LECC Room DB schedule

Project / Building name LECC room


Address / location PDO Mai office
Distribution Board no DB-SA-01 Incoming cable size/type 4C x 16 Sqmm Cu/XLPE/SWA/PVC + 1C x 16 Sqmm Cu/PVC earth
Fed From SMDB Panel ( Clinic DG) Main Breaker type & rating 63A Isolator + 1x63A ELCB 100mA
CCT CLR Phase & Circuit load
RCD/MCB
Incomer CCT Ref. No. CODE Neutral Size Earth Size No. of Connected Load Circuit Load (W) after diversity
rating(A)
Sqmm Sqmm Circuit name/ Point refernce points per point R Y B (kW)

1 R1 20 4 4 Power outlets ( Floor Box) 1 3x400 1200 960

2 Y1 32 4 4 Power outlets ( Floor Box) 1 1x2000 1200 960

3 B1 20 4 4 Power outlets 1 5x400 2000 1600


63A TPN Isolaor + 63A ELCB 100mA

4 R2 20 4 4 Power outlets 1 5x400 2000 1600

5 Y2 32 4 4 Power outlets 1 4x400 1600 1280

6 B2 32 4 4 Power outlets 1 5x400 2000 1600

7 R3 16 2.5 2.5 600x600 Led Light fittings 1 8x36 288 230.4

8 Y3 16 2.5 2.5 15 W Led downlight 1 10x15 150 120

9 B3 10 2.5 2.5 Spare 7 10x4.5 45 36

10 R4 20 4 4 Power Outlet ( Digital clock) 1 1x50 50 40

11 Y4 20 4 4 1.5 TR Split AC 1 1x2000 1600


2000

12 B4 20 4 4 1.5 TR Split AC 1 1x2000 2000 1600

Total Connected Load (kW) = 14.53 3538 4950 6045 11626.4


Diversified load ( kW) = 11.63