System

Refrigerant number
Occupancy
Safety group
refrigerating system
classification
Correction
allowable refrigerant quantity lb/1000 ft3
Corrected allowable refrigerant quantity lb/1000 ft3
Occupied area served by package unit in m2
Height in m
Occupied volume served by package unit in m3
Occupied volume served by package unit in ft3
Plenum height
additional dilution volume in m3
additional dilution volume in ft3
Total dilution volume in ft3
Number of refrigeration circuits
Maximum refrigerant quantity in
each independent circuit in lb
Rooftop package unit
R-134a
Institutional
A1

high probability

0.5
13
6.5
39
3.1
120.9
4357
0.8
31.2
1124
5481
2

35.63