PROTECTIONS & Interlocks Diary 300MW
PROTECTIONS & Interlocks Diary 300MW
4X300 MW
PROTECTIONS
AND
INTERLOCKS DIARY
4X300 MW
APRIL 2014
FOREWARD
Thermal Power Plant O&M is a challenging & exciting
environment that can be immensely rewarding for a
Vision vibrant & dynamic individual. Many aspects of the Power
Global recognition for Quality and Efficiency business are interlocked with day to day operations in the
while nurturing Nature and Society plant. With this in mind & to assist plant people, this
Protections & Interlocks Diary of 300 MW Vijayanagar
plant is prepared for you. This is a guide to everyday
procedures and best practices in the Industry as well as
Mission reference point for you on specific O&M queries.
Supporting India's growth in core economic sectors Given the nature of our business and embracing the
with speed and innovation need for progress, this dairy shall be consistently reviewed
and revised. Therefore we hope the following chapters
here would be as beneficial for everyone associated with
Core Values Thermal power plant O&M as it is for us to put it together.
INDEX
FOREWARD S.No Description Page No
I&C Maintenance is bringing out this protection & BOILER & AUXILIARIES
interlocks diary for Vijayanagar 4X300 MW Units. 1 BOILER PURGE PERMISSIVE
This diary will be very useful to all O&M employees. 2 MASTER FUEL TRIP
3 LDO OIL ELEVATIONS
We thank our Plant Head & Management for the 4 LDO PUMPS
encouragement & support in bringing out this diary. 5 LOFT - LFO TRIP VALVE
We also thank all those who are involved 6 HFO OIL ELEVATIONS
7 HFO PUMPS
directly / indirectly in making of this diary.
8 HOFT – HFO TRIP VALVE
9 ID FAN
10 ID FAN SCOOP CONTROL ACTUATOR
11 ID FAN AOP INTERLOCKS
12 FD FAN
13 BLADE PITCH CONTROL
14 FD FAN OUT LET DAMPER
Keshav reddy KT 15 PA FAN
16 PA FAN SCOOP ACTUATOR
AGM (C&I)
17 COAL MILL
18 MILL OIL SYSTEM
19 HOT AIR CONTROL DAMPER
20 COLD AIR CONTROL DAMPER
21 HOT AIR SHUT OFF GATE
22 COLD AIR SHUT OFF GATE
23 MILL DISCHARGE VALVE
24 MILL SEAL AIR DAMPER
I&C Protections & Interlocks 4 I&C Protections & Interlocks 5
12. Second FD fan permissive: (true if all the conditions 13. BLADE PITCH CONTROL:
are satisfied) 13.1 Increment block: (on any of the following condition)
o Other FD fan status on o Oil station abnormal
o Both APH on o Furnace Pressure > 0.75KPa
13.2 Cancel participation: (on any of the following
o Both ID on condition)
12.2 PROTECTIONS o Oil station abnormal
o Fan stop
VALUES Time Delay 13.3 Over ride close: (true if all the conditions are satisfied)
DESCRIPTION TRIP (SEC) o Corresponding FD Fan stop
MOTOR WINDING TEMPERATURE V HI [3 / 6] 0C 120 5 o Other FD fan running
FD FAN BRG TEMP V HI (DE & NDE) 0C 95 5 o Oil station Normal: All below conditions are
satisfied
FD MOTOR BRG TEMP V HI (DE & NDE) 0C 95 5
* Oil Temp not High < 50 0C
BOTH ID FANS OFF / TRIP TRIP - * Oil Pressure not Low > 0.8 MPa
BOILER MFT & FURNACE PRESSURE > +1.4 KPa TRIP 20 * Oil tank Level not Low > 30 %
BOTH APH TRIPPED TRIP 10 MIN * Any LOP Running.
OTHER FD FAN ON AND SAME PASS ID FAN OFF 13.4 Set to manual: On any of the following condition
TRIP -
o MFT
o Blade pitch-Deviation between command &
feedback high
o Oil station abnormal
o FD Fan Status OFF
13.5 Decrement block: On any of the following condition
o Furnace pressure < -0.75KPa
o FDF oil station abnormal.
I&C Protections & Interlocks 21 I&C Protections & Interlocks 22
o low)
lSupply oil temperature > 65C
FEEDER ON & PA FLOW LOW < 40.03 T/Hr 18.3 STAND BY PUMP START: (true if all the conditions
FEEDER ON & PA FLOW V LOW < 24.71 T/Hr 3min are satisfied)
MILL DISCHARGE VALVE CLOSED (more than 2) 5 sec 1) Mill running
ADJACENT CORNER COAL FLAME LOST - 2) on any of the following conditions
LOSS OF PA FAN TRIP (Only for) : (3or more Mills o Other pump running and pressure low < 90Kpa.
running) and (Any PA fan stop) Applicable to Mill 30min o Running lube oil pump trips
D, E, F only. With progressive time delay of 5 sec
starting from top mill for which trip is instantaneous
I&C Protections & Interlocks 27 I&C Protections & Interlocks 28
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
18.4 Over ride STOP: After 2 min of mill stop and on any 19. HOT AIR CONTROL DAMPER:
one of the below conditions 19.1 Decrement over ride: any of the following condition
1) Oil station fault (Lube oil press V low OR any gear box 1) Mill protection trip
temp > 80oC) 2) Mill outlet temp. high ≥ 93°C (2/3 logic)
3) Mill stop
2) Supply oil temp > 65oC with 5Sec delay
4) Mill hot air gate closed
3) Both pumps stop 19.2 Increment block:
1) Mill outlet temperature > 85°C
19.3 Set to Manual: any of the following condition
1) Mill stop
2) PA flow control PID Deviation between SP &
PV High HOT air damper feedback and command
deviation High
20. COLD AIR CONTROL DAMPER:
20.1 Over ride close: any of the following condition
1. Close to 5% If Mill trip
2. Mill protection trip (10s pulse)
20.2 Over ride Open: Mill outlet mixture air temp
o
> 85 C
20.3 Set to Manual: any of the following condition
1) Mill stop
2) PA flow control PID Deviation between SP & PV
High
3) Cold air damper feedback and command
deviation High
21. HOT AIR SHUT OFF GATE: 24.MILL SEAL AIR DAMPER
21.1 Open permissive: (true if all the conditions are 24.1 Over ride open:
satisfied) 1) On mill start
1) Mill status ON 24.2 Close permissive:
2) Seal air fan is running
1) 60 min after Mill stopped.
3) Mill seal air damper full opened
25.SEAL AIR DAMPER OF MILL DISCHARGE VALVE
21.2 Over ride close: any of the following condition
1) Mill outlet temp. high ≥ 93°C (1/3 logic) 25.1 Over ride open:
2) Mill stopped 1) MDV closed
3) Mill protection trip 25.2 Over ride close:
4) Runback acted for Mill-C, D, E & F (If runback PB 1) MDV opened
ON & Load >240 MW) 25.3 Close permissive:
22. COLD AIR SHUT OFF GATE : 1) 60 min after mill stopped
22.1 Over ride open: 26. COAL FEEDERS
1) On mill start 26.1 PERMISSIVES: (true if all the conditions are
23. MILL DISCHARGE VALVE: satisfied)
23.1 Open permissive: (true if all the conditions are 1) Pulverizer ON
satisfied)
2) Coal layer permissive available
1) Coal layer permissive available
2) Seal air fan is running 3) Mill O/L temp less than 93 oC
3) Mill seal air damper full opened 4) Seal air MOV open
23.2 Over ride open: On mill start 5) Feeder in Remote
23.3 Over ride close: On mill stop 6) Feeder not tripped
4.2 Auto Start of DC JOP :( True if all the following condition 6. OIL DEMISTER FAN
satisfied) Auto Start of Demister Fan (True if all the following
1) JOP inlet Pressure not Low > 0.0211MPa condition satisfied)
2) On any of the following condition: 1. Demister Fan should be on Back Up & any one of
o {(Both JOP A & B Off) AND turbine Speed < 600 following condition)
RPM} – 10 sec delay.
o {Other JOP A or B Running AND Header Pressure o Running Fan Trips
< 10 Mpa} - 10 Sec delay o {Other Fan Running & Demister Fan Pressure
o JOP A Start Fail OR JOP A Feedback Loss Low< -0.5 Mpa}- 10 sec time delay
(Intermediate) 7. EH OIL PUMPS
AND 7.1 Start permissive:
JOP B Start Fail OR JOP B Feedback Loss Either of the tank temperatures > 21 oC
(Intermediate) 7.2Auto Start of EH Oil Pump :( on all the following
4.3 Auto Stop of AC/DC JOP
condition satisfied)
o If Turbine Speed > 2600rpm
OR 1) On Back Up
o Jacking Oil Inlet Pressure V Low < 0.0211MPa 2) On any of the following condition:
with 5sec ON time delay o Running Pump Trips
5. HP Seal Oil Pump o EH Oil Pressure Low < 11.25 MPa
5.1 Auto Start of HP Seal Oil Pump: (True if all the 7.3EH oil pump Protection Trip: (True if all the following
following condition satisfied) condition satisfies)
1) HP Seal Oil Pump on Back Up 1) EH oil tank level low(295.15 mm) OR V
2) On any of the following condition:
LOW(193.54 mm)-Derived from level switch
o Bearing Oil Press. Low < 0.082 MPa
o Lube Oil Pump Test Press. Low < 0.075mpa 2) EH oil tank level < 295.15mm - Derived from
o Turbine Speed < 2900 RPM level transmitter
Note:-For BOP, EOP and HP SOP Pumps there is no Auto
Stop only Manual Stop is available
14. CONDENSATE EXTRACTION PUMP (CEP) 14.2 NEW VFD DRIV E FOR CEPs
14.1 START PERMISSIVES: (True if all the following START INTERLOCK: (True if all the following
condition satisfied) condition satisfied)
1) Any of the following condition 1) All the following condition satisfied (VFD
}
o Recirculation control valve bypass motorized healthy)
o VFD no fault
valve OPEN
o VFD not running
o Min. Recirculation control valve position > o VFD Ready VFD Healthy
95% o VFD no common alarm
o Other CEP running o VFD no motor fault
2) Motor stator coil temp normal <110°C 2) Any one of the following condition
}
3) Thrust bearing, motor upper & lower bearing A If all the following condition satisfied
temp normal < 75°C o CEP A Input isolator closed (QS1)
4) Motor trip not persisting o CEP A Output isolator closed (QS2)
5) Breaker selection in Remote o CEP A Bypass isolator opened (QS3) CEP A
o CEP B Input isolator opened (QS11) selected
6) Condenser Hot well level adequate > 524 mm
o CEP B Output isolator opened (QS12) for VFD
14.2 PROTECTIONS: o CEP A start command by operator
DESCRIPTION ALARM AUTO TRIP Delay o CEP A 'ON' feedback (Breaker closed)
}
CEP ON and discharge valve not opened TRIP 60 sec B If all the following condition satisfied
Hot well level V Low (2/3) < 524mm < 150 mm 4 sec o CEP B Input isolator closed (QS11)
o CEP B Output isolator closed (QS12) CEP B
Any of the bearing temp. V Hi o CEP A Bypass isolator opened (QS13)
> 95°C 3 sec selected
(Motor upper OR lower) o CEP A Input isolator opened (QS1)
Thrust bearing temp. V Hi > 70 °C > 80 °C 3 sec o CEP A Output isolator opened (QS2) for VFD
Condensate water flow V Low AND < 120TPH 3 sec o CEP B start command by operator
RC valve < 5% AND bypass MOV close o CEP B 'ON' feedback (Breaker closed)
Motor Winding Temp. V Hi (2/6) (°C) > 105 > 130 5 sec
STOP INTERLOCK: Any one of the following condition Over ride Open/Go preset : (pulse 3 sec)
1) If all the following conditions satisfied {CEP on VFD ON & Header
}
o CEP-A Input isolator QS1 closed pressure < 2 MPa
o CEP-A Output isolator QS2 closed (CEP-A running OR
o CEP-A breaker closed on VFD) CEP on VFD ON & CEP on DOL
o VFD ON started}
Preset value : 100%
o CEP-A operator stop OR CEP A breaker opened Override close : VFD stopped (5 Sec pulse)
2) If all the following conditions satisfied Feed forward * : Based on Condensate flow &
}
o CEP-B Input isolator QS1 closed VFD speed curves
o CEP-B Output isolator QS2 closed (CEP-B running *(During AUTO operation only)
o CEP-B breaker closed on VFD) 100% CV PID controller :
o VFD ON Set Point : Combined set value derived
o CEP-B operator stop OR CEP B breaker opened from levels of Dearator & hot
NEW PID controller for VFD: well = (D/a level SP x 0.7) – (Hot
Set Point : (Dea level SP x 0.7) – (Hot well well level SP)
level SP) Process Variable : (D/a level x 0.7)–(Hot well level)
Process Variable : (Dea level x 0.7) – (Hot well Set to Auto : (Any one of below conditions
level) satisfied) - 5 Sec Pulse
{DOL CEP started}
Set to auto : CEP Discharge header OR
pressure more than 21 KSC {CEP on VFD ON AND Header
AND pressure < 2 MPa}
Auto selected by operator Set to Manual : CEP on VFD ON & VFD drive ON
Set to Manual : On VFD stop & VFD controller in Auto
OR Override open : Nil
DOL CEP started Over ride close/Go preset : {CEP on VFD stopped AND
OR DOL CEP started}(pulse 3 sec)
Discharge header press < 2 Preset value : Derived from (MW to flow to
MPa valve opening %)
I&C Protections & Interlocks 53 I&C Protections & Interlocks 54
Energy, Vijayanagar. 4X300 MW
15. STANDBY CEP START INTERLOCKS:
Stand by pump starts when all of the below
condition satisfied
1) Back up enabled
2) Start permissive available.
3) (Running pump trips) OR (Discharge header
pressure low < 1.8 MPA - 5 sec time delay)
16. REGENERATIVE HEATERS
SEQUENCE REQUIRED CONDITION
LPH 1 OR 2
B/P MOV open (LPH1 or LPH 2 level ≥ 584mm)
or (LPH12 manual trip button)
I/L MOV close B/P MOV Open & (LPH1 or LPH 2 level
≥ 584 mm or LPH12 manual trip button)
O/L MOV close B/P MOV Open & (LPH1 or LPH 2 level
≥ 584 mm or LPH 12 manual trip button)
LPH 2 to LPH 1 cascading LPH 1 level ≥ 534mm OR (I/L & O/L MOV
CV override close Close & Bypass MOV Open)
LPH 1 to condenser cascading (Condenser level > 776 mm) OR
CV override close (Vacuum > - 30 KPa)
LPH 1 Emergency Drain PCV Condenser Vacuum >-30KPa
override close
LPH 1 Emergency Drain PCV Heater level ≥ 534 MM or (I/L & O/L
override open MOV Close & Bypass MOV Open)
LPH 2 Emergency Drain PCV Condenser Vacuum >-30 KPa
override close
LPH 2 Emergency Drain PCV Heater level ≥ 534 MM or (I/L & O/L
override open MOV Close & Bypass MOV Open)
I&C Protections & Interlocks 55
B/P MOV Open & Heater level ≥334mm or B/P MOV Open & (Heater level ≥334mm
O/L MOV CLOSE O/L MOV CLOSE
(LPH3 manual trip button) Or LPH4 manual trip button)
LPH 3 to LPH 2 cascading LPH 2level ≥ 534 or (LPH1&2 I/O MOV LPH 4 to LPH 3 cascading LPH3level ≥ 284 mm or (LPH3 I/O
PCV override close Close & Bypass MOV Open) PCV override close MOV Close & Bypass MOV Open)
LPH 3 Emergency Drain Condenser Vacuum ≥ -30KPa LPH 4 Emergency Drain Condenser Vacuum ≥ -30KPa
PCV override close PCV override close
LPH 3 Emergency Drain Heater level ≥ 284mm or (I/O MOV LPH 4 Emergency Drain Heater level ≥ 284mm or (I/O MOV
PCV override open Close & B/P MOV Open) PCV override open Close & Bypass MOV Open)
B/P MOV open Heater level ≥440mm or HPH7 manual trip B/P MOV open Heater level ≥409mm or HPH8 manual trip button
button
B/P MOV open FB & (Heater level
B/P MOV open FB & (Heater level ≥44 I/L MOV close
I/L MOV close ≥409mm or HPH8 manual trip button)
0mm or HPH7 manual trip button)
B/P MOV open FB & (Heater level
O/L MOV close
B/P MOV open FB & (Heater level ≥409mm or HPH8 manual trip button)
O/L MOV close
≥440mm or HPH7 manual trip button)
HPH 8 to HPH 6 cascading Heater 7 level ≥390mm or (HPH-7 I/O
HPH 7 to HPH 6 cascading Heater 6 level ≥455mm or (HPH6 I/O PCV override close MOV Close & Bypass MOV Open )
PCV override close MOV Close & Bypass MOV Open )
HPH 8 Emergency Drain
Condenser Vacuum ≥ -30KPa
Emergency Drain PCV close Condenser Vacuum >/= -30KPa PCV override close
Emergency Drain PCV open Heater 7 level ≥390mm or (I/O MOV HPH 8 Emergency Drain Heater 8 level ≥409mm or (I/O MOV
Close & Bypass MOV Open ) PCV override open Close & Bypass MOV Open )
o On all the below conditions: {HPH 7 trip OR turbine trip OR turbine over
§ Total energy flow of boiler >10% speed activated > 103% OR total energy flow of
§ Over ride open not persisting boiler <10%}
§ NRV open & EXTN motorized block valve Override close:
open - 3 min on time delay o SETS on condenser vacuum >-30KPa, RESET on
18. EXTRACTION 7: condenser vacuum < -50KPa
NRV UP STREAM DRAIN VALVE: OR
Override open: (on any one of these conditions) o On all the below conditions:
o NRV close feedback or EXTN motorized block § Total energy flow of boiler >10%
valve close feedback § Over ride open not persisting
o Turbine proper water drain PB activated AND § NRV open & EXTN motorized block valve
open - 3 min on time delay
{HPH 7 trip OR turbine trip OR turbine over
19. EXTRACTION 6:
speed activated>103% OR total energy flow of
NRV UP STREAM DRAIN VALVE:
boiler <10%}
Override open: (on any one of these conditions)
Override close: On all the below conditions
o NRV close feedback or EXTN motorized block
o Total energy flow of boiler >10%
valve close feedback
o Over ride open not persisting o Turbine proper water drain PB activated AND
o NRV open & EXTN motorized block valve open - 3 {HPH 6 trip OR turbine trip OR turbine over
min on time delay. speed activated >103% OR total energy flow of
NRV DOWN STREAM DRAIN VALVE: boiler <10%}
Override open: (on any one of these conditions) Override close: On all the below conditions
o NRV close feedback or EXTN motorized block o Total energy flow of boiler >10%
valve close feedback o Over ride open not persisting
o Turbine proper water drain PB activated o NRV open & EXTN motorized block valve open - 3
AND min on time delay.
I&C Protections & Interlocks 64 I&C Protections & Interlocks 65
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
NRV DOWN STREAM DRAIN VALVE: Override close: 3 min time delay after all the
Override open: (on any one of these conditions) following conditions are satisfied.
o NRV close feedback or EXTN motorized block o Total energy flow of boiler > 20%
valve close feedback o DEA level < 400 mm
o Turbine proper water drain PB activated AND o Motorized block valve opened & NRV 1 opened &
{HPH 6 trip OR turbine trip OR turbine over NRV 2 opened
speed activated > 103% OR total energy flow of NRV-2 UP STREAM DRAIN VALVE:
boiler <10%}
Override open: on any one of these conditions:
Override close:
o Total energy flow of boiler < 20%
o SETS on condenser vacuum >-30KPa, RESET on
condenser vacuum <-50KPa o Turbine trip
OR o DEA level > 400 mm
o On all the below conditions: o Motorized block valve closed OR NRV 1 closed
l Total energy flow of boiler >10% OR NRV 2 closed
l Over ride open not persisting Override open: on any one of these conditions:
l NRV open & EXTN motorized block valve o SETS on condenser vacuum > -30KPa, RESET on
open - 3 min on time delay. condenser vacuum < -50KPa
20. EXTRACTION 5: o After 3 min of all the below conditions satisfied:
NRV-1 UP STREAM DRAIN VALVE: l Total energy flow of boiler >10%
Override open: (on any one of these conditions) l DEA level < 400 mm
o Total energy flow of boiler < 20% l Motorized block valve opened & NRV 1
o Turbine trip opened & NRV 2 opened
o DEA level > 400 mm
o Motorized block valve closed OR NRV 1 closed
OR NRV 2 closed
I&C Protections & Interlocks 66 I&C Protections & Interlocks 67
1.3INTERLOCK START for unit pumps: (All of the 3. COMMON PUMP DISCHARGE VALVE TOWARDS
UNIT-1:
below condition satisfied)
Over ride close: On pump stop
1) Back up enabled Over ride open: (All of the below condition
2) Pump start permissive available satisfied)
3) Pump is in stopped condition o Pump C running and pump C breaker is in service
4) On any one of the following condition: o Discharge valve of unit-2 closed
o Any of the unit-1 pump trips
o Other running Pump Tripped
4. PUMP C DISCHARGE VALVE TOWARDS UNIT-2:
o (Common Pump C tripped) and (its Over ride close: On pump stop
discharge valve Open towards the Over ride open: (All of the below condition
respective unit) satisfied)
1.4 INTERLOCK START for common pump: (All of o Pump C running and pump C breaker is in service
the below condition satisfied) o Discharge valve of unit-1 closed
1) Back up enabled o Any of the unit-2 pump trips
5. CT FAN INTERLOCKS AND PROTECTION:
2) Pump start permissive available
CT FAN START UP: (All the following conditions
3) Pump is in stopped condition should be satisfied)
4) On any one of the following condition: o Low level switch not acted.(> ADD mark in Dip
o Pump 1A tripped stick)
o Pump 1B tripped o Vibro-trip switch not acted.(< 4.5 mm/sec)
o Local E-stop push button should be in released
o Pump 2A tripped condition.
o Pump 2B tripped o Motor electric trip condition not persisting.
2. ALL CW PUMP DISCHARGE VALVES: o If any of the below condition is satisfied
Over ride close: On pump stop a. Remote Start: Start command given by operator.
Over ride open: On pump start b. Local Start: Local start command given by
operator.
I&C Protections & Interlocks 94 I&C Protections & Interlocks 95
8.3 Porcelain Heater start Logic: (All the following 3. If any of the below conditions is satisfied.
conditions should be satisfied) P Auto start.
1. System start command push button is enabled l Hopper Heater is selected in Auto
2. Stop command not persisting l Hopper Temperature < 80 Deg C
3. If any of the below conditions is satisfied. l Hopper Temperature not > 100 Deg C
P Auto start. P Manual Start
l Porcelain Heater is selected in Auto l Hopper Heater is selected in Manual
l Temperature < 80 Deg C and start command given by operator
l Temperature not > 100 Deg C
P Manual Start 8.6 Hopper Heater stops permissive (If any of the
l Porcelain Heater is selected in Manual and below condition reached)
start command given by operator 1) Hopper Temperature > 100 Deg C
8.4 Porcelain Heater stop Logic: (If any of the below 2) Manual stop by operator
condition reached)
1. Temperature > 100 Deg C
2. Manual stop by operator
8.5 Hopper Heater start Logic: (All the below
conditions are satisfied)
1. System start command push button is
enabled
2. Stop command not persisting
I&C Protections & Interlocks 100 I&C Protections & Interlocks 101
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
9.1.2 ESP Hopper 1st & 2nd Fields Interlocks Timer settings:
Note: These two systems are connected to silo through a Description 1st Field 2nd Field
common conveying line with switch valves in each
system Cycle gap Time 50 sec 50 sec
Step 1: Start Vessel Filling Cycle (all below Initial Purge Time 30 sec 30 sec
conditions satisfied) Filling Time 20 sec 20 sec
l Respective Hoppers Selector switch (near Conveying Timer 80 sec 80 sec
local panel) is in start position Line Block Timer 400 sec 400 sec
l Respective Hoppers Selector switch (in HMI
Master Boosting Timer 20 sec 20 sec
graphics) is in start position
l Respective Hoppers Inlet dome Valve Seal Slave-1 Boosting Timer 20 sec 20 sec
Press is OK (> 5.5 Bar) for all the 4 vessels. Slave-2 Boosting Timer 20 sec 20 sec
l Respective Hoppers Vessel pressure is low. (< Slave-3 Boosting Timer 20 sec 20 sec
0.3 bar) CAM Timer 100 sec 100 sec
l Respective field Conveying air pressure is OK.
(> 4.0 Bar) 9.1.3 ESP Hopper 3, 4, 5 and 6th Fields interlocks:
Step 2: Start Conveying Cycle (all below conditions Note: These four fields are connected to silo through a
satisfied) common conveying line with switch valves in each
l Respective Hoppers Switch valve is Open field
l Respective Hoppers Inlet dome Valve Seal Step 1: Start Vessel Filling Cycle (all below
Press OK (> 5.5 Bar) for all the 4 vessels conditions satisfied)
l Respective field Conveying air pressure OK. l Respective Hoppers Selector switch (near
(> 4.0 Bar) local panel) is in start position
I&C Protections & Interlocks 104 I&C Protections & Interlocks 105
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
l Respective Hoppers Selector switch (in HMI 9.2 ASH WATER PUMPS 1, 2, 3
graphics) is in start position Start Permissive: (all the conditions satisfied)
l Respective Hoppers Inlet dome Valve Seal o Pump suction Pressure Not Low (> 0.5 KSC)
Press is OK (> 5.5 Bar) for all the 4 vessels. o Pump Discharge valve Open.
l Respective Hoppers Vessel pressure is low. (< Trip Interlocks: (any of the conditions satisfied)
0.3 bar) o Suction Pressure Low (< 0.5 KSC)
l Respective field Conveying air pressure is OK. Auto Start Conditions:
(> 4.0 Bar) o Respective pump Selected in Standby mode
Step 2: Start Conveying Cycle (all below conditions
AND
satisfied)
o Running Pump Tripped
l Respective field Switch valve is Open
l Other Hoppers Switch valves for is closed. 9.3 CLEAR WATER PUMPS 1, 2
l Respective Hoppers Inlet dome Valve Seal Start Permissive: (all the conditions satisfied)
Press OK (> 5.5 Bar) for all the 4 vessels o Clear water sump level high (> 1.5 meter)
l Respective field Conveying air pressure OK. o Clear water sump level not low low (> 0.5
(> 4.0 Bar) meter)
Timer settings: o Pump Discharge valve Closed
Trip Interlocks: (any of the conditions satisfied)
Description 3rd Field 4th Field 5th Field 46th Field o Clear water sump level Low Low (< 0.5 meter)
Cycle gap Time 100 sec 100 sec 100 sec 100 sec o Clear water pump discharge valve closed.
o Other pump discharge valve opened.
Initial Purge Time 30 sec 30 sec 30 sec 30 sec 9.4 ESP and silo Blower Heaters:
Filling Time 20 sec 20 sec 20 sec 20 sec Start Permissive:
Conveying Timer 40 sec 40 sec 20 sec 20 sec o Blower running
o Blower Outlet Pr Normal.
Line Block Timer 180 sec 180 sec 180 sec 180 sec
o Temperature Not High.(<120 deg C)
CAM Timer 100 sec 300 sec 600 sec 900 sec
I&C Protections & Interlocks 106 I&C Protections & Interlocks 107
I&C Protections & Interlocks 108 I&C Protections & Interlocks 109
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
10 COAL HANDLING SYSTEM BCN 1A/1B Hydraulic Oil pump start: (All the
10.1 CHP (7MT) PLC INTERLOCKS AND PROTECTION: below conditions satisfied)
BCN 2A/2B/3A/3B START UP: (All the following 1. Scoop oil pump overload trip not persists
conditions should be satisfied) 2. Scoop start command from HMI
1. Pull chord, Belt sway and ZSS Alarm not
BCN 1A/1B Hydraulic Oil pump stop (Any of the
acted.
below conditions)
2. Switchgear healthy signal from MCC.(only for
3A/3B) 1. Stop command given by operator.
3. Overload trip is not coming. 2. Hydraulic pump Overload trip.
4. 1 minute's siren timer is completed. BCN 1A/1B HT MOTOR START PERMIT: (If all
5. If any of the below condition is satisfied the conditions below satisfy)
a. Remote Start: (All the following conditions 1. HT Motor Switchgear healthy.
should be satisfied) 2. HT Motor Switchgear selected in Remote.
l Selector switch (near drive) in remote 3. HT Motor Switchgear Overload trip not
l Start command given by operator persists
b. Local Start: (All the following conditions
4. HT Motor scoop in decoupled.
should be satisfied) (Only for 2A/2B)
5. HT Motor stop command is not persisting.
l Selector switch (near drive) in Local
l Local start command given by operator 6. HT Motor not running
(Only for 2A/2B) 7. HT Motor consecutive starts < 2 in 1 hour
STOP/TRIP: (Any of the following conditions) 8. Hydraulic oil pressure OK >1.5 KSC
1. Pull chord OR Belt sway OR ZSS Acted. 9. Hydraulic oil temperature ok. <102 Deg C
2. Overload trip acted. 10. HT motor winding and bearing temperature
3. Remote Stop from PLC: (All the following OK. <115 Deg C
conditions should be satisfied)
I&C Protections & Interlocks 110 I&C Protections & Interlocks 111
BCN 1A/ 1B HT MOTOR STOP: (Any of the BCN 1A/1B Scoop Forward (Stop/Decouple with
conditions below satisfy) motor) (If all the below condition satisfy)
1. HT Motor Switchgear not healthy. 1. Scoop oil flow low.
2. HT Motor selection switch (Near switchgear) 2. Scoop oil filter DP High
selected to Local. 3. Scoop Pump oil pressure Low. <1.5 KSC
3. If any of the below conditions satisfy. 4. Oil temperature is high. >102 Deg C
P Scoop Oil Pressure Low < 1.5 KSC 5. Any Pull chord/Belt sway/ZSS acted.
P Motor Winding Temperature Hi. > 115 Deg C.
6. HT Motor winding or bearing temperature is HI >
Delay 3 Sec
115deg C
P Motor bearing Temperature Hi. > 115 Deg C.
Delay 3 Sec
P Motor overload trip
B C N 1 A / 1 B S c o o p Re ve r s e Pe r m i s s ive :
(Start/Couple with motor)
1. Scoop Hydraulic pump start permissive is
through.(if all the below conditions satisfy)
l Scoop oil flow not low
l Scoop oil filter DP not High
l Scoop Pump oil pressure normal. >1.5 KSC
l Oil temperature is normal. <102 Deg C
2. Scoop stop command not persists
3. Scoop forward limit switch acted (Decoupled)
4. Belt Pull chord, Belt sway, ZSS not acted.
5. Scoop oil pump overload trip is not persists
I&C Protections & Interlocks 112 I&C Protections & Interlocks 113
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
PERMISSIVES SIGNAL FOR STARTING STEEL BELT d) Both belt conveyor (BCN 1A AND 1B) vibro
(94 C1, 10C1, 10C2) feeder running. (only for Steel Belt 94C1
Note : 94 C1 belt permit signal is sent to RMHS. Start/Stop Run signal)
is done from RMHS e) Flap gate selected for both conveyors
Case 1)any one conveyor running (BCN 1A OR 1B) (middle) (BCN 1A AND 1B)
a) Selected belt conveyor (1A OR 1B) f) Required Upstream belt conveyor is
switchgear healthy. selected in HMI (94C1/10C1/10C2).
b) Selected belt conveyor (1A OR 1B)Running DUST SUPPRESSION SYSTEM (DSS).
(Derived from ZSS signal) DSS START:
c) Selected belt conveyor (1A OR 1B)Scoop limit Case 1: Selector switch is in Auto. (All the following
switch is (Coupled) conditions should be satisfied)
d) Selected belt conveyor (1A OR 1B) vibro 1. DSS Air pressure is OK.
feeder running. (only for Steel Belt 94C1 Run 2. Belt is running.
signal) 3. DSS HE Material sensor is acted /Load more
e) Flap gate position is towards required belt than 30 TPH
conveyor Case 2: Selector switch is in Manual. (All the following
f) Required Upstream belt conveyor is selected conditions should be satisfied)
in HMI (94C1/10C1/10C2). 1. DSS Air pressure is OK.
Case 2) both conveyors running (BCN 1A AND 1B) DSS STOP/TRIP: (If any of the below conditions satisfy)
a) Both belt conveyor (BCN 1A AND 1B) 1. Selector switch is in Off.
switchgear healthy. 2. DSS air pressure is not OK.
b) Both belt conveyor (BCN 1A AND 1B) 3. DSS selected in Auto and Material load in <
Running (Derived from ZSS signal) 30TPH.
c) Both belt conveyor (BCN 1A AND 1B) Scoop 4. DSS selected in Auto and belt not running
limit switch is (Coupled)
I&C Protections & Interlocks 114 I&C Protections & Interlocks 115
10.2 CHP (10MT) PLC INTERLOCKS AND PROTECTION: 8. Required conveyor Overload trip is not coming.
Note: 9. Required conveyor 1 minute's siren timer is
1. 9C1& 9C2 belt running signal (Derived from ZSS) is completed.
sent to 10MT CHP Steel Conveyor (for staring 10. Any of the below condition is satisfied
permissive to downstream conveyor). Start/Stop is a. Remote Start: (All the following conditions
done from 10MT Steel CHP Control room. should be satisfied)
2. 8C1&8C2 belt running signal (Derived from ZSS) is l Required conveyor Selector switch (near
received in 10MT Energy CHP PLC panel. (For drive) in remote.
Monitor purpose) l Required conveyor Start command given
A) BCN 10C1/10C2/9RSC1/9RSC2/9C1/9C2 START by operator in HMI.
UP: (All the following conditions should be b. Local Start: (All the following conditions
satisfied) should be satisfied)
1. Required conveyor Auto/Manual selected in l Required conveyor Selector switch (near
I&C Protections & Interlocks 116 I&C Protections & Interlocks 117
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
l Respective conveyor Selector switch (near drive) 2. DSS air pressure is not OK.
in remote 3. DSS selected in Auto and Material load in <
l Respective conveyor Stop command is given by 30TPH.
operator in HMI. 4. DSS selected in Auto and belt not running
5. Local Stop: (All the following conditions should be 11) DM PLANT
satisfied) 11.1 DM PLANT FEED PUMPS: 3 no
l Respective conveyor Selector switch (near drive) Start permissive (for Service or Refill or Rinse
in Local mode):
l Respective conveyor Local stop command given 1. One pump shall be in Main Mode and at least
by operator. one of the other pumps in Standby mode.
B. 10MT CHP DUST SUPPRESSION SYSTEM 2. Selected pump shall be in Remote & Auto
DSS START: mode.
Case 1: Selector switch is in Auto. (All the following 3. DMF (Dual Media Filter) 1 or DMF-2 in
conditions should be satisfied) (Refill or Service Mode or Rinse mode)
1. DSS Air pressure is OK. Trip Interlocks (Service or Refill or Rinse mode):
2. Belt is running. 1. After 18 Hours of Service or Operator
3. DSS HE Material sensor is acted /Load more than Entered Time.
30 TPH 2. DP Across DMF Is High. (>0.5 Bar)
Case 2: Selector switch is in Manual. (All the following Start per missives for back wash Mode
conditions should be satisfied) 1. Valve VA-2 in close condition.
1. DSS Air pressure is OK. 2. One BFT (Filter air blower) in Main mode
DSS STOP/TRIP: (If any of the below conditions satisfy) and other BFT In standby mode.
1. Selector switch is in Off. 3. One Filter Back wash pump in Main mode &
Remote mode.
I&C Protections & Interlocks 118 I&C Protections & Interlocks 119
I&C Protections & Interlocks 120 I&C Protections & Interlocks 121
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
11.4 MB System (Mixed bed Exchanger)-2 numbers 11.5 DM Water Transfer Pumps (P.D.M) - 3 no
Start per missives for Service mode: Start permissive: Nil
1. One S.B.A in Service Mode Trip Interlocks:
2. Selection shall be in Service mode. 1. DMST-B (DM water tank-b) level low
Trip Interlocks for Service mode: (<2500mm)
1. After 126 Hours of cycle or Operator entered 11.6 Acid dosing Pumps (P.H.L) - 2 no
Time. Start permissive: Nil
2. Totalized flow >9000Tons Trip Interlocks:
3. Conductivity high. (>0.5 Micro Siemens) 1. Sulphuric Acid Tank level low (<100mm)
4. Silica High (20ppb)
11.7 Alkali Dosing Pumps (P.A.K)
5. DMST Tank level high (>5700mm)
Start permissive: Nil
Start per missives for Regeneration mode:
Trip Interlocks:
1. One S.B.A in Service Mode
1. NaoH (Sodium hydroxide) Tank level low
2. M.H.L Tank level shall be high
3. M.A.K Tank level shall be high (<100mm)
4. One B.M.B is in Auto & Main mode and other 12) ELECTRO CHLORINATION PLANT
B.M.B in Standby mode. Permissive (ENABLE) for system start up:
5. One P.D.M.R is in Auto & Main mode and other 1. Stream O/L temperature < 65 deg C.
B.M.B in Standby mode 2. Hypo tank high level switch not acted.
6. MB Outlet valve (VA-2) shall be in close 3. Raw water I/L flow should be healthy i.e.
condition. For single stream > 1000 LPH
Trip Interlocks for Regeneration mode: For double stream > 2000 LPH
1. MHL (Sulphuric acid) Tank level High
(>100mm)
I&C Protections & Interlocks 122 I&C Protections & Interlocks 123
I&C Protections & Interlocks 124 I&C Protections & Interlocks 125
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
I&C Protections & Interlocks 132 I&C Protections & Interlocks 133
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
13. 1 RO Feed Pump Any of the RO Feed Pump P-301A / P-301B / P-
P
Permissive 301C running
P RO Product Tank Level Should be < 98 % RO High Pressure Pump Suction Pressure not
P
P UF Storage Tank Level Should be > 10 % LOW (> 1 KSC)
P Any of the SMBS Dosing Pump DP 301 A / DP 301 RO Dump Valve XV-301 Closed
P
B should be in service, for Single/Dual Skid RO Feed Isolation Valve XV-302 Open feedback
P
Operation should persist
P Any of the Anti Scalant Dosing Pump DP 302 Trip Interlock
A/DP 302 B should be in service, for Single/Dual P Any of the above mentioned permissive is lost
Skid Operation P ORP > 1500 mv persists for the duration of 3
Trip Interlock minutes
P Any of the above mentioned permissive lost P RO High Pressure Pump fail to Start
P ORP > 1500 mv persists for the duration of 3 Start Sequence
minutes STEP NO Description Condition
P RO Feed Pump fail to Start 01 Start Command Initiated
P All RO High Pressure Pump in stop Condition & 02 RO Dump Valve Open
Dump Valve XV-301 is closed for duration of 2 03 RO Product By-pass Valve Open
minutes 04 RO Reject By-pass Valve Open
13.2 RO High Pressure Pump 05 Selected RO Feed Pump Start
Permissive 06 RO Feed Isolation Valve Open
P Corresponding skid RO Reject Bypass valve 07 Selected SMBS Pump Start
closed. 08 Selected Anti Scalant Pump Start
P Any of the SMBS Dosing Pump DP 301 A / DP 301 09 RO Dump Valve Close
B running. 10 RO Product By-pass Valve Close
P Any of the Anti Scalant Dosing Pump DP 302 11 RO Reject By-pass Valve Close
A/DP 302 B shall be running 12 Selected RO High Pressure Pump Start
I&C Protections & Interlocks 134 I&C Protections & Interlocks 135
I&C Protections & Interlocks 136 I&C Protections & Interlocks 137
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
Selected CEB-1 DP 201-A/DP 201-B Pump fail to
P After the Initiation of start command, each train will
start. operate in a sequential process which is mentioned
Selected CEB-2 DP 202-A/DP 202-B Pump fail to
P below.
start Ultra filtration Cycle
Any of the Pneumatic Operated Valve of
P
MODE DESCRIPTION DURATION
Corresponding train, Fail to Open/Fail to Close
Service Mode 60 Minutes
Fast Flush Mode 30 Seconds
Brief Write up on Ultra filtration Cycle of Operation
Back Wash Mode 60 Seconds
VALVE NOMENCLATURE
After 18 Cycles of Service, train shall go to CEB-1 Back Wash mode (HCL)
DESCRIPTION UF UF UF UF CEB-1 Circulation Mode 300 Seconds
TRAIN-1 TRAIN-2 TRAIN-3 TRAIN-4 CEB-1 Soaking Mode 60 Seconds
CEB-1 Back Wash Mode 60 Seconds
Service inlet Valve XV-201A XV-202A XV-203A XV-204A
After completion of CEB-1 Back Wash mode train, shall go to CEB-2 Back Wash Mode (Hypo)
Service outlet Valve XV-201B XV-202B XV-203B XV-204B CEB-2 Circulation Mode 300 Seconds
CEB-2 Soaking Mode 60 Seconds
Backwash inlet Valve XV-201C XV-202C XV-203C XV-204C CEB-2 Back Wash Mode 60 Seconds
Backwash outlet Valve XV-201D XV-202D XV-203D XV-204D
I&C Protections & Interlocks 138 I&C Protections & Interlocks 139
I&C Protections & Interlocks 144 I&C Protections & Interlocks 145
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
I&C Protections & Interlocks 146 I&C Protections & Interlocks 147
I&C Protections & Interlocks 148 I&C Protections & Interlocks 149
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
15.2 ESP CONTROL ROOM o Air Handling Unit 5 (ESP control room)
o Air Handling Unit 4 (ESP control room) l START UP: (All the following conditions should
l START UP: (All the following conditions should be satisfied)
be satisfied) P In SCADA AHU 5 should be selected.
P In SCADA AHU 4 should be selected. P Motor electric trip condition not persists.
P Motor electric trip condition not persisting. P No stop CMD should persist.
P No stop CMD should persist. P No fire alarm should persist.
P No fire alarm should persist. P Supply & return air ESP duct dampers
P Supply & return ESP air duct damper opened.
opened. P Remote Start: Start command given from
P Remote Start: Start command given from SCADA.
SCADA. Local start: Start command given from local panel.
Local start: Start command given from local panel. l STOP/TRIP: (Any of the following conditions)
l STOP/TRIP: (Any of the following conditions) P Fire alarm came.
P Fire alarm came. P Overload trip acted.
P Overload trip acted. P Any of the supply or return ESP duct
P Any of the supply or return ESP duct damper closed.
dampers closed. Stop command given from SCADA or Local
P Stop command given from SCADA or Local Panel.
Panel.
I&C Protections & Interlocks 150 I&C Protections & Interlocks 151
15.3 AIR WASHER (AT TG 12.6 M, SIDE OF Motor electric trip condition not
P
ELECTRICAL OFFICE) persisting.
o Air Washer Unit Fan 1&2 In SCADA AHU 2&3 should not be
P
l START UP: (All the following conditions
selected.
should be satisfied) No stop CMD should persist.
P
P Motor electric trip condition not No fire alarm should persist.
P
persists. Run Feedback for any Air washer unit fan
P
P No fire alarm should persist. should be available.
P Remote Start: Start command given from Water tank level low switch not acted.
P
SCADA. l STO P / T R I P : ( A ny o f t h e fo l l o w i n g
Local start: Start command given from local conditions)
panel. P Fire alarm came.
l STOP/TRIP: (Any of the following
P Overload trip acted.
conditions) P Fan running feedback lost.
P Fire alarm came. P Stop command given from SCADA or Local
P Overload trip acted. Panel.
P Stop command given from SCADA or o Air Washer Pump 2
l START UP: (All the following conditions
Local Panel.
o Air Washer Pump 1 should be satisfied)
l START UP: (All the following conditions
P In SCADA AWU pump 1&2 or AWU pump
should be satisfied) 2&3 should be selected.
P In SCADA AWU pump 1&2 OR AWU P Motor electric trip condition not
pump 1&3 should be selected. persisting.
I&C Protections & Interlocks 152 I&C Protections & Interlocks 153
Energy, Vijayanagar. 4X300 MW Energy, Vijayanagar. 4X300 MW
I&C Protections & Interlocks 154 I&C Protections & Interlocks 155
I&C Protections & Interlocks 156 I&C Protections & Interlocks 157