GENERAL NOTES AND SPECIFICATIONS No.

CKT

CKT. VA
LOAD Description Voltage Ampere AT AF P WIRES AND CONDUITS
No. Connected
1. ALL ELECTRICAL WORK SHALL CONFORM TO THE LATEST EDITION OF THE PHILIPPINE 1 LIGHTINGS 1 555.00 230 2.41 15 20 2 2 - 3.5mm2 THHN / 20mmø PVC
ELECTRICAL CODE, TO THE RULES AND REGULATIONS OF LOCAL AND NATIONAL AUTHORITIES
2 LIGHTINGS 2 315.00 230 1.37 15 20 2 2 - 3.5mm2 THHN / 20mmø PVC
CONCERNED AND THE REQUIREMENTS OF LOCAL UTILITY COMPANIES.
3 LIGHTINGS 3 278.00 230 1.21 15 20 2 2 - 3.5mm2 THHN / 20mmø PVC
2. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL BE BRAND NEW AND OF APROVED 4 POWER LAYOUT 1 6.26 30 2 2 - 5.5mm2 THHN / 20mmø PVC
1440.00 230 40
TYPE FOR BOTH LOCATION AND PURPOSES.
5 POWER LAYOUT 2 1440.00 230 6.26 30 40 2 2 - 5.5mm2 THHN / 20mmø PVC
3. MINIMUM SIZE OF WIRE AND CONDUIT SHALL BE 3.5mm2 THHN AND 20mmø RESPECTIVELY 6 POWER LAYOUT 3 1260.00 230 5.48 30 40 2 2 - 5.5mm2 THHN / 20mmø PVC
UNLESS OTHERWISE SPECIFIED ON PLANS. 7 ACU 1, 2HP (BEDROOM 1) 1865.00 230 8.11 20 20 2 2 - 3.5mm2 THHN / 20mmø PVC
4. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: 8 ACU 2, 2HP (BEDROOM 2) 1865.00 230 8.11 20 20 2 2 - 3.5mm2 THHN / 20mmø PVC
A. LIGHT SWITCHES --------------- 1.40M ABOVE FLOOR FINISH 9 COMPRESSOR ( 21 HP) 466.25 230 2.03 15 20 2 2 - 3.5mm2 THHN / 20mmø PVC
B. RECEPTACLES ------------------- 0.30M ABOVE FLOOR FINISH
10 WATER PUMP (1 HP) 932.5 230 4.05 20 20 2 2 - 3.5mm2 THHN / 20mmø PVC
C. PANEL BOARD ------------------- 1.40M BOTTOM OF PANEL
11 EMERGENCY LIGHTS 406.25 230 1.77 15 20 2 2 - 3.5mm2 THHN / 20mmø PVC
5. THE JOB SHALL BE EXECUTED IN THE MOST THROUGH PROMPT AND WORKMAN LIKE 4.35 20 2 2 - 3.5mm2 THHN / 20mmø PVC
12 SPARE 1000.00 230 20
MANNER, EMPLOYING STANDARDS TOOLS, EQUIPMENT, METHODS AND GOOD ENGINEERING
PRACTICES. THE JOB SHALL BE DONE COMPLETE IN ALL ASPECTS AS REQUIRED IN PLANS AND
SPECIFICATIONS AND READY FOR OPERATION. TOTAL: 11823.00 45.15

6. NO REVISION IN THE DESIGN SHALL BE DONE WITHOUT THE PRIOR KNOWLEDGE AND COMPUTATION: USE:
APPROVAL OF THE DESIGNER AND THE OWNER. ANY SUCH REVISION DONE WITHOUT THE @80% DEMAND FACTOR 2 - 22 mm2 THHN / 25mmø IMC
230V, 60Hz, 85A MAIN CB AT 100AF
APPROVAL SHALL CAUSE RESPONSIBILITY OF THE DESIGNER TO CEASED AS A WHOLE.
IFEEDER= 45.15 x 0.80 x 1.25 = 45.15A (FLUSH MOUNTED PANEL 12 BRANCHES NEMA 3R)
7. THERE SHALL BE ONLY ONE SERVICE DROP TO THE PROPOSED BUILDING , SECONDARY ICB= 45.15 + 2.03(2.5) = 50.225A
SERVICE ENTRANCE SHALL BE 230V, SINGLE PHASE, AC.
8. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY
LICENSED ELECTRICAL ENGINEER OR REGISTERED MASTER ELECTRICIAN.
PANEL BOARD SCHEDULE
1 SCHEDULE OF LOADS
SCALE LETTER 1:100
LOCAL POWER SUPPLY
1ø, 230V, 60Hz, AC 2 - 22 mm2 THHN / 25mmø IMC
E-1
MDP

SERVICE kW-Hr METER


CONCRETE PEDESTAL 15 AT 15 AT
1 2
15 AT 30 AT
3 4
ECB, 1ø, 85AT, 230V, 60Hz 30 AT 30 AT
IN NEMA 3R 5 6
20 AT 20 AT
7 8
RED TAGGING

RED TAGGING
20 AT 20 AT
9 10
20 AT 20 AT
11 12

GROUND TERMINAL
# 14MM2 INSULATED WHITE COOLER

RISER DIAGRAM 16MM DIA. X 2400MM


COPPERWELD

Designed by: Project Title: Owner: In-charge of Design: In-charge of Installation: Sheet Contents: Page Number:

SCHEDULE OF LOADS
RISER DIAGRAM
Proposed One-Storey Roxanne Evangelio Vincent Tarcena Vincent Tarcena 1
PANEL BOARD SCHEDULE
Residential Bldg.
GENERAL NOTES AND
SPECIFICATION E-1
v-plus electrical PRC NO: TIN: PRC NO: TIN:
PTR NO: DATE: PTR NO: DATE:
services inc. Location: Panique, Odiongan, Romblon PLACE: PLACE: