Professional Documents
Culture Documents
RM-DCM-2 Quick Start Installation Guide - World Class Security ...
RM-DCM-2 Quick Start Installation Guide - World Class Security ...
Quick Start
Installation Guide
Version E0
Document Part Number UM-215
June 2007
OVERVIEW The RM-DCM-2 is a UL294 Listed door control module that includes the
RM-4E Reader Module (RM-4E) and enclosure. The RM-DCM-2 is
designed to support up to two RM-4E modules, providing a single
enclosure for doors with IN and OUT readers.
The enclosure also has space for up to three I/8 and/or R/8 boards, for a
total of four boards. The RM-DCM-2 supports an optional battery (12
VDC, 4A), which will be recharged by the RM-4E battery charging circuit.
The I/8 module provides eight supervised inputs and the R/8 module
provides eight dry contact, Form C relay outputs.
NOTE For information about the RM-4E, I/8, or R/8 modules, refer to the Quick
Start guides listed in Table 13.
1
Overview
2
RM-DCM-2 Unit
RM-DCM-2 UNIT Figure 1 shows the RM-DCM-2 unit with one RM-4E board, an optional
battery, and LCD.
LCD
Battery
RM-4E
NOTE The on-board battery is for memory retention only. UL has not evaluated
the battery for the Standby Power requirements of the UL294 Standard.
3
Features
Optional Equipment
RM-DCM-2 with RM-4E, The RM-4E Reader Module (RM-4E) simplifies installation by providing
I/8, R/8, and Battery clearly labeled termination points to identify functionality and device
information. The RM-4E also features LEDs for output, RS-485, power,
and input status to make it easier to install and service the system.
The RM-4E board is installed and mounted at the top of the door.
Another RM-4E board and any combination of I/8 and R/8 modules, up
to a total of four boards, can be mounted on the door and within the
enclosure.
Figure 2 shows an RM-DCM-2 unit with one RM-4E, R/8, I/8, and
battery. There could also be another RM-4E board, I/8, or R/8 mounted
in the space provided within the enclosure.
4
Features
Tamper Switch
Tamper Switch
NOTE The switch is normally closed so that when the door is closed the tamper
is secure. If the door is forced, the switch will open causing an alarm
event.
5
RM-4E Reader Interface
RM-4E READER You can interface read heads that supply Wiegand signaling or magnetic
INTERFACE (ABA) signaling to the apC/8X, iSTAR, and iSTAR Pro using RM-4E
boards.
6
RM-4E Reader Interface
RM-4E Layout Figure 4 shows the photograph of an RM-4E board with LCD.
7
RM-4E Components
RM-4E Figure 5 shows the location of connection points, switches, and LEDs on
COMPONENTS the RM-4E board.
This section lists the RM-4E components — starting from the upper right
corner of Figure 5 and moving in a clockwise direction.
Tamper
The RM-DCM-2 tamper input twisted pair wires, shown in Figure 2, are
connected to the TAMPER (SW2) input pins.
8
RM-4E Components
NOTE: Do not use both power connection methods at the same time.
+12/24 VDC
NOTE The battery charger only works if you power through the Power IN
connector.
9
RM-4E Components
NOTE The +12 VDC input on Pin 1 has a protection diode that prevents you
from using the RS-485 connector as a source of +12 VDC if you power
through the Power IN connector.
Battery
Connect the plus and minus sides of the 12 VDC battery to the Battery
connector. The battery provides power for memory retention in the event
of a power failure. When power is restored, the battery is charged by the
power supplied through the Power In connector.
LED Connector Table 2 lists LED Connector Signals and Functions on the RM-4E board.
TABLE 2. LED Connector Signals and Functions
6 Gnd Ground
10
RM-4E Components
NOTE When the wiring gauge is too small or the wiring runs are too long, the
Yellow LED drive oscillation can cause cross-talk and result in misreads.
RS 485 Reader Bus RS 485 is the reader bus connection to the apC or iSTAR.
It is two wire, half duplex RS 485.
Connect Tx+ / Rx+ to Pin 2 and connect Tx- / Rx- to Pin 3.
The pins are numbered right to left on the connector.
4 Gnd Ground
Wiegand Signaling
For Wiegand signaling, use the following pinout; set SW5-1 to ON.
3 N/C No connection
5 GND Ground
11
RM-4E Components
For Magnetic (ABA) signaling, use the following pinout; set SW5-1 to
OFF.
1 CRD N/A
5 GND Ground
Relay 1, Relay 2, The RM-4E provides lock components that facilitate connecting magnetic
MagLock, and Bypass and electric strike locks.
Relay 1 is a standard Form C, dry contact relay, identical to the relays
found on the iSTAR ACM.
Relay 2, along with the MagLock and Bypass connectors have
internal etch connections for wiring magnetic and electric strike locks
Tie Point (TP1/TP2) connector pins are not connected to the circuitry.
They are used as connection points to avoid field splices when
connecting locks to Relay1. TP1-1 is tied to TP1-2, and TP2-1 is tied to
TP2-2.
12
Lock Wiring Configurations
LOCK WIRING RM-4E lock connectors support the following wiring configurations:
CONFIGURATIONS Magnetic Lock using Relay 2
Electric Strike using Relay 2
Electric Strike using Relay 1
Magnetic Locks The normal state of a magnetic lock has current flowing through an
electromagnet on the lock that pulls a strike plate with a force of 500-2000
lbs.
Safety codes usually require a bypass switch for emergency egress. This
is not the Request to Exit (REX) switch.
Note the internal etch connections between Relay 2, Maglock, and the
Bypass connector.
Connecting a Magnetic The following figure shows an example of connecting the power supply,
Lock magnetic lock, and bypass switch.
13
Lock Wiring Configurations
14
Lock Wiring Configurations
Magnetic Lock This section describes the components and connections for magnetic lock
Components wiring.
Power Supply
The power for a magnetic lock must be filtered, regulated direct current
(DC) voltage. Alternating current (AC) does not work and half wave
rectified DC does not work reliably.
18 AWG wire is generally recommended. If the wire runs exceed 100 feet,
use 16AWG wire instead.
The power supply to a magnetic lock must be isolated. Do not connect the
output of the power supply or the negative side of the lock to earth
ground. The connection from the minus side of the power supply must
go to Maglock pin 3.
Bypass Switch
It will be necessary to connect the J15 Bypass jumper (closed) if you install
an electric strike on Relay 2.
Diode Protection
When using the configuration shown, the magnetic lock remains locked
if the RM-4E loses connection to the apC or iSTAR because the normally
closed (NC) connection of Relay 2 is used. The magnetic lock also remains
locked if the RM-4E loses power.
15
Lock Wiring Configurations
You have the option of wiring to the normally open (NO) connector of
Relay 2 if you want to have the Magnetic lock unlock under those
conditions. If you use the normally open (NO) connector then Relay 2
will have to be normally energized using the C•CURE Administration
application.
If the power supply fails, the magnetic lock will unlock regardless of
whether the normally closed (NC) or normally open (NO) is used.
Electric Strikes Unlike magnetic locks, electric strike locks typically lock when not
powered and unlock when powered.
You must decide if you want to wire for “fail-secure” or “fail-safe.” Fail-
secure means that if there is a power failure, the door goes to a secure or
locked state. Fail-safe (fail-open) means that the door is open if there is a
failure. It is important that local codes be followed to avoid people
getting trapped in an emergency situation. Usually fail-secure doors have
crash bars to allow emergency egress.
Using Relay 2 for an The same internal connections that are used for a magnetic lock can be
Electric Strike used to wire an electric strike. Connect the plus side of the power supply
to the normally open (NO) connection of Relay 2 and connect the
remaining external connections the same as the magnetic lock
16
Lock Wiring Configurations
17
Lock Wiring Configurations
Electric Strike This section describes components and connections for electric strike
Components wiring using Relay 2.
Bypass Switch
Diode Protection
Using Relay 1 for an Relay 1 is a standard Form-C dry contact relay. Wiring door strikes using
Electric Strike this relay on the RM-4E is the same as wiring them to apCs, iSTARs, R/
8s etc.
Two pair of isolated tie points have been added to minimize splices.
Connect the strike and the power supply as shown. There is no
internal etch to consider when using Relay 1.
In the example below, a fail-secure door is shown with the normally open
(NO) contact. You can add an optional external suppression diode, if
desired.
18
Inputs
INPUTS
Input 1 and Input 2 Connect inputs using the standard Software House supervision for either
NO or NC. Figure 11 shows an example of wiring Normally Open (NO)
and Normally Closed (NC) inputs.
19
Inputs
Each input uses a Red, Yellow, or Green LED to show the input status.
Only one color will be on at a time for each input.
Table 6 lists the LED color and the corresponding input status.
Red LED indicates alert (nominal 500 ohms or 2K ohms).
Green LED indicates secure hardware state (nominal 1k ohms).
Yellow LED indicates supervision error (open circuit, shorted, or line
fault).
The RM-4E input status LEDs show flashing status if the RM-4E is
communicating with the apC or iSTAR and at least one input or
output is configured, or the reader is being used on a door. (The apC
or iSTAR needs a configured reason to communicate.)
20
Inputs
21
LED Control
LED CONTROL SW5-3 and SW5-2 control the reader LED display.
SW5-3 and SW5-2 provide the same LED control that is available on the
RM-4 and the iSTAR ACM.
Three Wire LED Control When both SW5-3 and SW5-2 are Off, it specifies Three wire LED control.
In this case, the Red, Green, and Yellow LED drives are wired to the
associated LED of the same color as shown in Figure 12.
22
LED Control
RM LEDs
Table 9 describes the various conditions indicated by the red, green, and
yellow RM reader LEDs.
Fast flash for 2 sec. Off Off Access denied (Software Flag
Enabled)
Fast flash Fast flash Fast flash Alarm: door forced/held open
23
LED Control
External Bi-color LED When SW 5-3 is On and SW5-2 is Off, the function is External Bi-color
Control because there are two LEDs (Red and Green) in the reader.
The LEDs will appear as Yellow when both Red and Green are on,
making the function essentially a Tri-color (Red, Green, Yellow).
There are two cases of External Bi-color — two wire and one wire. With
two wire, the Red and Green LED drives are wired as shown in Figure 13
24
LED Control
With one wire, the Yellow drive is wired as shown in Figure 14.
The Yellow LED drive gets inverted in the read head resulting in a Red
LED when the signal is low and a Green LED when the signal is high. If
the Yellow LED drive is oscillating, the Red and Green LEDs will be
oscillating and will appear to the human eye that the LED is Yellow. The
RM-4E will oscillate the Yellow drive at 1 KHz when a Yellow LED
display is required.
Special RM-4E 1-Wire Setting both SW5-3 and SW5-2 On results in a special RM-4E legacy mode
LED Control that is equivalent to the 1-wire Bi-color mode on earlier versions of the
RM-4E.
In the standard 1-wire Yellow drive connection, the drive will oscillate,
resulting in the appearance of a Yellow LED. In the special mode, the
drive does not oscillate and there is no Yellow indication.
25
LED Control
One Wire (A,B,C) LED When SW5-2 is On, it specifies One Wire (A,B,C) mode. In this case, a
Control single LED drive (Red or Green or Yellow) is wired with varying results
as shown in Figure 15.
One wire mode is typically used for older read heads with a single LED
that is either On, Off, or flashing.
26
Installation Requirements
Make sure the installation location provides sufficient space for the RM-
DCM-2 enclosure, and the necessary electrical conduit.
27
Installation Requirements
Module Dimensions Figure 17 shows the dimensions of the RM-4E, R/8, and I/8 modules.
Maximum component height is 0.5 inches (12.7 mm).
Enclosures UL has approved the RM-DCM-2 enclosure for use with R/8, and I/8
boards.
There are four possible mount positions for the three boards in the
enclosure.
28
Installation Requirements
Mounting Mounting
Studs Studs
Mounting
Studs
Power Supply and Each module (RM-4E, I/8, R/8) has a typical rating of 125mA, plus
Wiring another 25mA for each active relay. The need for an external power
supply is based on the electrical current available from the apC panel or
iSTAR controller power supply, the calculated draw of other boards in
the system, and the voltage drop due to wiring length.
NOTE Wiring methods shall be in accordance with the National Electric Code
(ANSI/NFPA 70), local codes, and the authorities having jurisdiction.
Environment Operating temperature ranges for the RM-DCM-2 is 32-120° F (0-49° C);
85% relative humidity @ 86° F ± 3° (30° C ± 2°).
29
RM-DCM-2 Specifications
NOTE UL has evaluated the RM-DCM-2 for indoor use with a range of 0° C to
49°C (32°F to 120°F).
Software and Firmware Current versions of C•CURE 9000 and C•CURE 800/8000 system
Support software and firmware support the RM-DCM-2 components.
Power Requirements Table 10 lists the power requirements and operating specifications of the
and Specifications RM-4E board in the RM-DCM-2 enclosure.
TABLE 10. RM-4E Power Requirements and Operating Specifications
Requirement Specification
NOTE Software House recommends local power when using the battery
charging circuit and when the RM-4E is used with high-power, long-
range readers.
See “Power In” on page 9 for information.
30
RM-DCM-2 Specifications
31
Parts List
Physical Specifications
TABLE 12. RM-DCM-2 Physical Dimensions
Requirement Specification
PARTS LIST Table 13 lists part numbers for the RM-DCM-2 product.
TABLE 13. RM-DCM-2 Parts List
Compliance The RM-DCM-2 has been tested and certified for compliance with the
standards listed below:
UL Listed
UL 294
Other
FCC Part 15B class A
CE
EN50081-1
EN50130-4
32
Testing the RM-DCM-2
Required Equipment
Configuration Requirements
33
Testing the RM-DCM-2
Self-Test Mode
The RM-4E has a built-in self-test mode. Perform the steps in this section
to run the self-test.
1. Remove power to the RM-4E.
2. Set Rotary Switch SW4 to position 0.
3. To test the reader LEDs, connect three LEDs to the Reader LED port as
shown in Figure 19. Connect the anode (long lead) of each LED to Pin 1
(+5v). Cover the LED wires with heat shrink to prevent short circuits.
NOTE If you are using an older LED that does not have a built-in current-limiting
resistor, add a 1K-ohm resistor in series.
34
Testing the RM-DCM-2
Input 1 Input 2
1K-ohm
resistors
6. To test each reader line, short to ground, one at a time, each of the three
reader data lines (D0, D1, and DAT) on the Reader port.
After shorting a data line, the display should show a “1” in the appropriate
reader line position to indicate that the data line is low (for example, W=010
when you short the D1 line).
After removing the short from the data line, the display should revert to 0
for that reader line.
35
Testing the RM-DCM-2
7. To test the tamper switch, short tamper connector SW2-2 to ground. The
display should change to T=0.
Remove the short. The display should revert to T=1.
8. To test SW5 positions 1, 2, and 3, set each of these DIP switches to the Off
(open) position.
The display should show S5=111. Set each of these DIP switches to the On
(closed) position. The display should show S5=000.
9. To test the keypad, short to ground each of the eight keypad connectors on
port J2 one at a time.
The display should indicate that a voltage level change was detected. For
example, if you short keypad connector 3, the display should show K3=0,
where K3 is the keypad connector number and 0 is the new state.
36
CE Notice
The corresponding LED (DS3 for output #1 and DS10 for output #2) will
light.
The multi-meter can be used to check for continuity between the C and NO
pins on connectors Relay1 and Relay2.
6. Check the reader interface.
The reader interface can only be tested with the reader chosen for the
installation.
Reading a card will cause the display to show “Access Granted” or “Access
Denied”, depending upon the clearance of the card.
CE NOTICE This product is in compliance with the CE EMC and Electrical Safety
Directives of the European Community when used with the Software
House apC or iSTAR products. This unit must be enclosed in a box
similar to the units noted in the “Enclosures” on page 28 in order to be in
compliance.
37
CE Notice
Certain Product names mentioned herein may be trade names and/or registered
trademarks of other companies. Information about other products furnished by
Software House is believed to be accurate. However, no responsibility is
assumed by Software House for the use of these products, or for an
infringement of rights of the other companies that may result from their use.
38