Indra: Piping Line List Unit 45

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

DOCUMENT NO.

REV

ARS-P-LI-45-001 1A
Contract No. 3510005187 SHEET 1 OF 10

PIPING LINE LIST UNIT 45


FIRE FIGHTING SYSTEM AND FIRE SYSTEM

BLOCK-A GAS DEVELOPMENT PROJECT

APPROVED FOR CONSTRUCTION

Class 1 X Class 2 Class 3

CONTRACTOR COMPANY
REV DATE PAGE DESCRIPTION
PREP'D CHK'D APP'D APP'D

1A 24-AUG-17 ALL APPROVED FOR CONSTRUCTION W. SUTRISNO W. ABHINIMPUNO B. WIRATMAN

1 16-DEC-16 ALL APPROVED FOR CONSTRUCTION W. SUTRISNO W. ABHINIMPUNO B. WIRATMAN

0 17-JUN-16 ALL ISSUED FOR CONSTRUCTION W. SUTRISNO W. ABHINIMPUNO B. WIRATMAN

A 18-FEB-16 ALL ISSUED FOR REVIEW W. SUTRISNO W. ABHINIMPUNO B. WIRATMAN

JOB CODE: CONTRACTOR ID :

0-0709-00-0000 S-045-1360-001

D R A
IN4-AUG 17
2
- 2 0
Block‐A Gas Development Project Doc No.: ARS‐P‐LI‐45‐001
PIPING LINE LIST UNIT 45 <Rev. 1A>
SHEET 1 OF 1

RECORD OF REVISION
The revisions listed below have been incorporated in this copy of the document
REV. PAGE
SECTION DESCRIPTION OF CHANGES
NO. NO.
1A General 4-10 Update data as per-P&ID rev. 1A and TQ No. : JES-MES-EMT-002

D R A
IN4-AUG 17
2
- 2 0 CONTRACTOR ID: S‐045‐1360‐001 <Rev. 1A>
Block-A Development Project Doc No.: ARS-P-LI-45-001
PIPING LINE LIST UNIT 45 <Rev. 1A>
SHEET 3 OF 10

TABLE OF CONTENTS

1. Line Index 4

D R A
IN4-AUG 17
2
- 2 0
Contractor ID : S-045-1360-001 <Rev. 1A>
Block-A Gas Development Project Doc No. : ARS-P-LI-45-001
LINE LIST UNIT 45 <Rev. 1A>
SHEET 4 of 10

Block-A Project Line List NOTE

1. "X" in Rev No. column indicates lines which have been deleted.
2. This line list is based on latest revision of P&ID
3. Test Fluid is indicated as follows; "H": Hydrostatic Test, "P": Pneumatic Test, "V": Visual Test, "S": Service Test.
Line Number Insulation Terminal Points Operating Conditions (1) Operating Conditions (2) Max Design Conditions Vacuum Test NDE
Operating Heat Hardness
(NOTE1) Fluid Density Max Min Design PWHT Req. Paint System
Unit Line Fluid Seq Line Thk Phase Press Temp / AMB Press Temp / AMB Temp. Press Press Trace Temp Press RT PT Test P&ID No. Remarks
Hold Type From To Name (lb/ft3) Temp Temp Temp Fluid (Y/N) No.
Code Size Code No Class (Inch) (psig) (degF) (psig) (degF) for Paint (psig) (psig) (degC) (psig) (%) (%) (%)
Rev No. (degF) (degF) (degF)
(degF)

1A 44 3" UW 44007 1B - - UW-44067 45-ABM-401 Utility Water L 62.31 70 AMB - - AMB 120 140 70 - - - S 70 5 5 - N 1 ARS-F-PI-45-001

1 45 1" CH 45001 1B - - 45-PAT-331A/B UW-44007 Chemicals L 67.422 80 AMB - - AMB 130 140 70 - - - H 195 100 100 - N 1 ARS-F-PI-45-001

1 45 20" FW 45001 1B - - 45-ABM-401 Fire Water Pump Fire Water L 62.31 18.5 AMB - - AMB 50 140 70 - - - H 75 5 5 - N 1 ARS-F-PI-45-001

X 45 16" FW 45001 1B - - 45-ABM-401 Fire Water Pump Fire Water L 62.31 18.5 AMB - - AMB 50 140 70 - - - H 200 5 5 - N 1 ARS-F-PI-45-001 Deleted

0 45 4" FW 45020 1B - - 45-ABM-401 Open Ditch Fire Water L 62.31 ATM AMB - - AMB ATM 140 70 - - - V - 5 5 - N 1 ARS-F-PI-45-001

1 45 3" FW 45001 1B - - 45-ABM-401 Fire Water Pump Fire Water L 62.31 18.5 AMB - - AMB 50 140 70 - - - H 75 5 5 - N 1 ARS-F-PI-45-001

0 45 3" FW 45003 1B - - FW-45001 45-PBE-332 Fire Water L 62.31 18.5 AMB - - AMB 50 140 70 - - - H 75 5 5 - N 1 ARS-F-PI-45-001

0 45 3" FW 45001 1B - - FW-45001 FW-45003 Fire Water L 62.31 18.5 AMB - - AMB 50 140 70 - - - H 75 5 5 - N 1 ARS-F-PI-45-001

A 45 2" FW 45004 1B - - 45-PBE-332 FW-45006 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-001

A 45 2" FW 45005 1B - - FW-45004 FW-45007 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-001

A 45 14" FW 45006 1B - - FW-45004 FW-45041 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-001

0 45 2" FW 45006 1B - - FW-45004 FW-45006 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-001

A 45 12" FW 45007 1B - - FW-45006 45-ABM-401 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-001

A 45 2" FW 45007 1B - - FW-45005 FW-45007 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-001

0 45 6" FW 45007 1B - - FW-45007 FW-45007 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-001

0 45 8" FW 45007 1B - - FW-45007 FW-45007 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-001

0 45 12" FW 45006 1B - - FW-45009 FW-45006 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-002

0 45 12" FW 45006 1B - - FW-45015 FW-45006 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-002

1 45 16" FW 45008 1B - - FW-45001 45-PBE-331A Fire Water L 62.31 18.5 AMB - - AMB 50 140 70 - - - H 75 5 5 - N 1 ARS-F-PI-45-002

A 45 12" FW 45009 1B - - 45-PBE-331A FW-45006 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-002

A 45 2" FW 45013 1B - - 45-PBE-331A Open Ditch Fire Water L 62.31 ATM AMB - - AMB ATM 140 70 - - - V - 5 5 - N 1 ARS-F-PI-45-002

1A 45 1/2" FW 45023 1X - - FW-45009 FW-45010 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-002

1A 45 1/2" FW 45010 1B - - FW-45023 Open Ditch Fire Water L 62.31 ATM AMB - - AMB ATM 140 70 - - - V - 5 5 - N 1 ARS-F-PI-45-002

A 45 8" FW 45009 1B - - FW-45009 PSV-331A Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-002

D R A
N
I 24-AU 17
G - 2 0
Contractor ID : S-045-1360-001 <Rev. 1A>
Block-A Gas Development Project Doc No. : ARS-P-LI-45-001
LINE LIST UNIT 45 <Rev. 1A>
SHEET 5 of 10

Block-A Project Line List NOTE

1. "X" in Rev No. column indicates lines which have been deleted.
2. This line list is based on latest revision of P&ID
3. Test Fluid is indicated as follows; "H": Hydrostatic Test, "P": Pneumatic Test, "V": Visual Test, "S": Service Test.
Line Number Insulation Terminal Points Operating Conditions (1) Operating Conditions (2) Max Design Conditions Vacuum Test NDE
Operating Heat Hardness
(NOTE1) Fluid Density Max Min Design PWHT Req. Paint System
Unit Line Fluid Seq Line Thk Phase Press Temp / AMB Press Temp / AMB Temp. Press Press Trace Temp Press RT PT Test P&ID No. Remarks
Hold Type From To Name (lb/ft3) Temp Temp Temp Fluid (Y/N) No.
Code Size Code No Class (Inch) (psig) (degF) (psig) (degF) for Paint (psig) (psig) (degC) (psig) (%) (%) (%)
Rev No. (degF) (degF) (degF)
(degF)

1A 45 12" FW 45012 1B - - PSV-331A Open Ditch Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - V - 5 5 - N 1 ARS-F-PI-45-002

1 45 8" VN 45001 1B IH 65 45-PBE-331A ATM Flue Gas V 0.07 ATM 120 - - 12 ATM 170 70 - - - V - 5 5 - N 4 ARS-F-PI-45-002

1 43 2" DF 43009 1B - - 43-PBE-331 45-ABM-402A/B Diesel Fuel L 53 24 AMB - - AMB 50 140 70 - - - H 75 5 5 - N 1 ARS-F-PI-45-002

1 45 3/4" DF 45002 1B - - 45-ABM-402A 45-PBE-331A Diesel Fuel L 53 ATM AMB - - AMB 220 140 70 FV 150 - H 330 5 5 - N 1 ARS-F-PI-45-002

1 45 3/4" DF 45001 1B - - 45-PBE-331A 45-ABM-402A Diesel Fuel L 53 ATM AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-002

1 45 16" FW 45014 1B - - FW-45001 45-PBE-331B Fire Water L 62.31 18.5 AMB - - AMB 50 140 70 - - - H 75 5 5 - N 1 ARS-F-PI-45-002

A 45 12" FW 45015 1B - - 45-PBE-331B FW-45006 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-002

X 45 14" FW 45041 1Z - - FW-45006 RING MAIN Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 - - - N - ARS-F-PI-45-002 Deleted

A 45 8" FW 45015 1B - - FW-45015 45-PSV-331B Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-002

1A 45 12" FW 45018 1B - - 45-PSV-331B OPEN DITCH Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - V - 5 5 - N 1 ARS-F-PI-45-002

1A 45 1/2" FW 45021 1X - - FW-45015 FW-45039 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-002

1A 45 1/2" FW 45039 1B - - FW-45021 OPEN DITCH Fire Water L 62.31 ATM AMB - - AMB ATM 140 70 - - - V - 5 5 - N 1 ARS-F-PI-45-002

A 45 2" FW 45019 1B - - 45-PBE-331B OPEN DITCH Fire Water L 62.31 ATM AMB - - AMB ATM 140 70 - - - V - 5 5 - N 1 ARS-F-PI-45-002

1 45 8" VN 45002 1B IH 65 45-PBE-331B ATM Flue Gas V 0.07 ATM 120 - - 12 ATM 170 70 - - - V - 5 5 - N 4 ARS-F-PI-45-002

1 45 3/4" DF 45003 1B - - 45-PBE-331B 45-ABM-402B Diesel Fuel L 53 ATM AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-002

1 45 3/4" DF 45004 1B - - 45-ABM-402B 45-PBE-331B Diesel Fuel L 53 ATM AMB - - AMB 220 140 70 FV 150 - H 330 5 5 - N 1 ARS-F-PI-45-002

1A 45 2" DF 45017 1B - - 45-ABM-402A OPEN DITCH Diesel Fuel L 53 ATM AMB - - AMB ATM 140 70 - - - V - 5 5 - N 1 ARS-F-PI-45-002

1A 45 2" DF 45040 1B - - 45-ABM-402B OPEN DITCH Diesel Fuel Fire Water 53 ATM AMB - - AMB ATM 140 70 - - - V - 5 5 - N 1 ARS-F-PI-45-002

1 45 2" FW 45128 1B - - 45-PBE-331A OPEN DITCH Fire Water Fire Water 62.31 ATM AMB - - AMB ATM 140 70 - - - V - 5 5 - N 1 ARS-F-PI-45-002

1 45 2" FW 45129 1B - - 45-PBE-331B OPEN DITCH Fire Water Fire Water 62.31 ATM AMB - - AMB ATM 140 70 - - - V - 5 5 - N 1 ARS-F-PI-45-002

1A 45 12" FW 45062 1Z - - FW-45025 OFFSITE AREA Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 - - - N - ARS-F-PI-45-003

0 45 14" FW 45025 1Z - - FW-45041 FW-45062 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 - - - N - ARS-F-PI-45-003

0 45 14" FW 45028 1Z - - RING MAIN FW-45025 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 - - - N - ARS-F-PI-45-003

0 45 14" FW 45027 1Z - - RING MAIN FW-45025 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 - - - N - ARS-F-PI-45-003

0 45 14" FW 45026 1Z - - RING MAIN RING MAIN Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 - - - N - ARS-F-PI-45-003

D R A
N
I 24-AU 17
G - 2 0
Contractor ID : S-045-1360-001 <Rev. 1A>
Block-A Gas Development Project Doc No. : ARS-P-LI-45-001
LINE LIST UNIT 45 <Rev. 1A>
SHEET 6 of 10

Block-A Project Line List NOTE

1. "X" in Rev No. column indicates lines which have been deleted.
2. This line list is based on latest revision of P&ID
3. Test Fluid is indicated as follows; "H": Hydrostatic Test, "P": Pneumatic Test, "V": Visual Test, "S": Service Test.
Line Number Insulation Terminal Points Operating Conditions (1) Operating Conditions (2) Max Design Conditions Vacuum Test NDE
Operating Heat Hardness
(NOTE1) Fluid Density Max Min Design PWHT Req. Paint System
Unit Line Fluid Seq Line Thk Phase Press Temp / AMB Press Temp / AMB Temp. Press Press Trace Temp Press RT PT Test P&ID No. Remarks
Hold Type From To Name (lb/ft3) Temp Temp Temp Fluid (Y/N) No.
Code Size Code No Class (Inch) (psig) (degF) (psig) (degF) for Paint (psig) (psig) (degC) (psig) (%) (%) (%)
Rev No. (degF) (degF) (degF)
(degF)

0 45 14" FW 45029 1Z - - RING MAIN RING MAIN Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 - - - N - ARS-F-PI-45-003

0 45 14" FW 45030 1Z - - RING MAIN RING MAIN Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 - - - N - ARS-F-PI-45-003

0 45 10" FW 45123 1Z - - RING MAIN FW-45031 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 - - - N - ARS-F-PI-45-003

1A 45 8" FW 45031 1B - - FW-45123 045-HYD-1412 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

1A 45 12" FW 45055 1Z - - RING MAIN OFFSITE AREA Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 - - - N - ARS-F-PI-45-003

1 45 10" FW 45122 1Z - - RING MAIN FW-45122 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 - - - N - ARS-F-PI-45-003

1A 45 8" FW 45086 1B - - FW-45122 045-HYD-1427 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

TRUCK LOADING
0 45 6" FW 45030 1B - - FW-45030 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003
AREA

TRUCK LOADING
0 45 6" FW 45072 1B - - FW-45029 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003
AREA

0 45 6" FW 45075 1B - - FW-45025 045-HYD-1401 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 3" FW 45076 1B - - FW-45025 045-FHR-1501 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45077 1B - - FW-45025 045-HYD-1402 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45078 1B - - FW-45025 045-HYD-1403 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45079 1B - - FW-45029 045-HYD-1404 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45090 1B - - FW-45029 045-FWM-1102 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45081 1B - - FW-45029 045-FWM-1111 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45080 1B - - FW-45029 045-HYD-1410 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

1A 45 3" FW 45133 1B - - FW-45029 PROPANE TANK Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 3" FW 45073 1B - - FW-45029 PROPANE TANK Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45082 1B - - FW-45029 045-HYD-1405 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45083 1B - - FW-45029 045-HYD-1406 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45084 1B - - FW-45029 045-HYD-1407 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

1 45 12" FW 45074 1B - - FW-45029 45-ABM-403 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

1A 45 12" FW 45132 1B - - FW-45029 45-ABM-403 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45085 1B - - FW-45029 045-HYD-1408 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

D R A
N
I 24-AU 17
G - 2 0
Contractor ID : S-045-1360-001 <Rev. 1A>
Block-A Gas Development Project Doc No. : ARS-P-LI-45-001
LINE LIST UNIT 45 <Rev. 1A>
SHEET 7 of 10

Block-A Project Line List NOTE

1. "X" in Rev No. column indicates lines which have been deleted.
2. This line list is based on latest revision of P&ID
3. Test Fluid is indicated as follows; "H": Hydrostatic Test, "P": Pneumatic Test, "V": Visual Test, "S": Service Test.
Line Number Insulation Terminal Points Operating Conditions (1) Operating Conditions (2) Max Design Conditions Vacuum Test NDE
Operating Heat Hardness
(NOTE1) Fluid Density Max Min Design PWHT Req. Paint System
Unit Line Fluid Seq Line Thk Phase Press Temp / AMB Press Temp / AMB Temp. Press Press Trace Temp Press RT PT Test P&ID No. Remarks
Hold Type From To Name (lb/ft3) Temp Temp Temp Fluid (Y/N) No.
Code Size Code No Class (Inch) (psig) (degF) (psig) (degF) for Paint (psig) (psig) (degC) (psig) (%) (%) (%)
Rev No. (degF) (degF) (degF)
(degF)

0 45 6" FW 45093 1B - - FW-45029 045-FWM-1104 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45087 1B - - FW-45029 045-HYD-1409 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45088 1B - - FW-45030 045-HYD-1411 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45089 1B - - FW-45030 045-FWM-1101 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45091 1B - - FW-45025 045-HYD-1413 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45092 1B - - FW-45025 045-FWM-1103 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45094 1B - - FW-45025 045-HYD-1414 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45095 1B - - FW-45025 045-FWM-1105 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45096 1B - - FW-45025 045-FWM-1106 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45097 1B - - FW-45025 045-HYD-1415 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45098 1B - - FW-45025 045-FWM-1107 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45099 1B - - FW-45025 045-HYD-1416 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45100 1B - - FW-45025 045-HYD-1417 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

HAZARDOUS
1 45 3" FW 45067 1B - - FW-45028 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003
WASTE STORAGE

FLAMMABLE &
0 45 6" FW 45069 1B - - FW-45028 NON FLAMMABLE Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003
LUBE OIL STORAGE

0 45 6" FW 45101 1B - - FW-45028 045-HYD-1418 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45107 1B - - FW-45026 045-HYD-1419 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45108 1B - - FW-45026 045-FWM-1108 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45109 1B - - FW-45026 045-HYD-1420 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45110 1B - - FW-45026 045-FWM-1109 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 3" FW 45111 1B - - FW-45026 045-FHR-1502 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45112 1B - - FW-45026 045-FWM-1110 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

DEW POINT
0 45 8" FW 45071 1B - - FW-45026 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003
CONTROL SKID

0 45 6" FW 45115 1B - - FW-45026 045-HYD-1421 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

DEW POINT
1A 45 8" FW 45131 1B - - FW-45026 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003
CONTROL SKID

D R A
N
I 24-AU 17
G - 2 0
Contractor ID : S-045-1360-001 <Rev. 1A>
Block-A Gas Development Project Doc No. : ARS-P-LI-45-001
LINE LIST UNIT 45 <Rev. 1A>
SHEET 8 of 10

Block-A Project Line List NOTE

1. "X" in Rev No. column indicates lines which have been deleted.
2. This line list is based on latest revision of P&ID
3. Test Fluid is indicated as follows; "H": Hydrostatic Test, "P": Pneumatic Test, "V": Visual Test, "S": Service Test.
Line Number Insulation Terminal Points Operating Conditions (1) Operating Conditions (2) Max Design Conditions Vacuum Test NDE
Operating Heat Hardness
(NOTE1) Fluid Density Max Min Design PWHT Req. Paint System
Unit Line Fluid Seq Line Thk Phase Press Temp / AMB Press Temp / AMB Temp. Press Press Trace Temp Press RT PT Test P&ID No. Remarks
Hold Type From To Name (lb/ft3) Temp Temp Temp Fluid (Y/N) No.
Code Size Code No Class (Inch) (psig) (degF) (psig) (degF) for Paint (psig) (psig) (degC) (psig) (%) (%) (%)
Rev No. (degF) (degF) (degF)
(degF)

0 45 3" FW 45113 1B - - FW-45026 045-FHR-1503 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45116 1B - - FW-45026 045-FWM-1112 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45117 1B - - FW-45026 045-FWM-113 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45119 1B - - FW-45026 045-FWM-1115 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 3" FW 45118 1B - - FW-45026 045-FHR-1504 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45121 1B - - FW-45026 045-HYD-1422 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45102 1B - - FW-45027 045-HYD-1423 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

WORKSHOP &
0 45 6" FW 45070 1B - - FW-45027 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003
WAREHOUSE

0 45 6" FW 45103 1B - - FW-45025 045-HYD-1424 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45104 1B - - FW-45025 045-FWM-1114 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45105 1B - - FW-45025 045-HYD-1425 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

0 45 6" FW 45106 1B - - FW-45025 045-HYD-1426 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003

FLUSHING
X 45 10" FW 45029 1B - - FW-45029 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003 Deleted
CONNECTION

FUTURE
X 45 12" FW 45025 1B - - FW-45025 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003 Deleted
CONNECTION

FUTURE
X 45 12" FW 45026 1B - - FW-45026 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-003 Deleted
CONNECTION

0 45 14" FW 45074 1B - - RING MAIN 45-ABM-403 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-004

X 45 14" FW 45029 1B - - RING MAIN 45-ABM-403 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-004 Deleted

X 45 12" FW 45016 1B - - RING MAIN 45-ABM-403 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-004 Deleted

FW-
1A 45 10" FW 45016 1B - - FW-45132 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-004
45036,45037,45038

0 45 3" FW 45034 1A - - 45-ABM-403 37-ABJ-401B Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-004

0 45 3" FW 45035 1A - - 45-ABM-403 37-ABJ-401A Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-004

0 45 6" FW 45057 1A - - 45-ABM-403 37-ABJ-402C Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-004

0 45 10" FW 45036 1A - - 45-ABM-403 45-FFM-1202 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-004

0 45 10" FW 45037 1A - - 45-ABM-403 45-FFM-1203 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-004

0 45 10" FW 45038 1A - - 45-ABM-403 45-FFM-1201 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-004

D R A
N
I 24-AU 17
G - 2 0
Contractor ID : S-045-1360-001 <Rev. 1A>
Block-A Gas Development Project Doc No. : ARS-P-LI-45-001
LINE LIST UNIT 45 <Rev. 1A>
SHEET 9 of 10

Block-A Project Line List NOTE

1. "X" in Rev No. column indicates lines which have been deleted.
2. This line list is based on latest revision of P&ID
3. Test Fluid is indicated as follows; "H": Hydrostatic Test, "P": Pneumatic Test, "V": Visual Test, "S": Service Test.
Line Number Insulation Terminal Points Operating Conditions (1) Operating Conditions (2) Max Design Conditions Vacuum Test NDE
Operating Heat Hardness
(NOTE1) Fluid Density Max Min Design PWHT Req. Paint System
Unit Line Fluid Seq Line Thk Phase Press Temp / AMB Press Temp / AMB Temp. Press Press Trace Temp Press RT PT Test P&ID No. Remarks
Hold Type From To Name (lb/ft3) Temp Temp Temp Fluid (Y/N) No.
Code Size Code No Class (Inch) (psig) (degF) (psig) (degF) for Paint (psig) (psig) (degC) (psig) (%) (%) (%)
Rev No. (degF) (degF) (degF)
(degF)

1A 45 10" FW 45058 1A - - 45-ABM-403 37-ABJ-402C DIKE Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-004

X 45 10" FW 45058 1A - - FW-45058 37-ABJ-402C DIKE Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-004 Deleted

1A 45 6" FW 45059 1A - - FW-45058 37-ABJ-402C DIKE Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-004

X 45 6" FW 45016 1A - - FW-45016 FW-45036 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-004 Deleted

X 45 6" FW 45032 1A - - FW-45016 FW-45038 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-004 Deleted

X 45 6" FW 45033 1A - - FW-45016 FW-45037 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-004 Deleted

X 45 8" FW 45026 1B - - RING MAIN 45-DV-301 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-005 Deleted

0 45 8" FW 45071 1B - - RING MAIN FW-45011 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-005

DP CONTROL
A 45 8" FW 45011 1A - - FW-45026 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-005
WATER SPRAY

1 45 8" FW 45011 1Z - - FW-45011 FW-45011 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 - - - N - ARS-F-PI-45-005

DP CONTROL
0 45 3" FW 45022 1A - - FW-45011 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-005
WATER SPRAY

DP CONTROL
0 45 3" FW 45065 1A - - FW-45011 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-005
WATER SPRAY

DP CONTROL
0 45 3" FW 45066 1A - - FW-45011 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-005
WATER SPRAY

DP CONTROL
0 45 3" FW 45064 1A - - FW-45011 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-005
WATER SPRAY

DP CONTROL
0 45 6" FW 45063 1A - - FW-45011 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-005
WATER SPRAY

REFRIGERATION
X 45 4" FW 45042 1A - - FW-45022 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-005 Deleted
VESSEL SKID

REFRIGERATION
X 45 4" FW 45024 1A - - FW-45022 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-005 Deleted
VESSEL SKID

REFRIGERATION
X 45 4" FW 45022 1A - - FW-45022 COMPRESSOR SKID Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-005 Deleted
A/B

0 45 6" FW 45030 1B - - RING MAIN 45-DV-302 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-008

0 45 6" FW 45072 1B - - RING MAIN FW-45056 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-008

0 45 6" FW 45056 1A - - FW-45030 45-ABM-404 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008

0 45 6" FW 45043 1A - - 45-ABM-404 FW-40544 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008

Truck Loading Foam


1 45 4" FW 45044 1A - - FW-45043 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008
Water Spray System

Truck Loading Foam


1 45 2" FW 45045 1A - - FW-45044 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008
Water Spray System

Truck Loading Foam


1 45 2" FW 45046 1A - - FW-45044 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008
Water Spray System

D R A
N
I 24-AU 17
G - 2 0
Contractor ID : S-045-1360-001 <Rev. 1A>
Block-A Gas Development Project Doc No. : ARS-P-LI-45-001
LINE LIST UNIT 45 <Rev. 1A>
SHEET 10 of 10

Block-A Project Line List NOTE

1. "X" in Rev No. column indicates lines which have been deleted.
2. This line list is based on latest revision of P&ID
3. Test Fluid is indicated as follows; "H": Hydrostatic Test, "P": Pneumatic Test, "V": Visual Test, "S": Service Test.
Line Number Insulation Terminal Points Operating Conditions (1) Operating Conditions (2) Max Design Conditions Vacuum Test NDE
Operating Heat Hardness
(NOTE1) Fluid Density Max Min Design PWHT Req. Paint System
Unit Line Fluid Seq Line Thk Phase Press Temp / AMB Press Temp / AMB Temp. Press Press Trace Temp Press RT PT Test P&ID No. Remarks
Hold Type From To Name (lb/ft3) Temp Temp Temp Fluid (Y/N) No.
Code Size Code No Class (Inch) (psig) (degF) (psig) (degF) for Paint (psig) (psig) (degC) (psig) (%) (%) (%)
Rev No. (degF) (degF) (degF)
(degF)

Truck Loading Foam


1 45 2" FW 45047 1A - - FW-45044 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008
Water Spray System

Truck Loading Foam


1 45 2" FW 45048 1A - - FW-45044 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008
Water Spray System

Truck Loading Foam


1 45 2" FW 45049 1A - - FW-45044 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008
Water Spray System

Truck Loading Foam


1 45 2" FW 45050 1A - - FW-45044 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008
Water Spray System

Truck Loading Foam


1 45 2" FW 45051 1A - - FW-45044 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008
Water Spray System

Truck Loading Foam


1 45 2" FW 45052 1A - - FW-45044 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008
Water Spray System

Truck Loading Foam


1 45 2" FW 45053 1A - - FW-45044 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008
Water Spray System

Truck Loading Foam


1 45 2" FW 45054 1A - - FW-45044 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008
Water Spray System

Truck Loading Foam


1 45 4" FW 45130 1A - - FW-450443 Foam L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-008
Water Spray System

X 45 3" FW 45029 1B - - RING MAIN 45-DV-303 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-007 Deleted

0 45 3" FW 45073 1B - - RING MAIN FW-45060 Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N 1 ARS-F-PI-45-007

Propane Tank
0 45 3" FW 45060 1A - - 45-DV-303 Firewater Spray Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-007
System

Propane Tank
0 45 1-1/2" FW 45061 1A - - FW-45060 Firewater Spray Fire Water L 62.31 163 AMB - - AMB 220 140 70 - - - H 330 5 5 - N - ARS-F-PI-45-007
System

1A 45 - FW 45002 1B - - TRIM 45-ABM-401 Fire Water L 62.31 18.5 AMB - - 50 140 70 - - - - H 210 5 5 - N 1 ARS-R-PI-45-001

1A 45 1/2" DA 45001 1B - - 45-PBE-332 Open Drain Atmospheric Drain L 62.31 163 AMB - - AMB 220 140 70 - - - V - 5 5 - N 1 BLA-R-ST-00-024

D R A
N
I 24-AU 17
G - 2 0
Contractor ID : S-045-1360-001 <Rev. 1A>