8 Function diagrams
General Page
Key to symbols ....................................................................................................................... 8-5
Basic functions
G100 Overview................................................................................................................................. 8-6
G101 Hardware configuration .......................................................................................................... 8-7
Inputs and outputs
G110 Binary inputs terminals 36 to 39 (CUD1)................................................................................ 8-8
G111 Binary inputs terminals 40 to 43 (CUD2)................................................................................ 8-9
G112 Binary outputs terminals 46/47 and 48/54 (CUD1) .............................................................. 8-10
Binary outputs terminals 50/51 and 52/53 (CUD2) .............................................................. 8-10
G113 Analog inputs terminals 4/5, 6/7 (CUD1), and 103/104 (power interface) ........................... 8-11
G114 Analog inputs terminals 8/9 and 10/11 (CUD2).................................................................... 8-12
G115 Analog outputs terminals 12/13, 14/15, and 16/17 (CUD1) ................................................. 8-13
G116 Analog outputs terminals 18/19 and 20/21 (CUD2) ............................................................. 8-14
G117 E-Stop, Relay output line contactor (power interface).......................................................... 8-15
Setpoint generation
G120 Fixed values.......................................................................................................................... 8-16
Fixed control bits................................................................................................................... 8-16
Constant fixed values and control bits.................................................................................. 8-16
G121 Connector and binector displays .......................................................................................... 8-17
G124 Connector selector switch .................................................................................................... 8-18
G125 Evaluation of a 4-step master switch.................................................................................... 8-19
G126 Motorized potentiometer....................................................................................................... 8-20
G127 Fixed setpoint ....................................................................................................................... 8-21
G128 Oscillation / square-wave generator..................................................................................... 8-22
G129 Inching setpoint..................................................................................................................... 8-23
G130 Crawling setpoint / terminal 37 ............................................................................................. 8-24
G135 Setpoint processing .............................................................................................................. 8-25
G136 Ramp-function generator (1) ................................................................................................ 8-26
G137 Ramp-function generator (2) ................................................................................................ 8-27
Internal control
G140 Brake control......................................................................................................................... 8-28
Actual speed value
G145 Pulse generator evaluation................................................................................................... 8-29
Controllers
G150 Starting pulse - speed controller........................................................................................... 8-30
G151 Speed controller (1) .............................................................................................................. 8-31
G152 Speed controller (2) .............................................................................................................. 8-32
G153 Friction compensation .......................................................................................................... 8-33
Compensation of moment of inertia (dv/dt injection) ............................................................ 8-33
G160 Torque limitation, speed limit controller................................................................................ 8-34
G161 Current limitation................................................................................................................... 8-35
G162 Closed-loop armature current control................................................................................... 8-36
G163 Auto-reversing stage, armature gating unit .......................................................................... 8-37
G165 Closed-loop EMF control ...................................................................................................... 8-38
G166 Closed-loop field current control, field gating unit ................................................................ 8-39
G167 Field current monitoring........................................................................................................ 8-40
NOTE
Freely assignable function blocks are enabled in parameter U977.
For enabling instructions, please refer to Section 11, Parameter List, description of parameters
U977 and n978.
B 510
0.00...300.00s = setting range .03 Selected binectors for each index can be specified in symbol
B 1
r045.02
SIEMENS AG 6RX1700-0AD76
Display parameter Selection of a connector
Parameter number = r045 P510 (2) Factory setting in parentheses
.02 = index 2 of parameter K Setting range = all binector numbers
Selected connector can be specified in symbol
Connector
K0401
(freely connectable 16-bit value) P606 (9) Selection of connectors via "indexed" parameter
.01 Factory setting in parentheses
K
- 000 -
8-5
Function diagrams
8-6
1 2 3 4 5 6 7 8
Overview
Function diagrams
setpoint before r-f generator controller limiting speed controller torque setpoint current setpoint controller
Speed
controller
Current
Current controller
Main Setpoint Armature
setpoint
setpoint processing gating unit
generation
[G110 - G130] Ramp-functiongenerator Ramp-function Setpoint [G151, G152] Torque limiting Current limiting [G162] [G163]
setpoint limiting generator limiting
[G161] Precontrol
[G135] [G136] [G136] [G160]
Basic functions Sheets G100 to G200
Actual value
speed controller
Field current
limits
- G100 -
Arrangement of board
locations 1 to 3 and slots
Hardware configuration D to G in electronics box
1 3 2
Select / deselect slots
U910.005 U910.003
F D
U910.004 U910.002
SIEMENS AG 6RX1700-0AD76
CUDx
Definition of SIMOREG DC Master power section Board code Board compatibility Software identifiers G E
0 Board in slot D
Control word for
Total thermal 1
P077 r063.004 r064.004 r065.004
reduction factor
0
Options according to rating plate r068 Board in slot G
1
r063.001 r064.001 r065.001
Serial number r069
Board in location 1
MLFB (order number) r070
Creation date
Converter rated
r071 Software version of software
supply voltage (armature)
.001 CUD .001 Year
Converter rated .002 Slot D .002 Month
r072 Checksum
DC current (armature) .003 Slot E .003 Day
.004 Slot F .004 Hour .001 Converter firmware
Converter rated .005 Slot G .005 Minute .002 Boot sector
r073 r060 r061 r062
DC current (field)
- G101 -
8-7
Function diagrams
8-8
1 2 3 4 5 6 7 8
34
P24_S Display of terminal states on 7-segment display
E-
Stop 214 213 212 211
r010
43 42 41 40 39 38 37 36
35
M
K0020
36 24V
B0010
5V
1 B0011
M
37 24V
Sheet G110 Binary inputs terminals 36 to 39
38 24V
Enable operation (to sheet "Control word 1")
5V [G180.2]
B0014
M
1 B0015
39 24V
IRES (to sheet "Pulse encoder evaluation")
5V [G145.2]
B0016
M
1 B0017
- G110 -
X163 CUD2
SIEMENS AG 6RX1700-0AD76
diagram "Binary inputs (1)"
45
M
[G145.2]
Enable counter for zero markers
40 24V
B0018
5V
M 1 B0019
Sheet G111 Binary inputs terminals 40 to 43
41 24V
B0020
5V
M 1 B0021
42 24V
B0022
5V
M 1 B0023
43 24V
B0024
5V
M 1 B0025
- G111 -
8-9
Function diagrams
1 2 3 4 5 6 7 8
8-10
r011
Indication of terminal states on 7-segment display
Binary outputs r011
K0021 109 52 50 48 46
Function diagrams
110
P775 (0ms)
(0...10000ms) P770.01 (0) P24
CUD1
P771 (0) T T 0 X171
<1>
B
1
1
46
ON/OFF delay Inversion
M
P776 (0ms) 47
(0...10000ms) P770.02 (0)
P772 (0) T T 0
<1>
B
1
1
48
ON/OFF delay Inversion
M
54
P777 (0ms)
(0...10000ms) P770.03 (0)
CUD2
P773 (0) 0 X163
T T <1>
B
1
1
50
ON/OFF delay Inversion
M
P778 (0ms) 51
(0...10000ms) P770.04 (0)
Sheet G112 Binary outputs terminals 46/47, 48/54, 50/51 and 52/53
P774 (0) T T 0
<1>
B
1
1
52
ON/OFF delay Inversion
M
53
<1> With log. "1": Output transistor is conductive
- G112 -
SIEMENS AG 6RX1700-0AD76
-1 3
0
4 0 0%
A P701 -1 2 K0011
u i 1
±10V
* 100% -1 [G127.2]
±20mA D 1 1
5 Switch in
0
10V =100% Sign reversal Filtering analog input
K0010
B B
Resolution Normalization Offset
CUD1 X174 P717 (12Bit) P711.F(100,0) P712 (0,00) P713 (0) Filter time [ms] r003
P715 (0)
Analog select Hardware-
input 1 Smoothing 1ms
-1 3
0
6 0 0%
A P711 -1 2 K0015
u i 1
±10V
* 100% -1
±20mA D 1 1
7 Switch in
0
10V =100% Sign reversal Filtering analog input
K0014
20mA=100%
2 1 0 2 1 0
Signal type Open circuit
P710 (0) B0051 (i ≤ 2mA)
1 = "Fault F047"
- G113 -
8-11
Function diagrams
1 2 3 4 5 6 7 8
8-12
Analog inputs (2)
(to ground)
CUD2
Function diagrams
X164
P724 (0) P726 (1)
B B
Normalization Offset
P721.F(100,0) P722 (0,00) P723 (0) Filter time [ms] r004
P725 (0)
Analog select 10V = 100%
input 2
1ms -1 3
0
8 0 0%
A P721 -1 2 K0017
u 1
* 100% -1
±10V D 1 1
9 Switch in
0
Hardware- Sign reversal Filtering analog input
smoothing
K0016
- G114 -
SIEMENS AG 6RX1700-0AD76
1 lact actual current
0
13
M
- G115 -
8-13
Function diagrams
1 2 3 4 5 6 7 8
8-14
Analog outputs (2)
Function diagrams
CUD2
K x x y D
-1 2 y [V] = * P768
100% A 20
1
Analog output 4
0
K0029
21
M
- G116 -
B0169
1 B0168
SIEMENS AG 6RX1700-0AD76
Pushbutton operation Switch operation
1
Instantaneous pulse disable on E Stop
XS XS 0
0 [G163.6]
"E Stop" switch [G180.2]
(NC contact)
Initiate
E Stop
24 V 106 106
24 V
XR
E Stop Power
ON
"Reset E Stop" button 108 108
(NO contact) Line contactor
Reset
E Stop
energize line contactor 110
Power U619.B(124)
Interface [G182.6] B
0 1 Power-
Interface
K0021
r011
r011
Indication of terminal states on 7-segment display
NOTICE
8-15
Function diagrams
1 2 3 4 5 6 7 8
8-16
11 fixed values 5 fixed values 8 fixed control bits Constant fixed values
setting range setting range and control bits
-199.99 to +199.99% -32768 to +32767
K0407 B0427
K0408 B0428
0 B0000
P409.F (0,00)
K0409
1 B0001
P410.F (0,00)
K0410
P411.F (0,00)
K0411
- G120 -
Sheet G120 Fixed values, fixed control bits, constant fixed values and control bits
Connector displays
Display in % (-200.0 to 199.9 %) Display decimal (-32768 to 32767) Display hexadecimal (0000h to FFFFh)
SIEMENS AG 6RX1700-0AD76
r043.07 n045.03 n047.03
P044 (0) r043.02 r043.04 r043.06 U044 (0) n045.02 n045.04 U046 (0) n047.02 n047.04
.01 .01 .01
K K K
.02 .02 .02
K K K
.03 .03 .03
K K K
.04 .04 .04
K K K
r045.01 r045.03
τ ≈ 300 ms r041.01
P042 (0) P046 (0) r045.02 r045.04
.01 .01
K B
.02 .02
K B
.03
B
.04
τ ≈ 300 ms r041.02 B
- G121 -
8-17
Function diagrams
1 2 3 4 5 6 7 8
8-18
Connector selector switch
Function diagrams
P456 (0)
.01
B
.02
B
P455 (0)
.01 0
K
.02
K
1 0
Sheet G124 Connector selector switch
.03 K0230
K
1
P458 (0)
.01
B
.02
B
P457 (0)
.01 0
K
.02
K
1 0
.03 K0231
K
1
- G124-
SIEMENS AG 6RX1700-0AD76
1
1 1
1 1
∗ -1
0 0% K0510
0 0
0 0
U662 (0) Setpoint of the 4-position
Setpoint step S2 S2 master switch
B
U664 (0)
Setpoint step S4 S4
B
U660 (0)
Travel command 1 SR
B
U661 (0)
Travel command 2 SL
B
Sheet G125 Evaluation of a 4-step master switch
U666
n2
e.g. 50%
U665
n1
e.g. 20%
0 Slow Medium Fast Full
SL / SR S2 S3 S4 Input signals
= Control commands from the master switch
= Activation of the setpoint steps
- G125 -
8-19
Function diagrams
1 2 3 4 5 6 7 8
8-20
Motorized potentiometer operating mode
Motorized potentiometer 0 ... The motorized potentiometer ramp-function generator is bypassed in
P460.F (1)
automatic mode (effect as for P462 and P463 = 0)
1 ... The motorized potentiometer ramp-function generator is effective in
the manual and automatic modes P465.F(0)
60 1
P473.F (0) (0 or 1)
Function diagrams
P469.F(-100,00%) P468.F(+100,00%)
(-199,99...+199,99%) (-199,99...+199,99%)
Sheet G126 Motorized potentiometer
P467.F(0,0)
≥1 (-199,9...+199,9%) y=x
MOP Starting value B0241
Acceleration/deceleration
completed
1
0 * -1
1
0 Setting value
(Capacitor symbolizes 0
value memory) P466.F (0)
K 1
Decrease motorized potentiometer
from control word1 P470.B (0) P471.B (0) P472.B (0)
Bit14 [G180.6] B B B
Clockwise Manual/Automatic Set motorized
Increase motorized potentiometer
/Counterclockwise potentiometer
from control word 1
Bit13 [G180.6]
- G126 -
Fixed setpoint
SIEMENS AG 6RX1700-0AD76
≥1
[G181.5]
&
Select fixed setpoint 1 &
from control word 2 &
Sheet G127 Fixed setpoint
[G181.5]
≥1 ≥1 Bypass ramp-function generator
&
& to sheet "Ramp-function generator"
Select
setpoint
P431 (0) 0
.01
K
.02 0 1
K
.03 0 1
K
.04 0 1
K
.05 0 1 K0204
K
.06 0 1
K
.07 0 1
K
.08 0 1
K
1
1
P433.F (11)
K0209
[G113.8] K
0 [G128.3]
- G127 -
8-21
Function diagrams
1 2 3 4 5 6 7 8
8-22
Oscillating / square-wave generator
Function diagrams
Setpoint1 Setpoint2
P480.F P482.F
Square-wave generator
%
P481.F P483.F
Time1 Time2
Sheet G128 Oscillation, square-wave generator
1
P484.F(209)
K0208
[G127.7] K 0
[G129.2]
Oscillation
P485.B (0)
B
- G128 -
Inching setpoint
P437.07 P437.05 P437.03 P437.01
P437.08 P437.06 P437.04 P437.02
Inching, bit 0
from control word 1 ≥1 &
[G180.6]
&
Inching, bit 1 &
SIEMENS AG 6RX1700-0AD76
from control word 1 ≥1 &
[G180.6]
≥1 Bypass ramp-function generator
&
& to sheet "Ramp-function generator"
Select injection
[G136.4]
of inching &
Sheet G129 Inching setpoint
setpoint &
=1 &
Select
setpoint
P436 (0) 0
.01
K 0 1
.02
K 0 1
.03
K 0 1 0% 0
.04
K 0 1
.05
K 1
.06 0 1
K 0
.07 1
K 0 1 K0202
.08
K 1
1
P438.F(208)
K0207
[G128.6] K
0 [G130.2]
- G129 -
8-23
Function diagrams
1 2 3 4 5 6 7 8
8-24
Level/edge
Selection for P445 Crawling setpoint / Terminal 37
switch-on/shutdown
P654.B (1) 1 [G180.2] Switch-on command
B from ON/OFF1
Function diagrams
P440 (0)
.01 R 0
B
.02
B
.03
B
.04 ON command from
B [G180.2]
.05 ≥1 CRAWL
B
.06 (to control word 1)
B
.07
B
.08
B
Select <1> Flip-Flops are reset when P445=0
crawling setpoint
P441 (0) 0
.01
K 0
.02 1
K 0
.03 1
K 0
.04 1
K 0
.05 1 K0201
K 0 1
.06
K 0
.07 1
K 0 1
.08
K
1
1
P443.F(207)
K0206
[G129.7] K 0 [G135.1]
- G130 -
Setpoint processing
P642 (2)
.01
K
.02
K
.03
SIEMENS AG 6RX1700-0AD76
K
.04
K
Minimum
P322.F (1)
K K0198 K0197 U607.B (1)
B
Maximum
P643 (9)
.01 <1> Enable positive direction of rotation from control word 1
K
.02 <1> [G180.6]
K
.03 <1>
K Enable negative direction of rotation from control word 1
.04 <1>
K [G180.6]
P323.F (1)
K
- G135 -
8-25
Function diagrams
1 2 3 4 5 6 7 8
8-26
Lower transition Upper transition
Ramp-function generator (1) Ramp-up time Ramp-down time rounding rounding
P303.F P304.F P305.F P306.F ... RFG setting 1 [s] Ramp-function Effective
P307.F P308.F P309.F P310.F ... RFG setting 2 [s] generator setting parameters
P636 (1) P311.F P312.F P313.F P314.F ... RFG setting 3 [s] 2 3
.01
K 0 0 P303 - P306
.02 0 1 P311 - P314
Function diagrams
K
.03 1 0 P307 - P310
K
.04
K
.05
K
.06
K
Effective times for emergency stop (OFF3):
P637.B (0) P296.F Ramp-down time
RFG-setting 2
B Parameter selection
This changeover to RFG settings 2 and 3 P297.F Lower transition rounding
has priority over the input of RFG setting 3 Lower transition Upper transition
by the starting integrator control Ramp-up time Ramp-down time rounding rounding P298.F Upper transition rounding
P638.B (0)
RFG setting 3
B 1
60
from starting integrator control ≥1
(see P302) 1
0
r315.1 r315.2 r315.3 r315.4 Time difference [s]
Ramp-function generator [G180.6] P330.F(0)
start from control word 1 P542.F
RFG input [G135.7] r028
1
Sheet G136 Ramp-function generator (1)
P632 (1)
SIEMENS AG 6RX1700-0AD76
.01
K
.02
K positive
.03 setpoint limit
K
.04 P300.F
K
K0183
P634 FS [G152.1][G160.1][G188.1]
Sheet G137 Ramp-function generator (2)
.01
[G136.8] K 190 K0170 Speed setpoint
.02
K 0
P633 (9)
.01 <1>
K P301.F
.02 <1> negative
K setpoint limit
.03 <1>
K
.04 <1>
K
- G137 -
8-27
Function diagrams
1 2 3 4 5 6 7 8
8-28
Brake control
Function diagrams
P087 (0.00)
(-10.00...0.00 s)
[see footnote 2]
Brake opening time
Automatic restart
(see footnote 1) T 0
Sheet G140 Brake control
SET B0255
≥1
(Q=1) Q
[G182.6] B0104
Open brake
Operation
1
& RESET
P080
≥1 Q B0250
(Q=0)
Close brake
2 Priority:
1
1. RESET
1 2. SET
[G187.6] B0164
P088 (0.00)
1 = n<nmin (0.00...10.00 s)
Delayed firing pulse disable
T 0
& Firing pulse disable
OFF1 or OFF3 (1 = firing pulse disabled)
from the sequence control
from control word 1
[G180.6]
Footnote 1:
The signal "automatic restart" is generated by the sequence control.
If the voltage at the power section fails briefly in the "operating" state (see P086)
(and if automatic restart is selected, i.e. P086 > 0), the "operating" signal goes to log. "0" and
the "automatic restart" signal to log. "1" during this time.
This causes the brake to remain open during this short time without torque.
Footnote 2:
A negative value in P087 means that the signal "Open brake" is delayed with respect to the enable
for the firing pulses for the thyristor. Only this case is shown in this function diagram.
- G140 -
SIEMENS AG 6RX1700-0AD76
Pulse encoder
supply 27 Actual speed value
M K0040 from pulse encoder
28 [G151.1]
COMP r024
Track 1 29 Speed measurement
X>Y Actual speed value
K0048 from pulse encoder
30 in rpm
Maximum Measuring
speed time
Pulse encoder faulty
P140 P141 P148.F
Pulse No. of Pulse encoder 1 = "Fault F048"
encoder encoder monitoring with fault value 2
type pulses ON/OFF B0052
Reset Underflow
B0053
position counter
P450.F
B0054 Overflow
8-29
Function diagrams
1 2 3 4 5 6 7 8
8-30
Starting pulse - speed controller
Function diagrams
U657.B (0)
<1> B
U651.F (0,00%) This connector can be used as a setting
value for the I component of the speed
U655 (451) <1> controller (Sheet G152, P631)
0
K0451 K
K0454
1
U652.F (50,00%)
Rated motor current (P100.F)
Sheet G150 Starting pulse - speed controller
K0453
U653.F (0,00%)
<1>
<1> 100% corresponds to 100% of the rated current of the motor (P100)
- G150 -
SIEMENS AG 6RX1700-0AD76
0 P051
1 P227.F (0,0)
-1 (0,0 ... 10,0)
1 x
n contr. droop Kp2
[G113.8] P083.F
Main actual value 0%
- G151 -
8-31
Function diagrams
1 2 3 4 5 6 7 8
8-32
Master/slave drive from control word 2:
Speed controller (2) Make I component follow on slave drive
so that M(set, n contr.) = M(set, limit) and set Speed controller integration time
speed setpoint = actual speed value (K0179) from Sheet Speed controller 1
[G181.5] [G151.7]
P229.F (0)
Speed controller P gain
Function diagrams
Friction compensation
Friction characteristic
P520.F to P530.F
SIEMENS AG 6RX1700-0AD76
P530
K0172
P521
P519 FS P520
.01 -100%
[G152.3] K 179 n
.02 0% 100%
K 0
Friction moment
K0171 and moment of inertia
[G152.7] compensation
Compensation of moment of inertia (dv/dt injection)
Filter time
(0...10000ms)
P546.F (0) K0173
[G136.8]
P619 (191)
dv/dt * P542 1
K0191 K
from ramp-function generator
[G136.6] 0% 0
P540.F
Enable dv/dt
injection
Compensation of moment of inertia (dv/dt injection)
n controller setpoint
[G152.3] K0174 K0150 P697.B (1)
B
Threshold
P543.F
P541.F
- G153 -
8-33
Function diagrams
1 2 3 4 5 6 7 8
8-34
Changeover speed
P184.F (0,00) P515.F (3,00)
Torque limitation, speed limit controller (0,10...200,00)
A Kp
B>A <2> <2> P513.F (-105,0) P512.F (105,0)
[G151.3] K0166 B P180.F P182.F (-199,9...0,0 %) (0,0...199,9 %)
Absolute actual speed n(max,neg. rot.) n(max,pos. rot.)
Function diagrams
0 1 [G166.5]
P694.B (0) Motor flux Pos. speed limit reached
& P510 (2) y1
B
K0290 M K B0192
Torque limit x
changeover P100.F
________ ϕ
P171.F(100,0%) Minimum r072.002 P511 (4) Neg. speed limit reached
<2> K B0193
P605 (2) y2
.01 Minimum
K
.02 P509 (167) Speed limit controller Limit controller active
K P169.F x
.03 K
K (n act) 1 B0201 [G163.2]
.04 [G151.3]
K y2 y1
.05 0 1
K
K0137 Mlimit2(act)
P084 (1) Master/slave drive
M(set, n contr.)
from control word 2 K0136 Mlimit1(act)
P607.B(148) (0 = master, 1 = slave) K0143
1 [G181.5] Motor flux
K
Upper torque [G166.5] K0290
[G152.8] P503.F(100%)
0 K0147 K0145 B0202 M
2 limit active
[G161.1] [G163.2] ϕ
P500.B(170) 1 y y
K 1 Iset
[G137.5] 0 P601 FS
[G152.8] x .01 x K0134
K0141 K 141
M(set, n contr.) K0148 .02 0 [G161.1]
1 K 0
Sheet G160 Torque limitation, speed limit controller
P109 (0)
Current limitation
Absolute
actual speed Speed-depend. current P104 (n1)
Shutdown limit
[G151.3] K0166 I limit
[G180.8] B0161 P105 (i1)
SIEMENS AG 6RX1700-0AD76
pos. current limit P108 (n3)
|n act|
P171.F *)
(100,0%) P100.F
________
r072.002
P603 FS Min. P075 P077
.01
K 1
.02 Min.
K 1
Sheet G161 Current limitation
- G161 -
8-35
Function diagrams
1 2 3 4 5 6 7 8
8-36
r072.002
P100.F
Closed-loop armature current control
K0149
*) The following applies with these parameters
or connectors:
[G166.5] K0290 100% corresponds to the rated
Function diagrams
Absolute actual
K0116 armature current P176.F(1)
K
Average value over
K0114
1 current peak
P175.F(1)
K0109 Average value over K
r019*) 6 current peaks
I=0 signal
Changeover threshold
P159.F
0 = No torque direction P160.F Additional
SIEMENS AG 6RX1700-0AD76
K0106
Auto-reversing stage (0,000s) dead interval
1 = Torque direction I
0.05% 2 = Torque direction II Number of additional αW pulses
P161.F (0)
with disabled second pulses
I Requested Number of additional αW pulses
0 torque direction P179.F (0)
[G162.4] with enabled second pulses
K0119
[G163.5]
II Enabled torque direction
K 0
.03 MII 1
K 0
.04 MII 2
K 0 [G165.1] αW no immediate MII 3
K0101 B0197 pulse disable MII 4
continuous αW-limit reached P177.B (1) MII 5
current ≥1 B MII 6
0 1
fire all thyristors
165° simultaneously
P192.F P151.F P178.B (0) P152.F
Filtering of line
B frequency
tracking
Current limitation [G161.7] B0200 [G152.6] P826.ii P079
[G117.7]
Limitation controller [G160.8] Correction of Short/long
B0201 ≥1 B0204 zero passages pulses
Instantaneous pulse disable
Upper torque limit [G160.5] B0202 Limitation active on E Stop or in the case of F030
Lower torque limit [G160.5] B0203
active
- G163 -
8-37
Function diagrams
1 2 3 4 5 6 7 8
8-38
Closed-loop EMF control Rated motor
field current
P102.F
P613 (1) Minimum
Ra .01
P110.F r037 K
.02
K
Function diagrams
EMF .03
K
K0287 K0285 .04
P275.F P276.F P277.F K
.05
K
Kp Tn Droop
P616 (286)
ua K0286 K - EMF controller
Actual K0283 EMF controller set/actual diff.
value K0284 EMF controlller set/actual diff. after droop
With operating status >=o10
or
K0286>P357 AND |K0179/K0287|<5%:
Setpoint upper limit ="old" K265
With operating status >=05 :
Setpoint upper limit = 200%
("Release")
Closed-loop field current control, field gating unit 0: Field firing pulses disabled
1: Field firing pulses enabled with ≤ o5.0
Field characteristic 2: Standstill field with ≥ o7.0
P263 (1) P120.F to P139.F 3: Field firing pulses are always enabled
4: Field gating pulses enabled
[G166.3] K0268 with "Auxiliaries ON" (B0251)
Motor flux 11..14: External 40.00 A - field power module
2
r073.001=40.00 A
1 r073.002 otherwise as for P082=1...4
[G165.5] K0293 * P102 K0290 [G160.3]
<1> 0 [G160.7] 21..24: External field device
[G162.1] Setpoint from K0268
SIEMENS AG 6RX1700-0AD76
<1> With "Standstill field" K0268 Actual value to P612
P255.F P256.F r073.001 and r073.002=U838
r035*) (P076.002 is ineffective)
Kp Tn Field current controller otherwise as for P082=1...4
P612 FS
Internal actual .01 K0263 set/actual diff.
K0266 K 266 - Current controller field
field current .02 Actual value
K 0 K0261 P comp. P097: Response to fault messages
Delay time
1 = Field firing pulses disabled
Field precontrol
P252.F
V_control_F
P082<21 (no external field device) Filtering of line
frequency tracking
P082=21 and operating state > o5.0 ≥1
K0271
P082=24 and auxiliaries OFF
8-39
Function diagrams
1 2 3 4 5 6 7 8
8-40
Field current monitoring
Function diagrams
2% of r073.002 A
B>A
Setpoint at field K0268 B
current controller input
[G166.3]
Monitoring time
Threshold P397.F (0,50)
Sheet G167 Field current monitoring
- G167 -
[G171.5] [G172.5]
[G170.5] [G173.5] [G174.5]
SIEMENS AG 6RX1700-0AD76
K2001 LOW K6001 LOW K9001 LOW
HIGH KK2031 HIGH KK6081 HIGH KK9081
K2002 LOW K6002 LOW K9002 LOW
HIGH KK2032 HIGH KK6082 HIGH KK9082
K2003 LOW K6003 LOW K9003 LOW
- G169 -
8-41
Function diagrams
1 2 3 4 5 6 7 8
8-42
USS interface 1 Receive data Transmit data
r810.17 r810.18 r810.19 r810.20 r811.17 r811.18 r811.19 r811.20
USS parameter data USS parameter data
X300: Word 1: Param.-ID Word 1: Param.-ID
PMU G-SST1 (PKE) (PKE)
Function diagrams
every 16 bits
8 Rx-/Tx-
≥1 Word 1 <1> K2001 [G182.6] K 32 .01 Word 1
.02
Word 2 K2002 [G151.3] K 167 Word 2
5 RS485
M Word 3 K2003 K 0 .03 Word 3
9
M Word 4 K2004 [G183.6] K 33 .04 Word 4
P785.001 (0)
Submin D Word 5 K2005 K 0 .05 Word 5
0 1 0 1
Word 6 K2006 K 0 .06 Word 6
Bus terminator Word 7 K2007 K 0 .07 Word 7
Word 8 K2008 K 0 .08 Word 8
.09
+ M Word 9 K2009 K 0 Word 9
.10
Word 10 K2010 K 0 Word 10
.11
Word 11 K2011 K 0 Word 11
<1> P785.002=0:
Word 12 K2012 K 0 .12 Word 12
Bit 10 is not treated as "control by PLC".
Word 13 K2013 K 0 .13 Word 13
P785.002=1:
Bit 10 is treated as "control by PLC", Word 14 K2014 K 0 .14 Word 14
i.e. when bit 10=0, the other bits of word 1 as well as Word 15 K2015 K 0 .15 Word 15
words 2 to 16 are not written to connectors K2001 to K2016 0 .16
Word 16 K2016 K Word 16
or to binectors B2100 to 2915.
All these connectors and binectors retain their old values. Bit 0 ... Bit 15
B2100 B2115
Parameters for USS interface B2200 B2215 U116 (0)
.01
1 = "Telegram B
B2300 B2315
P780 (2) USS On/Off monitoring
timeout" B2400 B2415
P787 (0,000s) Telegram monitoring time B2030 .16
B2500 B2515 B
P786 (0) Slave address 1s
B2600 B2615
P783 (6) Baud rate B2031 15 0
B2700 B2715
P781 (2) Length of process data Binector / connector K2020
B2800 B2815
converter
P782 (127) Length of parameter data B2900 B2915
Fault message trigger
r789 USS diagnostic parameter P788 (2030)
B 1 = "Fault F011"
P927 Enable parameterization
For transmission of double-word connectors see Section 9.13.1
See also connector type converter on sheet G169 - G170 -
SIEMENS AG 6RX1700-0AD76
56 Tx+
Word 4: Param.Value Word 4: Param.Value
High Word High Word
57 Tx-
1
58 Rx+/Tx+ Process data r812.01 to .16 r813.01 to .16 Process data
from USS interface [G169.4] to USS interface
P794 FS
Sheet G171 USS interface 2
8-43
Function diagrams
1 2 3 4 5 6 7 8
8-44
USS interface 3 Receive data Transmit data
r814.17 r814.18 r814.19 r814.20 r815.17 r815.18 r815.19 r815.20
USS parameter data USS parameter data
Word 1: Param.-ID Word 1: Param.-ID
(PKE) (PKE)
Function diagrams
CUD2 G-SST3
Word 2: Param.Index Parameter Word 2: Param.Index
X162 1 Word 3: Param.Value processing Word 3: Param.Value
Low Word Low Word
61 Tx+ Word 4: Param.Value
Word 4: Param.Value
High Word High Word
62 Tx-
1
63 Rx+/Tx+ Process data r814.01 to .16 r815.01 to .16 Process data
from USS interface [G169.6] FS to USS interface
P804
Sheet G172 USS interface 3
Peer-to-peer interface 2
SIEMENS AG 6RX1700-0AD76
CUD1 G-SST2 1
X172 0
.03
Word 3 K6003 K 0 Word 3
60 RS485 .04
M 0 Word 4 K6004 [G183.6] K 33 Word 4
.05
Word 5 K6005 K 0 Word 5
U117 (0)
.01
B
Parametes for peer-to-peer interface :
1 = "Telegram
Fault signal trip .16
Peer-to-peer On/Off monitoring B
P790 (0) P798 (6030)
timeout"
P797 (0,000s) Telegram monitoring time B6030 B 1 = "Fault F012"
Baud rate 1s 15 0
P793 (6)
Binector / connector K6020
P791 (2) No. of words (1...5) B6031 converter
r799 Peer-to-peer diagnostic parameter
- G173 -
8-45
Function diagrams
1 2 3 4 5 6 7 8
8-46
Peer-to-peer interface 3
X162 0
.03
Word 3 K9003 K 0 Word 3
65 RS485 0 .04
M Word 4 K9004 [G183.6] K 33 Word 4
.05
Word 5 K9005 K 0 Word 5
U118 (0)
.01
B
Parameters for peer-to-peer interface:
1 = "Telegram .16
Peer-to-peer On/Off monitoring Fault signal trip B
P800 (0) timeout" P808 (9030)
P807 (0,000s) Telegram monitoring time B9030 B 1 = "Fault F013"
15 0
P803 (13) Baud rate 1s
Binector / connector K9020
P801 (2) No. of Words (1...5) B9031 converter
r809 Peer-to-peer diagnostic parameter
- G174 -
Data sets
SIEMENS AG 6RX1700-0AD76
Copy function data set Parameter
Sheet G175 Data sets
xxxx
Function data set bit 0
xxxx K0034
Target data set (1...4) from control word 2
xxxx
[G181.5]
xxxx
Source data set (1...4)
xxxx
Bico data set xxxx K0035
Target data set (1/2) from control word 2 xxxx
[G181.5] xxxx
Source data set (1/2) Note:
xxxx
The applicable parameters
xxxx
are identified by the
xxxx
code ".B"
...
- G175 -
8-47
Function diagrams
1 2 3 4 5 6 7 8
8-48
When P648 = 9, bit-serial input of control bits (P654 to P675 are effective)
Control word 1 When P648 <> 9, word-serial input of control bits (P654 to P675 are not effective) 15 14 13 12 11 10 9 Bit8
Terminals 37 and 38 are always active. They are ANDed with bit 0 or bit 3. r650
7 6 5 4 3 2 1 Bit0
Switch-on commmand from ON/OFF1 Control word 1
P648.B (9)
(from sheet "Crawling setpoint [G130.7] Bit No. Meaning K0030 Display of control word 1 (r650)
K
Function diagrams
[G140.3] 1 B0161
B
Bit 3 1=Enable, enable pulses to sequencing control [G136.1]
Enable operation
& 0=Pulse disable [G161.1]
(from Sheet "Binary inputs 1") P662.B (1) to sheet from optimization run
[G110.5] B Bit 4 1=Enable ramp-function generator
"Ramp-function generator" from control logic for field reversal
P655.B (1) 0=Set ramp-function generator to 0
[G136.3]
B P663.B (1)
B Bit 5 1=Ramp-function generator start to sheet "Ramp-function generator"
P656.B (1) 0=Ramp-function generator stop [G136.2]
B P664.B (1)
B Bit 6 1=Enable setpoint to sheet "Ramp-function generator"
P657.B (1) & 0=Disable setpoint [G136.1]
B
P key ≥1 B0179
E-Stop Bit 7 0 =>1 edge Acknowledge to sequencing control
from E-Stop, relay outp.line contactor (PMU)
P668.B (0)
[G117.7]
P658.B (1) B Bit 8 1=Inching bit 0 to sheet "Inching setpoint"
B [G129.2]
P669.B (0)
P659.B (1) to sheet "Inching setpoint"
B Bit 9 1=Inching bit 1
B & [G129.2]
P660.B (1) 1=Control by PLC <1>
Bit 10
B 0=No control by PLC
150ms P671.B (1)
P665.B (0) 1=Enable positive direction of rotation
B Bit 11 to sheet "Setpoint processing"
B 0=Positive direction of rotation disabled [G135.6]
P666.B (0) P672.B (1)
B Bit 12 1=Enable negative direction of rotation to sheet "Setpoint processing"
B ≥1 0=Negative direction of rotation disabled [G135.6]
P667.B (0) P673.B (0)
to sheet
B B Bit 13 1=Increase motorized potentiometer
"Motorized potentiometer" P360.01 (0ms)
[G126.2] (0...10000ms)
Pulse generator P674.B (0)
Bit 14 1=Decrease motorized potentiometer to sheet
B
<1> "Motorized potentiometer"
Bit 10 is displayed in connector K0030 and [G126.2] External fault 1
P675.B (1)
parameter r650 when control word 1 is 0=External fault 1 (F021)
input in word mode. It is not, however, B Bit 15 Fault F021
1=No external fault
functional. The mode of functioning of bit 10
is shown on Sheets G170, G171,
G172, Z110 and Z111
- G180 -
Control word 2
When P649 = 9, bit-serial input of control bits (P676 to P691 are effective)
When P649 <> 9, word-serial input of control bits (P676 to P691 are not effective) r651 31 30 29 28 27 26 25 Bit24
P649.B (9) Control word 2
23 22 21 20 19 18 17 Bit16
K Bit No. Meaning K0031
SIEMENS AG 6RX1700-0AD76
P677.B (0)
B Bit 17 Select function data set bit 1 to sheet "Data sets"
[G175.4]
Bit 18 Spare
Sheet G181 Control word 2
P680.B (0)
B Bit 20 Select fixed setpoint 0 to sheet "Fixed setpoint"
[G127.2]
P681.B (0)
B Bit 21 Select fixed setpoint 1 to sheet "Fixed setpoint"
[G127.2]
Bit 22 Spare
Bit 23 Spare
P360.02 (0ms)
P684.B (1) (0...10000ms)
B Bit 24 1=Enable speed controller droop to sheet "Speed controller (1)"
0=Speed controller droop disabled [G151.6]
P685.B (1) External fault 2
B Bit 25 1=Enable speed controller to sheet "Speed controller (2)"
0=Speed controller disabled Fault F022
[G152.6]
P686.B (1)
B Bit 26 0=External fault 2 (F022)
1=No external fault 2 P360.03 (0ms)
P687.B (0) to sheets (0...10000ms)
B Bit 27 0=Master drive (speed control) "Torque limitation" and
1=Slave drive (torque control) "Speed controller (2)"
P688.B (1) External alarm 1
[G160.2] [G152.4]
B Bit 28 0=External alarm 1 (A021)
Alarm A021
1=No external alarm 1
P689.B (1)
B Bit 29 0=External alarm 2 (A022)
1=No external alarm 2 P360.04 (0ms)
P690 (0) (0...10000ms)
B Bit 30 0=Select Bico data set 1
to sheet "Data sets"
1=Select Bico data set 2
[G175.4] External alarm 2
P691.B (0)
B Bit 31 Main contactor check-back signal to sequencing control Alarm A022
- G181 -
8-49
Function diagrams
1 2 3 4 5 6 7 8
8-50
Status word 1 [G170.6][G171.6]
[G172.6][G173.6] 15 14 13 12 11 10 9 Bit8
r652
[G174.6][Z110.6]
Status word 1 7 6 5 4 3 2 1 Bit0
Bit No. Meaning K0032
Function diagrams
0 = Pulses disabled
1 B0105
Bit 3 1 = Fault is active (pulses disabled)
from fault processing B0106
0 = No fault is active
1 B0107
Bit 4 0 = OFF2 applied
rom sequencing control B0108
1 = No OFF2 applied
1 B0109
Bit 5 0 = OFF3 applied
from sequencing control B0110 [G160.1][G160.2]
1 = No OFF3 applied
1 B0111
Bit 6 1 = Switch-on inhibit
from sequencing control 0 = No switch-on inhibit (converter can be switched on) B0112
1 B0113
Bit 7 1 = Alarm is active
from alarm processing B0114
0 = No alarm is active
1 B0115
Bit 8 0 = Setpoint/actual value deviation detected
from sheet "Signals (1)" B0116
1 = No setpoint/actual value deviation detected
[G187.6]
1 B0117
from sequencing control Bit 9 1 = PZD control requests (always 1)
from sheet "Signals (1)" Bit 10 1=Actual value ≥ comparison setpoint (P373) B0120
[G187.6] 0=Actual value < comparison setpoint (P373)
1 B0121
Bit 11 1 = Undervoltage fault (F006)
from fault processing B0122
0 = No undervoltage fault is active
[G117.5][G166.1] 1 B0123
Bit 12 1 = Request to energize main contactor
from relay output line contactor B0124
0 = Request not to energize main contactor
1 B0125
Bit 13 1 = Ramp-function generator active
from ramp-function generator B0126
0 = Ramp-function generator not active
[G136.7]
1 B0127
from sheet "Signals (2)" Bit 14 1 = Positive speed setpoint
B0128
[G188.3] 0 = Negative speed setpoint
1 B0129
Bit 15 Spare
- G182 -
SIEMENS AG 6RX1700-0AD76
Bit 17 Spare
[G188.7] 1 = No overspeed
1 B0137
from sequencing control Bit 19 1 = External fault 1 active (F021)
B0138
0 = No external fault 1 active
Bit 30 spare
Bit 31 spare
- G183 -
8-51
Function diagrams
1 2 3 4 5 6 7 8
8-52
Motor interface (1)
CUD1 P492.F
<1> r012.01
X174 0
Select Motor temperature
fault analog 1 1
temperature sensor
≥1 2
(PTC alarm) 01:1 P490.01
3
(PTC trip) 02:1 Motor temperature 1 <1>
(KTY84) 15:1 22
<3> K0051 0 Motor temperature
Motor temperature alarm (analog)
1 alarm analog 1 1
01:2 2
02:2 # ≥1 ≥1 1 = "Alarm A029"
15:2 23 2 3
Sheet G185 Motor interface (1)
0,6 s B0184
<5> P491.F
Alarm temperature
<1> Parameter r012 and connectors K0051 / K0052 output valid values only if a KTY84 is selected.
When a PTC is selected, r012 and K0051 / K0052 always output "0".
<2> Response temperature used depends on the type of PTC
<5> Use a shielded cable and connect it to ground at both ends - G185 -
SIEMENS AG 6RX1700-0AD76
Brush length monitoring (binary) + P495.F Brush length alarm (binary)
0 = Fault <1>
90:1 90:2 211 1 = "Alarm A025"
1 B0040 0
T 0 Brush length fault (binary)
1
2
B0041 1 = "Fault F025"
1
1 B0047 0 M o to r te m p e ra tu re
T 0
M 1 fa u lt (b in a ry)
215
2
1 = "Fault F028"
10s ON delay
216 B0183
217
M
- G186 -
8-53
Function diagrams
1 2 3 4 5 6 7 8
8-54
P388.F (3,00)
Signals (1) (0,00...199,99%) P390.F (3,0)
Setp./act.val. dev. (perm.) (0,0...100,0 s)
Setp./act.val. dev. (time)
n(set, smooth)
P590 (174) [G182.2]
1 0 T
Setpoint/act. value deviation
Function diagrams
P376.F (3,00)
Sheet G187 Messages (1)
P373.F (100,00)
(0,00...199,99%) P375.F (3,0)
n(comp.) (0,0...100,0 s)
Comparison (time)
n(act)
P592 (167) [G182.2]
1 0 T
[G151.3] K Comparison setpoint reached
to status word 1, bit 10
0
OFF delay
P374.F (3,00)
(0,00...199,99%)
n(comp.hyst.)
[G140.2]
P370.F (0,50) B0164 n<nmin
(0,00...199,99%)
OFF shutdown speed P088 (0,00)
(0,00...10,00 s)
1 B0165 Comparison (time)
n(act)
P593 (167) 1
[G151.3] K T 0
0 & Firing pulse disable
OFF1 or OFF3 from
(1 = Firing pulses disabled)
sequencing control
P371.F (0,50)
(0,00...199,99%)
OFF shutdown speed (hyst.) - G187 -
SIEMENS AG 6RX1700-0AD76
x [G200.1]
Sheet G188 Messages (2)
- G188 -
8-55
Function diagrams
1 2 3 4 5 6 7 8
8-56
Fault memory
K0801 <1>
K9812 K9813
K9811
Function diagrams
Fault No. r947.01 Fault value r949.01 Fault No. r947.09 Fault value r949.09 Fault No. r947.17 Fault value r949.17
Fault trip from
sequencing control .02 .02 .10 .10 .18 .18
.03 .03 .11 .11 .19 .19
.04 .04 .12 .12 .20 .20
.05 .05 .13 .13 .21 .21
.06 .06 .14 .14 .22 .22
Operation from .07 .07 .15 .23
sequencing control .15 .23
.08 .08 .16 .16 .24 .24
Sheet G189 Fault memory
Hours run Fault time (hours run) r049.01 Fault time (hours run) r049.02 Fault time (hours run) r049.03
r048
Current fault 1. acknowledged fault 2. acknowledged fault
Hours
run
meter
K9814 K9815 K9816
K0311
Fault No. r947.25 Fault value r949.25 Fault No. r947.33 Fault value r949.33 Fault No. r947.41 Fault value r949.41
.26 .26 .34 .34 .42 .42
.27 .27 .35 .35 .43 .43
.28 .28 .36 .36 .44 .44
<1> K0801: .29 .29 .37 .37 .45 .45
LOW byte: Current alarm number .30 .30 .38 .38 .46 .46
HIGH byte: Current fault number .31 .31 .39 .39 .47 .47
.32 .32 .40 .40 .48 .48
Fault time (hours run) r049.04 Fault time (hours run) r049.05 Fault time (hours run) r049.06
K9817 K9818
Fault No. r947.49 Fault value r949.49 Fault No. r947.57 Fault value r949.57
.50 .50 .58 .58
.51 .51 .59 .59
.52 .52 .60 .60
.53 .53 .61 .61
.54 .54 .62 .62
.55 .55 .63 .63
.56 .56 .64 .64
Fault time (hours run) r049.07 Fault time (hours run) r049.08
- G189 -
SIEMENS AG 6RX1700-0AD76
RS485 Receiving data K
Rx+/Tx+ 16Bit .08 activated on the master and
K6021 K
0 from Word 1 .09 the standby master when the
master K6022 K “master” function is transferred
1 Word 2 .10
K to the standby master
Rx-/Tx- 12..16 ≥1 Word 3 K6023
1 from Word 4 K6024 Word1 bit2 = Run
2..6 Slave 2 Word 5 K6025 bit3 = Fault
8-57
Function diagrams
1 2 3 4 5 6 7 8
8-58
Field reversal with SIMOREG single-quadrant converter
Function diagrams
1C1 1D1 3C 3D
(no delay) (not inverted)
X171
P775=0 P770.01=0
(CUD1)
M
Reverse polarity actual speed value K0167
to Sheet "Speed controller (2)" 54
[G188.5] B0215 [G151.2]
If < Ifmin
(from Sheet Messages 2) P092 (0,0...10,0s)
.01 (3,0s): Delay time for field reduction before
[G188.5] B0216 opening of the current field contactor
If < Ifx .02 (0,2s): Delay time before actuation of the
new field contactor *) Protective circuit
(from Sheet Messages 2)
.03 (0,1s): Delay time before enable of the
field firing pulses a) with protective resistor b) with varistor
Sheet G200 Field reversal with SIMOREG single-quadrant device
RS ≤ 1.5 kΩ
V1 = B32k420 (SIOV, block varistor)
- G200 -
NOTE
Freely assignable function blocks are enabled in parameter U977.
For enabling instructions, please refer to Section 11, Parameter List, description of parameters U977
and n978.
The setting for the sequence in which these function blocks are executed is made using parameters
U960, U961, U962, and U963.
8-60
Function diagram SIMOREG 6RA70 - Contents of the technology software in the basic converter, option S00
Content Sheet Content Sheet
Function diagrams
Startup of the technology software (option S00) B101 1 Position/positional deviation acquisition B152
1 Root extractor B153
Fixed values
100 Fixed values B110 Control elements
3 Integrators B155
Monitoring 3 DT1 elements B155
1 Voltage monitor for electronics power supply B110 10 Derivative/delay elements (LEAD / LAG blocks) B156 - B158
Alarm, fault messages Characteristics
8 Alarm message triggers B115 9 Characteristic blocks B160
Sheet B100 Table of contents
2. Setting and activating For each function block, it is necessary to define in which "time slice" (i.e. with which sampling time) it is processed.
(Note: In the factory setting of the parameters, all existing function blocks are activated)
SIEMENS AG 6RX1700-0AD76
the sampling times
5 time slices are available:
Time slice Sampling time Function block No. Setting with parameter
1 1 * T0 (firing-pulse-synchronous time slice) <1> 1 U950.01
2 2 * T0 (firing-pulse-synchronous time slice) <1> 2 U950.02
. .
4 4 * T0 (firing-pulse-synchronous time slice) <1> . .
3. Execution sequence The execution sequence of the function blocks can be defined with parameters U960, U961, and U962.
Sheet B101 Startup of the technology software (option S00)
4. Automatic setting The execution sequence of the function blocks and their activation can also be made automatic:
U969 = 1: Restore standard sequence
U960, U961, and U962 are set to the factory setting
= 2: Set optimum sequence
U960, U961, and U962 are set in such a way that as few deadtimes as possible occur
= 3: Set standard setting of the sampling times. U950, U951, and U952 are set to the factory setting!
= 4: Automatic activation/deactivation
U950, U951, and U952 are set in such a way that the unwired function blocks are deselected
and the wired function blocks are selected (activated), if they are not yet selected.
The time slice 10 (sampling time 20 ms) is set for all function blocks not previously activated,
unchanged for all previously activated function blocks. - B101 -
8-61
Function diagrams
1 2 3 4 5 6 7 8
8-62
Function diagrams
POWER ON
.01
U099 (0) K9501 100ms
.02
U099 (0) K9502
.03
U099 (0) K9503 B9050
POWER ON
10ms
.98
U099 (0) K9598 B9051
.99
U099 (0) K9599
.100 POWER OFF
U099 (0) K9600
Sheet B110 Voltage monitor for electronics power supply, fixed values
- B110 -
SIEMENS AG 6RX1700-0AD76
B 1 = F023 fault value 2 B 1 = F033 fault value 2
.03 .03
B 1 = F023 fault value 3 B 1 = F033 fault value 3
.04 .04
B 1 = F023 fault value 4 B 1 = F033 fault value 4
U104 (0)
.02 256
B 1 = "Alarm A019"
- B115 -
8-63
Function diagrams
1 2 3 4 5 6 7 8
8-64
3 connector/binector converters
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 <1> 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 <1>
B9052 B9068
B9053 B9069
B9054 B9070
B9055 B9071
B9056 B9072
B9057 10 B9073 11
B9058 B9074
B9059 B9075
B9060 B9076
B9061 B9077
B9062 B9078
B9063 B9079
B9064 B9080
B9065 B9081
B9066 B9082
Sheet B120 Connector / binector converters
B9067 B9083
B9084
B9085
B9086
B9087
B9088
<1> 7-segment display of bit fields
B9089 12 by converters n010, n011 and n012
B9090
B9091
15 14 13 12 11 10 9 Bit8
B9092
B9093 7 6 5 4 3 2 1 Bit0
B9094
B9095
B9096
B9097
B9098
B9099
- B120 -
SIEMENS AG 6RX1700-0AD76
B B
.08 .08
B B
.09 .09
B B
.10 .10
B B
.11 .11
B B
.12 .12
B B
.13 13 .13 14
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit field 4 K9113 Bit field 5 K9114
Binector / connector converter 1 Binector / connector converter 2
Sheet B121 Binector / connector converters
U115 (0)
.01
B
.02
B
.03
B
.04
B
.05
B
.06
B
.07
B
.08
B
.09
B
.10
B
.11
B
.12
B
.13 15
B
.14
B
.15
B <1> 7-segment-display of bit fields
.16 by converters n013, n014 and n015
B n015 <1>
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 15 14 13 12 11 10 9 Bit8
- B121 -
8-65
Function diagrams
1 2 3 4 5 6 7 8
8-66
15 adders / subtractors 4 sign inverters 2 switchable sign inverters
.01
20 .01 28
K K
.02 .02 U135 (0) U141 (0)
K K9120 K K9128 x y
.03 .03 K -1 K9135 B
K K
40
y = -x 35
U121 (0) 21 U129 (0) 29 U140 (0)
.01 .01 0
K K K
.02 .02 K9140
K K9121 K K9129 U136 (0)
.03 .03 x y 1
K K K -1 K9136
x y
-1
U122 (0) 22 U130 (0) y = -x 36
.01 .01 30
K K y = -x
.02 .02
K K9122 K K9130
.03 .03 U137 (0)
K K x y U143 (0)
K -1 K9137
B
U123 (0) 23 U131 (0) 31
.01 .01 y = -x 37 41
K K
.02 .02
K K9123 K K9131 U142 (0)
.03 .03 0
K K K
U138 (0) K9141
x y
K -1 K9138 1
Sheet B125 Adders / subtractors, sign inverters
U127 (0) 27
.01
K
.02
K K9127
.03
K
- B125 -
12 multipliers
SIEMENS AG 6RX1700-0AD76
.01 x1 .03 x1 .05 x1
K y K y K y
.02 x2 K9150 .04 x2 K9430 .06 x2 K9431
Sheet B130 Multipliers
K K K
x1 * x2 50 x1 * x2 290 x1 * x2 291
100% 100% 100%
x1 * x2 51 x1 * x2 292 x1 * x2
293
100% 100% 100%
x1 * x2 52 x1 * x2 294 x1 * x2 295
100% 100% 100%
x1 * x2
53 x1 * x2 296 x1 * x2
297
100% 100% 100%
- B130 -
8-67
Function diagrams
1 2 3 4 5 6 7 8
8-68
6 dividers 3 high-resolution multipliers / dividers
Function diagrams
U155 (1)
.01 x1 x4 (32Bit)
K y
U145 (1) U145 (1) .02 x2 K9155
.01 x1 .03 x1 K
K y K y .03 x3
.02 x2 K9145 .04 x2 K9142 K
K K x4= y= 55
x1 * x2 x4 / x3
x1 *100%
45 x1 * 100%
42
x2 x2
U156 (1)
U146 (1) U146 (1) .01 x1 x4 (32Bit)
.01 x1 .03 x1 K y
K y K y .02 x2 K9156
.02 x2 K9146 .04 x2 K9143 K
K K .03 x3
K
x4= y= 56
x1 *100%
46 x1 * 100%
43 x1 * x2 x4 / x3
x2 x2
Examples:
x1 x2 x3 y
With division by 0 (x2 = 0): With division by 0 (x3 = 0):
when x1 > 0: y = +199.99% when x4 > 0: y = +199.99% 100% 100% 100% 100%
when x1 = 0: y = 0.00% when x4 = 0: y = 0.00% 100% 40% 50% 80%
when x1 < 0: y = -199.99% when x4 < 0: y = -199.99% -200% -200% -200% -200%
- B131 -
3 limiters
B+ X>B+ B9156
y
B+
U175 FS
Sheet B134 Limiters
SIEMENS AG 6RX1700-0AD76
.04 x
K 0 x y K9176
U176.02 .05
K9174 K 9174 B–
(100,00)
.06
K9175 K 9175 B– X<B– B9157
-1
B+ X>B+ B9158
y
B+
U177 FS
.04 x
K 0 x y K9179
U178.02 .05
K9177 K 9177 B–
(100,00)
.06
K9178 K 9178 B– X<B– B9159
-1 213
B+ X>B+ B9295
y
B+
U179 FS
.04 x
K 0 x y K9262
U180.02 .05
K9260 K 9260 B–
(100,00)
.06
K9261 K 9261 B– X<B– B9296
-1 214
- B134 -
8-69
Function diagrams
1 2 3 4 5 6 7 8
8-70
4 absolute-value generators with filter 3 limiters
Function diagrams
0
B+ X>B+ B9154
y
U170 (0) Filter time B+
U179 FS
0...10000ms .01 x
U171 (0) K 0 x y K9173
U180.01 .02
63 K9171 K 9171 B–
-1 3 (100,00)
.03
U169 (0) K9172 K 9172 B– X<B– B9155
K -1 2 K9163
1 -1 67
0
- B135 -
Hysteresis Hysteresis
0,00...100,00 0,00...100,00
Filter time U188 (0,00) Filter time U196 (0,00)
K9180 K9184
0...10000ms 0...10000ms
U187 (0) U195 (0)
SIEMENS AG 6RX1700-0AD76
U186 (0,00) U188 U188 U194 (0,00) U196 U196
U185 FS |A|<B U193 FS |A|<B
0 B9160 .01 0 B9166
.01
K 0 A K 0 A
.02 B B A .02 B B A
K9181 K 9181 K9185 K 9185
U188 U196
B A B A
U188 U196
Sheet B136 Limit-value monitors with filter
Hysteresis
0,00...100,00
Filter time U192 (0,00)
K9182
0...10000ms
U191 (0)
U190 (0,00) U192 U192
U189 FS |A|<B
.01 0 B9163
K 0 A
.02 B B A
K9183 K 9183
U192
A<B
0 B9164
<1>
B A
71
U192/2
B A=B
0 B9165
B A
U192
8-71
Function diagrams
1 2 3 4 5 6 7 8
8-72
4 limit-value monitors without filter
Function diagrams
Hysteresis Hysteresis
0,00...100,00 0,00..100,00
U199 (0,00) U205 (0,00)
U199/2 U205/2
B A=B B A=B
0 B9171 0 B9177
B A B A
U199 U205
Hysteresis Hysteresis
Sheet B137 Limit-value monitors without filter
0,00...100,00 0,00...100,00
U202 (0,00) U208 (0,00)
U202/2 U208/2
B A=B B A=B
0 B9174 0 B9180
B A B A
U202 U208
Hysteresis Hysteresis
0,00...100,00 0,00...100,00
U212 (0,00) U218 (0,00)
SIEMENS AG 6RX1700-0AD76
U211 (0,00) U212 U212 U217 (0,00) U218 U218
U210 FS |A|<B U216 FS |A|<B
.01 0 B9181 .01 0 B9187
K 0 A K 0 A
.02 A .02 A
K9190 K 9190 B B K9192 K 9192 B B
U212 U218
U212/2 U218/2
B A=B B A=B
0 B9183 0 B9189
B A B A
U212 U218
Hysteresis
Sheet B138 Limit-value monitors without filter
0,00...100,00
U215 (0,00)
U215/2
B A=B
0 B9186
B A
U215
8-73
Function diagrams
1 2 3 4 5 6 7 8
8-74
4 averagers
Function diagrams
Sheet B139 Averagers
n n
16 18
U172 (0) averaging U172 (0) averaging
.01 x y .03 x y
K over K9455 K over K9457
n values n values
n n
17 19
U172 (0) averaging U172 (0) averaging
.02 x y .04 x y
K over K9456 K over K9458
n values n values
- B139 -
Maximum selection
SIEMENS AG 6RX1700-0AD76
U220 (0) U220 (0) U220 (0) U220 (0)
.01 x1 .04 x1 .07 x1 .10 x1
K K K K
.02 x2 y .05 x2 y .08 x2 y .11 x2 y
K MAX K9193 K MAX K9460 K MAX K9461 K MAX K9462
.03 x3 .06 x3 .09 x3 .12 x3
K K K K
Minimum selection
Sheet B140 Maximum selections, minimum selections
- B140 -
8-75
Function diagrams
1 2 3 4 5 6 7 8
8-76
2 tracking / storage elements
TRACK TRACK
U222 (0) U225 (0)
K x y K9195 K x y K9196
82 83
STORE STORE
Priority: Priority:
U223 (0) U226 (0)
.01 1. RESET .01 1. RESET
B RESET (y=0) 2. TRACK B RESET (y=0) 2. TRACK
.02 .02
B 3. STORE B 3. STORE
.03 .03
B B
2 connector-memories
(y=x) (y=x)
RESET 84 RESET 85
POWER ON POWER ON
(y=0) (y=0)
<2> <2>
SIEMENS AG 6RX1700-0AD76
U240 (0) U250 (0) U250 (0)
.01 0 .01 0 .03 0
K K K
.02 K9210 .02 K9215 .04 K9265
K K K
1 1 1
- B150 -
8-77
Function diagrams
1 2 3 4 5 6 7 8
8-78
High-resolution blocks
Hysteresis
0,00...100,00
68 U182.01 (0,00) 298
U098 (0)
.01 LOW
K
U182.01 U182.01 .02 HIGH KK9498
K
U181 (0) |A|<B
0 A B9680
.01
KK A
.02 B B
KK 299
U182.01 U098 (0)
.03 LOW
K
A<B .04 HIGH KK9499
0 A B9681 K
<1>
B
Sheet B151 High-resolution blocks
U182.01/2
B A=B
0 A B9682
B U182.01
Adders / subtractors
(for double-word connectors)
Hysteresis
0,00...100,00
69 U182.02 (0,00)
U132 (0) 48
.01
U182.02 U182.02 KK
.02
|A|<B KK KK9490
U181 (0) A B9683 .03
.03 0 KK
KK A
.04 B B K9491
KK
U182.02
A<B
0 A B9684
<1>
U132 (0) 49
B .04
KK
U182.02/2 .05
KK KK9492
B A=B .06
0 A B9685 KK
K9493
B U182.02
- B151 -
SIEMENS AG 6RX1700-0AD76
positional deviation B .01
U677 (0)
.02 KK9471
Position 1 U671 (0) U677 (0)
.01 .03
Reset B SET U677 (0)
.02 0 .04 KK9472
Set B
≥1 (y=x) U676 (9474) 0 U677 (0)
.05
Offset positional deviation KK U677 (0)
1 .06 KK9473
Priority: K9484
1. RESET
2. SET
Positional deviation U671 (0)
transformation ratio .05
Reset B SET
U673.F(10000) <1> .06 ≥1 (y=x)
Set B
Sheet B152 Position/positional deviation acquisition
Priority: KK9482
1. RESET RESET
U674.F(10000) <1> 2. SET POWER ON (y=0)
<2>
Position 2 U671 (0)
.03 Priority:
Reset B SET
.04 ≥1 1. RESET
Set B (y=x)
2. SET
<1> U873 must be set less than or equal to U674
Position 2 U672 (9472) .02 0
KK (otherwise F058 is output with fault value 14)
Set value
0 <2> from voltage monitor for electronics power supply
1
<3> Initial value is dependent on U678
RESET = 0: Initial value = 0
POWER ON y=initial value = 1: Initial value is set such that on POWER ON KK9481 or KK9482 assumes whatever
<2> <3> its setting value was before the electronics supply was disconnected.
- B152 -
8-79
Function diagrams
1 2 3 4 5 6 7 8
8-80
Root extractor Parameters:
[B152.8]
U684.001
U684.002
U680 (9483)
KK K9485
Input
U683.002
U683.001
Threshold Hysteresis
U681 (1) U682 (1)
U682 U682
0 B9686
U681 U681
1 B9687
- B153 -
3 integrators
y y y
SIEMENS AG 6RX1700-0AD76
U260 (0) x U264 (0) x U268 (0) x
x y x y x y
K K9220 K K9221 K K9222
Tn t Tn t Tn t
s
3 DT1 elements (transfer function: G(s) = Tv * ------------ )
1 + s T1
y y y
U272 (0) U275 (0) U278 (0)
y y y
K K9223 K K9225 K K9227
t t t
-1 K9224 -1 K9226 -1 K9228
- B155 -
8-81
Function diagrams
1 2 3 4 5 6 7 8
8-82
4 LEAD / LAG blocks
Transfer function:
1 + sTv
U551 (1) U553 (1) U551 (1) U553 (1)
Function diagrams
Tv T1 Tv T1
270 272
Derivative action time Filter time Derivative action time Filter time
0...10000ms 1...10000ms 0...10000ms 1...10000ms
U552.02 (100ms) U554.02 (100ms) U552.04 (100ms) U554.04 (100ms)
Sheet B156 Derivative / delay elements (LEAD / LAG blocks)
Tv T1 Tv T1
271 273
- B156 -
1 + sTv
U551 (1) U553 (1) U551 (1) U553 (1)
.05 .05 .07 .07 G(s) = ---------
K K K K
1 + sT1
Derivative action time Filter time Derivative action time Filter time
SIEMENS AG 6RX1700-0AD76
0...10000ms 1...10000ms 0...10000ms 1...10000ms
U552.05 (100ms) U554.05 (100ms) U552.07 (100ms) U554.07 (100ms)
Tv T1 Tv T1
Derivative action time Filter time Derivative action time Filter time
0...10000ms 1...10000ms 0...10000ms 1...10000ms
U552.06 (100ms) U554.06 (100ms) U552.08 (100ms) U554.08 (100ms)
Sheet B157 Derivative / delay elements (LEAD / LAG blocks)
Tv T1 Tv T1
275 277
- B157 -
8-83
Function diagrams
1 2 3 4 5 6 7 8
8-84
2 LEAD / LAG blocks
Transfer function:
U551 (1) U553 (1)
Function diagrams
Tv T1
278
U550 (0)
.09
K K9408
Tv T1
279
U550 (0)
.10
K K9409
- B158 -
9 characteristic blocks
Y values Y values Y values
U283.01 to .10 (0) U286.01 to .10 (0) U289.01 to .10 (0)
106 107 108
y 10 y 10 y 10
y10 y10 y10
SIEMENS AG 6RX1700-0AD76
x x x
y 10 y 10 y 10
y10 y10 y10
y 10 y 10 y 10
y10 y10 y10
8-85
Function diagrams
1 2 3 4 5 6 7 8
8-86
3 dead zones Setpoint branching
Function diagrams
Dead zone z
U291 (0,00) Minimum Maximum
speed speed
109 U297(0,00) U298(100,00)
y 112
U290 (0)
x -z y y
K K9232
z x U298
U297
U296 (0)
x -100% x y
K K9235
100%
-U297
Dead zone z
U293 (0,00) -U298
110 U299
Sheet B161 Dead zones, Setpoint branching
y
U292 (0) U299 (0,00)
x -z y
K K9233 Hysteresis
z x
Dead zone z
U295 (0,00)
111
y
U294 (0)
x -z y
K K9234
z x
- B161 -
SIEMENS AG 6RX1700-0AD76
Ramp-up time Ramp-down time
U302 (0,00) U303 (0,00)
0s 0s
113
Bypass simple ramp-function 0 1 0 1
generator
TH TR
U300 (0) x y
K K9236
y=x
freeze y y=0 B9190
Sheet B165 Simple ramp-function generator
U301 FS
.01 Stop simple ramp-function
B 0 R Q B9191
.02 generator
B 0
.03 0 = Ramp-function generator
B 1 initial run
1 = Enable simple ramp-function 1 S
generator
0 = Reset simple ramp-function
generator
Priority:
1. S (SET)
2. R (RESET)
POWER ON <2>
<1> When U301.01 = 9191, the ramp-function generator operates only once after it has been enabled (edge log. "0" to "1")
- B165 -
8-87
Function diagrams
1 2 3 4 5 6 7 8
8-88
Technology controller 114
U489 (0) Kp adaptation
K
U497.F(0,0)
Function diagrams
0%
Kp-factors
U496 (0) K9247 P component
0,10...30,00 0 1
U492.F U493.F X B
(1,00) (1,00) K9248 I component
Y Droop injection
n018
Y2
Y
1000 1 U507 (1) U511 (1)
Kp-factor U498.F U499.F
Y1 (100,00) (-100,00) U495.F(0) K K
1 0
X1 X2 X U508.F U512.F
(100,0) (100,0)
U483.F(0) U482.F(0,000)
Sheet B170 Technology controller
U485.F (0,00)
<1> 0 = D component acts only in actual-value channel
1 = Normal PID controller: D component is applied for control deviation - B170 -
U534 (1)
.01 P component
K K9301
SIEMENS AG 6RX1700-0AD76
I component
U537.01 U539.01 K9302 K9306
* -1
(3,00) (3,000 s)
Positive limit
K9303
Sheet B180 PI controller 1
8-89
Function diagrams
1 2 3 4 5 6 7 8
8-90
PI-controller Transfer function:
2 U538 (1) U542 (1)
.02 .02
K K 1 1 + sTn
261
U543.02
G(s) = --------- * Kp * ---------
U536 (1)
Function diagrams
U534 (1)
.02 P component
K K9311
I component
U537.02 U539.02 K9312 K9316
* -1
(3,00) (3,000 s)
Positive limit
K9313
Sheet B181 PI controller 2
U534 (1)
.03 P component
K K9321
SIEMENS AG 6RX1700-0AD76
I component
U537.03 U539.03 K9322 K9326
* -1
(3,00) (3,000 s)
Positive limit
K9323
Sheet B182 PI controller 3
8-91
Function diagrams
1 2 3 4 5 6 7 8
8-92
PI-controller Transfer function:
4 U538 (1) U542 (1)
.04 .04
K K 1 1 + sTn
263
U543.04
G(s) = --------- * Kp * ---------
U536 (1)
Function diagrams
U534 (1)
.04 P component
K K9331
I component
U537.04 U539.04 K9332 K9336
* -1
(3,00) (3,000 s)
Positive limit
K9333
Sheet B183 PI controller 4
U534 (1)
.05 P component
K K9341
SIEMENS AG 6RX1700-0AD76
I component
U537.05 U539.05 K9342 K9346
* -1
(3,00) (3,000 s)
Positive limit
K9343
Sheet B184 PI controller 5
8-93
Function diagrams
1 2 3 4 5 6 7 8
8-94
PI-controller Transfer function:
6 U538 (1) U542 (1)
.06 .06
K K 1 1 + sTn
265
U543.06
G(s) = --------- * Kp * ---------
U536 (1)
Function diagrams
U534 (1)
.06 P component
K K9351
I component
U537.06 U539.06 K9352 K9356
* -1
(3,00) (3,000 s)
Positive limit
K9353
Sheet B185 PI controller 6
U534 (1)
.07 P component
K K9361
SIEMENS AG 6RX1700-0AD76
I component
U537.07 U539.07 K9362 K9366
* -1
(3,00) (3,000 s)
Positive limit
K9363
Sheet B186 PI controller 7
8-95
Function diagrams
1 2 3 4 5 6 7 8
8-96
PI-controller Transfer function:
8 U538 (1) U542 (1)
.08 .08
K K 1 1 + sTn
267
U543.08
G(s) = --------- * Kp * ---------
U536 (1)
Function diagrams
U534 (1)
.08 P component
K K9371
I component
U537.08 U539.08 K9372 K9376
* -1
(3,00) (3,000 s)
Positive limit
K9373
Sheet B187 PI controller 8
U534 (1)
.09 P component
K K9381
SIEMENS AG 6RX1700-0AD76
I component
U537.09 U539.09 K9382 K9386
* -1
(3,00) (3,000 s)
Positive limit
K9383
Sheet B188 PI controller 9
8-97
Function diagrams
1 2 3 4 5 6 7 8
8-98
PI-controller Transfer function:
10 U538 (1) U542 (1)
.10 .10
K K 1 1 + sTn
269
U543.10
G(s) = --------- * Kp * ---------
U536 (1)
Function diagrams
U534 (1)
.10 P component
K K9391
I component
U537.10 U539.10 K9392 K9396
* -1
(3,00) (3,000 s)
Positive limit
K9393
Filter time K9395
Sheet B189 PI controller 10
U535.10 (0 ms)
Stop I component in
pos.direction and limit
K9390 PI-controller it to positive limit Controller at pos.
output limit
Kp Tn (K9395)
B9669
T1
1
Kp
U530 (0) 0 PI-controller output
.10 X 0 Y
K K9394
1 1
sTn 0 0
B9679
Stop I component in
neg.direction and limit Controller at neg.
Enable PI-controller output limit
it to negative limit
U531 (0) (K9397)
.10 0 = disable PI-controller <1> 1 B9659
B U545.10
.20 1 = freeze I component <5> U540.10 (1) U541.10 (1) Controller at
B (100,0) output limit
.30 1 = freeze output <3> 0 = Reset P 0 = Reset I
B
.40 1 = freeze I comp. in pos. direction <6> component component U544 (9396)
B .10
.50 1 = freeze I comp. in neg. direction <7> K K9397
B
Negative limit
Set PI-controller
U532 (0)
.10 1 = set I component <4> <1> disable PI-controller: <5> freeze I component: Priority:
B
.20 1 = set output <2> P component = 0 P component active 1. disable PI-controller
B I component = 0 I component is frozen 2. set output
output = 0 output = P component + I component 3. freeze output
<2> set output: <6> freeze I component in pos. direction: 4. set I component
U533 (0) P component active P component active 5. freeze I component
.10 setting value for I component
K I component = setting value - P component if controller input (X) is positive, 6. freeze I component in pos. direction
.20 setting value for PI-controller output 7. freeze I component in neg. direction
K output = setting value I component is frozen
<3> freeze output: output = P component + I component
P component active <7> freeze I component in neg. direction:
I component = frozen output - P component P component active
output is frozen if controller input (X) is negative,
<4> set I component: I component is frozen
P component active output = P component + I component
I component = setting value
output = P component + I component - B189 -
115
SIEMENS AG 6RX1700-0AD76
Actual velocity Normalization
(-32,768...32,767 m/s) U521 (16,38)
n021 (0,01...327,67m/s)
Actual speed Speed-velocity calculator
n020
U515 (0)
K n act v act K9256
U516 (0)
K v set nset K9257
vset ∗ i
nset = ----------------- ∗ 100%
D ∗ π ∗ nrated
D i n rated
Diameter
U517 (0)
K
- B190 -
8-99
Function diagrams
1 2 3 4 5 6 7 8
8-100
Variable inertia
Function diagrams
U525 (1)
.01
K D
.02
K
.03 Variable inertia
K Normalization diameter
.04
K of sleeve
U527 (10000)
(10...60000mm) D4 - DCore4
JV = ------------------ * K
Sheet B191 Calculation variable inertia
DCore Dmax4
Normalization of
max. diameter
U528 (10000) JV K9258
(10...60000mm)
Dmax
U529 (1,00)
(0,10...100,00)
- B191 -
3 Multiplexers
SIEMENS AG 6RX1700-0AD76
.02 .08
B B
.03 .09
Sheet B195 Multiplexer
B B
U311 (0) B3 B2 B1 B3 B2 B1
U313 (0)
K .01 X0 K .01 X0
U310 (0)
.04
B
.05
B
.06
B
B3 B2 B1 Y
B3 B2 B1
U312 (0)
.01 X0 0 0 0 X0
K
.02 X1 87 0 0 1 X1
K
.03 X2 0 1 0 X2
K
.04 X3 0 1 1 X3
K Y
.05 X4 K9451 1 0 0 X4
K
.06 X5 1 0 1 X5
K
.07 X6 1 1 0 X6
K
.08 X7 1 1 1 X7
K
- B195 -
8-101
Function diagrams
1 2 3 4 5 6 7 8
8-102
16-bit software counter
Maximum counting frequency = 1 / scanning time <3> Binary output
89
0...65535
n314
Function diagrams
Priority: U317 FS
1. Enable counter .01 Count up
B 0
2. Set counter UP OUT K9445
3. Stop counter
&
4. Count up / down .02 Count down
B 0
.03 Stop counter & DOWN
B 0 1
.04 Set counter (Binary code)
B 0
.05 Enable counter
B 1 1
Set counter
Minimum counter value U316 FS to minimum
.01 Minimum value
Sheet B196 16-bit software counter
POWER ON <1>
from sheet B110
Count down
<3> Example: The counter operates in the time slice 1 → max. counting frequency = 300 Hz 2 2
Overflow
Note: The sampling time and sequence of the upstream signal processor 7 7
must also be taken into account Underflow
- B196 -
SIEMENS AG 6RX1700-0AD76
Q0 Q0
U318 (0) B9250 U319 (0) B9270
.01 /Q0 .01 /Q0
B i0 B9260 B i0 B9280
.02 .02
B i1 Q1 B i1 Q1
.03 B9251 .03 B9271
B i2 /Q1 B i2 /Q1
B9261 B9281
Q2 Q2
B9267
- B200 -
8-103
Function diagrams
1 2 3 4 5 6 7 8
8-104
28 AND elements with 3 inputs each
Function diagrams
U320 (1) 120 U327 (1) 127 U334 (1) 134 U341 (1) 141
.01 .01 .01 .01
B B B B
.02 .02 .02 .02
B & B9350 B & B9357 B & B9364 B & B9371
.03 .03 .03 .03
B B B B
U321 (1) 121 U328 (1) 128 U335 (1) 135 U342 (1) 142
.01 .01 .01 .01
B B B B
Sheet B205 AND elements
U322 (1) 122 U329 (1) 129 U336 (1) 136 U343 (1) 143
.01 .01 .01 .01
B B B B
.02 .02 .02 .02
B & B9352 B & B9359 B & B9366 B & B9373
.03 .03 .03 .03
B B B B
U323 (1) 123 U330 (1) 130 U337 (1) 137 U344 (1) 144
.01 .01 .01 .01
B B B B
.02 .02 .02 .02
B & B9353 B & B9360 B & B9367 B & B9374
.03 .03 .03 .03
B B B B
U324 (1) 124 U331 (1) 131 U338 (1) 138 U345 (1) 145
.01 .01 .01 .01
B B B B
.02 .02 .02 .02
B & B9354 B & B9361 B & B9368 B & B9375
.03 .03 .03 .03
B B B B
U325 (1) 125 U332 (1) 132 U339 (1) 139 U346 (1) 146
.01 .01 .01 .01
B B B B
.02 .02 .02 .02
B & B9355 B & B9362 B & B9369 B & B9376
.03 .03 .03 .03
B B B B
U326 (1) 126 U333 (1) 133 U340 (1) 140 U347 (1) 147
.01 .01 .01 .01
B B B B
.02 .02 .02 .02
B & B9356 B & B9363 B & B9370 B & B9377
.03 .03 .03 .03
B B B B
- B205 -
SIEMENS AG 6RX1700-0AD76
≥1 ≥1 ≥1
.03 .03 .03
B B B
172
U352 (0) 152 U359 (0) 159 U366 (0) 166 U372 (0)
.01 .01 .01 .01
B B B B
.02 .02 .02 .02 =1 B9197
B ≥1 B9382 B ≥1 B9389 B ≥1 B9396 B
.03 .03 .03
B B B
173
U353 (0) 153 U360 (0) 160 U367 (0) 167 U373 (0)
.01 .01 .01 .01
B B B B
.02 .02 .02 .02 =1 B9198
B ≥1 B9383 B ≥1 B9390 B ≥1 B9397 B
.03 .03 .03
B B B
Sheet B206 OR elements, EXCLUSIVE OR elements
- B206 -
8-105
Function diagrams
1 2 3 4 5 6 7 8
8-106
16 inverters 12 NAND elements with 3 inputs each
Function diagrams
180 188
U380 (0) U388 (0) U400 (1) 200 U406 (1) 206
.01 .01
B 1 B9450 B 1 B9458 B B
.02 .02
B & B9470 B & B9476
.03 .03
B B
181 189
U381 (0) U389 (0)
B 1 B9451 B 1 B9459
U401 (1) 201 U407 (1) 207
.01 .01
B B
.02 .02
B & B9471 B & B9477
182 190 .03 .03
U382 (0) U390 (0) B B
B 1 B9452 B 1 B9460
.01 .01
183 191 B B
U383 (0) U391 (0) .02 .02
B & B9472 B & B9478
B 1 B9453 B 1 B9461 .03 .03
B B
- B207 -
14 RS flipflops
SIEMENS AG 6RX1700-0AD76
POWER ON
1 (Q=0) POWER ON
1 (Q=0) POWER ON
1 (Q=0)
<1> <1> <1>
Sheet B210 RS flipflops
Priority:
U419 (0) U424 (0)
.01 SET .01 SET 1. RESET
B Q B9558 B Q B9568 2. SET
.02 (Q=1) .02 (Q=1)
B B
219 224
RESET RESET <1> from voltage monitor for electronics power supply
1 Q B9559 1 Q B9569
POWER ON (Q=0) POWER ON (Q=0)
<1> <1>
- B210 -
8-107
Function diagrams
1 2 3 4 5 6 7 8
8-108
4 D flipflops
Function diagrams
Q B9491 Q B9495
1 1
POWER ON POWER ON
<1> <1>
Q B9493 Q B9497
Priority:
1. RESET
RESET (Q=0) RESET (Q=0) 2. SET
3. STORE
1 1
POWER ON POWER ON
<1> <1>
- B211 -
6 timers
SIEMENS AG 6RX1700-0AD76
ON delay ON delay ON delay
T O T O T O
0 0 0
240 242 244
OFF delay OFF delay OFF delay
O T O T O T
U440 (0) 1 U446 (0) 1 U452 (0) 1
.01 .01 .01
B B9580 B B9584 B B9588
T 3 T 3 T 3
- B215 -
8-109
Function diagrams
1 2 3 4 5 6 7 8
8-110
4 timers 5 binary signal selector switches
Function diagrams
T Mode T Mode
1 = Reset 1 = Reset
U472 (0)
.01 252
B
.02 0
U462 (0,00) U468 (0,00) B
.03 B9484
(0,00...600,00s) U463 (0) (0,00...600,00s) U469 (0) B
1
T Mode T Mode
ON delay ON delay
U473 (0)
T O T O .01 253
0 0 B
.02 0
247 249 B
OFF delay OFF delay .03 B9485
O T O T B
1 1 1
U461 (0) U467 (0)
.01 .01
B B9594 B B9598
.02 ON/OFF delay .02 ON/OFF delay
B T T B T T
2 2 U474 (0)
B9595 B9599
.01 254
1 1 B
Pulse generator Pulse generator .02 0
B
Sheet B216 Timers (0.00...600.00s), Binary signal selector switches
T T .03 B9486
3 3 B
1
1 = Reset 1 = Reset
- B216 -
Content Sheet
Data exchange with a technology board (TB) or the 1st communication board (CB) Z110
SIEMENS AG 6RX1700-0AD76
Data exchange with the 2nd communication board (CB) Z111
1st EB1 analog inputs Z112
1st EB1 analog outputs Z113
1st EB1 bidirectional inputs/outputs, digital inputs Z114
Sheet Z100 Table of contents
- Z100 -
8-111
Function diagrams
1 2 3 4 5 6 7 8
8-112
Data exchange with a technology board (TB) or the 1st communications board (CB)
Receive data n733.01 to .16 Transmit data
n735.01 to .16
Function diagrams
B3031 .16
B Valid for the following configurations:
- CB only
Fault message trigger - TB only
15 0 - CB after TB (CB in slot G)
1 = "Fault F082"
(fault value 10) Binector / connector K3020 - 2 CBs (for CB with the lower slot letter)
converter
For transmission of double-word connectors see Section 7.7.10
See also connector type converter on sheet Z124 - Z110 -
SIEMENS AG 6RX1700-0AD76
.05
Word 5 K8005 K Word 5
.06
Word 6 K8006 K Word 6
.07
Word 7 K8007 K Word 7
.08
Word 8 K8008 K Word 8
from supplementary board .09 to supplementary board
Word 9 K8009 K Word 9
Word 14 .14
the other bits of word 1, as well as words K8014 K Word 14
nd
1s
B8031 .16
B Valid for the following configurations:
Fault message trigger - 2 CBs (for CB with the higher slot letter)
15 0
1 = "Fault F082"
(fault value 10) Binector / connector K8020
converter
For transmission of double-word connectors see Section 7.7.10
See also connector type converter on sheet Z124 - Z111 -
8-113
Function diagrams
1 2 3 4 5 6 7 8
8-114
1st EB1: Analog input 1 (differential input)
Signal type Standardization U759.1 (0) U761.1 (1)
-1000,0...1000,0 U758.1 (0) B Time constant B
(0/1=10V/20mA) 0...10000ms
U755.1 (0) U756.1(100,0)
Hardware U760.1 (0) n762.1
Function diagrams
st
- Z112 -
SIEMENS AG 6RX1700-0AD76
U764.1 (0) -10,00...+10,00V
(0...10000ms) -200,00...+199,99V
U765.1 (0) n768.1 U766.1 (10,00) U767.1 (0,00)
K5104
-1 3 11 Bit + VZ Uout [V] = * Standardization [V] + Offset [V]
U763.1 (0) AO1 100%
x x y D
K -1 2 y [V] = * U766.1
100% A
-1 3 11 bits + sign
U763.2 (0) AO2
x x y D
K -1 2 y [V] = * U766.2
100% A 48
1
-10V...+10V
0
K5105
49
M K5105
Uout [V] = * Standardization [V] + Offset [V]
100%
- Z113 -
8-115
Function diagrams
1 2 3 4 5 6 7 8
8-116
1st EB1: 4 bidirectional inputs / outputs
38
24V M_external
Function diagrams
st
39 Outputs
Inputs
NOTICE
U769.1 (0)
B 1 B5104 If one of the terminals 43 to 46 is to be used as an
Out In 43 DIO1 23 Out
input, the corresponding output must be set to
B5105 "0" (transistor blocked)!
In
U769.2 (0) Example: Terminal 45 = input => U769.3=0
B 1 B5106
44 DIO2 24 Out
Out B5107
In
Out/In
U769.3 (0)
5V In B 1 B5108
45 DIO3 25 Out
24V
In B5109
U769.4 (0)
B 1 B5110
46 DIO4 26 Out
In B5111
Outputs
1 B5112
40 DI1 20 5V
B5113
24V
1 B5114
41
DI2 5V
21
B5115
24V Display of terminal states in n770.1 on the PMU
Sheet Z114 1 EB1: 4 bidirectional inputs- / outputs, 3 digital inputs
1 B5116
42
DI3 5V
22
B5117 46 45 44 43 42 41 40
24V
Inputs
n770.1
K5106
- Z114 -
AI1 -1 3
0
50 A 0 0%
U756.4 -1 2 K5201
u i 1
SIEMENS AG 6RX1700-0AD76
D * 100% -1
±10V ±20mA 1 1
51 Analog input
0
1 2 3 10V =100% Sign reversal Smoothing connection
X488 20mA=100% Offset
B5201 -100,00...100,00%
20mA 10V Open circuit (|i| ≤ 2mA) U757.4 (0,00)
- Z115 -
8-117
Function diagrams
1 2 3 4 5 6 7 8
8-118
2nd EB1: Analog outputs
Sheet Z116 2
Function diagrams
nd
-1 3 11 bits + sign
U763.4 (0) AO2
x x y D
K -1 2 y [V] = * U766.4
100% A 48
1
-10V...+10V
0
K5205
49
M K5205
Uout [V] = * Standardization [V] + Offset [V]
100%
- Z116 -
24V M_external
Sheet Z117 2
39
nd
Outputs
Inputs
U769.5 (0) NOTICE
B 1 B5204
Out In 43 DIO1 Out If one of the terminals 43 to 46 is to be used as an
23
SIEMENS AG 6RX1700-0AD76
input, the corresponding output must be set to
In B5205 "0" (transistor blocked)!
U769.6 (0) Example: Terminal 45 = input => U769.7=0
B 1 B5206
44 DIO2 24 Out
Out B5207
In
U769.8 (0)
B 1 B5210
46
DIO4 26 Out
In B5211
Outputs
1 B5212
40 DI1 20 5V
B5213
24V
1 B5214
41 DI2 21 5V
B5215
24V Display of terminal states in n770.2 on the PMU
EB1: 4 bidirectional inputs- / outputs, 3 digital inputs
1 B5216
42 DI3 22 5V
B5217 46 45 44 43 42 41 40
24V
Inputs
n770.2
K5206
- Z117 -
8-119
Function diagrams
1 2 3 4 5 6 7 8
8-120
1st EB2: Analog input (differential input)
U779.1 (0) U781.1 (1)
Signal type Standardization U778.1 (0) B Time constant B
(0/1=10V/20mA) -1000,0...1000,0 0...10000ms
U775.1 (0) Hardware U776.1(100,0) U780.1 (0) n782.1
smoothing 220 µs 11 bits + sign
AI
Function diagrams
±10V ± 20mA -1 3
st
0
49 A 0 0%
U776.1 -1 2 K5111
u i 1
D * 100% -1
1 1
50 Analog input
1 2 3 0 connection
10V =100% Sign reversal Smoothing
X498 20mA=100% B5121 Offset
-100,00...100,00%
20mA 10V Open circuit (|i| ≤ 2mA) U777.1 (0,00)
51
1st EB2: 2 digital inputs 1st EB2: 4 relay outputs
M_external
24V 38
22 39
DO1
40
52 Display of terminal states in n773.1 on the PMU
P24_aux 41
23
DO2
1 B5122
42
53 DI1 5V U774 (0)
B5123 45 43 41 39 54 53 .01 43
20 24V B 24
.02 DO3
B
.03 44
M_external B
1 B5124 .04
n773.1 B 45
54 DI2 5V 25
B5125 DO4
21 24V 46
K5113
M_external
Sheet Z118 1 EB2: Analog input, Analog output, 2 digital inputs, 4 relay outputs
- Z118 -
0
49 A 0 0%
U776.2 -1 2 K5211
u i 1
D * 100% -1
1 1
SIEMENS AG 6RX1700-0AD76
50 Analog input
1 2 3 0 connection
10V =100% Sign reversal Smoothing
X498 20mA=100% B5221 Offset
-100,00...100,00%
20mA 10V Open circuit (|i| ≤ 2mA) U777.2 (0,00)
51
2nd EB2: 2 digital inputs 2nd EB2: 4 Relay outputs
M_external 38
24V
22 39
DO1
40
52 Display of terminal states in n773.2 an der PMU
P24_aux 41
23
1 B5222
DO2
42
53 DI1 5V U774 (0)
B5223 45 43 41 39 54 53 .05 43
20 B 24
24V .06
B DO3
.07 44
M_external B
1 B5224 .08
n773.2 B
25 45
54 DI2 5V
B5225 DO4
1 46
2 24V
K5213
M_external
EB2: Analog input, Analog output, 2 digital inputs, 4 relay outputs
- Z119 -
8-121
Function diagrams
1 2 3 4 5 6 7 8
8-122
SBP pulse encoder evaluation
Reference speed
50.0...6500.0
U794 (500,0)
Function diagrams
Supply voltage
U791 = 0: 5V n795
U791 = 1: 15V
0 0
1 & 1
2
Encoder type Voltage level Number of lines &
U793=0: A/B track U790.01: A/B, CTRL track 100...20000
U793=1: Forward/reverse tracks U790.02: Zero pulse U792 (1024)
X401 <1>
Track A +
68
Track A Track A - B0055 Underflow
69
Track B +
70
Track B Track B - Pulse encoder evaluation Position acquisition B0056 Overflow
71
Zero pulse +
72 Position
Zero pulse Zero pulse - KK0036
73 value range:
8000 0000H to 7FFF FFFFH
CTRL +
74
Control track CTRL - = M B7000 Control track
75
<1> 0=Enable position counter (KK0036)
1=Reset (KK0036:=0)
<2> The signals "coarse pulse 2" and "fine pulse 2"
are only routed to binectors B7002 and B7003
in the SIMOREG DC Master.
They have no other function.
- Z120 -
SIEMENS AG 6RX1700-0AD76
1 = "Fault F015" i002: No. of CRC errors
U741.01 (0 ms) n748
0...6500ms i003: No. of timeout errors
i004: last accessible bus address
i005: Address node transmitting the
SLB node B7030 Telegram failure special "timeout" telegram
address
i006:Implemented bus cycle time
U740.01 (0) Monitoring is activated after the first valid telegram i007: Number of re-configurations
0...200
SLB channel
selection Dispatcher- Dispatcher
Sheet Z121 SIMOLINK board: Configuration, diagnosis
B7050
f Starting alarm
<1>
U746 + 3,18 µs 1
<1> f: No. of addressed nodes = ( ---------------------- – 2) • --------
6,36 µs U745
6,36 µs = time for 1 telegram
- Z121 -
8-123
Function diagrams
1 2 3 4 5 6 7 8
8-124
SIMOLINK board: Receiving, transmitting
Function diagrams
Word 1 K7101
B7200 B7215
Word 2 K7102
B7300 B7315
Word 3 K7103
B7400 B7415
Special Word 4 K7104
data B7500 B7515
Word 5 K7105
Word 6 K7106 B7600 B7615
Word 7 K7107 B7700 B7715
Word 8 K7108 B7800 B7815
B7900 B7915
For transmission of double-word connectors see Section 7.7.4 "Procedure for starting up SIMOLINK boards"
See also connector type converter on sheet Z124
- Z122 -
SIEMENS AG 6RX1700-0AD76
display of r059 display of r028 display of r025
Operating state Speed setpoint Speed controller act. value
6.0%0.0V 00
# 25.00%
∗
Fault
Run
Reversing key
The control commands from the OP1S panel are transferred via word 1 in the USS protocol ON key I Raise key
and can be wired up to other functions via the binectors below (see also Section 7.2.2).
8-125
Function diagrams
1 2 3 4 5 6 7 8
8-126
Interfaces: connector-type converters
Function diagrams
Technology board /
1st communications board (Z110) 2nd communications board (Z111) SIMOLINK board (Z122)
- Z124 -
24V 1 B4120
Binary input 2 B4 21
5V B4101
24V B4121
SIEMENS AG 6RX1700-0AD76
1
Binary input 3 B5 22
5V B4102
24V 1 B4122
Binary input 4 B6 23
5V B4103
24V 1 B4125
<1>
=Supply of binary Binary input 7 A4 26
inputs via SCI1 5V B4106
24V 1 B4126
=external supply Binary input 8 A5 27
of binary inputs 5V B4107
Sheet Z130 SCB1 with SCI1 as slave 1: binary inputs
24V 1 B4127
Binary input 9 A6 28
5V B4108
Supply for
binary inputs 24V 1 B4128
(optional)
Binary input 10 A7 29
5V B4109
A8
<1> <1> 24V 1 B4129
Reference point for
24V binary inputs 6 to 10
A1
B9
n699.01
B10
B11
P24
A2
~ Supply for the A9
~ ~ SCI1 board A10
~ 24V DC A11
M
- Z130 -
8-127
Function diagrams
1 2 3 4 5 6 7 8
8-128
SCB1 with SCI1 as slave 2: binary inputs
SCI slave 2
X427 0
Binary input 1 B3 2
5V B4200
Function diagrams
24V 1 B4220
Binary input 2 B4 21
5V B4201
24V 1 B4221
Binary input 3 B5 22
5V B4202
24V 1 B4222
Binary input 4 B6 23
5V B4203
24V 1 B4223
Binary input 5 B7 24
5V B4204
B8
24V 1 B4224
Reference point for
binary inputs 1 to 5
Binary input 6 A3 25
5V B4205
24V 1 B4225
<1>
= Supply of binary Binary input 7 A4 26
inputs via SCI1 5V B4206
24V 1 B4226
= external supply of Binary input 8 A5 27
binary inputs 5V B4207
Sheet Z131 SCB1 with SCI1 as slave 2: binary inputs
24V 1 B4227
Binary input 9 A6 28
5V B4208
Supply for
binary inputs 24V 1 B4228
(optional) Binary input 10 A7 29
5V B4209
A8
<1> <1> 24V 1 B4229
Reference point for
24V binary inputs 6 to 10
A1
B9
n699.05
B10
B11
P24
A2
~ Supply for the A9
~ ~ SCI1 board A10
~ 24V DC A11
M
- Z131 -
Binary output 1
2
SIEMENS AG 6RX1700-0AD76
Binary output 2
4
Binary output 3
6
Binary output 4
8
10
Binary output 5
n699.09 11
12
U698 (0)
.01 20 13
B
.02 21
B
.03 22 Binary output 6
B
Sheet Z135 SCB1 with SCI1 as slave 1: binary outputs
.04 23 14
B
.05 24
B 15
.06 25
B
.07 26 16
B
.08 27
B Binary output 7
17
18
B1 Binary output 8
driver P24 VDC
B2
driver 100 mA
short-circuit-proof
X427
- Z135 -
8-129
Function diagrams
1 2 3 4 5 6 7 8
8-130
SCB1 with SCI1 as slave 2: binary outputs X429
1
Binary output 1
Function diagrams
Binary output 2
4
Binary output 3
6
Binary output 4
8
10
Binary output 5
n699.13 11
12
U698 (0)
.13 20 13
B
.14 21
B
.15 22 Binary output 6
B
Sheet Z136 SCB1 with SCI1 as slave 2: binary outputs
.16 23 14
B
.17 24
B 15
.18 25
B
.19 26 16
B
.20 27
B Binary output 7
17
18
B1
Binary output 8
B2 100 mA short-circuit-proof
X427
- Z136 -
SIEMENS AG 6RX1700-0AD76
B4101 B4109
binary inputs B9 A9
24V 1 B4127 24V 1 B4135
(optional)
<1> n699.01
24V
<1> Reference point for Reference point for
binary inputs 1 to 8 binary inputs 9 to 16
B10
B11 <1>
=Supply of binary
B12
P24 inputs via the SCI2
~ A10
~ ~ A11
~ 24V DC A12 = external supply of
M
binary inputs
Supply of
SCI2 board X437
- Z140 -
8-131
Function diagrams
1 2 3 4 5 6 7 8
8-132
SCB1 with SCI2 as slave 2: binary inputs
X437 X437
Binary input Binary input
SCI slave 2 SCI slave 2
Function diagrams
1 B1 20 9 A1 28
5V B4200 5V B4208
binary inputs B9 A9
24V 1 B4227 24V 1 B4235
(optional)
<1> n699.05
24V SCB1/SCI
<1> Reference point for Reference point for process data
binary inputs 1 to 8 binary inputs 9 to 16
B10
B11 <1>
=Supply of binary
B12
P24 inputs via SCI2
~ A10
~ ~ A11
~ 24V DC A12 =external supply of
M
binary inputs
Supply for the
SCI2 board X437
- Z141 -
Binary output 1
2
3
SIEMENS AG 6RX1700-0AD76
Binary output 2
4
5 X438
Binary output 3
6 B1
Binary output 4
B3
8
Binary output 9
9 B4
10
B5
Binary output 5
11 Binary output 10
B6
12
A1
13
Binary output 11
A2
Binary output 6
n699.09 14
Sheet Z145 SCB1 with SCI2 as slave 1: binary outputs
A3
15
U698 (0) Binary output 12
.01 20 16 A4
B
.02 21
B Binary output 7
.03 22 A5
B 17 P24 Auxiliary voltage P24 VDC
.04 23
B
.05 24 18 A6 Auxiliary voltage M for
B M binary outputs
.06 25
B
.07 26
B
.08 27
B
.09 28
B
.10 29
B
.11 210
B
.12 211
B
- Z145 -
8-133
Function diagrams
1 2 3 4 5 6 7 8
8-134
SCB1 with SCI2 as slave 2: binary outputs
X439
1
Function diagrams
Binary output 1
2
3
Binary output 2
4
5 X438
Binary output 3
6 B1
Binary output 8
7 B2
Binary output 4 B3
8
Binary output 9
9 B4
10
B5
Binary output 5
11 Binary output 10
B6
12
A1
13
Binary output 11
A2
Binary output 6
n699.13 14
Sheet Z146 SCB1 with SCI2 as slave 2: binary outputs
A3
15
U698 (0) Binary output 12
.13 20 16 A4
B
.14 21
B Binary output 7
.15 22 A5
B 17 P24 Auxiliary voltage P24 VDC
.16 23
B
.17 24 18 A6 Auxiliary voltage M for
B M binary outputs
.18 25
B
.19 26
B
.20 27
B
.21 28
B
.22 29
B
.23 210
B
.24 211
B
- Z146 -
SIEMENS AG 6RX1700-0AD76
0...2 Offset Smoothing
U690.01(0) -20,00...20,00V 0...15
<1> U692.01(0) U691.01(2) n699.02
<2>
3 12 bits + sign SCI Slave 1
U
±10V 3 A
6
A
K4102 Analog input 2
7
D
8
Sheet Z150 SCB1 with SCI1 as slave 1: analog inputs
Hardware-
Smoothing 1ms
Signal type
0...2 Offset Smoothing
U690.03(0) -20,00...20,00V 0...15
<1> U692.03(0) U691.03(2) n699.04
<2>
12 bits + sign
9 A
10 K4103 Analog input 3
D
11
Hardware-
Smoothing 1ms
X428
Changes to parameters U690, U691 or U692 do not take
effect until the system is reconfigured (e.g. using U710=0). - Z150 -
8-135
Function diagrams
1 2 3 4 5 6 7 8
8-136
<1> Signal type
SCB1 with SCI1 as slave 2: analog inputs U690 Voltage input Current input
Kl. X428.3, .6, .9 Kl. X428.5, .8, .11
2 - 4 ... 20 mA
2 -10 V / 5 mA for potentiometer, short-circuit-proof
6
A
K4202 Analog input 2
7
D
8
Sheet Z151 SCB1 with SCI1 as slave 2: analog inputs
Hardware-
Smoothing 1ms
Signal type
0...2 Offset Smoothing
U690.06(0) -20,00...20,00V 0...15
<1> U692.06(0) U691.06(2) n699.08
12 bits + sign <2>
9 A
10 K4203 Analog input 3
D
11
Hardware-
Smoothing 1ms
X428
Changes to parameters U690, U691 or U692 do not take
effect until the system is reconfigured (e.g. using U710=0). - Z151 -
Gain Offset
-320,00...+320,00V -100,00...+100,00V X428
n699.10 U694.01 (10,00) U695.01 (0,00)
SIEMENS AG 6RX1700-0AD76
U693.01(0) x y
x D 12
K y [V] = * U694.01
100% A
13
U 14
Gain Offset I
-320,00...+320,00V -100,00...+100,00V
n699.11 U694.02 (10,00) U695.02 (0,00) Iout = -20 ... 20 mA
U693.02(0) x y
x D 15
K y [V] = * U694.02
100% A
16
Analog output 2
M
U 17
Sheet Z155 SCB1 with SCI1 as slave 1: analog outputs
Gain Offset I
-320,00...+320,00V -100,00...+100,00V
n699.12 U694.03 (10,00) U695.03 (0,00) Iout = -20 ... 20 mA
U693.03(0) x y
x D 18
K y [V] = * U694.03
100% A
19
Analog output 3
M
U 20
I
Iout = -20 ... 20 mA
Changes to parameters U694 or U695 do not take
effect until the system is reconfigured (e.g. using U710=0).
- Z155 -
8-137
Function diagrams
1 2 3 4 5 6 7 8
8-138
SCB1 with SCI1 as slave 2: analog outputs
Function diagrams
Gain Offset
-320,00...+320,00V -100,00...+100,00V X428
n699.14 U694.04 (10,00) U695.04 (0,00)
U693.04(0) x y
x D 12
K y [V] = * U694.04
100% A
13
Analog output 1
M
U 14
Gain Offset I
-320,00...+320,00V -100,00...+100,00V
n699.15 U694.05 (10,00) U695.05 (0,00) Iout = -20 ... 20 mA
U693.05(0) x y
x D 15
K y [V] = * U694.05
100% A
16
Analog output 2
M
U 17
Sheet Z156 SCB1 with SCI1 as slave 2: analog outputs
Gain Offset I
-320,00...+320,00V -100,00...+100,00V
n699.16 U694.06 (10,00) U695.06 (0,00) Iout = -20 ... 20 mA
U693.06(0) x y
x D 18
K y [V] = * U694.06
100% A
19
Analog output 3
M
U 20
I
Iout = -20 ... 20 mA
Changes to parameters U694 or U695 do not take
effect until the system is reconfigured (e.g. using U710=0).
- Z156 -