TX Tap Calculation
TX Tap Calculation
TX Tap Calculation
Primary Voltage
Nominal tap (100% tap) Actual Primary
Tap after tap changer
Primary Voltage (V1) Voltage (V1)
(V)
11000 -5.0% 10450 11000
ap Calculation (11kV)
Actual Primary Normal tap (100% tap) Secondary
Ratio
Voltage (V1) Primary Voltage (V2) Voltage
11000 415 25.2 437
Key in data or editable area
Transformer settings
Tap Primary Sec. Voltage Turns Actual Sec. voltage
Setting Voltage (V) (V) Ratio (V)
5% 11550 27.8 395
2.5% 11275 27.2 405
0% 11000 415 26.5 415
-2.5% 10725 25.8 426
-5% 10450 25.2 437
Example 1. when the tap setting is at 0% and the actual voltage drop below the primary setting voltage then the actual sec volt
Transformer settings
Tap Primary Sec. Voltage Turns Actual Sec. voltage
Setting Voltage (V) (V) Ratio (V)
5% 11550 27.8 375
2.5% 11275 27.2 385
0% 11000 415 26.5 394
-2.5% 10725 25.8 404
-5% 10450 25.2 415
a or editable area
𝑉_2=𝑉_1/(𝑇𝑢𝑟𝑛𝑠 𝑅𝑎𝑡𝑖𝑜)