Professional Documents
Culture Documents
Final Exam Solution EE4035 PSPA202203
Final Exam Solution EE4035 PSPA202203
Final Exam Solution EE4035 PSPA202203
Serial No:
EE4035 - Power System Final Exam
Protection Total Time: 03 Hour
Wednesday, December 21, 2022 Total Marks: 100
Course Instructor
________________
Dr. Muhammad Jafar Signature of Invigilator
SOLUTION
___________________________ __________ __________ _____________________
Student Name Roll No Section Signature
Marks Obtained
i. State whether this scheme is used to block tripping for stable power swings or unstable power
swings.
ii. Suppose that measured impedance reaches point A on the characteristic diagram at 𝑡 = 0.
The contact of the blocking relay closes immediately, and a timer coil is activated. The
impedance measurement continues on the locus and reaches point C at 𝑡 = 5 ms. The timer
set value in the circuit diagram is 𝑇𝑒 = 10 ms. Will the distance scheme trip the circuit breaker
or not? The distance scheme contact is 𝑍1 which closes as soon as the impedance
measurement reaches point C. Explain your answer in one sentence.
[1+2]
Solution:
i.
The scheme is used to block tripping for stable power swings.
ii.
The distance scheme will trip because the impedance enters the distance relay’s operation zone
before the normally-closed contact of the timer coil opens to block it.
i. State whether the scheme trips or restrains tripping during a violent power swing.
ii. Fill out the table with “Trip” or “Restrain” for each relay when the measured impedance is at a
location given by the underlined letters in the diagram.
Location of measured “Trip” or “Restrain”
impedance Mho relay Blinder B1 Blinder B2
Q
R
S
T
[1+12]
Solution:
i.
The scheme is used to trip the circuit breaker during a violent power swing.
ii.
Location of measured “Trip” or “Restrain”
impedance Mho relay Blinder B1 Blinder B2
[9]
i.
Since |𝐒𝐨 | > |𝐒𝐫 |, the amplitude comparator will generate a trip output.
ii.
The inputs to the cosine-type phase comparator will be as under:
𝐒𝐦 = 𝐒𝐨 + 𝐒𝐫 = 1∠0° + 0.5∠120° = 1 + 0.5(−0.5 + 𝑗0.866) = 0.75 + 𝑗0.433 = 0.866∠30°
𝐒𝐩 = 𝐒𝐨 − 𝐒𝐫 = 1∠0° − 0.5∠120° = 1 − 0.5(−0.5 + 𝑗0.866) = 1.25 − 𝑗0.433 = 1.322∠ − 19.11°
𝐒𝐦
Arg ( ) = 30° − (−19.11°) = 49.11° < 90° & > −90°
𝐒𝐩
Therefore, the cosine-type phase comparator will also generate a trip output.
ii.
iii.
Hints:
Calculate the rated line current on the 𝑌-side using the equation:
𝑆
𝐼𝑌𝑟𝑎𝑡𝑒𝑑 =
√3𝑉
Calculate the maximum current on the 𝑌-side using the allowable overload percentage.
Select the CT ratio based on the maximum allowable current value calculated.
Calculate the plug setting of the relay using the equation:
𝐼𝑌𝑚𝑎𝑥
𝑃𝑆 =
𝐶𝑇𝑅
[7]
Solution:
The line current on the 𝑌-side is:
50 ∗ 1000000
𝐼𝑌𝑟𝑎𝑡𝑒𝑑 = = 218.7 A
√3 ∗ 132 ∗ 1000
The starting current in Amperes will need the calculation of the base current on the low-voltage side
which is calculated as under:
𝑆𝐵𝑇 1000000
𝐼𝐵𝑇𝑋 = = = 175 A
√3 ∗ 𝑉𝐵𝑇𝑋 √3 ∗ 3300
The starting current on the low-voltage side is thus:
𝐼𝑠𝑡𝑎𝑟𝑡𝑇𝑋 = 𝐼𝑠𝑡𝑎𝑟𝑡𝑇𝑝𝑢 ∗ 𝐼𝐵𝑇𝑋 = 2.419 ∗ 175 = 423.3 A
[1+2+10]
Solution:
i.
Since all phases of a generator should be able to handle the same current magnitude, the current
rating of the third phase is also 7000 A.
This current flows through the two equal halves, therefore, the rating of each half of the winding is
7000/2 = 3500 A.
ii.
The required CT ratio is 3500/5 A.
iii.
We need to work our way backwards from the current in the overcurrent relay which is 1 A.
Similarly, the healthy half of the winding carries its rated current equal to 3500 A.
Hence the CT secondary at the bottom will carry 5 A.
For KCL to be satisfied in the secondary circuit, the CT secondary for the faulty half should carry 4 A.
This implies that the primary of this CT should carry 4 ∗ 3500/5 = 2800 A.
The diagram is redrawn with proper values indicated at all arrows of phase-𝑐.