HVA Report M74-L3


Company ABB Location Puerto Bolívar, Machala
Customer PO# YILPORT Owner IELMESA S.A.
Job # PBOJV-ADM-SCT-003 Owner Representative IELMESA S.A.
Date 1/17/2024 11:32:00 AM Temperature 30.5 °C
Tested by IELMESA S.A. Humidity 62.2 %
Substation RSS RMU46-RSS TRX46 Position RSS RMU46-RSS TRX46
Circuit ID M74-L3
________________________
________________________
________________________
________________________
Device Under Test is Cable
Rated Voltage 15.0 kV Operating Voltage 13.8 kV
Manufacturer VATAN KABLO Model NA2XS
Insulation Type XLPE Insulation Thickness 450 mm
Shield Type Cu Grounding YES
Conductor Size 3Cx95 sqmm Conductor Material Al
# of Conductors 1 Length 10 m
Installed in 2023 Age <1 year
Cable Test End 17/01/2024 Cable Far End SS-RR46 Trafo
Termination near SS-RR46 Termination far SS-RR46 Trafo
# of Splices 0 Splice Locations N/A
Jacket Yes Jacket Integrity OK
________________________
________________________
________________________
________________________
Equipment
Equipment Used GH5237 Serialnumber GH5237.23K004
________________________
________________________
________________________
________________________
Test Setup
Type of HV Test Diagnostic Test Test Voltage 0.5 / 5.0 / 15.0 / 24.0 kVrms
Waveform Sine Planned Test Duration 1 / 1 / 1 / 15 min
Frequency 0.1 Hz Current Limit Trip out on Arc
________________________
________________________
________________________
________________________
Measurements / Results
Breakdown No Breakdown Voltage
Time to Failure
M74 finished successfully
Step Voltage Current Capacitance Resistance Frequency
1 0.5 kVrms 3.0 uArms 9.48 nF 19 GOhm 0.1 Hz
2 5.0 kVrms 11 uArms 3.48 nF >20 GOhm 0.1 Hz
3 15.0 kVrms 31 uArms 3.28 nF 13 GOhm 0.1 Hz
4 24.0 kVrms 48 uArms 3.19 nF 12 GOhm 0.1 Hz

Test is X Acceptable Unacceptable

Comments The VLF electrical testing analysis on the cable M74 on phase L3 indicates
thatwith an injection voltage of 24 kVrms (34 kV peak) for 15 minutes,
according to the IEC 60502-2 (2014) standards, there was no arc discharge,
passing thetest. The cable can be energized.