Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

sh

Date : - 1 Sep. 2022

Date: - 03/06/2023
Pressure Test

The transformer radiator was tested for nitrogen leaks by pressurizing the radiator with dry
nitrogen through a pressure test fitting at a pressure of 2 PSIG. The radiator was pressurized
for two hours, then the radiator and fittings were checked for nitrogen leaks and Oil leaks
there were no leakage from radiator. And pressure test was found to be ok.

Transformer Details:-
Make: - CGL Capacity: - 2 MVA V/R: - 6.6/0.433 KV

Sr. NO:- 34454VFRadiator quantity: - 03 Nos