Transformer Tap Calculation (11kV)

Primary Voltage
Nominal tap (100% tap) Actual Primary
Tap after tap changer
Primary Voltage (V1) Voltage (V1)
(V)
11000 -5.0% 10450 11000
ap Calculation (11kV)
Actual Primary Normal tap (100% tap) Secondary
Ratio
Voltage (V1) Primary Voltage (V2) Voltage
11000 415 25.2 437
Key in data or editable area

Actual Voltage (V) 11000


HV (V) 11000
LV (V) 415

Transformer settings
Tap Primary Sec. Voltage Turns Actual Sec. voltage
Setting Voltage (V) (V) Ratio (V)
5% 11550 27.8 395
2.5% 11275 27.2 405
0% 11000 415 26.5 415
-2.5% 10725 25.8 426
-5% 10450 25.2 437

Example 1. when the tap setting is at 0% and the actual voltage drop below the primary setting voltage then the actual sec volt

Actual Voltage (V) 10450


HV (V) 11000
LV (V) 415

Transformer settings
Tap Primary Sec. Voltage Turns Actual Sec. voltage
Setting Voltage (V) (V) Ratio (V)
5% 11550 27.8 375
2.5% 11275 27.2 385
0% 11000 415 26.5 394
-2.5% 10725 25.8 404
-5% 10450 25.2 415
a or editable area

ng voltage then the actual sec voltage is drop as well

𝑉_1/𝑉_2 =𝑇𝑢𝑟𝑛𝑠 𝑅𝑎𝑡𝑖𝑜

𝑉_2=𝑉_1/(𝑇𝑢𝑟𝑛𝑠 𝑅𝑎𝑡𝑖𝑜)

𝑉_2 𝑖𝑠 𝑖𝑛𝑣𝑒𝑟𝑠𝑙𝑦 𝑝𝑟𝑜𝑝𝑜𝑟𝑡𝑖𝑜𝑛𝑎𝑙 𝑡𝑜 𝑡𝑢𝑟𝑛𝑠 𝑟𝑎𝑡𝑖𝑜

2. if want to increase the sec


voltage then we need decrease
the turn ratio by changing the
tap setting to negative tap