Fan & Motor Specs

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 15

S14015-0100M

DESIGN FOR TWO NEW BRT TERMINUS STATIONS

SECTION 15853 - POWER VENTILATORS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Utility set fans.


2. In-line ventilators.
3. In-line centrifugal fans.

B. Related Sections: The following Sections contain requirements that relate to this Section:

1. Division 7 Section "Manufactured Roof Specialties" for roof curbs and equipment
supports.
2. Division 15 Section "Mechanical Vibration Controls and Seismic Restraints" for
vibration hangers and supports.
3. Division 15 Section "HVAC Instrumentation and Controls" for control devices.
4. Division 16 Section "Enclosed Switches and Circuit Breakers" for disconnect
switches.
5. Division 16 Section "Motor-Control Centers" for starters and fusible switches.

C. Products furnished, but not installed, under this Section include roof curbs for roof-mounted
exhaust fans.

1.3 PERFORMANCE REQUIREMENTS

A. Project Altitude: Base air ratings on actual site elevations.

B. Operating Limits: Classify according to AMCA 99.

C. Performance Criteria:

1. The fan schedule shows cubic feet per minute (CFM) and design static pressure.
2. Provide fans and motors capable of stable operation at design conditions and at ll0
percent pressure but not to exceed 185 Pa (3/4-inch) additional pressure.
3. Lower than design pressure drop of approved individual components may allow use
of a smaller fan motor and still provide the safety factor. When submitted as a
deviation a smaller motor may be approved in the interest of energy conservation.
4. Select fan operating point as follows:

a. Forward curved and axial fans: Right hand side of peak pressure point.
b. Airfoil, backward inclined or tubular: Near the peak of static efficiency.

POWER VENTILATORS 15853 - Page 1 of 11


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

D. Safety Criteria: Provide manufacturer's standard screen on fan inlet and discharge exposed
to operating and maintenance personnel.

1.4 SUBMITTALS

A. Product Data including rated capacities of each unit, weights (shipping, installed, and
operating), furnished specialties, accessories, and the following:

1. Certified fan performance curves with system operating conditions indicated.


2. Certified fan sound power ratings.
3. Motor ratings and electrical characteristics plus motor and electrical accessories.
4. Material gages and finishes, including color charts.
5. Dampers, including housings, linkages, and operators.

B. Design Analysis and Calculations shall be submitted for fans indicating the manufacturer's
recommended sound pressure level ratings, self-alignment and thrust load requirements,
horsepower ratings, and required system rpm's.

C. Shop Drawings from manufacturer detailing equipment assemblies and indicating


dimensions, weights, loadings, required clearances, method of field assembly, components,
and location and size of each field connection.

D. Coordination Drawings for roof penetration requirements and for reflected ceiling plans
drawn accurately to scale and coordinating penetrations and units mounted above ceiling.
Submit with Shop Drawings. Show the following:

1. Roof framing and support members relative to duct penetrations.


2. Ceiling suspension assembly members.
3. Size and location of initial access modules for acoustical tile.
4. Ceiling-mounted items including light fixtures, diffusers, grilles, speakers, sprinklers,
access panels, and special moldings.

E. Wiring diagrams detailing wiring for power and control systems and differentiating clearly
between manufacturer-installed and field-installed wiring.

F. Field Test and Commissioning Reports: As specified in "Field Quality Control" and
"Commissioning" Articles in Part 3 of this Section. Indicate and interpret test results for
compliance with performance requirements.

G. Maintenance data for power ventilators to include in the operation and maintenance manual
specified in Division 1.

1. Include lists of parts and troubleshooting maintenance data.

1.5 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in latest
and relevant IEC standard, by a testing agency acceptable to the Engineer. Electrical
components and devices for the smoke extract fans and kitchen exhaust fans shall comply
with NFPA 70 and to be UL705 listed.

B. Listing and Labeling: Provide electrically operated fixtures specified in this Section that are
listed and labeled.

POWER VENTILATORS 15853 - Page 2 of 11


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

C. AMCA Compliance: Provide products that meet performance requirements and are licensed
to use the AMCA Seal.

D. UL Standard: Provide power ventilators that comply with UL 705. Smoke exhaust fans to
be UL label for “Power Ventilators for smoke control systems”.

1.6 PROJECT CONDITIONS

A. Field Measurements: Verify dimensions by field measurements. Verify clearances.

B. Do not operate fans until ductwork is clean, filters are in place, bearings are lubricated, and
fans have been commissioned.

1.7 COORDINATION AND SCHEDULING

A. Coordinate the size and location of concrete housekeeping pads. Cast anchor-bolt inserts
into pad. Concrete reinforcement and formwork requirements are specified in Division 3
Section "Cast-in-Place Concrete."

B. Coordinate the size and location of structural steel support members.

C. Coordinate the installation of roof curbs, equipment supports, and roof penetrations. Roof
specialties are specified in Division 7 Sections.

1.8 EXTRA MATERIALS

A. Furnish one set of belts for each belt-driven fan that match products installed, are packaged
with protective covering for storage, and are identified with labels clearly describing
contents.

PART 2 - PRODUCTS

2.1 STANDARD COMMERCIAL PRODUCTS

A. Materials and equipment shall be standard products of a manufacturer regularly engaged in


the manufacturing of such products, which are of a similar material, design and
workmanship. The standard products shall have been in satisfactory commercial or
industrial use for 5 years prior to bid opening. The 5 year use shall include applications of
equipment and materials under similar circumstances and of similar size. The 5 years
experience shall be satisfactorily completed by a product that has been sold or is offered for
sale on the commercial market through advertisements, manufacturer's catalogs, or
brochures. Products having less than a 5 year field service record shall not be acceptable.
Products shall be supported by a service organization. System components shall be
environmentally suitable for the indicated locations.

POWER VENTILATORS 15853 - Page 3 of 11


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

2.2 GENERAL FAN REQUIREMENTS

A. General

1. Performance data for all fans and spare parts shall be determined in accordance with
the provisions of ASHRAE 51.
2. Sound pressure level ratings of ducted fans shall comply with AMCA 301 and shall
be the result of tests made in accordance with AMCA 300.
3. Sound pressure level ratings of non-ducted fans shall comply with AMCA 301 and
shall be the result of tests made in accordance with AMCA 300. Application of
sound pressure level ratings shall conform to AMCA 302. Unit construction shall
conform to applicable standards contained in AMCA 99 and to requirements
specified.
4. Safety provisions for power transmission equipment and non-ducted inlets and outlets
shall include guards and screens, unless other provisions are required, and shall be
constructed in accordance with applicable provisions of ASME B15.1. Installation
shall be such that fan vibration-isolation provisions are not negated.
5. Fan wheels shall be statically and dynamically balanced at the factory.

B. Corrosion Protection: All steel shall be mill-galvanized, or phosphatized and coated with
minimum two coats, corrosion resistant enamel paint. Manufacturers paint and paint system
shall meet the minimum specifications of: ASTM D 1735 water fog; ASTM B 117 salt
spray; ASTM D 3359 adhesion; and ASTM G 23 weathermeter.

C. Bearings

1. Bearings shall be antifriction ball or roller type, unless otherwise specified, with
provisions for self-alignment and thrust-load requirements that may be imposed by
the service.
2. Bearings shall be constructed of vacuum degassed or processed steel alloys and shall
have a certified ABMA 9, L-10 minimum life expectancy rating of 200,000 hours.
Bearings shall have dusttight seals suitable for lubricant pressures encountered.
Housings shall be cast iron unless otherwise specified or approved.
3. Bearings shall be grease lubricated. Lubrication provisions shall preclude
overheating due to excess lubricant. Grease supply fittings shall be surface ball check
type. Where necessary, manual or automatic grease pressure relief fittings shall be
provided. Bearing and seal construction permitting, relief fittings shall be located on
the side opposite the supply fitting. Relief fittings shall be visible from normal
maintenance locations. Lubrication provisions shall include extension tubes where
necessary.
4. Bearings shall be dowelled in place with AISI 18-8 corrosion-resistant steel spiral
wrapped or split pins, unless otherwise specified or approved. Taper pins are not
acceptable.
5. Factory sealed antifriction bearings which conform to above specified materials and
ABMA 9, L-10 life expectancy requirements shall be provided for fans driven by
motors with a power rating of smaller than 1/2 horsepower (375 watt)

D. Drives:

1. Fan drives shall be V-belt type.


2. V-belt drive application shall conform to the manufacturer's published
recommendations.
3. Horsepower (Wattage) rating of drive shall be based on maximum pitch diameter of
sheave.

POWER VENTILATORS 15853 - Page 4 of 11


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

4. Drives with motors up to and including 10 horsepower (7500 watt) shall be standard
belt section, variable sheave type, with a service factor of not less than 1.5.
5. Drives with motors over 10 horsepower (7500 watt) and up to and including 40
horsepower (30 kilowatt of power) shall be standard section, fixed-sheave or
variable-sheave type, with a service factor of not less than 1.5.
6. Drives with motors over 40 horsepower (30 kilowatt of power) shall be fixed-sheave,
high-capacity, supertype, with a service factor of not less than 1.5.
7. Belt drives shall be located outboard of bearings. Drive and driven shafts shall be
aligned by the four-point method.
8. Belt tension shall be adjusted in accordance with the manufacturer's
recommendations.
9. Alignment and final belt tensioning shall be performed in the presence of the
Engineer.

E. Belts:

1. Belts shall be endless, of Dacron-reinforced elastomer construction, with cross


section to suit sheave grooves.
2. Belts shall be matched and measured on a belt-matching machine at the factory.
Selection by code numbers, sag numbers, or match numbers is not acceptable. Each
belt set shall be bound with wire and tagged with equipment identification.

2.3 UTILITY SET FANS

A. Description: Belt-driven centrifugal fans consisting of housing, wheel, fan shaft, bearings,
motor, drive assembly, and accessories.

B. Housings: Fabricated of steel with side sheets fastened with a deep lock seam or welded to
scroll sheets.

1. Housings Discharge Arrangement: Adjustable to 8 standard positions.

C. Fan Wheels: Single width, single inlet, welded to cast-iron or cast-steel hub and spun-steel
inlet cone, with hub keyed to shaft.

1. Blade Materials: Steel.


2. Blade Type: Die formed, backward inclined or forward curved, as scheduled.

D. Fan Shaft: Turned, ground, and polished steel keyed to wheel hub.

E. Shaft Bearings: Prelubricated and sealed, self-aligning, pillow-block-type ball bearings with
AFBMA 9, L-50 of 200,000 hours.

F. Belt Drives: Factory mounted, with final alignment and belt adjustment made after
installation.

1. Service Factor Based on Fan Motor: 1.5.


2. Motor Pulleys: Adjustable pitch. Select pulley so that pitch adjustment is at the
middle of the adjustment range at fan design conditions.
3. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for multiple belt drives.
4. Belt Guards: Fabricate of steel for motors mounted on the outside of the fan cabinet.

POWER VENTILATORS 15853 - Page 5 of 11


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

G. Accessories: The following accessories are required as indicated:

1. Backdraft Dampers: Gravity actuated with counterweight and interlocking aluminum


blades and felt edges in steel frame installed on fan discharge.
2. Access Doors: Gasketed doors with latch-type handles.
3. Scroll Dampers: Single-blade damper installed at fan scroll top with adjustable
linkage.
4. Spark-Resistant Construction: AMCA 99 construction, as indicated.
5. Inlet Screens: Removable wire mesh.
6. Drain Connections: DN20 threaded coupling drain connection installed at lowest
point of housing.
7. Weather Hoods: Weather resistant with stamped vents over motor and drive
compartment.

2.4 IN-LINE VENTILATORS

A. Description: Centrifugal fans designed for installing in ceiling, wall, duct, or for concealed
in-line applications.

B. Housing: Galvanized steel lined with acoustical insulation.

C. Fan Wheel: Centrifugal wheels directly mounted on motor shaft. Fan shrouds, motor, and
fan wheel shall be removable for service.

D. Electrical Requirements: Junction box for electrical connection on housing and receptacle
for motor plug-in.

E. Variable-Speed Controller: Solid-state control to reduce speed from 100 percent to less than
50 percent.

F. Accessories: Manufacturer's standard roof jack, wall cap, or duct collars, and transition
fittings.

2.5 IN-LINE CENTRIFUGAL FANS

A. Description: In-line, belt-driven centrifugal fans consisting of housing, wheel, outlet guide
vanes, fan shaft, bearings, drive assembly, motor and disconnect switch, mounting brackets,
and accessories.

B. Housing: Split, spun-aluminum housing, with aluminum straightening vanes; inlet and
outlet flanges; and support bracket adaptable to floor, side wall, or ceiling mounting.

C. Direct-Drive Units: Motor encased in housing out of air stream, factory wired to disconnect
located on outside of fan housing.

D. Belt-Driven Units: Motor mounted on adjustable base, with adjustable sheaves, enclosure
around belts within fan housing, and lubricating tubes from fan bearings extended to outside
of fan housing.

E. Fan Wheels: Aluminum, airfoil blades welded to aluminum hub.

POWER VENTILATORS 15853 - Page 6 of 11


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

F. Accessories: The following accessories are required as indicated:

1. Volume-Control Damper: Manually operated with quadrant lock, located in fan


outlet.
2. Companion Flanges: For inlet and outlet duct connections.
3. Fan Guards: Expanded metal in removable frame. Provide belt guards for units not
connected to ductwork.

2.6 MOTORS

A. Refer to Division 15 Section "Motors" for general requirements for factory-installed motors.

B. Motor Construction: NEMA MG 1, general purpose, continuous duty, Design B or


equivalent characteristics in accordance with IEC 34.

C. Air-over-motor units shall be provided with NEMA-rated Class H insulation for all services
where air stream temperature exceeds 38 deg. C (100 deg. F). Air velocity over motor
surfaces shall be sufficient to maintain insulation temperatures within NEMA standards at
maximum fan horsepower. Motors used with variable frequency drives (VFDs) shall be
rated for VFD use.

D. Enclosure Type: The following features are required as indicated:

1. Open dripproof motors where satisfactorily housed or remotely located during


operation.
2. Guarded dripproof motors where exposed to contact by employees or building
occupants.
3. Totally enclosed motors where located in unfiltered air streams.

E. Motor Bases: Motor shall be provided with adjustable motor bases, except as otherwise
specified. Motors over 7-1/2 horsepower (5600 watt of power) with fixed-sheave standard
belt section drives shall be provided with adjustable, pivoted motor bases wherever
equipment configuration permits proper installation.

2.7 FACTORY FINISHES

A. Sheet Metal Parts: Prime coat before final assembly.

B. Exterior Surfaces: Baked-enamel finish coat after assembly.

C. Aluminum Parts: No finish required.

D. Paint finish of fans exposed to outdoor shall be suitable for the hot and humid climate of the
project.

E. Internal sides of fans used for 100 percent outdoor air shall be specially painted.

POWER VENTILATORS 15853 - Page 7 of 11


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

2.8 SOURCE QUALITY CONTROL

A. Testing Requirements: The following factory tests are required as indicated:

1. Sound Power Level Ratings: Comply with AMCA 301, "Methods for Calculating
Fan Sound Ratings From Laboratory Test Data." Test fans according to AMCA 300,
"Reverberant Room Method for Sound Testing of Fans." Label fans with the AMCA
Seal.
2. Fan Performance Ratings: Establish flow rate, pressure, power, air density, speed of
rotation, and efficiency by factory tests and ratings according to AMCA 210,
"Laboratory Methods of Testing Fans for Rating."

B. Fans used for smoke extract shall be UL listed and suitable for high smoke temperature of
260 deg. C (500 deg. F) for a minimum of four hours continuous operation ..

C. Noise level of fans shall not exceed noise level specified for location of installation. The
overall efficiency shall be minimum 60%.

D. Fans utilized for kitchen extract shall be spark-resistant and suitable for kitchen operation.
Fans shall be UL and cUL listed for grease removal, tested under high temperature exhaust
of 190 deg. C (375 deg. F). Fans shall be tested in accordance with relevant NFPA
standard. Fan coating shall be as directed by the Engineer. Units shall include the
following:

1. Bolted access door.


2. Drain connection.
3. Aluminum grease trap.
4. Weatherhood.
5. Upblast discharge.
6. Windband discharge cap with gravity damper.
7. Outlet guard where fan discharge is accessible.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine areas and conditions for compliance with requirements of installation tolerances
and other conditions affecting performance of the power ventilators. Do not proceed with
installation until unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A. Install power ventilators according to manufacturer's written instructions.

B. Support units using the vibration-control devices indicated. Vibration-control devices are
specified in Division 15 Section "Mechanical Vibration Control Controls and Seismic
Restraints."

1. Support utility set fans on concrete housekeeping bases or roof supports using
neoprene pads. Secure units to anchor bolts installed in housekeeping base.

POWER VENTILATORS 15853 - Page 8 of 11


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

2. Support utility set fans on concrete housekeeping bases or roof supports using housed
spring isolators. Secure units to anchor bolts installed in housekeeping base.
3. Secure roof-mounted fans to roof curbs with cadmium-plated hardware.

a. Installation of roof curbs is specified in Division 7 Sections.

4. Suspend units from structural steel support frame using threaded steel rods, vibration
isolation springs, and seismic restraints.
5. Ceiling Units: Suspend units from structure using threaded rods or metal straps, and
neoprene washers.

C. Install units with clearances for service and maintenance.

D. Label units according to requirements specified in Division 15 Section "Mechanical


Identification."

3.3 HOUSEKEEPING BASES

A. Construct concrete housekeeping pads as follows:

1. Coordinate size of housekeeping bases with actual unit sizes provided. Construct
base 100 mm larger, in both directions, than the overall dimensions of the supported
unit.
2. Form concrete pads with steel channels conforming to ASTM A 36M, size and
location as indicated. Miter and weld corner and provide cross bracing. Anchor or
key to floor slab.
3. Install reinforcing bars, tied to frame, and place anchor bolts and sleeves to facilitate
securing units.
4. Place concrete and allow to cure before installing units. Use Portland cement
conforming to ASTM C 150, 27-MPa compressive strength, and normal-weight
aggregate.
5. Clean exposed steel form according to SSPC Surface Preparation Specifications SP 2
or SP 3 and apply 2 coats of rust-preventive metal primer and paint.

3.4 CONNECTIONS

A. Duct installation and connection requirements are specified in other Division 15 Sections.
Drawings indicate the general arrangement of ducts and duct accessories. Make final duct
connections with flexible connectors.

B. Electrical: Conform to applicable requirements in Division 16 Sections.

C. Grounding: Ground equipment. Tighten electrical connectors and terminals, including


grounding connections, according to manufacturer's published torque-tightening values.
Where manufacturer's torque values are not indicated, use those specified in UL 486A and
UL 486B.

3.5 FIELD QUALITY CONTROL

A. Manufacturer's Field Service: Engage a factory-authorized service representative to


supervise the field assembly of components and installation of fans, including duct and
electrical connections, and to report results in writing.

POWER VENTILATORS 15853 - Page 9 of 11


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

3.6 ADJUSTING

A. Adjust damper linkages for proper damper operation.

B. Adjust belt tension.

C. Lubricate bearings.

3.7 CLEANING

A. After completing installation, inspect exposed finish. Remove burrs, dirt, and construction
debris, and repair damaged finishes including chips, scratches, and abrasions.

B. Clean fan interiors to remove foreign material and construction debris. Vacuum clean fan
wheel and cabinet.

3.8 COMMISSIONING

A. Final Checks before Startup: Perform the following operations and checks before startup,
and report results in writing:

1. Verify that shipping, blocking, and bracing are removed.


2. Verify that unit is secure on mountings and supporting devices and that connections
for ducts, and electrical components are complete. Verify that proper thermal-
overload protection is installed in motors, starters, and disconnects.
3. Perform cleaning and adjusting specified in this Section.
4. Disconnect fan drive from motor, verify proper motor rotation direction, and verify
fan wheel free rotation and smooth bearing operation. Reconnect fan drive system,
align and adjust belts, and install belt guards.
5. Lubricate bearings, pulleys, belts, and other moving parts with factory-recommended
lubricants.
6. Verify that manual and automatic volume control and fire and smoke dampers in
connected ductwork systems are in the fully open position.
7. Disable automatic temperature-control operators.

B. Starting procedures for fans are as follows:

1. Energize motor; verify proper operation of motor, drive system, and fan wheel.
Adjust fan to indicated RPM.
2. Measure and record motor voltage and amperage.

C. Shut unit down and reconnect automatic temperature-control operators.

D. Refer to Division 15 Section "Testing, Adjusting, and Balancing" for procedures for air-
handling system testing, adjusting, and balancing.

E. Replace or adjust fan and motor pulleys as required to achieve design conditions. Fix in
final position after balancing is achieved.

POWER VENTILATORS 15853 - Page 10 of 11


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

3.9 DEMONSTRATION

A. Train the Employer's maintenance personnel to adjust, operate, and maintain power
ventilator units. Refer to Division 1 Section "[Demonstration and Training] [Closeout
Procedures]."

END OF SECTION 15853

POWER VENTILATORS 15853 - Page 11 of 11


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

SECTION 15170 - MOTORS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including Conditions of Contract and
Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes basic requirements for factory-installed and field-installed motors.

B. Related Sections include the following:

1. Division 15 Sections for application of motors and reference to specific motor


requirements for motor-driven equipment.
2. Division 16 Sections for application of motors with Variable Frequency Drives
(VFD).

1.3 SUBMITTALS

A. Product Data: Show nameplate data and ratings; characteristics; mounting arrangements;
size and location of winding termination lugs, conduit entry, and grounding lug; and
coatings.

B. Factory Test Reports: For specified tests.

C. Field Test Reports: Indicate and interpret test results for compliance with performance
requirements.

1.4 QUALITY ASSURANCE

A. Comply with related electrical Standards, referred to in Division 16.

B. Comply with DEWA regulations for electrical installations.

PART 2 - PRODUCTS

2.1 BASIC MOTOR REQUIREMENTS

A. Basic requirements apply to mechanical equipment motors, unless otherwise indicated.

B. Motors shall be of the energy efficient design.

C. Motors 0.37 kW (1/2 HP) and Larger: Three phase, 400 V up to 150 kW (200 HP) and soft
starters or 11,000 V for 150 kW (250 HP) and larger.

MOTORS 15170 - Page 1 of 4


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

D. Motors smaller than 0.37 (1/2 HP): Single phase, 230 V.

E. Frequency Rating: 50 Hz, unless otherwise indicated.

F. Voltage Rating: Determined by voltage of circuit to which motor is connected.

G. Service Factor: According to IEC 60034 and 60072, unless otherwise indicated.

H. Capacity and Torque Characteristics: Rated for continuous duty and sufficient to start,
accelerate, and operate connected loads at designated speeds, in indicated environment, with
indicated operating sequence, and without exceeding nameplate ratings or considering
service factor.

I. Enclosure: Totally enclosed, fan-cooled type, unless otherwise indicated.

J. Index of Protection (IP): Motors shall be [IP55][IP56][IP65][IP66] for outdoor use and
[IP42], [IP43] for indoor use.

K. Temperature Rise: Shall not exceed the permissible limit for the insulation class based on 50
deg. C (122 deg. F) ambient temperature, for outdoors conditions and 40 deg. C for indoor
conditions unless otherwise indicated.

L. Motors that utilize a Variable Frequency Drive (VFD) shall be inverter rated and shall
comply with Division 16, Section “Motor Control Centers”.

2.2 THREE PHASE MOTORS

A. Description: IEC 60034 and 60072, medium induction motor.

1. Design Characteristics: IEC Standards, unless otherwise indicated.


2. Energy-Efficient Design: Premium efficiency – Class “eff1”, unless otherwise
indicated. Classification in accordance with the definition set by the “European
Commission of Electric Machinery and Power Electronics Manufacturers”.
3. Stator: Copper windings, unless otherwise indicated. Multispeed motors have
separate winding for each speed.
4. Rotor: Squirrel cage, unless otherwise indicated.
5. Bearings: Double-shielded, prelubricated ball bearings suitable for radial and thrust
loading.
6. Temperature Rise: Match insulation rating, unless otherwise indicated.
7. Insulation: Unless otherwise indicated, Class B for motors located in air-conditioned
spaces and Class F for motors located outside or in non air-conditioned spaces.

B. Motors Used with Reduced-Inrush Controllers: Match wiring connection requirements for
indicated controller, with required motor leads brought to motor terminal box to suit control
method. Maximum permissible starting current shall be 5 times the Full Load Current
(FLC).

C. Motors Used with Variable-Frequency Controllers: Ratings, characteristics, and features


coordinated with and approved by controller manufacturer.

1. Critical vibration frequencies are not within operating range of controller output.
2. Temperature Rise: Match rating for Class F insulation.
3. Insulation: Class F.

MOTORS 15170 - Page 2 of 4


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

4. Thermal Protection: Where indicated, conform to IEC requirements for thermally


protected motors.

D. Rugged-Duty Motors: Where indicated, motors are totally enclosed with 1.25 minimum
service factor, greased bearings, integral condensate drains, and capped relief vents.
Windings are insulated with nonhygroscopic material. External finish is chemical-resistant
paint over corrosion-resistant primer.

E. Source Quality Control: Perform the following routine tests according to IEC:

1. Measurement of winding resistance.


2. No-load readings of current and speed at rated voltage and frequency.
3. Locked rotor current at rated frequency.
4. High-potential test.
5. Alignment.

2.3 SINGLE-PHASE MOTORS

A. Type: As indicated or selected by manufacturer from one of the following, to suit starting
torque and other requirements of specific motor application.

1. Permanent-split capacitor.
2. Split-phase start, capacitor run.
3. Capacitor start, capacitor run.
4. Insulation: Unless otherwise indicated, Class B for motors located in air-conditioned
spaces and Class F for motors located outside or in non air-conditioned spaces.
5. Energy-Efficient Design: Premium efficiency – Class “eff1”, unless otherwise
indicated. Classification in accordance with the definition set by the “European
Commission of Electric Machinery and Power Electronics Manufacturers”.

B. Shaded-Pole Motors: Do not use, unless motors are smaller than 0.037 kW (1/20 hp).

C. Thermal Protection: Where indicated or required, internal protection automatically opens


power supply circuit to motor when winding temperature exceeds a safe value calibrated to
temperature rating of motor insulation. Thermal protection device automatically resets
when motor temperature returns to normal range, unless otherwise indicated.

D. Bearings: Ball-bearing type for belt-connected motors and other motors with high radial
forces on motor shaft. Sealed, prelubricated sleeve bearings for other single-phase motors.

PART 3 - EXECUTION

3.1 ADJUSTING

A. Use adjustable motor mounting bases for belt-driven motors.

B. Align pulleys and install belts.

C. Tension according to manufacturer's written instructions.

D. Install power feeders to motors in raceways. Locate raceways close to motor terminal box
and use liquidtight flex for final connection to motor terminal box.

MOTORS 15170 - Page 3 of 4


S14015-FD-03-SPC-TS00-ME-01 REV 0
S14015-0100M
DESIGN FOR TWO NEW BRT TERMINUS STATIONS

E. Motors located in classified areas shall be installed in accordance with IEC


recommendations for“Hazardous (classified) Locations”.

3.2 COMMISSIONING

A. Check operating motors for unusual conditions during normal operation. Coordinate with
the commissioning of the equipment for which the motor is a part.

B. Take measurements and prepare a log of voltage, current, frequency, and power.

C. Report unusual conditions.

D. Report current deficiencies of field-installed units.

END OF SECTION 15170

MOTORS 15170 - Page 4 of 4


S14015-FD-03-SPC-TS00-ME-01 REV 0

You might also like