Download as pdf or txt
Download as pdf or txt
You are on page 1of 42

Date: 2015-11-12

Architectural Interior Drawings Mechanical Drawings Key Plan - First Floor


5109-ID01 General Notes 5109-M0 Mechanical Title Page
5109-ID02 Furniture Plan - First Floor 5109-M1 Mechanical Demolition - First Floor
5109-ID03 Demolition Plan - First Floor 5109-M2 Mechanical Demolition - Second Floor
5109-ID04 Reflected Ceiling Demolition Plan - First Floor 5109-M3 Mechanical Demolition - Third Floor
5109-ID05 Partition Plan - First Floor 5109-M4 Mechanical New - First Floor
5109-ID06 Reflected Ceiling Plan - First Floor 5109-M5 Mechanical New - Second Floor
211-2141 Thurston Drive 5109-ID07 Power/Voice/Data Plan - First Floor 5109-M6 Mechanical New - Third Floor
Ottawa ON K1G 6C9 5109-ID08 Floor and Wall Finish Plans - First Floor 5109-M7 Mechanical New - Ground + First Floor

Issued for: Tender


5109-ID09 Furniture Plan - Second and Third Floors Entrance Vestibules Dn

T 613-739-3699 5109-ID10 Demolition Plan - Second and Third Floors 5109-M8 HVAC Works Ground Floor Up
Stair F

F 613-739-3965 5109-ID11 Reflected Ceiling Demolition Plan - Second and Third Floors
5109-ID12 Partition Plan - Second and Third Floors Electrical Drawings
info@LWG-ai.com
5109-ID13 Reflected Ceiling Plan - Second and Third Floors
LWG-ai.com 5109-E0 Electrical Title Page Up Dn
Up Up

5109-ID14 Power/Voice/Data Plan - Second and Third Floors


5109-ID15 Floor and Wall Finish Plans - Second and Third Floors 5109-E1 Electrical Demolition - First Floor Stair D

5109-ID16 Reception Desk Detail Plan 5109-E2 Electrical Demolition - Second Floor
5109-ID17 Reception Desk Elevations 5109-E3 Electrical Demolition - Third Floor
5109-ID18 Elevator Facade Elevations 5109-E4 Electrical New - First Floor
5109-ID19 Graphics Display Elevations 5109-E5 Electrical New - Second Floor
5109-ID20 Graphics Display and Millwork Elevations 5109-E6 Electrical New - Third Floor
5109-ID21 5109-E7 Electrical Specifications
Reception Desk Millwork Sections Key Plan - Second Floor
5109-ID22 Millwork and Architectural Sections

Dn

Stair F

Up

Up Dn

Stair D

Key Plan - Third Floor


NRC Lobby

Project: NRC Lobby Renovation


Renovation
1200 Montreal Road - M58
1st, 2nd, and 3rd Floor Lobby

Project Number: 14087


Ottawa ON
Dn

Mechanical & Electrical Consultants

TTF Engineering Stair F

Project North
1.0 EXAMINATION 24.0 REFLECTED CEILING-GENERAL NOTES 31.0 WALLCOVERING-PREPARATION OF SURFACES

1.0.1 Reserved. 24.0.1 Replace all damaged or soiled tiles. Replace all damaged or soiled gypsum and plaster ceiling finishes. 31.0.1 Size and treat wall surfaces to receive wall covering to installation.

2.0 GENERAL CONSTRUCTION NOTES 24.0.2 This drawing is for location of light fixtures only and is to be read in conjunction with Electrical drawings. 32.0 WALLCOVERING-INSTALLATION

2.0.1 All partitions to be constructed on grid unless shown otherwise. All walls to be built at a 90 or 45 degree angle per plan unless noted otherwise. 24.0.3 For location of exit signs and emergency lighting, refer to Electrical/Mechanical drawings. 32.0.1 Use rolls in collective numerical sequence of Manufacturer.

2.0.2 All partitions to be constructed from center of Base Building perimeter window mullions, where applicable. 24.0.4 Contractor to ensure air handling balance report is submitted and that system is balanced to the satisfaction of the Building Representative, Client and Mechanical Consultant. 32.0.2 Place panels consecutively in exact order they are cut from roll including spaces above and below windows, doors and similar penetrations.

2.0.3 Consult Department Representative before work commences on particular items where Department Representative approval is required. 24.0.5 Contractor to ensure installation and/or relocation of thermostats as required. Refer to Engineer's drawings for locations. 32.0.3 Reverse alternate strips except on match patterns.

2.0.4 Contractor shall only make changes to the design or materials specified upon written approval from the Department Representative. 24.0.6 Contractor shall refer to Mechanical drawings for exact location of exhaust fans. 32.0.4 Trim additional selvage where required to achieve colour pattern match at seams.

2.0.5 Contractor to ensure that all trades will cooperate to facilitate speedy execution of work. While trades are completing work, they shall protect all work and materials of other trades. 24.0.7 Existing exhaust tiles to be cleaned or replaced if damaged. 32.0.5 Apply adhesive to wall using a roller or paste brush.

2.0.6 Chalk all partition locations and obtain approval from Department Representative prior to installing metal track and studs. 24.0.8 All switches and cover plates to be white. 32.0.6 Hang non-matched patterns by overlapping edges and double cutting through both thickness with 1mm or 1.5mm thick zinc or aluminum strip back up to prevent cutting substrate.

2.0.7 Contractor to perform all work specified on all drawings & specifications and supply all necessary material & labour required to complete all phases of the work. 24.0.9 All switches unless otherwise noted to be installed at 1067 mm A.F.F. (Centered). Refer to proper elevations. 32.0.7 Wrap fabric 150mm beyond inside and outside corners. No cutting at corners permitted, unless pattern or colour changes.

2.0.8 Partitions falling on a window mullion to include adhesive "Neoprene" gasket for sound insulation. 24.0.10 Unless indicated otherwise, all general fluorescent light fixtures are to be switched from Base Building central location. Refer to Electrical drawings. 32.0.8 No horizontal seams permitted.

2.0.9 Gypsum board is taped, sanded & primed ready to receive new finish unless otherwise noted. Refer to Finish Plan. 24.0.11 Contractor is responsible for replacing any ceiling tiles and/or grid damaged and/or soiled during construction. 32.0.9 Use stiff brittle brush or broad knife to eliminate air pockets and secure wallpaper to substrate.

2.0.10 Gypsum board joints are to be staggered on each side of metal studs. 24.0.12 All ceiling fixtures and components not utilized in construction are to be returned to Building Representative. 32.0.10 Remove excess adhesive with damp sponge from seams as work progresses, and wipe clean and dry with cloth towel.

2.0.11 All dimensions are to the centreline of walls, except to the face of core walls & unless otherwise noted. 24.0.13 Unless noted otherwise, new GWB ceilings and bulkheads to be painted P1. 32.0.11 Leave completed work smooth, clean, without wrinkles, gaps, overlaps or air pockets.

2.0.12 Contractor to refer to Millwork Drawings for all millwork located on Partition Plan. Contractor to coordinate required blocking or concealed components within partitions for proper millwork support. 24.0.14 Contractor to mark location of pot lights for approval by Department Representative prior to installation. Ceiling tiles or GWB cut without approval shall be replaced or repaired by the Contractor at his expense. 33.0 CASH ALLOWANCE

2.0.13 It is the Contractor's responsibility to read this and all Interior Design drawings in conjunction with all other drawings including other drawings. Any discrepancies between drawings will be reported to the 24.0.15 All fixture dimensions are O.C. unless noted otherwise. 33.0.1 Provide cash allowance of $103, 429.14 (HST included) for Europtimum graphic display panels. Contractor to coordinate installation.
Department Representative for clarification during the tender process and prior to construction.
24.0.16 Contractor to ensure location of ceiling fixtures do not interfere with any structural or mechanical components and will report any conflicts prior to commencing work. The Contractor will be responsible for the 33.0.2 Provide separate line item pricing in Tender package for custom metal lettering and standoffs at reception desk.
3.0 GUARANTEES cost to relocate any new building systems should he fail to report conflicts prior to installation.
211-2141 Thurston Drive T 613-739-3699
3.0.1 Before completion of work, collect all agreements, guarantees and warranties and deposit with Building Owner. 25.0 INSTALLATION NOTES-SUSPENDED CEILINGS ABBREVIATIONS
Ottawa ON K1G 6C9 F 613-739-3965
4.0 SHOP DRAWINGS 25.0.1 Set Inserts In structural ceiling not more than 1219mm centers both ways to limit deflection to 1/360 without sag. A.F.F.: Above Finished Floor
GWB: Gypsum Wall Board
4.0.1 Shop Drawings as required are to be provided for Department Representative's approval prior to start of fabrication. 25.0.2 Lay-in tiles per Manufacturer's specifications. Refer to legend for specification of new ceiling grid and tile as required. O.C.: On Center
w/: With
info@LWG-ai.com LWG-ai.com
4.0.2 The Contractor shall provide control samples for approval by Department Representatives of all paints specified. 305mm x 305mm samples to be tagged according to paint finishes legend. All paint samples 25.0.3 Use edge moulding and shadow wall mouldings at vertical surfaces. Mouldings to match adjacent t-bar grid. c/w: Complete With
shall be approved by Department Representative prior to application. Samples to be provided on actual substrate material. ga: Gage
25.0.4 Do not erect ceiling suspension system grid until work above ceiling has been inspected by Mechanical and Electrical Consultants. u/s: Under Side
5.0 MATERIALS - MINIMUM STANDARD U.O.N.: Unless Otherwise Noted
25.0.5 Hang ceiling independent of walls, columns, fascias, ducts, pipes and conduit.
5.0.1 Contractor to check all materials for defects prior to commencing construction.
25.0.6 Where position of electrical and mechanical fixtures is changed by tile, restore as closely as possible to original.
5.0.2 Contractor shall not deviate from Department Representative's specifications without prior written authorization of Department Representative.
25.0.7 Completed suspension system grid to support superimposed loads, such as lighting fixtures, diffusers, grilles and speakers.
5.0.3 Contractor to notify Department Representative of any materials that are unavailable or have delayed delivery dates.
25.0.8 Interlock cross member to main runner to provide rigid assembly.
5.0.4 Unauthorized substitutions will not be accepted.
25.0.9 Finished ceiling system grid to be square with adjoining walls and level within 1:1000.
5.0.5 All materials are to be ordered when the construction contract is awarded. At this time the Contractor is to confirm that all deliveries will meet Construction Schedule. Substitutions will not be accepted due to late
ordering. In the event that materials are not available in time to meet scheduled completion dates, the Contractor shall provide proof of date of order of materials prior to requesting substitutions. 26.0 MECHANICAL/PLUMBING PLAN

6.0 FEES, PERMITS, CERTIFICATES 26.0.1 This plan is for information regarding occupancy loads only and is to be read in conjunction with Mechanical drawings.

6.0.1 Reserved. 26.0.2 All mechanical work to be coordinated and overseen by the Contractor.

7.0 FIRE AND SAFETY REQUIREMENTS 26.0.3 Contractor to ensure installation and/or relocation of thermostats as required. Refer to Mechanical drawings for specifications.

7.0.1 All materials to meet flame spread rating requirement of authorities having jurisdiction. 26.0.4 Exhaust fans to be baffled and motors to be remote to rooms. Motors to be located in corridors. Exhaust fan controls to be located in conjunction with light switches. Refer to reflected ceiling plan for heights,

7.0.2 Fire stop new or existing penetrations in floor & walls requiring fire rating.
locations, notes and specifications.

26.0.5 Refer to Mechanical drawings for smoke detector locations.


Project
8.0 SERVICES

8.0.1 Reserved.
26.0.6 Ensure new partitions within plenum areas do not interfere with mechanical ducts, electrical conduits, boxes or other. Contractor to build bulkhead around mechanical and electrical items as required. Refer to
Mechanical drawings.
North
9.0 REMOVED MATERIAL 26.0.7 Refer to Mechanical and Electrical drawings for all Mechanical and Electrical requirements.

9.0.1 The Contractor shall remove existing equipment and finishes not required for this project. 27.0 VOICE/DATA/ELECTRICAL-GENERAL NOTES

9.0.2 Retain and reuse any existing items suitable to new construction. Refer to Demolition Plan as required for location of reused materials. 27.0.1 This plan is for location of electrical and communication outlets only and is to be used in conjunction with Electrical drawings.

9.0.3 Except if expressly stated otherwise, materials indicated for removal become the Building Owner's property and shall not be taken from the site. 27.0.2 Any discrepancies arising from the Electrical drawings being used without reference to this drawing may not be acceptable.

10.0 CEILING REPAIRS 27.0.3 Electrical and Mechanical drawings will indicate electrical panels wiring diagrams, air supply and return, exhaust fan connections, and any other special requirements.

10.0.1 Repairs shall include: 27.0.4 All electrical work to be coordinated and overseen by the General Contractor.

27.0.5 Contractor to provide two weeks advanced notice for commencement of telephone installation and wiring for networking may commence. Contractor to coordinate with Building Representative relating to all
telephone, sound system, speakers, and computer equipment wiring.
10.0.2 Infrequent small holes left in ceiling grid by nails or screws may be repaired by filling with gypsum paste if made imperceptible.
27.0.6 All electrical work, all conduits and boxes for communicating equipment to be supplied and installed by Contractor.
11.0 PROTECTION AND DUST CONTROL
27.0.7 All wiring to be concealed in partitions and/or plenum. Plenum rated wire to be used.
11.0.1 Protect finished work against damage until take over. Protect adjacent spaces against the spread of dust and dirt beyond the work area.
27.0.8 No double sided electrical or communication outlets to be used. Outlet groups to be staggered as indicated.
11.0.2 Contractor shall be responsible for protection of existing ceiling tiles and light fixtures. Tiles damaged and/or soiled during construction shall be replaced by the Contractor at his expense.
27.0.9 All outlets to be installed with ground wire down.
11.0.3 Protect fan coil units (with 4 mil. Polyethylene sheets) from construction dirt during demolition & construction.
27.0.10 All outlets to be installed vertically at 305mm A.F.F. except as noted.
12.0 CLEANUP
27.0.11 Where noted, refer to millwork drawings for exact location of electrical outlets.
12.0.1 Clean areas under contract to a condition at least to that previously existing and to the satisfaction of the Building Representative and Department Representative.
27.0.12 Unless dimensioned or noted otherwise, all outlets to be located in relation to ceiling grid lines as indicated.
12.0.2 Upon completion remove scaffolding, temporary protection and surplus materials. Make good defects satisfaction of the building Building Representative.
27.0.13 All outlets on this plan are dimensioned to centerline of outlet groupings.
12.0.3 Wash and polish glass, mirrors, ceramic tile, aluminum, chrome, stainless steel, baked or porcelain enamel, plastic surfaces, floors, hardware and washroom fixtures.
27.0.14 For all outlets mounted on or in close proximity to millwork, refer to applicable elevations and sections for exact location of outlets.
12.0.4 Clean manufactured articles in accordance with Manufacturer's direction.
27.0.15 All outlets to receive white cover plates and white bodies.
13.0 APPROVAL OF ALTERNATE MATERIALS
28.0 FINISHING MATERIALS-GENERAL NOTES
13.0.1 Cost of additional work and modifications to the design due to use of alternatives shall be borne by the Contractor.
28.0.1 Paint materials for each coating formulae to be products of a single Manufacturer.
14.0 PREPARATION OF SURFACES
28.0.2 Paint materials for each coating formulae to be products of the Manufacturer's as indicated on the drawing.
14.0.1 Fill all minor irregularities with spackling paste and sand to a smooth, level surface.
28.0.3 All paint materials must be delivered in original containers with the seals unbroken and label intact and with manufacturer's instructions printed thereon.
15.0 EXPLOSIVE ACTUATED FASTENING DEVICES
28.0.4 All painting materials to be of the best quality and shall be approved by the Department Representative. They shall bear identifying labels on the containers.
15.0.1 Reserved.
28.0.5 Paint shall not be badly settled, caked or thickened in the container, shall readily dispersed with paddle to a smooth consistency and have excellent application properties.
16.0 USE OF SITE AND FACILITIES
28.0.6 Paint to arrive on the job colour mixed except for tinting of undercoats.
16.0.1 Maintain existing services to building and provide for personal and vehicle access.
28.0.7 Any thinning or tinting shall be done as recommended by the manufacturer.
16.0.2 Contractor shall provide adequate protection of traffic areas used by trades.
28.0.8 Applicator to assume responsibility that all mixed colours match the colour selection provided by the Department Representative prior to application of the coating.
16.0.3 Contractor liable for damage, safety hazards and overloading of existing equipment.
28.0.9 Contractor responsible for verifying all materials used in construction against flaws and/or defects. Only new materials to be used.
16.0.4 Contractor to be cognizant of all building and site conditions, i.e.: freight elevator scheduling, waste disposal, etc. Use of freight elevator to be scheduled with the Building Representative with 24hrs notice.
28.0.10 Contractors to provide adequate protection of all flooring during painting/construction. 2015/11/12 Issued for Tender ML
17.0 DELIVERY AND STORAGE
28.0.11 Finishes to be ordered immediately upon receipt of contract. 2015/09/11 Issued for 99% Client Review ML
17.0.1 All materials to be delivered and stored in original packaging in a dry protected area and per Manufacturer's instructions. Delivery and storage details to be confirmed by Building Representative. Elevator to be
used between X:XX and X:XX 29.0 PAINTING-GENERAL NOTES 2015/08/10 Issued for 66% Client Review ML

29.0.1 Do not apply painting finishes in areas where dust is being generated.
Date Reason for Issue Issuer
17.0.2 Contractor to ensure elevators can accommodate large items to be delivered to site.

18.0 PAINTING WORKMANSHIP 29.0.2 For primed metal surfaces, use one coat spot priming, one coat enamel undercoat and two coat gloss enamel. Prepare existing exposed metal surfaces as required to receive new paint finish per
manufacturer's specifications.
18.0.1 All materials to be applied under adequate illumination, spread evenly and smoothly to avoid runs, sags, brush marks, air bubbles and excessive roller stipple.
29.0.3 All doors to be sanded lightly between finish coats.
18.0.2 Coverage and hide to be complete. When colour, stain, dirt or undercoats show through final coat of paint, the surfaces is to be covered by additional coats until the paint film is of uniform finish, colour,
appearance and coverage, at no additional cost to the Contract/Client. 29.0.4 For all gypsum board walls use one coat primer and two coats paint.

18.0.3 Enamel or varnish applied to wood or metal shall be sanded with fine sandpaper and then cleaned between coats to produce an even surface. 29.0.5 For all gypsum board ceilings use one coat primer and two coats flat paint as per Manufacturer's specifications.

18.0.4 Interior doors shall be sealed on the tops and bottoms with primer coat only. Side edges of interior doors shall be finished as faces of these doors. 29.0.6 When paint is dry, all components to be placed in original location.
18.0.5 All closet interiors shall be finished the same as adjoining rooms, unless otherwise specified.
29.0.7 For wood trims, doors and frames use one coat enamel undercoat and two coats semi-gloss enamel.
18.0.6 Surfaces to be stained shall appear uniform in shading with colour variations caused only by the natural wood grain.
29.0.8 For natural woodwork use one coat sealer, two coats stain and two finish coats matte polyethylene unless noted otherwise.
19.0 PREPARATION OF SURFACES
29.0.9 Paint both sides and edges of plywood back boards for equipment before installation. Leave equipment in original finish. Paint conduits, mounting accessories and unfinished items.
19.0.1 Gypsum wallboard:
Fill all minor irregularities with spackling paste and sand to a smooth level surface. Exercise care to avoid raising nap of paper. 29.0.10 Except where noted otherwise, paint finish for walls to be latex finish with 25% to 35% sheen.

20.0 CUTTING PATCHING AND REPAIRING 29.0.11 Unless otherwise noted, all existing surfaces where indicated and new painted partitions to be finished as follows:
Prime with one coat latex sealer, sand all surfaces, repair depressions etc. with drywall compound.
20.0.1 Elements such as existing GWB, bulkheads, columns etc. must be patched and repaired as required. Prepare surfaces to receive new finish. Spot prime all patched areas.
Sand, apply one finish coat paint as specified.
20.0.2 Patch and repair all surfaces damaged due to demolition. Prepare surfaces to suit new finish applications. After coat has dried re-sand and finish with one or more coats of specified paint as required for complete coverage.

20.0.3 Patch and repair all damaged ceiling t-bar, ceiling tile & convector units, as required, where partitions were removed. 29.0.12 Except where noted otherwise, all existing partitions, core walls and new partitions to be painted P1.

20.0.4 Patch & repair all damage to existing core walls, columns & convectors as required including where outlets are removed. 30.0 FLOOR FINISHES-GENERAL NOTES

20.0.5 Patch and repair all existing core walls & columns as required. Prepare to receive new finish. 30.0.1 When two flooring finishes meet at a doorway, joint to be covered when door is in closed position.

21.0 INSTALLATION NOTES-DOORS 30.0.2 Carpet and base to be cleaned thoroughly of all dust, dirt and adhesive to the satisfaction of the owner.

21.0.1 Reserved. 30.0.3 Contractor to protect all new and existing finished floor areas with 6 mil polyethylene. Polyethylene is to be removed at completion of work by Contractor. Tape joints with duct tape. Maintain floor protection and
patch hole for the duration of Construction.
22.0 HARDWARE-GENERAL NOTES
30.0.4 Carpet to be adhered to existing floor finish with re-usable LokDots backing.
22.0.1 Reserved.
30.0.5 Carpet accent and/or flooring patterns to be chalked for approval by Department Representative prior to commencing work.
23.0 GLAZING INSTALLATION NOTES
30.0.6 100mm rubber/vinyl base to be supplied on all partitions & columns of building where new vinyl tile to be installed.
23.0.1 Reserved.
30.0.7 The Contractor will be responsible for providing the Department Representative with written confirmation upon acceptance of carpet delivery, that all carpet has been inspected and is not damaged or defective.
The Contractor will be responsible for replacing all damaged materials should he fail to report damaged or defective goods prior to installation.

30.0.8 Prepare floor to accept new accent carpet floor finish where applicable.

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
1. Furniture to be supplied by Owner. Installation to be coordinated by Contractor. Full Height Graphic Display - at South Wing
Manufacturer: Europtimum
2. All TV monitors to be supplied by Owner and installed by Contractor unless otherwise Canvas Material: Eurostretch Fabric
noted. Refer to Elevations for more information. Frame Material: Aluminum
Frame Depth: 76mm
Sizes: 1029 x 2972mm (to be site verified)
3. Contractor to carry cash allowance of $103, 429.14 (HST included) for supply and Note: Refer to Elevation 2 on ID19 for exact panel locations. Installation to be
installation of Europtimum custom graphic displays. Refer to General Notes Section 33.0 coordinated with TV monitor installation heights.
on ID01 for more information.
Full Height Graphic Display - at Stairwell
Manufacturer: Europtimum
Canvas Material: Eurostretch Fabric
Frame Material: Aluminum
Frame Depth: 76mm
Individual Panel Sizes: 1755 x 878mm (site dimension required)
Quantity: 16
1755 x 730mm (site dimension required)
Quantity: 2
878 x 878mm (site dimension required) 211-2141 Thurston Drive T 613-739-3699
Quantity: 32 Ottawa ON K1G 6C9 F 613-739-3965
Overall Size: 1755 x 14,758mm (to be site verified)
Note: Refer to Elevation 1 on ID20 for exact panel locations. info@LWG-ai.com LWG-ai.com
Dn
Museum Display
Manufacturer: Europtimum
Shelf Display Material: Acrylic, back-painted with built-in LED lighting
Stair F Shelf Display Size: 445 x 445mm
Qty: 1
Shelf Display Size: 1295 x 445mm
Qty: 1
Up Note: Refer to Elevation 1 on ID19 for exact locations.

Up Dn
Key Plan
Up Up

Project
North

Stair D

Furniture Plan - First Floor


Scale: 1:100

2015/11/12 Issued for Tender ML


2015/09/11 Issued for 99% Client Review ML
2015/08/10 Issued for 66% Client Review ML
Date Reason for Issue Issuer

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Demolition Legend: Demolition Drawing Notes:
Existing partition to remain. All existing wall mounted equipment and signage at elevators including call
buttons, emergency recall key box, bilingual signage, floor indicators etc... to be
Interior u/s of suspended T-bar partition to be removed and discarded. removed and retained for reinstallation. All equipment associated with elevator call
system is to be removed by Owner's maintenance service contractor as required.
Existing door, door frame, hardware and components to remain. Contractor to coordinate.

Existing floor mounted benches to be removed and turned over to Owner. Patch
Existing double door, door frame, hardware and components to remain. and repair damaged floor and wall surfaces as required due to removal of
benches. All surfaces to be finished to like-new condition.

Existing glazing to remain. Patch, repair, and make good all existing floor and wall surfaces damaged due to
Ground Floor Ground Floor removal of existing millwork, partition, and electrical outlets as noted.
Existing terrazzo flooring and integrated cove base to remain. Refer to
Floor Finish Plan for more information. Existing reception desk millwork and associated equipment to be removed and
discarded. Refer to Elevations on ID17 for items to be reinstated. Patch, repair,
Existing tile flooring to remain. Refer to Floor Finish Plan for more and make good all terrazzo flooring damaged due to removal of millwork.
information.
Existing wall mount defibrillator and associated associated equipment to be
removed and retained for relocation. Refer to Electrical drawing for more 211-2141 Thurston Drive T 613-739-3699
R Existing duplex electrical outlet and related components to be relocated. information. Refer to Partition Plan ID05 for new location. Ottawa ON K1G 6C9 F 613-739-3965
Refer to Electrical drawings for more information.
Existing wall mounted clock to be removed and returned to Owner. Patch, repair, info@LWG-ai.com LWG-ai.com
Dn Existing LAN outlet and related components to be relocated. Refer to
R and make good existing partition as required. Refer to Electrical drawings for
Electrical drawings for more information. more information.

Existing duplex electrical outlet and related components to be removed Existing window coverings to be removed and discarded. Patch and repair
and discarded. Patch, repair, and make ready to receive new wall finish. existing ceilings and/or window mullions as required to like-new condition.
Refer to Electrical drawings.
Existing wall mount TV to be removed and turned over to Owner. Receptacles to
Existing voice/data outlet and related components to be removed and be relocated as required. Refer to ID07 for new installation heights and locations.
Up discarded. Cabling to be cut back to source. Patch, repair, and make Refer to Electrical drawings. Patch, repair, and make good existing partition to
ready to receive new wall finish. Refer to Electrical drawings. receive new wall finish as specified.

Existing data outlet and related components to be removed and


discarded. Cabling to be cut back to source. Patch, repair, and make required) to suit new partition depth. Refer to Partition Plan ID05 for more
ready to receive new wall finish. Refer to Electrical drawings. information. Existing power receptacle to be relocated to suit new lift panel
dimensions. Refer to ID07 for new installation heights and locations. Refer to
Existing blank cover plate to be removed and discarded. Refer to Electrical drawings for more information. Notify Department Representative
Electrical drawings. Opening to be patched, repaired, and made ready immediately if any discrepancies occur.
to receive new wall finish.
Existing wall mounted signage/ artwork to be carefully removed and returned to
R Existing thermostat to be removed and discarded. Refer to Mechanical
R Owner unless otherwise indicated. Patch, repair, and make good all damaged
drawings. Opening to be patched, repaired, and made ready to receive surfaces affected by removal of wall mounted equipment.
new wall finish.
Existing wall mount electrical and mechanical equipment in Ground Floor and First
Indicates area not in contract. Floor entrance vestibules including wall heaters, thermostats, switches, door
R operators, etc. to be removed and stored on site for re-installation as required.
Refer to Electrical and Mechanical drawings for more information.
Key Plan
Contractor to open existing partition where new display cases are scheduled for
installation. Refer to Elevation 1 on ID 19 for exact location and exact sizes of
display cases. Ensure opening is wide enough to accommodate new framing and
lintels as required. Patch, repair, and make good existing partition as required to
receive new paint finish. Project
North
Demolition General Notes:
1. It is the Contractor's responsibility to refer to all information in the General Notes located
on ID01.

2. It is the Contractor's responsibility to read this drawing in conjunction with all other

reported to the Department Representative for clarification during the Tender process and
prior to Construction.
Demolition Plan - First Floor 3. Contractor will be held responsible for any damage done to existing partitions, ceiling,
Scale: 1:100 finishes and all other components to remain and to adjacent spaces.

4. Refer to Mechanical and Electrical 's drawings for extent of demolition.


5. Unless otherwise noted, all existing partitions, door/ sidelight assembly, floor finish, etc.
to remain.

6.
the space.

7. Contractor to remove and turn over to Owner all items not being used for new 2015/11/12 Issued for Tender ML
construction, unless otherwise noted. 2015/09/11 Issued for 99% Client Review ML
2015/08/10 Issued for 66% Client Review ML
8. Any existing Base Building signage removed under demolition to be turned over to Date Reason for Issue Issuer
Owner unless otherwise noted.

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Existing 610mmx610mm recessed light fixture to be removed and Existing fluorescent lighting located within base building wayfinding signage to be
returned to Owner. Refer to Electrical drawings. removed and discarded. To be replaced with new LED lighting retrofitted into
existing frame, refer to Reflected Ceiling Plan ID06 and Electrical drawings for
Existing spot lights in stairwell to be removed and discarded. Typical all more information. Contractor to remove and reinstate existing plexiglass
floors. Refer to Electrical drawings. wayfinding panel.

All electrical components to be cut back to source and capped as required. Patch
Existing diffuser to be removed and discarded. Refer to Mechanical and repair stairwell and landing where spotlights are scheduled for removal. Make
drawings. ready to receive new paint finish as specified.

Patch and repair existing adjacent ceiling finish where bulkhead and/or gypsum
E Existing light switch to remain. ceiling has been removed. Make ready to receive new ceiling finish as indicated.
Refer to ID06 Reflected Ceiling Plan for more information.

Existing suspended T-bar ceiling and acoustical tiles to be removed and


discarded.

Existing suspended gypsum board ceiling to remain. 211-2141 Thurston Drive T 613-739-3699
1. It is the Contractor's responsibility to refer to all information in the General Notes located Ottawa ON K1G 6C9 F 613-739-3965
on ID01.
info@LWG-ai.com LWG-ai.com
Suspended gypsum board ceiling and related components to be 2. It is the Contractor's responsibility to read this drawing in conjunction with all other
removed and discarded.
to the Department Representative for clarification during the Tender process and prior to
Construction.
Existing glazing to remain
3. Contractor will be held responsible for any damage done to existing partitions, ceiling,
finishes and all other components to remain and to adjacent spaces.

4. Refer to Mechanical and Electrical drawings for extent of demolition.

5. Contractor to remove and turn over to Owner all items not being used for new
construction, unless otherwise noted.

Key Plan

Project
E
North

E
E

2015/11/12 Issued for Tender ML


2015/09/11 Issued for 99% Client Review ML

Reflected Ceiling Demolition Plan - First Floor 2015/08/10


Date
Issued for 66% Client Review
Reason for Issue
ML
Issuer
Scale: 1:100

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Partition Legend: Partition Drawing Notes:
Existing partition to remain. Relocated defibrillator to be installed at height to match previous location. Supply
and install surface mounted good one side plywood blocking to suit. To be
Furring Partition at Existing Terra Cotta Partitions installed with appropriate fasteners as required.
1 Partition to be 22mm 18 Gauge furring channel installed vertically at
1 05 22 410mm O.C. with 13mm gypsum board on all exposed faces from Contractor to use appropriate fasteners as required to adhere new furring strips
finished floor to u/s of finished ceiling (height varies). Finish partition and plywood blocking to existing terra cotta partitions. Gypsum board does not
ready to receive paint unless otherwise noted. require paint finish where Europtimum panels are scheduled for installation.
Align
Ensure no exposed or unfinished edges where panels are scheduled for
Align Furring Partition at Existing Pre-Cast Stone Aggregate Partitions installation.
2 2 2 Partition to be 22mm 18 Gauge furring channel installed vertically at
3 2
3 2 3 1 2 05 22 410mm O.C. with 13mm gypsum board on all exposed faces from Contractor to use appropriate fasteners as required to adhere new furring strips
05 05
2 finished floor to u/s of finished ceiling (height varies). Finish partition and plywood blocking to existing pre-cast stone aggregate partitions.
Typical ready to receive paint unless otherwise noted.
2 Ground Floor
Ground Floor New partition width is not to exceed width of existing window mullion. Notify
05 19
Furring Partition with Plywood Blocking Department Representative if discrepancies occur. Supply and install end caps
1 Partition to be 22mm 18 Gauge furring channel installed vertically at where partition and window mullions meet. End cap finish to match window
3 05 22 410mm O.C. with 22mm plywood blocking where Europtimum panels mullion (typical).
and/or TV monitors are scheduled for installation, sizes vary. Ensure
plywood is securely fastened to existing partition with blocking as New furring partition on stone aggregate walls to be installed from finished floor 211-2141 Thurston Drive T 613-739-3699
required. Plywood panels to be installed flush with furring channel to (Ground Floor) to underside of finished ceiling (First Floor) at approximately Ottawa ON K1G 6C9 F 613-739-3965
ensure level and even gypsum board application. Install 13mm gypsum 7087mm A.F.F. site verification required.
3 board on all exposed faces to u/s of finished ceiling (height varies).
Dn info@LWG-ai.com LWG-ai.com
Finish partition ready to receive paint unless otherwise noted. Existing wall mount electrical and mechanical equipment in Ground Floor and First
Floor entrance vestibules to be re-instated on new furring partitions. Ensure wall
Existing door, door frame, hardware and components to remain. heaters and receptacle covers are flush with new finished partition. Refer to
1
Electrical and Mechanical drawings for more information.
05 20
Stair F
Existing double door, door frame, hardware and components to remain. Supply and install wood framing and lintels as required at opening in terra cotta
brick partition to ensure structural stability of new display cases. Install wood
1 1&2 1
framing with appropriate fasteners. Coordinate clear opening dimensions for
05 18 05 16 05 19 Up Existing glazing to remain. display cases with Europtimum. Refer to Elevation 1 on ID19 and Detail 4 on ID22
3 for more information.
Room Number

Partition General Notes:


1. It is the Contractor's responsibility to refer to all information in the General Notes located
on ID01.

2. It is the Contractor's responsibility to read this drawing in conjunction with all other

reported to the Department Representative for clarification during the Tender process and
3 prior to Construction.
05 05

Typical Contractor will be held responsible for any damage done to existing partitions, ceiling,
finishes and all other components to remain and to adjacent spaces.

2
4. All dimensions are to the centerline of partitions, except to the face of core walls, unless Key Plan
Up Dn otherwise noted.
3 Up Up
2 5. Patch, sand, repair and make good to level 4 ready to receive new partition finish all
05 20 existing gypsum board and plaster surfaces where partitions, millwork, electrical Project
2 components and/or any other demolition occurred including any perforations, dents,
imperfections, etc... throughout the Contract Area prior to painting, unless otherwise noted. North
Contractor to ensure partition is smooth, straight and even. Remove and replace portion of
2 gypsum board as required to obtain a smooth surface.
2
Stair D 6. Ensure that all piping, ducting and any openings required for mechanical, electrical or
any other element that run-through new partitions or plenum barriers are properly sealed
with acoustic caulking. Refer to Mechanical and Electrical 's drawings for above ceiling
elements location.

7. Contractor to skim coat existing Base Building partitions in preparation to receive new
painted finish.
Partition Plan - First Floor
Scale: 1:100

Align 2015/11/12 Issued for Tender ML


(Typical) 2015/09/11 Issued for 99% Client Review ML
2015/08/10 Issued for 66% Client Review ML
Date Reason for Issue Issuer
13mm gypsum
board

Align Existing handrail


(Typical)

Line of existing
13mm gypsum landing
(Typical) (Typical)
board Europtimum Display Panel
22mm plywood blocking to (Typical)
be fastened to existing
partition. 22mm plywood blocking to be
fastened to existing partition
for TV monitor installation
(where applicable).

Plan Detail - Furring Partition with Plywood Blocking Plan Detail - First Floor Partitions at Door Frame
Scale: 1:10 Scale: 1:10

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Reflected Ceiling Legend: Reflected Ceiling Drawing Notes:
New recessed down light fixture. Refer to Electrical drawings. Existing fluorescent lighting located within base building wayfinding signage to be
Note: Custom sizes will be required for regressed fixtures in wood removed and discarded. To be replaced with new LED lighting retrofitted into
ceiling to ensure exact fit within opening (approximately 6 fixtures). existing frame. Refer to Electrical drawings for more information. Contractor to
remove and reinstate existing plexiglass wayfinding panel.
New pendant light fixtures. Refer to Electrical drawings.
Mounting Height: varies - refer to Elevation 1 on ID20 Refer to Wall Finish Plan ID08 for paint finish specifications. Paint finish to be
high-gloss on gypsum ceiling where indicated.

E Existing light switch to remain. Recessed linear diffuser. Refer to Electrical drawings. To be attached to recessed
T-bar grid as per Manufacturer's instructions.
New suspended T-bar ceiling grid and acoustical tiles.
Manufacturer: Armstrong Recessed continuous linear LED fixture to align with elevator frames (typical).
Refer to Electrical drawings. To be secured to recessed T-bar grid as per
Acoustical Tile Model #: Lyra (square tegular edge)
Manufacturer's instructions.
Acoustical Tile Size: 1219x1219mm
Acoustical Tile Finish: White Custom suspended ceiling wood veneer panels to align with custom wood veneer
T-bar Model #: Blizzard White wall panels on elevator facades. Site dimensions required prior to fabrication.
T-bar Finish: Blizzard White
211-2141 Thurston Drive T 613-739-3699
New suspended T-bar ceiling grid and wood acoustical tiles.
Ottawa ON K1G 6C9 F 613-739-3965
Manufacturer: Armstrong Reflected Ceiling
New Europtimum General
graphic display Notes:
panel to be installed within existing opening info@LWG-ai.com LWG-ai.com
Acoustical Tile Model #: Woodworks Vector
Acoustical Tile Size: varies 1. It is the Contractor's responsibility to refer to all information in the General Notes located
Acoustical Tile Finish: Walnut Wood Veneer with custom stain to match on ID01.
Tafisa L491(S)
Note: Provide sample on actual substrate material for Department 2. It is the Contractor's responsibility to read this drawing in conjunction with all other
Representative's review and approval prior to manufacturing.
to the Department Representative for clarification during the Tender process and prior to
Construction.
Existing suspended gypsum board ceiling to remain.
3. Contractor will be held responsible for any damage done to existing partitions, ceiling,
Typical finishes and all other components to remain and to adjacent spaces.
EQ EQ 5&6 EQ EQ
06 22 New suspended gypsum board ceiling. Ceiling to consist of 13mm 4. Symbols are for quantity and location only. Refer to Electrical drawings for additional
Align Align gypsum board on 65mm metal studs at 305mm O.C. New ceiling to be information.
taped, sanded and made ready to receive new finish.
5. All light fixtures to be centered within acoustical ceiling tiles, unless otherwise noted.
Indicates ceiling height
6. All light fixtures dimensions are O.C., unless noted otherwise.

Indicates room number 7. Contractor to ensure location of ceiling fixtures do not interfere with any structural or
mechanical components. Advise Department Representative of any conflicts prior to
ordering fixtures and commencing work. Contractor will be responsible for the cost to
relocating any new building construction should he fail to report conflicts prior to
installation.

8. Contractor to mark location of wall mounted, recessed down light and pendant light
fixtures for approval by Department Representative prior to installation. Acoustical ceiling
tiles and/or gypsum board cut without approval will be replaced or repaired by the Key Plan
Contractor at own expense.

Align Align 9. Contractor to remove and re-instate suspended T-bar ceiling grid as required for
mechanical demolition. Refer to Mechanical drawings. Contractor to avoid cutting main Project
E
10. Contractor to supply and install new suspended T-bar ceiling grid at heights specified
North
on drawings.
- Supply and install new acoustical ceiling tiles in new suspended T-bar ceiling grid.
- Finished ceiling system T-bar grid to be square with adjoining walls and level within
1:1000.
- Use edge moulding and shadow wall mouldings at vertical surfaces.
- Install system per manufacturer's instructions.

11. Patch, sand, repair and make good to level 4 (level 5 at all areas noted to receive high
gloss paint finish) all gypsum board ceiling and bulkhead, ready to receive new paint finish
as indicated.

12. All new and existing gypsum board ceiling and bulkhead to be painted P1, unless
otherwise noted.

13. Contractor to replace all damaged, soiled and broken acoustical ceiling tiles.
E
E 14. All proposed equivalent light fixtures to be approved by Department Representative
and Owner prior to Tender closing.

15. Contractor to supply and install access panel within gypsum board ceiling as required. 2015/11/12 Issued for Tender ML
Paint to match ceiling finish on all exposed surfaces. 2015/09/11 Issued for 99% Client Review ML

Reflected Ceiling Plan - First Floor 16. Contractor to provide reviewed and stamped shop drawings by Structural Engineer for
2015/08/10
Date
Issued for 66% Client Review
Reason for Issue
ML
Issuer
Scale: 1:100 suspended ceiling installation and seismic compliance. Suspended ceiling installation to
be seismically rated for local seismic zone as required.

17. All new suspended ceiling systems to be Class A fire rated unless otherwise noted.

Site dimension required


Site dimension
required

1219 1219 1219 1219 171

Detail Plan - Reflected Ceiling Dimensions


Scale: 1:50 c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Power/Voice/Data Legend: Power/Voice/Data Drawing Notes:
120V Duplex outlet mounted vertically at 305mm O.C. A.F.F., unless Refer to Elevations on ID17 for exact locations of new millwork receptacles.
otherwise noted.
Europtimum graphics display panels to be hardwired unless otherwise noted.
Building Standard wall mounted LAN outlet mounted at 305mm O.C. Supply and install slim profile transformers and junction boxes as required to be
A.F.F., unless otherwise noted. Contractor to provide conduit and pull installed within display framing, ensure no visible electrical or cabling components.
cord only in wall cavity from outlet box to ceiling. Wiring to be daisy-chained wherever possible. Exact locations and quantities to be
coordinated with Europtimum display installation type. Refer to Electrical drawings
Building Standard wall mounted combined voice/data outlet mounted at for more information.
H1H2H2RC H2 H1H1 305mm O.C. A.F.F., unless otherwise noted. Contractor to provide
conduit and pull cord only in wall cavity from outlet box to ceiling. Exact location of existing basefeed to be site verified by Department
Representative once existing reception millwork has been removed. New reception
New television cable outlet, to be mounted vertically at 1920mm O.C. millwork location to be adjusted as required to suit existing basefeed location.
C
A.F.F., unless otherwise noted. Contractor to provide conduit and pull
cord only in wall cavity from outlet box to ceiling. TV monitors to be supplied by Owner and installed by Contractor. Ensure no
exposed cabling or wiring components. Refer to Elevation 2 on ID20 for exact
D Indicates dedicated circuit. locations and mounting height of receptacles and monitors. Refer to Electrical
drawings for more information.
R Indicates relocated outlet
LED backlit display cases to be hardwired to suit installation unless otherwise 211-2141 Thurston Drive T 613-739-3699
RC Indicates recessed outlet. noted. Refer to Electrical Drawings for more information. Ottawa ON K1G 6C9 F 613-739-3965

H1 Indicates outlet mounted above at 1067mm O.C. A.F.F info@LWG-ai.com LWG-ai.com


Dn
H2 Indicates outlet mounted above at 1920 mm O.C A.F.F.
Power/Voice/Data General Notes:

Up

R,H2
R,H2

R
RC
RC
RC
RC
Key Plan
RC
RC
RC
RC
RC
Project
RC
RC
RC North

Power/Voice/Data Plan - First Floor


Scale: 1:100

2015/11/12 Issued for Tender ML


2015/08/10 Issued for 99% Client Review ML
2015/08/10 Issued for 66% Client Review ML
Date Reason for Issue Issuer

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Floor Finish Legend: Wall Finish Legend:
Existing terrazzo flooring to remain. Refer to Floor Finish Drawing Note #1 for Paint - General
details. Manufacturer: Sherwin Williams
Colour: SW7014 Eider White
Finish: Eggshell
Existing tile flooring to remain. Contractor to thoroughly clean. Note: Refer to Wall Finish Drawing Note #5 for areas to receive high gloss
paint finish.

Area Rug - made of various carpet tiles Paint - Doors and Frames
Refer to Detail Plans on ID08 for exact layout pattern. Manufacturer: Sherwin Willimans
P2 Colour: SW 7019 Gauntlet Grey
Finish: Semi-Gloss

C1 - Carpet Tile - General Vinyl Wallcovering


P2 Manufacturer: Shaw Supplier: Metro Wallcoverings
Pattern: Ignite Tile Manufacturer: Vescom
Colour: Oxidize Style: Utah
Installation: varies Colour: 776.01
Width: 54"
C2 Carpet Tile - Accent (Green) Installation: Vertical 211-2141 Thurston Drive T 613-739-3699
P2 Manufacturer: Shaw Notes: Ottawa ON K1G 6C9 F 613-739-3965
Pattern: Color Form - Install per Manufacturer's instructions.
Colour: Hyper Green - Ensure seams are overlapped and non-visible info@LWG-ai.com LWG-ai.com
Installation: varies - Install from finished floor to u/s of finished ceiling approx. 14, 783mm A.F.F.

C3 Carpet Tile - Accent (Yellow) Wood Veneer Panel


CG Manufacturer: Shaw Manufacturer: Armstong WoodWorks
Pattern: Color Form Species: Walnut TBC
Ground Floor Ground Floor Colour: Glowing Stain Colour: custom stain to match Tafisa L491(S) laminate
Installation: varies Notes:
- Sample to be provided on actual substrate material for Department
C4 Carpet Tile - Accent (Blue) Representative's review and approval.
Manufacturer: Shaw - Refer to Elevations 1 and 2 on ID20 for wall panel dimensions. All
Pattern: Color Form dimensions are to be site verified prior to manufacturing.
3
08 08
Colour: Hyper Blue Note: Wood veneer panels to be installed in accordance with Manufacturer's
Installation: varies instructions and in accordance with applicable flame and smoke spread
ratings.
CG C5 Carpet Tile - Accent (Magenta)
Manufacturer: Shaw Stainless Steel - Wall Panels
Pattern: Color Form Manufacturer: Armstrong
Dn
Colour: Puzzle Finish: to match elevators
Installation: varies Size: to suit application - site dimension required
Gauge: 22 (Heavy Duty)
Notes:
WV V1 - Refer to Elevations 1 and 2 on ID18 for exact locations of stainless steel wall
SS1 Floor Finish Drawing Notes: panels.

CG Supply and install new surface mounted stainless steel corner guard where
Up Contractor to grind, polish, and re-seal existing terrazzo flooring, staircase, and shown.
integrated cove base to a like-new condition. Typical throughout lobby unless Manufacturer: Koroguard (or equivalent)
CG otherwise noted. Key Plan
Quantity: 11
CG 2 Refer to 2/ID08 for carpet tile pattern. Supply and install LokDots backing to adhere
08 08
CG
carpet tile to terrazzo flooring. All exposed edges to receive vinyl transition strip. to be installed from finished floor to u/s of finished ceiling or
Refer to Floor Finish General Note #5 for specifications. directly above existing terrazzo base to u/s of finished ceiling where
applicable.
Project
CG
CG
Refer to 3/ID08 for carpet tile pattern. Supply and install LokDots backing to adhere
carpet tile to terrazzo flooring. All exposed edges to receive vinyl transition strip.
Notes:
- Ensure appropriate fastening method to secure to existing terra cotta
North
Refer to Floor Finish General Note #5 for specifications. partitions.
- Install per Manufacturer's instructions.
Indicates areas to receive new rubber base. See General Note #6 for specification. - Adhere to partition and install straight.
Refer to Detail 1 and 2 on ID22 for more information. - Ensure all edges are secured to partition. Ensure no protruding edges. If top
CG CG
edges cannot be adhered to partition, provide clear caulking and ensure
P2 P2 smooth edges.
CG CG
Floor Finish General Notes:
Wall Finish Drawing Notes:
1. It is the Contractor's responsibility to refer to all information in the General Notes located
on ID01.
Wall Finish Drawing Notes:
Indicates areas to be finished with high-gloss paint finish. Refer to Elevations on
2. It is the Contractor's responsibility to read this drawing in conjunction with all other ID18 and ID19 for more information.

to the Department Representative for clarification during the Tender process and prior to Contractor to paint spiral staircase continuous spine (3 storeys high) on all
Construction. exposed edges. Paint finish to be P1 throughout.

3. Contractor will be held responsible for any damage done to existing partitions, ceiling, All new and existing partitions within 2 storey atrium to be painted P1 unless
finishes and all other components to remain and to adjacent spaces. otherwise noted.

4. Contractor to provide samples of all finishes for Department Representative's approval Surface mount blocking to be painted to match adjacent partition finish.
prior to ordering any material.
2015/11/12 Issued for Tender ML
Supply and install sun control window film on glazing as noted. Window film to be
5. Carpet to terrazzo floor transition strip specification as follows: installed per Manufacturer's instructions. Refer to Millwork Legend for
2015/09/11 Issued for 99% Client Review ML
Manufacturer: Johnsonite specification details. 2015/08/10 Issued for 66% Client Review ML
Floor and Wall Finish Plan - First Floor Style: SSR-XX-B
Colour: 48 Grey WG
Date Reason for Issue Issuer

Scale: 1:100 Note: transition strip to be adhered to terrazzo flooring using Manufacturer's recommended
adhesive. Ensure adhesive does not damage existing terrazzo flooring.
Wall Finish General Notes:
6. New 102mm rubber base specification as follows:
Manufacturer: Johnsonite 1. It is the Contractor's responsibility to refer to all information in the General Notes located
Style: DC-XXX-4 on ID01.
Colour: 460 Cotton W
2. It is the Contractor's responsibility to read this drawing in conjunction with all other
3711
to the Department Representative for clarification during the Tender process and prior to
Construction.

3. Contractor will be held responsible for any damage done to existing partitions, ceiling,
finishes and all other components to remain and to adjacent spaces.

4. Contractor to provide samples of all finishes for Department Representative's approval


prior to ordering any materials.

5. Patch, sand, repair and make good to level 4 (Level 5 for all high gloss finish areas
3226

where indicated) ready to receive new partition finish all existing gypsum board and
plaster surfaces throughout the space prior to painting. Contractor to ensure finished
2286

partition is smooth, straight and even.

6. All wall finishes to be applied and installed per Manufacturer's instructions.

7. For all gypsum board partition, Contractor ensure to include in scope of work, one coat
primer and minimum two coats of paint. Some light colours may require additional coat (s)
to ensure uniform coverage. All dark colours to receive a minimum of three coats. Provide
smooth and uniform coverage and finish. This applies to all partitions, doors, frames, etc...
3712
8. Except where noted otherwise, all existing partitions, core walls, columns and new
partitions to be painted P1.

9. Remove door hardware and signage prior to painting of existing doors and frames.
Re-install once final paint coat has thoroughly dried.

10. Existing doors and frames as noted to be primed and painted P2 unless otherwise
noted. Ensure paint type is suitable for application and ensure no paint chipping. Existing
door hardware to be removed prior to painting. Doors to be painted offsite and reinstalled

Plan Detail - First Floor Area Carpet Plan Detail - First Floor Area Carpet
Scale: 1:50 Scale: 1:50 c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
1. Furniture to be supplied by Owner. Installation to be coordinated by Contractor.

2. All TV monitors to be supplied by Owner and installed by Contractor unless otherwise


noted. Refer to Elevations for more information.

3. Contractor to carry cash allowance of $103, 429.14 (HST included) for supply and
installation of Europtimum custom graphic displays. Refer to General Notes Section 33.0
on ID01 for more information.

211-2141 Thurston Drive T 613-739-3699


Ottawa ON K1G 6C9 F 613-739-3965

info@LWG-ai.com LWG-ai.com

Dn

Stair F

Up

Key Plan - Second Floor

Up Dn

Stair D

Key Plan - Third Floor


Furniture Plan - Second Floor
Scale: 1:100
Project
North

2015/11/12 Issued for Tender ML


2015/09/11 Issued for 99% Client Review ML
2015/08/10 Issued for 66% Client Review ML
Date Reason for Issue Issuer

Dn

Stair F

Furniture Plan - Third Floor


Scale: 1:100
c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Demolition Legend: Demolition Drawing Notes:
Existing partition to remain. All existing wall mounted equipment and signage at elevators including call
buttons, emergency recall key box, bilingual signage, floor indicators etc... to be
Existing door, door frame, hardware and components to remain. removed and retained for reinstallation. All equipment associated with elevator call
system is to be removed by Owner's maintenance service contractor as required.
Contractor to coordinate.
Existing double door, door frame, hardware and components to remain.
Existing wall mounted clock to be removed and returned to Owner. Refer to
Electrical drawings for more information. Patch, repair, and make good existing
Existing glazing to remain. partition as required.

Existing terrazzo flooring and integrated cove base to remain. Refer to Existing wall mounted equipment, signage, display cases, notification boards, etc
Floor Finish Plan for more information. (throughout lobby) to be removed and turned over to Owner. Patch, repair, and
make good existing partition to receive new wall finish as specified.
Existing duplex electrical outlet and related components to be removed
and discarded. Patch, repair, and make ready to receive new wall Existing wall mounted First Aid Kit to be removed and turned over to Owner.
finish. Refer to Electrical drawings. Owner to provide direction to Contractor for new installation location. Patch and
repair partition where equipment was removed and make ready to receive new
Existing thermostat to be removed and discarded. Refer to Mechanical finish as specified.
drawings. Opening to be patched, repaired, and made ready to receive 211-2141 Thurston Drive T 613-739-3699
new wall finish. Existing stainless steel corner guard to be removed and discarded. Patch and Ottawa ON K1G 6C9 F 613-739-3965
repair partitions and integrated cove base where corner guards have been
removed and make ready to receive new wall finish as specified. info@LWG-ai.com LWG-ai.com
T
Existing wall mounted lettering to be removed and retained for re-installation.
Dn Patch and repair partitions as required and make ready to receive new wall finish
as specified.

Existing built-in marble millwork and glass counter surface to be removed and
discarded. Patch and repair terrazzo flooring and base as required to like-new
Stair F condition. Patch and repair damaged partitions as required and make ready to
receive new wall finish as specified.

Up
Demolition General Notes:
1. It is the Contractor's responsibility to refer to all information in the General Notes located
on ID01.

2. It is the Contractor's responsibility to read this drawing in conjunction with all other

be reported to the Department Representative for clarification during the Tender process
and prior to Construction.
T
3. Contractor will be held responsible for any damage done to existing partitions, ceiling,
finishes and all other components to remain and to adjacent spaces.

4. Refer to Mechanical and Electrical drawings for extent of demolition.


5. Unless otherwise noted, all existing partitions, door/ sidelight assembly, floor finish, etc.
Key Plan - Second Floor
to remain.

6.
Up Dn the space.

7. Contractor to remove and turn over to Owner all items not being used for new
construction, unless otherwise noted.

8. Any existing Base Building signage removed under demolition to be turned over to
Owner unless otherwise noted.

Stair D
Key Plan - Third Floor
Demolition Plan - Second Floor
Scale: 1:100
Project
North

2015/11/12 Issued for Tender ML


2015/09/11 Issued for 99% Client Review ML
2015/08/10 Issued for 66% Client Review ML
Date Reason for Issue Issuer

Dn

Stair F

Demolition Plan - Third Floor


Scale: 1:100
c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Existing 610 x 1219mm base building fluorescent fixture to remain. Existing fluorescent lighting located within base building wayfinding signage to be
removed and discarded. To be replaced with new LED lighting retrofitted into
Existing 610 x 1219mm base building ceiling grid to remain.Existing existing frame, refer to Reflected Ceiling Plan ID13 and Electrical drawings for
610mmx610mm recessed light fixture to be removed and returned to more information. Contractor to remove and reinstate existing plexiglass
Owner. Refer to Electrical drawings. wayfinding panel.

Existing 610mm x 610mm recessed light fixture to be removed and All electrical components to be cut back to source and capped as required. Patch
returned to Owner. Refer to Electrical drawings. and repair stairwell and landing where spotlights are scheduled for removal. Make
ready to receive new paint finish.
Existing spot lights in stairwell to be removed and discarded. Typical all
floors. Refer to Electrical drawings. Contractor to remove existing plaster ceiling and associated components located
above existing suspended ceiling where indicated. Contractor to notify
Existing diffuser to be removed and discarded. Refer to Mechanical Department Representative immediately of any site conditions that may impact
drawings. new proposed ceiling installation.

E Existing recessed fixture to be removed and discarded. Refer to Existing plaster ceiling and recessed bulkhead to remain. Contractor to patch and
Electrical drawings. repair existing ceiling as required and make ready to receive new finish as
indicated on ID13.
E Existing light switch to remain. 211-2141 Thurston Drive T 613-739-3699
Existing suspended ceiling in lobby area to be removed by Owner prior to Ottawa ON K1G 6C9 F 613-739-3965
construction. Contractor is responsible for extent of all repair work required.
Existing 610mm x 610mm suspended T-bar ceiling and acoustical tiles Owner to coordinate Site Inspection during Tender phase. info@LWG-ai.com LWG-ai.com
to be removed and discarded.
EE Patch and repair existing gypsum ceiling where recessed potlights were removed
and make ready to receive new ceiling finish as indicated on ID13.
Existing suspended gypsum board ceiling to remain.
Patch and repair existing adjacent ceiling finish and partitions where bulkhead
and/or gypsum ceiling has been removed (where applicable). Make ready to
receive new ceiling finish as indicated. Refer to ID06 Reflected Ceiling Plan for
Suspended gypsum board ceiling and related components to be more information.
removed and discarded.

Indicates existing base building lighting, suspended ceiling system and


related components to be removed by Owner prior to Construction.
Refer to Reflected Ceiling Demolition Drawing Notes, Note #5 for more
information. 1. It is the Contractor's responsibility to refer to all information in the General Notes located
on ID01.

2. It is the Contractor's responsibility to read this drawing in conjunction with all other

be reported to the Department Representative for clarification during the Tender process
and prior to Construction.

3. Contractor will be held responsible for any damage done to existing partitions, ceiling,
finishes and all other components to remain and to adjacent spaces.

4. Refer to Mechanical and Electrical drawings for extent of demolition.

5. Contractor to remove and turn over to Owner all items not being used for new
Key Plan - Second Floor
construction, unless otherwise noted.

Reflected Ceiling Demolition Plan - Second Floor Key Plan - Third Floor
Scale: 1:100

Project
North

2015/11/12 Issued for Tender ML


2015/09/11 Issued for 99% Client Review ML
2015/07/30 Issued for 66% Client Review ML
Date Reason for Issue Issuer

Reflected Ceiling Demolition Plan - Third Floor


Scale: 1:100
c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Partition Legend: Partition Drawing Notes:
Existing partition to remain. Contractor to use appropriate fasteners as required to adhere new furring strips
and plywood blocking to existing terra cotta partitions.
Furring Partition at Existing Terra Cotta Partitions
1 Partition to be 22mm 18 Gauge furring channel installed vertically at
1 12 22 410mm O.C. with 13mm gypsum board on all exposed faces to u/s of
finished ceiling (height varies). Install 22mm plywood blocking from
floor to u/s of finished ceiling where Europtimum panels are scheduled
Partition General Notes:
for installation, sizes vary, ensure plywood and gypsum board are
flush. Finish partition ready to receive paint unless otherwise noted. 1. It is the Contractor's responsibility to refer to all information in the General Notes located
on ID01.
Furring Partition with Plywood Blocking
1 Partition to be 22mm 18 Gauge furring channel installed vertically at 2. It is the Contractor's responsibility to read this drawing in conjunction with all other
3 12 22
410mm O.C. with 22mm plywood blocking where Europtimum panels
and/or TV monitors are scheduled for installation, sizes vary. Ensure to the Department Representative for clarification during the Tender process and prior to
plywood is securely fastened to existing partition with blocking as Construction.
required. Plywood panels to be installed flush with furring channel to
ensure level and even gypsum board application. Install 13mm gypsum 3. Contractor will be held responsible for any damage done to existing partitions, ceiling,
board on all exposed faces to u/s of finished ceiling (height varies). finishes and all other components to remain and to adjacent spaces.
Finish partition ready to receive paint unless otherwise noted.
211-2141 Thurston Drive T 613-739-3699
4. All dimensions are to the centerline of partitions, except to the face of core walls, unless Ottawa ON K1G 6C9 F 613-739-3965
Existing door, door frame, hardware and components to remain. otherwise noted.
info@LWG-ai.com LWG-ai.com
5. Patch, sand, repair and make good to level 4 (Level 5 for all high gloss paint finish
3 Existing double door, door frame, hardware and components to remain. areas where indicated) ready to receive new partition finish all existing gypsum board and
Dn plaster surfaces where partitions, millwork, electrical components and/or any other
demolition occurred including any perforations, dents, imperfections, etc... throughout the
Existing glazing to remain. Contract Area prior to painting, unless otherwise noted. Contractor to ensure partition is
smooth, straight and even. Remove and replace portion of gypsum board as required to
Room Number obtain a smooth surface.
2 Stair F
12 18
6. Ensure that all piping, ducting and any openings required for mechanical, electrical or
any other element that run-through new partitions or plenum barriers are properly sealed
with acoustic caulking. Refer to Mechanical and Electrical drawings for above ceiling
Up elements location.
3

7. Contractor to skim coat existing Base Building partitions in preparation to receive new
painted finish.

3
Key Plan - Second Floor
12 20

1 3 1
Up Dn

Align Align

Stair D
Key Plan - Third Floor
Partition Plan -Second Floor
Scale: 1:100
Project
North

2015/11/12 Issued for Tender ML


2015/09/11 Issued for 99% Client Review ML
2015/08/10 Issued for 66% Client Review ML
Date Reason for Issue Issuer

Dn

2
12 18

Stair F
3

Partition Plan - Third Floor


Scale: 1:100 c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Reflected Ceiling Legend: Reflected Ceiling Drawing Notes:
Existing 610 x 1219mm base building fluorescent fixture to remain. Existing fluorescent lighting located within base building wayfinding signage to be
removed and discarded. To be replaced with new LED lighting retrofitted into
existing frame. Refer to Electrical drawings for more information. Contractor to
New recessed LED down light. Refer to Electrical drawings. remove and reinstate existing plexiglass wayfinding panel.

New recessed down light fixture. Refer to Electrical drawings. Armstrong Radial wood panel ceiling to be installed within existing recessed
Notes: bulkhead. Site dimensions required prior to fabrication. Refer to radial suspended
Custom sizes will be required for regressed fixtures in wood ceiling to ceiling isometric view detail 8 on ID22 for more information and installation details.
ensure exact fit within opening (approximately 6 fixtures).
Fixture canopy to be installed centered within existing recessed ceiling. Site
New pendant light fixtures. Refer to Electrical drawings. dimension required. Contractor to install cross bracing between joists above
Mounting Height: varies - refer to Elevation 1 on ID20 finished ceiling as required to provide support for new light fixture installation. New
bracing to be secured to ceiling structure with appropriate fasteners. Contractor to
provide stamped structural review by a certified Ontario structural engineer.

E E Existing light switch to remain. New gypsum ceiling in third floor stairwell to align with existing plaster ceiling.
Ensure seamless transition between new and existing ceiling finish. See Reflected
Existing 610 x 1219mm base building ceiling grid to remain. Ceiling General Notes, Note #12 for new ceiling paint finish.
211-2141 Thurston Drive T 613-739-3699
Recessed linear diffuser. Refer to Mechanical drawings. To be attached to Ottawa ON K1G 6C9 F 613-739-3965
recessed T-bar grid as per Manufacturer's instructions.
New suspended T-bar ceiling grid and acoustical tiles. info@LWG-ai.com LWG-ai.com

773
Manufacturer: Armstrong Recessed linear LED fixtures to align with elevator frames (typical). Refer to
EE Acoustical Tile Model #: Lyra (square tegular edge) Electrical drawings. To be secured to recessed T-bar grid as per Manufacturer's
instructions.

Site dimension required


773 Acoustical Tile Size: 1219x1219mm
Acoustical Tile Finish: White Contractor to ensure linear fixture is installed flush with existing gypsum and/or
T-bar Model #: Blizzard White plaster ceiling finish. Patch and repair any damaged surfaces affected by
T-bar Finish: Blizzard White installation and make ready to receive new ceiling finish as noted

New suspended T-bar ceiling grid and wood acoustical tiles. Custom suspended ceiling wood veneer panels to align with custom wood veneer
773 Manufacturer: Armstrong wall panels on elevator facades. Site dimensions required prior to fabrication.
Refer to Elevation 2 on ID18 for more information.
Acoustical Tile Model #: Woodworks Vector
Align

773
Acoustical Tile Size: varies Refer to Wall Finish Plan ID08 for paint finish specifications. Paint finish to be
Acoustical Tile Finish: Walnut Wood Veneer with custom stain to match high-gloss on gypsum ceiling where indicated.
Tafisa L491(S)
Align EQ1 EQ1 EQ1 EQ1 EQ1 Align Note: Provide sample on actual substrate material for Department
Representative's review and approval prior to manufacturing.
Site dimension required
New suspended radial ceiling grid and wood acoustical tiles.
Reflected Ceiling General Notes:
Manufacturer: Armstrong
1. It is the Contractor's responsibility to refer to all information in the General Notes located
Acoustical Tile Model #: Radial Woodworks on ID01.
Acoustical Tile Size: varies
Acoustical Tile Finish: Walnut Wood Veneer with custom stain to match 2. It is the Contractor's responsibility to read this drawing in conjunction with all other
Tafisa L491(S)
Note: Provide sample on actual substrate material for Department be reported to the Department Representative for clarification during the Tender process
Representative's review and approval prior to manufacturing. and prior to Construction. Key Plan - Second Floor
3. Contractor will be held responsible for any damage done to existing partitions, ceiling,
Existing suspended gypsum board ceiling to remain.
finishes and all other components to remain and to adjacent spaces.

4. Symbols are for quantity and location only. Refer to Electrical drawings for additional
information.
1686

1686

New suspended gypsum board ceiling. Ceiling to consist of 13mm


gypsum board on 65mm metal studs at 305mm O.C. New ceiling to be 5. All light fixtures to be centered within acoustical ceiling tiles, unless otherwise noted.
taped, sanded and made ready to receive new finish.
6. All light fixtures dimensions are O.C., unless noted otherwise.
EQ2 EQ2 EQ3 EQ3
Indicates ceiling height
7. Contractor to ensure location of ceiling fixtures do not interfere with any structural or
mechanical components. Advise Department Representative of any conflicts prior to
ordering fixtures and commencing work. Contractor will be responsible for the cost of
relocating any new building construction should he fail to report conflicts prior to
installation. Key Plan - Third Floor
Reflected Ceiling Plan - Second Floor 8. Contractor to mark location of wall mounted, recessed down light and pendant light
Scale: 1:100 fixtures for approval by Department Representative prior to installation. Acoustical ceiling
tiles and/or gypsum board cut without approval will be replaced or repaired by the
Contractor at own expense.
Project
9. Contractor to remove and re-instate suspended T-bar ceiling grid as required for
mechanical demolition. Refer to Mechanical drawings. Contractor to avoid cutting main North
10. Contractor to supply and install new suspended T-bar ceiling grid at heights specified
on drawings.
- Supply and install new acoustical ceiling tiles in new suspended T-bar ceiling grid.
- Finished ceiling system T-bar grid to be square with adjoining walls and level within
1:1000. 2015/11/12 Issued for Tender ML
- Use edge moulding and shadow wall mouldings at vertical surfaces. 2015/09/11 Issued for 99% Client Review ML
- Install system per manufacturer's instructions.
2015/08/10 Issued for 66% Client Review ML
Date Reason for Issue Issuer
11. Patch, sand, repair and make good to level 4 (Level 5 for all high gloss finish areas
where indicated) all gypsum board ceiling and bulkhead, ready to receive new paint finish
as indicated.

12. All new and existing gypsum board ceiling and bulkhead to be painted P1, unless
otherwise noted.

13. Contractor to replace all damaged, soiled and broken acoustical ceiling tiles. Style and
column to match existing.

14. All proposed equivalent light fixtures to be approved by Department Representative


and Owner prior to Tender closing.
738

738 15. All new and existing access panels to be painted to match ceiling finish on all exposed
surfaces.
Site dimension required

16. All new suspended ceiling systems to be Class A fire rated unless otherwise noted.

738
738

Align EQ4 EQ4 EQ4 EQ4 EQ4 Align

Reflected Ceiling Plan - Third Floor


Scale: 1:100
c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Power/Voice/Data Legend: Power/Voice/Data Drawing Notes:
120V Duplex outlet mounted vertically at 305mm O.C. A.F.F., unless Refer to Elevation 3 on ID20 for exact locations of receptacles for monitors and
otherwise noted. touchdown station.

Building Standard wall mounted LAN outlet mounted at 305mm O.C. Indicates location of new TV monitor. Monitor to be supplied by Owner and
A.F.F., unless otherwise noted. Contractor to provide conduit and pull installed by Contractor.
cord only in wall cavity from outlet box to ceiling.

Building Standard wall mounted combined voice/data outlet mounted at


305mm O.C. A.F.F., unless otherwise noted. Contractor to provide
conduit and pull cord only in wall cavity from outlet box to ceiling.
Power/Voice/Data General Notes:
New television cable outlet, to be mounted vertically at 1920mm O.C.
C
A.F.F., unless otherwise noted. Contractor to provide conduit and pull
cord only in wall cavity from outlet box to ceiling.

D Indicates dedicated circuit.

RC Indicates recessed outlet.


211-2141 Thurston Drive T 613-739-3699
H1 Indicates outlet mounted above at 1067mm O.C. A.F.F. Ottawa ON K1G 6C9 F 613-739-3965

H2 Indicates outlet mounted above at 1920mm O.C. A.F.F info@LWG-ai.com LWG-ai.com

Dn

Stair F

Up

Key Plan - Second Floor

RC RC RC
Up Dn
H1 H2 H2 H2 H1H1

Stair D
Key Plan - Third Floor
Power/Voice/Data Plan - Second Floor
Scale: 1:100
Project
North

2015/11/12 Issued for Tender ML


2015/09/11 Issued for 99% Client Review ML
2015/08/10 Issued for 66% Client Review ML
Date Reason for Issue Issuer

Dn

Stair F

RCRCRC
H2 H2 H2

Power Voice Data Plan - Third Floor


Scale: 1:100 c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Floor Finish Legend: Wall Finish Legend:
Existing flooring to remain. Paint - General
Manufacturer: Sherwin Williams
Colour: SW7014 Eider White
Area Rug - made of various carpet tiles Finish: Eggshell
Refer to X/IDXX for exact layout pattern. Note: Refer to Wall Finish Drawing Note #3 for areas to receive high gloss
paint finish.

Paint - Doors and Frames


C1 - Carpet Tile - General Manufacturer: Sherwin Willimans
Manufacturer: Shaw Colour: SW 7019 Gauntlet Grey
Pattern: Ignite Tile Finish: Semi-Gloss
Colour: Oxidize
Installation: varies Vinyl Wallcovering
Supplier: Metro Wallcoverings
C2 Carpet Tile - Accent (Green) Manufacturer: Vescom
Manufacturer: Shaw Style: Utah
Pattern: Color Form Colour: 776.01
Colour: Hyper Green Width: 54" 211-2141 Thurston Drive T 613-739-3699
Installation: varies Installation: Vertical Ottawa ON K1G 6C9 F 613-739-3965
Notes:
C3 Carpet Tile - Accent (Yellow) - Install per Manufacturer's instructions.
Manufacturer: Shaw - Ensure seams are overlapped and non-visible
info@LWG-ai.com LWG-ai.com
CG CG
Pattern: Color Form
CG CG
Colour: Glowing Wood Veneer Panel
Installation: varies Manufacturer: Armstong WoodWorks
Species: Walnut TBC
C4 Carpet Tile - Accent (Blue) Stain Colour: custom stain to match Tafisa L491(S) laminate
Manufacturer: Shaw Notes:
WV Pattern: Color Form - Sample to be provided on actual substrate material for Department
V1 Colour: Hyper Blue Representative's review and approval.
SS1
Installation: varies - Refer to Elevations 1 and 2 on ID18 for wall panel dimensions. All
dimensions are to be site verified prior to manufacturing.
C5 Carpet Tile - Accent (Magenta) - Wood veneer panels to be installed in accordance with Manufacturer's
Manufacturer: Shaw instructions.
Pattern: Color Form
Colour: Puzzle Stainless Steel - Wall Panels
Installation: varies Manufacturer: Armstrong
CG CG Finish: to match elevators
Size: to suit application - site dimension required
3
15 15
Gauge: 22 (Heavy Duty)
EQ EQ
CG CG
Floor Finish Drawing Notes: Notes:
- Refer to Elevations 1 and 2 on ID18 for exact locations of stainless steel wall
panels.
Contractor to grind, polish, and seal existing terrazzo flooring and integrated cove
base to a like-new condition. Typical throughout lobby. CG Supply and install new surface mounted stainless steel corner guard where
shown.
Refer to 3/ID15 for carpet tile pattern. Supply and install LokDots backing to Manufacturer: Koroguard (or equivalent)
adhere carpet tile to terrazzo flooring. All exposed edges to receive vinyl transition
strip. Refer to Floor Finish General Note #5 for specifications. Quantity: 14 Key Plan - Second Floor
to be installed from finished floor to u/s of finished ceiling or
directly above existing terrazzo base to u/s of finished ceiling where
Floor Finish General Notes: applicable.
1470

Notes:
- Ensure appropriate fastening method to secure to existing terra cotta
1. It is the Contractor's responsibility to refer to all information in the General Notes partitions.
located on ID01. - Install per Manufacturer's instructions.
- Adhere to partition and install straight.
2. It is the Contractor's responsibility to read this drawing in conjunction with all other - Ensure all edges are secured to partition. Ensure no protruding edges. If top
edges cannot be adhered to partition, provide clear caulking and ensure
be reported to the Department Representative for clarification during the Tender process smooth edges.
and prior to Construction.

3. Contractor will be held responsible for any damage done to existing partitions, ceiling,
finishes and all other components to remain and to adjacent spaces.
Wall Finish Drawing Notes: Key Plan - Third Floor
Floor and Wall Finish Plan - Second Floor 4. Contractor to provide samples of all finishes for Department Representative's approval
prior to ordering any material. To be finished with high-gloss paint finish. Refer to Elevations on ID17 for more
Scale: 1:100 information.
5. Carpet to terrazzo floor transition strip specification as follows:
Manufacturer: Johnsonite
Project
Contractor to paint spiral staircase continuous spine (3 storeys high) on all
Style: SSR-XX-B
Colour: 48 Grey WG
exposed edges. Paint finish to be P1 throughout. North
6. New 102mm rubber base specification as follows:
Manufacturer: Johnsonite
Style: DC-XXX-4 Wall Finish General Notes:
Colour: 460 Cotton W
1. It is the Contractor's responsibility to refer to all information in the General Notes located
2015/11/12 Issued for Tender ML
on ID01.
2015/08/10 Issued for 99% Client Review ML

2. It is the Contractor's responsibility to read this drawing in conjunction with all other 2015/08/10 Issued for 66% Client Review ML
Date Reason for Issue Issuer
be reported to the Department Representative for clarification during the Tender process
and prior to Construction.

3. Contractor will be held responsible for any damage done to existing partitions, ceiling,
finishes and all other components to remain and to adjacent spaces.

4. Contractor to provide samples of all finishes for Department Representative's approval


prior to ordering any materials.
EQ 5536 EQ
5. Patch, sand, repair and make good to level 4 (level 5 for high gloss paint finish areas
where indicated) ready to receive new partition finish all existing gypsum board and plaster
surfaces throughout the space prior to painting. Contractor to ensure finished partition is
smooth, straight and even.
CG CG
6. All wall finishes to be applied and installed per Manufacturer's instructions.
CG CG
7. For all gypsum board partition, Contractor ensure to include in scope of work, one coat
primer and minimum two coats of paint. Some light colours may require additional coat (s)
Dn
to ensure uniform coverage. All dark colours to receive a minimum of three coats. Provide
smooth and uniform coverage and finish. This applies to all partitions, doors, frames, etc...
WV
V1 8. Except where noted otherwise, all existing partitions, core walls, columns and new
SS1 partitions to be painted P1.

9. Remove door hardware and signage prior to painting of existing doors and frames.
Stair F
Re-install once final paint coat has thoroughly dried.

10. Doors as indicated to be primed and painted P2 and all door/sidelight frames to be
primed and painted P2, unless otherwise noted. Ensure paint type is suitable for
CG application and ensure no paint chipping.
CG
11. Contractor to provide wood veneer samples for Department Representative's approval
prior to fabrication.

Floor and Wall Finish Plan - Third Floor Plan Detail - Area Rug - Second Floor
Scale: 1:100 Scale: 1:50
c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Millwork Legend:
2 Wood Veneer - Wall and Ceiling Panels
16 17
Manufacturer: Armstrong
Species Walnut
Stain: custom stain to match Tafisa L491(S) laminate

Wood Veneer - Reception Desk

126
Species: Walnut
3 Stain: custom stain to match Tafisa L488(S) laminate
16 17

Stainless Steel - Wall Panels


Manufacturer: Armstrong

R18
Finish: to match elevators

1
Gauge: 22 (Heavy Duty)

3
4
16 17
Stainless Steel - Base
Finish: to match elevators
Size: As noted
Gauge: 22 (Heavy Duty)
211-2141 Thurston Drive T 613-739-3699

3
R105
Solid Surface Countertop Ottawa ON K1G 6C9 F 613-739-3965
Manufacturer: Corian
5
54 Colour: Arctic Ice info@LWG-ai.com LWG-ai.com
R1 Thickness: 12mm

Resin Panel
2
R185 Manufacturer: 3Form
Collection: Screen Print
Colour: Code Silver
1 Colour #: 0-91-120
2 16 17
16 17 Finish: Patina (both sides)
Panel Thickness: 12mm
Suspension Series: 200.08
- Suspended Side-Fastening Partition

clea
799 307

915 ening
r op
Window Film
Manufacturer: 3M
Series: Sun Control Window Film Prestige Series
Style No: PR 60

Millwork Drawing Notes:


Exact location of existing basefeed to be determined on site
3
16 17
prior to installation of new reception millwork. New location of
reception desk millwork to conceal existing basefeed. Notify
Department Representative if discrepencies occur.
Key Plan
4 site with Department Representative. Grommets to receive
16 17 white plastic covers unless otherwise noted.

12mm resin panels to be mounted to solid surface countertop


Project
as per manufacturers installation instructions. Radius of curved
panels is to be coordinated with millwork manufacturer to
North
ensure radius of panels is equal to radius of curved countertop.

16
1
17
Millwork Notes:
1. Countertops to be 19mm plywood, finished with 12mm solid surface
material unless otherwise noted.
Detail Plan - Reception Desk
2. Cabinets to be 19mm high density particle board, finished with
Scale: 1:20 plastic laminate, unless otherwise noted.

3. Shelves to be 12mm high density particle board.

4. Interior surfaces of cabinets, drawers and adjustable shelves to be


2
16 21
finished with standard white melamine.

5. Cabinet hinges to be concealed and self-closing.


3
16 21 6. Drawers to be installed on full extension heavy duty glides with
built-in stops.
1
16 21
Line of 2015/11/12 Issued for Tender ML
adjustable 7.
2015/09/11 Issued for 99% Client Review ML
shelf pins in holes blind drilled 50mm O.C., unless otherwise noted.
2015/08/10 Issued for 66% Client Review ML
407 Date Reason for Issue
Blocking to suit 8. Additional blocking to be provided in partition cavity as required to Issuer

(typical) support millwork.

48 9. Corian counters to be supplied and installed by a qualified fabricator.


3 All seams to be buffed out in accordance with Manufacturer's
EQ instructions.

10. Refer to Mechanical s Drawings for connection of equipment.

11. Veneer stained to match sample provided by Department


EQ

Line of Representative. Contractor shall supply 305mm square sample of


adjustable material and finish for Department Representative's approval before
shelf application. Veneer to be shop-stained and finished with three coats of
4
catalyzed polyurethane (satin). Sand between coats. Finish all sides
16 21
and edges.
Line of counter 12. It is the Contractor's responsibility to read this drawing in
top above conjunction with all other drawings including other 's drawings. Any
discrepancies between drawings will be reported to the Department
Representative for clarification during the Tender process and prior to
Cable and wire construction.
management tray
13. Specification for all wood veneers to be as follows: Veneer to be
75
Walnut "AAA" Architectural Grade Sequence Match. All flitch to be
equal, all veneer to be from same flitch. Contractor to supply 305mm
square sample for Department Representative's approval before
matching and fabrication.
40 Line of counter
7 top above 14. Drawer slide for printer specification as follows:
Manufacturer: Richelieu
Product No: 9996W12B
5 Size: 500mm
16 21 Quantity: 2
* or equivalent alternate *

15. Typical millwork drawer pull hardware specification as follows:


Cable and wire Manufacturer: Richelieu
2 management tray Product No: BP64664195
16 21 6 Size: 79mm
16 21
Finish: Matte Chrome
Quantity: 7

Detail Plan - Reception Desk (Below Counter Layout) 16. Typical millwork door pull hardware specification as follows:
Manufacturer: Richelieu
Scale: 1:20 c Product No: BP31925195

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Millwork Legend:
Wood Veneer - Wall and Ceiling Panels
Manufacturer: Armstrong
Species Walnut
Stain: custom stain to match Tafisa L491(S) laminate

Wood Veneer - Reception Desk


Species: Walnut
Stain: custom stain to match Tafisa L488(S) laminate

Stainless Steel - Wall Panels


Manufacturer: Armstrong
Finish: to match elevators
Gauge: 22 (Heavy Duty)

2006

2006
Stainless Steel - Base
Finish: to match elevators
Size: As noted
Gauge: 22 (Heavy Duty)
211-2141 Thurston Drive T 613-739-3699
Solid Surface Countertop Ottawa ON K1G 6C9 F 613-739-3965
Manufacturer: Corian
Colour: Arctic Ice info@LWG-ai.com LWG-ai.com
Thickness: 12mm

Resin Panel
Manufacturer: 3Form
Collection: Screen Print
Colour: Code Silver

357

380
Colour #: 0-91-120

50
Finish: Patina (both sides)
Panel Thickness: 12mm
Suspension Series: 200.08

50

1067

1067
Cable tray - Suspended Side-Fastening Partition

558
760
Window Film
Manufacturer: 3M
Open Series: Sun Control Window Film Prestige Series
Style No: PR 60

152
Elevation - Reception Desk Front View Elevation - Reception Desk Back View
Scale: 1:20 Scale: 1:20
Millwork Drawing Notes:
Key Plan
Representative. Grommets to receive white plastic covers unless otherwise noted.

12mm resin panels to be mounted to solid surface countertop as per manufacturers installation Project
instructions. Radius of curved panels is to be coordinated with millwork manufacturer to ensure
radius of panels matches radius of curved countertop. North
Indicates existing under-counter mount keyboard tray to be reinstated.

Indicates new dual monitor arm to be installed. Monitor arm to be supplied by Owner and installed
by Contractor.

Indicates cable tray c/w cable hooks to support required BX cabling and wiring as required. All
exposed edges to be finished with WV2 unless otherwise noted.

Stainless steel lettering on metal standoffs. Exact font style and size to be provided by Owner.
Contractor to coordinate. Contractor to provide separate pricing during Tender period for Owner's
review and approval.

Millwork Notes:
1. Countertops to be 19mm plywood, finished with 12mm solid surface material unless otherwise noted.

2. Cabinets to be 19mm high density particle board, finished with plastic laminate, unless otherwise
noted.

3. Shelves to be 12mm high density particle board. 2015/11/12 Issued for Tender ML
2015/09/11 Issued for 99% Client Review ML
4. Interior surfaces of cabinets, drawers and adjustable shelves to be finished with standard white 2015/08/10 Issued for 66% Client Review ML
melamine.
Monitor Monitor Date Reason for Issue Issuer
357

357
NIC NIC Phone 5. Cabinet hinges to be concealed and self-closing.
NIC
6. Drawers to be installed on full extension heavy duty glides with built-in stops.
Printer
NIC
1067

1067

1067
7.
O.C., unless otherwise noted.
710

710
Open 8. Additional blocking to be provided in partition cavity as required to support millwork.
487

9. Corian counters to be supplied and installed by a qualified fabricator. All seams to be buffed out in
152

152
accordance with Manufacturer's instructions.

10. Refer to Mechanical Consultants Drawings for connection of equipment.

11. Veneer stained to match sample provided by Department Representative. Contractor shall supply
305mm square sample of material and finish for Department Representative's approval before

Elevation - Reception Desk Interior View 1 Elevation - Reception Desk Interior View 2 application. Veneer to be shop-stained and finished with three coats of catalyzed polyurethane (satin).
Sand between coats. Finish all sides and edges.
Scale: 1:20 Scale: 1:20
12. It is the Contractor's responsibility to read this drawing in conjunction with all other drawings including
other drawings. Any discrepancies between drawings will be reported to the Department Representative
for clarification during the Tender process and prior to construction.

13. Specification for all wood veneers to be as follows: Veneer to be Walnut "AAA" Architectural Grade
Sequence Match. All flitch to be equal, all veneer to be from same flitch. Contractor to supply 305mm
square sample for Department Representative's approval before matching and fabrication.

14. Drawer slide for printer specification as follows:


Manufacturer: Richelieu
Product No: 9996W12B
Size: 500mm
* or equivalent alternate *

15. Typical millwork drawer pull hardware specification as follows:


Manufacturer: Richelieu
Product No: BP64664195
Size: 79mm
Finish: Matte Chrome

16. Typical millwork door pull hardware specification as follows:


Manufacturer: Richelieu
Product No: BP31925195
Size: 25mm
c Finish: Matte Chrome

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
18
3
22
Millwork Legend:
Typical
Wood Veneer - Wall and Ceiling Panels
Manufacturer: Armstrong
Species Walnut
Stain: to match Tafisa custom stain to match Tafisa
L491(S) laminate

Wood Veneer - Reception Desk


Species: Walnut TBC
Stain: custom stain to match Tafisa L488(S) laminate
Align

7
Stainless Steel - Wall Panels
(Typical)
Manufacturer: Armstrong
Align Finish: to match elevators
(Typical) Gauge: 22 (Heavy Duty)

Stainless Steel - Base


Finish: to match elevators
Size: As noted
Gauge: 22 (Heavy Duty) 211-2141 Thurston Drive T 613-739-3699
Ottawa ON K1G 6C9 F 613-739-3965
Solid Surface Countertop
Manufacturer: Corian info@LWG-ai.com LWG-ai.com
Colour: Arctic Ice
Thickness: 12mm

Resin Panel

7
Manufacturer: 3Form
Collection: Screen Print
Colour: Code Silver
Colour #: 0-91-120
Finish: Patina (both sides)
Panel Thickness: 12mm
Suspension Series: 200.08
Typical Typical 7
- Suspended Side-Fastening Partition
18 22
9 9
Window Film
18 22 18 22
Manufacturer: 3M
Series: Sun Control Window Film Prestige Series
102 Style No: PR 60

448 641 1187 1597 1187 654 435


Millwork Drawing Notes:
Existing basebuilding wayfinding to be retrofitted w/ LED lighting (typical
throughout). Existing plexiglass signage display to be removed and
Elevation - First Floor Elevator Facade reinstated by Contractor.

Scale: 1:20 Existing Elevator equipment to be re-instated in same location where


removed. All equipment is to be removed by Owner's maintenance service
Key Plan
contractor as required. Contractor to coordinate.

Indicates location of new stainless steel corner guard. Refer to Detail 9 on


ID22 for details.
Project
3 Custom Armstrong Woodworks and Stainless Steel wall and ceiling panels
North
18 22 to align where panels meet at wall/ceiling transition. Ensure no visible gaps
Typical between panels.

Columns to be finished with high gloss paint finish on all exposed faces.
Refer to Wall Finish Plan ID08 for more information.

Europtimum panel 1029x2972mm (to be site verified) c/w 76mm aluminum

Align
Millwork Notes:
7

(Typical)
1. Countertops to be 19mm plywood, finished with 12mm solid surface material
Align unless otherwise noted.
(Typical)
2. Cabinets to be 19mm high density particle board, finished with plastic laminate,
unless otherwise noted.

3. Shelves to be 12mm high density particle board.

4. Interior surfaces of cabinets, drawers and adjustable shelves to be finished with


standard white melamine.

5. Cabinet hinges to be concealed and self-closing.


2015/11/12 Issued for Tender ML
2015/09/11 Issued for 99% Client Review ML
6. Drawers to be installed on full extension heavy duty glides with built-in stops.
2015/08/10 Issued for 66% Client Review ML
7

7. Date Reason for Issue Issuer


blind drilled 50mm O.C., unless otherwise noted.

8. Additional blocking to be provided in partition cavity as required to support


millwork.

9. Corian counters to be supplied and installed by a qualified fabricator. All seams


Typical Typical to be buffed out in accordance with Manufacturer's instructions.
9 9
18 22 18 22
10. Refer to Mechanical Consultants Drawings for connection of equipment.

11. Veneer stained to match sample provided by Department Representative.


102

Contractor shall supply 305mm square sample of material and finish for
Department Representative's approval before application. Veneer to be
shop-stained and finished with three coats of catalyzed polyurethane (satin). Sand
between coats. Finish all sides and edges.

12. It is the Contractor's responsibility to read this drawing in conjunction with all
other drawings including other drawings. Any discrepancies between drawings will
be reported to the Department Representative for clarification during the Tender
process and prior to construction.
Elevation - Second and Third Floor Elevator Facade (Typical)
13. Specification for all wood veneers to be as follows: Veneer to be Walnut "AAA"
Scale: 1:20 Architectural Grade Sequence Match. All flitch to be equal, all veneer to be from
same flitch. Contractor to supply 305mm square sample for Department
Representative's approval before matching and fabrication.

14. Drawer slide for printer specification as follows:


Manufacturer: Richelieu
Product No: 9996W12B
Size: 500mm
* or equivalent alternate *

15. Typical millwork drawer pull hardware specification as follows:


Manufacturer: Richelieu
Product No: BP64664195
Size: 79mm
Finish: Matte Chrome

16. Typical millwork door pull hardware specification as follows:


Manufacturer: Richelieu
Product No: BP31925195
Size: 25mm
Finish: Matte Chrome
c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
32" TV MONITOR

445
211-2141 Thurston Drive T 613-739-3699

88
Align
Ottawa ON K1G 6C9 F 613-739-3965

445
info@LWG-ai.com LWG-ai.com

1155
Line of existing Line of existing Line of existing
Line of new
terrazzo base terrazzo base terrazzo base
rubber base

Elevation - First Floor Staircase and Museum Display Feature Wall


Scale: 1:20

Millwork Legend: Millwork Notes: Key Plan


Wood Veneer - Wall and Ceiling Panels 1. Countertops to be 19mm plywood, finished with 12mm solid surface
Manufacturer: Armstrong material unless otherwise noted.
South - Sud
Species Walnut
Stain: custom stain to match Tafisa L491(S) laminate 2. Cabinets to be 19mm high density particle board, finished with
Project
S-101 - S-126
Wood Veneer - Reception Desk
plastic laminate, unless otherwise noted.
North
Species: Walnut 3. Shelves to be 12mm high density particle board.
Stain: custom stain to match Tafisa L488(S) laminate
Digital Clock 4. Interior surfaces of cabinets, drawers and adjustable shelves to be
N.I.C Stainless Steel - Wall Panels finished with standard white melamine.
Manufacturer: Armstrong
Finish: to match elevators 5. Cabinet hinges to be concealed and self-closing.
55" TV Monitor Gauge: 22 (Heavy Duty)
6. Drawers to be installed on full extension heavy duty glides with
Stainless Steel - Base built-in stops.
Finish: to match elevators
Size: As noted 7.
Gauge: 22 (Heavy Duty) pins in holes blind drilled 50mm O.C., unless otherwise noted.

Solid Surface Countertop 8. Additional blocking to be provided in partition cavity as required to


Manufacturer: Corian support millwork.
Colour: Arctic Ice
10 Thickness: 12mm 9. Corian counters to be supplied and installed by a qualified fabricator.
1920

19 22 All seams to be buffed out in accordance with Manufacturer's


Resin Panel instructions.
Manufacturer: 3Form
Collection: Screen Print 10. Refer to Mechanical s Drawings for connection of equipment.
Colour: Code Silver
Colour #: 0-91-120 11. Veneer stained to match sample provided by Department 2015/11/12 Issued for Tender ML
Finish: Patina (both sides) Representative. Contractor shall supply 305mm square sample of 2015/09/11 Issued for 99% Client Review ML
Panel Thickness: 12mm material and finish for Department Representative's approval before
1219

2015/08/10 Issued for 66% Client Review ML


Suspension Series: 200.08 application. Veneer to be shop-stained and finished with three coats of
1067

- Suspended Side-Fastening Partition catalyzed polyurethane (satin). Sand between coats. Finish all sides Date Reason for Issue Issuer
and edges.
Window Film
Manufacturer: 3M 12. It is the Contractor's responsibility to read this drawing in
Series: Sun Control Window Film Prestige Series conjunction with all other drawings including other 's drawings. Any
Style No: PR 60 discrepancies between drawings will be reported to the Department
Representative for clarification during the Tender process and prior to
Line of new Line of new construction.
rubber base rubber base
1617 2058 1393 13. Specification for all wood veneers to be as follows: Veneer to be
Millwork Drawing Notes: Walnut "AAA" Architectural Grade Sequence Match. All flitch to be
equal, all veneer to be from same flitch. Contractor to supply 305mm
Existing basebuilding wayfinding to be retrofitted w/ LED square sample for Department Representative's approval before
lighting (typical throughout). Existing plexiglass signage display matching and fabrication.
to be removed and reinstated by Contractor.
14. Drawer slide for printer specification as follows:
Elevation - First Floor Graphic Display and Touchdown Station Existing Elevator equipment to be re-instated in same location Manufacturer: Richelieu
where removed. All equipment to be re-instated by certified Product No: 9996W12B
Scale: 1:20 Size: 500mm
professional as required.
Quantity: 2
Indicates location of new stainless steel corner guard. Refer to * or equivalent alternate *
Detail 9 on ID22 for details.
15. Typical millwork drawer pull hardware specification as follows:
Custom Armstrong Woodworks and Stainless Steel wall and Manufacturer: Richelieu
ceiling panels to align where panels meet at wall/ceiling Product No: BP64664195
transition. Ensure no visible gaps between panels. Size: 79mm
Finish: Matte Chrome
Columns to be finished with high gloss paint finish on all Quantity: 7
exposed faces. Refer to Wall Finish Plan ID08 for more
information. 16. Typical millwork door pull hardware specification as follows:
Manufacturer: Richelieu
Europtimum panel 1029x2972mm (to be site verified) c/w Product No: BP31925195
76mm aluminum backlit frame. All panels to be hardwired to Size: 25mm
suit application and daisy-chaines where applicable, refer to Finish: Matte Chrome
Electrical drawings. Panels to be installed as per Quantity: 4
Manufacturer's instructions.

Indicates full height Europtimum graphic display panels at


staircase wall. All panels to be hardwired to suit application and
daisey-chained where applicable, refer to Electrical drawings.
Panels to be installed as per Manufacturer's instructions.

Museum display c/w semi-recessed backlit display cases and


associated hardware. Refer to ID02 for Europtimum equipment
c and materials specifications.

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
LINE OF THIRD FLOOR FINISHED CEILING
Millwork Legend:
Wood Veneer - Wall and Ceiling Panels
Manufacturer: Armstrong
Species Walnut
Stain: custom stain to match Tafisa L491(S) laminate

Site dimension required


Wood Veneer - Reception Desk
Species: Walnut
Stain: custom stain to match Tafisa L488(S) laminate

Stainless Steel - Wall Panels


32" TV Manufacturer: Armstrong
MONITOR Finish: to match elevators
Gauge: 22 (Heavy Duty)

Stainless Steel - Base


55" TV MONITOR Finish: to match elevators
32" TV Size: As noted
MONITOR Gauge: 22 (Heavy Duty)
211-2141 Thurston Drive T 613-739-3699
Solid Surface Countertop Ottawa ON K1G 6C9 F 613-739-3965
Manufacturer: Corian
LINE OF THIRD FLOOR
Colour: Arctic Ice info@LWG-ai.com LWG-ai.com
Thickness: 12mm

32" TV MONITOR Resin Panel


55" TV MONITOR Manufacturer: 3Form
Collection: Screen Print
Colour: Code Silver
Colour #: 0-91-120
Finish: Patina (both sides)
LINE OF SECOND FLOOR FINISHED CEILING Panel Thickness: 12mm
55" TV MONITOR Suspension Series: 200.08
- Suspended Side-Fastening Partition

Window Film
Manufacturer: 3M
Series: Sun Control Window Film Prestige Series
Style No: PR 60
Site dimension required

Millwork Drawing Notes:


Exact location of TV monitors and receptacles to be coordinated
on site with Department Representative. All monitors and
associated mounting equipment to be supplied by Owner and
installed by Contractor.
Line of new rubber base
Key Plan
Mounting height and locations of pendant fixture to be
coordinated on site with Department Representative.
Elevation - First Floor Media Wall Project
LINE OF SECOND FLOOR
Scale: 1:20
Millwork Notes: North
1. Countertops to be 19mm plywood, finished with 12mm solid surface
material unless otherwise noted.

2. Cabinets to be 19mm high density particle board, finished with


plastic laminate, unless otherwise noted.
LINE OF FIRST FLOOR FINISHED CEILING
3. Shelves to be 12mm high density particle board.

4. Interior surfaces of cabinets, drawers and adjustable shelves to be


finished with standard white melamine.

5. Cabinet hinges to be concealed and self-closing.

6. Drawers to be installed on full extension heavy duty glides with


built-in stops.
Site dimension required

7.
55" TV MONITOR pins in holes blind drilled 50mm O.C., unless otherwise noted.

8. Additional blocking to be provided in partition cavity as required to


support millwork.
2015/11/12 Issued for Tender ML
9. Corian counters to be supplied and installed by a qualified fabricator. 2015/09/11 Issued for 99% Client Review ML
All seams to be buffed out in accordance with Manufacturer's
2015/08/10 Issued for 66% Client Review ML
instructions.
Date Reason for Issue Issuer
10. Refer to Mechanical s Drawings for connection of equipment.
10

1920
20 22 11. Veneer stained to match sample provided by Department
Representative. Contractor shall supply 305mm square sample of
Align Align material and finish for Department Representative's approval before
LINE OF FIRST FLOOR application. Veneer to be shop-stained and finished with three coats of
catalyzed polyurethane (satin). Sand between coats. Finish all sides
and edges.

12. It is the Contractor's responsibility to read this drawing in

1219
conjunction with all other drawings including other 's drawings. Any
discrepancies between drawings will be reported to the Department
Representative for clarification during the Tender process and prior to
LINE OF GROUND FLOOR FINISHED CEILING construction.

13. Specification for all wood veneers to be as follows: Veneer to be


Walnut "AAA" Architectural Grade Sequence Match. All flitch to be
equal, all veneer to be from same flitch. Contractor to supply 305mm
square sample for Department Representative's approval before
New rubber base matching and fabrication.

14. Drawer slide for printer specification as follows:


Elevation - Second Floor Touchdown Station Manufacturer: Richelieu
Product No: 9996W12B
Site dimension required

Scale: 1:20 Size: 500mm


Quantity: 2
* or equivalent alternate *

15. Typical millwork drawer pull hardware specification as follows:


Manufacturer: Richelieu
Product No: BP64664195
Size: 79mm
Finish: Matte Chrome
Quantity: 7

16. Typical millwork door pull hardware specification as follows:


Manufacturer: Richelieu
Product No: BP31925195
Size: 25mm
Finish: Matte Chrome
LINE OF GROUND FLOOR Quantity: 4

Elevation - Staircase (Full Height)


Scale: NTS
c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Millwork Legend:
307 307 Wood Veneer - Wall and Ceiling Panels
126 Manufacturer: Armstrong

35
12
Species Walnut
Stain: custom stain to match Tafisa L491(S) laminate

35
25 25 Wood Veneer - Reception Desk
Species: Walnut

307

272
357

272
Stain: custom stain to match Tafisa L488(S) laminate

357
609
609 609
Stainless Steel - Wall Panels
Manufacturer: Armstrong

50

50
Finish: to match elevators

50
Gauge: 22 (Heavy Duty)
Door pull (typical). 96 Drawer drawer pull 96 Power receptacle.

138
903 Refer to Note #16 for (typical). Refer to See elevations for Stainless Steel - Base
specification. Note #15 for exact locations. Finish: to match elevators
1067

1067

1067
Adjustable shelf specification. Size: As noted
PRINTER Pull out shelf on
(typical). Gauge: 22 (Heavy Duty)
self-closing drawer

203
NIC 211-2141 Thurston Drive T 613-739-3699

558

558
slide (500mm). See
millwork notes for Solid Surface Countertop Ottawa ON K1G 6C9 F 613-739-3965

760

760

760
19
specification. Manufacturer: Corian
Blocking Colour: Arctic Ice
to suit info@LWG-ai.com LWG-ai.com
Thickness: 12mm

203

203
BX cable to run Drawer pull (typical).
within millwork Resin Panel
Refer to Note #15 for
cavity. Manufacturer: 3Form
specification.
Collection: Screen Print
Support blocking as Support blocking as Support blocking as Colour: Code Silver

152
152

152

152

152
required required required Colour #: 0-91-120
Finish: Patina (both sides)
Panel Thickness: 12mm
75 522 75 94 522 75 Suspension Series: 200.08
94 522 75
- Suspended Side-Fastening Partition

Window Film
Section - Reception Desk Closed Cabinet Section - Reception Desk Drawers Section - Reception Desk Printer Cabinet Manufacturer: 3M
Series: Sun Control Window Film Prestige Series
Scale: 1:10 Scale: 1:10 Scale: 1:10 Style No: PR 60

307 307
Millwork Notes:

35
35

Line of transaction Line of transaction Line of transaction 1. Countertops to be 19mm plywood, finished with 12mm solid surface
top beyond top beyond. top beyond material unless otherwise noted.

2. Cabinets to be 19mm high density particle board, finished with


Key Plan

307
finished with white finished with white plastic laminate, unless otherwise noted.

357
357

cover. 799 cover.


3. Shelves to be 12mm high density particle board.

4. Interior surfaces of cabinets, drawers and adjustable shelves to be


50

50
50
finished with standard white melamine.
Project

50
96 Cable tray for BX. To 152
be 19mm plywood 500 Cable tray for BX. To
5. Cabinet hinges to be concealed and self-closing.
finished in WV2 on Clear width 50 be 19mm plywood
finished in WV2 on
25mm gable finished North
all exposed faces. with WV2 on all 6. Drawers to be installed on full extension heavy duty glides with

1067
1067

Grommet beyond for all exposed faces. exposed faces. built-in stops.
BX to pass through.
Line of millwork
558

558

Line of millwork 7.
beyond. beyond. pins in holes blind drilled 50mm O.C., unless otherwise noted.
760

760
760
710

Line of millwork 8. Additional blocking to be provided in partition cavity as required to


Power receptacle. support millwork.
beyond.
BX cable to run See elevations for
19mm support gable. within millwork exact locations. 9. Corian counters to be supplied and installed by a qualified fabricator.
cavity. All seams to be buffed out in accordance with Manufacturer's
75 instructions.
152

152

10. Refer to Mechanical s Drawings for connection of equipment.

11. Veneer stained to match sample provided by Department


Representative. Contractor shall supply 305mm square sample of
Section - Reception Desk Gable w/ Wire Section - Reception Desk Accessible Counter Section - Reception Desk Gable w/ Grommet material and finish for Department Representative's approval before
application. Veneer to be shop-stained and finished with three coats of
Scale: 1:10 Management Cable Tray Scale: 1:10 Scale: 1:10 catalyzed polyurethane (satin). Sand between coats. Finish all sides
and edges.

12. It is the Contractor's responsibility to read this drawing in 2015/11/12 Issued for Tender ML
conjunction with all other drawings including other 's drawings. Any
2015/09/11 Issued for 99% Client Review ML
discrepancies between drawings will be reported to the Department
Representative for clarification during the Tender process and prior to Date Reason for Issue Issuer
construction.

13. Specification for all wood veneers to be as follows: Veneer to be


Walnut "AAA" Architectural Grade Sequence Match. All flitch to be
equal, all veneer to be from same flitch. Contractor to supply 305mm
square sample for Department Representative's approval before
matching and fabrication.

14. Drawer slide for printer specification as follows:


Manufacturer: Richelieu
Product No: 9996W12B
Size: 500mm
Quantity: 2
* or equivalent alternate *

15. Typical millwork drawer pull hardware specification as follows:


Manufacturer: Richelieu
Product No: BP64664195
Size: 79mm
Finish: Matte Chrome
Quantity: 7

16. Typical millwork door pull hardware specification as follows:


Manufacturer: Richelieu
Product No: BP31925195
Size: 25mm
Finish: Matte Chrome
Quantity: 4

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Line of finished ceiling. Line of finished ceiling. Line of finished ceiling.
Millwork Legend:
Line of finished ceiling. Ensure no
visible gaps at wall/ceiling transition. Wood Veneer - Wall and Ceiling Panels
Existing terra cotta w/ plaster finish Manufacturer: Armstrong
Existing terra cotta w/ plaster finish or stone aggregate partition fascia. Species Walnut
or stone aggregate partition fascia. Z Clips to be installed as per Stain: custom stain to match Tafisa L491(S) laminate
Manufacturer's installation
instructions. Ensure appropriate Wood Veneer - Reception Desk
Wood framing to be installed at Species: Walnut
fasteners are used to adhere Z Clips
perimeter of display case to provide Stain: custom stain to match Tafisa L488(S) laminate
to marble slab and terra cotta tiles.
73 structural support as required
(typical). Secure framing to existing Stainless Steel - Wall Panels
Armstrong Woodworks panel with
Line of 22mm metal furring channel. Line of 22mm furring channel. To be 152 partition with appropriate fasteners. Manufacturer: Armstrong
custom wood veneer finish.
To be securely fastened to existing securely fastened to existing partition Clear opening dimension for display

445
Finish: to match elevators
partition with appropriate fasteners. with appropriate fasteners. case installation to be coordinated

7
Gauge: 22 (Heavy Duty)
with Europtimum.
22mm plywood blocking to be Stainless Steel - Base
securely fastened to existing Supply and install 13mm gypsum Finish: to match elevators
partitions, flush with furring Ensure minimum 7mm gap in
between panels. board at all exposed edges of Size: As noted
channels, where Europtimum panels exposed blocking and/or terra cotta Gauge: 22 (Heavy Duty)
Existing stone aggregate partition.
and/or TV monitors are scheduled 211-2141 Thurston Drive T 613-739-3699

88
bricks. Gypsum to be flush with face
for installation. of existing partition. Make ready to Solid Surface Countertop Ottawa ON K1G 6C9 F 613-739-3965
Note:
13mm gypsum board to be installed All panels intended for Z-clip receive new paint finish. Manufacturer: Corian
to u/s of finished ceiling. Tape, fill, and installations to be ordered with no Colour: Arctic Ice info@LWG-ai.com LWG-ai.com
sand smooth ready for paint or other kerfs in any edges. Line of existing partition beyond. Thickness: 12mm
finish.
Resin Panel

445
76mm aluminum framed Europtimum Manufacturer: 3Form
graphic display (where applicable) to Collection: Screen Print
be hardwired and installed as per Armstrong panel to be installed
min. 7mm above base. Colour: Code Silver
Manufacturer's instructions. Colour #: 0-91-120
13mm gypsum board to be installed to Adhere blocking directly to existing Semi-recessed acrylic display case Finish: Patina (both sides)
Install panel directly above Schluter
u/s of finished ceiling. Tape, fill, and marble facade (size to suit to be supplied and installed by Panel Thickness: 12mm
trim.
sand smooth ready for paint or other application). Europtimum. Max. protrusion of Suspension Series: 200.08
Supply and install 13mm Schluter Deco finish. 73mm beyond face of finished - Suspended Side-Fastening Partition
Stainless steel base (to match
SG satin anodized aluminum trim partition.
elevator finish) to be installed on
between gypsum and wall base. Install Supply and install 13mm Schluter Deco all exposed edges. Align wall base Window Film
per Manufacturer's instructions. SG satin anodized aluminum trim with face of new wall panels Manufacturer: 3M
between gypsum and wall base. Install (typical throughout). Series: Sun Control Window Film Prestige Series
Adhere new 102mm rubber wall base to per Manufacturer's instructions. Style No: PR 60
12mm plywood blocking. Wall base to Existing terrazzo cove base to be

102
be aligned with gypsum wallboard. Adhere new 102mm rubber wall base to chipped out and removed. Patch Existing cove base to remain.
Existing cove base to be conealed 12mm plywood blocking. Wall base to and repair terrazzo flooring as
(where applicable). be aligned with gypsum wallboard. required.

Millwork Notes:
Section - Furring Partition Type 1 and Section - Furring Partition Type 2 Section - Wall Panel Section - Existing Partition at 1. Countertops to be 19mm plywood, finished with 12mm solid surface
material unless otherwise noted.
Scale: 1:10 Type 3 Scale: 1:10 Scale: 1:5 Scale: 1:10
Display Case 2. Cabinets to be 19mm high density particle board, finished with
plastic laminate, unless otherwise noted. Key Plan
3. Shelves to be 12mm high density particle board.
Install stainless steel corned
guard from floor to ceiling. 4. Interior surfaces of cabinets, drawers and adjustable shelves to be
Ensure no visible exposed
edges of existing terrazzo
finished with standard white melamine.
Project
Aluminum panel hook to H-Bar hanger
#12 hanger wire at 1219mm
O.C. max. To be supplied
cove base. 5. Cabinet hinges to be concealed and self-closing.
North
U-Profile - 1219mm Existing column to be finished 6. Drawers to be installed on full extension heavy duty glides with
O.C. max or as be field attached using #10 and installed by Contractor.
Plug-in clip with high gloss paint. built-in stops.
required by Ontario x 16mm pan head screws
Panel hold down Wall anchor to suit
Building Code (min. 3 per hook)
seismic spring @ application type. 1219 x 1219mm Lyra New stainless steel base to be flush 7.

63
406mm O.C max. suspended ceiling tile w/ with face of column. Ensure no pins in holes blind drilled 50mm O.C., unless otherwise noted.
square tegular profile exposed or sharp edges. Install
(typical) 13mm blocking and adhere directly 8. Additional blocking to be provided in partition cavity as required to
28 10 to existing column. support millwork.
Existing cove base to be removed.

31
9. Corian counters to be supplied and installed by a qualified fabricator.
Column to be chipped out All seams to be buffed out in accordance with Manufacturer's
Slack cable assembly - Blizzard white ceiling grid (typical) approximately 14mm x 102mm to
6mm foam Woodworks Aluminum RA-3 shadow Suspended instructions.
gasket minimum 2 per panel wall angle. gypsum bulkhead accommodate new recessed
hook-on panel H-Bar
required. Allow for Use appropriate w/ metal runner - Suspended gypsum ceiling to be finished with stainless steel wall base. 10. Refer to Mechanical s Drawings for connection of equipment.
152mm (max) panel drop fasteners for size to suit. high gloss paint on all exposed faces. Existing terrazzo flooring
from adjacent panel. application type. 11. Veneer stained to match sample provided by Department
Representative. Contractor shall supply 305mm square sample of
material and finish for Department Representative's approval before
Section - WoodWorks Suspended Ceiling at Gypsum Ceiling Section - Suspended Ceiling Section - Wall Base at Column application. Veneer to be shop-stained and finished with three coats of
catalyzed polyurethane (satin). Sand between coats. Finish all sides
Scale: 1:5 Scale: 1:5 Scale: 1:5 and edges.

12. It is the Contractor's responsibility to read this drawing in 2015/11/12 Issued for Tender ML
conjunction with all other drawings including other 's drawings. Any
2015/09/11 Issued for 99% Client Review ML
discrepancies between drawings will be reported to the Department
Representative for clarification during the Tender process and prior to Date Reason for Issue Issuer
Line of finished construction.
partition.
12 gauge hanger wire at 1219mm o.c. (max.) or as required by local seismic
13. Specification for all wood veneers to be as follows: Veneer to be
regulations. To be supplied by Contractor.
Walnut "AAA" Architectural Grade Sequence Match. All flitch to be
equal, all veneer to be from same flitch. Contractor to supply 305mm
Countertop edge to square sample for Department Representative's approval before
align with partition

31
610mm x 610mm drywall grid system matching and fabrication.
(First Floor only).
to be supplied by Contractor.
14. Drawer slide for printer specification as follows:
Manufacturer: Richelieu
406 Support L bracket Product No: 9996W12B
Woodworks radial access panel mounted to furring Size: 500mm

306
partition to support Quantity: 2
millwork installation. * or equivalent alternate *

15. Typical millwork drawer pull hardware specification as follows:


Manufacturer: Richelieu
Line of waterfall edge Product No: BP64664195
WV2 finish on all beyond. Size: 79mm
exposed edges. Thickness: 1" (typ.) Finish: Matte Chrome

1067
Quantity: 7

16. Typical millwork door pull hardware specification as follows:


3mm foam gasket reveal Manufacturer: Richelieu
Terrazzo cove base to be
chipped out as required to Product No: BP31925195
accommodate new Size: 25mm
stainless steel corner Finish: Matte Chrome
3mm foam gasket reveal guard. Ensure no exposed Line of recessed stainless Custom Woodworks wall Elevator Quantity: 4
edges. Secure corner steel base and blocking. panels by Armstrong. frame
Radial system center opening to suit guard with clear silicone Terrazzo cove base to be Existing marble facade to
dimensions of canopy for pendant fixture. caulking. chipped out to accommodate be concealed.
Site verification required prior to new recessed stainless steel
installation. Stainless steel corner guard. base.

Radial Suspended Ceiling Isometric View Section - Wall Base and Corner Guard Installation Section - Touchdown Counter
Scale: 1:20 Scale: 1:5 Scale: 1:10
20 (Typical)

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
211-2141 Thurston Drive T 613-739-3699
MECHANICAL LEGEND Ottawa ON K1G 6C9 F 613-739-3965

info@LWG-ai.com LWG-ai.com

B B B
## ## ##
## ## ##
A A A TTF Engineering Unit 205 - 1600 Merivale Road
Ottawa, ON K2G 5J8 Tel. 613-592-1677

FE FE FE

Key Plan
Project
North

CEILING LEGEND

NEW SUSPENDED T-BAR CEILING GRID


AND ACOUSTICAL TILES
2015/08/10 66% Review TTF Eng.
Date Reason for Issue Issuer

NEW SUSPENDED T-BAR CEILING GRID


AND WOOD ACOUSTICAL TILES

EXISTING SUSPENDED GYPSUM BOARD


CEILING TO REMAIN

NEW SUSPENDED GYPSUM BOARD


CEILING

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
211-2141 Thurston Drive T 613-739-3699
Ottawa ON K1G 6C9 F 613-739-3965

info@LWG-ai.com LWG-ai.com

TTF Engineering Unit 205 - 1600 Merivale Road


Ottawa, ON K2G 5J8 Tel. 613-592-1677

Key Plan
Project
North

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Dn 211-2141 Thurston Drive T 613-739-3699
Ottawa ON K1G 6C9 F 613-739-3965

info@LWG-ai.com LWG-ai.com
Stair F

Up

9"
9"

TTF Engineering Unit 205 - 1600 Merivale Road


Ottawa, ON K2G 5J8 Tel. 613-592-1677

AD

9"
14 15

9" Up Up

Up Dn

Stair A

Up Dn Dn

Stair F

Up

Up

Up Dn
Dn Up

Up Dn
Stair D
Stair E

Stair D

Stair D
Key Plan
Project
North

2015/10/08 66% Review TTF Eng.


Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
C310

C310A
M
FE

60"X30"

AD
22"X30"

211-2141 Thurston Drive T 613-739-3699


Ottawa ON K1G 6C9 F 613-739-3965

info@LWG-ai.com LWG-ai.com
E302 W304

46"X30"

W304A TTF Engineering Unit 205 - 1600 Merivale Road


Ottawa, ON K2G 5J8 Tel. 613-592-1677
AD

S325

S323 Stair A

S320
S319
S321
S318

S300
S317
S316

S315 S319

E301 W305

S307A
S314
S313

S310
S311

S311A
S308

S306
S303

S304

C310

C310A
M

E322 E320 E318 E316 E314 E312 E310 E308 E306 E302 W304 W308 W310 W312 W314 W318 W322 W324

W304A W300 W307A W315A W321 16

E319 E317 E315 E311 E309 E307 E305 E303 E301 W305 W307 W311 W315 W317 W319
Stair C Stair E

Stair D

Stair D
Key Plan
Project
North

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
211-2141 Thurston Drive T 613-739-3699
Ottawa ON K1G 6C9 F 613-739-3965

440 CFM
info@LWG-ai.com LWG-ai.com

TTF Engineering Unit 205 - 1600 Merivale Road


D D Ottawa, ON K2G 5J8 Tel. 613-592-1677
D
VAV-1

B
440 CFM

D
D B
D 440 CFM
D D

D A-A
VAV-1 M-4

440
CFM

A
D
D

D
VAV-1
D
Key Plan
Project
North
440
CFM

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

L-1 LIGHT FIXTURE

SUPPLY AIR
PLENUM

ONE SLOT DIFFUSER


TYPE B,C,D CEILING T-BAR

A-A ONE SLOT DIFFUSER & L-1 LIGHT FIXTURE SECTION A-A
M-4 Scale: 1:4

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
Dn 211-2141 Thurston Drive T 613-739-3699
Ottawa ON K1G 6C9 F 613-739-3965
C 330 CFM
info@LWG-ai.com LWG-ai.com
Stair F
C 330 CFM D
D
D
D
VAV-2 D
Up

9"
9"

TTF Engineering Unit 205 - 1600 Merivale Road


Ottawa, ON K2G 5J8 Tel. 613-592-1677

665 CFM AD

9"
A
D 14 15

D 9" Up Up

Up Dn

Stair A

D
VAV-2

Up Dn Dn

Stair F

Up

Up

Up Dn
Dn Up

Up Dn
Stair D
Stair E

Stair D

Stair D
Key Plan
Project
North

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
C310

C310A
M
FE

60"X30"

AD
22"X30"

211-2141 Thurston Drive T 613-739-3699


Ottawa ON K1G 6C9 F 613-739-3965
410 CFM
D
D
info@LWG-ai.com LWG-ai.com
E302 410 CFM D
D
D W304
D
VAV-1

46"X30"

W304A TTF Engineering Unit 205 - 1600 Merivale Road


Ottawa, ON K2G 5J8 Tel. 613-592-1677
AD

S325

S323 Stair A

S320
S319
S321
S318

S300
S317
S316

S315 S319

E301 W305

S307A
S314
S313

S310
S311

S311A
S308

S306
S303

S304

C310

C310A
M

E322 E320 E318 E316 E314 E312 E310 E308 E306 E302 W304 W308 W310 W312 W314 W318 W322 W324

W304A W300 W307A W315A W321 16

E319 E317 E315 E311 E309 E307 E305 E303 E301 W305 W307 W311 W315 W317 W319
Stair C Stair E

Stair D

Stair D
Key Plan
Project
North

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
211-2141 Thurston Drive T 613-739-3699
Ottawa ON K1G 6C9 F 613-739-3965

info@LWG-ai.com LWG-ai.com

TTF Engineering Unit 205 - 1600 Merivale Road


Ottawa, ON K2G 5J8 Tel. 613-592-1677

S325

S323 Stair A

S320
S319
S321
S318

S300
S317
S316

S315 S319

S307A
S314
S313

S310
S311

S311A
S308

S306
S303

S304

C310

C310A
M

E322 E320 E318 E316 E314 E312 E310 E308 E306 E302 W304 W308 W310 W312 W314 W318 W322 W324

W304A W300 W307A W315A W321 16

E319 E317 E315 E311 E309 E307 E305 E303 E301 W305 W307 W311 W315 W317 W319
Stair C Stair E

Stair D

Key Plan
Project
North

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
SG-04A

CG-07

WG-02
211-2141 Thurston Drive T 613-739-3699
Ottawa ON K1G 6C9 F 613-739-3965
EG-02 Stair F
info@LWG-ai.com LWG-ai.com

CG-05
TTF Engineering Unit 205 - 1600 Merivale Road
CG-02 Ottawa, ON K2G 5J8 Tel. 613-592-1677
CG-01C

M WG-01
EG-01 F
CG-01

CG-02A

U D

CG-02B
66"x5" 66"x5"
CG-01B
Stair D

Key Plan
Project
North

SG-04A

FFH-1 FFH-1

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

CG-07
WG-02

EG-02 Stair F

CG-05
CG-02
CG-01C

M WG-01
EG-01 F
CG-01

CG-02A

U D
FCU-1

CG-02B
66"x5" 66"x5"
CG-01B
A1-007052-01-01
Stair D
c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
211-2141 Thurston Drive T 613-739-3699
ELECTRICAL LEGEND Ottawa ON K1G 6C9 F 613-739-3965

info@LWG-ai.com LWG-ai.com

H H H

TTF Engineering Unit 205 - 1600 Merivale Road


S S S Ottawa, ON K2G 5J8 Tel. 613-592-1677

D D D

D D D

D D D
Key Plan
Project
North

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

CEILING LEGEND

NEW SUSPENDED T-BAR CEILING GRID


AND ACOUSTICAL TILES

LIGHTING FIXTURE SCHEDULE


NEW SUSPENDED T-BAR CEILING GRID
AND WOOD ACOUSTICAL TILES
L-3 L-3 L-3
EXISTING SUSPENDED GYPSUM BOARD L-1 L-1 L-1
CEILING TO REMAIN
L-2 L-2 L-2
NEW SUSPENDED GYPSUM BOARD
CEILING
L-4 L-4 L-4

L-5 L-5 L-5

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
H
211-2141 Thurston Drive T 613-739-3699
Ottawa ON K1G 6C9 F 613-739-3965

info@LWG-ai.com LWG-ai.com

TTF Engineering Unit 205 - 1600 Merivale Road


Ottawa, ON K2G 5J8 Tel. 613-592-1677

Key Plan
FROM L-15
Project
North
S

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
211-2141 Thurston Drive T 613-739-3699
Ottawa ON K1G 6C9 F 613-739-3965

info@LWG-ai.com LWG-ai.com

TTF Engineering Unit 205 - 1600 Merivale Road


Ottawa, ON K2G 5J8 Tel. 613-592-1677
Dn

S
Stair F 14 15

Up Up

Up Dn

Stair A

Up

Dn

Stair F

Up

Up

Up Dn
Dn Up

Up Dn
Stair D
Stair E

Stair D

Key Plan
S

Project
Up Dn
North

Stair D

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
S306
S303

211-2141 Thurston Drive T 613-739-3699


Ottawa ON K1G 6C9 F 613-739-3965
S304
EXISTING PANELS info@LWG-ai.com LWG-ai.com
L-29 ; L-30 ; L-30A

C310

C310A
TTF Engineering Unit 205 - 1600 Merivale Road
Ottawa, ON K2G 5J8 Tel. 613-592-1677

M
S325

S323 Stair A

S320
S319
S321
S318

S300
S317
S316
S
S315 S319

S307A
S314
S313

S310
S311

S311A
S308

S306
S303

S304

S C310

C310A
E302 W304 E322 E320 E318 E316 E314 E312 E310 E308 E306 E302
M

W304

W304A
W308

W300
W310

W307A
W312

W315A
W314 W318 W322

W321
W324

16

E319 E317 E315 E311 E309 E307 E305 E303 E301 W305 W307 W311 W315 W317 W319
Stair C Stair E

Stair D

W304A
S

Key Plan
Project
North
E301 W305

EXISTING
PANEL
Stair D L-28
2015/08/10 66% Review TTF Eng.
Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
L-1

L-1
211-2141 Thurston Drive T 613-739-3699
Ottawa ON K1G 6C9 F 613-739-3965
L-2
info@LWG-ai.com LWG-ai.com

L-1 L-1

L-1 L-1
L-1

TTF Engineering Unit 205 - 1600 Merivale Road


Ottawa, ON K2G 5J8 Tel. 613-592-1677

L-1
L-5
L-3

L-1

L-1 L-2
L-2 L-1

L-1 L-1

L-1 FROM L-15


L-1 L-1

S
Key Plan
Project
North
L-1

L-1

L-1

L-1 L-1 L-1

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

TYPICAL

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
L-1

L-1
S

L-2

Dn 211-2141 Thurston Drive T 613-739-3699


Ottawa ON K1G 6C9 F 613-739-3965
L-1

L-5 info@LWG-ai.com LWG-ai.com


Stair F
L-3
L-1

Up

L-1 L-1

L-2
TTF Engineering Unit 205 - 1600 Merivale Road
L-1 L-1 Ottawa, ON K2G 5J8 Tel. 613-592-1677
L-2

L-1
14 15

Up Up

Up Dn

Stair A

L-1 L-1

Up Dn Dn

Stair F

Up

Up

Up Dn
Dn Up

Up Dn
Stair D
Stair E

Stair D

L-1 L-1

Stair D
TYPICAL Key Plan
Project
North

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
EXISTING PANELS
L-29 ; L-30 ; L-30A

C310 L-1

C310A
L-1
M
S

L-2

211-2141 Thurston Drive T 613-739-3699


Ottawa ON K1G 6C9 F 613-739-3965
L-1 L-1 L-1 L-1

L-5
info@LWG-ai.com LWG-ai.com
L-3

E302 L-1 L-1 L-1 L-1


S
W304

TTF Engineering Unit 205 - 1600 Merivale Road

W304A
S
Ottawa, ON K2G 5J8 Tel. 613-592-1677
L-1 L-1 L-1 L-1
L-2 L-2

S325

S323 Stair A

S320
S319
S321
S318

S300
S317
S316

S315 S319

S307A
S314
S313

W305
S310

E301
S311

S311A
S308

S306
S303

S304

C310

C310A
M

E322 E320 E318 E316 E314 E312 E310 E308 E306 E302 W304 W308 W310 W312 W314 W318 W322 W324

W304A W300 W307A W315A W321 16

E319 E317 E315 E311 E309 E307 E305 E303 E301 W305 W307 W311 W315 W317 W319
Stair C Stair E

Stair D

EXISTING
PANEL
Stair D L-28
TYPICAL Key Plan
Project
North

2015/09/14 99% Review TTF Eng.


2015/08/10 66% Review TTF Eng.
Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
211-2141 Thurston Drive T 613-739-3699
Ottawa ON K1G 6C9 F 613-739-3965

info@LWG-ai.com LWG-ai.com

TTF Engineering Unit 205 - 1600 Merivale Road


Ottawa, ON K2G 5J8 Tel. 613-592-1677

S325

S323 Stair A

S320
S319
S321
S318

S300
S317
S316

S315 S319

S307A
S314
S313

S310
S311

S311A
S308

S306
S303

S304

C310

C310A
M

E322 E320 E318 E316 E314 E312 E310 E308 E306 E302 W304 W308 W310 W312 W314 W318 W322 W324

W304A W300 W307A W315A W321 16

E319 E317 E315 E311 E309 E307 E305 E303 E301 W305 W307 W311 W315 W317 W319
Stair C Stair E

Stair D

Key Plan
Project
North

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
SG-04A

CG-07

WG-02
211-2141 Thurston Drive T 613-739-3699
Ottawa ON K1G 6C9 F 613-739-3965
EG-02 Stair F
info@LWG-ai.com LWG-ai.com

CG-05
TTF Engineering Unit 205 - 1600 Merivale Road
CG-02 Ottawa, ON K2G 5J8 Tel. 613-592-1677
CG-01C

M WG-01
EG-01 F
CG-01

CG-02A

U D

CG-02B

CG-01B
Stair D

Key Plan
Project
North

SG-04A

2015/08/10 66% Review TTF Eng.


Date Reason for Issue Issuer

CG-07
WG-02

EG-02 Stair F

CG-05
CG-02
CG-01C

M WG-01
EG-01 F
CG-01

CG-02A

U D

CG-02B

CG-01B
A1-007052-01-01
Stair D
c

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm
LIGHTING

1. LIGHTING FIXTURES

1. L-1: RECESSED VERTICAL MOUNT LED LIGHT FIXTURE


INSTALL:
REGRESSED - FOR CUSTOM WOOD SUSPENDED CEILING
FLUSH - FOR STANDARD SUSPENDED CEILING SYSTEM

SPECIFIED PRODUCT: AXIS


MODEL: BEAM 4

2. L-2: 4' LED LINEAR LIGHT FIXTURE


INSTALL IN EXISTING WAY FINDING SIGNAGE .

SPECIFIED PRODUCT: PHILIPS


MODEL: FLUXSTREAM-EZ

3. L-3: PENDANT LIGHT FIXTURES, CIRCULAR.


-FINISH: MATTE WHITE WHM
-INSTALL CENTERED
-SIZES & QUANTITIES:
609 mm (X4 CYCLES) 211-2141 Thurston Drive T 613-739-3699
914mm (X2 CYCLES) Ottawa ON K1G 6C9 F 613-739-3965
REFER TO INTERIOR DESIGN DRAWINGS FOR INSTALLATION DETAILS.

SPECIFIED PRODUCT: EUREKA


info@LWG-ai.com LWG-ai.com
MODEL: CYCLE

4. L-4: RECESSED DOWN LIGHT


ELECTRICAL REQUIREMENTS: 120 TO 277 V

SPECIFIED PRODUCT: LUMENPULSE


MODEL: LUMENALPHA DOWNLIGHT

2. WIRING:
.1 FOR NEW FLUORESCENT TROFFER LUMINARIES IN OFFICES. CONNECT LUMINARIES TO TTF Engineering Unit 205 - 1600 Merivale Road
SWITCHED LIGHTING CIRCUITS. VOLTAGES AS INDICATED. Ottawa, ON K2G 5J8 Tel. 613-592-1677
.2 CONNECT FLUORESCENT LUMINARIES IN WAREHOUSE RACKING AREA. CONNECT TO 347
VOLT CIRCUITS AS SHOWN ON DRAWINGS.
.3 CONNECT NIGHT LIGHT FIXTURES TO UNSWITCHED FLUORESCENT CIRCUITS.
.4 CONNECT EXTERIOR FLOOD LIGHTING TO TIME CLOCK CONTROLLED CIRCUITS.

3. SUPPORTS:
.1 SUPPORT ALL NEW LUMINARIES MOUNTED IN CEILING GRID INDEPENDENTLY OF
SUSPENDED CEILING GRID BY CHAINS IN ACCORDANCE WITH LOCAL INSPECTION
REQUIREMENTS.
EXIT LIGHTS AND EMERGENCY BATTERY UNITS
1. EXIT LIGHTS
.1 EXIT SIGNAGE TO NRCAN/ CSA C860-01 REGULATIONS.
.2 COMMERCIAL GRADE, THERMOPLASTIC EXIT SIGN. SNAP TOGETHER DESIGN.
.3 LED TYPE AC INPUT 120 TO 347 VOLT WITH A 12 VDC SECONDARY.
.4 LIFE EXPECTANCY OF THE LEDS TO BE 25 YEARS.
.5 GREEN COLORED RUNNING PICTOGRAM
.6 FACE PLATE TO REMAIN CAPTIVE FOR RELAMPING.
.7 UNIVERSAL MOUNTING.
.8 ARROW RIGHT, LEFT, BOTH DIRECTIONS AS SHOWN ON DRAWINGS.
.9 CEILING OR WALL MOUNTING CANOPY AND MOUNTING PLATE FOR INSTALLATION ON
100mm OCTAGONAL JUNCTION BOX.
.10 INSTALL EXIT LIGHTS AS INDICATED, TO REQUIREMENTS OF OBC-2012
.11 CONNECT FIXTURES TO DEDICATED EXIT LIGHT CIRCUITS AS INDICATED.
.12 STANDARD OF ACCEPTANCE: LUMACELL LP3WU
SMOKE DETECTOR:
1. SELF-DIAGNOSTIC, PHOTOELECTRIC, TWO WIRE SMOKE DETECTORS. 12-24 VDC C/W
AUXILIARY RELAY.
Key Plan
SPECIFIED PRODUCT: CHUBB-EDWARDS
MODEL: C2M-PDHRC
Project
North

2015/11/13 Isued For Tender TTF Eng.


2015/08/10 66% Review TTF Eng.
Date Reason for Issue Issuer

A1-007052-01-01

ASPM A1 (841x594)
0 10 20mm 40 60 80 100 120 140 160 180 200mm