B503PRO SERIES SENSORLESS VECTOR CONTROL CONTROLLER SIMPLE MANUAL
Fault
Fault Type Possible Causes Solutions
Code
Constant Speed 2. An external force drives the motor during Cancel the external force or install
operation the braking resistor
Control Power 1. The input voltage is not within the Adjust the voltage to the allowable
CPE
Supply Fault allowable range range
1. Instantaneous power failure occurs on the
input power supply.
2. The AC drive’s input voltage is not within Reset the fault
the allowable range Adjust the voltage to normal range
UV Under-voltage 3. The DC bus voltage is abnormal Contact the agent or BEDFORD
4. The rectifier bridge and buffer resistor are Contact the agent or BEDFORD
faulty Contact the agent or BEDFORD
5. The drive board is faulty
6. The main control board is faulty
1. Fb.01 is set improperly Set Fb.01 correctly
2. The load is too heavy or locked rotor occurs Reduce the load and check the
OL1 Motor Overload
on the motor motor and the mechanical condition
3. The model is of too small power class Select a model of higher power class
1. The load is heavy or locked rotor occures Reduce the load and check the
AC drive
OL2 on the motor motor and the mechanical condition
Overload
2. The model is of too small power class Select a model of higher power class
1. The three phase input power is abnormal Eliminate the external faults
Power Input
SPI 2. The drive board is faulty Contact the agent or BEDFORD
Phase Failure
3. The main control board is faulty. Contact the agent or BEDFORD
1. The cable connecting AC drive and motor is
Eliminate the external faults
faulty
Check whether the motor
Power Output 2. The controller’s three -phase outputs are
SPO three-phase winding is normal
Phase Failure unbalanced when the motor is running
Contact the agent or BEDFORD
3. The drive board is faulty
Contact the agent or BEDFORD
4. The IGBT is faulty
1. The ambient temperature is too high Lower the ambient temperature
2. The air filter is blocked Clean the air filter
OH2 IGBT Overheat 3. The fan is damaged Replace the damaged fan
4. The thermistor of the IGBT is damaged Replace the damaged the thermistor
5. The AC drive IGBT is damaged Replace the AC drive IGBT
External Check the external equipment input
EF 1. External fault signal is input via DI
Equipment Fault Reset the operation
Check the cabling of the host
computer
1. The host computer is in abnormal state
Check the communication cabling
Communication 2. The communication cable is faulty
CE Set the communication parameters
Fault 3. The communication parameters are set
properly
improperly
Press STOP/RST key to reset or
Contact the agent or BEDFORD
1. The drive board and power supply are Replace the drive board or power
CF Contactor Fault faulty supply board
2. The contactor is faulty Replace the contactor
1. The cabling of the main control board is in Check the connector and plug the
Current
ITE bad contact cable again
Detection Fault
2. Auxiliary power supply is damaged Contact the agent or BEDFORD
26
B503PRO SERIES SENSORLESS VECTOR CONTROL CONTROLLER SIMPLE MANUAL
Fault
Fault Type Possible Causes Solutions
Code
3. The HALL device is damaged Contact the agent or BEDFORD
4. Amplication circuit is abnormal Contact the agent or BEDFORD
1. The motor capacity and the controller Replace the controller model
power class are not matched according to motor capacity
2. The motor parameters are set according to Set the parameters according to the
Motor
the nameplate nameplate properly
TE Auto-tuning
3. The deviation between the auto-tuning Make the motor non-loaded and
Fault
parameter and the nameplate parameter is identify the nameplate again.
too big Check the cable connecting the
4. The motor auto-tuning times out motor and the AC drive
1. Read-write fault of control parameter Press STOP/RST key to reset or
EEPROM
EEP occurs contact the agent or BEDFORD
Read-write Fault
2. EEPROM chip is damaged Contact the agent or BEDFORD
The Controller 1. Over-voltage exits Handle based on over-voltage
IHE
Hardware Fault 2. Over-current exits Handle based on over-current
Shot Circuit to
SCF 1. The motor is short circuit to the ground Replace the cable or motor
Ground
Accumulative
1. The accumulative running time reaches the Clean the record through parameter
End2 Running Time
setting value initialization function
Reached
Load Becoming 1. The running current of AC drive is too
LFE Check whether the load becomes 0
0 Fault small
PID Feedback
1. PID feedback cable is disconnected Check PID feedback cable
PIDE Lost During
2. PID feedback source is disappeared Check PID feedback source
Running
Pulse-by-pulse 1. The load is too heavy or locked rotor occurs Reduce the load and check the
CLE Current Limit on the motor motor and mechanical condition
Fault 2. The model is of too small power class Select a model of higher power class
Motor
1. Change the selection of the motor during Perform motor switch over after the
SPE Switchover Fault
the running of the controller controller stops
During Running
Check whether the motor
mechanical is abnormal ,the motor
1. Locked rotor occurs on the motor
Too Large Speed auto-tuning is performed and
ADL 2. The cable between the AC drive’s output
Deviation parameter of F2.10 is too small
terminals UVW and the motor is abnormal
Check the cable connecting the AC
drive and motor
Motor
OSE 1. The motor auto-tuning is not performed Perform the motor auto-tuning
Over-speed