 Batten

6 PUMP ROOM Y 200 2.9 0.80 2.1 6.8 7.8 52.6 1.72 Batten Luminaire 40W 0.7096 0.8037 1,200 20 20 4 5 0 208 Batten

7 SLUDGE ROOM Y 200 2.9 0.80 2.1 4.5 4.0 18.0 1.01 Batten Luminaire 40W 0.5432 0.8037 1,200 9 9 3 3 0 210 Batten

8 FILTER MACHINE ROOM Y 200 2.9 0.80 2.1 5.0 4.0 20.0 1.06 Batten Luminaire 40W 0.5592 0.8037 1,200 10 12 3 4 0 259 Batten

9 RO SYSTEM ROOM Y 200 2.9 0.80 2.1 7.8 6.0 46.8 1.61 Batten Luminaire 40W 0.6898 0.8037 1,200 18 20 4 5 0 227 Batten

10 FAN ROOM Y 200 2.9 0.80 2.1 7.3 3.5 25.6 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 12 15 5 3 0 263 Batten

11 OPERATION ROOM Y 200 2.9 0.80 2.1 7.0 3.5 24.5 1.11 Batten Luminaire 40W 0.5752 0.8037 1,200 12 12 4 3 0 217 Batten

12 PHARMACY Y 200 2.9 0.80 2.1 4.0 3.5 14.0 0.89 Batten Luminaire 40W 0.5015 0.8037 1,200 8 6 3 2 0 166 Batten

13 2nd QC Y 700 2.9 0.80 2.1 5.7 26.9 152.9 2.23 Batten Luminaire 40W 0.7876 0.8037 1,200 177 180 6 30 0 716 Batten

14 FINAL QC Y 700 2.5 0.80 1.7 11.8 10.3 121.0 3.23 Batten Luminaire 40W 0.8738 0.8037 1,200 126 132 12 11 0 736 Batten

15 PACKING Y 550 2.5 0.80 1.7 11.8 4.8 57.2 2.02 Batten Luminaire 40W 0.7624 0.8037 1,200 54 15 5 3 0 154 Batten

16 PRODUCTION WAREHOUSE Y 300 2.5 0.80 1.7 11.8 11.2 132.3 3.38 Batten Luminaire 40W 0.8828 0.8037 1,200 59 28 7 4 0 144 Batten

17 FABRIC WAREHOUSE Y 300 2.9 0.80 2.1 20.0 27.0 540.0 5.47 Batten Luminaire 40W 0.96 0.8037 1,200 219 120 12 10 0 165 Batten

18 CAD ROOM Y 500 2.5 0.80 1.7 11.5 2.3 22.9 0.97 Batten Luminaire 40W 0.5295 0.8037 1,200 28 8 4 2 0 143 Batten

19 CUTTING AREA Y 550 2.1 0.80 1.3 48.4 26.6 1288.7 13.21 Batten Luminaire 40W 0.96 0.8037 1,200 957 261 29 9 0 150 Batten

20 LINE IMPORT Y 550 2.9 0.80 2.1 10.0 22.5 225.0 3.30 Batten Luminaire 40W 0.878 0.8037 1,200 183 50 5 10 0 151 Batten

21 GENERATOR ROOM Y 200 2.9 0.80 2.1 8.3 10.3 85.6 2.19 Batten Luminaire 40W 0.7828 0.8037 1,200 29 32 4 8 0 226 Batten

22 WASHING AREA (PART-1) Y 300 2.9 0.80 2.1 21.8 15.8 343.9 4.36 Batten Luminaire 40W 0.9344 0.8037 1,200 144 154 14 11 0 323 Batten

23 WASHING AREA (PART-2) Y 300 2.9 0.80 2.1 5.5 1.8 10.1 0.66 Batten Luminaire 40W 0.407 0.8037 1,200 10 10 5 2 0 310 Batten

24 WASHING AREA (PART-3) Y 300 2.9 0.80 2.1 9.7 1.9 19.0 0.77 Batten Luminaire 40W 0.4565 0.8037 1,200 17 5 5 1 0 93 Batten

25 WASHING AREA (PART-4) Y 300 2.9 0.80 2.1 8.7 6.2 53.8 1.72 Batten Luminaire 40W 0.7096 0.8037 1,200 30 30 6 5 0 305 Batten

26 BAR TACK (OVERALL) Y 600 2.1 0.80 1.3 5.6 26.9 149.8 3.55 Batten Luminaire 40W 0.893 0.8037 1,200 131 135 5 27 0 621 Batten

27 BAR TACK (PART-1) Y 200 2.9 0.80 2.1 1.2 26.9 33.2 0.56 Batten Luminaire 40W 0.38 0.8037 1,200 23 23 1 23 0 203 Batten

28 BAR TACK (PART-2) Y 600 2.1 0.80 1.3 3.1 26.9 83.4 2.14 Batten Luminaire 40W 0.7768 0.8037 1,200 84 84 2 42 0 604 Batten

29 BAR TACK (PART-3) Y 200 2.9 0.80 2.1 1.2 26.9 33.2 0.56 Batten Luminaire 40W 0.38 0.8037 1,200 23 23 1 23 0 203 Batten

30 IRON (OVERALL) Y 500 2.1 0.80 1.3 7.7 26.9 206.1 4.59 Batten Luminaire 40W 0.9436 0.8037 1,200 142 144 6 24 0 509 Batten

31 IRON (PART-1) Y 500 2.1 0.80 1.3 2.9 26.9 78.0 2.01 Batten Luminaire 40W 0.7612 0.8037 1,200 67 68 2 34 0 512 Batten

32 IRON (PART-2) Y 200 2.9 0.80 2.1 1.1 26.9 29.6 0.50 Batten Luminaire 40W 0.38 0.8037 1,200 21 21 1 21 0 208 Batten

33 IRON (PART-3) Y 500 2.1 0.80 1.3 2.9 26.9 78.0 2.01 Batten Luminaire 40W 0.7612 0.8037 1,200 67 68 2 34 0 512 Batten

34 PUMP ROOM _2 Y 200 2.9 0.80 2.1 4.7 5.2 24.5 1.18 Batten Luminaire 40W 0.5976 0.8037 1,200 11 9 3 3 0 169 Batten

35 KNIFE BAND AREA Y 200 2.9 0.80 2.1 10.2 2.8 28.6 1.05 Batten Luminaire 40W 0.556 0.8037 1,200 14 5 5 1 0 75 Batten

36 BET @LINE IMPORT & MACHNE INTERLIY 200 2.9 0.80 2.1 1.5 25.3 38.0 0.67 Batten Luminaire 40W 0.4115 0.8037 1,200 24 11 1 11 0 92 Batten

37 CORRIDOR-1 (GL_@4 & E _ K) PART-1 Y 200 2.9 0.80 2.1 51.4 3.1 160.2 1.40 Batten Luminaire 40W 0.65 0.8037 1,200 64 18 18 1 0 56 Batten

38 CORRIDOR-1 (GL_@4 & K _ Bet Q&R)PAY 200 2.9 0.80 2.1 50.4 1.7 85.7 0.78 Batten Luminaire 40W 0.461 0.8037 1,200 49 14 14 1 0 58 Batten

39 CORRIDOR-1 (GL_@4 & Bet Q&R _ S)PAY 200 2.9 0.80 2.1 13.3 3.0 39.8 1.17 Batten Luminaire 40W 0.5944 0.8037 1,200 18 6 3 2 0 69 Batten

40 MULTIPORPOSE (GL_@1&4_S&T)PART-1Y 200 2.9 0.80 2.1 4.6 24.7 113.1 1.84 Batten Luminaire 40W 0.7312 0.8037 1,200 41 22 2 11 0 110 Batten

41 MULTIPORPOSE (GL_@1&4_S&T)PART-2Y 200 2.9 0.80 2.1 3.8 3.2 12.2 0.83 Batten Luminaire 40W 0.4805 0.8037 1,200 7 4 2 2 0 122 Batten

42 CORRIDOR-2 (GL_@1 & K _ S) Y 200 2.9 0.80 2.1 65.4 1.7 111.1 0.79 Batten Luminaire 40W 0.4655 0.8037 1,200 62 72 18 4 0 233 Batten

43 PASSAGEWAY Y 200 4.5 0.80 3.7 2.8 12.5 34.7 0.61 Batten Luminaire 40W 0.3845 0.8037 1,200 24 14 2 7 0 120 Batten

44 STEEL ROLLING SHUTTER Y 200 4.5 0.80 3.7 5.0 3.0 15.0 0.51 Batten Luminaire 40W 0.38 0.8037 1,200 11 3 3 1 0 58 Batten

45 STEEL ROLLING SHUTTER Y 200 4.5 0.80 3.7 5.0 3.0 15.0 0.51 Batten Luminaire 40W 0.38 0.8037 1,200 11 3 3 1 0 58 Batten

B CANTEEN { GROUND FLOOR }

46 LOCKER 1 Y 200 2.9 0.80 2.1 17.5 2.1 37.1 0.90 Batten Luminaire 40W 0.505 0.8037 1,200 20 5 5 1 0 52 Batten

47 CANTEEN Y 150 2.9 0.80 2.1 18.5 40.1 742.9 6.03 Batten Luminaire 40W 0.96 0.8037 1,200 151 50 5 10 0 50 Batten

page 11 of 18
Q'ty
Lamp Working Lighting Fixture type LTG Q'ty E(lux)
E Room Mantainance Luminous Manua E(lux)
No. Room height height Hm(m) X (m) Y (m) S (m2) (Phillips Light U Factor Q'ty Put in LGT lay-out Put in Code
(Lux) Index Factor Flux l Manual
(m) (m) Reference) Cal. Room Room
Decide
48 CORRIDOR (CANTEEN TO LOCKER-2) Y 200 3.5 0.80 2.7 3.0 10.3 30.8 0.86 Batten Luminaire 40W 0.491 0.8037 1,200 17 8 2 4 0 98 Batten

49 LOCKER 2 Y 200 2.9 0.80 2.1 15.4 4.7 73.1 1.73 Batten Luminaire 40W 0.7114 0.8037 1,200 27 28 4 7 0 210 Batten

C FACTORY { FIRST FLOOR }

1 TOILET (F) GL@A Y 200 2.5 0.00 2.5 3.4 9.5 32.2 1.00 Batten Luminaire 40W 0.54 0.8037 1,200 16 16 2 8 0 207 Batten

2 TOILET (M) GL@A Y 200 2.5 0.00 2.5 3.4 3.2 10.7 0.65 Batten Luminaire 40W 0.4025 0.8037 1,200 7 8 2 4 0 232 Batten

3 PRODUCTION WAREHOUSE Y 300 3.5 0.80 2.7 16.4 24.0 393.6 3.58 Batten Luminaire 40W 0.8948 0.8037 1,200 172 90 10 9 0 158 Batten

4 PACKING Y 550 2.5 0.80 1.7 7.8 23.5 182.9 3.44 Batten Luminaire 40W 0.8864 0.8037 1,200 148 84 6 14 0 314 Batten

5 DRY ROOM & PRODUCTION STORAGE Y 300 2.5 0.80 1.7 23.1 23.5 544.8 6.86 Batten Luminaire 40W 0.96 0.8037 1,200 221 126 14 9 0 171 Batten

6 FINAL QC Y 700 3.5 0.80 2.7 4.3 24.0 103.6 1.36 Batten Luminaire 40W 0.642 0.8037 1,200 147 100 5 20 0 478 Batten

7 IRON (OVERALL) Y 500 2.1 0.80 1.3 5.9 24.0 140.5 3.62 Batten Luminaire 40W 0.8972 0.8037 1,200 102 104 4 26 0 512 Batten

8 IRON (PART-1) Y 500 2.1 0.80 1.3 2.9 24.0 69.6 1.99 Batten Luminaire 40W 0.7582 0.8037 1,200 60 60 2 30 0 504 Batten

9 IRON (PART-2) Y 200 3.4 0.80 2.6 1.5 24.0 35.4 0.53 Batten Luminaire 40W 0.38 0.8037 1,200 25 25 1 25 0 207 Batten

10 IRON (PART-3) Y 200 3.4 0.80 2.6 1.5 24.0 35.5 0.54 Batten Luminaire 40W 0.38 0.8037 1,200 25 25 1 25 0 206 Batten

11 2nd QC Y 700 3.4 0.80 2.6 4.8 24.0 116.1 1.55 Batten Luminaire 40W 0.679 0.8037 1,200 156 75 5 15 0 338 Batten

12 BAR TACK (OVERALL) Y 600 2.1 0.80 1.3 5.3 24.0 127.7 3.35 Batten Luminaire 40W 0.881 0.8037 1,200 113 80 5 16 0 426 Batten

13 BAR TACK (PART-1) Y 200 3.4 0.80 2.6 1.1 24.0 26.6 0.41 Batten Luminaire 40W 0.38 0.8037 1,200 19 5 1 5 0 55 Batten

14 BAR TACK (PART-2) Y 600 2.1 0.80 1.3 3.1 24.0 74.4 2.11 Batten Luminaire 40W 0.7732 0.8037 1,200 75 20 2 10 0 160 Batten

15 BAR TACK (PART-3) Y 200 3.4 0.80 2.6 1.1 24.0 26.6 0.41 Batten Luminaire 40W 0.38 0.8037 1,200 19 5 1 5 0 55 Batten

16 SEWING (OVERALL) Y 600 2.1 0.80 1.3 49.6 24.0 1190.4 12.44 Batten Luminaire 40W 0.96 0.8037 1,200 965 968 44 22 0 602 Batten

17 SEWING (ON THE TABLE) Y 600 2.1 0.80 1.3 23.3 2.8 65.2 1.92 Batten Luminaire 40W 0.7456 0.8037 1,200 69 18 9 2 0 159 Batten

18 SEWING (BESIDE THE TABLE) Y 200 3.4 0.80 2.6 23.3 1.2 26.8 0.42 Batten Luminaire 40W 0.38 0.8037 1,200 19 5 5 1 0 55 Batten

19 SEWING (BESIDE THE TABLE) Y 200 3.4 0.80 2.6 23.3 3.9 89.7 1.27 Batten Luminaire 40W 0.624 0.8037 1,200 38 10 5 2 0 54 Batten

20 CORRIDOR-5(GL_@1_4 & J_K)BESIDE Y 200 3.4 0.80 2.6 3.0 24.0 72.0 1.03 Batten Luminaire 40W 0.5496 0.8037 1,200 34 34 2 17 0 200 Batten

21 CORRIDOR-6 (GL_@1_4 & Q_R)BESIDE Y 200 3.4 0.80 2.6 7.1 20.4 144.8 2.02 Batten Luminaire 40W 0.7624 0.8037 1,200 50 52 4 13 0 211 Batten

22 STORE 1 Y 200 3.4 0.80 2.6 9.5 10.2 97.3 1.90 Batten Luminaire 40W 0.742 0.8037 1,200 34 35 5 7 0 206 Batten

23 STORE 2 Y 200 3.4 0.80 2.6 9.5 10.2 97.3 1.90 Batten Luminaire 40W 0.742 0.8037 1,200 34 35 5 7 0 206 Batten

24 TOILET (F) GL@T Y 200 2.5 0.00 2.5 3.6 9.8 34.9 1.05 Batten Luminaire 40W 0.556 0.8037 1,200 17 18 2 9 0 221 Batten

25 TOILET (M) GL@T Y 200 2.5 0.00 2.5 3.6 3.5 12.3 0.70 Batten Luminaire 40W 0.425 0.8037 1,200 8 4 2 2 0 106 Batten

26 CORRIDOR-1 (GL_@4 & B_T)(PART-1) Y 200 3.4 0.80 2.6 141.8 3.0 425.4 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 190 53 53 1 0 56 Batten

27 CORRIDOR-1 (GL_@3_4 & Q_S)(PART-2)Y 200 3.4 0.80 2.6 16.6 3.6 59.2 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 27 7 7 1 0 53 Batten

28 CORRIDOR-2 (GL_@1_4 & S_T)(PART-1)Y 200 3.4 0.80 2.6 3.0 23.4 71.1 1.03 Batten Luminaire 40W 0.5496 0.8037 1,200 34 18 2 9 0 107 Batten

29 CORRIDOR-2 (GL_@1_2 & S_T)(PART-2)Y 200 3.4 0.80 2.6 3.8 5.7 21.7 0.88 Batten Luminaire 40W 0.498 0.8037 1,200 12 6 2 3 0 106 Batten

30 CORRIDOR-3 (GL_@1 & B_T) Y 200 3.4 0.80 2.6 144.3 3.0 433.0 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 193 53 53 1 0 55 Batten

31 CORRIDOR-4 (GL_@1_2 & A_B)(PART-1)Y 200 3.4 0.80 2.6 7.9 10.5 83.3 1.74 Batten Luminaire 40W 0.7132 0.8037 1,200 31 16 4 4 0 106 Batten

32 CORRIDOR-4 (GL_@2_4 & A_B)(PART-2)Y 200 3.4 0.80 2.6 4.3 16.5 70.9 1.31 Batten Luminaire 40W 0.632 0.8037 1,200 30 16 2 8 0 110 Batten

CANTEEN { FIRST FLOOR }

33 LOCKER 1 Y 200 3.4 0.80 2.6 17.5 2.1 37.1 0.73 Batten Luminaire 40W 0.4385 0.8037 1,200 22 6 6 1 0 55 Batten

34 CANTEEN Y 150 3.4 0.80 2.6 18.5 40.1 742.9 4.87 Batten Luminaire 40W 0.9548 0.8037 1,200 152 50 5 10 0 50 Batten

35 CORRIDOR (CANTEEN TO LOCKER-2) Y 200 3.4 0.80 2.6 3.0 10.3 30.8 0.89 Batten Luminaire 40W 0.5015 0.8037 1,200 16 8 2 4 0 100 Batten

36 LOCKER 2 Y 200 3.4 0.80 2.6 15.4 4.7 73.1 1.40 Batten Luminaire 40W 0.65 0.8037 1,200 30 8 4 2 0 55 Batten

E FACTORY { SECOND FLOOR }

1 TOILET (F) GL@A Y 200 2.5 0.00 2.5 3.4 11.3 38.3 1.04 Batten Luminaire 40W 0.5528 0.8037 1,200 18 10 2 5 0 111 Batten

2 TOILET (M) GL@A Y 200 2.5 0.00 2.5 3.4 3.2 10.7 0.65 Batten Luminaire 40W 0.4025 0.8037 1,200 7 8 2 4 0 232 Batten

3 PRODUCTION WAREHOUSE Y 300 3.5 0.80 2.7 16.4 24.0 393.6 3.58 Batten Luminaire 40W 0.8948 0.8037 1,200 172 90 10 9 0 158 Batten

4 PACKING Y 550 2.5 0.80 1.7 7.8 23.5 182.9 3.44 Batten Luminaire 40W 0.8864 0.8037 1,200 148 84 6 14 0 314 Batten

5 DRY ROOM & PRODUCTION STORAGE Y 300 2.5 0.80 1.7 23.1 23.5 544.8 6.86 Batten Luminaire 40W 0.96 0.8037 1,200 221 126 14 9 0 171 Batten

6 FINAL QC Y 700 3.5 0.80 2.7 4.3 24.0 103.6 1.36 Batten Luminaire 40W 0.642 0.8037 1,200 147 150 5 30 0 717 Batten

7 IRON (OVERALL) Y 500 2.1 0.80 1.3 5.9 24.0 140.5 3.62 Batten Luminaire 40W 0.8972 0.8037 1,200 102 104 4 26 0 512 Batten

8 IRON (PART-1) Y 500 2.1 0.80 1.3 2.9 24.0 69.6 1.99 Batten Luminaire 40W 0.7582 0.8037 1,200 60 60 2 30 0 504 Batten

9 IRON (PART-2) Y 200 3.4 0.80 2.6 1.5 24.0 35.4 0.53 Batten Luminaire 40W 0.38 0.8037 1,200 25 25 1 25 0 207 Batten

10 IRON (PART-3) Y 200 3.4 0.80 2.6 1.5 24.0 35.5 0.54 Batten Luminaire 40W 0.38 0.8037 1,200 25 25 1 25 0 206 Batten

11 2nd QC Y 700 3.4 0.80 2.6 4.8 24.0 116.1 1.55 Batten Luminaire 40W 0.679 0.8037 1,200 156 160 5 32 0 722 Batten

12 BAR TACK (OVERALL) Y 600 2.1 0.80 1.3 5.3 24.0 127.7 3.35 Batten Luminaire 40W 0.881 0.8037 1,200 113 80 5 16 0 426 Batten

13 BAR TACK (PART-1) Y 200 3.4 0.80 2.6 1.1 24.0 26.6 0.41 Batten Luminaire 40W 0.38 0.8037 1,200 19 5 1 5 0 55 Batten

14 BAR TACK (PART-2) Y 600 2.1 0.80 1.3 3.1 24.0 74.4 2.11 Batten Luminaire 40W 0.7732 0.8037 1,200 75 20 2 10 0 160 Batten

15 BAR TACK (PART-3) Y 200 3.4 0.80 2.6 1.1 24.0 26.6 0.41 Batten Luminaire 40W 0.38 0.8037 1,200 19 5 1 5 0 55 Batten

16 SEWING (OVERALL) Y 600 2.1 0.80 1.3 49.6 24.0 1190.4 12.44 Batten Luminaire 40W 0.96 0.8037 1,200 965 968 44 22 0 602 Batten

17 SEWING (ON THE TABLE) Y 600 2.1 0.80 1.3 23.3 2.8 65.2 1.92 Batten Luminaire 40W 0.7456 0.8037 1,200 69 18 9 2 0 159 Batten

18 SEWING (BESIDE THE TABLE) Y 200 3.4 0.80 2.6 23.3 2.5 58.3 0.87 Batten Luminaire 40W 0.4945 0.8037 1,200 31 8 8 1 0 52 Batten

19 CORRIDOR-5(GL_@1_4 & J_K)BESIDE Y 200 3.4 0.80 2.6 3.0 24.0 72.0 1.03 Batten Luminaire 40W 0.5496 0.8037 1,200 34 34 2 17 0 200 Batten

20 CORRIDOR-6 (GL_@1_4 & Q_R)BESIDE Y 200 3.4 0.80 2.6 7.1 20.4 144.8 2.02 Batten Luminaire 40W 0.7624 0.8037 1,200 50 52 4 13 0 211 Batten

21 SAMPLE Y 200 3.5 0.80 2.7 9.5 10.2 97.3 1.83 Batten Luminaire 40W 0.7294 0.8037 1,200 35 35 5 7 0 202 Batten

22 MAINTENANCE Y 200 3.5 0.80 2.7 9.5 10.2 97.3 1.83 Batten Luminaire 40W 0.7294 0.8037 1,200 35 35 5 7 0 202 Batten

23 TOILET (F) GL@T Y 200 2.5 0.00 2.5 3.6 11.6 41.4 1.09 Batten Luminaire 40W 0.5688 0.8037 1,200 19 10 2 5 0 106 Batten

24 TOILET (M) GL@T Y 200 2.5 0.00 2.5 3.6 3.4 12.3 0.70 Batten Luminaire 40W 0.425 0.8037 1,200 8 4 2 2 0 107 Batten

25 CORRIDOR-1 (GL_@4 & B_T)(PART-1) Y 200 3.4 0.80 2.6 141.8 3.0 425.4 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 190 53 53 1 0 56 Batten

page 12 of 18
Q'ty
Lamp Working Lighting Fixture type LTG Q'ty E(lux)
E Room Mantainance Luminous Manua E(lux)
No. Room height height Hm(m) X (m) Y (m) S (m2) (Phillips Light U Factor Q'ty Put in LGT lay-out Put in Code
(Lux) Index Factor Flux l Manual
(m) (m) Reference) Cal. Room Room
Decide
26 CORRIDOR-1 (GL_@3_4 & Q_S)(PART-2)Y 200 3.4 0.80 2.6 16.6 3.6 59.2 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 27 7 7 1 0 53 Batten

27 CORRIDOR-2 (GL_@1_4 & S_T)(PART-1)Y 200 3.4 0.80 2.6 3.0 23.4 71.1 1.03 Batten Luminaire 40W 0.5496 0.8037 1,200 34 18 2 9 0 107 Batten

28 CORRIDOR-2 (GL_@1_2 & S_T)(PART-2)Y 200 3.4 0.80 2.6 3.8 3.9 14.9 0.74 Batten Luminaire 40W 0.443 0.8037 1,200 9 6 2 3 0 138 Batten

29 CORRIDOR-3 (GL_@1 & B_T) Y 200 3.4 0.80 2.6 144.3 3.0 433.0 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 193 53 53 1 0 55 Batten

30 CORRIDOR-4 (GL_@1_2 & A_B)(PART-1)Y 200 3.4 0.80 2.6 7.9 8.7 68.9 1.60 Batten Luminaire 40W 0.688 0.8037 1,200 26 16 4 4 0 123 Batten

31 CORRIDOR-4 (GL_@2_4 & A_B)(PART-2)Y 200 3.4 0.80 2.6 4.3 18.3 78.6 1.34 Batten Luminaire 40W 0.638 0.8037 1,200 32 18 2 9 0 113 Batten

F CANTEEN { SEDOND FLOOR }

32 LOCKER 1 Y 200 3.5 0.80 2.7 17.5 2.1 37.1 0.70 Batten Luminaire 40W 0.425 0.8037 1,200 23 6 6 1 0 53 Batten

33 CANTEEN Y 150 3.5 0.80 2.7 18.5 40.1 742.9 4.69 Batten Luminaire 40W 0.9476 0.8037 1,200 153 50 5 10 0 49 Batten

page 13 of 18
PROJECT:
LIGHTING CALCULATION SHEET

Design Key:

Luminaire Maintenance Factor – LMF


Room condition Luminaire Cleaning Time
Clean 1 Year Clean
Room Surface Maintenance Factor - RMF
Room condition Luminaire Cleaning Time
Clean 1 Year Room Clean
Direct
Luminaire Type
Luminaires
Lamp Survival Factor - LSF
Lamp Lumen Maintenance Factor - LLMF

Maintaince Factor - MF

Linear Interpolation

No. Room SHR x1 x2 y1 y2 y Luminaire Code

A FACTORY { GROUND FLOOR } ceiling

1 TOILET (F) Y 0.588 1 1.25 0.54 0.62 0.572 Ba

2 TOILET (M) Y 0.505 1 0.8 0.38 0.47 0.4295 Ba

3 ELECTRICAL ROOM Y 0.811 2 2 0.67 0.76 0.7564 Ba

4 BOILER ROOM Y 0.834 2 2.5 0.76 0.82 0.8128 Ba

5 COMPRESSOR ROOM Y 0.584 1 1.25 0.54 0.62 0.5816 Ba

6 PUMP ROOM Y 0.772 2 2 0.67 0.76 0.7096 Ba

7 SLUDGE ROOM Y 0.673 1 1.25 0.54 0.62 0.5432 Ba

8 FILTER MACHINE ROOM Y 0.673 1 1.25 0.54 0.62 0.5592 Ba

9 RO SYSTEM ROOM Y 0.768 2 2 0.67 0.76 0.6898 Ba

10 FAN ROOM Y 0.695 1 1.25 0.54 0.62 0.5816 Ba

11 OPERATION ROOM Y 0.68 1 1.25 0.54 0.62 0.5752 Ba

12 PHARMACY Y 0.63 1 1 0.47 0.54 0.5015 Ba

13 2nd QC Y 0.443 2 2.5 0.76 0.82 0.7876 Ba

14 FINAL QC Y 0.576 3 4 0.86 0.92 0.8738 Ba

15 PACKING Y 0.605 2 2.5 0.76 0.82 0.7624 Ba

16 PRODUCTION WAREHOUSE Y 0.881 3 4 0.86 0.92 0.8828 Ba

17 FABRIC WAREHOUSE Y 0.748 5 ### 0.96 ### Err:502 Ba

18 CAD ROOM Y 0.532 1 1 0.47 0.54 0.5295 Ba

19 CUTTING AREA Y 0.893 5 ### 0.96 ### Err:502 Ba

20 LINE IMPORT Y 0.528 3 4 0.86 0.92 0.878 Ba

21 GENERATOR ROOM Y 0.818 2 2.5 0.76 0.82 0.7828 Ba

22 WASHING AREA (PART-1) Y 0.736 4 5 0.92 0.96 0.9344 Ba

23 WASHING AREA (PART-2) Y 0.479 1 0.8 0.38 0.47 0.407 Ba

24 WASHING AREA (PART-3) Y 0.503 1 0.8 0.38 0.47 0.4565 Ba

25 WASHING AREA (PART-4) Y 0.638 2 2 0.67 0.76 0.7096 Ba

26 BAR TACK (OVERALL) Y 0.823 3 4 0.86 0.92 0.893 Ba

27 BAR TACK (PART-1) Y 0.572 1 0.6 0.38 0.38 0.38 Ba

28 BAR TACK (PART-2) Y 0.766 2 2.5 0.76 0.82 0.7768 Ba

29 BAR TACK (PART-3) Y 0.572 1 0.6 0.38 0.38 0.38 Ba

30 IRON (OVERALL) Y 0.927 4 5 0.92 0.96 0.9436 Ba

31 IRON (PART-1) Y 0.83 2 2.5 0.76 0.82 0.7612 Ba

32 IRON (PART-2) Y 0.565 1 0.6 0.38 0.38 0.38 Ba

33 IRON (PART-3) Y 0.83 2 2.5 0.76 0.82 0.7612 Ba

34 PUMP ROOM _2 Y 0.711 1 1.25 0.54 0.62 0.5976 Ba

35 KNIFE BAND AREA Y 0.681 1 1.25 0.54 0.62 0.556 Ba

36 BET @LINE IMPORT & MACHNE INTERLIY 0.599 1 0.8 0.38 0.47 0.4115 Ba

37 CORRIDOR-1 (GL_@4 & E _ K) PART-1 Y 0.753 1 1.5 0.62 0.67 0.65 Ba

38 CORRIDOR-1 (GL_@4 & K _ Bet Q&R)PAY 0.63 1 0.8 0.38 0.47 0.461 Ba

39 CORRIDOR-1 (GL_@4 & Bet Q&R _ S)PAY 0.708 1 1.25 0.54 0.62 0.5944 Ba

40 MULTIPORPOSE (GL_@1&4_S&T)PART-1Y 0.791 2 2 0.67 0.76 0.7312 Ba

41 MULTIPORPOSE (GL_@1&4_S&T)PART-2Y 0.628 1 1 0.47 0.54 0.4805 Ba

42 CORRIDOR-2 (GL_@1 & K _ S) Y 0.638 1 0.8 0.38 0.47 0.4655 Ba

43 PASSAGEWAY Y 0.325 1 0.8 0.38 0.47 0.3845 Ba

44 STEEL ROLLING SHUTTER Y 0.316 1 0.6 0.38 0.38 0.38 Ba

45 STEEL ROLLING SHUTTER Y 0.316 1 0.6 0.38 0.38 0.38 Ba

B CANTEEN { GROUND FLOOR }

46 LOCKER 1 Y 0.649 1 1 0.47 0.54 0.505 Ba

47 CANTEEN Y 1.056 5 ### 0.96 ### Err:502 Ba

page 14 of 18
Linear Interpolation

No. Room SHR x1 x2 y1 y2 y Luminaire Code

48 CORRIDOR (CANTEEN TO LOCKER-2) Y 0.499 1 1 0.47 0.54 0.491 Ba

49 LOCKER 2 Y 0.784 2 2 0.67 0.76 0.7114 Ba

C FACTORY { FIRST FLOOR }

1 TOILET (F) GL@A Y 0.567 1 1.25 0.54 0.62 0.54 Ba

2 TOILET (M) GL@A Y 0.494 1 0.8 0.38 0.47 0.4025 Ba

3 PRODUCTION WAREHOUSE Y 0.556 3 4 0.86 0.92 0.8948 Ba

4 PACKING Y 0.654 3 4 0.86 0.92 0.8864 Ba

5 DRY ROOM & PRODUCTION STORAGE Y 0.924 5 ### 0.96 ### Err:502 Ba

6 FINAL QC Y 0.311 1 1.5 0.62 0.67 0.642 Ba

7 IRON (OVERALL) Y 0.903 3 4 0.86 0.92 0.8972 Ba

8 IRON (PART-1) Y 0.828 2 2 0.67 0.76 0.7582 Ba

9 IRON (PART-2) Y 0.458 1 0.6 0.38 0.38 0.38 Ba

10 IRON (PART-3) Y 0.458 1 0.6 0.38 0.38 0.38 Ba

11 2nd QC Y 0.332 2 2 0.67 0.76 0.679 Ba

12 BAR TACK (OVERALL) Y 0.818 3 4 0.86 0.92 0.881 Ba

13 BAR TACK (PART-1) Y 0.455### #N/A #N/A #N/A #N/A Ba

14 BAR TACK (PART-2) Y 0.766 2 2.5 0.76 0.82 0.7732 Ba

15 BAR TACK (PART-3) Y 0.455### #N/A #N/A #N/A #N/A Ba

16 SEWING (OVERALL) Y 0.854 5 ### 0.96 ### Err:502 Ba

17 SEWING (ON THE TABLE) Y 0.748 2 2 0.67 0.76 0.7456 Ba

18 SEWING (BESIDE THE TABLE) Y 0.457### #N/A #N/A #N/A #N/A Ba

19 SEWING (BESIDE THE TABLE) Y 0.591 1 1.5 0.62 0.67 0.624 Ba

20 CORRIDOR-5(GL_@1_4 & J_K)BESIDE Y 0.56 1 1.25 0.54 0.62 0.5496 Ba

21 CORRIDOR-6 (GL_@1_4 & Q_R)BESIDE Y 0.654 2 2.5 0.76 0.82 0.7624 Ba

22 STORE 1 Y 0.651 2 2 0.67 0.76 0.742 Ba

23 STORE 2 Y 0.651 2 2 0.67 0.76 0.742 Ba

24 TOILET (F) GL@T Y 0.573 1 1.25 0.54 0.62 0.556 Ba

25 TOILET (M) GL@T Y 0.497 1 0.8 0.38 0.47 0.425 Ba

26 CORRIDOR-1 (GL_@4 & B_T)(PART-1) Y 0.575 1 1.25 0.54 0.62 0.5816 Ba

27 CORRIDOR-1 (GL_@3_4 & Q_S)(PART-2)Y 0.569 1 1.25 0.54 0.62 0.5816 Ba

28 CORRIDOR-2 (GL_@1_4 & S_T)(PART-1)Y 0.556 1 1.25 0.54 0.62 0.5496 Ba

29 CORRIDOR-2 (GL_@1_2 & S_T)(PART-2)Y 0.517 1 1 0.47 0.54 0.498 Ba

30 CORRIDOR-3 (GL_@1 & B_T) Y 0.576 1 1.25 0.54 0.62 0.5816 Ba

31 CORRIDOR-4 (GL_@1_2 & A_B)(PART-1)Y 0.63 2 2 0.67 0.76 0.7132 Ba

32 CORRIDOR-4 (GL_@2_4 & A_B)(PART-2)Y 0.591 1 1.5 0.62 0.67 0.632 Ba

CANTEEN { FIRST FLOOR }

33 LOCKER 1 Y 0.499 1 0.8 0.38 0.47 0.4385 Ba

34 CANTEEN Y 0.85 4 5 0.92 0.96 0.9548 Ba

35 CORRIDOR (CANTEEN TO LOCKER-2) Y 0.534 1 1 0.47 0.54 0.5015 Ba

36 LOCKER 2 Y 0.6 1 1.5 0.62 0.67 0.65 Ba

E FACTORY { SECOND FLOOR }

1 TOILET (F) GL@A Y 0.583 1 1.25 0.54 0.62 0.5528 Ba

2 TOILET (M) GL@A Y 0.494 1 0.8 0.38 0.47 0.4025 Ba

3 PRODUCTION WAREHOUSE Y 0.556 3 4 0.86 0.92 0.8948 Ba

4 PACKING Y 0.654 3 4 0.86 0.92 0.8864 Ba

5 DRY ROOM & PRODUCTION STORAGE Y 0.924 5 ### 0.96 ### Err:502 Ba

6 FINAL QC Y 0.311 1 1.5 0.62 0.67 0.642 Ba

7 IRON (OVERALL) Y 0.903 3 4 0.86 0.92 0.8972 Ba

8 IRON (PART-1) Y 0.828 2 2 0.67 0.76 0.7582 Ba

9 IRON (PART-2) Y 0.458 1 0.6 0.38 0.38 0.38 Ba

10 IRON (PART-3) Y 0.458 1 0.6 0.38 0.38 0.38 Ba

11 2nd QC Y 0.332 2 2 0.67 0.76 0.679 Ba

12 BAR TACK (OVERALL) Y 0.818 3 4 0.86 0.92 0.881 Ba

13 BAR TACK (PART-1) Y 0.455### #N/A #N/A #N/A #N/A Ba

14 BAR TACK (PART-2) Y 0.766 2 2.5 0.76 0.82 0.7732 Ba

15 BAR TACK (PART-3) Y 0.455### #N/A #N/A #N/A #N/A Ba

16 SEWING (OVERALL) Y 0.854 5 ### 0.96 ### Err:502 Ba

17 SEWING (ON THE TABLE) Y 0.748 2 2 0.67 0.76 0.7456 Ba

18 SEWING (BESIDE THE TABLE) Y 0.527 1 1 0.47 0.54 0.4945 Ba

19 CORRIDOR-5(GL_@1_4 & J_K)BESIDE Y 0.56 1 1.25 0.54 0.62 0.5496 Ba

20 CORRIDOR-6 (GL_@1_4 & Q_R)BESIDE Y 0.654 2 2.5 0.76 0.82 0.7624 Ba

21 SAMPLE Y 0.617 2 2 0.67 0.76 0.7294 Ba

22 MAINTENANCE Y 0.617 2 2 0.67 0.76 0.7294 Ba

23 TOILET (F) GL@T Y 0.59 1 1.25 0.54 0.62 0.5688 Ba

24 TOILET (M) GL@T Y 0.495 1 0.8 0.38 0.47 0.425 Ba

25 CORRIDOR-1 (GL_@4 & B_T)(PART-1) Y 0.575 1 1.25 0.54 0.62 0.5816 Ba

page 15 of 18
Linear Interpolation

No. Room SHR x1 x2 y1 y2 y Luminaire Code

26 CORRIDOR-1 (GL_@3_4 & Q_S)(PART-2)Y 0.569 1 1.25 0.54 0.62 0.5816 Ba

27 CORRIDOR-2 (GL_@1_4 & S_T)(PART-1)Y 0.556 1 1.25 0.54 0.62 0.5496 Ba

28 CORRIDOR-2 (GL_@1_2 & S_T)(PART-2)Y 0.494 1 0.8 0.38 0.47 0.443 Ba

29 CORRIDOR-3 (GL_@1 & B_T) Y 0.576 1 1.25 0.54 0.62 0.5816 Ba

30 CORRIDOR-4 (GL_@1_2 & A_B)(PART-1)Y 0.626 2 2 0.67 0.76 0.688 Ba

31 CORRIDOR-4 (GL_@2_4 & A_B)(PART-2)Y 0.603 1 1.5 0.62 0.67 0.638 Ba

F CANTEEN { SEDOND FLOOR }

32 LOCKER 1 Y 0.47 1 0.8 0.38 0.47 0.425 Ba

33 CANTEEN Y 0.816 4 5 0.92 0.96 0.9476 Ba

page 16 of 18
PROJECT:
LIGHTING CALCULATION SHEET

Date: 3/6/2024
Design Key: Notes: Reflectance Factor:

Luminaire Maintenance Factor – LMF 0.94 1. Lamp Lumen Maintenance Factor – LLMF Ceiling 0.70 Standard Ceiling
As with conventional source lamps LED output will depreciate
Room condition Luminaire Cleaning Time Wall 0.50 Standard Wall
over time.
Clean 1 Year Clean 2. Luminaire Maintenance Factor – LMF Working Plane 0.30 Standard Floor
Room Surface Maintenance Factor - RMF 0.95 It indicate annual luminaires cleaning time
Room condition Luminaire Cleaning Time 3. Room Surface Maintenance Factor - RMF Light loss facto 0.80
Clean 1 Year Room Clean It indicate annual luminaires cleaning time & Type of Luminaire
Direct
Luminaire Type 4. Lamp Survival Factor - LSF
Luminaires
Lamp Survival Factor - LSF 1 It indicate failure factor of LED Lamp - Usually equal 1
Lamp Lumen Maintenance Factor - LLMF 0.9

Maintaince Factor - MF 0.8037

Linear Interpolation
Q'ty
Lamp Working LTG Q'ty E(lux) E(lux)
E Room Lighting Fixture type Mantainance Luminous Manua
No. Room height height Hm(m) X (m) Y (m) S (m2) U Factor Q'ty Put in LGT lay-out Manua Put in Code SHR x1 x2 y1 y2 y
(Lux) Index (Phillips Light Reference) Factor Flux l
(m) (m) Cal. Room l Room
Decide
A FACTORY { GROUND FLOOR } ceiling X Y

1 BED ROOM 1 Y 200 1.8 0.00 1.8 5.1 2.1 10.7 0.83 Batten Luminaire 40W 0.4805 0.8037 1,200 6 4 2 2 0 138 Batten 0.742 1 1 0.47 0.54 0.4805

2 TOILET (M) Y 200 2.5 0.00 2.5 3.6 3.5 12.7 0.71 Batten Luminaire 40W 0.4295 0.8037 1,200 8 4 2 2 0 104 Batten 0.505 1 0.8 0.38 0.47 0.4295

3 ELECTRICAL ROOM Y 200 2.9 0.80 2.1 9.0 7.7 69.7 1.98 Batten Luminaire 40W 0.7564 0.8037 1,200 24 25 5 5 0 209 Batten 0.811 2 2 0.67 0.76 0.7564

4 BOILER ROOM Y 200 2.9 0.80 2.1 8.4 13.2 110.5 2.44 Batten Luminaire 40W 0.8128 0.8037 1,200 36 20 4 5 0 114 Batten 0.834 2 2.5 0.76 0.82 0.8128

5 COMPRESSOR ROOM Y 200 3.3 0.80 2.5 5.5 5.9 32.8 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 15 15 3 5 0 205 Batten 0.584 1 1.25 0.54 0.62 0.5816

6 PUMP ROOM _1 Y 200 2.9 0.80 2.1 6.8 7.8 52.6 1.72 Batten Luminaire 40W 0.7096 0.8037 1,200 20 20 4 5 0 208 Batten 0.772 2 2 0.67 0.76 0.7096

7 SLUDGE ROOM Y 200 2.9 0.80 2.1 4.5 4.0 18.0 1.01 Batten Luminaire 40W 0.5432 0.8037 1,200 9 12 3 4 0 279 Batten 0.673 1 1.25 0.54 0.62 0.5432

8 FILTER MACHINE ROOM Y 200 2.9 0.80 2.1 5.0 4.0 20.0 1.06 Batten Luminaire 40W 0.5592 0.8037 1,200 10 12 3 4 0 259 Batten 0.673 1 1.25 0.54 0.62 0.5592

9 RO SYSTEM ROOM Y 200 2.9 0.80 2.1 7.8 6.0 46.8 1.61 Batten Luminaire 40W 0.6898 0.8037 1,200 18 20 4 5 0 227 Batten 0.768 2 2 0.67 0.76 0.6898

10 FAN ROOM Y 200 2.9 0.80 2.1 7.3 3.5 25.6 1.13 Batten Luminaire 40W 0.5816 0.8037 1,200 12 12 3 4 0 211 Batten 0.695 1 1.25 0.54 0.62 0.5816

11 OPERATION ROOM Y 200 2.9 0.80 2.1 7.0 3.5 24.5 1.11 Batten Luminaire 40W 0.5752 0.8037 1,200 12 12 3 4 0 217 Batten 0.68 1 1.25 0.54 0.62 0.5752

12 PHARMACY Y 200 2.9 0.80 2.1 4.0 3.5 14.0 0.89 Batten Luminaire 40W 0.5015 0.8037 1,200 8 4 2 2 0 111 Batten 0.63 1 1 0.47 0.54 0.5015

13 2nd QC Y 700 2.9 0.80 2.1 5.7 26.9 152.9 2.23 Batten Luminaire 40W 0.7876 0.8037 1,200 177 50 5 10 0 199 Batten 0.443 2 2.5 0.76 0.82 0.7876

14 FINAL QC Y 700 2.5 0.80 1.7 11.8 10.3 121.0 3.23 Batten Luminaire 40W 0.8738 0.8037 1,200 126 25 5 5 0 139 Batten 0.576 3 4 0.86 0.92 0.8738

15 PACKING Y 550 2.5 0.80 1.7 11.8 4.8 57.2 2.02 Batten Luminaire 40W 0.7624 0.8037 1,200 54 15 5 3 0 154 Batten 0.605 2 2.5 0.76 0.82 0.7624

16 PRODUCTION WAREHOUSE Y 300 2.5 0.80 1.7 11.8 11.2 132.3 3.38 Batten Luminaire 40W 0.8828 0.8037 1,200 59 28 7 4 0 144 Batten 0.881 3 4 0.86 0.92 0.8828

17 FABRIC WAREHOUSE Y 300 2.9 0.80 2.1 20.0 30.0 600.0 5.71 Batten Luminaire 40W 0.96 0.8037 1,200 244 63 7 9 0 78 Batten 0.747 5 ### 0.96 ### Err:502

18 CAD ROOM Y 500 2.5 0.80 1.7 11.5 2.3 26.2 1.12 Batten Luminaire 40W 0.5784 0.8037 1,200 30 8 4 2 0 136 Batten 0.55 1 1.25 0.54 0.62 0.5784

19 CUTTING AREA Y 550 2.1 0.80 1.3 48.4 26.6 1288.7 13.21 Batten Luminaire 40W 0.96 0.8037 1,200 957 216 24 9 0 124 Batten 0.893 5 ### 0.96 ### Err:502

20 LINE IMPORT Y 550 2.9 0.80 2.1 10.0 22.5 225.0 3.30 Batten Luminaire 40W 0.878 0.8037 1,200 183 50 5 10 0 151 Batten 0.528 3 4 0.86 0.92 0.878

page 17 of 18
PROJECT:
LIGHTING CALCULATION SHEET

Date: 3/6/2024
Design Key: Notes: Reflectance Factor:

Luminaire Maintenance Factor – LMF 0.94 1. Lamp Lumen Maintenance Factor – LLMF Ceiling 0.70 Standard Ceiling
As with conventional source lamps LED output will depreciate
Room condition Luminaire Cleaning Time Wall 0.50 Standard Wall
over time.
Clean 1 Year Clean 2. Luminaire Maintenance Factor – LMF Working Plane 0.30 Standard Floor
Room Surface Maintenance Factor - RMF 0.95 It indicate annual luminaires cleaning time
Room condition Luminaire Cleaning Time 3. Room Surface Maintenance Factor - RMF Light loss facto 0.80
Clean 1 Year Room Clean It indicate annual luminaires cleaning time & Type of Luminaire
Direct
Luminaire Type 4. Lamp Survival Factor - LSF
Luminaires
Lamp Survival Factor - LSF 1 It indicate failure factor of LED Lamp - Usually equal 1
Lamp Lumen Maintenance Factor - LLMF 0.9

Maintaince Factor - MF 0.8037

Linear Interpolation
Q'ty
Lamp Working LTG Q'ty E(lux) E(lux)
E Room Lighting Fixture type Mantainance Luminous Manua
No. Room height height Hm(m) X (m) Y (m) S (m2) U Factor Q'ty Put in LGT lay-out Manua Put in Code SHR x1 x2 y1 y2 y
(Lux) Index (Phillips Light Reference) Factor Flux l
(m) (m) Cal. Room l Room
Decide
21 GENERATOR ROOM Y 200 2.9 0.80 2.1 8.3 10.3 85.6 2.19 Batten Luminaire 40W 0.7828 0.8037 1,200 29 11 4 8 0 78 Batten 0.818 2 2.5 0.76 0.82 0.7828

22 BAR TACK Y 600 2.1 0.80 1.3 5.6 26.9 149.8 3.55 Batten Luminaire 40W 0.893 0.8037 1,200 131 32 5 27 0 147 Batten 0.823 3 4 0.86 0.92 0.893

23 IRON Y 500 2.1 0.80 1.3 7.7 26.9 205.9 4.59 Batten Luminaire 40W 0.9436 0.8037 1,200 142 34 6 24 0 120 Batten 0.926 4 5 0.92 0.96 0.9436