The Standard shall cover the minimum requirements for the installation of private service
mains and their appurtenances, which include the following
-Automatic Sprinkler Systems
-Open Sprinkler Systems
-Water Spray Fixed Systems
-Foam Systems
-Private Hydrants
-Monitor Nozzles or Standpipe Systems with reference to water supplies
-Hose Houses
The standard shall apply to combined service mains intended to carry water for fire service
and other uses
The standard shall NOT apply to underground fire mains serving sprinkler systems designed
and installed in accordance with NFPA 13R that are less than 4 in in nomimal diameter
The standard shall not apply to underground mains serving sprinkler systems designed and
installed in accordance with NFPA 13D
The Purpose of this standard shall be to provide a reasonable degree of protection for life and
property from fire through installation requirements for private service main systems based
on sound engineering principles, test data, and field experience.
The provisions of this standard reflect a consensus for what is necessary to provide an
acceptable degree of protection from the hazards addressed in this standard at the time the
standard was issued.
Residual Pressure
The pressure that exists in the distribution system, measured at the residual hydrant at the
time the flow readings are taken at the flow hydrants.
Static Pressure
The pressure that exists at a given point under normal distribution system conditions
measured at the residual hydrant with no hydrants flowing.
Flow Test
A test performed by the flow and measurement of water from one hydrant and the static and
residual pressures from an adjacent hydrant for the purpose of determining the available
water supply at that location.
Flushing Test
A test of a piping system using high velocity flows to remove debris from the piping system
prior to it being placed in service
Hydrostatic Test
A test of a closed piping system and its appurtenances consisting of subjecting to an increased
internal pressure for a specified duration to verify system integrity and system leakage rates.
Check Valve
A valve that allows flow in one direction but prevents flow in the opposite direction.
Indicating Valve
A valve that has components that show if the valve is open or closed. Examples are outside
screw and yoke (OS&Y) gate valves and underground gate valves with indicator posts.
Dry-Barrel Hydrant
Fire hydrant that has its operating valve located at the base or foot of the hydrant rather than
in the barrel of the hydrant. When operating properly, there is no water in the barrel of the
hydrant when it is not in use. These hydrants are used in areas where freezing may occur.
Flow Hydrant
The hydrant that is used for the flow and flow measurement of water during a flow test.
Public Hydrant
A valved connection on a water supply system having one or more outlets that is used to
supply hose and fire department pumpers with water.
Residual Hydrant
The hydrant that is used for measuring static and residual pressures during a flow test
Wet-Barrel Hydrant
A hydrant used in areas that are not susceptible to freezing. The barrel of the hydrant is
normally filled with water.
Where post indicator valves are used, they shall be set so that the top of each post is
32-40 inches above final grade
The connection from the hydrant to the main shall not be less than
6 inches
Hydrants shall be located not less than _______ from the building to be protected
40ft
Where hydrants located closer than 40ft to the building, shall be permitted to be used where
approved by
the AHJ
The center of a hose outlet shall not be less than_______above final grade
18 inches
The center of a hose outlet shall not be more than_______above final grade
36 inches
The center of a hose outlet located in a hose house shall not be less than _______ above the
floor
12 inches
Master streams shall be delivered by monitor nozzles, hydrant-mounted monitor nozzles, and
similar master stream equipment capable of delivering more than
250 GPM ( 950 LPM)
The top of the pipe shall not be buried less than _______ nelow the frost line for the locality.
12 Inches
In locations where freezing is not a factor, the depth cover shall not be less than ______
below grade to prevent mechanical damage.
30 Inches
Private fire service mains installed under driveways or roadways shall be buried at a
minimum depth of
36 inches
Private fire mains installed under railroad tracks shall be buried at minimum depth of
4 ft
Private fire mains installed under large piles of heavy commodities or subject to heavy shock
and vibrations shall be buried at a minimum depth of
4 ft
NFPA 24
AHJ
Working plans shall be submitted for approval to the _____ before any equipment is installed
or remodeled.
Pressure-Regulating devices
____ shall not be used
Control Valves
______ shall not be installed in the piping from the fire department connection to the fire
service main
Control Valves
_____ shall be permitted in the system downstream of the fire department connection
Check Valve
When more than one water supply exists, a ___________ shall be installed in each
connection
Control Valve
All check valves shall have a ________ installed upstream and downstream of the check
valve.
40 ft
A post indicator valve installed not less than____ from the building
32-40 inches
Where post indicator valves are used, they shall be set so that the top of each post is _______
above final grade not be required.
shall be cleaned and thoroughly coated with a bituminous or other acceptable corrosion-
retarding material
After installation, rods, nuts, bolts, washers, clamps, and other restraining devices
_____________________
facing uphill
Bell ends shall be __________
clear of debris
The flushing operation shall continue until water flow is verified to be ___________
gauge pressure of 200 psi or 50 psi above working pressure for 2 hours
All piping shall be hydrostatically tested at ____________________________
10 ft/sec
Flow required to produce velocity of __________ in pipes
control valves
______________ do not include drain valves, check valves, or relief valves
NFPA 24
Standard for the Installation of Private Fire Service Mains and Their Appurtenances
AHJ
Authority Having Jurisdiction
Appurtenance
An accessory or attachment that enables the private fire service main to perform its intended
function.
Corrosion-Resistant Piping
Piping that has the property of being able to withstand deterioration of its surface or its
properties when exposed to its environment.
Corrosion-Retarding Material
A lining or coating material that when applied to piping or appurtenances has the property of
reducing or slowing the deterioration of the objects surface or properties when exposed to it
environment.
Fire Pump
A pump that is a provider of liquid flow and pressure dedicated to fire protection. A fire pump
is a part of a fire standpipe system's water supply and can be powered by electric, diesel or
steam. The pump intake is either connected to the public underground water supply piping or
a static water source (e.g., tank, reservoir, lake). The pump provides water flow at higher
pressure and volume to the standpipe system risers and hose standpipes.
Hose House
An enclosure located over or adjacent to a hydrant or other water supply designed to contain
the necessary hose nozzles, hose wrenches, gaskets, and spanners to be used in fire fighting in
conjunction with and to provide aid to the local fire department.
Hydrant Butt
The hose connection outlet of a hydrant
Residual Pressure
The pressure that exists in the distribution system, measured at the residual hydrant at the
time the flow readings are taken at the flow hydrants.
Static Pressure
The pressure that exists at a given point under normal distribution system conditions
measured at the residual hydrant with no hydrants flowing.
Pressure-Regulating Device
A device designed for the purpose of reducing, regulating controlling, or restricting water
pressure. Example includes pressure reducing valve, pressure control valves, and pressure-
restricting devices.
Private Fire Service Main
Private fire service main, as used in this standard, is that pipe and its appurtenances on private
property (1) between a source of water and the base of the system riser for water-based fire
protection systems, (2) between a source of water and inlets to foam-making systems, (3)
between a source of water and the base elbow of private hydrants or monitor nozzles, and (4)
used as fire pump suction and discharge piping, (5) beginning at the inlet side of the check
valve on a gravity or pressure tank
Pumper Outlet
The hydrant outlet intended for use by fire departments for taking supply from the hydrant for
pumpers
Rated Capacity
The flow available from a hydrant at the designated residual pressure (rated pressure) either
measured or calculated
Flow Test
A test performed by the flow and measurement of water from one hydrant and the static and
residual pressures from an adjacent hydrant for the purpose of determining the available
water supply at that location.
Flushing Test
A test of a piping system using flow rates intended to remove debris from the piping system
prior to it being placed in service.
Hydrostatic Test
A test of a closed piping system and its attached appurtenances consisting of subjecting the
piping to an increased internal pressure for a specified period of duration to verify system
integrity and leak rates
Check Valve
A valve that allows flow in one direction only.
Indicating Valve
A valve that has components that show if the valve is open or closed. Examples are outside
screw and yoke (OS&Y) gate valves and underground gate valves with indicator posts.
Hydrant
An exterior valved connection to a water supply system that provides hose connections
Flow Hydrant
The hydrant that is used for the flow and flow measurement of water during a flow test.
Public Hydrant
A valved connection on a water supply system having one or more outlets that is used to
supply hose and fire department pumpers with water.
Residual Hydrant
The hydrant that is used for measuring static and residual pressures during a flow test
Residual Pressure
The pressure that exists in the distribution system, measured at the residual hydrant at the
time the flow readings are taken at the flow hydrants.
Static Pressure
The pressure that exists at a given point under normal distribution system conditions
measured at the residual hydrant with no hydrants flowing.
Flow Test
A test performed by the flow and measurement of water from one hydrant and the static and
residual pressures from an adjacent hydrant for the purpose of determining the available
water supply at that location.
Flushing Test
A test of a piping system using high velocity flows to remove debris from the piping system
prior to it being placed in service.
Hydrostatic Test
A test of a closed piping system and its attached appurtenances consisting of subjecting the
piping to an increased internal pressure for a specified duration to verify system integrity and
system leakage rates.
Check Valve
A valve that allows flow in one direction only.
Indicating Valve
A valve that has components that provide the valve operating condition, open or closed.
Flow Hydrant
The hydrant that is used for the flow and flow measurement of water during a flow test.
Residual Hydrant
The hydrant that is used for measuring static and residual pressures during a flow test.
6 in (150 mm)
For mains that supply fire hydrants, pipe size shall not be less than _____.
6 in
The connection from the hydrant to the main shall not be less than _____.
control valve
A listed _____ _____ shall be installed in each hydrant connection.
AWWA C900
Standard for PVC pressure pipe and fittings, 4 in through 63 in
Shall not be installed between fire hydrant, and the control valve
Check Valves, Detector Check Valves, Backflow Prevention Valves, Other Similar
Appurtenances