The HGM type maximizes diversity in product selection by developing a variety of products.
In addition, the newly developed HGM1250&1600 MCCB is an electronic type, so its characteristics can be adjusted.
1,250 AF
1: Long time delayed tripping current.
3: Short-time delayed tripping current
Upon Request Type 5: Instant opening current
I1 0,7 0,8
0,9
I2 5 6
7
I3 5 6
7
t1 0,6 0,95 4 8 4 8
0,5 1 xIn 3 10 xI1 3 10 xI1
0,4 2 2
t2 t1(s) t2(s) O n I ² t Of f L3 LED
8
4 12 0,3 0,05 0,1
L1 L2 L3
2 16 0,2 0,2
I1 I2 I3 @ 6 I1 1 20 0,1 0,05 0,3
Over current
0,5 I>0.2xIn I>I 1
LED
· The desired value can be set between %40 and %100 of I1 switch
and In breaker value.
· I2t "OFF"; When larger current pass over circuit breaker other than
the set I2, trips the circuit breaker at the end of fixed time delays.
· I2t "ON"; There are time delay in proportion with (8xI1)2 at the "ON"
section. Card detects period of time in inverse proportion with the
square root of the tripping current. (Tripping time)=[(8xI1)2/I2]xt2
· I3 switch can be adjusted between 2 and 10 times the current I1.
There is no any delay function.
·L
1, L2, L3; Indicates on which phase the over current passes through.
· I>0.2xIn; Indicates that the card is operational and current passes
through the circuit breaker.
· I>I1; Indicates that current passes through the circuit breaker and if
the situation does not return to normal, In accodance with release
curve the circuit breaker will trip after a while.
1,600 AF
Recognition code
S S S
for order
AC660/690 V 25 25 25
Rated short-circuit
breaking capacity AC480/500 V 35 35 35
[Icu] (kA rms)
AC440/460 V 45 45 45
AC380/415 V 70 70 70
AC220/240 V 50 50 70
Trip Device
● ● ●
Long time [LT, I1] 0.4-0.5-0.6-0.7-0.8-0.9-0.95-1×In 0.4-0.5-0.6-0.7-0.8-0.9-0.95-1×In 0.4-0.5-0.6-0.7-0.8-0.9-0.95-1×In
Electronic
Short time [STD, I2] 2–3–4–5–6–7–8-10×I1 2–3–4–5–6–7–8-10×I1 2–3–4–5–6–7–8-10×I1
Accessory
● ● ●
Internal
Shunt trip SHT
Draw-out - - -
External TDM(LINE/LOAD) - - -
Plug-in
TDM(LINE Only) - - -
Plug-in - - -
HGM1000/1250
Unit : mm
3P 4P
70 70 47 70 70 70
70 16 70 70
14.5
4-Ø6 or M6 Tap 6-Ø6 or M6 Tap
23 Mounting Screw
M6xL50
280
46 54.5
45 8
Ø13 46.5
14.5
70.25 40.25
40.25
338
340
110.5
274
325
370
496
110
61.25
14.5
45 45 Ø13 43.5 22.5 Ø13
210 121.5
124 45 45
138.5 280
181
264
40.25
40.5
40.5
40.5
40.25
40.25
110.5
110.5
111
111
186.75
186.75
HGM1600
Unit : mm
70 70 42,5
70 20
4-Ø6,5 or M6 Tap
16
Mounting Screw
M6 x L50
280
154
46
307,5
338
370
110
70,5
55,5
64
105
154
16 46
Mounting Screw 45
M6 x L50 70
15
Ø13 Ø13
152,5
32
Ø13
Hexagon Head Bolt
32
M12 x L55
46
46
46
110
110
200
10000,00 10000,00
I1=(0,4-1)In I1=(0,4-1)In
1000,00 1000,00
Time (sec)
10,00 10,00
I2=(2-10)I1 I2=(2-10)I1
t2=0.05-0,3s t2=0.05-0,3s
1,00 1,00
0,10 0,10
I2t off:t=t2 I2t off:t=t2
0,01 0,01
0,10 1,00 10,00 0,10 1,00 10,00
100,000
100,000
Energy (kA2s)
Energy (kA2s)
10,000
10,000
1,000
100 1,000
10 100 10 20 30 40 50 60 70 80 90 100
100 100
Current (kApeek)
Current (kApeek)
10 10
1 1
10 20 30 40 50 60 70 80 90100 10 20 30 40 50 60 70 80 90100
Ordering guidelines
① Type
② Frame
④ Number of Poles
⑤ Product Description
⑥ Mounting
⑨ Frequency
⑩ Rated Current
⑪ Trip Device
① Type ④ Number of Poles ⑦ Auxiliary Contact & Alarm Switch(AUX/ALT) ⑩ Rated Current
② Frame ⑤ Product Description ⑧ Shunt Trip & Under Voltage Trip Devices(SHT/UVT) ⑪ Trip Device
Sales Office 5th Floor 55, Bundang-ro, Bundang-gu, Seongnam-si, Tel : +82-31-8006-6780, 6786 Fax : +82-31-8006-6629
Gyeonggi-do, Korea
Branch Offices
Atlanta 6100 Atlantic Boulevard, 2nd FL., Norcross, GA30071, U.S.A Tel : +1-678-823-7839 Fax : +1-678-823-7553
Osaka 5th Floor Nagahori Plaza Bldg. 2-4-8 Minami Senba, Chuo-ku, Tel : +81-6-6261-5766~7 Fax : +81-6-6261-5818
Osaka 542-0081, Japan
Moscow World Trade Center, Ent.3, #703, Krasnopresnenskaya Nab.12, Tel : +7-495-258-1381
Moscow, 123610, Russia
Dubai Unit 205, Emaar Square Building No.4 Sheikh Zayed Road, Tel : +971-4-425-7995 Fax : +971-4-425-7996
Dubai 252458, U.A.E
Bangkok 19th Floor, Unit 1908, Sathorn Square Office Tower, 98 North Tel : +66-02-115-7920 Fax : +66-2-115-7898
Sathorn Road, Silom, Bangrak, Bangkok 10500, Thailand
www.hyundai-electric.com