Chillgard® LE Photoacoustic Infrared

Refrigerant Monitor
[ The new wave of photoacoustic IR refrigerant leak detection monitors ]
The Chillgard LE Photoacoustic Infrared exposed to while in the mechanical equip- immunity to interferants com-
Refrigerant Monitor provides economical, ment room. Because of these factors, monly found in mechanical
low-level monitoring of refrigerant gases monitoring for refrigerant gases is now a equipment rooms such as clean-
used in most refrigeration systems necessity. Also, ANSI/ASHRAE 15-1994 now ing agents and solvents. There is
or chillers. requires mechanical equipment room leak also little effect due to changes
detectors. The Chillgard LE Monitor is per- in humidity, a common problem
Many chillers still use the older ozone-
fectly suited for installation in these with all other sensor technolo-
depleting refrigerants which are being
rooms. gies. Both are typical sources of
phased out by the Montreal Protocol, an
false alarms when other sensing
international agreement. These refrigerants Sensor Technology technologies are in use.
are in short supply, as their manufacture ter-
minated at the end of 1995. This has driven The Chillgard LE Monitor utilizes very sta-
ble and highly selective photoacoustic Features
up replacement costs, making it essential to
detect low ppm-level leaks. Without the abili- infrared (PIR) technology to sense refriger- • Three modes of operation:
ty to monitor down to low levels, leaking ant gases at levels as low as 20 parts-per- single-point diffusion,
refrigerant gases can go undetected for long million. single-point pumped, and
periods of time. The Chillgard LE Monitor can operate for four-point pumped
Replacement cost of refrigerants is expen- months with virtually no zero drift. Its • Complies with
sive. The Chillgard LE Monitor saves operat- inherent stability eliminates the require- ANSI/ASHRAE 15-1994
ing costs by detecting leaks early enough to ment of various auto-zeroing techniques
which take the monitor "off-line "at regu- • Features photoacoustic IR
prevent a major loss of refrigerant gas. In technology
addition, some replacement refrigerants lar intervals, leaving the area unprotected.
have a threshold-limit value (TLV) lower than Installation of a "fresh air "sampling line or • Easy to install, operate and
their predecessors. The TLV determines the "on-line "scrubber is not required with the maintain
amount of refrigerant gas a worker can be Chillgard LE Monitor. • Plug-in PIR sensor
The Chillgard LE Monitor has a high
• Detectability down to 20 ppm
• 4-20 mA output
• 80 Db horn
• Operates over a wide temperature
range
• Patent pending
• 2-line x 20-character LCD display which
shows alarm indications and actual gas
concentration
• Three alarm levels
• Relay outputs for each alarm level
• Password protection
Applications
Common refrigerant gases used in Typical multipoint installation.
Four sampling points surround the chiller for maximum protection.
industries can also be monitored. These
applications include:
configure the entire system. Chillgard LE Monitor can also be
• Mechanical equipment rooms The front panel displays all alarm and converted. A simple replacement
• Propellant-filling operations trouble messages. If a fault condition of the internal photoacoustic
• Solvent cleaning stations occurs, the message is clearly shown on infrared sensor is needed to
the display and it indicates the type of detect the new refrigerant.
• Cold storage and transport facilities fault.
• Meat packing plants Other Available Accessories:
The display also indicates the monitored Remote Display Module, Top-
• Supermarkets and refrigerant storage location and the corresponding gas
locations Mounted Alarm Strobe, 100 DB
concentration. Horn
• Water- and corrosion-resistant plastic
enclosure. Upgradeability
Expandability When your chiller is converted to one of
the newer refrigerants, your MSA
Simply by selecting the multipoint option,
the Chillgard LE Refrigerant Monitor can be
expanded to monitor up to 4 locations. The Specifications:
multipoint sequencer is mounted internally Single-point Diffusion Model
in the monitor. The results are: Operating Range: 0-1000 ppm
Minimum Detectability: 20 ppm
• Refrigerant gas monitoring is now Linearity: 0-100 ppm linear, 100-1000 ppm ±5% of reading
more cost effective, especially when Warm-up time: 10 minutes
monitoring large areas or multiple Response time: 50% of a step change in less than 90 seconds
locations or chillers Operating temperatures: 0 to 40˚ C (32 to 104˚ F)
• The fastest possible response to any Non-operating temperatures: -40 to 60˚ C (-40 to 140˚ F)
leak or spill is obtained Temperature effect: <4%/10˚ C
• Fresh sample is pumped from locations Relative humidity: 0 to 99%
up to 300 feet for each sample Operating Power Options: 24 VAC/DC, 110/220 VAC optional
Analog output: 4 to 20 mA
• Point location can be monitored on the Physical: 14.7” high x 11.2” wide x 5” deep
display or the 0-10V output Weight: 9.5 lbs.
Simplicity
The Chillgard LE Monitor is easy to install Ordering Information
and operate. Four (4) front-panel keys See the Chillgard LE Assemble-To-Order (ATO) form for ordering information.

Note: This Data Sheet contains only a Instrument Division:


general description of the product P.O. Box 427, Pittsburgh Offices and representatives worldwide
shown. While uses and performance PA 15230 U.S.A. For further information:
http://www.msanet.com
capabilities are described, under no
circumstances should the product be In U.S.:
used except by qualified, trained Phone: 1-800-MSA-INST
personnel, and not until the instructions, Fax: 1-724-776-3280
labels or other literature accompanying
the product have been carefully read and In Canada:
Phone: 1-800-MSA-INST
understood and the precautions therein Fax: 1-905-238-4151
set forth followed. Only they contain the
complete and detailed information In Mexico:
concerning this product. Phone: 52 (5) 5 76 64 44
Fax: 52 (5) 3 59 43 30
Data Sheet 07-0008
MSA International:
Jun 2002 (L ) Phone: 412-967-3228
© MSA 2002 Printed in U.S.A. Fax: 412-967-3373