TANK EXTERIOR PE CONTAINED CATHODIC PROTECTION DESIGN WORKSHEET
IMPRESSED ANODES
(The following CP design is based on client supplied information)
COMPANY : PDVSA Color Form and pretabulated information.
PROJECT : Tank Bottom Color Information & options entered by Design Engineer.
LOCATION : 61 Meter Diameter Color Spreadsheet calculations based on entered data.
DATE : 03/08/24 Color Design Engineer's recommended CP system.
The CP design options must be determined
Calculate Total External Tank Bottom Surface Area: and manually entered by the engineer.
Tank Height (feet) : 0
Tank Diameter (feet) : 200.00 31,415.93 sf (Total Surface Area )
(meters): 60.976 or 2,918.65 sm (Total Surface Area )
Current Requirement:
% Bare = 100 Current Density = 1 (mA/sf)
10.8 (mA/sm)
I = Area* C.D.* (%Bare) = (Current Req'd ) = ### mA
Based on Life
I/Anode Feet Life CP
(ma) Req'd Years Design
50.00 6283.19 40.00 <<<<<
7853.981634
Metros 1915.6 % 2394.51
Comment 5,240 feet of MMO anode is required based on soil and circuit resistance. The anode current distribution
and life requires additional material (1,697'+) and is the controlling factor. The anode life, based
on complete consumption of the proposed material (7,937' of MMO), is between 25 to 40 years.
733401798.xls