LGAI Technological Center, S.A.

(APPLUS)
Campus UAB - Ronda de la Font del Carme
s/n 08193 Bellaterra (Barcelona)
T +34 93 567 20 00
F +34 93 567 20 01
www.applus.com

CERTIFICATE
No. 0370-CPR-3312
No.
CERTIFICATE OF CONSTANCY OF PERFORMANCE
In compliance with Regulation 305/2011/EU of the European Parliament and of the Council of 9 March 2011 (the
Construction Products Regulation or CPR), this certificate applies to the construction product:

SMOKE AND HEAT CONTROL SYSTEMS.


 PART 7: SMOKE DUCT SECTIONS
MODEL: TD/RSX

Place on the market under the name of:

S.C. GLOBAL MAT INSTALL, S.R.L.


BUCHAREST, 8 MURGUTA STREET, BL. 11, AP. 18, 6th DISTRICT (ROMANIA)

And produced in the manufacturing plant:

JILAVA, 33A SOS. GIURGIULUI STREET, ILFOV COUNTY (ROMANIA)

This certificate attests that all provisions concerning the assessment and verification of constancy of performance
described in Annex ZA of the standard

EN 12101-7:2011

under system 1 are applied and that the product fulfils all the prescribed requirements set out above.

This certificate was first issued on 6th May 2019 and will remain valid as long as the test methods and/or factory
production control requirements included in the harmonised standard, used to assess the performance of the declared
characteristics, do not change, and the product, and the manufacturing conditions in the plant are not modified
significantly.

The monitoring assessment will be done before May 2020

Bellaterra, 6th May 2019

Xavier Ruiz Peña


Managing Director, Product Conformity B.U.

This document is not valid without its technical annex, whose number coincides with the number of certificate

Page 1 / 3
LGAI TECHNOLOGICAL CENTER, S.A. CIF: A-63207492
LGAI
LGAI Technological Center, S.A. (APPLUS)
Campus UAB s/n – Ronda de la Font del Carme, s/n
E - 08193 Bellaterra (Barcelona)
T +34 93 567 20 00
F +34 93 567 20 01
www.appluslaboratories.com Technical Annex Ed. 1
06/05/2019

TECHNICAL ANNEX 0370-CPR-3312

CERTIFICATE OF CONSTANCY OF PERFORMANCE

PRODUCT

 TD/RSX – Rectangular duct for smoke control.


 Galvanized steel sheet, single-compartment smoke extraction duct with 4 sides exposed.
 Rectangular range dimensions up to 1250x1000 mm and thickness 1 mm.
 Pittsburgh longitudinal joint.
 Longitudinal reinforcements: each section incorporates two stiffeners composed by a 16 mm pipe with reference
“RURA OC. 3/8”” by Alnor®, placed at mid of the section length, distanced 330 mm in between.
LGAI Technological Center, S.A. C.I.F A63207492

 Flanges with reference “P30 S” by Gebhardt|Stahl®, made of galvanized steel sheet of 0.8 mm thick, fixed to
the duct each 50 mm in distance by welding spots.
 Section are linked to each other by means of corner flanges with reference “Corner SL30/3” by Gebhardt|Stahl®,
nut and bolts M10x20 mm and clamps with reference “G-Clamp PLUS” by Gebhardt|Stahl® (six placed at each
long side of the duct section, distanced in 150 mm between them, and one placed at the middle of the short
side).
 Sealant reference used “FIRECRYL FR” by Soudal
 Hangers are made of M10 threaded rods with two M10 nuts. U steel profiles with dimension 21x41x2 mm are
placed at the end of these rods.
 Maximum distance between hangers: 1500 mm.
 Maximum distance between hangers and joints: 240 mm.
 Distance between lateral of duct and axis of hanger element: 50 mm
 Pressure level 3: -1500 Pa
 Classification:
E600 120 S (ho) 1500 single

Complete technical details of the certified product are available in the technical file and in the test reports 19/18394-57,
19/18394-57-1 and 19/18395-140.

Page 2 / 3
LGAI
LGAI Technological Center, S.A. (APPLUS)
Campus UAB s/n – Ronda de la Font del Carme, s/n
E - 08193 Bellaterra (Barcelona)
T +34 93 567 20 00
F +34 93 567 20 01
www.appluslaboratories.com Technical Annex Ed. 1
06/05/2019

TECHNICAL ANNEX 0370-CPR-3312

CERTIFICATE OF CONSTANCY OF PERFORMANCE

REQUIREMENTS
ESSENTIAL CHARACTERISTICS CLAUSES EUROPEAN MANDATED LEVELS OR CLASSES
STANDARD

Fire resistance. Multi-compartment 4.1.1. NA

Integrity a) NA
LGAI Technological Center, S.A. C.I.F A63207492

Insulation b) NA

Smoke leakage c) NA

Mechanical stability d) NA

Maintenance of cross-section (under E) e) NA

Fire resistance. Single compartment 4.1.2. E600 120 S (ho) 1500 single

Integrity a) E600 120 S (ho) 1500 single

Smoke leakage b) E600 120 S (ho) 1500 single

Mechanical stability c) E600 120 S (ho) 1500 single

Maintenance of cross-section (under E) d) E600 120 S (ho) 1500 single

PASS; NPD = No Performance Determined; NA = Not Applicable