02 Whole

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 386

lÉ-tr- ()

AN INVESTIGATION OF THE
WEAK LINKS IN THE SEISMIC
LOAD PATH OF UNREINFORCEI)
MASONRY BUILDINGS

Kevin Thomas Doherty


B.E. Hons (Civil) The University of Adelaide

A thesis submitted to the Faculty of Engineering at The University of Adelaide for the
Degree of Doctor of Philosophy

Department of Civil and Environmental Engineering,

'n"'ïi;Äi[ff#""'o'

May 2000
Amendments To Thesis
'An Investigation of the Weak Links in the Seismic Load Path of Unreinforced
Masonry Buildings'

A1 Replace on Page 53, Figure 4.2.1the text 'Rigid Frame Fixed to Laboratory
Strong Floor'' with 'Stationary Reference Datum'.

A2 Insert the following regression coefficients to the figures indicated

Figure4.4.3 R=0.999
Figure 4.4.4 R=0.996
Figure4.4.5 R=0.997
Figure4.4.6 R=0.998
Figure4.4.7 R=0.999
Figure 4.4.8R=0.988

The regression coefficient R for the plots indicate a very good correlation of the
test data with a straight line.

A3 Insert the following paragraph as a new second paragraph on page 106:


Under the assumption adopted of unreinforced masonry building systems having
stiff shear waìl and diaphragms the restrained translation of floors providing equal
input motions at the base on top of wall specimens is appropriate. This is not the
case however where floor diaphragms are flexible such as those constructed of
timber. Where this is the case the response of the floor diaphragm may govern the
wall response with possibly quite different inputs at the base and top of the wall.
Here a different dynamic stability problem than that being investigated in the
current research project may develop as it is possible that the walls will not crack
at mid-height but will rock about their base after a crack forms at the base bed -
joint. Consequently these systems will have a much lower frequency thari thaf of
the individual wall panel.

A4 Insert the following paragraph as a new third paragraph on page 219:


The following points summarise the salient findings of the bending tests:
. Confirmation of mid-height cracking and dynamic stability problems
. Damping associated with the rocking walls was determined and generally
found to be of the order of 5Vo. Rayleigh Damping was found to best
approximate the damping by combining both stiffness and mass proportional
damping components. Increases in damping where found at high and low
frequencies,
. The force displacement relationship for URM walls cracked at mid height was
assessed via push tests. Here the variation in the force displacement
relationship with wall slenderness, boundary conditions, precompression and
degradation due to rocking cycles where determined. A tri-linear approximation
of the force displacement relationship was proposed to best approximate the true
relationship with empirically derived points to define the initial stiffness and
plateau for various levels of wall degradation.
. The effective resonant frequency associated with the frequency for maximum
displacement amplification was determined for URM walls cracked at mid
height for various slenderness, boundary conditions, precompression and
degradation due to rocking cycles.
a Both displacement and acceleration responses were recorded for walls
subjected to transient, impulse and free vibration for later comparison with
an al ytically derived response.

A5 Insert the following paragraph as the final paragraph on page220:


Since the current research project has focussed on the one-way bending of
unreinforced masonry walls to now take jnto account the two-way bending action
which is often observed in seismic failure modes further research is required.
Further as the assumption of the restrained translation of floors providing equal
input motions at the base on top of wall specimens appropriate for unreinforced
masonry building systems having stiff shear wall and diaphragms has been
adopted fulther research is requiled to take into account flexible floor diaphragms
and shear walls.

A6 Typographical errors:
page9,line l4 replace'earthquake' with'earthquakes'
page l6,1ine 6 replace 'Masonry' with 'masonry'
page 43,line 3 replace 'Section 0' with 'Section 2.4'
page 47,line 8 replace 'Chapter 0' with 'Chaprter 4'
page 49,line l1 replace 'f6"' with 'f¿'
page 51, title replace'Connection' with'Connections'
page 221, I 0'r' Citation replace'P.D.' with'D.P.'
Throughout document replace 'Nigel Priestly' with 'Nigel Pliestley'

A7 Insert the following paragraph as the final paragraph on page 47.


Along with variations in local material properties the wide variety of test
configurations discussed above may also be responsible for the wide scatter of
reported results. In particular in-plane tests are seen to be particularly sensitive to
variation in test configuration. Typically an average shear stress along the friction
plane is used to determine the friction coefficient. Accordingly where three high
brick plisms have been used for in plane testing the average shear stress and thus
frictional coefficient determined may be significantly effected by the end
conditions and the moment induced at the friction plane. By adopting wallets with
multiple brick lengths the effect of the end conditions and the variation in normal
stresses over the friction plane is reduced.

Insert the following paragraph as the final paragraph on page 54.


The results of the in plane tests presented in Figures 4.4.6to 4.4.8 show a
regression coefficient of near unity thus indicating a very good linear correlation.
Although in plane tests are always difficult due to the nature of pure shear tests the
good linear correlation indicates the assumption of a uniform shear stress for the
derivation of the average friction coefficient is appropriate. In reality, due to the
height of the lead weights a lever arm and thus overturning moment exists so that
a triangular stress profile is likely. Here the increase in frictional resistance at the
end subject to the increased vertical stress is offset by the decrease at the opposite
end. As a result the average frictional resistance is unaffected and thus the
derivation of the average frictional resistance remains appropriate.

Due to the length of the four brick wallets any end effects are also not apparent in
this test series.

A8 Add to Section 3.3.2last paragraph on page 42: Expected differential movements


associated with tirne dependant behaviour of URM walls including concrete
shrinkage or clay masonry expansion are generally in the order of around 3mm per
meter run of wall. This is dependant on ¡nany factors as has been briefly
discussed.

Tests associated with the time dependant movement of URM connections


containing DPC have recently been undertaken at the University of Newcastle,
New South Wales, Australia. These tests have highlighted that under shrinkage
creep the frictional resistance force appears to be less than under dynamic loading.
Consequently, the connections have been observed to slip undel the time
dependant forces but are less likely to slip under dynamic loading.

A9 Insert the following paragraph as the final paragraph on page 49:


It is widely recognised that vertical accelerations associatecl with seismic loading
may effectively reduce the gravitational force at the friction interface of DPC
connections. As a result, the frictional resistance and thus the shear resistive
capacity of the connection is also reduced. The SAA Masonry Code takes this
reduction into account in the derivation of the frictional resistance in Equation
3.4.1 by the application of the 0.9 factor applied to the gravitiational force. The
shear friction strength of the shear section under earthquake actions is thus defined
by
Vt" = 0.9 G,c k,

410 Page 55, last paragraph replace 'Although these four specimen tests were carried
out at only one value of vertical compressive stress (0.164MPa) both in-plane and
out-of-plane shaking were examined so that a total of eight tests were undertaken.'
'With 'Since each of the four standard and centered connection specimen where
tested at only one value of vertical compressive stress (0.164MPa) a total of eight
tests were undertaken.'

Page 57, first paragraph replace 'The slip joint tests were performed over a range
of three normal compression stresses being 0.04, 0.18 and 0.33 MPa conducted
only in the in-plane direction.'With 'The slip joint tests were performed over a
range of three normal compression stresses being 0.04, 0.I 8 and 0.33 MPa
conducted both in the in-plane and out-of-plane directions.'

All It is noted that the term 'overburden' used throughout the document may be more
commonly referred to as 'Pre-compression'.

Ã12 It is noted that in Section 6.3.1 the Characteristic bond strength should have been
calculated taking into account the specimen size. Also the standard deviation
values reported being based on three tests are relatively meaningless however are
provided as indicative for the quality of masonry.

413 Page 115 second paragraph replace 'The brickwork modulus was then calculated
for each specimen as the chold modulus between 57o and 33Vo of the ultimate
brickwork compressive strength, f',n.' with 'The brickwork modulus was then
calculated for each specimen as the chord modulus associated with the linear
portion of developed stress - strain curve.'

Page 115 last paragraph replace 'Table Ç3.2 presents a summary of the modulus
test results ranging from 3,300 MPa to 16,000 MPa for the l lOmm specimens and
6,'/00 MPa to 9,800 MPa for the 50mm specimens. While the results varied
significantly the modulus values were typically found to be relatively high as
expected of modern masonry.' With 'Table 6.3.2 presents a summary of the
modulus test results ranging from 4,000 MPa to 10,000 MPa for the l10mm
specimens and 5,000 MPa to 8,000 MPa for the 50mm specimens. It is suspected
that the large apparent variation in the brickwork modulus is due to
inconsistencies in the preparation of the five brick prisms. Here any slight
eccentricity of construction causes non uniform loading of he prism so that the
modulus calculation in some cases may have been slightly modified. The modulus
results attained however are provided typically the results are quite high as would
be expected of modern masonry.'
Replace Table 6.3.2Brickwork Modulus Test Results with
Table 6.3.2 Brickwork Modulus Test Results
Specimen No. Specimen Modulus Ultimate Compressive Masonry Compressi.ve
Thickness E- (MPa) Load (N) Strength, f'- (MPa)
l lOmm 330.000 13
2 l1Omm 10,000 332,000 13.1
J l1Omm 5.000 336,000 13.3
.l
4 I 0rnrn 4,000 333,000 13.1
5 llOmm 9,000 360,000 t4.2
6 llOmm 338,000 \3.4
1 l1Omm 9,000 313,000 t2.4
8 l10lnm 5,400 245,000 9.1
t1 l1Omm 8,000 359,000 14.2
t2 l1Omrn I 1,000 397,000 15.1
13 I lOlnm 397,000 15.1
AVERAGE 11Omm 7,700 339,000 13.4
STANDARD 2,500 47,528 1.64
DEVIATION

l0 50mm 8,000 307.000 26.1


14 50mm 5,000 303,000 26.3
AVERAGE 50mm 6.s00 305.000 26.5
STANDARD 2,Loo 2,824 0.28
DEVIATION
TABLE OF CONTENTS

TABLE OF CONTENTS ................ ll

LIST OF FIGURES vr

LIST OF TABLES xrl

ABSTRACT v

DECLARATION

ACKNOWLEDGMENT

1. INTRODUCTION.. 1

1.1. Study Objectives and Key Outcomes

l.2.Brief Outline of Report

2. EARTHQUAKES AND UNREINFORCED MASONRY

2. 1. lntroduction..........
2.2. Ausr: alian Seismicity ............
2.3.IJRM Building Stock in Australia
2.4. IJRM Vulnerability in Moderate Seismicity Regions .................
2.4.l.Fa1ture Modes of URM Elements (Related to Seismic Load Path)... ..20
2.4.2.Review of the Seismic Performance of URM Buildings ..21
2.4.3.Common URM Element Failure Modes .25
2.4.4.'Weak Link' URM Failure Modes ........ .29

2.5.'Capacity' Design for Improved Seismic Response 3l


2.6 Overall Project Aim..... 32

3. DPC CONNECTIONS IN IJRM CONSTRUCTION..... ......34

3. 1. Introduction.......... 34
3.2. General Friction Review 35
3.2.1. Coulomb Friction Behaviour ........., 35
3.2.1.1. Classically Behaving Materials 37

l1
TABLE OF CONTENTS

3.2.1.2. Polymers 37
3.3. LJRM Connection: Previous Research .........,....38
3.3.1. Plain-Masonry Joint Shear ..............38
3.3.2. Serviceability Requirements ........ '......,,.....41
3.3.3. Positive Anchorage............. ....,,,.......43
3.3.4. Shea¡ Resistance of URM Connection Containing DPC Membrane.... ,...,...44
3.4. Australian Code Provision: URM Connections ............ ...,,...48
3.5.Implication of the Dynamic Friction Coefficient ........50
3.6. Specific Research Focus ........50

DYNAMIC SHEAR CAPACITY TF^STS ON TJRM CONNECTION


4.
CONTAINING DAMP PROOF COTJRSE MEM8RAN8.............

4.1. Introduction...
4.2. Dynarmc Shear Tests..........
4.2.1. Instrumentation
4.2,2. D amp-Proof Course Membrane and Materials ................
4.2.3 . Dynamic Test Methodolo gy....................
4.2.4. DPC Connection Tests ................
4.2.5. Slip Joint Connection Tests...................
4.3. Results Formulation and Data Analysis....... 57
4.3.l.Data Filtering 58
4 .3 .2. Dynamic Friction Coefficient Representative Calculation 59
4.3.3. Theoretical Check 6l
4.4.Dynamic Test Results ....... 62
4.4.l.DPC Connection Dynamic Test Results ......... 62
4.4.2. Slip Joint Connection Dynamic Test Results.. 64
4.4.3. Comparison of Dynamic with Static and Quasi-Static Test Results ..... 67
4.5. Summary and Conclusion: Implication for Design. 68

5.STABILITY OF SIMPLY SUPPORTED IJRM lryALLS SUBJECTED TO


TRANSIENT OUT.OF-PLANE FORCES. ............69

5.1. Introduction .69


5.2. Fundamentals of Out-of-Plane URM WalI Behaviour....... ..70
5. 2. I . Post-cracked Force-Disp lace ment (F-A) Relationship
5.2.2. Boundary Condition Impact on Force-Displacement Relationship..
5 .2.3 . Un-cracked Force-Displacement Relationship ................
5.2.3.L. Low Applied Overburden Force
5.2.3.2. High Applied Overburden Force
5.3. Previous Research: Experimental Studies
5.3.1. Static Tests .........
5.3.2. Dynamic Tests...

lll
TABLE OF CONTENTS

5.4. Critical Review of Current Analysis Methodologies


5.4. 1 . Quasi-Static Analysis Procedures .92
5 .4.2. Dynamic Analysis Procedures ............... .97

5.5. Specific Research Focus 101

6. OUT-OF.PLANE SHAKE TABLE TESTING OF SIMPLY SUPPORTED IJRM


waLLS .............102

6. I . Introduction.......... 102
6.2. General Test Set Up ........... 103
6.2.1. Test Specimens ........... 103
6.2.2.Test Rig..... ...........105
6.2.3. Instrumentation ..... ,.......... 109

6.3. Material Tests... 111


6.3.1. Bond Wrench ......... rt2
6.3.2. Modulus of Elasticity...... lt4
6.3.3. Mortar Compressive Strength ............... tt7
6.4. Out-of-Plane Testing of Simply Supported URM Walls......... tt7
6.4.l.Data Filter.... 119
6.4.2. U n-cracked Natural Frequency of Vibration tt9
6.4.2.1. Comparison with Simple Elastic Beam Theory............ 120
6.4.3. Specimen Lateral Capacity Analysis 72r
6.4.4. Harmonic Excitation Tests 124
6.4.5. Static Push Tests 737
6.4.6. Free Vibration Tests ......... 142
6.4.6.1. Non-linear Frequency - Mid-Height Displacement Relationship 143
6.4.6.2. Non-linear Dynamic Force- Mid-Height Displacement Relationship..... t45
6.4.6.3 . Non-linea¡ Damping-Frequency Relationship ................ 149
6.4.7 . Transient Excitation Tests... 153
6.4.7.1. Pulse Tests r53
6.4.7 .2. Real Earthquake Excitation Tests 160

7. NON.LII\EAR TIME IIISTORY ANALYSIS D8V8LOPMENT.......................163

7. 1. Introduction............
7 .2.Brief Description of Basic Linear SDOF System ............164
7.3. Negative Stiffness System Modelled as a Basic Linear SDOF System....... .........167
7.4. Rigid Simply Supported Object Rocking Response About Mid-height - Dynamic
Equation of Motion.. ......... 169

7.5. Semi-rigid URM Loadbea¡ing Wall Dynamic Equation of Motion .....................174


7.6. Modelling of Non-LinearDamping............ ... 180

7.7.Event Based Time-Stepping 4na1ysis................ ............... 183

1V
TABLE OF CONTENTS

7.8. Comparison of Experimental and Analytical Results ..... 184

8. LTNEARTSED DTSPLACEMENT-BASED (DB) ANALYSTS ...........188

8. I . Linearised DB Analysis Methodology......... 188


8.2. Proposed Linearised DB Analysis.... 190
Stucture' Stiffness
8.2. I . Derivation of Characteristic SDOF' Substitute 192
8.2.2. Simply Supported llRM Walls Modelled as a SDOF Oscillaror.. 194
8.2.2.1. Modelled Displacement Capacity 194
8.2.2.2. Modelled Damping Appropriate During Rocking Response 195
8.3. Effectiveness of the Linearised DB 4na1ysis............... 195
8.3.1. Effective Resonant Frequency of Simply Supported URM Walls 197
8.3.2. Linearised DB Analysis 199
8.3.3. THA for Various Transient Excitation 200
8.3.4. Comparison of Predictive Model Results............... 202
8.4. Conclusion ..205

9. STTMMARY AND CONCLUSIONS 218

REFERENCES 221

APPENDIX (A): Band Pass Filter Program FortranTT Code 241

APPENDIX (B): Representative DPC Connection Test Results 247

APPENDIX (C): Representative Slip Joint Connecrion Test Results.............................251

APPENDIX (D): Rigid F-Â - Various Boundary Conditions 25s

APPENDIX (E): Material Test Resulrs 261

APPENDIX (F): Simply Supported Wall Test Results 275

APPENDIX (G): Non-linear Time History Analysis ROV/MANRY - ForhanTT Code3lg

APPENDIX (Itr): Non-linea¡ Time History Analysis Experimental Confirmation........339

v
LIST OF FIGURES

Figure 1.1.1 Depiction of Damage During the 62 AD Earthquake in Pompeii... 2

Fi gure 2.2.1 Aastralia's Tectonic l-ocation................. 11

Figure 2.3 .1 lnternal Partition'Wall' Cornice' Connection Detail....... 18

Figure 2.3.2 URM Cavity Wall to Roof Truss Connection Detail (Inner L¡adbearing)...18
Figure 2.3.3 LJRM Cavity Wall to Roof Truss Connection Detail (Outer Loadbearing)..19
Figure 2.3.4 tlRM Wall to Inter Story Floor Slab DPC Connection Detail.......................19
Figure 2.3.5 IJRM Wall to Ground Floor Slab DPC Connection Detail............................19
Figure 2.4.1 Seismic [,oad Path for Unreinforced Masonry Building.... .........21

Figure 2.4.2Parapet Failure, Tighes Hill Campus, Newcastle Technical College ............22
Earthquake
Figure 2.4.3 Masonry Damage During 1997 labalpar, India .......24

Figure 2.4.4Damage to URM Building, Tangshan, China, 1976........... .........29

Figure 3.1.1 Types of URM Connection Containing DPC Membranes.............................35


Figure 3.2.1Diagrammatic Representation: Frictional Resistance vs Applied Shear.......38
Figure 3.3.1 Shear Failure Hypothesis .41

Figure 3.3.2 Results of Typical Quasi-static on DPC Connection .47

Figure 4.2.1 Schematic URM Connection Containing DPC Dynamic Test Set-up ..........53
Figure 4.2.2Test Specimen Free Body Diagram: DPC Connection during Sliding.........55
Figure 4.2.3 Dynamic Test Set-up for Standa¡d/Centered DPC Connection.....................56
Figure 4.2.4Photograph of Standard DPC Connection Set up - In-plane.........................56
Figure 4.2.5 SchematicDiagram of Dynamic Test Set-up For Slip Joint Connection......57
Figure 4.3.1 Dominant Response Acceleration Frequencies................. ...........58

Figure 4.3.2Parabolic Sided Band Pass Filter - Bandwidth .59

Figure 4.3.3 Relative Connection Displacements .60

Figure 4.3.4 Response Acceleration above Slip Interface during Slipping..... .60

Figure 4.3.5 Hysteresis Behaviour after Slip showing Maximum Shear Resistive Force.60

V1
LIST OF FIGURES

Figure 4.4.1 Graphical Results Summary for Standard DPC Connection Tests.......... ......62
Figure 4.4.2 Grapbical Results Summary for Centered DPC Connection Tests.......... ......63
Figure 4.4.3 Out-of-plane Slip Joint - I Layer of Standard Alcor .. 65
Figure 4.4.4 Out-of-plane Slip Joint Test - 2Layers of Standard Alcor............................65
Figure 4.4.5 Out-of-plane Slip Joint Test - 2Layers of Greased Galvanised Steel.......... 65
Figure 4.4.6Ln-plane Slip Joint Test Results - I Layer of Standard Alcor. 66
Figure 4.4.7 ln-plane Slip Joint Test Results -2Layers of Standa¡d Alcor 66
Figure 4.4.8 In-plane Slip Joint Test Results -2[-ayers of Greased Galvanised Steel 66

Figure 5.1.1 Out-of-plane \ilall Failure during Loma Prieta Earthquake, 1989................70
Figure 5.2. 1 Real Semi-rigid Non-linear Force-Displacement Relationship 74
Figure 5 .2.2 P ost-cr acked Frequency-Displace ment Relationship ... .... 78
Figure 5.2.3Un-cracked F-À for Low Applied Overburden Sftess URM Wall 82
Figure 5.2.4Un-cracked F-À for High Applied Overburden Stress URM Wa11................83
Figure 5.3.1 Comparison of Yokel Study with Simple Rigid Body Theory......................85
Figure 5.3.2 Typical Lateral Failure of Brick V/all .......... .............85
Figure 5.3.3 Comparison of West etal1973 Tests with Simple Rigid Body Theory.......87
Figure 5.3.4 Top of Parapet Wall Disp. Correlated to Table Velocity and Acceleration..gl
Figure 5.3.5 Top of Parapet Wall Disp. Conelated to Table Disp........... ........91
Figure 5.4.1 Quasi-Static Linear Elastic Design Methodology............... .........94
Fi gure 5 .4.2 Expenmental and An alytical F-AComp ari son 96
Figure 5.4.3 Compa¡ison of Analysis Predictions....... 99

Figure 6.2.1 Standard Three Hole Extruded Clay Brick (110mm) 104
Figure 6.2.2 Constuction of URM Wall Panels ................... 105
Figure 6.2.3Top 'Cornice' Support Connection 106
Figure 6.2.4 Out-of-plane Test Rig 707
Figure 6.2.5 Overburden Rig............ 107
Figure 6.2.6Top Vertical Reaction - Overburden Test Rig 108
Figure 6.2.7 Out-of-plane Wall Test Instrumentation Locations ................... 109
Figure 6.3.1 Bond Wrench Apparatus Dimensions (1lOmm Brick).............. 113
Figure 6.3.2 Bond Wrench Test Set Up 113

vl1
LIST OF FIGURES

Figure 6.3.3 Five Brick Prism at Ultimate Compressive Load 115

Figure 6.4.1Un-cracked Natural Frequency of Vibration 50mm Non-loadbearing Wall120


Figure 6.4.2 Cunent Available Analysis Comparison - 11Omm Thick WaII.......... .......I22
Figure 6.4.3 Current Available Analysis Comparison - 110mm Thick WaII.......... .......122
Figure 6.4.4Un-cracked Non-loadbearing URM Wall Ha¡monic Excitation Test ........129
Figure 6.4.5 Pre-cracked Non-loadbearing URM Wall Harmonic Excitation Test........ 130
Figure 6.4.6 Un-cracked Non-loadbearing URM Wall Harmonic Excitation Test ........134
Figure 6.4.7 Un-cracked Non-loadbearing URM V/all - First Cracking........................ 135

Figure 6.4.8 Un-cracked Non-loadbearing URM Wall - First Rocking 135

Figure 6.4.9 Static Push Test 137

Figure 6.4.10 Comparison of 11Omm Specimen Static Push F-A with Analytical......... 139
Figure 6.4.11Comparison of 50mm Specimen Static Push F-A with Anal¡ical........... 140
Condition............
Figure 6.4.12 Mid-height Rotation Joint ........l4l
Figure 6.4.13 Free Vibration Calculation............ ....143
Figure 6.4.14 50mm Specimen Frequency vs Average Cycle Mid-Height Disp............144
Figure 6.4.15 110mm Specimen Frequency vs Average Cycle Mid-Height Disp. ........145
Figure 6.4.t6 50mm Wall Dynamic F-A Relationships (Various Overburden)..............147
Figure 6.4.17 110mm Wall Dynamic F-Â Relationship................ ................147

Figure 6.4.18 50mm Wall Compa¡ison of Static and Dynamic F-Â Relationships........ 148
Figure 6.4.19 110mm Wall Comparison of Static and Dynamic F-A Relationship........ 149
Figure 6.4.20 50mm Wall Non-linear ( vs Frequency (Various Overburden)............... 150
Figure 6.4.2150mm Wall Non-linear Cs¡,op/ùI" vs Frequency (Various Overburden) . 151
Figure 6.4.22 Non-loadbearing 11Omm Wall Non-linear ( vs Frequency............... ......I52
Figure 6.4.23 Nonloadbearing 50mm and 110mm'Wall Csr,oe/lVl, vs Frequency ........152
Figure 6.4.24 0.5H2 Normalized Gaussian Displacement Pulse Input.... r54
Fi gure 6.4.25 Correspondin g Acce leration Input. 154
Figure 6.4.26 Effective Resonant Frequency (By Wall Thickness and Overburden) .... 159

Figure 7 .2.t Basic Linear SDOF System.............. 165

Figure 7.3.1 Negative Stiffness F-Â Relationship 167

Figure 7.4.1 Non-loadbearing Simply Supported Object at Rocking at Mid-height...... 171


Figure 7.5.1 Tri-tinear 'Semi-rigid' Non-linear F-Â Relationship Approximation........ 175

vlll
LIST OF FIGURES

Figure 7.5.2Tri-ltnear F-A Approximation for Va¡ious V/all Degradation 176


Figure 7.5.3 Analytical vs Experimental F-A- 11Omm, No Overburden........... 178
Figure 7.5.4 Analytical vs Experimental F-Â- 50mm, No Overburden........... 179
Figure 7.5.5 Analytical vs Experimental F-A- 50mm, 0.07MPa Overburden 179
Figure 7.5.6 Analytical vs Experimental F-Â- 50mm, 0.15MPa Overburden 779
Figure 7.6.1 Experimental I vs Rayleigh 6 - 50mm \ù/all, No Applied overburden..... 181
Figure 7 .6.2 lterative Damping 182
Figure 7.7.1 'Pseudo Static' F-A relationship 183
Figure 7.8.1 Comparison of Analytical and Experimental Pulse Test Results ............... 185
Figure 7.8.2 THA and Experimental Peak Pulse Mid-height Disp. Response................ 186
Figure 7.8.3 Comparison of Analytical and Experimental Earthquake Test Results ..... 187

Figure 8.1.1 Linearised DB Analysis for Elastic Perfectly Plastic System..................... 189
Figure 8.2.1 Typical Elastic Displacement Response Spectrum ................... 191
Figure 8.2.2Linearised DB Analysis Characteristic Stiffness, IÇ6 193
Figure 8.3.1Gaussian Pulse: 3.3m Tall, 110mm Thick, Moderate Degradation THA ... 198
Figure 8.3.2 Relative ElCent¡o Earthquake Elastic Response Specftum (3Vo damping) 200
Figure 8.3.3 THA ElCentro Earthquake: 1.5m Tall, Moderate Degradation.......... ........201
Figure 8.3.4 ElCentro Earthquake: 3.3m Tall, Moderate Degradation............................ 201
Figure 8.3.5 ElCentro Earthquake: 4.0m Tall, Moderate Degradation............................202
Figure 8.3.6 Comparison of DB Analysis and THA Ultimate Instability Prediction .....203
Figure 8.3.7 R*(1) vs THA Ultimate Instability Prediction. ......204
Figure 8.3.8 'Quasi-static' Rigid Body vs THA Ultimate Instability Prediction...........205

APPENDICIES
Figure B 1 - Standard DPC Connection One Layer of Standard 41cor...........................247
Figure B 2 - Standard DPC Connection One Layer of Super 41cor......... ....248
Figure B 3 - Standard DPC Connection One Layer of Polyflash ................ ....................249
Figure B 4 - Standard DPC Connection One Layer of Dry-Cor (Embossed Potythene) 250

Figure C 1- Slip Joint Two layers of Standard Alcor ....... 251


Figure C 2- Slip Joint One layer of Standa¡d 41cor.......... 252

lx
LIST OF FIGURES

Figure C 3- Slip Joint Two layers of Greased Galvanised Steel.......... 253


Figure C 4- Slip Joint One layer of Embossed Polythene (Dry-Cor) 254

Figure D 1 - Concrete Slab with DPC Connection Above........ 255


Figure D 2 - Rigid F-Â Relationship- Top Vertical Reaction at læeward Face.............257
Figure D 3 - Timber Top Plate Above............ 258
Figure D 4 - Rigid F-Â Relationship- Top Vertical Reaction at Centerline ................ ...260

Figure E 1 - Bond Vy'rench Calibration Plot 110mm Brick Specimen Bond Wrench....26l
Figure E 2- Bond Wrench Calibration Plot 50mm Brick Specimen Bond'Wrench.......26l

Figure F 1- Static Push Test - Un-cracked, 11Omm, No Overburden .........275


Figure F 2- Static Push Test - Un-cracked, 11Omm, 0.15MPa Overburden ..................275
FigureF3-StaticPushTest-Cracked, 0.l5MPaOverburden ....,276
11Omm,

Figure F 4- Static Push Test - Cracked, 50mm, No Overburden ........... ......276


Figure F 5 - Static Push Test - Un-cracked, 50mm, 0.075MPa Overburden ..................277
Figure F 6- Static Push Test - Cracked, 50mm, 0.075 Overburden .............277
Figure F 7- Static Push Test - Cracked, 11Omm, No Overburden ........... ....278
Figure F 8 - Static Push Test - Un-cracked, 110mm, 0.15MPa Overburden ..................278
Figure F 9 - Static Push Test - UN-cracked, 11Omm, No Overburden........... ................279
Figure F 10- Static Push Test - Cracked, 110mm, No Overburden 279
Figure F 11- Static Push Test - Un-cracked, 1lOmm, No Overburden........................... 280
Figure F 12- Static Push Test (Hysteretic) - Cracked, 110mm, No Overburden ........... 280
Figure F 13- September9S Specimen 13 - Resonant Energy l¡ss Per Cycle 281
Figure F 14 - Static Push Test - Un-cracked, 11Omm, No Overburden.......... 282
Figure F 15 - Static Push Test - Cracked, 50mm, 0.15MPa Overburden....... 282
Figure F 16 - Release Test (1) - 50mm, No Overburden........... 283
Figure F 17 - Release Test (2) - 50mm, No Overburden........... 284
Figure F 18 - Release Test (3) - 50mm, 0.075MPa Overburden 285
Figure F 19 - Release Test (4) - 11Omm, No Overburden........... 286
Figure F 20 - Release Test (5) - 110mm, No Overburden 287
Figure F 2l - Release Test (6) - 110mm, No Ove¡burden..................... 288

x
LIST OF FIGURES

Figure F 22 - 0.5H2 Half Sine Displacement Pulse, 50mm, No Overburden ........... ......289
Figure F 23- 7.0HzHalf Sine Displacement Pulse, 50mm, No Overburden............. .....29O
Figure F 24 - 2.OHzHalf Sine Displacement Pulse, 50mm, No Overburden ........... ......291
Figure F 25 - 0.5H2 Half Sine Displacement Pulse, 50mm, 0.075MPa Overburden .....292
Figure F 26- 1.0H2 Half Sine Displacement Pulse, 50mm, 0.075MPa Overburden .....293
Figure F 27 - Z.OHz Half Sine Displacement Pulse, 50mm, 0.075MPa Overburden .....294
Figure F 28- 3.OHz Half Sine Displacement Pulse, 50mm, 0.075MPa Overburden ....295
Figure F 29- 0.5}l2 Half Sine Displacement Pulse, 50mm, 0.l5MPa Overburden ........296
Figure F 30- 1.0H2 Half Sine Displacement Pulse, 50mm, 0.15MPa Overburden........297
Figure F 31 - 2.0}J.2 Half Sine Displacement Pulse, 50nim, 0.15MPa Overburden .......298
Figure F 32- 2.OHz Half Sine Displacement Pulse, 50mm, 0.15MPa Overburden ........299
Figure F 33- 1.0H2 Half Sine Displacement Pulse, 110mm, No Overburden ................ 300
Figure F 34- l.0Hz Half Sine Displacement Pulse, 11Omm, No Overburden ................ 301
Figure F 35- 2.0}{2 Half Sine Displacement Pulse, 11Omm, No Overburden ........... .....302
Figure F 36- 1.0H2 Gaussian Displacement Pulse, 11Omm, No Overburden................. 303
FigureF3T-l.O}lzGaussianDisplacementPulse, 110mm,NoOverburden.................304
Figure F 38- 1.0H2 Gaussian Displacement Pulse, 11Omm, No Overburden................. 305
Figure F 39- 1.0H2 Gaussian Displacement Pulse, 11Omm, No Overburden................. 306
Figure F 40- 0.5H2 Gaussian Displacement Pulse, 11Omm, No Overburden........... .....307
Figure F 4l- 0.5H2 Gaussian Displacement Pulse, 11Omm, No Overburden................. 308
Figure F 42- 0.5}{2 Gaussian Displacement Pulse, I 10mm, No Overburden................. 309
Figure F 43- Transient Excitation Test - 66VoF,lcenfto, 11Omm, No Overburden........ 310
Figure F 44 - Transient Excitation Test - l00Vo Nahanni, I 10mm, No Overburden...... 31 1

Figure F 45- Transient Excitation Test - 200Vo Nahanni, 1 10mm, No Overburden.......3l2


Figure F 46 - Transient Excitation Test - 300Vo Nahanni, 110mm, No Overburden......3l3
Figure F 47 - Transient Excitation Test - 400Vo Nahanni, I 10mm, No Overburden...... 3 14
Figure F 48 - Transient Excitation Test - 66VoElCentro, 11Omm, No Overburden...... 315
Figure F 49- Transient Excitation Test - 66Vo Pacoima Dam, 110mm, No Overburden3l6
Figure F 50- Transient Excitation Test - 80Vo Pacoima Dam, 1 10mm, No Overburd en3l7
FigureF5l -TransientExcitationTest- lÙOVo PacoimaDam, llOmm,NoOverburden
318

xl
LIST OF TABLES

Table 3.3.1 DPC Connection Static Friction Coefficient Summary (Page 1994)..............46
Table 3.3.2 Slip Joint Connection Static Friction Coefficient Summary (Page 1994)......46

Table 4.2.lDPC Membrane Test Specimens .54

Table 4.4.1 Results Summary for Standard DPC Connection Tests... .62

Table 4.4.2 Results Summary for Centered DPC Connection Tests .......... .63

Table 4.4.3 Standard DPC Connection Friction Coefficient Comparison .67

Table 4.4.4 Slip Joint Connection Friction Coefficient Comparison .67

Table 5.2.1 Rigid Bi-Linear F-A Relationship - Various Boundary Conditions 80

Table 6.2. 1 Out-of-plane'Wall Test Instrumentation Description 110

Table 6.3.1 Bond \ürench Test Results Summary tt4


Table 6.3.2 Brickwork Modulus Test Results 116

Table 6.4.1 Experimental Phase Test Program 118

Table 6.4.2 Analysis of Test Specimen 124


Table 6.4.3 llOmm'Wall, Non-loadbearing - Harmonic Excitation Test Results....... t3r
Table 6.4.411Omm Wall, 0.15MPa - Harmonic Excitation Test Results............. ......136
Table 6.4.5 Result Summary of Static Push Tests ...... 138

Table 6.4.6 Summary of Release Test Results ......t43


Table 6.4.7 Summary of Key Pulse Test Results (50mm Walls)........ ...... 155

Table 6.4.8 Summary of Key Pulse Test Results (110mm Walls)........ ......157
Table 6 .4.9 Earthquake Excitation Descripti on ...... 161

Table ó.4.10 Summary of Key Earthquake Excitation Test Results (50mm Walls) ......162
Table 6.4.71Summary of Key Earthquake Excitation Test Results (110mm Walls ) ....162

Table 7.5.1 Dehning Displacements of the Tri-linea¡ F-A Approximation t76

xll
LIST OF TABLES

Table 8.4.1 ElCentro Analysis Comparison: 1.5m Height Wall 206


Table 8.4.2 ElCentro Analysis Comparison: 3.3m Height Wall 207
Table 8.4.3 ElCentro Analysis Comparison: 4.0m Height Wall ....208
Table 8.4.4Taft Analysis Comparison: 1.5m Height V/aII........ ....209
Table 8.4.5 Taft Analysis Comparison: 3.3m Height V/all........ ....210
Table 8.4.6 Taft Analysis Comparison: 4.0m Height WaII........ ,...211
Table 8.4.7 Pacoima Dam Analysis Comparison: 1.5m Height Wall ....212
Table 8.4.8 Pacoima Dam Analysis Comparison: 3.3m Height V/all ....213
Table 8.4.9 Pacoima Dam Analysis Comparison: 4.0m Height Wall ....... ....274
Table 8.4.10 Nahanni Analysis Comparison: 1.5m Height Wa1I............... ....215
Table 8.4.11 Nahanni Analysis Comparison: 3.3m Height WaII............... 216
Table 8.4.12 Nahanni Analysis Comparison: 4.0m Height WaII............... 217

xllt
ABSTRACT

A large proportion of domestic and low rise building stock in Australia is of unreinforced
masonry (URM) construction and has not been designed to resist earthquake loads.
Previous researchers have identifred that under current Australian design conditions the
two predominant weak links in the seismic load path for URM buildings are the shear
connections between the walls and floor or roof and out-of-plane wall flexure.

This report documents the experimental and analytical research undertaken at The
University of Adelaide aimed at providing the fundamental tools required to successfully
avoid the identified brittle 'weak link' failures in the design of new and the assessment of
existing URM buildings. This was achieved for the DPC connections through an
extensive series of shaking table tests, which provided realistic data on the dynamic
capacity of these connections. For the out-of-plane failure of walls in the upper stories of
URM buildings, an extensive series of shaking table tests was used to develop a botter
understanding of the physical processes governing the collapse behaviour. Following this
realistic anal¡ical models were developed to provide accurate and reliable assessment of
actual wall capacities. Since these were necessarily complex, a further refinement was
undertaken to produce a more simplistic but rational analysis procedure for practical
applications based on the 'Displacement-based' failure criteria.

xlv
DECLARATION

This thesis contains no material which has been accepted for the award of any other
degree or diploma in any university or other tertiary institution and, to the best of my
knowledge and belief, contains no material previously published or written by another
person, except where due reference is made in the text.

I give consent to this copy of my thesis, when deposited in the University Library, being
made available for loan or photocopying.

Kevin Thomas Doherty Dare '2a lS lo-

xv
ACKNOWLEDGMENT

I would firstly like to recognise the contributions made throughout the duration of this
project by Associate Professor Mike Griffith of The University of Adelaide as his
foresight and direction \Mas largely responsible for the conception and success of this
project. I am also indebted to my collaborative researchers, Dr. Nelson Lam and Dr. John
V/ilson of The University of Melbourne for valuable research meetings, ideas and

discussions. I would also like to acknowledge the exceptional technical assistance


provided by the Laboratory staff at the Chapman Structural Testing Laboratory at The
University of Adelaide under the supervision of Mr. Greg Atkins.

Funding for this project was provided through an Australian Research Council grant as

well as a University of Adelaide Postgraduate Scholarship Award for which I am


appreciative.

I would also like to express my sincerest appreciation to my Mother and Father, Joan and
Lindsay Doherty for their guidance and encouragement throughout both my under- and
post-graduate careers. My Father, whom also being a structural engineer has spent many

nights discussing with me issues related to structural and earthquake engineering


providing me with motivation to succeed in my professional endeavors. Finally,I would
like to acknowledge the contribution of my Fiancée Tammie. For her endless tolerance
and support I am eternally indebted. The supports of these exceptional people have
provided me with the inspiration and resolve to undertake this project for which I am
extremely grateful.

XVI
I.. INTRODUCTION

From the time of earliest civilisation, the use of masonry has provided a successful
building technique. Examples of early stone masonry construction can be found dating as

far back as c. 9000 BC in Israel and to the better known pyramids of Egypt constructed

- 2000 BC. Later, along with the emergent Roman Empire in around 700
around c. 2800
BC, the use of masonry became widespread. Notable cities were established and
developed throughout the colony comprising elaborate masonry palaces, churches,
bridges and aqueducts. Over the centuries significant advancements have been made in
the processes of masoffy construction and to this day world cities have substantial
building stock comprised of unreinforced masonry (LJRM).

The main characteristics of masoffy that have enabled it to endure as a building medium
through the ages are both the simplicity of laying stones or bricks on top of one another
and the ready availability of materials and labour. Aesthetically, masoffy is available in

a vast array of colour and texture. Due to the small modular size of bricks and blocks it is
also extremely versatile in application in that it can be used to form a great variety of
shapes and sizes of walls, piers, arches, domes or chimneys. Furthermore masonry's
exceptional fire resistance prompted Charles II to insist that all buildings built after the
1666 Great Fire of t¡ndon be constructed of brick or stone. Durability, sound insulation

and thermal mass are other advantageous characteristics of masonry construction.

In contrast, from its very foundation, the intrinsic drawback of masonry construction has
been its poor seismic performance. While recent earthquakes have heightened modern

awareness of this problem (Benuska 1990, Page 1990, Somers 1994, Pham 1995,
Bruneau 1996, Spence 1999, Alcocer 1999,Pujol 1999) it is also evident that the problem
existed even from the early days of the Roman Empire (Dobbins 1994). One remarkable
example was the city of Pompeii. l,ocated near the Bay of Naples in ltaly, Pompeii,

1
CHAPTER ( I ) - Introduction

having been incorporated as a Roman Colony in 808C, had an estimated population of


between 8,000 and 12,000 people. It is believed that the final years of the city were
framed by two natural disasters. The first \ryas a devastating earthquake in 62 AD which
caused considerable damage to the city's masonry infrastructure requiring large scale
rebuilding. The second, a cataclysmic eruption of Mount Versuvius 17 years later,
desfroyed Pompeii and the neighboring city of Herculaneum. The eruption of 79 AD is
significant here as the resulting ash layer preserved much of the evidence of the
earthquake damage that would have otherwise been obscured had Pompeii endured
throughout antiquity. Figure 1.1.1 shows an ancient depiction taken from the house of
Lucius Caecilius Iucundus of damage to the Temple of Jupiter and The Arch of Triumph
at Pompeii during the 62 AD earthquake.

Figure 1.1.1 Depiction of Damage During the 62 AD Earthquake in pompeü


(Kozak Collection, Earthquake Engineering Research Center, University of Califomia, Berkeley)

Unlike modern steel and reinforced concrete construction it is clear that the development
of masonry construction followed a different path. Throughout history, forms of
structural masonry passed from generation to generation and evolved from trial and error
as opposed to that of specialised research. As a consequence, methods have tended to be

less sophisticated and more empirically based with generally little if any consideration

2
CHAPTER (l) - Intoduction

given to seismic action until comparatively recently. These buildings have thus tended to
be at greater seismic risk than comparable new buildings. This is not only because they
have not been designed for seismic loading requirements but also because they are less
capable of dissipating energy through large inelastic deformations during an earthquake.

Historically this has resulted in an abundance of seismically induced catastrophic


masonry failures often with a high loss of life. For example 50 years ago it was

customary to support floors on stone or masonry corbels. During an earthquake the floor
and walls would vibrate typically eventuating in the floor slipping from the corbel and
collapsing dramatically.

In response to the observed damage to un-engineered or poorly constructed buildings,


public prejudice developed against the use of structural URM. A consequence has been
its disappearance from modern construction in regions of high seismicity with a

respective increase in the popularity of steel and concrete construction. Owing to this
shift in focus comparatively little research has been undertaken on the ultimate dynamic
behaviour of URM construction.

Although the performance of URM buildings when subjected to earthquake excitation


has typically been poor there is also signif,rcant evidence suggesting that these buildings

do not necessarily perform poorly in areas of low to moderate seismicity (Scrivener 1993,
Tomazevic and lùy'eiss 1994, Abrams 1995). This was highlighted in 1989 in Australia by
the Mr5.6 Newcastle eafthquake. Here it was reported (Melchers 1990, Griffith 1991,
Page 1992, Murphy 1993) that while older masonry buildings, typically in poor condition

and not having been designed with any consideration to lateral loading, suffered
significant damage, many other masonry buildings performed well suffering only minor
or no damage at all. These findings have placed an increased pressure on engineers in
regions of low to moderate seismicity to continue taking advantage of the significant
beneficial characteristics of masonry construction by designing and detailing URM
buildings to perform adequately during an earthquake.

3
CHAPTER ( I ) - Introduction

The current URM research focus is therefore twofold. Firstly, there is a need to
rationalise the design of new URM buildings for regions of low to moderate seismicity.
This involves the identification of weaknesses in masonry construction practices and
correlating these to observed catastrophic failures. Consequent development and
implementation of design guidelines would then prevent future occurrences of similar
brittle failures occurring in newly designed structures.

Secondly, there is a need to assess the seismic vulnerability of the large numbers of URM

building stock of unknown quality and condition in cities around the world. These
structures were generally constructed prior to mandatory earthquake design requirements

and due to the sporadic nature of earthquake loading many remain untested against
seismic action. Earthquakes have repeatedly impressed the need to review the seismic
adequacy of existing masonry buildings. As a recent example historically significant
structures in Italy, having stood for hundreds of years, have failed dramatically under
seismic loading. These failures clearly illustrate the potential risk in assuming age-old
structures will last forever and the possible physical and social consequence of inaction.
With these constant reminders owners are now recognising that they must reconcile the
potential for structural retrofitting with the level of seismic risk.

The distinction is drawn between the development of analysis and design procedures for
new and existing buildings since for the design of a new building a ceftain degree of
conservatism may impose only a minor economic penalty. In contrast, the same degree
of conservatism for the review of an existing structure may impose substantial economic
penalty and hence cross the line of being economically viable to seismically retrofit.
Should the imposed economic penalty be deemed too great historically or socially
significant structures could be lost.

The research challenge therefore lay in establishing a better understanding of the physical
processes governing the collapse behaviour thus permitting the development of realistic,

accurate assessment methodologies for the determination of the dynamic capacity of


URM buildings and their constituent components.

4
CHAPTER (1 ) - Introduction

1.1. Study Objectives and Key Outcomes

The specific focus of the current research project was an investigation of the brittle 'weak
links' in the seismic load path for Australian URM buildings under earthquake loading.
As is discussed in more detail in Chapter (2) the 'weak links' are evident through the
review of damage surveillance documentation and have been confirmed through an

analytical study (Klopp 1998) as:

( 1) The limited force capacity of connections between floors and walls, in particular the
friction dependent connections containing damp proof course (DPC) membranes and

(2) the out-of-plane failure of walls in the upper stories of URM buildings.

The primary intention of the cunent project \Mas therefore to provide the fundamental
tools required to successfully avoid the identified brittle 'weak link' failures in the design
of new and the assessment of existing tlRM buildings. This was achieved for the DPC
connections through an extensive series of shaking table tests, which provided realistic
data on the dynamic capacity of these connections. For the out-of-plane failure of walls
in the upper stories of URM buildings, an extensive series of shaking table tests was used
to develop a better understanding of the physical processes governing the collapse
behaviour. Following this realistic analytical models were developed to provide accurate
and reliable assessment of actual wall capacities. Since these were necessarily complex,

a further refinement was undertaken to produce a more simplistic but rational analysis
procedure for practical applications. To encourage the ready introduction and acceptance

into the real design environment, where optimisation of design output is often the driving
force, it was necessary that the simplihed procedure be formulated through easily
understood and familiar concepts while still encompassing the essential ingredients of the

dynamic behaviour.

Since a building's structural capacity is related to its weakest link, by avoiding the
identif,red brittle 'weak link' failure modes the overall effective structural capacity and

thus seismic performance will improve. An additional beneht is that with a better

5
CHAPTER ( I ) - Introduction

understanding of the physical process governing the dynamic collapse behaviour,


designers will more readily be able to adopt the desirable 'Capacity' type design
approach discussed further in Chapter (2). Where this enables more ductile failure modes
to be activated, the structure's effective capacity and energy dissipating characteristics
will be further enhanced.

Although specifically related to Australian construction practices and conditions, it is


expected that these research outcomes are sufficiently general so that they will be easily
extrapolated to other regions of similar seismicity and construction techniques.

1.2. Brief Outline of Report


To set the overall scene a general overview of earthquakes and URM is presented in
Chapter (2) where the basic aspects of seismicity and URM performance, both
internationally and in Australia are covered. Following this, a brief review of the
development of seismic design criteria and URM construction practices in Australia are
presented as these dictate the standard of the existing URM buitding stock. This includes

the results of a survey performed as part of the current research project to catalogue
typical URM wall connections and levels of applied overburden stress based on
Australian masonry construction. A review of the vulnerability of LJRM failure modes
from reconnaissance documentation is then presented to conñrm the typical weak link
URM failure patterns in areas of moderate intensity shaking.

Chapters (3) and (4) are devoted to the shear capacity of URM connections containing
DPC membranes being, the first of the previously identified weak links. Chapter (3)
commences with a general description of connections containing DPC membranes. A
specihc literature survey covering previous experimental and related work is then
presented. Chapter (3) concludes with the specific research requirement to be undertaken

within the scope of this project being the experimental dete¡mination of dynamic friction
data for DPC connections typically used in Australian masonry construction.

6
CHAPTER ( I ) - Introduction

Chapter (4) presents the results of a series of dynamic friction tests for DPC connections.
Here the experimentally determined dynamic friction coefficients ¿re compared with
static test results (Page 1995, Griffith et al 1998) for connections of the same
configuration and concludes with recommendations on the suitability of current codified
friction coefficients.

Chapters (5) to (8) are devoted to the out-of-plane failure of walls in the upper stories of
URM buildings being the second of the weak links to be investigated. This is specifically
related to the dynamic stability of simply supported tlRM walls subjected to transient
out-of-plane forces.

Chapter (5) introduces the physical considerations that must be assessed for out-of-plane
analysis including boundary conditions and dynamic stabilising effects. Following this a

specific literature review is presented which hightights key aspects of previous related
experimental and analytical work. Further to the literature review a critical assessment of
currently available analysis and design methodologies for face-loaded URM walls under
one-way bending action subjected to transient excitations is presented. Here it is found
that the existing methods have serious limitations for the realistic prediction of the
ultimate dynamic wall capacity.

In Chapter (6) the key results of an extensive series of static push and shaking table tests
on simply supported face loaded LJRM walls are presented. Here the results of static,
impulse and free vibration tests are used to examine the non-linear force-displacement (F-

Â), frequency-displacement (fA) and damping characteristics of URM walls. Harmonic


and transient excitations are also used to examine the dynamic response at various
excitation frequency and amplitude content and for later confirmation of the

comprehensive analytical model.

Chapter (7) describes the development of a comprehensive analytical model for the semi-
rigid rocking response of post cracked URM walls subjected to out-of-plane forces. The
computer software ROWMANRY, developed as part of the current research project to

7
CHAPTER (l) - Introduction

the highly non-linear time-history analysis (THA), is also presented. Results of


experimental work as described in Chapter (6) are then used to calibrate and confirm the
accuracy of the analytical results.

In Chapter (8) a rational simplistic displacement-based (DB) analysis procedure is


presented for the prediction of the ultimate capacity of face loaded URM walls. A brief
description of the displacement-based design methodology is provided and followed by
key aspects as it is applied to rocking URM walls. In order to confirm the effectiveness
of the linearised DB analysis, comparisons with experimental and comprehensive TFIA
results are presented. Similar comparisons are also made with currently available
ultimate analysis methodologies where it is concluded that the linea¡ised DB
methodology provides the most effective estimate of ultimate wall capacity.

Chapter (9) summarises the results of the study, highlighting key outcomes, design
recommendations and future research requirements.

8
2. EARTHQUAKES AND UNREINFORCEI)
MASONRY

2.1. Introduction

Earthquakes pose a substantial threat to life with an average fatality rate this century of
around 10,000 deaths per year (McCue t992). Damage to unreinforced masonry (uRM)
buildings and elements is a ubiquitous aspect of many earthquakes and as such URM has
a poor seismic performance record throughout the world. It has been reported (Scrivener

1993), however, that the poor overall public perception of URM can generally be
attributed to media reports not mentioning typical causes of the failures such as:
- buildings not designed to any engineering code, let alone an earthquake code;
- poorly constructed of adobe, mud brick or weak clay bricks with weak mortar of
mud or earth or with insufficient cement; and

- un-connected structural elements often with heavy roofs

In many instances the damage level has been enormous with masonry littering streets and
in larger earthquakes the complete collapse of URM buildings. This severe damage has

often been responsible for a non-commensurable loss of life and injury during
earthquake, which is both unacceptable and unnecessary. The spectacular nature of the

damage has therefore tended to obscure the satisfactory performance of many other URM

buildings in earthquakes. This is supported by research (Griffrth 1991, Page 1992,


Schrivener 1993, Tomazevic and \ileiss 1994, Abrarns 1995) indicating that URM
buildings can satisfactorily withstand moderate levels of ground shaking if designed,

detailed and constructed with consideration to seismic loading.

This Chapter provides a general overview of the seismicity, URM construction and

seismic performance in Australia. Aspects which are applicable for Australian conditions

are clarified and vulnerable weak links in URM buildings designed to current practices

9
CHAPTER (2) - Earthquakes and Unreinforced Masonry

are identified. To quantify the performance of IJRM buildings in areas of moderate


seismicity, a summary of observed damage patterns for Australian and relevant
international earthquakes is presented. This section concludes with the specific research
focus to be addressed within the scope of this report.

2.2. A¡ustralian Seismicity


While it is possible for an earthquake to occur at any location their occurrence frequency
is unevenly distributed over the earth. The majority of earthquakes are found to occur
along relatively narrow continuous belts at the convergent boundaries of the major crustal
plates. Here, inter-plate earthquakes contribute more than 90Vo of the earth's release of
seismic energy (Bolt 1996) with the remaining released as interior or intra-plate type
events. Further, approximately 75Vo of the total energy release is believed to occur along
the edges of the Pacific ocean, where the thinner Pacific plate is being forced beneath the

thicker continental crust (BGS 1999). This is demonstrated in active inter-plate regions
such as Japan, California or Papua New Guinea where the major plates interact at
velocities of up to 100 mm/year. As a consequence, it can take only tens to hundreds of
years for sufficient strain energy to build culminating in the release of a large magnitude

earthquake. In contrast, for an intra-plate region it may take hundreds of thousands of


years for similar levels of compressive stress and strain energy to develop. Thus, due to

the paucity of records this type of event is far more difficult to forecast.

The long return period of major earthquakes and the absence of interim perceptible
seismic activity in intra-plate regions has led to these areas being referred to as being of
low seismicity or low seismic risk. A common misconception follows that this infers
weak ground motion while the reality is that strong ground motion can still occur but less
frequently. In probabilistic terms there is a much reduced likelihood of intra-plate strong
ground motion occurring at a particular time and place than inter-plate. This aspect
substantially impacts on building code provisions where the design basis event is
prescribed in probabilistic terms, rather than on maximum earthquake potential. Thus for

l0
CHAPTER (2) - Earthquakes and Unreinforced Masonry

intra-plate regions the design event magnitude will be smaller than for inter-plate regions
(Somerville et al 1998).

The ea¡liest earthquake reported in Australia was in June 1788 at Port Jackson (Sydney)
where the First Fleet settlers were shaken by a strong local earthquake lasting for not
more than two or three seconds. Since this time small earthquakes have been reported
under most of the major Australian cities (AGSO 1999).

The Australian continent lies whoþ within the Indo-Australian tectonic plate (refer

Figure 2.2.1) and as such is only subjected to intra-plate earthquakes. The closest
Australian city to an active plate boundary is Darwin, which is regularly but lightly
shaken by earthquakes along the subducting Java Trench in the Banda Sea.

Pacific Plate

Convergent plate
boundary
Direction of
Inter-Plate Region
crustal plaæ
movement
--+ Ausüalia

\\
Indo-Ausüalia Plate
v
i
High Seismicity Zones
Separating major crustal
plaæs
Antårctic Plate

Figure 2.2.1 Australia's Tectonic Location

Since earthquakes only occur in the earth's outer crust where rocks a¡e cold enough to be
brittle, in Australia, earthquakes typically only occur to a depth of a¡ound 20km (Gibson

11
CHAPTER (2) - Eanhquakes ønd Unreinforced Masonry

1990). This limitation constrains the vertical fault dimension so that for the release of a
large amount of strain energy the rupture would need to be very long. By practically
limiting the fault length to around 100km the maximum magnitude of earthquake that
could be realistically expected in Australia is around Ms 7.5. This assumption is
supported by studies of prehistoric Australian fault scarps where no scarp longer than
45km has yet been found (Denham 1992). It is therefore not unreasonable to argue that a
maximum credible earthquake of this magnitude be adopted for earthquake risk in
Australia.

Over the relatively short-recorded seismic history in Australia the largest known
earthquake occurred in 1906 off of the Northwest Coast of the continent with an
estimated magnitude of 7.2. On land the 1941 Meeberrie earthquake, which was felt over
most of Western Australia, appears to have been the largest having a magnitude of
approximately 7 (Denham 1992).

In 1968 a magnitude 6.9 earthquake devastated the Western Australian agricultural


township of Meckering. Here although no people died, 85 dwellings were severely
damaged being predominantly of unreinforced masonry construction. Later, in 1954,
Adelaide was subjected to a damaging magnitude 5.5 earthquake. Here again there were
no fatalities however over 30,000 dwellings sustained damage (hish 1992) costing at the
time in excess of 4 million pounds or $91m in 1995 dollars (AGSO 1999). More
recently, in 1988, a magnitude 6.8 earthquake having a 35km fault length and maximum
surface displacement of 2.0m (AGSO 1999) struck Tennant Creek in the Northern
Territory of Australia. Fortunately due to the remoteness of the area there was only
moderate damage caused.

By far the most devastating and expensive, although not the largest seismic event in
Australia's brief recorded history, was the 1989 Newcastle earthquake. Despite by world
standards being only a moderate magnitude 5.6 the earthquake caused massive damage to

both property and infrastructure with damage estimates of over a billion dollars at the
time of the earthquake (Melchers 1990, Blong 1992). It is also the only earthquake in

t2
CHAPTER (2) - Earthquakes qnd Unreinforced Masonry

recorded Australian history to have been responsible for the loss of life with thirteen
people killed and over one hundred injured. Furthermore, it was only the fortunate
timing of the event that saved many more from being killed or injured (Melchers 1990).

Attributed to the vastness of the Australian continent it has been fortunate that previous
large magnitude Australian earthquakes have occurred far from populated centers causing

only relatively low-level property damage. With an ever-increasing population density


and aging building stock the potential for earthquake disaster in Australia is becoming a

far greater threat to our society so that earthquake hazud must now be fully considered in
risk assessment scenarios. To further place the seismic risk of Australian cities into
perspective it has been reported (Blong 1993) that a design magnitude event, i.e. a 500
year return period earthquake, in Melbourne or Sydney could result in more than 500
deaths and $8 billion dollars worth of damage to domestic construction alone.

2.3. URM Building Stock in Australia

Due to Australia's modest level of seismicity and the many advantageous characteristics
of masonry, the use of URM as a building medium in Australia has been widely
embraced. The majority of Australian URM building stock is of either or
commercial low-rise construction although some taller buildings, up have 7
been constructed. For housing, masonry is often used as a veneer although with older
homes in the 'Western states cavity wall construction is more prevalent. Single skin
grouted or partially grouted masonry is also popular in the north of Australia (Page

1995). V/ith a large proportion of LJRM building stock comprising single occupancy
housing, multiple occupancy residence (three to four storey 'walk up' flats) and low rise
commercial buildings, URM is prevalent in the inner suburban areas of Australian cities.
In these areas the population densities are often the highest and combined with the

relative older age of the URM building stock the potential seismic vulnerability of these
areas is appreciable.

t3
CHAPTER (2) - Earthquakes and Unreinforced Masonry

The historical development and implementation of the Australian Earthquake Loading


Code provides an insight into the current thinking in AustraHa on the seismic
vulnerability of existing URM building stock. As highlighted in Section 2.2, even though
there had been a number of Australian earthquakes greater in magnitude 5.0, the first
Australian Earthquake Code, AS2l2l, was not published until 1979 as a response to the
1968 Meckering earthquake. Due to the lack of prior Australian strong ground motion
and research, this standard was based largely on requirements in the 1977 Structural
Engineers Association of California (SEAOC) Code and the 1976 Uniform Building
Code (UBC). After its release AS2l2l was seldom used and with the seismic zone map
having most of the country located in 'zone 0', which did not require seismic loading to
be considered, very few buildings were designed for earthquake loading. In fact, only the

South Australian and Commonwealth Governments actually used the code and in some
states with seismic design requirements these were ignored as they were not gazetted by
state authorities. It is possible that the misconception that design for wind also provided
for earthquakes led to this oversight.

With an increased understanding of earthquakes, 452121 was due for revision in 1989
when the Newcastle earthquake struck giving impetus and point to the deliberation. The
revised standard was again adapted from codes developed by Ameerican institutions such
as the Applied Technology Council (ATC), The National Hazatd Reduction Program
(NEHRP) and SEAOC before being incorporated into the Australian Loading Code in
1993 as the SAA Earthquake Loading Code, 4S1170.4-1993. This, the current standard,
ensures that for every building constructed in Australia a minimum consideration is given

to seismic loading. The level required varies in sophistication from simple detailing to
comprehensive dynamic analysis depending on structural category and regularity. For
masonry the general detailing provisions are referenced from the respective material
standard being the SAA Masonry Code, 453700-1998. As a consequence of the recent

development of earthquake codes almost all of Australia's existing URM building stock
was constructed in the absence of mandatory earthquake design requirements.

t4
CHAPTER (2) - Earthquakes ønd Unreinforced Masonry

Unlike other popular methods, masonry construction is labour intensive in nature and
consequently quality is particularly sensitive to workmanship. Paradoxically, unlike more

modern construction methods, masonry is often not subjected to a high degree of quality
control due largely to its traditional background. For these reasons finished product
quality has been highly variable and is often not indicative of the designer's assumptions.

For URM buildings having relatively low levels of overburden stress a critical property
of masonry is the bond between brick units and mortar known as the flexural tensile

strength. This is also possibly the most variable and sensitive property to workmanship
with variations of 30Vo to 35Vo found to be not unusual. The factors influencing bond
strength have been well-documented (Taylor-Firth 1990, Van den Boon 1994, DeVitis
1995,Lawrence 1995, Page 1998) and include the suction of the masonry units, the water
retention of the mortar, the morta¡ ingredients, the use of additives and the method of
laying.

A recent study (Nawar 1994) which documented current masonry construction practices
on building sites in Sydney identified large gaps between the designers intent and actual
practices. Here it was found that over 50Vo of the sites inspected had serious omissions
capable of compromising the long-term performance of the masonry. In a second study
(Zsembery 1995) the measurement of flexural bond strength at 19 sites in the Melbourne
area was undertaken where a significant va¡iation in the results was also found.

The 1989 Newcastle earthquake highlighted the vulnerability of non seismicaþ designed
buildings with a significant proportion of the damage attributed to the lack of
consideration to ea¡thquake loading and inadequate standards of URM design, detailing
and construction (Melchers 1990, Page 7992). An additional finding was that the real
masonry quality was much lower than would have been expected (Page 1992). In many
cases damage surveillance reported that in what appeared to be sound outer masomy
skins, problems such as inadequately frlled bed and perpend joints and inadequate tying
or support of one or both of the skins was evident. In older structures poor maintenance
and wall tie corrosion also played a significant role in exacerbating the damage. The

15
CHAPTER (2) - Earthquakes and Unreinforced Masonry

presence of weak lime mortars is also thought to have been responsible for a high
proportion of the billion dolla¡s worth of damage during the Newcastle earthquake. It
followed that the resistance of the effectively pre-cracked LJRM walls was left to rely
solely on stabilising gravity effects.

While deficiencies associated with poor workmanship and maintenance are the
responsibility of the Masonry industry as a whole, their existence and consequent
influence on structural durability and ductility must be recognised. As the Newcastle
situation is not unique in Australia it must be assumed that the same scen¿rio of non-
seismically designed buildings in poorly maintained condition, constructed of poor
quality materials and concentrated in inner suburban areas where population densities are
greatest exist in other Australian cities.

In recognition of the need to strengthen existing buildings with an assessed inadequate


seismic resistance the voluntary code 'strengthening of Existing Buildings for
Earthquakes',453826-1998, has recently been released in Australia. This requires the
designer to consider the same philosophical approach as 4S1170.4-1993 by establishing
clear load paths for the transmission of vertical and lateral loads. Many existing masonry
structures would be economically infeasible to upgrade to a capacity able to withstand the
full loads specihed in AS1l7O.4-1993. 453826-1998 therefore specifies lower th¡eshold
values for retrofitting structures based on the buildings use classification being either
33Vo or 66Vo of the full A51170.4-1993 specihed loads. In the absence of realistic
dynamic anaþsis methodologies the rationale here is that with the long return period of
large magnitude earthquakes, a greater degree of risk is acceptable in existing buildings
than that allowed in the design and construction of new buildings.

In the ideal situation structural engineers retained to investigate the seismic resistance of
a URM building would have at their disposal tools enabling them to prepare a realistic,
neither unduly conservative nor permissive, statement of the seismic resistive capacity of
both structural and architectural components. Since the traditional design methodologies
inherently provide conservative assessment of the seismic vulnerability of a URM

t6
CHAPTER (2) - Earthquakes and Unreinforced Masonry

building, adoption of these techniques may lead to the possibility of incorrectly labeling a

seismically adequate building as unsafe. In contrast overestimating the dynamic capacity


of elements to resist damaging cycles of seismic excitation could lead to a false and
dangerous sense of security. In this context, the benefit of developing better tools to
accurately determine the seismic resistance capacity of URM buildings and components
is apparent.

The first stage of the current research project was to survey and catalogue URM
connection details and overburden stress levels typical of Australian masonry
construction. Figures 2.3.1 to 2.3.5 show construction drawings of the most

predominantly used URM connections.

Figure 2.3.1 shows a 'cornice' type connection frequently used for internal non-
loadbearing URM partition walls. Often return walls are not incorporated into the
internal partition walls so that one-way bending predominates. Since the cornice
connection provides only horizontal restraint, the wall acts as a propped cantilever under
face loading.

Figure 2.3.2 and Figure 2.3.3 show conìmon connection details used in cavity wall
construction. V/here both brick leaves are laid on flat, the roof truss is typically
supported on the internal loadbearing leaf using a 'wooden top plate'. Alternatively,
often for economy of material use, the external leaf is laid brick on flat but the internal
leaf is brick on edge. In this case the internal leaf is unsuitable for roof support and the
roof truss is supported on the outer loadbearing leaf. For either case nails or masonry
anchors are used to fix the top plate to the tlRM wall providing a positive connection to
resist horizontal shearing forces. Light gauge steel trusses and wall plates are now also
used as an alternative to timber. To resist wind uplift a galvanised strap is typically
detailed being fixed to the roof truss and hooked around a support bar in the wall
approximately l.2mbelow the top (Figure 2.3.3).

t7
CHAPTER (2) - Earthquøkes and Unreinforced Masonry

Connections sholvn in Figure 2.3.4 andFigure 2.3.5 are often used between concrete slab
and loadbearing masonry elements. As will be discussed in Chapter 3, this type of
connection is typically detailed to meet serviceability design criteria.

Since, in general, only one wall leaf of cavity wall construction is loadbearing with the
other supporting only its own weight, the loadbearing leaf has a superior lateral strength.
Both URM wall leaves are connected via wall ties. The stiffer loadbearing wall therefore
must carry the combined inertia load from the dynamic response of both of the URM wall

leaves. Past earthquakes, in particular the Newcastle earthquake (Page 1992), have
demonstrated that wall ties can corrode thus becoming ineffective or that they may pull

out from deteriorated weak lime mortar under lateral loading. This often leads to the
weaker non-loadbearing outer leaf acting as an individual element being extremely
vulnerable to earthquake damage with a peeling off of the outer leaf commonly reported.

Ceiling under
trussed roof

Timber or plaster
cornice

Figure 2.3.1 Internal Partition Wall 'Cornice' Connection Detail

75 x25mmwooden
top plate
g

Þ;Ër
Non-loadbearing Nails or masonry anchors @
outer leaf 720 centers (third perpend)

f-oadbearing inner leaf -


Brick on flat

Figure 2.3.2 URM Cavity Wall to Roof Truss Connection Detail (Inner Loadbearing)

18
CHAPTER (2 ) - Earthquake s and Unr e info rc e d M as onry

Truss connection -
and hoop iron strips

Galv strap for wind uplift Non-loadbearing


internal leaf -
Brick on edge

Figure 2.3.3 URM Cavity \üall to Roof Truss Connection Detail (Outcr Loadbearing)

-r DPC

a

..;f,, ;.
¡;-'
r
ó'.
l, r.

Figure 2.3.4 URM Wall to Inter Story Floor Slab DPC Connection Detail

I
t
I
I Ds{
I ;.'
t a
-a]
DPC

Figure 2.3.5 URM Wall to Ground Floor Slab DPC Connection lÞtail

t9
CHAPTER (2) - Earthquakes anà Unreinforced Møsonry

A second outcome of this survey was the determination of typical levels of overburden
stress in Australia. This involved the analysis of numerous existing two to four story tall
LJRM buildings. Structural configurations included cavity and veneer URM consüuction,
concrete slab and timber floor diaphragms and both light gauge galvanised and heavy
tiled roof diaphragms. The conclusion of this survey was that overburden stress typically
ranged from 0.4MPa in the lower stories reducing to less than 0.1MPa in the upper
stories.

2.4. URM Vulnerability in Moderate Seismicity Regions

2.4.1. Failure Modes of LIRM Elements (Related to Seismic Load Path)

While the earthquake ground motion itself does not constitute a direct threat to life safety
the subsequent failure of man made structures does. During an earthquake a building is
subjected to a series of random ground displacements. As the structure reacts to these
displacements inertial forces are induced. The structural response to these inertia forces

is dependent on the natural frequencies and inherent damping of the building, and its
components, which themselves are dependent on the structural mass and stiffness.

To assist in illustrating elemental failure modes within a URM building it is pertinent to


describe the path that seismic input energy follows (Priestly 1985, Bruneau 1994, Calvi et

al 1996) as is shown in Figure 2.4.I. When subjected to seismic ground motion, the
foundation transmits seismic energy to the stiffest elements of the LJRM building beirrg
the in-plane sûuctural walls. The response of the shear walls, which itself is dependent
on height, stiffrress and overburden stress excite the floor diaphragm, through the wall to
floor connection, with a motion that has now been filtered by the shear wall. Following
this the floor diaphragm response excites the out-of-pl¿¡1s vvalls, through the wall to floor
connection, such that its dynamic characteristics directly influence the severity of the out-
of-plane wall excitation. The input excitation at the top of the face-loaded walls need
therefore not necessarily be in phase or even of the same magnitude as the bottom.

20
CHAPTER (2) - Eatthqual<es and Unreinforced Masonry

Floor diaphragm response Shaking


amplifies accelerations and motion \ Parapet wall
transmits load to out-of-plane
walls I
I
I
I
I
).-
ì
2-

In-plane shear walls


response filærs the
ground motion and
transmits to floor
diaphragms e
Earthquake Excitation at
footings

.<-
Out-of-plane wall

Figure 2.4.1 Seismic Load Path for Unreinforced Masonry Building

2.42. Review of the Seismic Performance of URM Buildings


As has been discussed in Section 2.2 the most damaging and therefore relevant
earthquake in Australia's recorded history was the 1989 Newcastle earthquake, Mr 5.6.
The earthquake intensity in outer Newcastle has been assessed at MM6.0Cí.5 (McCue
1990, Melchers 1990) while for inner Newcastle areas the general level of damage was

consistent with an intensity of MM7.0t0.5. Mean soft soil amplification factors of 3+1
are therefore considered indicative for the inner areas of Newcastle.

In reviewing damage patterns in Newcastle (Bubb 1990, Donaldson 1990, toke 1990,

Pederson 1990, Melchers 1990, Jordan et al 1990, Page 1990:1992, Griffith 1991,
Welhelm 1998) it is apparent that timber housing performed best followed by brick
veneer construction and that cavity brick construction was worst affected. It is noted
however that the latter mainly consisted of older buildings, many at least 60 years old,
and with significant structural deterioration. With few exceptions modern buildings

2l
CHAPTER (2) - Earthquakes and Unreinforced Masonry

performed better with damage conflned to masonry cladding and infill. The nature of the
damage can be summarised as:

- extensive cracking and deterioration of walls due to in-plane racking


- tilting of walls under transverse forces including sliding at damp proof courses
- partial loss of roof support by sliding from support walls
- cracking of walls in flexure under the action of transverse forces
- loss of end walls under transverse forces due to corroded wall ties

- gable end and parapet failures

LJRM parapet wall failure was the major form of damage in both older and newer
buildings and constituted a signif,rcant safety hazard both during and after the earthquake.
Often the collapse of parapets onto awnings preempted failure of the awnings in turn
leading to out-of-plane wall collapse. The most widespread incidence of parapet failure
was at the Tighes Hill Campus of the Newcastle Technical College as shown in Figure
2.4.2.

Figure 2.4.2Panpet Failure, Tighes Hill Campus, Newcastle Technical College


(Newcastle Earthqu.ake Study, The Institution of Etrgineers, Ar¡stralia, 1990)

22
CHAPTER (2) - Earthquakcs and Unreinforced Masonry

A study (Murphy & Stewa¡t 1993) of 651 Government buildings damaged during the
earthquake at 300 different locations found that parapets on buildings founded on
alluvium soil appear to have been the most haza¡dous with 55Vo of these incurring
hazardous damage as opposed to l77o on non-alluvium. This then suggested that the
amplified gtound motion on the soft alluvium \ryas substantial enough to cause the parapet

walls to become unstable. In contrast, on non-alluvium soil areas where there was less
ground motion amplification the parapets were less prone to becoming unstable, although
base cracking of parapets was still observed.

The Australian experience of IJRM performing poorly in earthquakes is not unique.


However, care must be taken when reviewing overseas URM research papers as the
lessons learnt from their experience is typically determined from different standards of
URM construction. Often the type of masonry construction and materials being referred
to bear little resemblance to materials and practices used in Australia. For example, after
both the 1997 labalpar, India, Ms 6.0, and 1999 Mexico, Ms 6.7, earthquakes, the
collapse and severe damage to URM housing was reported (Jain et al 1997, Alcocer
1999). The implication for poor URM performance is apparent. \With poor quality
materials such as burnt brick in mud mortar and very weak adobe masonry being the
predominantly used building materials, these bear little resemblance to materials used'in
Australia and as such few lessons can be learnt. Figure 2.4.3 gives an indication of the
typical quality of masonry in the Jabalpar earthquake.

Similar examples can be made of Greek (Fardis 1995) and Italian (Spence et al 1999)
earthquakes where damage to URM buildings often dating as far back as the middle ages
are being reported.

23
CHAPTER (2) - Eørthqualces and Unreinforced Masonry

Figure 2.4.3 lldasonry Darmge During 1997 Jabalpar, India Earthquake


(Jain er at 1997)

An analogy can however be drawn between earthquake damage to URM in some US,
New Zealand and Chinese cities where simila¡ LJRM construction types, materials and
seismic design histories to that in Australia exist. For example, like Ausfialia, many of
these cities comprise old LJRM buildings in inner suburban areas that havg been designed

with Iittle or no consideration for seismic action. Similarly weak lime mortars and poor
maintenance are also commonly found. Recent events in seismically active a¡eas where
ordinances have been place to upgrade vulnerable URM buildings have also enabled
comparisons of reEofitted and un-reftofitted damage to be made.

Selected documented events include: 1933 long Beach, California (Fatemi t999),1935
Helena, Montana (James 1999), 1971 San Fernando, California (Iæeds lg72), 1975
Imperial Valley, California and Mexico (Blakie et al 1992), 1983 Colinga, California
(Blakie et al1992),1983 Borah Peak, Idaho (Reitherman 1985), 1987 Whittier Narrows,
California (Deppe 1988, Hart 1988, Moore et al 1988), 1989 l¡ma Prieta, California
(Benuska 1990, Lizundia et al1994),1994 Northridge, California (Somers 1996), 1855

24
CHAPTER (2) - Earthquakes and Unreinforced Masonry

and 1942 Wairarapa, Central New Zealand (Grapes & Downes 1997, Blakie et al 1992),
1931 Hawke's Bay, East Coast New Zealand (Blakie et all992),1990 Weber, East Coast
New Zealand (Blakie etal7992),Tangshan, China, 1976 (Yuxian1979).

2.43. Common tlRM Element Failure Modes


Blakie et al1992 has presented URM damage data relevant for MM6 to MM8 intensities
as could be expected for regions of moderate seismicity although some examples of high

intensity shaking to MM10 are also included. At MM7 no URM buildings were reported
to collapse as compared with 87o to 45Vo at MM8. Similarly, around 70Vo had only slight
or no damage at MM7, dropping to 20Vo at MM8. Where retrof,rt o¡dinances had been
undertaken URM performance was acceptable with mostly only low level damage. At
MM10 severe damage was reported for URM buildings with as many as 75Vo of multi-
storey brick buildings collapsing. Here current retrofit methods were found to be
insufficient to prevent failures.

The following paragraphs provide a brief description and review of common failure
modes for URM buildings which have been more prevalent during past earthquakes.

Anchorage failures'. Anchorage is an important factor as it enables seismic load to pass


between walls and the floor or roof diaphragm. In many URM buildings diaphragm
joists and beams rest on LJRM walls, sometimes on special corbels although mostþ these
are recessed into the wall. Without effective anchorage face loaded exterior walls behave

as cantilevets over the total building height thus increasing the risk of face loaded wall
failure which may in turn precipitate total collapse. Global structural failure may also
occur by slippage of joists and beams from their supports. Where floor diaphragms are
positively connected to URM walls these anchors may rupture at the connection points
leading to the condition of 'lack of anchorage' as described above.

Anchorage failure has been the most frequent cause of wall and gable collapse in
mode¡ate earthquakes however this has often been ¡elated to deteriorated or poor quality
lime mortar.

25
CHAPTER (2) - Earthquakes an¿ Unreinforced Møsonry

Diaphragm flexibility and strengrå: No instance of complete diaphragm failure was


reported for any moderate intensity earthquake although the flexibility of the floor and
roof diaphragm has been suggested as a possible cause of wall damage. A particular case
is unsecured gable wall ends, which are extremely vulnerable through impact with the
roof structure.

As the floor diaphragm response directly excites the out-of-plane walls it is critical to the
URM building seismic response. In an attempt to mitigate the effect that diaphragm
response has on the dynamic behaviour of URM buildings, research has been undertaken

in the United States (ABK 1984). Here fourteen different diaphragms were tested to
obtain information on their in-plane static and dynamic, linear and non-linear properties.
Eleven of the diaphragms tested were of wood construction and the remaining of steel
decking either filled with concrete or not. Results showed that strong diaphragms
produced large amplifications of up to 3 to 4 times the input accelerations in the elastic
range essentially behaving as 2Vo damped oscillators. Flexible diaphragms were found to
have highly non-linear flexible behaviou¡ with typical amplifications in the order of 2 to
2.25.

Out-of-plane wallfailur¿s: When suff,rcient anchorage exists between the diaphragms and
walls, out-of-plane wall behaviour is as a one storey high panel dynamically excited at
either end. These panels themselves are susceptible to out-of-plane bending failure and
while in-plane failure does not always endanger the gravity load carrying capabilities of
the structure out-of-plane failure does. As amplihcation of the ground motion increases
with building height, face loaded walls in the upper stories of URM buildings tend to be
at the highest risk of failure. Parapet wall failures are also prone to flexural failure due to

the lack of masonry tensile strength.

In moderate magnitude earthquakes cracking of walls loaded in the out-of-plane direction


is common. For MM7 intensity shaking there appear to have been very few instances
where pure simply supported out-of-plane collapse occurred where walls were adequately
supported at the top and bottom. For MM8 intensity areas out-of-plane wall collapse was

26
CHAPTER (2) - Earthquakes and Unreinforced Masonry

a more prevalent cause of URM damage. Although many of these failures would have
been instigated by anchorage problems it is possible that a number resulted from
excessive out-of-plane displacements at the mid-height of the wall spanning between the
diaphragms. At MM10 intensity shaking out-of-plane wall failure was reported as

profuse, In some instances, adequately supported out-of-plane walls have survived even
this intensity shaking. It was also found that buildings with concrete floors had a lower
percentage of damage attributed to increased overburden stress.

Interior partition walls: As generally these walls are only one wythe thick and typically
have no overburden other than their own self weight they have been particularly
vulnerable even in moderate intensity shaking.

Parapet wall failure: Parapet collapse has been reported in all reviewed earthquakes. For
moderate intensity shaking these typically have been responsible for most loss of life.

In-Plane WaIl Failures: As seismic load passes through the structural shear wall, in-plane
failure may occur if the inertial bending or shear forces induced exceeds the wall
capacity. Over the past ten or so years a substantial quantity of experimental and

analytical research into in-plane ultimate behavioral properties of URM walls has been
reported (König et al 1988, Abrams 1992, Tercelj et al 1992, Pdtrsenjad et al t994,
Magenes et al 1995, Jankulovski et al 1995, Gambarotta et al1995, Lafuente et al1995,

Romano et al 1995, Anthoine et al 1995, Zhuge et al 1996). In reviewing this


documentation a wide variety of behaviour, which depends on the wall height to length
ratio, the applied load and the mechanical properties of the materials constituting the
brickwork can be found.

With different combinations of parameters three failure mechanisms have been identified.
These include (1) rocking/flexural mechanism, (2) shear-sliding mechanism and (3) shear
cracking mechanism typified by double diagonal (X) cracking. The first two failure
modes are considered to be favourable as they are capable of significant energy
dissipation without compromising the gravity load carrying capacity thus providing an

27
CHAPTER (2) - Earthquakes and Unreinforced Masonry

effective ductility. In contrast the third failure mechanism is considered to be non-


favourable as brittle collapse often results. If a stair stepped crack pattern occurs along
bed and head joints the element may still possess ductile characteristics as shear forces
can still be resisted through friction. [,ow aspect ratios and high axial loads have been
reported to develop diagonal cracking failure, while rocking and sliding were more likely

to occur with low axial loads and high aspect ¡atio walls. Higher mortar strength was
also found to inhibit shear cracking failure mechanisms in favour of rocking and sliding
failure. lncreased axial load was found to increase lateral strength in terms of the
maximum load carrying capacity although the seismic performance lvas also worsened
with the undesirable transition from a favourable to non-favourable failure mechanism.

Whether a URM wall element is controlled by flexural or shear, if suitable details are
provided the lateral force deflection behaviour will include a significant plateau portion
much like an elastic plastic material provided vertical compressive stress is present.

Both diagonal (X) cracking and horizontal cracking at the top and bottom of piers have
been commonly reported in most areas of moderate intensity shaking but do not appear to
have been responsiblefor any total building collapse. In contrast, brittle shear failure
caused by the diagonal shear (X) cracking failure mechanism was a serious cause of

collapse in more intensely shaken regions. For example in the 1976 Tangshan
earthquake, M5 8.0, where shaking intensities reached MM10, hundreds of URM
buildings were reported to have failed due to shear failure in loadbearing URM walls.
Figure 2.4.4 shows a school in Tangshan damaged by the earthquake where in-plane
distress can clearly be seen in the front wall piers and out-of-plane wall failure has
occurred at the top end wall.

28
CHAPTER (2) - Earthquakcs and Unreinforced Møsonry

Figure 2.4.4Darage to IIRM Building, Tangshan' China' 1976


(Steinbrugge Colleclion, Eartþuake Engineering Research Center, University of Califomia Be¡keley)

z.4A.'Weak LinK LIRM Failure Modes


In summarising the data presented in Section 2.4.3, for moderate intensity shaking, the

'weak link' failure mode, which predominates for regular LJRM buildings, is the lack of
anchorage between structural elements, in particular between floor/roof diaphragms and

URM walls. Typically this has been due to a lack of consideration to lateral loading and
in most cases could have been avoided by the provision of positive connections. As will
be discussed funher in Chapter 3, where the diaphragm is relatively rigid the provision of
positive connections may cause serviceability problems and as such friction based
'Where
connections are often relied upon. sufficient anchorage between structural
elements has been provided the dominant 'weak link' failure mode is the out-of-plane
flexure of URM walls including both simply supported and parapet walls. Tytng patapets
back to the main structure has proven to be a successful retrofit method for moderate
intensity shaking.

In regions of moderate intensity shaking there have been many reported instances of
URM buildings that have suffered minimal or no damage at all while other buildings of a

simila¡ nature and in the same shaking intensity region have suffered substantial

29
CHAPTER (2) - Earthquakcs and. Unreinforced Masonry

structural damage. It is therefore clear that provided the 'weak link' failure modes can be
avoided URM can be relied upon to behave adequately during moderate earthquakes.
Clearly for areas where the probability of stronger intensity shaking is deemed
sufficiently high LJRM construction is not appropriate with the logical alternatives being
more ductile methods such as reinforced masonry, reinforced concrete or steel
construction.

Analytical resea¡ch by Klopp 1998 has also identified 'weak link' URM failure modes.
This involved the analysis of eleven existing LJRM buildings in Adelaide using the
response spectrum method and equivalent static force requirements of ASl 170.4-1993.
As a results Klopp reported that the two most likely failure modes for Australian URM
construction are:

(I ) The limited force capacity of connections betvveen floors and walls. Klopp reported
that the code guidelines for connection force capacities benveen the floors and walls of
LJRM buildings were found to be insufficient being significantly smaller than the
requirement determined by elastic response spectrum analysis to ASI170.4-I993.
Despite this Klopp also reported that typical forms of positive connection could generally
easily meet the earthquake shearing forces induced. Of more concern were connections
containing a DPC membrane often found in URM-concrete slab buildings, which rely on
friction to transfer horizontal forces. In comparing the calculated connection shear force
demand under the AS1170.4-1993 design earthquake, friction coefficients of a¡ound 0.3
to 0.4 were required. These values are of about the same magnitude as static friction
coeff,rcients reported by Page 1994,1995 for connections containing DPC membranes
commonly used in Australian masoffy construction. This suggests that friction might
sufficientþ transfer the shearing forces although this assumes that the full static frictional
resistance can be relied upon. This assumption therefore warrants further investigation.

(2) The out-of-plane bending failure of walls of URM buildings. Klopp found that hve
out of the eleven LJRM buildings analysed under the A51770.4-1993 earthquake had
bending stresses greater than the simply supported elastic bending capacity of the wall.

30
CHAPTER (2) - Earthquakes and Unreinforced Masonry

Current design practice in Australia would thus indicate failure. As will be discussed in
Chapter 5, however, the resulting cracked condition may not constitute failure or collapse

as a reserve dynamic capacity may exist. An additional factor was reported that the stress
was more likely to exceed capacity in the upper stories of URM buildings where
excitation amplification is a maximum and beneficial overburden stress is at a minimum.

2.5.'Capacity' Design for Improved Seismic Response


\ühen considering the preservation of life the most important design criterion is the

Ultimate Limit State. In Australia only the Ultimate Limit State is considered. Here
relatively large inelastic deformations must be accommodated without significant loss of
lateral force resistance or the integrity of the structure to support gravity loads. Although
non-repairable residual plastic deformations may occur the principal aim is to ensure that
collapse is avoided.

The 'Capacity' design strategy has been defined (Paulay 1997) as "In structures so

designed for of the prinnry lateral force


earthquake resistance, distinct elements
resisting system are chosen and suitably designed and detailed for energy dissipation
under severe imposed deþrmations. All other elements are then to be protected against
actions that could cause failure by providing them with strength greater than that
corresponding to the mnximum feasible strength in the potential plastic regions." In
theory the application of the 'Capacity' design principal leads to a benign and tolerant
inelastic response with a high degree of protection against the collapse of structures
subjected to severe earthquakes.

For framed reinforced concrete structures the 'Capacity' design methodology can be

followed by detailing plastic hinge locations in beam elements ¡ather than in columns.
Thus, at the Ultimate Limit State a ductile inelastic sway mechanism having strong
energy dissipative qualities is formed without the creation of a failure mechanism. In a
similar fashion for a URM building the 'Capacity' design methodology can be followed

31
CHAPTER (2) - Earthquakes and Unreinforced Masonry

by the selection of a suitably ductile mechanism capable of dissipating seismic energy


without damaging other structural elements due to severe deformations.

As has been discussed in Section 2.4.3 with the correct selection of URM in-plane wall
geometry a failure mode capable of inelastic deformation and seismic energy dissipation

suitable for 'Capacity' design is possible. Other less desirable failure modes such as out-
of-plane bending and anchorage failure must then be protected against. Clearly if the
'Capacity' design principals are to be used effectively for URM it is important that
realistic assessment of dynamic capacity of these failure modes is possible.

2.6 Overall Project Aim


As a result of this literature suryey the research aim to be addressed within the scope of
this report has been determined as providing designers with appropriate tools to avoid the
brittle 'weak link' failure modes in the design of new and the assessment of existing
URM buildings being:

(1 ) The limited force capacity of connections between floors and walls, in particular the
friction dependent connections containing damp proof course (DPC) membranes and

(2) the out-of-planefailure of walls in the upper stories of URM buildings

The first aim was achieved for the DPC connections through an extensive series of
shaking table tests, which provided realistic data on the connections' dynamic capacity.
The second aim was achieved by an extensive series of shaking table tests used to
develop a better understanding of the physical processes governing the collapse
behaviour of face loaded URM walls. From this improved understanding realistic
analytical models were developed to provide an accurate and reliable assessment of
actual capacity. As these were complex, by necessity, a further rehnement was to
produce a simplistic rational analysis procedure for practical applications.

32
CHAPTER (2) - Earthquakes and Unreinforced Masonry

Once these 'weak links' have been avoided with adequate seismic load paths developed,
carefully designed, detailed and constructed, regular URM buildings have repeatedly
shown that they will behave adequately during moderate intensity earthquakes. Further,
this allows the 'capacity' design methodology to be more effectively undertaken resulting
in an increased effective ductility for URM buildings to be realized.

JJ
3. DPC CONNBCTIONS IN URM
CONSTRUCTION

3.L. Introduction

In general, masonry buildings are constructed utilising a vast array of flashings, damp
proof course (DPC) membranes and construction joints aimed at ensuring satisfactory
serviceability performance. As highlighted in Section 2.3 for Australian unreinforced

masonry (tlRM) construction, connections between a concrete slab and masonry wall are

commonly detailed containing DPC membrane.

Typically, DPC membranes used for URM connections are flexible, manufactured from
either embossed polythene or a light gauge aluminium and covered with polythene or
bitumen. Normal practice is either to incorporate the membrane laid directly adjacent to
the slab with a single mortar layer placed between the membrane and brick or to place it
one to two brick courses up from the slab. This configuration is referred to as a standard
DPC connection. Alternatively, the membrane may also be sandwiched between two
mortar layers although not often used in practice as it is labour intensive. This is referred
to as a centered DPC connection. Finally, in some circumstances no mortar is used with
the membrane laid directly between the brick and slab or brick and brick. For these
connections two layers of DPC membrane are often used back to back. This is referred to

as a slip joint connection. Figure 3.1.1 provides a representation of the above three
connection configurations.

In masonry construction, connections containing a DPC membrane are generally detailed


to fulfil the dual serviceability role of providing an impervious barrier to moisture

movement while acting as a plane of separation between structural elements. The latter
role prevents distress of the connected elements by limiting the transfer of forces and

34
CHAPTER (3) - DPC Connections in URM Construction

strains through the connection, caused by differential movements. While these


movements will be discussed further in Section 3.3.2 it is clear that these connections
must be capable of satisfying two conflicting horizontal shear requirements. Firstly, they
must have the ability to allow for long-term relative movements between structural
elements by limiting force transfer. Secondly, they must provide sufficient shear
resistance to give lateral support to the wall under short-term earthquake loading. With
friction being relied upon for horizontal shear resistance, the frictional properties are
therefore critical to the successful application of these connections.

Standard DPC Connection Centered DPC Connection Slip Joint Connection

Brick Brick
Mortar Mortar Brick
DPC DPC DPC
Slab \ Mort¿¡
Slab
Slab Often2
A A À À layers DPC
A
À 4 A À

Figure 3.1.1 Types of URM Connection Containing DpC Membranes

This Chapter reviews previous work and relevant literature associated with both
serviceability requirements and shear-resisting capacity of URM to concrete slab
connections containing DPC membrane material and presents the specific 'weak link'
research focus to be further considered within the scope of this project.

3.2. General Friction Review


The shear-resisting behaviour of a URM connection containing a DPC membrane is
characterised by Coulomb (dry) friction, which involves rigid bodies in contact along a
non-lubricated surface.

3.2.1. Coulomb Friction Behaviour

Investigations (Suh & Turner 1975) into surface topography have shown that the surface
of a dry material such as metal, polymer or brickwork is not smooth but made up of many
tiny peaks called 'asperities'. Thus, when two surfaces touch the real contact area is much

35
CHAPTER (3) - DPC Connections in URM Construction

less than is apparent as only the asperities interact and consequently these govern the
frictional behaviour. When a normal stress is applied to the friction plane the real contact
area increases along with interaction between the asperities.

The static friction coefficient, kv.st¿tic, can be defined as the minimal tangential foÍce, F^,

required to initiate tangential motion divided by the normal load acting on the interface,
N, as is represented by Equation 3.2.1. Hencl, kv.stotic is governed by adhesion of the
touching asperities and has been found to be independent of the apparent contact area,
normal load and duration of loading. Once the adhesion force between asperities F. is
exceeded slip at the friction interface follows (refer Figure 3.2.1).

kv.statíc='/* (3.2.1)

The plowing of soft surface layers by hard asperities primarily controls the sliding or
dynamic friction between solids. On sliding, the magnitude of force required to sustain
motion drops from F, to the lesser dynamic friction force, Fr. This reduction in resistance
is caused by less interpenetration of the surface asperities when the surfaces move with
respect to one another and is well documented to be generally of the order of 25Vo (Suh &.
Turner 1975). Thus, the dynamic friction coefficient, kv dynamic, is less than the static
friction coefficient, kv.sta¡c.

Both the static and dynamic friction coefficients strongly depend on the nature of the
surfaces in contact. As the exact condition of the surface dictates these coefhcients they

are seldom known within an accuracy of greater than 5Vo as any foreign material present
at the interface, such as corrosion or dirt, will alter the coefficient.

Coulomb friction can be further catagorised by the type of material at the friction plane as
classically (e.g. metals) and non-classically behaving (e.g. polymers) friction. Since DPC
membranes found in Australian URM construction are cornmonly produced in both of
these materials a brief review of both Coulomb friction behaviours will be presented.

36
CHAPTER (3) - DPC Connections in URM Construction

3.2. I J. Clas sic ally B ehaving Materíals

There are three generally accepted laws of friction for classically behaving materials.
These are (i) Friction is proportional to the normal load, (ii) Friction is independent of the
apparent area of contact and (iii) Friction is independent of sliding speed.

Once sliding for a classically behaving material has commenced the dynamic friction
force, F¿, remains approximately constant provided there is no material degradation (refer
Figure 3.2.1).

3.2.1.2. Polymers

The frictional behaviour of polymers differs from that of classically behaving materials in
that it does not necessarily obey the classical laws of friction. Since the static friction
coefficient for polymers is sensitive to the hydrostatic component of stress it becomes
dependent on normal stress. It has been reported (Suh and Turner 1975) that the dynamic
friction coefficient for polymers can reduce substantially with increased normal force.

A second difference is that polymer frictional behaviour is very sensitive to sliding


velocity caused by the large strain rate and temperature dependence of the flow stress of
polymers. In any frictional scenario, as sliding velocities are increased the mechanical
work done also increases the interfacial temperature. At a critical velocity/temperature a
maximum dynamic friction coefhcient is reached, and thus a maximum dynamic
frictional resistance force, F q (refer Figure 3.2.1).

For some polymers Fp bas been reported (Rosato et al 1991) to be higher than the
original static resistance force, F.. This is attributed to sliding velocity/temperature
increase prior to the maximum coefhcient of dynamic friction being reached. As strain
rate effects dominate the frictional behaviour the shear force for deformation also
increases. After the critical velocity is passed the frictional behaviour is no longer
dominated by strain rate increases but softening of the polymer which reduces the
dynamic friction coefficient. It has been reported (Corneliussen 1986) that the reduction

37
CHAPTER (3) - DPC Connections in URM Construction

of dynamic friction coefficient may be due to a molten film of polymer developing which
acts as a lubricant so that a hydrostatic sliding condition prevails.

Equilibrium Motion
Static Dynamic Polymer dynanic friction
behaviour, increase due to
strain effects with maximum
dynamic friction coefficient at
t¡r F- polymer critical velociw
(l)
ko Frp
o Classical Dynamic
f¡r
o Behaviour
9
sø Fr
a
c)
ú
Cd
É
o

()
tli

CRJTICAL FRICTIONAL SIIEAR


RESISTANCE: F. notreached due ûo
vertical disturbance of the planes

Applied Horizontal Shear Force

Figure 3.2.1 Diagrammatic Representation: Frictional Resistance vs Applied Shear

3.3. URM Connection: Previous Research


In the following section a review of previous work carried out by other researchers
relevant to the serviceability and shear resistance of URM connections is presented.

33.1. Plain-Masonry Joint Shear


As URM connections containing DPC are in essence a plain-masoffy joint containing a
thin flexible DPC membrane, thefu shear behaviour is closely related to that of a plain-
masomy joint. The main differences are frrstly that the frictional properties of the DPC-

brick, slab or mortar interface rather than the mortar-brick interface must be considered.
Secondly, the initial shear bond, caused by mechanical interlock of mortar and brick in a
plain-masonry joint, is typically reduced significantly where a DPC membrane is present.

38
CHAPTER (3 ) - D PC Conne uions in U RM Construction

Previous investigators have shown that when an increasing normal compressive stress is
applied to brickwork, the horizontal shear strength at a plain-masonry joint increases
linearly with compressive stress up to a limiting compressive stress. The widely accepted
explanation for this is that the strength of the joint is derived from a combination of initial
shea¡ bond and Coulomb friction between the brick and the mortat. Consequentþ, the
relationship between ultimate shear strengh, G, and normal compressive stress, o", is
often expressed by a Coulomb type relationship, such as that shown in Equation 3.3.1
where to is the initial shea¡ bond and p is the friction coefficient of the brick-mortar
interface.

Íu=To* FC" (3.3.1)

Hendry and Sinha, 1981 have reported on a series of tests carried out on full-scale and
model shear walls built of wire cut bricks in l:V¿:3lime mortar. It was found that the
shear resistance for this type of brickwork was well represented by the Coulomb type
relationship shown in Equation 3.3.2urp to a normal compressive stress level of 2MPa.

t,=03+0.5o" (3.3.2)

Similar results using different brick and mortar combinations have also been reported
(Stafford Smith & Carter 1971, Riddington &Ghazali 1990, Magenes & Ca\vi 1992,
seisun etal1994, Mullins & o'conner 1995). Although ro (0.1 to 1.19) and ¡r (0.4 to
1.33) have varied signif,rcantly with the type of materials tested, a similar Coulomb type
relationship has been obtained for low levels of normal compressive stress.

While the linear Coulomb relationship has been consistently reported for relatively low
Ievels of normal compressive stress the above resea¡ch has also indicated that the rate of
increase in shear strength reduces at higher normal compressive stresses. Where this is

the case the value of p appears to decrease with increasing normal compressive stress.
The level at which this reduction begins has generally been reported to be a¡ound 2MPa

39
CHAPTER (3) - DPC Connections in URM Construction

although this is dependent on the quality of masonry construction and materials


considered.

Although initially it was proposed that an average value of ¡r could be assumed over all
normal compressive stress ranges this was questioned as it did not realistically model the
true shear behaviour at higher over burden stresses. In recognition of this Riddington
and Ghazzali (1990) proposed a hypothesis for the shear failure of plain

Here, simila¡ to the original findings of Hendry and Sinha (1981) and the was

postulated that below a normal compressive strsss of around 2MPa, 1S

initiated by joint slip as predicted by a typical Coulomb relationship. Above this the
shear failure mechanism is governed by tensile failure within the mortar and finally at
very high compressive stress the compression failure of the brickwork becomes the
dominant factor. An experimental investigation was also reported (Riddington & Ghazali
1990) confirming the plain-masonry shear failure hypothesis as represented in Figure
3.3.t.

Also shown in Figure 3.1.1, the plain-masomy joint failure hypothesis (Riddington &
Ghazah 1990) can be related to URM connections containing DPC membrane. Since for

these connections both the initial shear bond and friction coefficient may be reduced as

compared with a plain-masonry joint, the intersection of the DPC joint slip and mortar
tensile failure lines will occur at a higher normal compressive stress. For the range of
normal compressive stress commonly found in Australian masonry construction, as

described Section 2.3 it is therefore unlikely that a mortar tensile failure mechanism
would dominate under horizontal load but rather a joint slip mechanism (refer Figure
3.3.1).

.t
,1 n lô.'.
I
\" \'f 'r
\,¿l'
, l,t"
f'
.t'

\l
\,r
Q trüd
u
tl,il '.t
\ ''-
\"Ì
v
*rY
-l 40
CHAPTER (3) - DPC Connections in URM Construction

o
çt
o. Morar Tensile Failure
ñt
L)
k
ñl
(l)

U)
Brickwork
Plain-
()
c! Slip
E

a
t:¡

Approx. Overburden SEess, o.


2MPa

Range of overburden stress associated with typical Australian applications


Initial
Joint slip is the critical failure mode
shear
bond

Figure 3.3.1 She¡r Failure Hypothesis


(Riddington & Ghazali 1990)

In a real loading scen¿rio masonry elements are rarely subject to only one type of load
and are generally in a complex state of stress where in-plane and out-of-plane actions
occur simultaneously (Yokel & Fattal 1976). rüith loading such as earthquake or wind,
URM walls can experience cyclic bi-axial stress states being either tension or
compression. Dhanasekar (1985) has reported on a series of half scale brick masonry
panel tests subjected to bi-axial compression-compression and compression-tension.
Here, it was found that morta¡ joints acted as planes of weakness influencing the failure
loads and failure patterns.

3 3 2. Serviceability Requirements
The following section presents a brief summary of previous research associated with
serviceability requirements of connections within URM buildings. One such connection
serviceability requirement is the prevention of distress caused by differential movement
of structural elements. Since movement may be caused by differential movements
associated with concrete slab shrinkage, growth/shrinkage of claylconcrete masoffy
units, thermal movements or foundation settlement, each structural element will behave
differently over time. Consequently, each element will induce forces into adjoining

4l
CHAPTER (3) - DPC Connections in URM Construction

elements. Where the induced force is in shear its magnitude is limited by the shear
capacity of the connection joining the structural elements.

It is well documented that concrete, whether it constitutes masonry units or floor slab
undergoes shrinkage and creep with time. In contrast the time dependent behaviour of
clay masonry is not as well documented and is complicated by the composite nature of
the material. It has however been reported (Beard et al 1969) that the time dependent
movement of brickwork is caused by one or a combination of thermal movement,

moisture movement, chemical expansion or deformation under load. Further research


(Beard et al1969, Cole & læwis I974,Wyatt 1976) has reported on studies associated
with the movement of brickwork. In general, findings were that all of the walls expanded
horizontally and vertically with time and the rate of expansion was maximum during the
early life of the wall and decreased with time.^
(- T tp J r'Ln !
It is therefore clear that there is a conflict between the time dependent behaviour of
concrete and clay constructed structural elements. As mentioned in Section 3.1, URM
connections containing DPC are typically detailed to fulfil a dual serviceability role, one
of which is that the shear resistive capacity is sufficiently low to allow the differential
movement between structural elements. Research (Beard et al 1969) has been carried out

to determine if this is actually the case as the magnitude of force transmitted by the
differential movement is difficult to ascertain. Here the movement of brickwork above
and below a lead cored bituminous standard DPC connection at the base of an actual
building was measured. It was found that the lack of shear restraint offered allowed the
brickwork above the connection to move.

Although not directly related to seismic loading another important aspect of URM
building serviceability is the movement of footings supporting masonry walls. Research
(Page & Kleenman 1994) has been undertaken to establish parameters influencing wall
behaviour under such actions. Here, provided the walls had sufficient strength to resist
cracking they were found to bridge the movement of the flexible footings. [n practice

42
CHAPTER (3) - DPC Connections in URM Construction

masonry walls often do not have sufficient strength to resist cracking and are commonly

observed to crack under deformations permitted by flexible footing movement.

3.33. Positive Anchorage


As highlighted in S lack of anchorage of masonry walls to floor and roof
diaphragms contributed separation and non-uniform vibration of walls in areas of
( t\' moderate intensity shaking. This was less prevalent, however, with concrete slab
diaphragms, which provided a higher normal compressive stress and increased frictional

resistance than in LJRM buildings with flexible timber diaphragms. Conversely,


anchorage through positive connection of concrete slab and URM wall is more likely to

create a serviceability conflict due to differential movement whereas this is less likely
with the more flexible timber diaphragms.

In order to assess the vulnerabilify of non-anchored timber diaphragms a non-linear


dynamic analysis able to model the friction and impact characteristics of wood joist
bearing on a brick wall has been developed (Jones & Cross 1993). Using this model
comparisons were made with the dynamic response of a retrofitted building in Gilroy,
California having a well anchored timber floor diaphragm which survived the M. 7.1
[,oma Prieta (1989) earthquake. While entire city blocks were demolished in nearby
Santa C¡uz and another LJRM building, a Town Hall, two blocks south was severely
damaged the Gilroy building sustained very little damage despite roof accelerations of
0.799. As a result of the analysis it was found that the structural response remained
elastic provided the diaphragms and wall were connected. If, however, the joist to wall
connections were disconnected the response of the structure moved into the inelastic
range. In the latter case two possible failure mechanisms were identified as (1) collapse
of the wall in out-of-plane bending and (2) when joists moved sufficiently to cause them
to fall from the wall.

Tomazevic et al (1995) have also reported on a series of shaking table tests completed
with V¿ - scale, 2 storey masonry and stone houses having both unconnected timber joists
supporting a concrete slab and connected timber joists also supporting a concrete slab. It

43
CHAPTER (i) - DPC Connections in URM Construction

was found that freely supported wooden floors did not prevent separation of the walls and

severe out-of-plane vibration of the wall was noted. Where horizontal steel ties were

provided separation of the walls was prevented with ultimate collapse caused by shear
failure of the walls in the first story. The input energy needed to cause collapse of the
model building with connected timber joists was over two times greater than the case of
the model without ties. It was concluded that separation of wall can be prevented by
either anchoring wooden floor joists into the wall using steel ties or replacing wooden
floors with reinforced concrete slabs.

Buccino and Vitiello (1995) have reported on an experimental investigation on three


types of anchorage to assess their pull out resistance. The experiments showed that the
shape of the anchorage and quality of the brickwork had a great influence on the
resistance to pull out ofthe anchorage.
:
ì'- ¡rlì'-L "" l" .''6''"'' .;'' "J' 4

3.3.4. Shear Resistance of URM Connection Containing DPC Membrane


Since the frictional resistance properties of connections containing a DPC membrane íue

specific to the particular membrane used overseas research data is not strictly applicable
for Australian URM construction. This being the case a brief review will be presented
for overseas research where applicable with more focus placed on Australian resea¡ch.

As part of a study of the long term differential movement resistance of DPC connections
British researchers (Beard et al1969) first highlighted the need for an understanding of
the frictional resistance of DPC connections. Here it was highlighted that the shear
resistance was significantly less than for a plain-masonry joint. This was confi¡med by a
further experimental study (Hodgkinson & West 1982) which reported on shear tests to
determine the shear resistance of British DPC materials.

Experimental investigations (McGinley & Borchelt 1990:1991) have also been

undertaken to evaluate static friction coefficients for eight connections containing a DPC

membrane commonly found in the United States. Both in-plane and out-of-plane loading

M
CHAPTER (3) - DPC Connections in URM Construction

directions were investigated with both concrete and steel supports. For standard DpC
connections on a concrete slab, static friction coefficients were found to vary from 0.19 to
0.5. Simila¡ results were reported for steel supports however a significant reduction was
noted with the presence of a coating such as galvanising or paint. While it is generally
accepted that rougher slip plane surfaces produce higher coefficients offriction this study
indicated that both the stiffness of the support material on either side of the membrane as
well as the DPC membrane had a significant effect on the friction behaviour. For a given
roughness of DPC material, stiffer membranes produced higher friction coefficients and

are more likely affected by the properties of the supports. In contrast, for a more flexible
DPC the properties of the membrane tended to dominate the frictional behaviour. The in-
plane and out-of-plane behaviour was also found to vary significantly which was
attributed to the differing surface texture of the brickwork in either direction.

Static friction tests on a series of three-brick high prisms with up to 0.9MPa normal
compressive stress have also been reported (Suter & Ibrahim 1992) for DPC materials
commonly available in North America. The significance of these tests is that it was hrst
recognised that the location of the DPC membrane within the mortar joint has an effect
on the frictional behaviour. As such, standard DPC, centered DPC and slip joint
connections were tested. Static friction coefficients were found to range from 0.1 for slip
joint connections to 0.6 for the centered DPC connections.

To establish the frictional characteristics of connections containing DPC membranes


directly applicable to Australian masonry construction a comprehensive series of static
tests (Page 1994:1995) has been reported. The membrane t)pes selected were chosen on

the basis of advice from industry to obtain a reasonable representation of common


construction practice in Australia. Here both two and th¡ee-brick long specimens laid in
running bond with standard DPC, centered DPC and slip joint connection configurations
were tested. Both in-plane and out-of-plane tests were carried out with normal
compressive stress ranging up to l.5MPa. For the range of compressive stress considered

a Coulomb friction relationship was used to describe the shear resistive behaviour. Thus,
tests were performed at various normal compressive sffess and a linear regression of the

45
CHAPTER (3 ) - DPC Conne ctions ín URM Construction

data points used to determine the static friction coefficient and initial shear bond strength.
The resulting static friction coefficients are summarised for DPC connections in Table
3.3.1 and slip joint connections in Table 3.3.2.

Table 3.3.1 DPC Connection Static Friction Coefficient Sumnury (Page 1994)

In-plane 0c,) Out-of-Plane (/s")


CONNECTION COMMERCIAL Centered Standard Centered Standard
CONFIGERATION NAME
Bitumen Coated Standard Alcore 0.41 0.49 0.50 0.47
Aluminium
Bitumen Coated Super Alcore 0.60 0.41 0.57 0.48
Aluminium
Poþthylene/Bitumen Rencourse 0.26 0.26 0.31 0.35
Coated Aluminium
Embossed Polythene Supercourse 500 0.68 0.59 0.59 0.56
Embossed Pol¡hene SupercourseT5O o.7l 0.58 0.60 0.59

Table 3.3.2 Slip Joint Connection Static Friction Coeffcient Summary (Page 1994)

SLIP JOINT CONNECTION CONFIGERATION Out-of-Plane


(k")
1Layer of Super Alcor 0.57
2Layers of Super Alcor 0.48
2Layers of Galvanised Steel with Molydenum 0.06
Disulphide Grease

In conclusion Page reported that for all of the DPC materials considered, with the
exception of poþthylene/bitumen coated aluminium (Rencourse), the static friction

coefficient could conservatively be taken as 0.3 for earthquake loading. Also, although
small shear bond strengths were reported these were generally very small (OMPa to
0.12MPa) and as such would be neglected.

Using similar connection details to the static tests reported by Page (1994:1995), quasi-
static (cyclic) shear tests have also been reported (Griffith & Page 1998). These tests
were aimed at studying the cychc performance of the various membranes under repeated

46
CHAPTER (3) - DPC Connections in URM Construction

loading cycles, in particular the potential degradation of the materials. Quasi-static tests
were performed at velocities of between 50 and 2OOmm/minute and at three levels of
normal compressive stress. A continuous plot of shear force versus shear displacement
recorded which resulted in a series of hysteresis curves (refer Figure 3.3.2). From these
curves the maximum quasi-static shear resistance force was determined for each level of
normal compressive stress as the plateau of the hysteresis loop. The quasi-static friction
coefficient was then the quasi-static friction coefficients determined
will be presented in were found to be slightly larger than those
determined previously by A second significant finding of this research was
that even after many cycles of shear displacement very little degradation in shear capacity
was observed indicating that tlRM connections containing a DPC membrane would
perform satisfactorily in service under cyclic loading.

CË 0,ô
ô-
à

I
Ø
c)
/
ts
v)

3 .10 t0

þ
()
U)

Displacement (mm)

Figure 3.3.2 Results of Typical Quasi-static on DPC Connection


(Griffith & Page 1998)

47
CHAPTER (3) - DPC Connections in URM Construction

3.4. Australian Code Provision: UII,M Connections

The 'SAA Earthquake toading Code', 451170.4-1993 requires connections to be

capable of transmitting a horizontal force of lO(aS) kN/m where ¿ is the acceleration

coefficient and S the site factor. To illustrate this requirement, for a firm soil site in
Adelaide, a = O.lE and S = 1.0. Thus, in this case, connections must be capable of
transmitting a force of lkN/m. Research (Klopp 1996) has indicated that this
requirement may be inadequate being as little as 1/13ù of the required shear capacity for
a two-storey URM building when subjected to the design magnitude earthquake. Despite
this, it was also reported that most typical forms of positive connection would still be
suff,rcient.

As discussed in Section 3.3.3, the positive connection of a concrete diaphragm to a

masonry wall may produce a serviceability problem so that URM connections containing
DPC are often used. Klopp (1996) therefore also compared the calculated confection
shear capacity with experimentally determined (Page 1994:1995) static shear resistance
of connection containing DPC membrane. In general he found that the frictional
resistance capacity was adequate.

Consequently, although friction is generally not recommended as a method of


transferring horizontal loads the 4S1170.4-1993 amendment No.l OCTOBER 1994, now
allows friction to be relied upon at connections containing DPC membrane within
loadbearing masonry construction. The shear resistance capacity however must still be
determined in accordance with the 'SAA Masonry Code',453700-1998 as:

48
CHAPTER (3) - DPC Connections in URM Construction

volv.+vr. (3.4.r)

where V¿ = the earthquake induced design shearforce


vo = the shear bond strength of the shear section
= Qf'^rA¿*
Vt" = the shearfriction strength of the shear section under earthquake actions
= 0.9 kuf¿, A¿n
0 = the capacity reductionfactor
l'^, = the characteristic shear strength of masonry
A¿n = the bedded area
k" - friction cofficient
fa = the design compressive stress on the bed joint for earthquake actions
= Gr/A¿n
Gs = the gravity load

The first term in Equation 3.4.1 represents the basic shear bond strength and the second
the frictional component of the capacity. For a plane containing a DPC membrane the
shear bond strength is usually negligible as the membrane is generally placed directly
onto brick. The shear capacity of the joint is therefore almost solely a function of friction
and thus on the friction coefficient, k, and the design compressive stress at the friction
plane,f¿.

Importantly, it must be recognised that the currently recommended friction coefficients


are based upon static friction coefficients for URM connections containing DPC
membrane. Confirmation was therefore required to determine if these will be indicative
of the dynamic friction coefficient under true dynamic excitation.

49
CHAPTER (3) - DPC Connections in URM Construction

3.5. Implication of the Dynamic Friction Coefficient

In any seismic event it is well recognised that both horizontal and vertical accelerations

occur. For example Glogau (1974) reported that vertical acceleration as large as two

thirds of the horizontal were recorded during the l9ll San Fernando earthquake. It is
therefore possible that with vertical disturbances at the slip interface of a connection
containing a DPC membrane that the maximum static peak tangential force, Fr, may not
be reached as the adhesion between the asperities may already be reduced or broken. If
this were the case the critical resistance to shear would then be governed by the lower
dynamic friction force, F¡, and thus dynamic coefficient of friction , kv dynamíc.

As can be seen in Figure 3.2.I the frictional behaviour of the polymer up to the static
frictional resistance force is similar to that of a classical behaving material. Although for
polymers it is possible for the dynamic shea¡ resistance to peak at a critical velocity this
value could not be relied upon due to the unpredictability of earthquake excitation. For
the above reasons it would therefore non-conservative to assume a maximum frictional
resistance force of either F^ or it is possible that the critical resistance to shear

would come from the lower force, F¡.


4 (n
I

f År,
3.6. Specific Research Focus

While both static and quasi-static testing has provided data on initial shear bond, static
friction coefficients and the potential degradation of the materials, realistic dynamic
testing is required to quantify the influence of dynamic loading on the frictional
resistance of connections containing DPC membranes. The specific focus of the current
research project related to the DPC connection 'weak link' has therefore been the
undertakingof dynamic testing for the provision of information regarding the true
dynamic behaviour of connections containing DPC membranes commonly found in
Australian masonry construction. This experimental testing phase is presented in Chapter
4 where recommendations are made on the applicability of assuming static or quasi-static
friction coefficients for the seismic design of connections containing DPC membranes.

50
4. DYNAMIC SHEAR CAPACITYTESTS
ON URM CONNBCTION CONTAINING
DAMP PROOF COURSE MEMBRANE

4.1. Introduction

As highlighted in Chapter 3, concern that the shear capacity of connections containing


DPC membrane under true dynamic loading will be less than under static loading have
led to a series of dynamic shear tests being undertaken. The tests described in this
Chapter were therefore aimed at determining values of dynamic friction coefficients for
connections containing DPC membrane commonly used in Australian masonry
construction.

4.2. Dynamic Shear Tests


Dynamic shear tests were conducted on clay brick masonry connections containing a

variety of DPC membrane material on the eafthquake simulator at the Chapman


Structural Testing Laboratory, University of Adelaide. These have included standard
DPC, centered DPC and slip joint connection conhgurations and considered both in-plane
and out-of-plane shaking. The main advantages of dynamic testing, as opposed to quasi-

static testing, are firstly that true inertial loading can be generated in contrast to
displacement-controlled testing. Secondly, a frequency of loading more representative of
the frequencies normally associated with earthquake induced loading can be applied.

Since dynamic tests are generally more expensive than quasi-static tests, these were used

as 'spot checks' to determine to what extent the quasi-statically determined friction

5l
CHAPTER (4)- þnamic Shear Capaciry Tests On URM Connections
Containing Proof Course Membrane

coefficients were representative of those which could be expected in seismic events. A


comparison of dynamic and quasi-statically determined friction coefficients is therefore
presented in Section 4.4.

The earthquake simulator at The University of Adelaide consists of a 1400mm x 2000mm


shake table mounted on bearing runners and is connected to a 200kN INSTRON
load/displacement hydraulic actuator, which is rigidly connected to the laboratory strong

floor. The maximum vertical load capacity (on table) of the INSTRON is 66kN and has a
maximum horizontal displacement capacity of +125mm.

4.2.1. Instrumentation

Prior to and during slip, response accelerations of the applied weight, W, above the slip
interface and the reference acceleration at the shaking table were recorded. The
instruments used to measure these horizontal accelerations were Kistler Servo
Accelerometers powered by a servo amplifier.

To determine relative displacements of the test specimen above and below the friction
interface, absolute displacements at both the table and concrete slab above the connection
were recorded relative to a stationary datum. Table displacements were recorded
internally by the INSTRON controller. A Linea¡ Voltage Potentiometer (POT), mounted
to a rigid frame connected to the laboratory strong floor, was used to record the absolute
response displacement of the unit above the slip interface. The POT used was a Housten

Scientihc model 1850-050 having a maximum displacement capacity of 500mm and was
powered by a lOVolt DC supply.

The 'Microsoft Windows' based data acquisition system 'Visual Designer' was used to
collect the four channels of data from the two accelerometers, displacement POT and
INSTRON. Data was collected at a period interval of 0.008 seconds (l25Hz), which was
found to be sufficient to capture all relevant frequencies of the response. Since 'Visual
Designer' uses a buffer system to temporarily store data prior to saving to disc, care had
to be taken to ensure that the buffer was sufficiently sized to hold data for the full test.

52
CHAPTER (4)- Dynamic Shear Capacity Tests On URM Connections
Contøining Damp Proof Course Metnbrane

The overall test set up, location of instrumentation and data acquisition is shown
schematically in Figure 4.2.1.

Test specimen
Rigid frame fixed ûo
laboratory stong floor
Displacement
(POT) Accelerometer

INSTRON
Hydraulic
Accelerometer

Shaking table

lrrarÂ"*
F ^rfu-
ooo ooo
INSTRON conhol panel Data acquisition

Figure 4.2.1 Schenratic URM Connection Containing DPC Dynamic Test Set-up

4.22. Damp-Proof Course Membrane and Materials


For the various dynamic connection shear tests undertaken, four different types of DPC
membrane were tested, having been selected to match as closely as possible materials
used in previous quasi-static tests (Griffith & Page 1998). A brief description of each

DPC material tested is given in Table 4.2.1.

It should be noted that both the Polyflash and Dry-Cor membrane were not identical to
the products used in quasi-static tests. Although the membranes were produced from
similar materials they had a different commercial name and the thickness varied slightly.
Despite this it was expected that their frictional behaviour would be similar.

53
CHAPTER (4)- þnamic Shear Capacity Tests On (JRM Connections
Containing Damp Proof Course Mernbrane

T able 4.2.1 DFC Membrane Test Specinrens


CommercialName Description Nominal Thickness
Standard Alcor Bitumen Coated Aluminium 950 pmm
Super Alcor Bitumen Coated Aluminium 1550 ¡rmm
Polyflash Polyethylene/ Bitumen Coated Aluminium 650 pmm
Dry-Cor Embossed Polythene Plastic 850 pmm

Bricks used to construct the connections were standard 'Red' 3 hole extruded clay bricks.
These had the nominal dimensions 230x110x76mm. Mortar was bucket batched using a

l:1:6 cement:lime:sand mix where water was added by the tradesman to achieve a
reasonable workability. Including sand absorbed moisture this typically resulted in a

total batch water content of approximately 23Vo. Associated material tests including
mortar compressive strength and masonry modulus will be described later in Chapter 6.

4.23. Dynamic Test Methodology


As shown in Figure 4.2.2 a concrete slab of dimensions 1000 x 1400 x 100mm was used
to support lead ingots above the connection to be tested thus providing a total normal
weight, W, at the friction interface. By varying the number of lead ingots the normal
compressive force at the friction interface, N (=W), could be varied enabling dynamic
shear tests to be carried out at various levels of normal compressive stress.

While an earthquake event comprises a wide range of frequencies, dominant frequencies


of around 2-5Hz arsnot uncommon. For all the dynamic tests reported here inertial loads
were induced across the friction interface by applying a represent ative ZHz sinusoidal
displacement motion to the earthquake platform. The amplitude of the motion was
gradually increased until slipping occurred at the connection. Once slip occurred, the
dynamic inertia force, Fi, was determined as, Fi -'W x a.¡0, where â5¡p wôs the sliding
response acceleration sustained by the mass above the friction interface. Since the weight
was already in motion it was assumed that initial shear bond was not relevant so that the
entire resistance force was due to friction. Therefore, for horizontal equilibrium,
equating the inertia force with the dynamic frictional resistance force, F* the dynamic

54
CHAPTER (4)- þnarnic Sheør Capa.ciry Tests On URM Conn¿ctions
Containing Danp Proof Course Membrane

friction coef|lcient, ku¿you-i"could be determined. As indicated in Figure 4.2.2, kv<lræamic


can be seen to be equal to the response sliding acceleration, rkup, in units of g's.

kad ingots
R Sþ response
acceleration, 4¡n Fr=Ìüxa'þ
V/ F.=ku¿t*¡xN
But
Test connection Concrete Slab W=N
containing DPC
membrane t Fi=F
a .Iip (8's) = k
"¿yo*t
F-

2Hz sinusoidal
displacement motion Concrete Base

Earthquake simulator pladorm

Figure 4.2.2 Test Specimen Free Body Diagram: DPC Connection durirry Sliding

4.2.4. DPC Connection Tests

For both the standard and centered DPC connection test specimens, two rolvs of
brickwork, four bricks long and two courses high were used to support the concrete slab
and lead ingots. The total area of the friction plane was 194,300mm2. For standard DPC
connections the membrane was placed directly on top of the bottom course of bricks and
mortar placed on top of the membrane material. For centered DPC connections the
membrane was sandwiched between two mortar layers located centrally between the top

and bottom course of bricks. The overall layout of a standard DPC test specimen is
shown schematically in Figure 4.2.3.

For both the standard and centered connections the following membrane conf,igurations
were tested dynamically: I layer of Standard Alcor; 1 layer of Super Alcor; I layer of

embossed plastic; attd ,1 layer of Coated Aluminium. Although

these four tests were ca.rried out at oqy one of vertical compressive sffess
(0.1 both in-plane and out-of-plane shaking examined so that a total of eight

55
CHAPTER (4)- þnamic Shcør Capøcity Tests On URM Connections
Danp Proof Course Membrane

tests were undertaken. Figure 4.2.4 shows a photograph of the set up for a standatd
connection containing I layer of Standard Alcor to be tested in the in-plane direction.

Iæad Ingots Standard DPC


connection

Concrete

Concrete Base

simulator

Figure 4.2.3 Dynam¡c Test Set-up for Standard/Centered DpC Connection

Displacement
POT

Accelerometers

Shaking
direction
(h-plane)

Figure 4.2.4 Photograph of Standard DPC Connection Set up - In-plarrc

425. Slip Joint Connection Tests


The slip joint tests were conducted using a similar procedure to that for the DPC
connection tests. The main difference \ryas that the concrete slab plus lead weights were
supported by four bricks which were bedded directly onto the earthquake simulator using

a high strength dental paste. The membrane material was placed between the top of each
brick and the underside of the concrete slab. Slip joint connections containing the

56
CHAPTER (4)- þnanic Shear Capaciry Tests On URM Connections
Containing Damp Proof Course Membran¿

following membrane conflgurations were tested dynamically: 1 layer of Standard Alcor;


2 layers of Standard Alcor; 1 layer of embossed plastic; and 2 layers of greased

galvanised steel sheets. The slip joint tests rr¡vere performed over a range of three normal
compression stresses being 9,q4,_Q.J8 an{_0.33 MPa conducted only the in-plane
.\
direction. According,.ly, twelve tests' \ryere'bompleted. As for the DPC
'\- -,
multiple conf,rrmatory tests were also undertaken.

ingots
Slip Jointmembrane
between brick and slab

Concrete slab

Dental paste Earthquake simulator pladorm


In-plane shaking direction

Figure 4.2.5 Schemtic Diagram of Dynamic Test Set-up For Slip Joint Connection

Although some polishing of the concrete slab was observed after multiple tests this was
not found to greatly reduce the dynamic friction coefficient.

4.3. Results Formulation and Data Analysis

The basic procedure for the formulation of results, including the calculation of the
dynamic friction coefficients was the same for both DPC and slip joint connections. This
process included:

(1) calibration of raw output data to the required units;


(2) filtering of calibrated data;
(3) determination of the time of first slip;
(4) determination of slip acceleration and corresponding force;
(5) check slip force using displacement amplitude just prior to slip;
(6) plotting of the shear stress versus normal compressive stress; and
(7) determination of the dynamic friction coefficient as the gradient of the shear stress
versus normal compressive stress plot.

57
CHAPTER Ø)- Dynanic Shear Capaciry Tests On URM Connections
Containing Proof Course Membrane

43.1. Data Filtering

Since a zlfz sinusoidal displacement motion was input to the earthquake platform only
frequencies near this were considered to be relevant to the response. Figure 4.3.1 shows a

typical Fast Fourier Transform (FFT) of response acceleration data where the 2Hz
frequency amplitude is clearly dominant. In order to remove irrelevant noise frequencies
from the raw data a Fortran 77 band-pass filter program was specif,rcally developed for
these tests (the code is included in Appendix (A)).

350
I
300

250
€o
2N
e
150

100

50
J .I^
0
?clcgq?eqqgeqcqqqqeeq
octo{h\oræo\O
ÈÈÊÊcl
tr'requency (Fz)

Figure 4.3.1 Dominant Response Acceleration Frequencies

Extensive testing of this filter was undertaken to determine the most suitable band-pass
shape and provide an indication of the accuracy of the filter. It was found that a parabolic
sided band-pass filter gave the best results although the hrst and last second of data was
found to be slightly corrupted and as such were discarded. Although the filter program
allows any band-pass range to be set to best encompass the relevant frequencies full pass
was considered between 1.5 and2.5Hz reducing to zero at 0.5H2 and3.SHzrespectively
(refer Figure 4.3.2).

58
CHAPTER (4)- þnatnic Shzør Capøcity Tests On URM Conncctions
Containing Danp Proof Course Membrane

rI
1.2

zr
õ \
? o.a

é \
o.u
I \
I
F<
4. o.¿
I
\
?, o,
0
/
o N or¡s
o N o
FREQIIENCY (Hz)

Figure 4.3.2 Parabolic Sided Band Pass Filter - Bandlvidth

4.3 2. Dynamic Friction Coefficient Represent¿tive Calculation


The following Section provides a representative calculation of the dynamic friction
coefficient. Here a slip joint configuration with two layers of Standa¡d Alcor (refer Table
4.2.1), subjected to in-plane shaking with a normal overburden stress of 0.18MPa
(N=17.8kN) is used to illustrate the result formulation procedure.

Figure 4.3.3 shows the absolute displacement response of both the connection above and
below the slip interface relative to the stationary datum. Prior to 24.5 seconds both the
top and bottom units behave as one as the input table sinusoidal displacement motion is
gradually increased. At 24.5 seconds the connection's shea¡ resistive capacity is

exceeded and slip occurs. From this time on the frictional resistive force is proportional

to the dynamic friction coefficient, ku.¿vou-i". Since this is slightly less than the static
friction coefficient there is a respective decrease in the sinusoidal response displacement
amplitude that the unit above the connection can sustain during sliding. The response
accelerations of the unit above the interface are recorded as is shown in Figure 4.3.4.
Here a maximum of 0.469 is observed. The dynamic friction coeff,rcient is then

determined directly from the slip acceleration as 0.46. From the acceleration response
data, hysteresis behaviour can also be developed as shown in Figure 4.3.5. The

maximum dynamic frictional resistive force can be determined as the top and bottom
plateau of each hysteresis loop as 7.7kN.

59
CHAPTER (4)- þrnmic Shear Capaciry Tests On URM Connections
Containing Danp Proof Course Membrane

Absolutc Dlsplacements Displacement belotÃ, connection

- Displacemøt above connection


60
Unit above connection moves
-
to one side due ø slightly different
frictional behaviou¡ in eiiber shaking
40 di¡ection. The average of botb directions must th¡efo¡e be considered.

E 'rn
È
Ëo
o
g o o
Ê
c
-20 ôl
oc
m
ô¡
{cì
c! d

ô!
\o
d
Ê
40
First slip hls 6çPuI€d at 24.5 s€cs
-60
Tlrne (secs)

Figure 4.3.3 Relative Connection Displacenrcnts

a(sllp) Just Aftor Xìrst Sllp V's Tlme


Fllûercd ave alnax (after first slip) = kv = 0.469
0.5
0.4
0.3

e 0.2
0.1
6 0
o
o q
æ \o
a
çq (ì
a
g
g
-0.1
çN c¡ a.¡
\o
N
-0.2
-0.3
-0.4
-0.5
Tlme (secs)

Figure 4.3.4 Response Acceleration above Slip Interface during Slipping

Hystereüc Behavlour
Fllte¡ed Ff(max) = 7.7 kN = amx N
l0
7.5

5
z
.¡a 2.5
o
o 0
f¡r n q)
t-
n
Ê -2.5 e.¡
N N
(t)
-5

:7.5

-10
Reladve Jolnt Dbplacemcnt (mm)

Figure 4.3.5 llysteresis Behavior¡r after Slip showing Maximum Shear Resistive Force

60
CHAPTER (4)- þnamic Shear Capacity Tests On URM Connections
Containing Darnp Proof Course Membrane

4.33. Theoretical Check


To check that recorded accelerations were of the correct order the following calculation
was undertaken for all tests.

The steady-state displacement response of a single degree of freedom system (SDOÐ


subjected to harmonic loading is of the form:

u(t;=Asin(CIt-0) (4.3.1)

where u(t) = displacement response


A = Displacement amplitude
6 = Angular frequency =2ftf
/= Frequency

0 = Phase angle

By integrating and double integrating this both the velocity v(t), and acceleration a(t)
response can be determined respectively as:

v(t) = -A sin (ot - e) (4.3.2)

a(t) = -Aõ2 sin (õt - 0) (4.3.3)

The maximum acceleration therefore occurs when sin(õt - e) = I and is given as:

âunx = l-eot l= l-Nzrrn'l Ø3.4)

For the case of a 2Hz sinusoidal response, the maximum acceleration is related to the
amplitude of the displacement response by:
Írnax= l-n4ù'l =157.94 1mm/s2)

For the example in Section 4.3.2, A at slip = 28.5mm implies


ârnx = 157.9 x28.5t(9.81x 103) = 0.46 g

This agrees thereby confirming that the acceleration data (and hence friction coeff,rcients)
were consistent.

6t
CHAPTER (4)- þnamic Shear Capacity Tests On'URM Connections
Containing Proof Course Membrane

4.4. Dynamic Test Results

4.4.1. DPC Connection Dynamic Test Results

Representative DPC connection test data is presented in Appendix (B) in a similar format

to that described in Section 4.3.2. A summary of results for standard DPC connection is
given below in Table 4.4.1 and presented graphically in Figure 4.4.1. Similarly a

summary of results for centered DPC connections is given in Table 4.4.2 and presented
graphically in Figure 4.4.2.

/
1 4.4.1 Results Sumrmry for Standard DPC Connection Tests

(/'
a\ Standard DPC Connection Normal Normal flma* FL Shear k v.dynamic
'1
0/ (Ref. Table 4.2.1) Force Stress Stress
(kN) (MPa) (g) (kN) (MPa)
/^\ 1 Layer Standard Alcor 31.9 0.164 0.44 14.0 0.072 0.44
LI
( 1 Layer Super Alco¡ 31.9 0.164 0.47 15.0 0.077 o.4l
1 Layer Polyflash 3r.9 0.764 0.37 1 1.8 0.061 o.37
I Layer Dry-Cor 31.9 0.164 0.36 11 .5 0.059 0.36

0.09
(Super Alcore)
0.08
0.07 Linea¡ (Polyflash) a
cl
È
-Linear
--- -Linear
0.06 -- (Standa¡d Alcore)
À =l(
ø
o
q)
0.05 Linear (Dry-Cor) tfJ
L
(t) 0.ù1
¡r
co) 0.03
v)
-
0.02 Slope defines dynamic
0.01 coeffrcient of friction

0.00
0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18

Normal Stress(MPa)

Figure 4.4.1 Graphical Results Sumrnary for Standard DPC Connection Tests

62
CHAPTER (4)- Dynnmic Shear Capaciry Tests On URM Connections
Containing Damp Proof Course Membrane

Table 4.4.2 Results Sunmnry for Centered DPC Connection Tests

Standard DPC Connection Normal Normal ânnx Fr Shear k v.dFamic


(Ref. Table 4.2.1) Force Stress Stress
(kN) (MPa) (e) (kN) (MPa)
1 Layer Standard Alcor 3t.9 0.164 0.31 9.9 0.05r 0.31

1 Layer Super Alcor 3r.9 0.164 0.35 tt.2 0.057 0.35

1 Layer Polyflash 31.9 0.164 0.38 t2.t 0.062 0.38

1 Layer Dry-Cor 3r.9 0.t64 0.41 13.1 0.067 0.41

0.08
(Super Alcore)
0.07 X
Linea¡ (Polyftash)
îÈ 0.06 -Linear
- - - - - -Linear (Standard Alcore) a
¿ 0.05
6
ø
c)
Linea¡ (Dry-Cor)
0.04
U)
¡r 0.03
6l
O
(t) 0.02

0.01

0.00
0.00 0.o2 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18

Normal Stress(MPa)

Figure 4.4.2 Graphical Results Sumrmry for Centered DPC Connection Tests

On completion of the dynamic tests the connection was examined to determine at which
interface slip had occurred. For centered DPC connections slip was always observed
between the mortar and DPC membrane and for standard DPC connections slip was
always observed between the brick and DPC membrane.

rüith the exception of embossed polythene (Dry-Cor) and Polyflash membrane, the
dynamic friction coefficient for centered DPC connections \Mere less than for standard
DPC connections. In contrast, other researchers (Page 1994) have reported static friction
coefficients for centered DPC connections usually greater than for standard DPC

63
CHAPTER (4)- þrumic Shear Capaciry Tests On URM Connections
Containing Damp Proof Course Membrane

connections. This difference is attributed to a high dependency on workmanship, as any


irregularity in the mortar bed below the membrane will significantly impact on the
frictional properties of a centered DPC connection. As such, comparison of the frictional
behaviour of these connections, with other researcher's results, is difficult.

As mentioned in Section 3.3.4 previous resea¡chers have found that for a given roughness
of flashing material, stiffer DPC membranes produce higher coefficients of friction and
are more likely to be affected by the properties of the support. The dynamic test results
imply that the mortar-DPC sliding plane of the centered DPC connection provided less
frictional resistance than the brick-DPC sliding plane of the standard DPC connection.
This indicates that the stiffness of the support mate¡ial on either side of the membrane
had a significant effect on the friction behaviour for the relatively stiffer Alcor
membranes. Further the Polyflash and embossed polythene, which were less stiff,
frictional properties did not appear to be as greatly effected by the properties of the
supports but were dominated by the behaviour of the DPC membrane.

4.42. Slip Joint Connection Dynamic Test Results


Representative DPC connection test data is presented in Appendix (C) in a similar format

to that described in Section 4.3.2. Results of dynamic stip joint shear tests at various
levels of normal compressive are presented in Figure 4.4.3 to Figure 4.4.5 for out-
of-plane loading and Figure 4.4.8 for in-plane loading. The dynamic
2.4.1
\
friction coefficient, as the gradient of the-lirea¡-regression line. The
embossed plastic (Dry-Cor) slip joint connection shear test was only completed at one
level of normal compressive stress (0.33MPa) where the dynamic friction coefficient was
0.41. Comparison of the in-plane and out-of plane plots indicated that no significant
difference was apparent in the dynamic friction coefficient obtained for the two loading
directions. This is attributed to there being no distinct difference in the roughness of the
brick fo¡ the two directions. Consequently no further distinction will be made with regard
to loading direction.

1
I ìI

64
CHAPTER (4)- Dynamic Shear Capacity Tests On URM Connections
Containing Damp Proof Course Membrane

(d
0.15
ê.
à
Ø 0.10
.t)
c)
€k
V)
L 0 .0 5

o)
V)
0.00
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35
Normal Stress (MPa)

Figure 4.4.3 Out-of-plane Slip Joint -l Layer of Standard Alcor

0.20
)
(n
À
à 0. 1 5 v =0.47x
Ø
.t)
o)
t< 0. 1 0
V)
li
o 0 .05
(t)
0.00
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35
Normal Stress (MPa)

Figure 4.4.4 Out-of-plane Slip Joint Test - 2 Layers of Standard Alcor

e
À
0.05

eØ o.o4
Ø
g 0.03
(t)
E
C)
0.02
Ø 0.01
0.00
0.00 0.0s 0.10 0.15 0.20 o.25 0.30 0.35
Normal Stress (MPa)

Figure 4.4.5 Out-of-plane Slip Joint Test - 2 Layers of Greased Galvanised Steel

65
CHAPTER (41 þnatnic Shear Capacity Tests On URM Connections
Containing Damp Proof Course Membrane

0.20
(!
ô-

E
Ø
0.10
L
V)
1ù'' =o'44x
þ
o)
0.0s
Y

u) o.oo
0.00 0.0s 0.10 0.15 0.20 0.25 0.30 0.3s
Normal Stress (MPa)

Figure 4.4.6 In-plane Slip Joint Test Resr¡lts - 1 Layer of Standard Alcor

0. 20
À

l<r
À 0. I 5
.t)
.t)
(l)
È
0. I 0
U)
¡r
cl
o) 0.05
v)
0.00
0.00 0.05 0.10 . 0.15 0.20 0.25 0.30 0.35
Normal Stress (MPa)

Figure 4.4.7 In-plane Slip Joint Test Results - 2 Layers of Standard Alcor

0.04
)
C€
lJi
à 0.03 Y= 0'lx
Ø
Ø
6)
È 0.02
U)
L

a
0.01
c)
v)
o
0.00
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35
Normal Stress (MPa)

Figure 4.4.8 In-plane Slip Joint Test Resr¡lts - 2 Layers of Greased Galvanised Steel

66
CHAPTER (4)- þnamíc Shear Capaciry Tests On URM Connections
Contøining Damp Proof Course Membrane

4.43. Comparison of Dynamic with Static and Quasi-Static Test Results


Table 4.4.3 and Table 4.4.4 respectively present a comparison of friction coefficients for
standard DPC and slip joint connections determined statically and quasi-statically by
previous research and dynamically as part of the current resea¡ch project.

Table 4.4.3 Standard DPC Connection Friction Coefficient Comparison

Joint Type Friction Coefhcient, ku Dynamic (%)


Static Quasi-static Dynamic Quasi-Static
Page Griffith et al
/1994) (1998)
1 layer of Standard Alcor 0.460 0.520 0.43 827o
2layer of Standard Alcor 0.470 0.569 0.46 817o
I Layer Dry-Cor (Embossed plastic) 0.304 o.267 0.41* N/A
2Layerc of Greased Galvanised Steel 0.074 0.108 0.11* lOOTo
* Not same commercial product as used in the quasi-static tests

Table 4.4.4 Slip Joint Connection Friction Coeffcient Comparison

Joint Type Friction Coefficient, k,, Dynamic (7o)


Static Quasi-static Dynamic Quasi-Static
Page Griffith et al
(tee4) (1ee8)
Standard Alcor 0.44 N/A
Super Alcor o.527 0.541 0.47 87Vo
Rencourse/Polyflash 0.259 0.3r7 o.37* N/A
Embossed Polythene/Dry-Cor o.397 0.329 0.36* N/A
* Not same conìmercial product as used in the quasi-static tests

Since by necessity the geometry of the quasi-static and dynamic testing apparatus were
not identical the direct comparison of results is somewhat limited. However, an indicative
comparison of results is still useful. It is of particular interest to note that the value of the
dynamic friction coefficient divided by the quasi-static result (as a percentage). For the
membrane qrpes, which \ilere coflìmon to both sets of tests, the dynamic friction
coefficients were greater than or equal to 80Vo of the quasi-static test value. For all
membranes, except the greased galvanised steel, the dynamic friction factor was also
found to be greater than the 453700-1998 code prescribed design value of 0.30.

67
CHAPTER (4)- þnamic Shear Capacity Tests On URM Connections
Containing Damp Proof Course Membrane

4.5. Summary and Conclusion: ImplÍcation for Design


The results of dynamic shake table tests on DPC and slip joint connections which are
typically used in unreinforced masonry construction in Australia have been presented.
The main purpose of these tests was to evaluate the connection performance under
dynamic loading in order to assess their seismic integrity. Dynamic friction coefficients
determined from these tests were then compared with qtrasi-static friction coefficients
determined by previous research (Griffith et al 1998) to assess to what extent the quasi-
statically determined friction coefficients represented those which could be expected in
seismic events. Here it was found that the dynamic friction coefficients were not more
than 20Vo less than those determined quasi-statically. Further, with the exception of
greased galvanised sheets no connection had a friction coefficient less than the 453700-

1998 code prescribed design value of 0.3. Additionally the observed 'seismic strength
capacity' of the connections considered were greater than the 'seismic load demand'
calculated by Klopp for most of the eleven buildings he analysed.

68
5. STABILITY OF SIMPLY SUPPORTED
URM WALLS SUBJECTED TO
TRANSIENT OUT-OF.PLANE FORCES

5.1. Introduction
(Paulay & Priestþ 1992) have described the response of masonry walls to out-of-plane
seismic excitation as:

" one of the most complex and ill-un-derstood areas of seismic a nalysis"

Traditionally designers have perceived URM as a brittle form of construction, and thus
considered it particularly sensitive to peak ground accelerations. In contrast, recent
research has shown that dynamically loaded IIRM walls may sustain accelerations well

exceeding their elastic capabilities (ABK 1985, Bariola 1990, Lam 1995). This apparent
anomaly points to our lack of understanding of the true collapse behaviour of URM
walls.

The complexity arises from the fact that the response can be highly non-linear as the
behaviour is largely governed by stability mechanisms rather than material failure. Not
surprisingly, when compared with other areas of structural and earthquake engineering,
the current knowledge of the out-of-plane behaviour of masonry walls to seismic loading
is sparse.

Figure 5.1.1 shows a fypical outof-plane wall failure in the upper story of a URM
building during the 1989 Loma Prieta, California earthquake.

69
CHAPTER (5)- Stability of Simply Supported URM WaIIs
Subjected to Transient Out-of-Pløne Forces

Figure 5.1.1 Out-of-plane Wall Failure during Lonra Prieta Earthquake, 1989

The following sections review important rispects of the behaviour of URM walls when
subjected to transient out-of-plane forces. Previous experimental and analytical work is
discussed and followedby a critical review of the current analysis and design
methodologies. This Chapter concludes with both the specific experimental and
analytical resea¡ch focus to be addressed within the scope of this report.

5.2. Fundamentåls of Out-of-Plane URM Walt Behaviour


The lateral strength capacity of a simply supported URM walls s,uþjscted to out-of-plane
loading depends on many variables. Possibly the most fundamental of these is the
manner of spanning of the wall between supports. In the simplest case a vertically
spanning wall is supported only at the top and bottom so that under out-of-plane loading
a vertical one-waj'bending action develops. Since vertical movement at the top support is
not restrained any applied vertical compressive force remains constant regardless of any
elongation of the tension face during loading. This type of wall can be related to either
loadbearing or non-loadbearing internal LIRM partition walls (without returns) or very
long URM walls where the side boundary conditions do not significantþ impact on the
wall behaviour.

70
CHAPTER (5)- Stability of Simply Supported URM Walk
Subjected to Transient Out-of-Plane Forces

When return walls or engaged piers are more closely spaced, the wall's response to out-
of-plane loading becomes more complicated, consisting of combined vertical and
horizontal bending. These walls are therefore referred to as two-way spanning walls and
tend to have an increased lateral force resistance capacity over that of a simila¡ sized but
one-way spanning wall. Further complications arise since brickwork is strongly

anistropic, i.e. behaving differently in orthogonal directions. Depending on the number


and nature of supported edges, various cracking patterns are also possible, thus affecting

the lateral resistive capacity of the wall. Over the past 30 years a number of static testing
programs have been completed on the two-way bending of URM wall panels (Baker
1973, Hendry 7973, West et al1973:1977, Lawrence 1975:1994, DeVerkey et al 1986,
Drysdale et al 1988) resulting in several static analysis techniques. The most recent of
these is the Virtual Work Method (Lawrence 1998) where internal and external work are

equated. Due to the complexity of the problem, however, as yet no static analysis

methodology has been readily evolved into a dynamic analysis procedure.

7 Another category of URM wall commonly found in Australia is the full infill panel where
ti
a masonry wall is constructed within a framed construction without gaps. In this case,
under lateral load, elongation of the tension face due to bending can not occur without
inducing a large compressive force from the surrounding frame, which acts as a rigid
abutment. This results in an arching behaviour where the vertical compressive force
increases with mid-height displacement. On further increasing lateral load the vertical
compressive forces become suff,rciently large to crumble the brickwork at vertical

reaction points. This material failure permits further displacement of the wall as its
length is reduced until ultimately instability occurs. However, a lateral strength capacity
typically much greater than one or two-way bending walls is realised. As the wall's
ultimate behaviour is dominated by progressive damage and material failure, a 'quasi-
static' analysis is often used to assess the peak lateral capacity of these walls. Various
researchers have addressed the out-of-plane behaviour of this type of wall resulting in
static arching analysis procedures (Baker 1978, Hendry 1981, Abrams et al 1996). In
Australia many inhll panels are constructed with a gap at the top, filled with mastic or

7l
CHAPTER (5)- Støbiliry of Simply SupportedURM Walts
Subjected to Transient Out-of-Plane Forces

sealant, and a gap at the sides with special connectors to allow for brick expansion. This
type of wall is therefore a special case of two-way spanning wall.

As a first stage in the development of a method that may also be applicable as a


component of the more complicated dynamic two-way behaviour, an understanding of
the physical process underlying one-way dynamic action must first be developed.
Consequently, the fundamental focus of the current research project has been the
experimental and analytical evaluation of the dynamic behaviour of one-way bending
URM walls.

For the one-way bending failure of URM walls there are three key contributing
phenomenon; (1) tension cracking of the masonry, (2) compression crushing of the
masomy at the vertical reactions (including mid-height) and (3) ultimate instabitiry of the

wall. Unless the walls have very high compressive axial loading, crushing is rarely
significant. Since in Australia overburden stresses are generally relatively low, local
crushing at vertical ¡eactions is not a major problem. Hence, cracking and instability of
the wall typically dominate the ultimate behaviour.

Another distinguishing aspect of URM walls subjected to out-of-plane forces is whether


the loading is a gradual monotonically increasing static load, or a more rapid and
reversible dynamic load. This distinction is drawn as 'dynamic stability' concepts,
discussed further in Section 5.3.2, contribute to the walls lateral force resistive capacity.

When a one-way spanning wall is dynamically loaded in the out-of-plane direction an


inertia load is induced into the masonry wall. Prior to cracking, the wall essentially acts
elastically where deformations are relatively small and hence do not significantly impact
on the distribution of inertia force. The accelerations felt by the wall can therefore be
obtained by averaging the input accelerations at the top and base of the wall. Should the
applied accelerations exceed the elastic capacity of the wall, cracks will form at locations
of maximum moment i.e. the top and base support and near the mid-height of the wall. If
the top and base crack occur first the theoretical position of the span crack will be

72
CHAPTER ( 5 )- Stability of S imply Supp orte d URM Wølls
Subjected to Transient Out-of-Plarc Forces

determined by the relative value of the induced moment at these locations. These

moments can be related to the eccentricity of the vertical reaction forces and are therefore

dependent on the connections forming the boundary conditions. Typically, the crack
occurs near the mid-height of the wall as the bending moment diagram in this region is
usually reasonably flat, generally only varying by 1l7o from the mid-height to the three
quarter height of the wall (Phipps 1994). Practically, the crack will only appear at a
mortar joint and will therefore depend on the relative weakness of individual mortar
joints in the region ofpeak stress.

As was discussed in Section 2.3, the 1989 Newcastle earthquake highlighted that the
condition of both new and existing LJRM building stock is generally unknown with poor
maintenance and workmanship common place. Further, many existing URM buildings
are already cracked due to low strength mortar, settlement of footings, or temperature and
moisture changes. Past earthquakes and/or accidental damage may also have previously
induced cracking. Despite this many severely cracked masonry buildings are often still
standing after earthquakes and have been able to resist strong aftershocks. Following
these observations it is pertinent to examine the post-cracked seismic resistance of simply
supported tlRM walls.

5.2.1,. Post-cracked Force-Displacernent (F-^) Relationship

Once cracking occurs three joints are formed at the top, mid-height and base of the wall,
such that the portions of the wall above and below the mid-height crack act as free
rocking bodies'
__j

The non-linea¡ F-Â relationship of a face loaded IJRM wall results f¡om the complex
interaction of gravity restoring moments, the movement of vertical reactions with mid-
height displacement and P-Â overturning moments. A coÍImon simplification is to
approximate the two free bodies as rigid thus having an infinite material stiffness as
shown in Figure 5.2.1. I-ateral load is initially resisted by gravity restoring moments due
to self-weight and applied overburden loads with the vertical reactions at the three joints
acting at the extreme compressive faces of the wall. This initial rigid resistance is termed

73
CHAPTER (5)- Stability of Sinply Supported URM Wøtts
Subjected to Transient PI¿ne Forces

the 'rigid threshold resistance' force, R"(l) and is related to wall geometry, overburden
and eccentricity of the vertical reactions and thus the wall boundary conditions.

'Peak Rigid Resistance Threshold' Force

R"(l) Rigid Infinite Initial Stiffness


\ Idealised Rigid Bi-linear F-Â Relationship
\
zJ¿ \ 'Peak Semi-rigid Resistance' Force
(B
È R*(1 Real Semi-rigid Non-linear F-Â Relationship
qt
o
o
f¡i
\ Rigid Incipient
3H \ Instabiliry
E

\ ( Displacement
€o \
\
Þ. \
È \
\
\
\
Mid-height Displacement ( A)
\rr, ¡o6 ¡¡¡y &rs ubìatyiígid )
(A) (B) (c)
Overburden
Force = O

Self weight
above crack
='ttrI12

Âc A¡or¡o6¡Y.¡y

Base reaction
=O+W

Figure 5.2.1 Reat Semi-rigid Non-linear X'orceDisplaccnænt Relationship

74
CHAPTER (5)- Stability of Simply Supported URM Wølls
Subjected to Transient Out-of-Plane Forces

When the lateral force exceeds R*(l), a mid-height displacement occurs, permitted by the
rigid rotation at the three joints. P-À effects then reduce the gravity restoring moments as

the resultant of the vertical forces above the mid-height crack moves toward the wall's

back compressive face. With further displacement P-À effects continue to reduce the
lateral resistance of the wall creating a negative stiffness arm, Ç(1), of the bi-linear F-A
relationship (refer Figure 5.2.1). \ilhen the vertical force resultant above the mid-height
crack moves outside of the wall thickness the resistance to overturning is reduced to zero.
The displacement at which this occurs is termed the 'rigid instability displacement',
Ainstabilitfrigid).

For a real URM wall, the brickwork comprising the two free bodies does not have an

infinite stiffness and as such does not behave completely as assumed by the idealised
rigid body theory. Instead the real semi-rigid F-À relationship for the rocking system is
more complicated and non-linear than that of the idealised bi-linear rigid F-A
relationship.

More realistically, in the vertical position prior to lateral load being applied, all vertical
reactions act along the centerline of the wall. Consequently, any applied lateral load will
cause a mid-height displacement to occur. This then forces the vertical reactions at the
joints to move towards the extreme compressive faces of the wall, thus increasing the
gravitational restoring moment lever arm (refer Figure 5.2.1 (A)). The rate at which the

reactions move is proportional to the rate of loading and modulus of the brickwork. On
further displacement the lateral resistance continues to increase due to the movement of
the vertical reactions increasing the gravity restoring moments at a greater rate than the

reduction caused by the P-A effects. At a critical displacement, when the stabilising
^",
effect of these two opposing actions equalize the peak 'semi-rigid resistance th¡eshold'
force, R*(l), is realised (refer Figure 5.2.1 (B)). The higher the modulus of brickwork
the closer the scenario is to that of the rigid assumption. As a result the closer the critical

displacement will occur to the vertical position and the higher the relative value of 'semi-
rigid resistance threshold' force. Beyond the non-linear relationship approaches the bi-
^c
linear rigid relationship as the vertical reactions are forced into the extreme compressive

75
CHAPTER (5)- Stability of Simply Supported URM Walls
Subjected to Transient Out-of-Plane Forces

zones. The curves do not converge, however, due to the finite compressive stress block
at the vertical reactions (refer gap Figure 5.2.1). The larger the overburden and the lower

the brickwork modulus the larger the gap.

For a static lateral load scenario, beyond the 'threshold resistance', regardless of whether
rigid or semi-rigid behaviour is considered, survival of the rocking wall is dependent on
the removal or reduction of the static load. Here the wall is said to be in 'unstable
equilibrium'. At any displacement, prior to the instability displacement being reached, if
the load is statically removed the wall unloading F-A relationship will trace back the
loading relationship to the vertical position.

As the wall mid-height is displaced its potential energy (PE) is increased with the raising
of the wall's center of gravity to a maximum at the incipient instability displacement.
Thus, in a dynamic lateral load scenario, survival of a wall beyond the 'threshold limit' is
dependent on whether or not the inertia force has sufficient energy to overcome the
increased potential energy (PE) so as to further increase the displacement to incipient
instability. This energy requirement can be related to the kinetic energy (KE) or velocity
of the rocking wall as it passes the static vertical alignment plus any additional input

energy that may occur within the failure half cycle. If insufficient energy is available and
instability does not take place, the PE which is a maximum at the peak half cycle
displacement, is converted back to KE by the gravitational restoring moments. As such,

the wall's F-A relationship will trace back the loading relationship forming a naffo\¡/
hysteresis loop due to energy losses in joint rotation. As the wall again passes the static
vertical alignment the KE is at a maximum (since the velocity is a maximum) and PE is
zeÍo. Again, KE is converted to PE with displacement in the opposite direction. This
exchange ofenergy continues as free vibration until energy losses reduce the total system

energy to zero. At this time the wall has returned to the vertical position. Provided the
three joints have not degraded through impact or joint dislocation on re-loading, the wall
will have a similar F-A relationship and dynamic behaviour.

76
CHAPTER (5)- Snbiliry of Simply Supported URM WølIs
Subjected to Trønsient Out-of-Plane Forces

Since the non-linear F-A relationship also largely governs the frequencydisplacement (/-

A) relationship of a rocking wall system, this is also highly non-linear. The non-linearity
can be illustrated by a comparison of secant stiffness at low and high levels of
displacement amplitude. Here the secant stiffness is associated with the effective

average half cycle secant stiffness. At low displacement amplitude the secant
^{-,
stiffness K¡, is substantially larger than at large displacement amplitude Ân, where the
secant stiffness is Ks (refer Figure 5.2.2). Since the secant stiffness is directly
proportional to the square of the haH cycle natural frequency it can be shown that the

frequency at low displacement amplitude is relatively large and reduces to zero at the
incipient instability displacement. Figure 5.2.2 also shows a schematicf relationship.

The schematic/-A relationship shown in Figure 5.2.2 is somewhat idealised as it is ra¡e


for frequencies nea¡ to the incipient instability displacement to occur so that a lower
frequencies limit, fi.¡t, is often observed. V/hile it is theoretically possible for
frequencies below/¡¡6¡ to occur they are unlikely as the system becomes unstable at these
displacements for reasons described below.

As already discussed the F-A relationship of URM walls are highly non-linear and as a
consequence the responses have no unique natural or resonant frequency. It has however
been shown that URM walls undergo larger displacement amplification at certain forcing
frequencies. This indicates that they have a unique effective resonant frequency being
related to the forcing frequency associated with the largest displacement amplification in
a simila¡ fashion to the natural frequency of an elastic system. For the non-linea¡ rocking

URM wall systems, the maximum displacement amplification will result when the

applied forcing frequency is derived from the average secant stiffness of the half cycle
under consideration. Thus, for the critical case where the maximum half cycle
displacement reaches the incipient instability displacement, Âinsrablity, the associated
effective resonant frequency,,f"n is related to the average incremental secant stiffness,
Ku,,", determined from the vertical to incipient instability displacements (refer Figure
s.2.2).

77
CHAPTER (5)- Stabiliry of Simply Supported URM Walls
Subjected to Transient Out-of-Plane Forces

During any transient excitation the wall displacement response increases and the response
frequencies decrease in accordance with the average half cycle secant stiffness. It is rare
for the frequency response to pass through the effective resonant frequency as the
likelihood of instability is increased with the increasing displacement amplification. The
effective resonant frequency thus provides the observed lower frequency limit so that

r _r
Jetr - Jlimit

The effective resonant frequency therefore also provides the corresponding maximum
expected average cycle mid-height displacement, Âr¡-¡t before collapse (refer Figure
s.2.2).

K¿> Kø
\z Real Semi-rigid Non-linea¡ F-Â
Jl Relationship
È
d
o
o Average instability cycle
q.
incremental secant stiffness
Ec.)
ct
Ec)
o.
o.

A¡nstabitity
N
Mid-height Displacement (Á)
6 * lK"
(.) f"
Frequencies d¡¡¡ are theoretically

t)
f, * {K, possible but a¡e unlikely, as more
g
f¡.
q)
2r rt¡n¡, n lr*" likely that instability would occur
with displacement amplification
ólL
À
ø
ú
c)

_1
lm¿, - Jave =fefr
fn
fi¡75¡aþ¡¡¡¡y
Ar
Mid-height Displacement (/)
Figure 5.2.2 Post-cracked Frequency-Displacenænt Relatioruhip

78
CHAPTER(5)- Stability of Simply SupportedURM Walls
Subjected to Trønsient Out-of-Plane Forces

5.2.2. Boundary Condition Impact on Force-Displacement Relationship

The types of wall support comprising the wall boundary conditions are an important
aspect that must be considered when assessing out-of-plane URM wall behaviour. To
some extent these determine the moment induced into the wall under lateral loading in

relation to the eccentricity of the vertical reaction forces at the joints. Typical

connections used in Australian masonry construction, such as DPC and 'timber top plate'

connections, have been reviewed in Section2.3.

In URM wall construction, connections to concrete footing beams and floor slabs

containing DPC membrane at the top and base wall supports are commonly used to meet
serviceability criteria. Consequently, at large mid-height displacements the vertical
reactions at the top, middle and base supports will all have been forced to the extreme
compressive faces of the wall. Thus, in comparison with other boundary conditions,
which do not force the vertical reactions to the wall edge, this scenario provides the
greatest 'rigid resistance threshold' force, R"(1), due to the larger overburden force lever

arm providing a maximum restoring moment. In Appendix (D) a generic calculation of


the bi-linear F-A relationship is presented for the concrete slab support at the top and
bottom connections. The generic defining terms Re(l), Ke(1) and Ai,'rauiuty (rieid) of the
rigid bi-linear F-A shown in Figure 5.2.2 arc summarised in Table 5.2.1 for these
boundary conditions as rigid loadbearing simply supported: top and base vertical
reactions at the leeward face (LBSSLL).

A second conìmon URM wall support, which is used in single storey URM dwellings, is
the connection of the timber roof truss to the masonry wall via a 'timber top plate' where
the wall base is set on a concrete slab and DPC connection. As the 'timber top plate' and

truss generally provide little rotational support even at large mid-height displacements the
top vertical reaction remains near the centerline of the wall, while the middle and base are
forced to the extreme compressive faces. With a reduced overburden force lever arm,
compared with the concrete slab above case, the 'rigid resistance threshold' force, R.(1),

is also respectively reduced. In Appendix (D) a generic calculation of the bi-linear F-A
relationship is presented for 'timber top plate' above and concrete slab below boundary

79
CHAPTER (5)- Stability of Simply SupportedURM Walts
Subjected to Transient Out-of-Plane Forces

conditions. The generic defining terms Re(l), Ke(l) ând ¡os¡¿6¡ty (rigid) of the rigid bi-
linear F-Â are sunìmarised in Table 5.2.1 for these boundary conditions as rigid
loadbearing simply supported: top vertical reaction at the centerline and base vertical
reaction at the leeward face (LBSSCL).

Table 5.2.1 also presents the generic def,rning terms &(1), &(1) and A¡r¡u5i¡¡r.¡g¡¿, for
other wall boundary conditions also relevant to Australian masonry construction
including rigid parapet (P), rigid non-loadbearing simply supported (NLBSSCL) and
rigid loadbearing simply supported at the centerline (LBSSCC). For walls with an applied

overburden stress, oo, the overburden factor, y, is defined as, +, where M is the
Ms
total wall mass.

Table 5.2.1 Rigid Bi-Linear F-À Relationship - Various Boundary Conditions

Support Type Support Type &(1) K(1) A^øUilitv


Abbreviation
Rigid Parapet (P) h -h t
gt b
û

Rigid Non-loadbearing Simply (NLBSSCL) 4.0 h -4.0h t


Supporæd:base Reaction at the gt o
b
I-eeward Face

Rigid Loadbearing Simply Supported (LBSSCC) 2.0(1+v)h -4.0 (l + v)h 0.5t


:Top and Bottom Vertical Reaction at gt o
Þ
the Centerline

Rigid Loadbearing Simply Supported (LBSSCL) 4.0 (l+7¿\¡) h -4.0 (l + V)h (l#/tv\ t
:Top Reaction at Centerline and Base gt o
b (l+v)
Reaction at The læewa¡d Face
%t(¡"s¡,¡x,(t
Rigid hadbearing Simply Supported (LBSSLL) 4.0(l +v)h -4.0 (l + v)h t
:Top and Base Vertical Reactions at gt o
the Leeward Face

[=

Table 5.2.1 shows that for most of the support conditions, with the exception of LBSSCC
and LBSSCL, the mid-height displacement at which static instability occurs is the
thickness of the rigid object (t). For the loadbearing simply supported object with top and

80
CHAPTER(5)- Snbiliry of Simply SupportedURM Walls
Subjected to Transient Out-of-Plane Forces

bottom vertical reactions at the centerline (LBSSCC) the mid-height displacement at


static instability occurs at half the thickness of the rigid object. For the loadbearing
simply supported object with the top vertical reaction at the centerline and the base
vertical reaction at the leeward face (LBSSCL) the mid-height displacement at which
static instability occurs is dependent on the ratio of self-weight to the applied overburden.
If the applied overburden is much greater than the seH-weight the mid-height instability

displacement approaches 75Vo of the thickness of the rigid object. If the self-weight is

much greater than the applied overburden the mid-height instability displacement
approaches the thickness of the rigid object. Accordingly the static mid-height instability
displacement is always between 3/r t and t.

5.23. Un-cracked Force-Displacement Relationship


In the un-cracked wall behaves essentially elastically where the lateral force
resistance increases linearly with displacement. Here the lateral elastic capacity is
governed by the tensile strength of the brickwork plus any compressive load due to
gravity. Once the elastic capacity has been exceeded, cracking takes place and the wall's
lateral force resistive capacity reverts to that of the cracked wall governed by the semi-

rigid non-linear F-Â relationship, as described in Section 5.2.1. The behaviour at

cracking is therefore dependent on whether or not the wall's elastic capacity is gteater
than the post-cracked 'semi-rigid resistance threshold' force, zu(l).For non-loadbearing

or low apptied overburden force walls the elastic capacity is typically greater than the
&,(1). In contrast, for high-applied overburden force walls the tensile strength of the
brickwork becomes less significant. Accordingly zu(1) is greater than the elastic
capacity. Therefore, to distinguish between the two types of un-cracked behaviour of
URM wall they must be catagorised as either low-applied overburden or high-applied
overburden force.

5.2.3.1. Low Applieil Overburden Force

The first category includes walls where there is no or a low applied overburden force so
that the compressive stresses at the critical mid-height cross section are also low. This
category of wall could be found as non-loadbearing internal partition walls or as

loadbearing walls in low-rise buildings or in the upper stories of multi story buildings.

81
CHAPTER (5)- Stability of Simply Supported URM Wails
Subjected to Transient Out-of-Plane Forces

For this category of wall, prior to cracking the lateral strength is almost entirely governed
by the masomy flexural tensile strength, fl1, so that the elastic capacity is greater than the
R*(1) (refer Figure 5.2.3). Thus, once the elastic capacity, &ur,i", has been exceeded the
lateral resistive force reverts back to the lower cracked wall resistance. Therefore, no
additional lateral capacity exists beyond cracking and wall survival is reliant on the
applied force being reduced to the cracked lateral capacity of the wall.

&u",i"
Force ControUDynamic I-oading @xplosive)

Un-cracked Elastic Capacity

Displacement Conrol Loading


\zÁ
J¿

È
Real Semi-rigid Non-linear F-Â
d
() zu(l)
k Relationship
Õ
t
G!
c)

E()
È
Þr
Un-cracked Linea¡ Elastic
Behaviour

Mid-heightDisplacement (/) A¡nsøbirity

Figure 5.23 Urrcracked F-A for Low Applied Overburden Stress URM Vl¡all

Where the wall is dynamically loaded, once the elastic capacity has been exceeded the
elastic inertia force is typically sufficient to continue to increase the wall displacement
(refer Figure 5.2.3). As a result this category of wall generally fail explosively under
dynamic loading having no reserve capacity to 'rock'. Consequently, an elastic static
analysis will provide a reasonable estimate of the dynamic capacity of this category of
wall. Should, however, the wall become cracked at any time during its life this type of
elastic static analysis may be highly non-conservative. Alternatively, should high
frequency spikes exist within a dynamic excitation these may have sufficient energy to

82
CHAPTER(5)- Stability of Simply SupportedURM Walls
Subjected to Transient Out-of-Plone Forces

crack a wall prematurely such that the maximum elastic capacity may not be realised and
the elastic static analysis methodology would again be non-conservative.

5.2.3.2. High þplied Overburden Force

The second category of wall is generally found two or more stories below roof level or in
upper concrete slab-URM wall construction. Here, where the applied overburden force is

larger, compressive stresses at the critical mid-height cross section are correspondingly
higher. In this case the benefit provided by the tensile capacity of the briclorork is
outweighed by the additional gravity restoring moment resulting from an increased lever
arm, as vertical reactions move towards the extreme compressive faces of the wall with
increased displacement. Accordingly, cracking of the wall does not alter the wall's
ultimate lateral capacity (refer
Figure 5.2.4). Typically, for a dynamic load scena¡io when the elastic capacity is
exceeded the elastic inertia force will not be sufficient to then exceed the 'semi-rigid
resistance threshold' force. Therefore, this category of wall behaves similarly to a pre-
cracked wall where a reserye capacity due to rocking and 'dynamic stability' concepts
must be considered.

z& R*(1) Real Semi-rigid Non-linear F-Â


Relationship
F &u",i"
c)
o Force/Dynamic
o
I¡r Conrol loading
G
k
o) Displacement
Conrol I-oading
Cd

€6)
o. Un-cracked Linear Elas[c
È
Behaviour

Mid-heightDisplacement(/) Ainsøb¿iry

Figure 5.2.4 Ur¡crackedF-Â for lligh Apptied Overburden Stress URM Wall

83
CHAPTER (5)- Snbility of Simply Supported UFJttI Walls
Subjected to Trqnsient Out-of-Plane Forces

5.3. Previous Research: Experimental Studies

Over the past 30 years or so there have been various experimental studies carried out on
both the static and dynamic out-of-plane behaviour of face loaded URM walls. Since
ea¡lier research was predominantly concerned with the effect of wind loading these
studies mainly considered static loading. More recently, however, the research focus has

been placed on seismic loading so that experimental studies have largely involved
dynamic loading. The following section provides a brief review of previous works
carried out by other researchers relevant to the one-way bending of face loaded LJRM
wall panels.

53.1. Static Tests


In the early L970's the U.S. Building Research Division of the National Bureau of
Standards (now the National Institute of Science and Technology, NIST) undertook an
extensive experimental study (Yokel et al 1971) on the static one-way out-of-plane
bending behaviour of masonry wall panels. In total 192 tests were completed including
both single leaf unreinforced brick and concrete block, cavity wall and reinforced
masonry. For each type of construction, specimens were subjected to a static vertical
compressive load, applied as a point load at the centerline of the top of the wall, followed

by a gradually increasing lateral pressure exerted by an inflated air bag. The boundary
condition at the base wall support was a steel channel with a fiberboard sheet adjacent to
the wall specimen. Boundary conditions were therefore representative of 'timber top
plate' above and concrete slab below.

Specimens with both low and high levels of appted overburden force were tested. At
low levels it was found that the maximum lateral strength occurred prior to cracking and
that this was related to the tensile strength of the masomy. In contrast, at higher levels of
applied overburden force additional wall capacity was found after cracking. The reasons
for this have been discussed in Section 5.2.3. For walls with moderate levels of
overburden force applied, a comparison with simple rigid body theory was found to be
consistent. Above lMPa overburden stress, however, the continuity began to drop away,
as crushing of the brickwork at vertical reactions became apparent (refer Figure 5.3.1).

84
CHAPTER (5)- Snbility of Simply Supported URM Walls
Subjected to Trutsient Out-of-Planc Forces

Typical failures for both low and high applied overburden stress are shown in Figure
5.3.2). \ühile the primary objective of this study was the development of appropriate
interaction curves for combined bending and the force-displacement (F-A)

relationships were also published (refer 5.4.2) 2


(\
Ë
g Sot-rd Þkrçhs
o
o -
É
.2 --- Hollow Uocl(s
a
É o10
ñ
o
ñ
È

a
o-05
--tGil,Þ\

r.o 2.A 30
Overbwden Sress MN/m2

Figure 5.3.1 Comparison of Yokel Sûrdy with Simple Rigid Body Theory
(Hødry 1973)

-iffi
-]___l+__i_L_
Crushing of
masonry
-Ì.H
J_- : ;---TÈ

Low Vertical
High Vertical
Compressive
Compressive Load
Load

Figure 5.3.2 Typical Latcral Failure of Brick l{all


cYokel et al l97l)

85
CHAPTER (5)- Stability of Simply Supported URM Walls
Subjected to Transient Out-of-Plane Forces

l-ater, Yokel and Fattal (1976) performed a similar experimental study to that of Yokel et
al (1971) also at the National Bureau of Standards. The main differences between the
studies where that for the 1976 tests smaller panel were used having steel half round bars
inserted at both top and base boundary conditions. This represented a simply supported
wall at its centerline. Since here the movement of vertical reactions was limited to only
the center joint, the prediction of the F-Â relationship w¿rs greatly simplified.
Experimental F-A relationships were again reported (refer Figure 5.4.2). For this case it
was observed that both the displacement at which instability occurred and the maximum
resistance were reduced in comparison with the Yokel study.

Base and Baker (1973) reported on a series of low overburden force out-of-plane tests.
These were aimed at providing fundamental data and an understanding of the action of
brickwork under a variety of loading conditions. Here the brickwork specimens were
observed to behave essentially elastically in the un-cracked state. A significant reduction
in bending strength was reported when brickwork beams were tested under simulated
uniform loading as compared with testing under central load over a shorter span. This
was attributed to the increased number of mortar joints within the loading span, thus
increasing the probability of a weak joint.

West et aI (1977) have also performed a series of static out-of-plane tests on wall panels.
Here no applied overburden force was considered so that the cracking load was reported
to be the maximum load the wall could resist. For these tests the top of the wall was
propped against lateral movement and a connection containing a DPC was used at the
base to represent as closely as possible the conditions used in practice. It was reported
that the material used for the DPC and the way in which it was embedded were important
in achieving the full bending strength. \ilhere the shea¡ capacity of the DPC connection
was exceeded the full bending sftength of the wall was not achieved since slip occurred at

the DPC. Further, both vertical and horizontal panels were examined where it was found
that the strength in the two orthogonal directions differed. The overall ratios of strength
in the direction perpendicular to the bed joint to that parallel joint were reported as being

I .2 ro 6.2 with a mean of around 3.

86
CHAPTER (5)- Stability of Simply Supported URM Walls
Subjected to Transient Out-of-Plane Forces

West, Hodkinson and Webb (1973) conducted extensive tests on strip walls
demonstrating the relationship between lateral strength and overburden force of storey
height walls of various thickness and materials. Support conditions considered were
similar to those of concrete slab above and below. Experimental results were reported as

being well represented up to a mid-height compressive stress of 1.4 MPa by the simple
relationship (refer Figure 5.3.3)

Pa = 8o/52

where po = ultimate lateral pressure


6c = ovêrburden compressive stress
S = slenderness ration = II/t
MN nr2 bl rn

o 0.r5 b
s
É
.g ,/
o
&
E x
o 18 +
Ë +
È t
ot +
/ x 1:?4:3 Morrer
+ o Do Fmdu
9/t + 1:1:6
I
12
I ---- Srmpletheory

r
0.os x.a f,e j"y
6 x x
+
o

t ¡
¡ r¡ tt- x
,a
rfs{ 250 3?5 500 1bl .,2
10 20 30 40 ÀlÍ{ t?
Overbr.¡rden Stress

Figure 5.3.3 Comparison of Wes 3 et al 1973 Tests with Simple Rigid Body Theory
(Hendry 1973)

This relationship was based on the rigid body theory with all vertical reactions pushed to
the extreme faces of the wall. Above 1.4 MPa overburden stress, the lateral resistance

was again reported to fall away from the linear relationship owing to compression and
local crushing. At low overburden force, experimental results tended to exceed the
theoretical values because of the tensile strength of the brickwork that is not taken into

87
CHAPTER (5)- Stability of Simply Supported URM Walls
Subjected to Transient Out-of-Plane Forces

account. It was also reported that the lateral strength of a wall with compression is only
slightly affected by brick and mortar strengths.

Anderson (1994) reported on the most recent series of static tests where 90 lateral load
tests on LIRM walls with various support conditions were undertaken. Here the
behaviour of vertically spanning strip walls was reported to be difficult to predict with
post-cracked rigid body theory considered to be a more satisfactory approach for static
limit state design. Eccentricity of the vertical load due to rotation of the base of the wall
was found to induce a stabilising moment. Consequently it was recommended that the
partial fixity moment due to the self-weight acting at an eccentricity of 0.45 of the wall
thickness be applied at the base of the wall. The mean height at which the bed joint
failed was 0.6 of the vertical span above the base. Failure by sliding was reported at the
DPC for some walls with low levels of applied overburden force.

5.32. Dynamic Tests


In the early 1980's a consortium of Californian engineers called the ABK Joint Venture
(ABK 1984) ca¡ried out research into the post-cracking seismic behaviour of URM wall
panels. The aim of the research was to develop standards for the renovation of URM
buildings in Los Angeles, particularly with respect to wall height-to-thickness ratios
(Kariotis et al 1985, Adham et al 1985). The study examined the one-way behaviour of
eight specimens of varying construction and geometry under a range of gravity loads.
Several dynamic motions were applied at the base and top support, simulating the input
motion from the ground or diaphragm anchorage. The base of the wall was allowed to
displace without rotation and the top of the wall was free to rotate and to move in the
vertical direction without restraint.

It was reported (ABK 1984) that a single horizontal crack typically formed near the mid-

height of the test specimen with another forming nea¡ its base. The stability of the fully
cracked URM wall, shaken by less than critical ground motion intensities, was
maintained by gravity load moments applied at the cracked surface. \ühen the center of
gravity of the vertical loads, above the cracked surface, lay within the wall thickness

88
CHAPTER (5)- Stability of Simply Supported URM WaIIs
Subjected to Trønsient Out-of-Plane Forces

dimension the gravity load moments were found to provide a restoring moment that
closed the crack upon reversal of the earthquake displacement motion. This ability to
displace without collapse resulted in the walls having a significant reserve capacity above

that of the 'semi-rigid threshold' force. The term 'dynamic stability' was used to
distinguish this type of behaviour from that which might be expected from static
calculations. Correspondingly, a major finding of the study was that neither static elastic
nor 'quasi-static' analysis procedures were completely satisfactory to define the dynamic
and highly nonlhnear response of the post-üacked URM walls'

Like the static F-A relationship, the hysteretic behaviour was found to have a declining
branch and on unloading the hysteretic F-A plot traced back along the loading plot.

As a result of this experimental investigation (ABK 1984) key parameters for predicting
the failure of URM walls subjected to face loading were identif,red. These were the waII
slenderness, the ratio of the applied gravity load to the wall self weight and the peak input
velocities at the base and top of the wall. A further important finding was that although
various phase shifts between the top and bottom excitation were examined, input
velocities simultaneous in time were found to be the critical case. That is, an in-phase
excitation at the top and base of the wall was the critical excitation case.

During the study the effect of vertical ground motion was not considered as it was
thought to not have a significant influence on the dynamic stability. This was explained,
as the frequency band of vertical motions in seismic events is generally not in the critical
frequency band of the horizontal ground motions. That is, the effect of high frequency
vertical motions on the restoring moments will not result in a bias of increasing or

reducing the restoring moment. This is due to the significantly lower frequency of
instability excursions as compared to the typical frequency of vertical seismic motions,
especially as the relative excursion of the center part of the wall approaches instability.

Ba¡iola et al (1990) reported on a series of tests where a gradually increasing excitation


was applied to the base of parapet URM walls. Here it was reported that prior to cracking

89
CHAPTER (5)- Stabiliry of Simply SupportedURM Walls
Subjected to Transient Out-of-Plane Forces

the natural frequency of the wall correlated well with simple elastic beam theory. In the
cracked state, however, no unique natural frequency was found as it decreased with
increased displacement response. Also, wall slenderness was not found to have a clear
influence on the peak acceleration required to cause instability. For walls of the same
slenderness wall but with different thickness, the thicker wall appeared to be more stable.

Results of another important dynamic experimental study of out-of-plane URM wall


behaviour was recently published by Lam et al (1995). This study focussed on one-way
bending of parapet walls with the objective of comparing various analytical approaches
with the experimental results. The subject of the experiment was a lm tall, I 10mm thick,
clay brick IJRM wall and was subjected to the El Centro ground motion. Free vibration
tests were also used to identify the frequency response and damping characteristics of the

cantilevered wall. The un-cracked elastic natural frequency was found to be between 5

and l0 Hz depending on the amplitude of vibration. Once the wall was cracked the
rocking frequency was found to decrease from about 4Hz at low amplitude displacements
to a lower frequency limit of approximately lHz at larger displacements. Although the
equivalent viscous damping, (, being a measure of energy loss was observed to vary
slightly (2.67o-3.4%o) with displacement it was reported to be fairly consistently around
37o.

Continuing from their earlier tests Lam et al (1998) have also reported on shaking table
tests on parapet walls of different dimensions using harmonic excitations of varying
amplitude and frequencies. Here the peak displacement of the wall was correlated to the
peak shaking table acceleration and velocity. These relationships were found to be highly

dependent on the excitation frequency so that plotting results associated with different
forcing frequencies produced large scatters (refer Figure 5.3.4). In contrast, a good linear
correlation was obtained between the relative displacement of the wall and the absolute
displacement of the shaking table (refer Figure 5.3.5). Typically, the peak relative
displacement at the top of the parapet wall was reported to be twice the peak absolute
displacement of the table irrespective of the frequency and amplitude of the table
motions. Inspection of the test results further showed that the center of gravity of the

90
CHAPTER (5)- Støbility of Simply Supported URM Walls
Subjected to Transient Out-of-Plane Forces

wall was displaced by a similar amount to the table so that the response was 1800 out of
phase with the table motion. In effect the center of gravity position remained effectively

stationary in space. Lam et al (1998) therefore postulated that for the harmonic forcing
frequencies considered, the 'equal displacement theory' could be adopted. Consequently,
wall instability would be predicted when the base displacement equaled half the thickness
of the parapet wall.

4
30
E Etqr¡ry5l5Hr âd 30
o &rqu¿Ft535Hr
ã
Ë . ElqEry 4 H¡ + &Êq¡{úy4H¡
É ¡ Êtgwy3.25IIr c
¡ ftr4ffJ31sH¡
g ê c Êt$EEy2tH¡ o c fte{ury2ll¡¡
Ízo ¡ Ë20
_!
A + .5
!o

a
â t ¡ E qa

I +
10 a g 10 a
q
a É t E

E
a l
E o
0 0
0 2 4 ú B 10 1¿ 0,0 o-1 o.2 o-3
Table Acceleratio n (nr¡ts2) T¡bh Vebciiy(¡n/Ð

(Harmonic tests on 500mm tall cantilever walls)

Figure 5.3.4 Top of Parapet \üall Disp. Correlated to Table Velocity and Acceleration
(Lam 1998)

^30
É
É o &tçnrn¡5f5IIr
ãas o Êtçttts¡{I&
ü
É
¡ Êtqury3l5IIz
0 o &tEurcyS-?Iù

A
eo
!
.9 ûô
a
15 ! f
a E
10 IE¡

Ë
I

0
o 5 10 15

T¡ble Displ¡nertpnt (m m)

Figure 5.3.5 Top of Parapet Wall Disp. Correlated to Table Disp.


(Lam 1998)

9l
CHAPTER (5)- Stability of Simply Supported URM Wqlls
Subjected to Transient Out-of-Plane Forces

It was noted, however, that the frequencies used were much higher than the effective
resonant frequency of the parapet wall tested at large displacements. Consequenily,
should excitation frequencies closer to those of the wall's effective resonant frequency at
large displacements have been used, displacement amplifications greater than unity
would have been more likely and the 'equal displacement theory' would not apply.

5.4. Critical Review of Current Analysis Methodologies

As a result of experimental and analytical studies previously carried out, various analysis
methodologies have been developed over the years to analyse the one-way out-of-plane
seismic capacity of URM walls. The following sections critically review these
methodologies highlighting the advantages and limitations of each method.

5.4.1. Quasi-Static Analysis Procedures

The response of a URM wall to earthquake induced base excitations is a complex


dynamic process. Analysis, however, is often simplified by considering an instantaneous
maximum acceleration occurring at a critical snapshot in time. As such, the peak-input
acceleration associated with either the ground motion (PGA) or building response,
depending on the location of the wall within the structure, is often used to represent the
associated inertia force. Displacements are assumed to be small so prior to failure the
induced inertia force is assumed to be uniformly distributed over the height of the wall
relative to the distribution of mass.

Alternatively, it is possible to estimate the wall's critical natural frequency, either in the
cracked or un-cracked state, thus permitting an estimate of the elastic spectral response
acceleration to be determined from an elastic response spectrum. The main limitation
here is that the natural frequency of a URM wall is not unique, as described in Section
5.2.I. In addition, for the cracked wall case where response displacements are relatively

large, in contrast to the uniformly distributed inertia load assumed above a trapezoidal
distributed inertia load is more likely. This is due to the additional triangular inertia force
induced by the vibration of the wall ove¡ the rectangular inertia force resulting from the
motion of the supports.

92
CHAPTER (5)- Snbiliry of Sirnply SupportedURM Walls
Subjected to Trqnsient Out-of-Plnn¿ Forces

Regardless of the method used to determine the 'snapshot acceleration' the dynamic
action is represented bya 'quasi-static' type analysis. Earthquake design codes and
standatds typically specify analysis methods based on this 'quasi-static' analysis
philosophy. The two most common methods are: (a) the stress based linear elastic (LE)
and (b) the rigid body (RB) equilibrium analyses. Both are briefly reviewed in this
section.

As described in Section 5.2.3 previous researchers have found that in the un-cracked state
URM walls behave essentially elastically. It is possible therefore to utilise the well
established linear elastic (LE) anatysis methodology to predict at what equivalent lateral
inertia force cracking stresses within a URM wall will be exceeded. The fundamental
principle is to equate the maximum seismically induced moment at a critical section Mu,
to the moment required for the cracking stresses at the leeward face lv[", to be exceeded.
Resistance to cracking is provided by both the flexural tensile strength of the brickwork

fl¡, and the compressive force at the mid-height of the wall from seH-weight and
overburden. Figure 5.4.1 shows a representation of the LE analysis for the prediction of
the cracking acceleration for a simply supported URM wall. Since elastic deformation
prior to cracking in URM walls is generally relatively small the vertical reactions at the
top and base supports are assumed to act at the centerline of the wall.

The current seismic design methodology in Australia (453700-1998) for the vertical one-
way bending of URM walls subjected to transient out-of-plane forces adopts the stress
based LE analysis of the un-cracked section. Here a 'Capacity Reduction Factor' of 0.6
is also used in design to allow for the variability in the flexural tensile sfrength.

93
CHAPTER (5)- Snbiliry of Simply Supported URM Walls
Subjected to Transient Out-of-Plane Forces

o
w kN/m
wh
f, 2
f,
I{
h
TT O+W2
2
TT
f It

tr
II ./'
r"
ft
w
o +-
h f, Me
f 6

lr
II Predicæd inertia induced

TT
distributed load to cause cracking

TT f
II w
8
F t.f"
T wh
6

W+O Predicted cracking acceleration

O+ w
where

W = self weightof URM walUm (kN/m)


w = wind or earüquake inertia load/m
a=
t
2
tr"
T = specific weight of URM (ld{/m3)
f r = flexural tensile strength where w=m.a-^lgt.a
O = superimposed load (concrete slab above)

Figure 5.4.1 Quas¡-Static Linear Elastic Design Methodolory

The assumption of an un-cracked wall and elastic stress-strain behaviour is a major


limitation of the linea¡ elastic anaþis methodology. As highlighted by the Newcastle
earthquake much of Australia's older LJRM building stock may have an appreciably
depleted masonry flexural tensile capacity or even be pre-cracked. Also, since the
analysis is dependent on a reliable estimate of the highly va¡iable flexural tensile strength

of the brickwork at the time of loading it is consequently diff,rcult to accurately predict


the cracking capacity. Another major limitation of this method is that the formation of
flexural tensile cracks does not necessarily result in failure of the wall as implied. [n fact,
as discussed in Section 5.2.3, for walls with applied overburden force, this is rarely the
case. Instead, after f,rrst cracking a small mid-height displacement causes the wall's

94
CHAPTER (5)- Stability of Simply Supported URM Walls
Subjected to Trønsient Out-of-Plane Forces

neutral axis to be forced in the direction of the compression zone at both mid-height and
vertical support reactions. This neutral-axis shift associated with crack propagation can
lead to a "tip-toe" situation in which the wall is supported on its edges.

The post-cracked seismic performance of an URM wall is therefore more realistically


analysed by the rigid body (RB) equilibrium analysis method, which compares the

overturning moment with the restoring moment taken about the rocking edge of the wall.
The overturning moment is obtained in the same manner as for LE analysis using the
quasi-static methodology, whereas the restoring moment is obtained by consideration of
the forces due to self-weight and any overburden acting on the free body above the mid-
height crack. This is identical to the method described in Section 5.2.1 for determining
the 'rigid threshold resistance' force, R.(1). A major limitation of this method is that it
assumes that the brickwork has an inhnite stiffness. In reality, it is semi-rigid and highly
dependent on its constituent materials. Correspondingly, the real 'semi-rigid resistance

threshold' force, zu(1), can be much lower than R"(1) as it occurs at a larger

displacement where P-A effects are more prominent.

To account for the reduced 'resistance threshold' caused by the semi-rigid behaviour of
URM walls, Priestly (1985) and Paulay (1992) proposed a method of determining the real

non-linear F-Â relationship. This method is based on first principles of beam theory, and
assumes a zero tensile strength for the masonry and simply supported wall at the

centerline. The fundamental approach is based on the assumption that the gradient of the
linear elastic stress diagram at the critical mid-height section, and thus the wall curvature,
is related to the mid-height displacement of the wall. As this relationship is derived
through examination of the stress diagram at the cracking displacement the assumed
modulus and boundary conditions are important considerations.

A finite element model ¡amed the Block-Interface Model has also been developed
(Martini IggT) in an attempt to determine the real static post-cracked F-^ relationship.
Here joints are represented by discontinuum elements so that the elastic properties of the
mortar and associated local effects at the block mortar interface are neglected with the

95
CHAPTER (5)- Stability of Simply SupportedURM Walls
S ubj e cte d to Transient O ut- of- Plane F or c e s

mortar joint representing a potential line of failure due to cracking (refer Figure 5.4.2).
Here increasing the number of laminations and layers increases the density of the frnite
element mesh and thus allows more accurate refinement however this also increases the
complexity of the model. The finite element Block-Interface approach has the advantage
of being able to be implemented using commercial software.

Figure 5.4.2 shows a comparison of experimentally derived F-A relationships from the
Fattal (1976) and Yokel (1971) studies with those determined analytically by the Block
Interface finite element model (Martini 1997) and the Priestly (1986) method.

I I
lo
Ë

t
:J

ar
z
Jtr 3

+ FàHål ErDuihül + Yolil E.rüiÐd


-è- Fifile ELld å- FEil. ELþ!t, ¡l LsiEtios, I l¿Ft
-{" Prisdyl{rtlod -è- fEù€ ElÊEÈ! ó l¡niutiry I l¡r¡
ô FEile ELñ.!t, ó lÀniDtios, 5 )¡nr

¡ú JÙ

Lòlerôl Dirph!Ê¡d d Biùheût (m) L.ld¡¡DieDl¡.æd ¡t Ei¡l-luùht (m)

Figure 5.4.2 Experimental and Analytical F-AComparison


(Martini 1997)

It must be recognized that none of the previously mentioned 'quasi-static' analyses take
into account the time-dependent nature of the response of the wall since only an

instantaneous acceleration occurring at a critical snapshot of the response is considered.

A URM wall will not necessarily become unstable and collapse should the quasi-static
force exceed the resistant capacity of the wall, as the incipient instability displacement
may not be reached. As such, the level of seismic loading to cause failure can greatly
exceed that predicted by the quasi-static analysis methods (ABK 1985, Bariola 1990,
Lam 1995) such that a reserve capacity exists. The quantification of the reserve capacity
is reliant on the frequency and amplitude content of the applied excitation so that more
realistic dynamic modeling approaches should be used to account for the dynamic
behaviour.

96
CHAPTER (5)- Stability of Simply Supported URM WaIIs
Subjected to Transient Outof-Plane Forces

5.4.2. Dynamic Analysis Procedures

Although being particularly useful as suitably conservative modern design tools the
'snapshot' quasi-static design methodologies described above may not be appropriate for
the review of existing URM structures. In the design of new structures the application of
conservative design tools will generally have only minor economic consequence.
However, in reviewing existing structures using procedures which do not recognise the
additional lateral strength capacity resulting from 'dynamic stability', a more significant
economic penalty may be incurred. An example is where the decision to demolish,
retrofit or 'leave as is' for a significant monumental IJRM structure may be in the
balance.

In recognition of the problem of assessing the dynamic response by the 'snapshot'


principle an alternative analysis method based on the widely recognised 'Equal Energy'
procedure has been proposed by (Priestly 19S5). The 'Equal Energy' procedure is based
on the observation that 'dynamic stability' concepts can be considered by using an
equivalent elastic capacity derived by equating the real energy required for instability
with that of an elastic system having a stiffness equal to the initial un-cracked stiffness of
the wall. Although based on an observation, this simplification has been shown to
predict reasonable estimates of peak displacement response for simple systems with
relatively short periods (Priestly 1985, Lam 1995). It has been observed however that for
systems with very short periods this procedure can provide very un-conservative
estimates of lateral dynamic capacity and for systems with longer periods a conservative
estimate of lateral dynamic capacity (Priestly 1985, Robertson 1985).

For URM wall dynamic capacity prediction using this method, the potential energy
absorptive capacity of a wall undergoing large displacement is first quantified. This is

achieved by determining the area under the non-linear F-À curve as the wall is pushed
from the vertical non-displaced position to that of the incipient instability displacement.
The procedure to approximate the F-Â curve of a simply supported load-bearing URM
wall pinned at the centerline for the purpose of appþing the equal-energy procedure has
been reported in Section 5.4.1. The maximum kinetic energy (KE) demand is then

97
CHAPTER (5)- Stability of Simply Supported URM WaIIs
Subjected to Transient Out-of-Plane Forces

derived from the maximum spectral velocity as obtained from an elastic response
spectrum to compare with the potential energy (PE) capacity. Thus, it is assumed that the
wall would remain un-cracked and behave linearly up to the time when the maximum KE
is reached (vertical position) and at commencement of the failure half cycle. At this time
the wall is assumed to crack and begin to rock as the PE is increased to absorb the KE.

The abrupt transition from the linear elastic response (in the un-cracked state) to the non-
linear rocking response (in the cracked state) is a major assumption of the equal energy
procedure. In reality, the dynamic behaviour of the wall at the commencement of the
failure half cycle is not always linearly elastic. It has been demonstrated by dynamic tests
(Lam 1995) that the stiffness and natural period of a URM wall can be highly amplitude
dependent even in the un-cracked state. Thus, the "elastic" natural period of vibration of
the wall, which governs its spectral velocity (and hence its maximum KE) can not be
predicted with certainty. Further, it is possible that the wall may have already cracked
and be responding in-elastically prior to the commencement of the failure half cycle. A
second major shortcoming of the 'equal energy' method is that ground excitations are
also assumed to have stopped once the failure rocking half cycle has commenced. As a
result the accumulated effects of multiple pulses on the wall during rocking can not be
accounted for as additional input energy into the system within the failure half cycle is
not considered.

Figure 5.4.3 presents a comparison of the predicted URM wall acceleration capacity
utilising the 'equal energy' method with the previously described quasi-static analyses.
As expected the linear elastic anaþis provides the most conservative prediction of
dynamic lateral capacity for moderate to high overburden stress ranges. For low
overburden stress, however, the rigid body analysis is more conservative. For all
overburden stress the 'Equal Energy' method provides the least conservative prediction
as an allowance is made for 'dynamic stability'. As the effectiveness of the 'equal
energy' observation is highly dependent on the system's un-cracked natural frequency the
prediction is very sensitive to the selection of elastic modulus. Often a realistic modulus
value can result in an extremely un-conservative lateral strength prediction.

98
CHAPTER (5)- Søbility of Simply Supported URM Walls
Subjected to Transient Out-of-Plane Forces

2.5
----lr*LINEAR ELASTIC
RIGID EODY
3'o '.'.'.'.{r'."'."' EQUAL ENERGY

F'=
...._,-._..........1
Ê
HÉro
¡''
¡i¡¡.....{.ìr.r!\'þnqf

Ei r'l
H$0.
4
0.0
0.0u 0.05 0.10 0.15 0.20
OVEREURDEN STRESS AT TOP OFI¡TALL

Figure 5.4.3 Comparison of Analysis Predictions

As discussed in Section 5.3.2, Lam (1998) has reported that for harmonic excitations of
varying amplitude and relatively high frequencies the center of gravity of a parapet wall
effectively remained stationary in space. Consequently, on an 'equal- based
displacement' methodology, wall instability could only occur when the table
displacement exceeded the incipient instability displacement, which could be related to
the thickness of the wall. It was also highlighted that for forcing frequencies closer to the
natural frequency of the wall at large displacements that significant displacement

amplification was possible so that instability could occur at table displacements less than
the incipient instability displacement thus invalidating the'equal-displacement'
methodology for practical applications. To overcome this shortfall a dynamic
amplification factor was proposed. \ilhile this method is useful for the dynamic analysis
subjected to ha¡monic excitations it is limited for multiple frequency, transient excitations
where random pulse arival will significantly affect the wall response.

The methods described so far have all used a single parameter (acceleration, velocity, or
displacement) to predict the effect of the excitation on the response of a URM wall. As a
result these methods all have limitations for dynamic analysis although the velocity based
dynamic analysis is satisfactory to analyse the response of single pulse excitation and the
equal displacement method is suitable for stationary periodic excitations. Unfortunately,
general, transient excitations can not be accurately represented by a single parameter so

99
CHAPTER(51 Stability of Simply SupportedURM Walls
Subjected to Transient Out-of-Plane Forces

that Time History Analysis (THA) procedures are required to take into account the effect

of the frequency content, duration and pulse arrival details of the excitations.

Although researchers (Housner 1963, Yim et al 1980, Hogan 1989) have reported on
analytical studies where explicit mathematical solutions of rigid rocking motion
equations have been derived these are limited for applications where the system can not
readily be idealised. Further, where transient excitations are considered explicit
mathematical representation is not possible. Consequently, to undertake a THA an
approximate numerical evaluation of the response integral must be used. This requires an
assumption to be made on the motion between consecutive time steps. For example,
acceleration may be assumed to be constant or linearly varying thus allowing the basic
integration equations to be developed (Clough & Penzien 1993).

Lam (19958) has reported on the development of specific THA software for the analysis
of the dynamic response of a parapet walls to transient excitations using the Constant
Average Acceleration Integration technique and a rigid bi-linear F-Â relationship. To
minimise computational time an iterative procedure was not included to model damping
but rather an average mass proportional damping coefficient for the response was
developed based on an estimate of the response frequency. Nevertheless, despite the
approximations made in modelling the F-Â and damping properties, results from this
THA have provided reasonable agreement with experimental results. Similar THA
techniques are also currently being developed for the in-plane rocking analysis of URM
walls (Magenes & Calvi 1996:1997, Abrams 1998).

In 1992 Blakie et al reported that a simplified Displacement-based (DB) analysis, which

compared the displacement demand with capacity, might better predict the seismic
capacity of out-of-plane panels. Although approximate, this method has the potential to
account for the dynamic behaviour and thus the walls reserve capacity. Simitar DB
analysis procedures are currently also being developed for the prediction of in-plane
rocking capacity of URM walls (Magenes & Calvi 1996:1997).

100
t

CHAPTER(5)- Stability of Simply SupportedURM Walls


Subjected to Transient Out-of-Plane Forces

5.5. Specific Research Focus

Although most URM walls are designed as two-way spanning elements, as a first stage in

the development of a method that may also be applicable as an analysis component of


dynamic two-way behaviour, an understanding of the physical process underlying one-
way dynamic action must first be developed.

While there has been a substantial research effort undertaken on the static loading
behaviour of one-way spanning wall panels, dynamic action has not been as well
examined. Consequently, simple static analysis procedures have been developed which
are capable of predicting cracking and ultimate loads and have been shown to correlate

well with experimental results. In contrast, the dynamic behaviour is not well
understood.

The few dynamic loading experimental studies that have been previously undertaken
have indicated that URM walls have a significant capacity to displace without becoming
unstable. As a result they are often observed to have the capability of sustaining inertia
forces greater than that predicted by 'quasi-static' methods. This is referred to as the
wall's dynamic 'reserve capacity' to rock. Unfortunately, currently available seismic
predictive models have been unable to account for this large displacement post-cracked
behaviour. Where the 'reserve capacity' to rock is overlooked in analysis a conservative
estimate of seismic capacity is made. Although this may be acceptable for the design of
new buildings, it may impose serious economic penalties in the analysis of existing
structures.

In response to the above shortfall a need was apparent for the development of a rational
and simple analysis procedure, encompassing the essence of the dynamic behaviour and
thus accounting for a URM wall's 'reserve capacity' to rock. The development of this
analysis procedure was adopted as the research focus for the final component of this
project.

101
6. OUT-OF.PLANE SHAKB TABLE
TESTING OF SIMPLY SUPPORTBI)
URMWALLS

6.1,. Introduction
With the aim of developing a better understanding of the physical processes governing
the dynamic collapse behaviour of simply supported URM walls a series of shaking table
tests were conducted on the earthquake simulator in the Chapman Structural Testing
Laboratory, University of Adelaide. In this experimental study the wall response to
harmonic, transient and pulse excitations was examined with the effect of wall va¡iables
including thickness, slenderness and the level of overburden stress taken into
consideration. In Chapter 7 the resulting dynamic response data is used to confirm the
reliability of a specifically developed non-linear Time History Analysis (THA) procedure
for modelling the semi-rigid rocking response of URM walls.

To complement the shaking table test data, static push tests and free vibration tests ïvere
also conducted. These complementary tests enabled the non-linear force-displacement
(F-^), frequency-displacement (/-A) and damping-frequency ((fl relationships for the

rocking wall to be investigated. In Chapter 7, these experimentally derived relationships


are used to calibrate the specifically developed non-linear Time History Analysis (THA)
program.

For completeness, material tests were conducted even-though the ultimate behaviour of
face loaded URM walls, at low levels of overburden, have not previously been found to
be particularly dependent on the constituent brickwork material properties. Nevertheless,

these results provide an indication of the masonry quality tested.

102
CHAPTER (6)- Out-of-Plane Shake Table Testing
of Simply Supported URM Walls

The following chapter presents a description of the experimental study undertaken


highlighting key results and where possible a comparison of experimental results with
theory is also presented. A representative cross section of test results is presented in the
Appendices E and F.

6.2. General Test Set Up

6.2.1. Test Specimens

In total, 14 one-way spanning URM wall panels were constructed for out-of-plane
testing. Where possible, multiple static and dynamic tests were performed on each
specimen. Details of each of the wall specimens are presented in Table 6.4.1. The
height of the wall panels was limited to 1.5m by the height of the laboratory gantry crane.
Consequently, standard 110mm thick wall specimens were constructed at a height of
1.5m giving a slenderness ratio of 13.6. For more realistic slenderness ratios to be
examined, 1.5m tall, 50mm thick walls were also constructed. These had a slenderness
ratio of 30.

The bricks used were standard extruded clay bricks having the dimensions 76 x 110 x
230mm and had 3 x Q45mm holes as shown in Figure 6.2.I. A 10mm mortar joint was
adopted for both horizontal and vertical perpends as per normal construction practices in
Australia. The average density of the llOmm thick brickwork was determined to be
1800kg/m3. This was achieved by weighing a representative sample of the brickwork and
dividing by its volume. In this way, the mortar which partially filled the brick holes was
also taken into account.

103
CHAPTER(6)- Out-of-Plane Shake Tøble Testing
of Simply SupportedURM Walls

Q45mm

Figure 6.2.1 Ståndard Three Hole Extruded Clay Brick (110mn)

The 50mm bricks used in these tests were solid having been cut from brick pavers, with
dimensions 33 x 50 x 230mm. For the 50mm thick wall specimens, a 5mm mortar joint
was adopted. Since wall geometry rather than material properties w¿ts considered critical
to the rocking behaviour, no attempt was made to model the constituent mortar materials
to half scale. The average density of the solid 50mm thick brickwork was measured at
23}}kstnf .

For all of the wall specimens a typical Australian mix of 1: l: 6 (cement: lime: sand)
mortar was used. Common 'brick' sand and Portland cement were used and water was
added until good workability of the mortff was achieved. No air entraining additives
were used and to improve consistency between mortil batches, 'bucket batching' was
used.

A professional bricklayer was employed to construct the one-way spanning wall


specimens. At the base of each wall an embossed polythene membrane DPC connection

was used (refer Figure 6.2.2). Wall specimens were constructed in three lots with four
110mm thick walls constructed in March 98 and June 98 and three 50mm thick and
110mm thick walls constructed in September 98. All walls \ryere constructed as a

standard veneer with wall ties connected to a timber support frame (refer Figure 6.2.2).
This construction method was adopted after preliminary tests showed that the mortar
bond could be depleted if wall panels \¡/ere constructed without lateral support. This was
attributed to the fact that lower brick layers were disturbed as the upper layers were

r04
CHAPTER (6)- Ourof-Plnne Shùc Tablz Testing
of Simply Supponed URM Walls

placed thus breaking the bond. Using the timber wall for support overcame this problem

by providing stability to the wall panel during construction. An added benefit was that
this also prevented accidental damage during curing and provided a more realistic
construction technique. After a minimum of 28 days curing time the wall ties were cut
and the wall panel carefully lifted onto the shaking table.

Throughout the fabrication of the test walls, two-brick and five-brick prisms and
100x100x100mm mortar cubes were regularly constructed for material testing, as
described in Section 6.3.

Veneer wall used for Embossed Polythene


construction DPC connection at base

Figure 6.2.2 Construction of URM Wall Panels

6.22. Test Rig


To provide a representative boundary condition at the top of each of the simply supported
URM wall panels tested, a braced steel frame was rigidly attached to the shake table with
a 'cornice' type support connection used to provide lateral restraint at the top of each
brick wall. The 'cornice' support was made up of steel angle and 10mm square, stiff
rubber spacers to prevent the wall from binding against the angle at large wall mid-height
displacements (refer Figure 6.2.3). Prior to testing the 'cornice' was fitted snuggly to the

wall. However, to ensure a minimal vertical restraint due to friction the 'cornice' was not
over tightened.

105
CHAPTER (6)- Ourof-Pløne Shake Table Testing
of Simply Supported URM Wqlls

AdjusEnent
l0mm stiff bolts
rubber spacer

Wall
Specimen

Figure 6.2.3Top 'Cornice' Support Connection

The stiffness of the braced frame was designed to represent as closely as possible the in-
plane stiffness of a URM structural shear wall (refer Figure 6.2.4). As a consequence, any

input excitation provided at the table was also applied approximately in phase at the top
of the wall. This w¿rs confirmed by comparison of the absolute displacements of the table
and top of the braced frame for each of the dynamic tests. Using an impulse free
vibration test the natural frequency of the braced frame was determined to be
approximately 10H2. For most of the tests this was not in the range of dominant driving
frequencies so that the small response amplification recorded at the top support was
neglected. For the relatively high un-cracked wall natural frequency tests, however,
where the mid-height of the wall specimen was excited using a mallet strike, the black
frame natural frequency dominated the response and thus was required to be filtered out.
Also, for harmonic tests completed near the frame's natural frequency of 10Hz

significant amplification of the base excitation was observed at the top support of the test
specimen so that an average input excitation had to be considered.

Preliminary tests showed that it was very difhcult, in practice, to apply an overburden

force at the top of the test walls in a realistic manner using weights supported by a

concrete slab. This method produced large overturning moments at the bearing support
rails of the shaking table, leading to a dangerous rocking action during testing that limited
the inertia forces that could be induced into the wall. To oYercome this problem an

106
CHAPTER (6)- Out-of-Plnne Shalce Table Testing
of Símply Supported URM Walls

overburden rig was designed which relied on six large springs to develop the required
level of overburden stress (refer Figure 6.2.4). The static deflection of the springs could
be altered by adjustment of the central thread, thus altering the overburden force at the
top of the wall through the base plate of the springs. The overburden test rig therefore had

the advantage of permitting easy changes to the overburden force.

Braced steel I
Cornice
frame
support
URM shear
wall action)

Shaking
direction

Table bearing
support rails X'igrrre 6.2.4 Out-of-plane Test Rig

6 x springs
3mm n¡bber mat between spring plate and wall

Figure 6.2.5 Overburden Rig

r07
CHAPTER (6)- Out-of-Plane Shake Table Testing
of Simply Supported URM WaIIs

The main disadvantage of using the overburden rig was that with increased mid-height
displacement the total wall height also increased slightly thus increasing the static spring
deflection and hence overburden force. Accordingly, the desired constant overburden
force at the top support was not realised at larger displacements. To overcome this
problem springs were selected so that the additional overburden force developed with the
expected increase in height was not signif,rcant. Further, since the increase in height with
mid-height displacement is inversely proportional to the wall slenderness the additional
overburden force on the 50mm walls was significantly less than that of the 110mm walls.
Correspondingly, for the 50mm wall specimens mid-height displacement changed the
mean overburden force by less than ! SVo so that the constant force assumption was
acceptable. In contrast, for the 110mm thick wall specimens significant increases in
overburden force were observed so that the constant force assumption was only
acceptable for mid-height displacements of less than 207o of the wall thickness. Static
compression tests were performed on the springs to calibrate the spring coefficients
where it was found that a 0.16kN force was developed for each mm of static spring
deflection.

Since the situation with overburden represented a vertical continuation of the wall or a
supported concrete slab, a point load connection was not used at the top of the wall
panels. Thus, the location of the top vertical reaction was governed by the spring base
plate, and with increased wall mid-height displacement the top vertical reaction was
forced to move to the compressive zone (refer Figure 6.2.6).

Test çecirren
Top vertical reaction location

Figure 6.2.6Top Yertical Reaction - Overburden Test Rig

108
CHAPTER (6)- Outof-Plnne Shakc Tablz Testing
of Simply SupponedURM Walls

The test boundary conditions were therefore considered similar to a concrete support slab
above and below where the vertical reactions are constånt but pushed to the compressive
zone with mid-height displacement.

6.23.Instrumentation
A total of nine channels of data were recorded for each of the dynamic tests in order to
capture the dynamic response characteristics of the rocking URM wall specimens. The
instrumentation consisted of five accelerometers, t'wo Linear Voltage Potentiometer
Transducers (POT), one Linear Voltage Displacement Transducer (LVDT) and the
internal INSTRON hydraulic actuator displacement transducer. For static tests, the same
instrumentation was used with the exception of the five accelerometers. Figure 6.2.7
shows the location of the nine instrument points and Table 6.2.1 presents a summary
description of the application of each instrument.

rffall specimen 5. ACCEL


(TA)
Timber wall I. LVP
catch (TrwD)

7. ACCEL
(refer Table 6.2.1 (rwA)
for instrument
codes)

8. ACCEL
2LYP (MwA)
(MwD)

9. ACCEL
(BWA)
3.LVDT Stationary
(BwD) reference frame:
6. ACCEL
Rigid connection
(TTA)
4.INSTRON to súong floor

Figure 6.2.7 Out-o[-plane WaIl Test Instrumentation Locations

109
CHAPTER (6)- Out-of-Plane Shake Table Testing
of Simply Supported URM Walls

Table 6.2.1 Out-of-plane Wall Test Instrumentation Description


Channel Location/Description Application Instrument
No. Code
I Absolute Top Wall Displacement Top wall displacement excitation TWD
2 Relative to Frame Mid-height Mid-height wall displacement response MWD
tWall Displacement
J Relative to Table Base Wall Base slip check BWD
Displacement
4 INSTRON internal displacement Base wall displacement excitation INSTRON
5 Top Frame Acceleration Top wall acceleration excitation TA
6 Table Top Acceleration Base wall acceleration excitation TTA
1 Top Wall Acceleration t/+ - wall height acceleration response TWA
8 Mid-heieht V/all Acceleration Mid-height wall acceleration response MWA
9 Bottom Wall Acceleration r/¿ - wall height acceleration response BWA

One Linear Voltage Potentiometer (POT) was mounted horizontally between the
stationaty reference frame, connected to the laboratory strong floor, and the braced frame
at the level of the top of the simply supported wall specimen to record the total top of
walVframe displacement (TWD). The POT was a Housten Scientifrc model 1850-050
having a maximum displacement of 500 mm and powered by a 10 Volt DC supply. A
similar instrument was used to record the relative mid-height wall response displacement
(MViD) between the wall and braced frame. In Chapter 7, the MWD is used for
comparison with analytical predictions of the mid-height displacement response of
simply supported URM walls using the specially developed THA program. A
Schlumberger Linear Voltage Displacement Transducer (LVDT) having a maximum

displacement of +1Omm was mounted between the base of the wall specimen, just above

the DPC connection, and the shaking table to measure the relative displacement between
the wall base and shaking table (BWD). The data from this instrument was only used to
ascertain if any sliding at the wall base DPC connection occurred during testing.

Kistler Servo Accelerometers powered by a servo amplifier were used to record the top
frame (TA), and tabletop (TTA) accelerations. These accelerometers have a measurable
acceleration range of + 50g and are able to detect accelerations as small as 0.1mm/s2'

These accelerations therefore represented the actual input excitations applied to the wall

specimen and are used in Chapter 7 as input for the non-linear THA. The top frame
accelerations were also compared with the table accelerations to identify how much
amplification of the base excitation was caused by the braced frame's flexibility.

110
CHAPTER (6)- Ourof-Plane Shake Table Testing
of Simply Supported URM Walls

The top (TWA), mid-height (MWA) and bottom (BWA) accelerations were recorded
using the 'Analogue Devices' single chip accelerometer, model ADXLO5 which were
adhered to the face of the wall at the 3/t -, mid - and r/¿ - height respectively. This less
expensive semi-disposable accelerometer was selected, as it was possible that should the

wall collapse these devices could be sacrificed. These accelerometers have a measurable
acceleration range of + 59 and a¡e able to detect accelerations as small as 0.019. A
limitation of this method was due to the accuacy of the accelerometers being reliant on a

horizontal datum. Since the accelerometers were glued to the wall surface they rotated
with the rocking of the wall so that as the wall's mid-height displacement increased the
accuracy of the data from these accelerometers decreased. For most of the critical
response however the accuracy was adequate for the purpose of the tests. Comparison of
the BWA and TWA with the mid-height acceleration response was useful in
characterising the total dynamic acceleration response profile. The mid-height
acceleration response was also later used for comparison with THA predictions.

In a similar fashion to the dynamic tests performed on tlRM connections containing a


DPC membrane, described in Chapter 4,the'Microsoft Windows' based data acquisition
system 'Visual Designer' was used to collect the nine channels of response data. Data
was collected at a period interval of 0.01 seconds (100H2).

Where restoring moments were ¡elatively small, in particular for the non-loadbearing
50mm thick wall specimen, care was taken to ensure that the instrumentation did not
influence the test outcome.

6.3. Material Tests

The material tests undertaken have included bond wrench tests to determine the
brickwork flexural tensile strength, fl1, and compression tests of brickwork prisms and
mortar cubes to determine the masonry's modulus of elasticit), Er* and ultimate
compressive strength, f -, and mortar's compressive strength, f". The following section
presents a brief discussion of these tests and their results.

111
CHAPTER (6)- Out-of-Pbrw Shnke Tablz Testing
of Simply Supporte d U RM Walls

63.1. Bond Wrench


The bond wrench test is one of two methods permitted in 453700-1998, Appendix (D) to
determine the flexural tensile strength, f t, of the bond between mortar and brick units

perpendicular to the bed joints. As described in Section 5.2.3, for un-cracked walls with
low levels of overburden, f ¡ is often the critical wall parameter for lateral loading. Here
the un+racked elastic lateral force capacity is greater than the cracked force capacity so
that at first cracking an explosive dynamic instability is possible.

Two bond wrenches were specifically manufactured for this project being for the 11Omm
and the 50mm brick specimens. The bond wrench is used to apply a moment to the joint
to be tested by appþing a load at the end of the lever a¡m. From the known applied
moment, f I can be determined with the assumption of an idealised stress distribution
across the bed joint. To best approximate this idealised stress distribution the bond
wrench design, as shown for the ll0mm brick specimen in Figure 6.3.1, was adopted
from research undertaken by Samarasinghe et al (1998). This bond wrench specification
has since been included in 453700-1998, Appendix (D). To simplify the procedure
strain gauges were adhered to the a¡m of the bond wrench with peak strains calibrated to
the applied force at the loading point. Calibration plots for the two bond wrenches are
presented in Appendix (E).

In order to ascertain if the flexural tensile strengths, determined from the two-brick prism
tests, were representative of the test specimens, bond wrench tests were also completed

on pre-dynamically tested LIRM wall specimens, ¿ls shown in

Figure 6.3.2. For each test specimen three prism and three wall tests were completed.
For the pre-dynamically tested walls the vertical perpends on either side of the test joint
were cut using a masoffy hand saw. Comparison of prism and wall test results showed
that the tested walls generally had a slightþ greater f ,. This was attributed to the wall
test including a vertical perpend in the course below as shown in Figure 6.3.2.

112
CHAPTER(6)- Out-of-Plan¿ Shake Tqbl¿ Testing
of Simply SupponedURM Walls

l5m
r ¿t0m
8Ouu
l6U*

¡t0lø
l5m Point
flIlu

l* '* lr
45m ãÌ- &lzu

25u
25m

X'igure 6.3.1 Bor¡d Wrench Apparatus Dinænsioru (llllmm Brick)

Vertical perpend
Strain gauges on ûop he-cut vertical perpends in course below
and botûom of loading
afm

I-oading Point

2-brick prism æst Pre-failed wall test

Figure 6.3.2 Bond Wrench Test Set Up

713
CHAPTER (6)- Out-of-Pbne Shake Table Testing
of Simply SupportedURM Walls

Table 6.3.1 presents a summary of the bond wrench test results showing a range of flr
between 0.17 and 0.99 MPa with a mean of 0.49MPa and overall standard deviation of
0.15MPa. The characteristic flexural tensile strength (= mean-1.64 x standard deviation)
is 0.25MPa. A comparison of this with the design fl, permitted by 453700-1998 of
0.2MPa indicates that the design assumption is slightþ conservative. A complete list of
bond wrench test results is presented in Appendix (E).
I

Tabte 6.3.1 Bond \ilrench Test Resr¡lts Sumrnary

Specimen Test Specimen Minimumf . Maximum Standard Average f,


No. Thiclness ft Deviation (3 tests)
I Prism 110mm o.22 0.36 0.07 0.28
V/all 1lOmm 0.53 0.72 0.10 o.64
2 Prism 110mm 0.30 0.41 0.06 0.36
Wall 110mm 0.39 0.54 0.07 0.47
J Prism 110mm 0.30 0.48 0.10 0.40
Wall 110mrn 0.42 0.53 0.05 0.47
4 Prism 110mm 0.35 0.48 0.07 o.42
V/all l10mm 0.39 0.84 o.22 0.61
5 Prism 110mm 0.40 0.71 o.r7 0.59
rWall 110mm 0.5s 0.99 0.25 0.71
6 Prism 110mm 0.41 0.48 0.04 0.43
Wall 110mm 0.48 0.53 0.11 0.56
1 Prism 110mm 0.50 0.68 0.09 0.6
Wall 110mm 0.27 0.53 0.13 0.41
8 Prism llOmm o.37 0.55 0.09 0.45
VfaI 110mm 0.53 0.63 0.05 0.59
10 Prism 5Omm 0.36 0.88 0.30 0.70
11 Prism 110mm o.l'l 0.55 0.20 0.32
t2 Prism 1l0mm 0.27 o.32 0.03 0.30
13 Prism 110mm 0.22 0.40 0.10 0.29
l4 Prism 5Omm 0.56 0.86 o.r7 0.76

X
6.32. Modulus of Elasticity
To determine the modulus of elasticity, Er* for each of the masonry specimens a

compressive test was conducted on a five-brick tall prism. Each prism \ryas constructed at

the same time and using the same materials as was used for each test wall. After a

minimum of 28 days a 2-inch set of Demec points was applied vertically at the center
brick and a 8-inch set on the opposite side of the prism thus covering two mortar joints
and the center brick. Following this each hve-brick prism was carefully placed onto the

tr4
CHAPTER(6)- Out-of-Pløw Shalce Tqble Testing
of S imply S upported URM Walls

base compressive platen of a hydraulic actuator. Dental paste was then applied to the top

of the prism before gently lowering the top compressive platen onto the dental paste
(refer Figure 6.3.3). This method provided an even loading platform so that stress
concentrations at the loading face would be avoided.

A preparatory compressive test was first undertaken to determine the approximate


ultimate compressive stength, f* of the prisms. Here strains wers not recorded. For
the remaining tests Demec strain readings were taken up to approximately 50Vo of the
estimated ultimate load. Each specimen was then loaded to f - without further recording
of strains (refer Figure 6.3.3 for tlpical splitting failure). Back calibration of the two
Demec readings allowed the strains in a representative sample of brickwork (one brick
{} and one mortar joint) to be determined. This permitted the stress-strain relationship to be

determined. The brickwork modulus was then calculated for each specimen as the chord
modulus between 5Vo and 33Vo of the ultimate brickwork compressive strength, f -.

I
-

Dental
Paste

Demecs

Figure 6.33 Five Brick Prism at Ultirmte Conrpressive Load

Table 6.3.2 presents a summary of the modulus test results ranging from 3,300 MPa to
16,000 MPa for the 110mm specimens and 6,700 Mpa to 9,800 Mpa for the 50mm

115
CHAPTER (6)- Ourof-Plane Shake Table Testing
of Simply Supported URM Walls

specimens. While the results vaded significantly the modulus values were typically
found to be relatively high as expected of modern masonry. For older masonry
constructed with weak lime mortars it is possible that the modulus values would be

lower, being in the order of 500MPa to l,000MPa (Robinson 1985). A complete list of
compressive test results for the five-brick prisms is presented in Appendix (E).

Table 6.3.2 Brickwork Modulus Test Results


Specimen No. Specimen Modulus Ultimate Compressive Masonry Compressive
Thiclness E- (MPa) I-oad (N) Strength, f'* (MPa)
1 ll0mm 330,000 13
2
3
llOmm
ll0mm
15,00Q
. 3;300 \
332,OOO
336,000
13.1
13.3 '2
(
4 llOmm i 3,380 ' 333,000 13.1
5 llOmm 16,000 360,000 t4.2
6 110mm 338,000 13.4 /4 touttk/-
7 l lOmrn 13,900 313,000 t2.4 d
U,r

8 llOmm 5,400 245,000 9.7 tn^"/,


11 l10mm 6,600 359,000 14.2
t2 110mm 11,600 397,000 t5.7
t3 l10mm 397,000 15.7
AVERAGE 110mm 9.400 R ¿ 339,000 13.4
STANDARI) 5,322 ) 41,528 t.g
DEVIATION

10 5Omm 9,800 307,000 26.7


t4 5Omm 6,700 303,000 26.3
AVERAGE 5Omm 8.250 305,000 26.5
STANDARI) 2,192 2,8U 0.28
DEVIATION

The masonry modulus of elasticity, E,* can be represented by the linear relationship

En -kf-

where k is a constant. Drysdale et al (1994) reported that from previous experimental


studies on clay brick prisms, k generally falls within the range of 2lO to 1670. For the
110mm prismtests k was estimated to be9,400113.4=7OO and is therefore within the
range of previous experimental results. For the 50mm bricks k was estimated to be
8,250126.5=310 and is therefore also in the lower range of the proposed values.

116
CHAPTER (6)- Out-of-Plane Shake Table Testing
of Simply Supported U RM Walls

6.33. Mortar Compressive Strength


Mortar compressive strength, f is often an important parameter for masonry because it
",
has an influence on the masonry compressive stress, however, it is typically used more as

a measure of quality control. For each test specimen three standard 100x100x100mm
mortar cubes were produced. After 28 days these were removed from their non-
absorptive casing and tested in compression. The typical failure mode was observed to
be a pyramidal shape. Due to the relatively high lime and sand content of the mortar as
compared to the cement content, the mean f of 5.17MPa
was quite low compared with
"
mortars of a higher cement content, ranging from 3.56MPa to 7.16MPa. A complete list
of mortar cube compressive test results is presented in Appendix (E)

6.4. Out-of-Plane Testing of Simply Supported URM Walls

To explore the out-of-plane dynamic response of simply supported URM walls harmonic,
pulse and transient excitation shaking table tests were conducted. The testing program is

best described by grouping the completed tests into the th¡ee construction lots of March
98, June 98 and September 98. For both March 98 and June 98, gradually increasing
harmonic excitation tests were performed on both cracked and un-cracked 110mm thick
URM walls. These harmonic tests were aimed at developing an understanding of the
basic physical characteristics governing the dynamic behaviour. Once a basic
understanding of the dynamic behaviour \ryas attained, the September 98 test series was
designed to further investigate the previously identifïed specific physical characteristics

and examine the influence of excitation frequency and amplitude on the wall's dynamic

behaviour. Consequently for the September 98 test series both pulse and real earthquake
transient excitations were used.

To complement the dynamic tests and further explore the important physical
characteristics of the out-of-plane behaviour of simply supported tlRM walls, static push
and free vibration tests were also undertaken for each wall configuration. Table 6.4.1
presents the full testing program undertaken.

tt7
CHAPTER (6)- Out-of-Plane Shake Table Testing
of Simply Supported URM Walls

Table 6.4.1 Experimental Phase Test Program

Corutruction Specinren Thickness Slenderness Overburden Dynamic Test


Lot No. (mm) Ratio (MPa)
March9S I 110 13.6 0 Un-cracked 2Hz Harmonic Excitation
0 Cracked 2Hz Harmonic Excitation
March9E 2 110 13.6 0 Un-cracked 2Hz Harmonic Excitation
0 Cracked 2Hz Harmonic Excitation
March9S J 110 13.6 0 Un-cracked Static Push Test
0 Cracked 2Hz Harmonic Excitation
March93 4 110 13.6 0 Un-cracked 2Hz Harmonic Excitation
0 Cracked 2Hz Harmonic Excitation
June98 5 110 13.6 0.15 Un-cracked l0Hz Harmonic Excitation
June98 6 110 13.6 0.15 Un-cracked 7Hz Harmonic Excitation
Cracked 7Hz Harmonic Excitation
June98 7 110 t3.6 0.15 Un-cracked 7Hz Harmonic Excitation
June98 8 110 13.6 0 Un-cracked Natural Frequency
0.15 Un-cracked Static Push Test
0.15 Cracked Static Push Test
0 Trianqular Displacement Impulse
Sentember9S 9 50 30 Poor Consfruction - Disregarded
September9S l0 50 30 0 Un-cracked Natural Frequency
0.07 Un-cracked Static Push Test
0.07 Cracked Static Push Test
0 Half Sine Displacement Pulse
007 Free Vibration Release Tests
0.07 Half Sine Displacement Pulse
0 Cracked Static Push Test
0.15 Half Sine Displacement Pulse
Septembe19E ll 110 13.6 0.15 Un-cracked Static Push Test
0 Free Vibration Release Tests
0 Half Sine Displacement Pulse
0 Cracked Static Push Test
September9S l2 110 13.6 0 Un-cracked Static Push Test
0 Gaussian Pulse
0 Transient Excitation
0 Cracked Søtic Push Test
September9S t3 110 30 0 Un-cracked Static Push Test
0 Gaussian Pulse
0 Transient Excitation
0 Cracked Søtic Push Test
September9S t4 50 13.6 0 Cracked Static Push Test
0 Gaussian Pulse
0 Transient Excitation
0.15 Gaussian Pulse
0.15 Cracked Static Push Test
0 Cracked Static Push Test

The following section describes each of the test procedures highlighting key results with
a representative cross section of results presented in Appendix (F). Both cracked and un-

118
CHAPTER (6)- Out-of-Plane Shake Table Testing
of Simply Supported URM WaIIs

cracked 'quasi-static' analyses of the test specimens are presented as these contribute to
the understanding of the wall response to dynamic loading.

6.4.1. Data Filter

The band-pass filter program, as described in Section 4.3.l,was used to filter noise from
the simply supported tlRM wall tests.

6.42. Un-cracked Natural Frequency of Vibration


In order to investigate the un-cracked natural frequency of vibration for both non-
loadbearing simply supported 11Omm and 50mm thick wall specimens, a force pulse was
applied to the wall mid-height using a rubber mallet. As displacements were too small
too measure accurately, being only a fraction of a millimeter, mid-height accelerations
were collected using the Kistler Accelerometer. Raw data was then filtered to remove
irrelevant noise frequencies and the natural frequencyresponse ofthe braced steel frame,
which tended to dominate the response.

Figure 6.4.1 shows a representative time trace for one of the tests performed on a non-
loadbearing 50mm thick wall specimen where the natural frequency of vibration is
approximately l9Hz. Similar tests on non-loadbearing simply supported ll0mm thick
walls indicated that the natural frequency of vibration was approximately 42H2.

119
CHAPTER (6)- Out-of-Phne Shake Table Testing
o1 Simply Supported URM Wølls

LINCRACKED NATIJRAL FREQUENCY - 0MPa OVERBITRDEN 5OmnTHICK WALL


FILTERED

0.04

0.03 T=0-053s T=0.053s T= 0.053w T = 0.05tuæ

0.02
\ I = t8.9llz I = tï.gllz I= tü.gltz Í =L'l'EHz

Ð
F
.E 0.01
I
d
o
o 0.00
o
o æ
4.01 I
ñ
4.02 T=0.053s T= 0.053s I=0.054s T=0.056s
f = tE.9l4z I = l8.9llz f = 18.5Ílz f =l7.EHz
{.03
\¿
{.04
Tire (Secs)

Figure 6.4.1Un-cracked Nab¡rat Frequency of Vibration 50mm Nonloadbearing \ilall

Unlike the findings of previous researchers (Lam 1995) the elastic natural frequency
appeared to be constant over the exponential decay of the wall's mid-height
displacement. This therefore supports the theory that URM walls in the un-cracked state
behave essentially as an elastically responding material. To further substantiate this a
comparison of the empirically determined un-cracked natural frequency \¡/ith that
predicted analyticaþ by simple elastic beam theory is presented in the following section.

6.4.2.1. Comparßon w¡th Simple Elastic Beatn Theory

From simple beam theory the square of the angular frequency response for a linear
elastic, simply supported beam is given by Equation 6.4.I (Gere & Timonshenco 1990)

âS'

,, - oo(E-1.)
vr)
(6.4.1)

where o = Angular Frequency =2ú


,f = Natural Frequency
E-= Elastic Modulus
m =Mass = yt
T = Material Density
t = Object Thickness
L = Object Length
I = Second Moment of Area =€t1.2

120
CHAPTER (6)- Ourof-Plane 5tu1æ Tablc Testing
of Simply Supponed URM Walls

Rearranging and substituting into Equation 6.4.2 the natural frequency of an elastic solid
beam can be shown to be:

t
r =-71 IT
t ,l /48v (6.4.2)

Using the experimentally derived E* and y, Equation 6.4.2 predicts the elastic natural
frequency for the 50mm brick wall as,

r --190.05
l -5"

and for 110mm brick wall as,

r --ta'1.5'
0.11 .4x10e
800) =50H2

As these are of the same order as experimentally derived natural frequencies it was
concluded that simple beam theory provides a reasonable prediction of the elastic natural
frequency of vibration for un-cracked simply supported LJRM walls without overburden
force applied.

6.43. Specimen Lateral Capacity Analysis


The predicted lateral acceleration capacity using the 'quasi-static' linear elastic and rigid
body analyses, as described in Chapter 5, are shown in Figure 6.4.2 for l10mm thick
walls and in Figure 6.4.3 for 50mm thick walls. The range of overburden presented is
relevant for Australian masoffy consEuction.

t2t
CHAPTER (6)- Out-of-Planc Shoke Tøblc Testing
ol Simply Supported URM Wolls

Yariable IIeigþt Thiclsress Efiective Modulus Density Flexural Tensile Strength


(m) (mm) (Mpa) ftdm1 (Mpa)
1.5 110 1000 1,800 o.46

8.00
ELASTIC 7.7i
+RJGIDBODY
'-
7.O0
a ALENERGY
z 6.00
¡r
& 5.00 )
Í¡l
Fl
re
(J
(.) 4.00

6 -/
â
rl 3.00
b ,.
â 2 00
r¡ 2.30
ú
È 1.75
1 00
0.29

0.00
0.00 0.03 0.05 0.08 0.10 0.13 0.1

OVERBURDEN STRESS AT TOPO['WALL

Figure 6.4.2 Current Available Analysis Comparison - 110mm Thick l{slt

Variable Height Thickrcss Efiective Modutus Deruity Flexural Tensile Strength


(m) (mm) (MPa) (kc/m3) (MPa)
1.5 50 5000 2,300 0.73

#
3.00
+|-LINEARELASTIC
a --_RIGIDBODY
z
2.50 #EQUALENERGY
ti
2.OO
,¿-
ú
rl
E 1.50
O 1.32
â ¿aé-
r¡ 1.18
ti 1.00
O
0.98
â
ri
ú
Cr 0.50
1-t-t'

0.13 -rtJ-
0.00
0.00 0.03 0.05 0.08 0.10 0.'13 0.

OVÐRBTJRDEN STRESS ÀT TOP OF IilALL

Figure 6.4.3 Current Available Analysis Conrparison - 110mm Thick VYall

r22
CHAPTER (6)- Out-of-Plane Shake Table Testing
of Simply Supported URM Walls

The predicted lateral acceleration capacity determined by the dynamic 'Equal Energy'
method of analysis is also included in the above plots for comparison.

For the 'quasi-static' elastic analysis prediction of the acceleration to cause cracking, the
average flexural tensile strength, fl,, determined from bond wrench tests, presented in
Section 6.3.1, was used with vertical reactions assumed to act at the centerline of the
wall. For the 'quasi-static' rigid body analysis prediction of the 'rigid resistance
threshold' acceleration, vertical reactions were assumed to act at the leeward face of the
wall. Lower values of modulus than those determined by five brick prism tests, presented
in Section 6.3.2, have been used for the 'Equal Energy' method as it was found that the
experimental values provided an unrealistically non-conservative prediction of lateral
acceleration capacity. This is because the test walls are relatively stocky and along with
the relatively high modulus the system period is lower than appropriate for the 'Equal
Energy' observation. Accordingly, the equivalent elastic prediction based on the 'Equal
Energy' observation provides a non-conservative estimate of wall's dynamic capacity.
By assuming a lower modulus the system period moves into the range were the 'Equal
Energy' observation has been shown to be more appropriate so that a reasonable estimate

of lateral capacity is achieved. It is therefore apparent that the 'Equal Energy' procedure
is not particularly relevant to the test walls however it may be more appropriate for taller
walls havin g a lar ger elastic period.

Examination of the analysis comparison plots show that for the non-loadbearing test
specimens the elastic capacity is greater than the cracked rigid capacity. For walls with
larger overburden sftess, however, the cracked rigid capacity is larger and thus in theory
dominates the behaviour. In all cases the 'Equal Energy' method provides less
conservative predictions as an allowance is incorporated for the walls 'reserye capacity'
due to dynamic stability concepts.

Table 6.4.2 presents a summary of the analytical results for the wall test specimens. The
highlighted analysis results are those which should, in theory, dominate the un-cracked
wall behavior.

123
CHAPTER (6)- Out-ol-Plane Shake Table Testíng
of Simply Supported URM Walls

Table 6.4.2 Analysis of Test Specirnen

Predicted Lateral Acceleration Capacity (g)

Height Thickness Overburden Stress Un-cracked Linear Cracked Rigid 'Equal Energy'
(m) (mm) (MPa) Elastic Analysis Body Analysis Method
1.5 110 0 1.75 o.29 2.53
1.5 110 0.15 2.3 3.62 7.72
1.5 50 0 0.9E 0.13 1.03
1.5 50 0.07 1.ls 0.65 2.15
1.5 50 0.15 1.18 1.32 2.82

6.4.4. Harmonic Excitation Tests

For the March 98 test series, harmonic excitation tests were conducted on 110mm thick
simply supported URM walls without applied overburden. For walls that fall within this
category the predicted un-cracked elastic lateral acceleration capacity of 1.75g is greater
than the cracked 'rigid resistance threshold' acceleration of 0.29g (refer Table 6.4.2). On
the basis that the peak 'semi-rigid resistance threshold' acceleration occurs at
approximately 2OVo of the incipient instability displacement, the 'semi-rigid resistance
threshold' acceleration was estimated to be approximately 207o kess than for the 'rigid
resistance th¡eshold' acceleration prediction. Consequently, for walls within this
category the cracked semi-rigid lateral acceleration resistance to rocking was estimated at
0.239.

On examination of the 'quasi-static' analysis results for the un-cracked wall specimens
the elastic behaviour was expected to dominate the dynamic response with applied
accelerations of up to 1.75g being withstood by the wall. This was then expected to be
followed by cracking and an explosive instability as the elastic kinetic and stored strain
energy would be sufficient to overcome the potential energy requirement for the wall to
become unstable. For pre-cracked walls the non-linear behaviour was expected to
dominate the response with accelerations at the wall's effective mass of up to
approximately 0.239 withstood prior to rocking, followed by a transient and then steady-
state response. Failure of the wall was then expected to only occur when the table
amplitude was increased sufficiently so that the maximum steady-state displacement
exceeded the incipient instability displacement. The applied acceleration can therefore be

t24
CHAPTER (6)- Out-of-Plane Shake Table Testing
of Simply Supported URM Walls

related to the level of displacement amplification and in turn to the wall's dynamic
'reserve capacity'.

To examine the physical dynamic response characteristics for both cracked and un-
cracked walls within this category, harmonic tests were conducted on each. In the March
98 test series a gradually increasing 2Hzharmonic excitation was selected for input to the

shake table as this was considered representative of what could be expected in URM
construction where the ground motion is filtered through the building. Of a more
practical concern, at this excitation frequency the predicted lateral accelerations required
were also within the capabilities of the shaking table.

Figure 6.4.4 (a) - (c) presents typical results of a 2Hz harmonic test completed on a non-
loadbearing and un-cracked 110mm thick simply supported URM wall. The
displacement versus time plot, shown in Figure 6.4.4 (a), indicates that prior to t=16
seconds the wall response was elastic and the wall's mid-height displacement responding
in phase with the table excitation. At t=16 seconds the wall was observed to crack. The
input acceleration at the base and top of the wall at this time was recorded as 0.309 (refer
Figure 6.4.4). As the relative elastic mid-height displacements were very small prior to
cracking the mid-height response acceleration was un-amplified at 0.3g. As the input base
ha¡monic displacement at this time was 19mm, the measured harmonic input acceleration
can be checked using a similar procedure to that outlined in Section 4.3.3 and Equation
4.3.4.

ânnx = l-eo' l= l-¡rerrn'l= l-n(+n)21 = ß7.9 A qmm/s2) = 0.0161 A (g)

= 0.0161(19) = 0.30 g

In contrast to the predicted elastic acceleration capacity the input base acceleration to
cause cracking of 0.309 was much lower than the predicted 1.7 59. On examination of the

wall mid-height acceleration data, high frequency spikes of greater than 29 were
observed just prior to cracking. These acceleration spikes were thought to have been a
consequence of the wall initially rocking as a single free body and impacting with the top
'cornice' support. The high impact accelerations are thought to have had sufficient

125
CHAPTER (6)- Out-ol-Plane Shqke Table Testing
of Simply Supported URM Walls

energy to crack the wall prematurely. To further substantiate this on cracking at mid-
height and the commencement of rocking as two free bodies the impact at the top support
was reduced and the high frequency spikes no longer observed. This finding highlighted
the possible non-conservative nature of adopting a stress based elastic analysis procedure
for this category of non-loadbearing URM wall.

After the premature cracking the wall's response underwent a transition to steady-state

rocking without becoming unstable as the elastic kinetic and stored strain energy were
insufficient to overcome the potential energy required to cause instability. Following the
transition phase the steady-state mid-height response rocking phase was observed to be
180o out of phase with the table excitation having a mid-height displacement

amplification of 45119 = 2.4. During the steady-state rocking response fhe Vt - and 3/c -
height accelerations were observed to reduce and the mid-height response acceleration
increased (refer Figure 6.4.4(b)). This indicated that the center of gravity (CG) of the two

rocking rigid bodies became closer to being stationary in space. Should the excitation
frequency have been increased further, according to 'equal displacement theory', the CG
would be expected to become completely stationary so that the wall mid-height would
have responded at the same displacement as the table. This would therefore reduce the

effective mid-height displacement amplification thus increasing the walls dynamic


'reserve capacity'.

Figure 6.4.4 (c) shows the hysteretic acceleration-displacement (a-A) behaviour where
initially the un-cracked behaviour was observed to be linear. After cracking the dynamic
wall behaviour switched to follow the non-linear a-À displacement relationship.

Figure 6.a.5 @) - (c) present typical results of a ZHz harmonic test completed on a pre-
cracked non-loadbearing 110mm thick simply supported URM wall. These show that
prior to t=32 seconds the 'semi-rigid threshold resistance' acceleration had not yet been
exceeded at the mid-height of the wall so that rocking had not yet commenced. The test

wall's dynamic behaviour was however governed by the cracked non-linear a-Â

relationship so that mid-height displacements were observed to be larger than for the un-

126
CHAPTER (61 Outof-Plane Shake Table Testing
of Simply Supported URM Walls

cracked wall specimens. Here the wall mid-height was responding in phase with the
table motion although some acceleration amplification of the wall mid-height was
observed due to the larger displacement response. At t=32 seconds the 'semi-rigid
threshold resistance' acceleration was exceeded at the mid-height of the wall. At this time

the wall mid-height response acceleration was 0.349 having a displacement amplitude of
2lmm. This can again be confirmed using a similar procedure to that outlined in Section
4.3.3 and Equation 4.3.4.

irnnx = l-Ro' l= l-lçzrq¡21= 0.0161 (21) =0.34 g (wall mid-height).

Following the commencement of rocking a transition period prior to steady-state rocking


response phase occurred. During the steady-state rocking response the wall mid-height

was again observed to have changed to respond 180o out of phase with the table motion.
A displacement amplification of the mid-height respons e of 37114=2.6 was observed.

Although not shown experimentally it can therefore be postulated that once a steady-state
rocking response had commenced without becoming unstable during the t¡ansition
period, the amplitude of the 2Hz excitation could then have been increased to ll}12.6 =
42mm prior to the instability displacement being reached. This input displacement
excitation corresponds to an input acceleration of 0.679. Thus, for the 2Hz harmonic
excitation this wall would have a 'reserve acceleration' capacity of 0.67-0.33 = 0.34g.
Even considering the full predicted dynamic 'reserve capacity' of the wall the 'Equal
Energy' prediction of 2.539 remains extremely non-conservative providing a misleading
assessment of the wall's acceleration capacity for the excitation being considered.

If the full dynamic 'reserve capacity' is to be relied upon for the assessment of cracked
URM walls, as has been proposed by previous researchers (ABK 1984, Priestly 1985), it
is important to assess the ability of the rotating mortar joints to sustain repeated loading
cycles during rocking. Throughout the March 98 series of harmonic tests on walls
without applied overburden, the ability of mortar joints to sustain repeated loading cycles
during rocking was found to be very good with only minor degradation observed. As will

127
CHAPTER (6)- Out-of-Plane Shake Table Testing
of S i¡nplv Swp orted U RM Walls

be discussed in Section 6.4.5 static push tests have been used to quantify the degradation

of the mortar joints caused by dynamic testing.

Table 6.4.3 presents a summary of results for the March 98 test series. A final
observation was that for cracked walls the mid-height response acceleration at the
coilrmencement of rocking w¿rs typically of the order of 1.5 times the estimated 'semi-
rigid threshold resistance' acceleration (0.341O.23=1.5). This suggests that for a pre-
cracked simpty supported IJRM wall, during dynamic loading a triangular wall
acceleration response relative to the supports is likely, resulting from the larger mid-
height response displacements as compared with the base and top of the wall.

t28
CHAPTER (6)- Out-of-Plan¿ Shak¿ Table Testing
of Simply Supponed URM Walls

(a) 70
60 -stâfe
50
40
30
420 -INSTRON
TWD
ëro
Ë0
Ê -ro
o r
Ë -zo
Ê -30
i5 ¡o
-50
{0
-70
-80
rllls(wsr
-90

(b
0.6
0.5
0.4
Mid-heieht acceleration at crackinq = 0.3s .t rl I

I t l-t il
0.3
¡'rllll ll lll
o 0.2 .rllI U
t
.E
0.1
EO
o
E ¡.r
<o 4.2
4.3
44 -TT/A
BWA
4.5
{.6 -TA
-TTA

(c TIYSTERESIS

Initial linea¡ elastic stiffness

At cracking just below 'semi-rigid


d)

o
+

d
o
o
o
o
ooô
*\oæ
Ð
¡¿
o

à non-linear a-Â relationship

Mid-beigbt Dþlacernt (rnm)

(l l0mm Wall, 2Hz Ha¡monic Excitation)


Figure 6.4.4 Urrcracked Non-loadbearing URM Wall Harmonic E¡citation Test

r29
CHAPTER (6)- Ouçof-Pløne Shake Table Tesrtng
of Simply SupportedURM Wqlls

Sæady
(a) 90
80
70
60
450 Resistance F-xce¡¡led I¡ ll
E¿o
Ë30
Ëzo
Hro
ã.0
i5-10
_20
r
-30
40
-50
60 r urÉ \ùecs,
_70

0.6
0.5
0.4
0.3
6 0.2
0.1
o 0
ão {.1
4.2
4.3
4.4
-TWA
BWA
{.5
{.ó
4.7 -TIA
-TA
ITYSTERESIS
(c

d)
ô
d
o
o
a
o
ooooo ooooooo
¡Ð r91T1 otn\orooo\
ô 7
¿
à

Mid-beight Displacenent (mm)

(1 l0mm Wall, 2Hz Harmonic Excitation)


Figure 6.4,5 Pre-cracked Norrloadbearing URM \{all Harmonic Excitation Test

130
CHAPTER (6)- Out-of-Plan¿ Shakc Table Testing
of Simply Supponed URM Wølls

Table ó.4.3 llùnm Wall, Non-Iædbearing - Ilarnronic Excitation Test Results


\ilall Wall Predicûed 'Quasi- Experinrcntal Comrrcnt
No Condition Static' Results
Acceleration
Capacity
(Refer Table 6.4.2)
Un-cracked 1.759 A=20mm (O.32e) Table input at crackinghocking
(032e) Mid-height acceleration response at
crackinglrocking (no amplification)
- High frequency spike (l2Hz) >2g prior to
cracking
50t2È2.5 Steady-state response displacement
amplifrcation
I Cracked 0.29e (Rigid) A=l5mm (0.2ag) Table input atrocking
0.23g (Semi-rigid) A=2lmm(03ae) Mid-height response at rocking
- No high frequency spikes observed
4Ol16=2.5 Steady-state response displacement
amplification
) Un-cracked 1.75g A=l6mm (O.Z6e) Table input at cracking/rocking
(o.2ee) Mid-height acceleration response at
cracking/rocking (small amplifrcation)
- High frequency spike (lzHz) >2g prior to
cracking
- Some elastic acceleration amplification
- Wall became unstable immediately after
cracking (no steady-state response)
2 Cracked 0.299 (Risid) A=l5mm (O.Ue) Table input at rocking
(refer Figure 0.239 (Semi-rigid) A=2lmm (0.3ae) Mid-height response at rocking
6.4.s) - No high frequency spikes observed
37114=2.6 Sûeady-state response displacement
amplification
3 Cracked 0.299 (Rigid) A=16mm (0.26e) Table input at rocking
0.23g (Semi-rigid) A=22mm(0.35g) Mid-height response at rocking
- No high frequency spikes obsewed
Morta¡ drop out prevented steady-state
response from occurring
4 Un-cracked 1.75g A=l9mm (0.30g) Table input at cracking/rocking
(refer Figure (0.30e) Mid-height acceleration response at
6.4.4) cracking/rocking (no amplification)
- High frequency spike (l2Hz) >2g prior to
cracking
45119=2.4 Steady-stat€ response displacement
amplifrcation
4 Cracked 0.299 (Rigid) A=13mm (O.zle) Table input at rocking
0.239 (Semi-rigid) A=19mm (0.30g) Mid-height response at rocking
- No high frequency spikes observed
Sæady-state response displacement
35113=2.7 amplification

l3t
CHAPTER (6)- Out-of-Plane Shake Table Testing
of Simply Supported URM Walls

For the June 98 test series, harmonic excitation tests were conducted on 110 mm thick
simply supported URM walls with 0.15 MPa applied overburden using the spring
overburden rig shown in Figure 6.2.5. As described in Section 6.2.2 for mid-height
displacements greater than approximately 2OVo of the wall thickness the additional static
spring deflection caused an unacceptable increase in overburden force at the top of the
wall. Results were therefore only valid for mid-height displacements less than 2OTo of

the wall thickness. For walls within this category the predicted un-cracked elastic lateral
acceleration capacity of 2.3g is less than the cracked 'rigid resistance threshold'
acceleration of 3.629 (refer Table 6.4.2). Estimates of the 'semi-rigid resistance
threshold' acceleration were approximately 20Vo less than for the rigid case where the
resistance to rocking was estimated to be2.9 g.

Accordingly, even for the un-cracked wall the non-linear cracked wall behaviour was
expected to dominate the dynamic response with cracking of the wall not expected to
have significant impact on the dynamic behaviour. Hence, initially elastic behaviour
was expected up to applied accelerations of 2.3 g followed by cracking with a slight
increase in the wall mid-height displacement response. An increase in applied

accelerations up to 2.9 g at the mid-height of the wall was then expected to be applied
prior to a transient then steady-state rocking response. As per the previously described
March 98 cracked wall response, failure was then expected to only occur when the table
amplitude was increased sufficiently so that the maximum steady-state displacement
exceeded the instabitity displacement. This would therefore again be related to the

displacement amplification and in turn to the wall's dynamic 'reSeIVe capacity'.

Thus, to examine the physical dynamic response characteristics of both cracked and un-
cracked walls within this category, harmonic tests were conducted on each wall
specimen. Much higher inertia forces were required for this test series so 7Hz to 10Hz
harmonic table excitations were selected. These were still considered to be representative
of what could be expected in URM construction due to ground motion. However, since
these frequencies were close to the resonant frequency of the braced steel frame some
amplification of the base excitation was observed at the top support.

t32
CHAPTER (6)- Out-of-Plane Shake Table Testing
of Simply Supported URM Walls

Figure 6.4.6 (a) - (c) present typical results for aTHz harmonic test of an un{racked 110
mm thick simply supported URM wall. The displacement versus time plot shown in
Figure 6.4.6 (a) indicates that prior to t=4.4 seconds the wall response was elastic and the
mid-height response and table excitation were in phase. At t=4.4 seconds the wall was
observed to crack with displacements increasing slightly. However, the mid-height
response and table excitation remained in phase (refer Figure 6.4.7) indicating that
rocking had not yet commenced. The average input acceleration at the time was recorded
as 1.8 g with the mid-height wall acceleration being 2.I g (refer Figure 6.4.6 (b)). Since
the input harmonic displacement at this time was 9mm this can again be confirmed using
a similar procedure to that outlined in Section 4.3.3 and Equation 4.3.4.

âmax = l-Ro' l= l-4zrç¡'l= l-n(t+n)'l = rg34.4 A (mm/s2) = 0.197 A (g)

= 0.197(9) = 1.8 g

Following cracking the 7Hz-table excitation amphtude was further increased until at
t=19.45 seconds the 'semi-rigid threshold resistance' acceleration was exceeded at the
mid-height of the wall. At this time the wall mid-height response acceleration was 4.3g
having displacement amplitude of 22 mm. This can again be checked by the following
calculation,
Írnnx = l-Ro' l= l-1r2nn2l=0.197(22) = 4.3g (wall mid-height).

Following the commencement of rocking a transition period prior to steady-state rocking


response phase occurred. During the steady-state rocking response the wall mid-height

was again observed to have changed to respond 180o out of phase with the table motion.
A displacement amplification of the mid-height response of 2519=2.77 was observed
(refer Figure 6.4.8).

r33
CHAPTER (6)- Out-of-Plane Shqke Table Testing
of Simply Supponed URM Walls

(a)
50

40

â30
g20
-INSTRON
TIVD
910
o
!0
À
.,"r ',' 1""" ' l't" r" ll',1 l'ì,lli ¡ti¡l lii
r
.F -lo
H ojôioo*\ \o o\
:20

-30
First cracking at 4.4 seconds
40
-50

(b) WALL ACCELERATIONS


6

Mid-height acceleration at rocking = 4.3g


4 -TWA
BWA

d)
.,
r' I ¡ | i{ T

€o
o rÉ;l Éh
o
o oô''\0 rç É ,&;
ó\
o d ..i ñ'pl?

4
Mid-height acceleration at fust crack = 1.99 Tine (Secs)

(c) HYSTERISIS
due to increased static
commencementof rockins spnng deflechor
ôo
{
É

d
.H//5V/'\-
7rz
o
o -
7-7
a "¿
o

d
Eo
¿
¿
,aniln
ANAæ
--Wv
Non-[neaf a-a fera[onsnrP

Mid-height Displacerent (mm)

(110mm V/all, 0.15MPa Overburden, 7Hz Harmonic Excitation)

Figure 6.4.6 Un-cracked NonJoadbearing URMWatl Harmonic Excitation Test

t34
CHAPTER (61 Ourof-Pl"ane Shake Table Testing
of Simply Supported URM Walls

8
6
4
la

Ë0
Ir
o
-Ë4
À
¡5 -o
-8
-10 TWD
-INSTRON
-12

(l10mm Wall, 0.l5MPa Overburden, 7Hz Harmonic Excitation)


Figure 6.4.7 Un-cracked NonJoadbearing URM Wall - First Cracking

50
40
a30
E
820
-MWD
TWT)
-INSTRON
'; f, t^\
xF10
õ0
o
A I I
+l I'l'
È-r0 æ ¡ -1
â-zo
V
-30
40 r rnË \ùcct,
-50

(l lOmm ÌWall, O.lSMPa Overburden, 7Hz Harmonic Excitation)


Figure 6.4.8 Un-cracked NonJoadbearing URM Wall - First Rocking

Typically, for the walls tested with applied overburden, once rocking commenced there
was a rapid degadation of the mid-height rotation joint. Physically this could be seen as
mortar being broken from the rotation joints by the impact of the two free bodies. This
was attributed to the rocking frequencies and impact forces being much larger for the
loadbearing walls. As a result of the degradation during rocking an increase in
displacement and reduction in response acceleration was observed, without further
increase in excitation until instability.

Table 6.4.4 presents results of the June 98 test series for 110 mm thick IJRM wall with
0.15 MPa overburden stress. These walls were subjected to an out-of-plane gradually
increasing 7 or 10 Hz harmonic excitation. Consistent with the March 98 tests, a final

135
CHAPTER (6)- Out-oÍ-Plnn¿ Shake Table Testing
of Simply Supponed URM Walls

observation from this test series was that for cracked walls the mid-height acceleration at
the commencement of rocking was again typically of the order of 1.5 times the estimated
'semi-rigid threshold resistance' acceleration.

Table 6.4.4 ll0mm WaIl, 0.15MPa - Ilarnnnic Excitation Test Results

WaIl Test Wall Predictcd 'Quasi- Experirrcntal Cornrnent


No Condition Static' Acceleration Results
Ca¡ncity
(Refer Table 6.4.2)
5 IOHz Un-cracked 2.3g (Cracking) A4mm (1.69) Average support input at
Harmonic 3.62e (Rieid) cracking
2.9g (Semi-rigid) (2.0e) Mid-height acceleration
response at cracking
A=5mm (2.0g) Average support input at rocking
A=10mm (4.1g) Mid-height response at rocking
- Amplification at top support as
at black frame resonance
6 7Hz Un-cracked 2.3g (Cracking) A=6mm (1.2g) Average support input at
Harmonic cracking
(1.6e) Mid-height acceleration
response at cracking
6 7Hz Cracked 3.62e (Rigid) A=8mm(1.6g) Average support input (rocking
Harmonic 2.9g (Semi-rigid) A=10mm (2.0g) not yetcommenced)
Mid-height response (rocking
not yet commenced)
7 7Hz Un-cracked 2.3g (Cracking) A=9mm (0.18g) Average support input at
Harmonic 3.62g (Rieid) cracking
(refer 2.9g (Semi-rigid) (2.re) Mid-height acceleration
Figure response at cracking
6.4.7) A=I2mm(2.4g) Average support input at rocking
A=22nm(4.39) Mid-height response at rocking
25llO=2.5 Sæady-state response
displacement amplification
-Rapid joint degradation during
rockinq

From both the harmonic March 98 and June 98 test series it was concluded that for most
practical cases non-linea¡ cracked behaviour is more relevant to a dynamic loading
scenario than the un-cracked properties. Also, from the identified dynamic mid-height
non-linear cracked F-A relationship, a fiiangular distribution of horizontal acceleration up
the height of the wall assumption relative to the supports has been identif,red as likely to
provide the best approximation of acceleration response.

136
CHAPTER (6)- Out-of-Planz Shalæ Tablc Testing
of S inply Supporîed URM Walls

6.45. Static Push Tests

To investigate the out-of-plane non-linear F-Â behaviour of simply supported URM walls
static push tests were conducted on both un-cracked and cracked wall test specimens. The

braced steel support frame was used to simply-support the wall panels in these tests.
Ioading was applied at the wall mid-height using a hand pump driven hydraulic actuator
(refer Figure 6.4.9). This was geometrically similar to statically apptyrng the same force
at the wall r/t - and t/¿ - height being the center of gravity (CG) of each of the two free
bodies. The applied static load was therefore related to the 'quasi-static' assumption of a
rectangularly distributed load having a resultant horizontal force at the free body CG.

A calibrated load cell was inserted between the actuator and the wall at mid-height to
record the resisting force applied by the wall onto the actuator. This force was recorded
for displacements from the vertical position to as near as possible to the incipient
instability displacement, where the resisting force was reduced to near zero. The recorded
data was that of the 'quasi-static' non-linear F-Â relationship by means of a rectangular
distributed load.

Í--
i r¡*
l I

Hand operaæd
hydraulic ram

Figure 6.4.9 Static Push Test

137
CHAPTER (6)- Outof-Plane Shal<e Table Testing
of Simply Supported URM Wqlls

A summary of the key results for the static push test and a comparison with static analysis
is shown in Table 6.4.5. Arepresentative cross-section of the experimentally derived F-A
plots is presented in Appendix (Ð. r- - /f,f F i'
^/rrt^t
Table 6.4.5 Resr¡lt Sumrmry of Static Push Tests

Construction WaIl Wall Thick Over- Predicted Peak Disp Vo o1 Conr¡rænt


Lot No. State -ness burden 'Static Force* at Rigid
(mm) (MPa) Capacity' (kN) Peak
(kN) Force
(mm)
March93 3 Un- 110 0 (r-B)2.@ 3.18 0.5
cracked (Pß) 0.41
June98 8 Un- 110 0.15 (rÆ) 4.82 5 0.45
cracked (RB) 5.31 6.2 2I
June98 8 Cracked 110 0.15 ( F)2.32 4.36 18.5 82 f .{MPa
(RB) 5.32
September9S 10 Cracked 50 0 (LE) 0.07 0.09 6 82 f ,{MPa
ßB) 0.r1
September9S 10 Un- 50 0.075 (LE) 1.07 0.95 0.79
cracked (Rß) 0.59
September9S 10 Cracked 50 0.075 (rÆ) 0.2e o.49 8.3 79 fd)MPa
(RB) 0.62
September9S 1l Cracked 110 0 .rl-ÐO.N 0.3 12.6 73 fl,{MPa
(RB) 0.41
September9S l1 Un- 110 0.15 (tÐo.n 4.5 0.66 Increased
cracked (RB) 0.41 5.3 21.5 spring
static
deflection
Sepûembcr98 12 Un- 110 0 .o-Ð2.8 3.0 0.3
cracked ßB) 0.41
September9S 12 Cracked 110 0 (LE)O.n 0.38 8.1 92 f ,=OMPa
(RB) 0.41
September9S T3 Un- 110 0 (rß)2.64 2.2 0.59
cracked ß.8) 0.59
Sepûember98 13 Cracked 110 0 (LF.)0.27 0.33 10 81 f ,{MPa
(RB) 0.41
September9S t4 Cracked 50 0 (LE) 0.07 0.084 8.8 77 f,=0MPa
(RB) 0.11 -before
dynamic
September9E T4 Cracked 50 0 (r-E) 0.07 0.075 10 68 f,=0MPa
(RB) 0.11 -afær
dynamic
September9S t4 Cracked 50 0.15 Q-E)0.47 o.7l 10 66 f ,{MPa
(RB) 1.07
* Real 'Semi-rigrd Force
r F = Linear Elastic Analysis
RB = Rigid Body Analysis

138
CHAPTER (6)- Outof-Plnne Shakc Tøblc Testing
of Simply Supported URM Walls

Examination of the un{racked wall static push test results indicated that the linea¡ elastic
analysis predicted the 'static' cracking load reasonably well, within the limits of accuracy

of the flexural tensile strength prediction.

For the cracked wall specimen tests, the predicted 'rigid threshold resistance' force,
R"(1), determined by rigid body analysis, was observed to overestimate the real 'semi-
rigid threshold resistance' by lÙVo to 4O7o wlnch was attributed mostly to the real 'semi-
rigid' nature of the masonry material. As highlighted in Section 5.3, a simple analytical
method has been proposed for predicting the semi-rigid F-A relationship (Priestþ 1985)
based on the assumption of a proportional relationship between the wall curvature and the

stress gradient across the critical section. This was not found to represent the current
tests well as it overestimated the initial stiffness and 'semi-rigid threshold resistance'
force, R*(1). Figure 6.4.10 presents a comparison of the analytical F-Â prediction for the
non-loadbearing 110mm thick specimen no.10 wall and Figure 6.4.11for the 50mm thick
specimen no.ll wall. Here, moduli of elasticity of 1000MPa were used to maintain the
initial stiffness and 'semi-rigid resistance threshold' force within reasonable limits. A
second shortfall was that the effect of degradation of the mortar joints could not be
considered.

120

2 ÐGERIMENTAL
X
H
r00 +PRIESTLYMETHoD
v +-RIGIDBODY
180
860
F
ç,
õ40

R
Ê

0
nono
ÊôtNo nono
6rftn
MID IIEIGHT DISPLACEMENT (mm)

Figure 6.4.10 comparison of ll0rnm specimen static Push F-a with anaryticat

r39
CHAPTER (6)- Ourof-Plane Shake Table Testing
of Simply Supported URM Wqlls

400
ÐGERIMENTAL
2 350 +PRESTLYMETHOD
H
300
RIGIDBODY
J
F 250
z
ô. 200
F
150 E= 1000MPa
H Septernber 98
r00
u Speciræn ll
¿ 50 SmmMortar Rake

0
oooeQ ooooo
\¿)ræo\3
Écloçn
MID HEIGTfT DISPLACEMENT

Figure 6.4.11 Comparison of S0mm Specimen Static Push F'A with Anatytical

After dynamic testing the degradation of rotation joints was observed and related to a

of the static F-À relationship and thus a lowering of average response


flattening
frequencies. To quantify this degradation the wall specimens were catagorised
throughout the dynamic testing as new, moderately degraded or severely degraded by
their appearance as shown in Figure 6.4.12. Using this visual categorisation of the wall
specimens, some broad empirically based predictions of the static F-Â relationship could

be made in relation to the idealised bi-linear rigid F-A relationship. The empirically
determined predictions are discussed further in Chapter 7 as they are related to the

modelling of the non-linear force displacement relationship required for THA.

Tests on non-loadbearing l lOmm thick walls were also performed having displacements
reduced from the incipient instability displacement to investigate the static hysteretic
behaviour as presented in Appendix (F¡. The area encompassed by each hysteresis loop
provided an indication of the energy loss per half cycle caused by joint rotation and
friction at the connections. The resonant energy loss per cycle method of estimating
damping was then used to assess the level of damping within the rocking system. Using
this approach the energy dissipated in a vibrational cycle of the wall was equated to that
of an equivalent viscous system. It was found that the equivalent single degree-of-

freedom (SDOÐ equivalent viscous damping (6sm") was approximately tÙVo,being of a

140
CHAPTER (61 Ourof-Plnne Shake TabI¿ Testing
oÍ Sinply Supported URM Walls

similar value to damping results determined in Section 6.4.6 by free vibration tests.
However, the accuracy of this method is limited as it only considers the response at
resonance. The highly non-linea¡ shape of the F-Â relationship for LIRM walls makes the
effective half cycle stiffness non-unique so that it is also difficult to use this method.

Moderaûe degraded wall


Visible crack slightly
rounded

drop out
New condition wall and crack
significantly
Severely degraded rvall rounded

Figure 6.4.12 Mid-height Rotation Joint Condition

From the static push tests on 110 mm walls with a 0.15 MPa overburden, it was
confirmed that a significant additional restoring force occurred at large mid-height
displacements due to the increased spring deflections. Consequently, for mid-height
displacements greater than approximately 207o of the wall thickness the constant force
assumption \ryas no longer valid.

In Section 6.4.6 the F-À relationships determined by the static push tests have also been
used for comparison with dynamic F-Â relationships, derived in accordance with the
assumption of a uiangula¡ distribution of acceleration. Here the response of the effective

t4r
CHAPTER (6)- Ourof-Plane Shøke Tøblc Testing
of Simply Supponed URM Walls

masses at 213 the free body height correlate well with the static push test results. This
further supports the use of a triangula¡ distribution of acceleration.

6.4.6. Free Vibration Tests

Free-vibration tests were performed on test specimens which were pre-cracked at mid-
height to investigate the physical characteristics of the free vibration response of simply
supported URM walls. To enhance the investigation of the free vibration response
additional data points have also been derived from the free vibration phase ofpulse tests,
reported in Section 6.4.7.t. To undertake these tests, the mid-height of the cracked test
panel was displaced statically to near the incipient instability displacement. In effect the

wall was provided with a degree of potential energy equal to that required to move the
wall from its initial vertical position to that of the incipient instability displacement.
From this displacement the wall specimens were released and permitted to vibrate freely
i.e. to rock between their leeward faces. This vibration resulted from a continuous energy
balance comprising an exchange of potential and kinetic energy. During the response the
total system energy was exponentially reduced to zero by energy losses associated with
the incremental damping at the crack closing impact and support friction. At that time
both the potential and kinetic energy are reduced to zero and the vibration ceases with the
wall in the vertical position.

The same instrumentation to that described in Section 6.2.3 was used to record both the
mid-height displacement and acceleration of the free vibration response. A representative
cross-section of the free vibration test results are presented in Appendix (F). For these
tests as well as the mid-height acceleration and displacement response the mid-height
hysteretic behaviour is also presented. From the free vibration tests the a-Â relationship
and thus the mid-height 'semi-rigid resistance threshold' acceleration and approximate
displacement at which this occurred were determined. Further, by adopting the
assumption of a triangular distribution of acceleration relative to the supports, the 'semi-
rigid resistance threshold' acceleration at the effective mass was determined as 213 of the
mid-height 'semi-rigid resistance threshold' acceleration. Table 6.4.6 presents a

summary of the free vibration release results.

r42
CHAPTER (6)- Ow-of-Plarc Shak¿ Tabl¿ Testing
of SirrWIy Supported URM Walls

Table 6.4.6 Summry of Release Test Results

Wall Thichress Over- 'Quasi-Static' Mid-height Efiective Mass Displacenrcnt at


No (mm) burden RigidBody 6Semi-rigid
'Senú-rigid 'SemÍ-rigid
(MPa) Acceleration Resistance Rcsistance Resistance
Capacity Threshold' Threshold' Ihreshold'
(Refer Table Acceleration Acceleration (mm)
6.4.21 (c) G)
l0 50 0 0.13 0.19 o.r2 9
10 50 0 0.13 0.18 o.t2 8
10 50 0.07 0.65 0.78 0.52 9
ll ll0 0 0.29 0.35 o.23 l5
1l ll0 0 0.29 0.35 o.23 t6
il 110 0 o.29 0.32 o.22 t7

As the effective mass 'semi-rigid resistance threshold' acceleration is consistently just


below the predicted 'quasi-static' acceleration this further suggests that the assumption of
a triangular acceleration distribution and thus effective mass location at the 213 freebody
height, is reasonable.

6,4.6. I. N o n-línear F requency - Mid- H eíght Dísplac eme nt Relationship

For all of the free vibration responses analysed, each cycle of the displacement response
was considered in turn. In doing so each mid-height response cycle start amplitude, Â1,

finish amplitude, Lz, and cycle period, T were determined as shown by Figure 6.4.13.

MID-HEIGITT FREE VIBRATION RESPONSE

20

g15
ä
2rc
E]

I
t\ \
A1

L2

+#
E]
o5

l \ I
ã0
Fi / -...i -..': -\ - -:
' O È Nló
-.: l-:
*
JS
l-
Þ
..:
q\ 'r4 q ù../ F M
f;-s
d\.,/NNNddN(

ó
E -10
\ I
-15

T TIME (SECS

-20

Figure 6.4.13 Free Vibration Calculation

143
CHAPTER (6)- Out-of-Pbne Shak¿ Tabl¿ Testing
oÍ Simply Supponed URM Walls

The average cycle amplitude, Au, was determined as,

Lo
2

and the individual cycle frequency as,

r =Yr

Having determined this information for each cycle, the non-linear frequency versus Âo

relationship was plotted including an exponential or logarithmic line of best ht. Figure

6.4.L4 presents this relationship for 50 mm thick specimens at various levels of applied
overburden and Figure 6.4.15 for 110 mm thick walls with no applied overburden. A
comparison of the empirically derived /-Au relationships with an analytical prediction
derived by the comparison of the dynamic equation of motion for a SDOF system and
those for the non-linear rocking system is presented in Chapter 7.

80
¡ trNOPRECOMP
7 0
. NOPRECOMPLogfit
o
ú e.o tr tr0.075MPa
z ¡ 0.075MPa Exp frt
o tr0.15MPa
t-
<
J
5.0 . 0.l5MPaExp fit
È
O EItr EPARAPET
8 +.o . PARAPET fit
sF tr
ð s.o
zFI
Þ
g 2.0
a
F B
o I o.
É
1.0
lÐh d
0.0
0 5 l0 15 20 25 30 35 40 45 50

AVERAGE CYCLE MID.IIEIGIIT DISPLACEMENT

Figure 6.4.14 50mm Specimen Frequency vs Average Cycle Mid-Height Disp.

144
CHAPTER (6)- Out-of-Plane Shake Tøble Testing
of Simply Supponed URM Walls

8.0

trNOPRECOMP
7.0
l INO PRECOMP Log [rt
se 6.0
z
o
f
F-
5.0
E
O
8 ¿.0

h"*
l&

tr
z
3.0
Êl
Ð
flú z.o
I&

1.0

0.0 -r-
0 10 20 30 40 50 60 't0 80 90 r00 110
AVERAGE CYCLE MID HEIGI{I DISPLACEMENT (mm)

Figure 6.4.15 1l0mm Specimen Frequerrcy vs Average Cycle Mid-Height Disp.

6, 4. 6. 2. N o n- lin e ar Dy namic F orc e - Mid- H eight Dß plac em e nt Relatío ns hip

Rearranging the previously established dynamic relationship (Clough et al1993)

a 2d E
tl* "
where o= cycle angular response frequency

IÇ = average cycle secant stiffness


M" - effective mass of the free body

the average cycle secant stiffness can be written as,

K,=(?-t¡f), M" (6.4.3)

Following from this an estimate of the response force can then be determined as

F =Ko 1,"= (Zr{), M L" (6.4.4)


"
where Â. = displacement of the effective mass

t45
CHAPTER (6)- O*of-Pbne Shakc Table Testing
of S imply Supp orted URM WølIs

Assuming that the acceleration response of each of the rocking free bodies is triangularly
distributed relative to the supports, the effective mass is located at 213 the height of the
free body. Consequently the ayera1e effective mass displacement, Â., can be related to
the average cycle mid-height displacement, Àn, bY
,)
o"=ío'

Substituting A" back into Equation 6.4.4 the force response at the effective mass can be
determined as,

, =1*, L"=|Q"f)' M
"
L^ (6.4.s)

This relationship is therefore directly comparable with static test results. From Equation
6.4.5, the dynamic F-A relationships at the effective mass for the test specimens have
been determined. Each point shown on Figure 6.4.16 shows this relationship for each
free vibration response cycle of the 50 mm thick specimens at various levels of applied
overburden and is compared with the bi-linear static rigid body F-A relationship. The

line of best fit has been derived using the line of best f,rt from the /-Â relationship
discussed in Section 6.4.6.I. Similarly, each point shown on Figure 6.4.17 represents the

relationship for each free vibration response cycle of the 110 mm thick walls with no
applied overburden again compared with the bi-linear static rigid body F-A relationship.

146
CHAPTER (6)- Out-of-Pløne Shake Tqbl¿ Testing
of SimPlY StPPorted URM Walls

tzOfj

tr NOPRECOMP
O NOPRECOMPLogfit
r000 {-NOPRECOMPRigidBody
tr 0.075MPa
O 0.075MPaE4fit
0.075MPa Rigid Body
800
tr 0.15MPa
a O.l5MPaExp fit
a t0.l5MPaRigidBody
rll
() 600
tr tr PARAPET
ú a . PARAPETITgfiT
l& PARAPET
tr a a
tr
400
D. tr


200
¡
p
0 -n
0 5 10 15 20 25 30 35 40 45 50
AVERAGE CYCLE MID TIEIGIIT DISPLACEMENT (mn)

Figure 6.4.16 50mm Wall Dynamic F-A Relationships (Various Overburden)

450

400

350
tr No pnncorvrp
a nopnncoMPlogñt
300
¿ tr
+No pnscoMp Rigid Body
H 250
O
ú tr
Ê zoo

150
\
100

50

0
0 5 1015202530354045 50556065 70 75 80 85 90 95 100 105 110
MID HEIGIIT DISPLACEMENT (mTn)

Figure 6.4.17 110mm Watl Dynanúc F-A Relationship

147
CHAPTER (6)- Ouçof-Pbne Shak¿ Table Testing
of Simply SupportedURM Wqlls

A comparison of the derived dynamic F-Â relationships with the results of the static push
tests also show a good correlation as presented in Figure 6.4.18 and Figure 6.4.19. This
observation further confirms that the assumption of a triangular acceleration response for
rocking free bodies relative to the supports provides a reasonable estimate of the true
acceleration response.

For the remainder of the analytical modelling of the rocking response of pre+racked
simply supported LIRM walls, the free body triangular acceleration response assumption
is adopted.

800

700
-+ NO OVER St¿tic Test
tr
1o o¡ \
NO OVERDynamic
a NO OVERExp frt
600
0.075MPa Static Test

E T Dynamic

z
500
I tr a 0.075MPaExp frt

t¡¡
(J ,t00
¡ 0.l5MPa Static Test
É tr nynar¡¡c
ÍJ. I l\ a 0.l5MPa frr
300
.a t
a \
200
I
-oË'f
100

0
0 5 l0 15 20 25 30 3s 4D 45 50

AYERAGE CYCLE MID IIEIGIIT DISPLACEMENT (MM)

Figure 6.4.1t 50mm Wall Comparison of Static and Dynamic F-A Relatioruhips

148
CHAPTER(6)- Ourof-Plnne Shakz Tablz Testing
oÍ Sirnply Supported URM Walls

400

?-*
350
o NoPRECoMpDynamic
+tøSepes Shtic Tesr

:3': o
300
4l-ttsep98 Static Test

250
A NOPRECOMPLOEFT
â o
Êl
U
ú 200
t¡r o o
r50

100

50

0 10 20 30 40 50 60 70 80 90 100 r10

AVERAGE CYCLE MIDMIGIIT DISPLACEMENT (mm)

Figure 6.4.19 110mm Wall Comparison of Static and Dynamic F-A Relatioruhip

6.4.6. 3. N on-linear Damping- Frequency Relationship


As discussed further in Chapter 7, for a single degreeof-freedom (SDOÐ system, \ryith
l00%o of its mass mobilized, the equivalent viscous damping ratio, (5¡rep, associated with
the per cycle energy loss can be estimated for each response cycle (refer Figure 6.4.13)
âS'

n(t,/^ \
Ésoop=# 6.4.6)

This estimate can be shown to be reasonable for €soo" less than approximately ZOVo
which is generally the case for building structures. Above this the damped frequency
becomes increasingly significant and must be considered. Since the frequency of each
response cycle was known, the non-linetr €s¡op versus frequency relationship was
developed. Figure 6.4-20 presents this relationship for the 50 mm wall specimens at
various levels of applied overburden and Figure 6.4.22 for non-loadbearing 110 mm wall
specimens. For both sets of walls a lowerbound estimate of 6soou of a¡ound 5Vo was
observed. This is slightly greater than the 3Vo observed by (tam 1995) for tests on

149
CHAPTER (6)- Ourof-Han¿ Shake Tablz Testing
of Simply Supponed URM Wqlls

l l0mm thick parapet walls. A possible reason for this is energy losses associated with
the simply supported wall mid-height rotation joint as well as the additional mass due the
relative heights of the test walls.

From the non-linear relationship an increase it E -u at very low response frequency


(large displacement oscillations) and at high response frequencies (small displacement
oscillations) was observed. Walls having overburden were also observed to typically
have relatively higher hr¡or values than for walls with small axial loads. The increased
energy loss at large displacement oscillations and for walls having overburden can be
explained by the increased impact energy loss per half cycle at the closing of the mid-
height, top and bottom cracks. The increased energy loss at small displacement
oscillation is likely to have been caused by friction losses at the supports becoming
proportionally more si gnificant.

A final observation was that the thicker wall specimens tended to have a slightly higher
energy loss per cycle although this was not proportional to the ratio of thickness since the

density of the two brickwork specimens were not equal.

25.Wo

O}¡OPRECIIMP
22.5%
!O.Cr/SMP¿
0.15MPà E
â
ø
2n.o%
!
õ
zô.
t7s%
td ¡
^
oo I ^
Ed
I l^
15.0'lo
o
I
!
o o o
o

"t
O t2.5%
E
ú
o
E
I E

,2
c) to.uk
ô
-tfirr o e !
f¡l
U 7.5%
& ^
t¡l
5.Uk -o
,__E_ ¡l
"o 0o o
LOWERBOUND E=SVo
2.5%

0.Wo
0 I 2 3 4 5 6 7 89
FREaUm{CY(Hz)

Figure 6.4.20 s0mm\ilatl NonJinear I vs Frequency (Various Overburden)

150
CHAPTER (6)- Out-of-Plønc Shake Table Testing
of Simply Supported URM Walls

I\O 24.0
I
;Ø 17.5

15.0 OIOPRE@MP
2
H l0.075lvtPa ¡¡
C)
E t2.5
0.l5Mh
r¡.¡
f,
U
(, 10.0

^8lol ir¡t
z.L

rl I!
7.5
A
! o8
,l
z 5.0
!_ I o^ lal
o I
F
ú J o !
2.5
Ê o
ú
o.
dp
0.0
0 1 2 t 4 5 6 7 89
FREQ{IE{CY(IIz)

Figure 6.4.21 50mm Wall NonJinear Csnor/t\4 vs Frequency (Yarior¡s OverburdeÐ

To minimise the effect of the specimen density difference the dynamic relationship
(Clough etal1993)

Croo,
M"
-4o l6 ,oo,

was used to derive the ratio of the SDOF proportional damping coefficient, Cs¡op, to the
effective mass, M". This was then plotted against the cycle frequency (refer Figure
6.4.21 and Figure 6.4.23). A comparison of the Csroe/Àft versus frequency relationship
for non-loadbearing 50 mm and 110 mm walls (refer Figure 6.4.23) shows that a good
correlation was found between the energy losses in the two rocking systems.

151
CHAPTER (6)- Outof-Plane Shake Table Testing
of Sirnply Supported URM Walls

30.v%

â
v)
25.Wo

È. o

il I I :;r
(, o
z 2fr.Vo
g I
ô
^:l¡l
â
c(J 15.Vo
ô ^ôô
c 8 o
F
H o o
ú
(J
F
tu o o o
0 e
3 8
0 o
z14 lO.Mo
o
(J
ú

È
0
Eon'õo
5.OVo
LO\ryERBOUND E= 6Vo

0.01o
0 I 2 3 4 5 6
FREQIJH{CY(rlz)

Figure ó.4.22 NonJoadbearing 110nun Wall Non-linear I vs Frequency

â
à
r4.0
a
(J 13.0
U)
v) 12.0 .l1OMMNOPRECOMP

ts
zI¡}
lr.0
r0.0
^
50MMÌ.¡OPREOCx\4P
o ôl
H
O a I
É 9.0
Í¡l
o 8.0
U a
(5
z 7.0
À a
6.0
A
J 5.0
A
a
z 4.0
F A
ts
ú 3.0
À ^ ¡
o 2.0
ú
À ^
1.0

0.0
0 I 2 ) 4 5 6
FRE@ENCY

Figure 6.4.23 Non-loadbearing 50mm and 1l0mm Wall Cs¡,or/l\¡f. vs Frequency

152
CHAPTER (6)- Out-of-Plnne Shnke Tabl-e Testing
of Simply Supported URM Walls

6.4.7. Transient Excitation Tests

The shaking table input selected for transient excitation tests included both pulse and real
earthquake excitations. The range of amplitude and frequency content was selected to
permit the rocking wall response to be thoroughly examined over a relevant range of
excitation scenario. This allowed critical excitation parameters to be identified and
directly related to the wall response. The resulting dynamic data was also used to provide
a basis for comparison with analytical response predictions using THA, as discussed in
the next chapter.

6.4.7.1. Pulse Tests

As part of the September 98 test series both half-sine (Yz SD) and gaussian displacement
pulse tests were performed on pre-cracked simply supported LJRM walls both with and
without applied overburden. Instrumentation as described in Section 6.2.3 was used to
completely record the dynamic response behaviour of the wall specimens.

The displacement pulse frequencies used for the experimental investigation ranged from
0.5Hz to 3H2.. This frequency range was selected to cover the lower response frequency
hmit, f¡,¡1, as described in Section 5.2.I, and thus permitted pulse forcing frequency at
which the maximum displacement amplification occurred or the effective wall 'resonant
frequency' to be approximately identified experimentally. Figure 6.4.24 shows a
normalized 0.5H2 input displacement gaussian pulse and Figure 6.4.25 the coresponding
acceleration input at the table

For each of the displacement pulse frequencies investigated a normalised displacement


pulse was first determined (e.g. refer Figure 6.4.24). The pulse displacement amplitude
input to the shaking table was gradually increased, at each frequency level, until rocking
and ultimately instability of the wall specimen occurred. The peak pulse displacement
(PGD) and acceleration (PGA) were then related to the peak mid-height displacement
response of the test specimen. This permitted the identification the displacement
amplif,rcation (peak mid-height displacement/PGD) of the wall mid-height response.
Table 6.4.7 presents a summary of key results of the pulse tests performed.

153
CHAPTER (6)- O*of-Plane Shalce Tablc Testing
of Simply SupportedURM WølIs

t.2

e Gaussian Pulse
El
A
-0.5H2

t\
<t
o
! o.s
N

7,
I
0.6

Ë
tr
o \
I
o.¿
o
a
9 nt \
Fr

0
/\
c) eì a I e - .ì a I oq d c.ì a 9 e ó q a I aq {
oooodNddooóo
Tiæ (secs)

Figure 6.4.A O5ftzNornnlized Gaussian Displacenrent Pulse Input

0 0r5

è¡)
00 I ^
do 0 005
N
Ë
0
tr
o f9oqô{
a -0.005
Ò
..É
-0.01
I
d
o
o -0.0r5
I
o
o 4.02
t
.a
d
F -0.025

-0.03
Tine (secs)

Figure 6.4.25 Conesponding Acceleration Input

On examination of the results it is evident that for each of the ïvall specimens the
maximum displacement amplification is associated with a particular frequency described
in Section 5.2.1 as the effective resonant frequency,/.ç. For the 1.5m tall, 50mm thick

wall without applied overburden, the maximum displacement amplif,rcation occurs at

pulse frequencies of between lHz and 2Hz. With the application of 0.07MPa overburden

the effective wall resonant frequency increases to between 2Hz and 3Hz and further to
greater than 3Hz with the application of 0.15MPa overburden (refer Table 6.4.7). For the

r54
CHAPTER (6)- Outof-Plønc Shalce Table Testing
of S imply Supporte d URM Walls

l.5m tall, 110mm thick wall without applied overburden the effective resonant frequency
is similar to that of the 50mm wall at l}Jz to ZHz (refer Table 6.4.3). A representative
cross section of the pulse test results where the mid-height displacement response and
input displacements are compared is presented in Appendix (F). The full wall response
including t/t -, mid- and 3/¿ - height acceleration response is also presented. During the
rocking free vibration response phase the mid-height acceleration response is typically
approximately twice ther/¿ - and3/c - height acceleration responses.

Table6.4.7 Summry of Key Pulse Test Results (S0mmWalls)

Wall Thick Over- Pulse Pulse Peak Peak PeakMid- PeakMid- Mid-height
No. - IreSS burden Type Freq. Pulse Pulse height height Disp.
(mm) (MPa) (Hz) Disp. Accel. Response Resporue Amp[fication
(mm) (mm) Accel. Disp.
k) (mm)
10* 50 0 Y2SD 0.5 20 0.1 0.15 5 0.25
l0* 50 0 Y2SD 0.5 30 0.15 0.18 t3 0.43
l0* 50 0 Y2SD 0.5 40 0.r9 0.19 20.5 0.51
10* 50 0 %sD 0.5 50 0.225 50 1.00
10* 50 0 Y2SD I t3 0.135 0.19 46 3.54
10* 50 0 Y2SD I l5 0.155 0.19 3t 2.07
l0* 50 0 Y2SD I 17 0.175 0.19 3l 1.82
10* 50 0 YzSD 1 20 o.2 50 2.s0
10* 50 0 YzSD 2 10 o.2s 0.18 28 2.80
l0* 50 0 YzSD 2 t3 0.33 0.18 3t 2.38
l0* 50 0 Y2SD 2 15.5 0.39 0.18 32 2.06
10* 50 0 Y2SD 2 r7.5 0.41 0.18 33 1.89
10* 50 0 Y2SD 2 20 0.46 0.18 50 2.50
t4 50 0 Gauss 1 5 0.07 o.t2 10.5 2.IO
l4 50 0 Gauss I 7.5 0.1 o.t2 16.5 2.20
t4 50 0 Gauss I l0 0.125 o.t2 24 2.40
t4 50 0 Gauss 1 12.5 0.15 o.t2 33 2.64
l4 50 0 Gauss 1 t4 0.18 0.r2 40 2.86
t4 50 0 Gauss 1 15 0.2 50 3.33
I4 50 0 Gauss I T6 o.2l 50 3.13
t4 50 0 Gauss I l4 0.16 0.13 35 2.50
t4 50 0 Gauss I l5 0.175 0.13 40 2.67
l4 50 0 Gauss 1 t6 0.19 50 3.r3
74 50 0 Gauss 2 15 0.1 0.09 6 0.40
l4 50 0 Gauss 2 2l 0.13 0.1 t7 0.81
T4 50 0 Gauss 2 22 0.15 0.r2 23 1.05
t4 50 0 Gauss 2 23 0.r6 0.13 29 r.26
T4 50 0 Gauss 2 u 0.r75 0.13 50 2.08
t4 50 0 Gauss 0.5 5 0.3 0.13 11 2.20
t4 50 0 Gauss 0.5 8 0.6 0.13 13 1.63
t4 50 0 Gauss 0.5 10.5 o.7 0.13 l5 1.43
t4 50 0 Gauss 0.5 T3 0.8 0.13 15.5 t.t9
t4 50 0 Gauss 0.5 l5 0.9 0.13 18 r.20
10* 50 0.07 t/2SD 0.5 20 0.19 0.5 3 0.15

155
CHAPTER (6 )- O ut- of- PIøne Shake Table'le s t ing
of Simply Supported URM Walls

Continued

\ilall Thick Over- Pulse Pulse Peak Peak PeakMid- PeakMid- Mid-height
No. - ness burden Type Freq. Pulse Pulse height height Disp.
(mm) (MPa) (Hz) Disp. Accel. Response Response Amplification
(mm) (mm) Accel. Disp.
G) (mm)
10* 50 0.07 %SD 0.5 30 0.25 0.6 4 0.13
l0* 50 0.07 7z SD 0.5 40 0.31 0.6 5.5 0.14
l0* 50 0.07 YzSD 0.5 50 0.375 0.6 6.5 0.13
10* 50 0.07 7z SD 0.5 'to 0.4 0.6 l0 0.14
l0* 50 0.07 7z SD 1 10 0.18 0.5 3.5 0.35
10* 50 0.07 Y2SD I 25 0.38 0.7 l5 0.60
l0* 50 0.07 lzz SD I 30 0.39 0.7 8 o.27
10* 50 0.07 YzSD I 35 0.4 0.7 10 o.29
10* 50 0.07 7z SD I 40 0.45 o.7 t4 0.35
l0* 50 0.07 7z SD 1 50 0.5 0.7 25 0.50
10* 50 0.07 Y2SD I 55 0.8 o.1 37 0.67
10* 50 0.07 %SD 2 l0 0.31 0.7 9 0.90
10* 50 0.07 YzSD 2 15 0.41 0.1 16 t.o7
10* 50 0.07 Y2SD 2 22.5 0.5 0;l 34 1.51
l0* 50 0.07 Y2SD 2 25 0.62 0.7 40 1.60
10* 50 0.07 YzSD J 10 0.7 o;l 2l 2.to
10* 50 0.07 %SD 3 l3 0.8 0.1 25 r.92
l0* 50 0.07 Y2SD J 16 0.9 0.7 40 2.50
10* 50 0.15 YzSD 0.5 30 0.45 1 7 o.23
10* 50 0.15 YzSD 0.5 40 0.5 I 8 o.20
10* 50 0.15 YzSD 0.5 50 0.55 I I7 o.34
10* 50 0. r5 t/zSD 0.5 55 0.6 I ll 0.20
10* 50 0.15 Y2SD 0.5 57.5 0.7 I 7 o.t2
10* 50 0.15 Y2SD 1 60 0.15 I l0 0.17
10* 50 0.15 /z SD I 62.5 0.8 I 36 0.58
10* 50 0.15 Y2SD I 62.5 0.8 1 20 o.32
10* 50 0.15 Y2SD I 65 0.85 I 30 0.46
10* 50 0.15 /z SD 2 20 0.5 I 20 1.00
10* 50 0.15 /z SD 2 22 0.6 I l3 0.59
l0* 50 0.15 Y2SD 2 28 0.8 I t4 0.50
10* 50 0.15 /z SD 2 30 0.85 I 1l o.37
10* 50 0.15 Y2SD 2 32.5 0.95 I ll 0.34
l0* 50 0.15 Y2SD 2 35 1 I 1l 0.31
l0* 50 0.15 %SD 2 37 1.05 I t2 0.32
t4 50 0.15 Gaus 0.5 36 N/A 0.9 9 o.25
t4 50 0.15 Gaus 0.5 4l N/A 0.9 20 o.49
l4 50 0.15 Gaus 0.5 46 N/A 1 24 0.52
t4 50 0.15 Gaus 0.5 49 N/A I 34 0.69

156
CHAPTER (6)- Out-of-Plane Shake Tøble Testing
of Simply Supported URM WaIIs

Table 6.4.8 Sumrmry of Key Pulse Test Results (110mrn Walls)


Wall Thick Over- Pulse P¡¡lse Peak Peak PeakMid- PeakMid- Mid-height
No. - ness burden Type Freq. Pulse Pulse height height Disp.
(nm) MPa) (Hz) Disp. Accel. Response Response Amplification
(mm) (mm) Accel. Disp.
(s)
l1r 110 0 7z SD I l5 0.16 0.28 8 0.53
1l* ll0 0 YzSD I 18 0.2 0.3 13.5 o.75
1l* ll0 0 YzSD I 20 0.22 0.3 23 l.l5
l1r 110 0 /z SD I 25 0.25 0.3 45 1.80
l1* 110 0 /z SD I 27 o.26 0.3 49 1.81
1l* ll0 0 %SD I 30 0.215 0.31 4l 1.37
1l* ll0 0 %SD I 32.s 0.3 0.31 40 1.23
ll* 110 0 /z SD I 37.5 0.32 0.31 62 1.65
ll* ll0 0 Y2SD I 40 0.33 0.31 72 1.80
11* ll0 0 %SD I 45 0.3s 0.31 82 1.82
l1* 110 0 Y2SD 2 l0 o.2 0.3 20 2.AO
l1* 110 0 %SD 2 l5 o.25 0.3 40 2.67
ll* ll0 0 YzSD 2 17.5 0.38 0.3 45 2.57
11* ll0 0 YzSD 2 20 0.43 0.3 45 2.25
l1* 110 0 %SD 2 25 0.5 0.3 58 2.32
l1* ll0 0 Y2SD 2 27 0.61 0.3 65 2.41
l1 ll0 0 YzSD 3 8 0.5 0.3 l3 1.63
11 ll0 0 7z SD 3 l5 0.8 0.3 26 t.73
1l 110 0 Y2SD J t7 0.9 0.3 27 1.59
l1 ll0 0 YzSD J l8 I 0.3 30 1.67
ll ll0 0 Y2SD J l6 0.6 0.31 38 2.38
ll 110 0 %SD J 20 0.65 0.3r 49 2.45
11 110 0 %SD 3 24 o.725 0.31 6t 2.54
t2 110 0 Gauss I 16 0.17 0.31 25.5 r.59
t2 110 0 Gauss I 2t 0.25 0.31 36 t.7r
t2 110 0 Gauss I 26 0.3 0.31 49 1.88
t2 ll0 0 Gauss I 28 0.35 0.31 54 1.93
t2 il0 0 Gauss I 29 0.375 0.31 57 1.97
t2 110 0 Gauss I 30 0.4 0.31 67 2.23
t2 ll0 0 Causs I 3l 0.425 0.31 73 2.3s
lz ll0 0 Gauss I 32 0.45 0.31 77 2.41
t2 110 0 Gauss I 31 o.425 0.31 72 2.32
l2 110 0 Gauss I 33 0.85 0.31 80 2.42
l2 ll0 0 Gauss I 34 0.9 0.31 85 2.50
T2 110 0 Gauss I 35 0.95 0.31 88 2.5r
t2 ll0 0 Gauss I 39 0.52 0.31 58 r.49
t2 ll0 0 Gauss I 4l 0.55 0.31 76 1.85
t2 110 0 Gauss I 44 0.58 0.31 78 1.17
t2 110 0 Gauss I 46 0.61 0.31 68 1.48
l2 110 0 Gauss I 48 0.65 0.31 55 1.15
l3* 110 0 Gauss I ll 0.125 0.3 6 0.55
l3* ll0 0 Gauss I 12.5 0.15 0.31 9 o.7z
l3* ll0 0 Gauss I 15.5 0.175 0.32 15.5 1.00
13* 110 0 Gauss I 17.5 0.225 0.33 20.5 t.t7
l3* ll0 0 Gauss I 20 0.25 0.33 26 1.30
l3* 110 0 Gauss I 22.5 0.275 0.33 30.5 1.36
l3* 110 0 Gauss I 25 0.3 0.33 35.5 r.42

r57
CHAPTER (6)- Ourof-Pbne Shake Table Testing
of Simply Supported URM Walls

Continued

Wall Thick Over- Pulse Pulse Peak Peak PeakMid- PeakMid- Md-height
No. - ness burden Type Freq. Pulse h¡lse height height Disp.
(mm) (MPa) (Hz) Disp. Accel. Response Response Amplification
(mm) (mm) Accel. Disp.
(s) (mm)
13* 110 0 Gauss I n.5 0.325 0.33 40 r.45
13+ 110 0 Gauss I 3L 0.35 0.33 45 r.45
13* 110 0 Gauss I JJ 0.4 0.33 57 1.73
13+ 110 0 Gauss 1 36 o.45 0.33 65 1.81
13* 110 0 Gauss 1 38 0.5 0.33 55 1.45
13* 110 0 Gauss 1 40 0.55 0.33 50 r.25
l3* 110 0 Gauss I 42.5 0.6 0.33 45 1.06
13* 110 0 Gauss 1 44 0.65 0.33 44 1.00
13* 110 0 Gauss I 45 o.7 0.33 50 1.1 1

13* 110 0 Gauss 0.5 50 0.225 0.33 20 0.40


13* 110 0 Gauss 0.5 55 o.25 0.33 24 o.44
13* 110 0 Gauss 0.5 60 o.275 0.33 28 o.47
13* 110 0 Gauss 0.5 65 0.3 0.33 4l 0.63
l3+ 110 0 Gauss 0.5 70 0.35 0.33 85 t.2r
l3* 110 0 Gauss 0.5 70 0.4 0.33 7l 1.01
13* 110 0 Gauss 0.5 75 0.45 0.33 76 1.01
l3r 110 0 Gauss 0.5 80 0.5 0.33 74 0.93
13* 110 0 Gauss 0.5 82.5 0.55 0.33 95 1.15
13* 110 0 Gauss 0.5 85 0.575 0.33 69 0.8r
13* 110 0 Gauss 0.5 87.5 0.6 0.33 85 0.97
13* 110 0 Gauss 0.5 90 0.625 0.33 76 0.84
Presented in Appendix (F)

The results also indicated that the wall thickness had only a small impact on the effective
resonant frequency but the application of overburden significantþ increased the effective

resonant frequency. This can be explained, as a change in the wall thickness does not
alter the average incremental cycle secant stiffness, Kur", and thus the effective resonant
frequency however an increase in overburden does (refer Figure 6.4.26). For a rigid wall
this is because an increase in wall thickness does not alter the negative stiffness value, as
both of the 'rigid resistance' fotce, R.(1), and instability displacement, A¡¡s¡¡6¡¡y, âfe
increased proportionally. The average incremental secant stiffness and effective resonant

frequency therefore remain the same. In contrast, with an increased overburden applied
at the leeward face, as was the case for the test specimens, Ç(1) is reduced as &(1)
increases however Âinsøbiìity does not alter. Thus, the average incrernental cycle secant

stiffness is increased. This is shown in Figure 6.4.14 where higher response frequencies
for the 50mm wall specimens with overburden are obseryed than without. Where an

158
CHAPTER (6)- Out-ol-Plane Shalcc TøbIe Testing
of Simply Supported URM WøIls

increase in overburden is applied at the leeward face of the wall, R"(1) again increases
but to a lesser extent and ¡s¡¿61¡t, is reduced to less than the thickness of the wall. The
reduction in A¡.66i¡s, is dependent on the ratio of overburden to the self weight of the wall
(refer Table 5.2.1). Consequentþ, again the average incremental cycle secant stiffness
and thus the effective resonant frequency are increased (refer Figure 6.4.26).

Increasing ayera5e
o Increased cycle secant stiffness
Ê and thus effective
Í¡r overburden at
(l)
centerline resonant frequency
o
É
sa
ø Increased
ú
ú.)
overburden at
cl leeward face ,,' a
È
c(d a
tl /\ ,
a
a
2R (1) a
>K u
K.
a
a
,
a
R.(1) a

Double original
thickness

Âinst¿bility
2
Mid-height displacement Â
Solid lines represent rigid F-Â relationships
Dashed lines represent ayeruge cycle secant stiffnesses

Figure 6.4.26E,frælíve Resonant Frequerrcy (By rvall rhickress and overburdeÐ

159
CHAPTER (6)- Outof-Plane Shake Table Testing
of Simply Supported URM Walls

Experimentally the range of effective resonant frequency observed is due to the changing
state of the rotation joints with continued testing and degradation of the rotation joints
flattening the F-À relationship. As such, there is a coresponding decrease in the average
incremental cycle secant stiffness and thus the effective resonant frequency of the wall.

6.4.7.2. Real Earthquake Excitation Tests

To complete the investigation into the response of both loadbearing and non-loadbearing
simply supported URM walls to transient excitations, shaking table tests were performed
using real earthquake accelerogram records to drive the shaking table. A comparison of
recorded table accelerations with the original accelerograms has shown a reasonable level
of correlation. Instrumentation as described in Section 6.2.3 was used to capture the

dynamic response behaviour of the wall specimens.

To investigate wall response over a range of excitation, relevant real earthquake scenario
of both 'low frequency large displacement' and 'high frequency small displacement'
excitation were selected. Table 6.4.9 presents a summary of the earthquake excitations
used for investigation. By comparison of the PGD and PGA an indication of the type and

severity of the earthquake can be attained. For instance it can be seen that the Nahanni
aftershock has a relatively high PGA but a small PGD indicating that this earthquake had
a dominant high frequency component. This was determined from the power frequency

spectrum as approximately l.75Hz to 2.25H2. Although traditionally this would

therefore not be expected to impact greatly on ductile structures the large accelerations
would be expected to impact more severely on stiff brittle structures. The Taft, Pacoima
Dam and ElCentro earthquakes typically have higher PGD and similarly large PGA thus
indicating a lower dominant frequency in the range of 0.7H2 to l.lHz.

In a similar fashion to the pulse tests each earthquake excitation was displacement
normalised setting the peak excitation displacement (PGD) to unity. The Vo of the
original excitation could then be related to the PGD input to the table. For each applied
excitation the 7o of the original excitation, was gradually increased until rocking and
ultimately instability of the wall specimen occurred. The peak transient excitation

160
CHAPTER (6)- Out-of-Plane Shake Table Testing
of Simply Supported URM Walls

displacement (PGD) and acceleration (PGA) were then related to the peak mid-height
displacement of the test specimen.

Table 6.4.9 Earthquake Excitation Description


Transient Excitation Description Abbr. ItÙVo lAOTo
Peak Ground Peak Ground
Displacenrent Acceleration
(PGD) (PGA)
NAHANNI, Canada: NH 4.2mm 2.24mJs'
Recorded at Iverson during an aftershock of the Nahanni EQ (o.23e)
23'd December 1985
Magnitude 5.5
Epicentral distance 7.5krn
Soil type rock
PACOIMA DAM, California: PD 53.9mm 4.26¡nls'
Recorded at Pacoima Dam, downsteam during Northridge EQ (0.43e)
lTth January 1994
Magnitude 6.6
Epicenral Distance I thn
Soil Type: Rock
ELCENTRO, California: EL 163.0mm 3.42m1s"
Recorded atElCentro during the Imperial Valley EQ (0.3se)
l8'h May 1940
Magnitude 6.6
Epicennal Distance 8l¡n
Soil rype: Rock
Accelerogram component NS
TAFT, California: TF 98.5mrn I.76rnls"
Recorded at Kern Counfy, TaftLincoln School Tunnel (0.18e)
21"'JDly 1952
Accelerogram component S69E
Epicenter 35 00 00N I 19 02 00rr)Y
Seismograph station 35 09 00N ll9 27 ODW

A representative cross section of the earthquake excitation results is presented in


Appendix (F). Here the mid-height displacement response and input displacements are
compared. The full wall response includingr/¿ -, mid- and 3/n -heigltt accelerations are
also presented. The recorded input excitation accelerations at the base and top of the wall

specimen are also presented as these are used in Chapter 7 for analytical THA predictions

and should be used for future analytical comparison with these experimental results.
Table 6.4.10 and Table 6.4.11present a summa¡y of key results of the earthquake tests
performed for the 50mm and l lOmm thick walls respectively.

161
CHAPTER (6)- Ouçol-Plane Shake Tøble Testing
of Simply Supported URM Walls

Table 6.4.10 Sumrnary of Key Earthquake Excitation Test Results (50mm Walls)
Wall Thick Over- Wâtl Excitation PGD PGA PeakMid- PeakMid- Mid-
No. ness burden Cond (refer (mm) G) height height height
(mm) (MPa) -ition Table Response Response Disp.
6.4.9) Accel. (s) Disp. (mm) Amo.
l2* 110 0 NEV/ 1007o NH 4.2 0.23 0.26 9 2.t7
12" ll0 0 NEW 200% NH 8.3 0.46 0.26 zt 2.53
12" 110 0 NEVT 3007o NH 12.5 0.69 0.26 28 2.25
l2* 110 0 NEW 4007o NH 16.6 0.92 o.26 32.5 1.96
t2 110 0 MOD 5OVoEL 81.5 0.18 0.26 16 0.20
l2* 110 0 MOD 66VoEL t01.6 0.23 Failed
t2 110 0 MOD SOVoEL 130.4 0.28 Failed
t2 110 0 MOD 1007o TF 98.5 0.18 0.33 3t 0.3r
t2 110 0 NEV/ 50VoPD 2',1.0 0.22 0.36 32 1.19
t2 110 0 NEV/ 66VoPD 35.6 0.28 0.35 65 1.83
l2 110 0 NEW 8O7oPD 43.1 o.34 0.35 80 1.86
12 ll0 0 NEW I00VoPD 53.9 o.43 0.34 105 1.95
t3 110 0 NEW 5OVoPD 27.0 o.22 0.31 5l 1.89
l3* ll0 0 NEW 667oPD 35.6 0.28 0.30 66 1.86
l3* 110 0 NEW 8O7oPD 43.1 0.34 0.32 70 t.62
13* 110 0 NEìW IOOVoPD s3.9 o.43 Failed
t3 110 0 MOD 5OVoEL 81.5 0.18 0.29 7I 0.87
l3* 110 0 MOD 667oEL r07.6 0.23 Failed
T3 110 0 MOD IOOVoEL 163.0 0.35 Failed
13 110 0 SER SOVoPD 43.1 0.34 Failed
*Presented rn (F)
Table 6.4.11 Sumnrary of Key Earthquake Excitation Test Results (l10mmWalls)
Wall Thick Over- Wall Excitation PGD PGA PeakMid- PeakMid- Mid-
No. - ness burden Cond (refer (mm) G) height height height
(mm) (MPa) -ition Table Response Response Disp.
6.4.91 Accel. (s) Disp. (mm) Amp.
t4 50 0 MOD l5VoEL 24.5 0.05 0.r5 l5 0.61
t4 50 0 MOD 2OVoEL 32.6 0.07 Failed
l4 50 0 MOD 25VoEL 40.8 0,09 Failed
t4 50 0 MOD 3O7oEL 48.9 0.1l Failed
l4 50 0 NEV/ 2OVoPD 10.8 0.09 0.18 28 2.60
14 50 0 NEV/ 25VoPD 13.5 0.1I Failed
t4 50 0 NEV/ 307oPD 16.2 0.13 Failed
t4 50 0 NEV/ 5OVo TF 49.3 0.09 0.15 13 0.26
l4 50 0 MOD 60VoTF 59.1 0.11 Failed
t4 50 0 MOD TOVoTF 69.0 0.13 Failed
t4 50 0 MOD 50% NH 2.1 o.t2 0.05 6 2.88
t4 50 0 MOD 70VoNH 2.9 0.16 0.1 8.5 2.92
t4 50 0 MOD 100% NH 4.2 0.23 0.23 l1 2.65
t4 50 0 MOD 2007¿ NH 8.3 0.46 0.4 22 2.65
t4 50 0 MOD 3007o NH 12.5 0.69 0.5 38 3.05
t4 50 0.15 SER IOOVoPD 53.9 o.43 0.9 t3 0.24
l4 50 0.15 SER I25VoPD 67.4 0.54 1.0 38 0.56
t4 50 0.15 SER l35VoPD 72.8 0.58 1.0 30 0.41
t4 50 0.15 SER l5OToPD 80.9 0.65 0.9 44 0.54
t4 50 0.15 SER l75Vo PD 94.3 0.7s Failed

r62

f' ,? .t L .,î ' j'ff"


*'-ì * {-o. 'f .- \..4 a-l\ ''- . r ':' t t i t..''
7. NON.LINEAR TIME HISTORY
ANALYSIS DBVELOPMENT

7.1. Introduction

Non-linear time-history analysis (THA) based on time-step integration is the most


representative and reliable method of accounting for the time-dependent nature of URM

wall response to applied excitations provided that the non-linear (F-Â) and damping
properties are accurately represented in the analyical model.

Time-stepping procedures have been developed for basic linear single degree-of-freedom
(SDOÐ systems having a known linear stiffness and damping component. This method
relies upon an assumption on the response behaviour between consecutive time steps
which permits the dynamic response to be estimated from the applied excitation. One
such assumption is the 'Newmark' constant acceleration assumption. For the rocking
response of 'semi-rigid' URM walls, since both the stiffness and damping properties are

highly non-linear and because the entire system mass is not mobilized evenly, the
response behaviour does not strictly follow the basic linear SDOF equation of motion.
Consequently, to permit the use of time-stepping procedures by substtution of the linear
SDOF damping and stiffness components with non-linear damping and stiffness
properties, correlation between the non-linea¡ 'semi-rigid' rocking and basic linear SDOF
system equations of motion must be established.

The following chapter presents the development of a specialised non-linear THA


program for the 'semi-rigid' rocking response of simply supported URM walls. This
includes the development of algorithms by comparison of the SDOF and non-linear
rocking equations of motion. Consideration to the various support conditions identihed
for Australian URM construction in Chapter 2 is also provided for in the non-linear THA

163
CHAPTER (7) - Non-Linear Time History
Analysis Development

program. Calibration of the stiffness and damping properties and confîrmation of


analytical predictions by comparison with experimental results described in Chapter ó are
also presented.

In the past the use of TIIA for the analytical prediction of the 'semi-rigid' rocking
response of simply supported URM walls has been restricted to commercially available

softwa¡e not designed specihcally for URM wall analysis. Consequently these
predictions have been limited and have not been adequately confirmed by experimental
studies. The main advantage of the current THA program is that it has been designed to
specifically take into account the critical non-linear stiffness and damping properties
which have been calibrated using the experimental results presented in Chapter 6. The
effect of various support conditions and degradation of rotation joints on the non-linear
stiffness component was also examined so that analytical comparisons of various realistic
situations are possible.

Although THA has limited application in design, as loading scenarios are diverse, it
remains a valuable resea¡ch analysis tool. In Chapter 8 the developed THA program is
used to undertake an in-depth parametric study of the 'semi-rigid' rocking response of
simply supported URM walls to further investigate the physical parameters which
influence URM wall response. Having developed an understanding of these critical
parameters a simplihed analysis procedure is then proposed and its effectiveness assessed

against the more comprehensive THA predictions.

7.2.ßnef Description of Basic Linear SDOF System


To permit the use of time-stepping procedures for the highly non-linear 'semi-rigid'
rocking response of simply supported URM walls an understanding of the development
of the dynamic equation of motion for a basic linear SDOF system is first required. Later
this will be expanded into the development of dynamic equations of motion for the non-
linear 'semi-rigid' rocking of the simply supported URM walls having various support
conditions.

164
CHAPTER (7) - Non-Linear Time History
Arwlysis Development

The equation of motion of a dynamic system is a representation of Newton's second law.


That is, the rate of change of momentum of any mass particle equals the force acting on
it. Together with d'Alemberts principle that a mass develops an inertial force opposing it
proportional to its acceleration the equation of motion can be expressed as an equation of

dynamic equilibrium. The essential properties governing the displacement response, A(t),
of a system subjected to an external excitation, P(t), are its mass, M stiffness and energy
loss mechanism or damping. For a basic linear SDOF system each of these properties is

concentrated into a single physical element as shown in Figure 7.2.1. Although the true
damping characteristics of real systems are typically very complicated and difficult to
define it is common to express the damping of real systems in terms of an equivalent
viscous damping, which shows a similar decay rate under free vibration conditions.
Therefore, in this case the elastic resistance is provided by the spring stiffness, /<, and the

energy loss mechanism by the velocity proportional viscous damper, c.

Linear spring
k ^(t)

P(t)

c
Linear damper

Figure 7.2.1 B,asic Linea¡ SDOF System

The motion-resisting forces are therefore the damping force being the product of the
damping constant, c, and velocity, v(t), the elastic force being the product of the spring
stiffness, ft and the response displacement, A(t) and the inertia force in accordance with
d'Alambert's principle being the product of the system mass, M and response

acceleration, a(t). Equating these motion-resisting forces to the external dynamic loading

provides the SDOF equation of motion as, \

Ma(t) + cv(t) +kA(t)= P(t) (7.2.1)

165
CHAPTER (7) - Non-Linear Tilne History
Analysis Development

If the loading to be considered is due to ground or support excitation this can be included
by expressing the inertial force in terms of the two acceleration components. By

re¿uranging and substit


"Mø,z=!rh" basic linear SDOF system dynamic equation of
uting

motion becomes,

aQ) + -L vlt) + a2 L(t¡ = - a, (t) (7.2.2)

where ú) = un-damped elastic angular natural frequency

By solving the dynamic equation of motion (Equation 7.2.2) it can be shown (Clough and
Penzien 1993) that for an under-critically damped system the critical damping coeff,rcient,
c., is,

cc=2M@=4Mnf (7.2.3)
where/- un-damped elastic natural frequency

Therefore by definition the SDOF equivalent viscous damping, 6sno¡, is,

€soor = c/cr= c/4 M nf (7.2.4)

and the SDOF proportional damping coefficient, csDoF,

Csoor=4MnfSnor (7.2.s)

Further to this by substituting zero initial conditions in to the SDOF dynamic equation of

motion solution it can be shown that for €,spor less than approximately 20Vo,,

r, -fi
1 ,rrl^'l
= ",[O*
5soor (7.2.6)
J
where 7ç = peak amplitude at the nù cycle

Ân+r = peak amplitude at the (n+1)ù cycle

166
CHAPTER (7) - Non-Linear Time History
Analysis Development

It should be noted that both the SDOF based equations 7.2.4 to 7.2.6 were used to
determine c and ( respectively for the experimental rocking wall in Section 6.4.6.2.
Since for the rocking v/all the system mass is not mobilized evenly as is assumed above a

conversion is required, as will be discussed in Section 7.3.

7.3. Negative Stiffness System Modelled as a Basic Linear SDOF System

In the following discussion a negative stiffness system is dehned as a system having a bi-
linea¡ F-Â relationship (refer Figure 7.3.I) comprising an initial infinite stiffness
component followed by a negative stiffness component. On application of a force to the
negative stiffness system, initially the infînite stiffness governs the behaviour until the
'threshold resistance' force, R.(1), is exceeded. Following this a negative stiffness,
IÇ(1), takes effect so that the force resistive capacity is reduced with increased

displacement. As described in Chapter 5, for 'semi-rigid' rocking the non-linear F-A


relationship has a negative stiffness component. It is thus pertinent to first examine the
modelling of a negative stiffness system as a basic linear SDOF system to determine if
existing time-stepping procedures can be utilised.

Half cycle under consideration


R"(1)

1)+IÇ(1)^(t)
(.)
o
H
o
q)
o
cl
a
Ø
(,) Negative stiffness
ú K(1)
c)
Ø

U)

Âvo DisPlacement Âr"o¡¡¡y


^(r)
Figure 7.3.1 Negative Stiffness F-Â Relationship

t67
CHAPTER (7) - Non-Lineør Titne History
Analysß Development

For all displacements, greater than zero, at any given time the instantaneous secant
^(t),
stiffness, Kdt), can be derived as,

K" 1r¡ =Ul)- + K, (1) for L(t) > 0 (7 .3 .t)


^(/)
This non-linea¡ instantaneous secant stiffness relationship is then used to derive the non-
linear frequency-displacement ff-L) relationship for the negative stiffness system which
becomes,

K"(t)
a=2nf= (7.3.2)
M

Rearranging this and substituting in the non-linear instantaneous secant stiffness


relationship gives the generic response frequency,

R,(1)
+ K"(l)
^(r) M
f 2n
for L(t) > 0 (7.3.3)

Assuming that the entire system mass is evenly mobilized the complete equation of
dynamic equilibrium for the negative stiffness system is derived as,

Ma(t) + cv(r) + R
"(1)
+ rK" (1)^(r) = - Ma, (t) for L(t) > 0 (7 .3.4)

By rearranging and substituting the non-linear instantaneous secant stiffness relationship


the equation of dynamic equilibrium for a negative stiffness system subjected to a base
excitation is,

a(t)+#rrrr*K"!)-tç)=-ar(t) for L(t) > 0 (7.3.5)

Thus, by comparison of the dynamic equation of motion for a basic linea¡ SDOF system
(Equation 7.2.2) and for the negative stiffness system (Equation 7.3.5) it can be seen that

168
CHAPTER (7) - Non-Linear Time History
Analysis Development

a similarity exists provided that the non-linear instantaneous secant stiffness relationship
is substituted for the linear stiffness. Thus by adopting this substitution the time-stepping
procedure can be applied to the negative stiffness system.

7.4. Rigid simply supported object Rocking Response About Mid-


height - Dynamic Equation of Motion
As a second phase in the modelling of the real 'semi-rigid' URM wall rocking response
for illustrative purposes we now consider the idealised simply supported rigid rocking
scenario. Here, as was the case for the negative stiffness system the idealised rigid F-À
curve is comprised of a bi-linear F-A relationship having an initial infinite stiffness
followed by a negative stiffness component due to P-A effects (refer Section 5.2.1). The
defining terms of the bi-linear F-Â curve, the 'rigid resistance threshold' force, R"(1), and
negative stiffness IÇ(1) are functions of the wall geometry and applied overburden at the
top of the simply supported object. Also influencing R.(1) and Ç(1) are the support
conditions as these govern the eccentricity of the vertical reactions.

For the rigid rocking of a simply supported object about it's mid-height it must also be

recognised that during the dynamic response the full system mass is not mobilized

evenly. Consequently, this must be considered when deriving the systems dynamic
equation of motion. As was concluded from the experimental study (Chapter 6) a
triangular acceleration distribution relative to the supports provides a good assessment of
the rocking object's acceleration response and is thus adopted. This therefore impacts on

both the dynamic stiffness and damping components of the dynamic equation of motion.

The following calculation illustrates the derivation of the dynamic equation of motion for
a rigid non-loadbearing simply supported wall rocking about a mid-height crack. This is
further related to the generic dynamic equation of motion for various rigid rocking
objects having other support conditions relevant to Australian masonry construction.

For any rigid rocking object the static bi-linear F-À relationship can be generically
defined as Equation 7.4.1 where R. (1) represents the 'rigid threshold resistance' force,

769
CHAPTER (7) - Non-Linear Time History
Analysis Development

IÇ(1) the negative stiffness component (-R*(1)/Ai"søuiuty) and Fr(t) the evenly distributed
'quasi-static' force. Further, the bracketed termrepresents the instantaneous static secant

stiffness, K,(t) at the mid-height displacement Â(t).

-FsQ)--Mo,(t)=[#*K"cl]r'l forL(t)>0 (7.4.1)

For a rigid non-loadbearing simply supported wall the static F-A relationship is derived
âS'

- F rt)- - Ma c Q) = M[f -'1)^,,,


t# for A(t) > 0 (7.4.2)

The generic defining terms of the static a-a relationship are therefore,

'Rigid Threshold Resistance' force n


"e)=ß#

Negative Stiffness K
"(t)=-49

Displacement at static incipient instability Linsøa;tiry


K"(t)

'Where
the load is applied dynamically the acceleration response also comprises a
triangular acceleration component, a-(t), as shown in Figure 7.4.1. The damping
component of the equation of motion will be neglected at this stage but will be discussed
in more detail following the derivation.

170
CHAPTER (7) - Non-Linear Time History
Arnlysis Development

Triangular
acceleration response t€d
due to rocking acceleration
displacements .(-..Ð responsedueto ht4
relative to supports motion of
supports

w4

a.(t) Cr0)

ht4

- ht4

<¡.+
INERTIALOAD
tÍ2-N2
M=mxh

Figure 7.4.1 NonJmdbearing Simply Supported Object at RocHng at Mid-height

The top support horizontal reaction Rr is determined by taking moments about the base
vertical reaction.

R' __ar(t)mh _a^(t)mh _!n(t) gt +m(t) gLG)


2M ^, 2422

Then horizontal equilibrium is used to determine the base support horizontal reaction as,

h a,(t)mh a^(t)mh , mgt- mg\(t)


nt=-a- 2 z

777
CHAPTER (7 ) - Non-Linear Time History
Annlysis Developrnent

Now considering the dynamic equilibrium of the top free body, by taking moments about
the mid-height vertical reaction, the mid-height dynamic equation of motion is,

"^ur.}(+h ,]\¡a>=-)",a> ror*(t)>, (7 43)

Writing this in generic terms becomes,

"^@*1;[[#. r,rrr]Jnr')=-2o,(t) rora(t)>o (7.4.4)

Including the damping component,

L*
i(+l#-'] )^,
-^t
a
^
Ø + v e) + t) ,(t) for L(t) > 0 (7.4.5)
2

where the proportional damping coefficient has been measured at the effective mass, Mr,
of the responding wall.

In order to continue to use the mid-height wall response as in Chapter 6 rather than the
response at the position of the effective mass the damping term must be multiplie dby 213
to compensate for the relative velocities.

The dynamic equation of motion for the rigid non-loadbearing simply supported object
rocking about its mid-height therefore becomes,

"^u,.1(ø1,,,, . i(+lh-'] )^r,,


=- 1o,,,, for L(t) > O (7 .4.6)

172
CHAPTER (7) - Non-Linear Time History
Analysis Development

This can again be rewritten in generic terms as,

a^(t) .i(t\.,v (' ) +


i;(H+ r' or ) = -
|a,(t) lor L(t) > o (7 .4.7)

)n'

and by substituting the instantaneous static secant stiffness, K(t), as,

,, zf r I 1K"(t) 3 ..
'rr\+ forL(t)>0 (7.4.8)
"^Ø*;ln " )",rr,r* ZËo(t)=-ia,(t)

Comparing the basic linear SDOF equation of motion (Equation 7.2.2) previously
developed for the system shown in Figure 7.2.1 and the generic dynamic equation of
motion for rigid rocking objects (Equation 7.4.6) it is evident that the following
substitutions can be made to permit the use of time stepping procedures and the mid-
height response of the wall.

l. Substitute the linear SDOF proportional damping with 213 of the experimentally

derived values
2. Substitute the linear stiffness component with the dynamic non-linear instantaneous
secant stiffness, IÇr(t), represented by 312 times the static instantaneous secant
stiffness. This is achieved by applying a factor of 312 to the static F-A relationship.

K^çt¡=1y,ç¡
¿

3. Apply a conversion factor of 312 to the applied ground acceleration.

Also from Equation 1.4.7 the theoretical rigid mid-height fA relationship without

K"(t)
damping can be derived in accordance with a =2n f = in generic terms as,
M"

l(ffi.*"r,
M.
f 2n
for L(t) > O (7.4.e)

173
CHAPTER (7) - Non-Linear Time History
Analysß Development

Since each set of support conditions alters the F-Â relationship by changing the value of
R.(1) and Ç(1) this also influences the dynamic equation of motion. The generic
defining terms R"(1) and IÇ(l) are shown in Table 5.2.1 and. can be substituted directly
into the above equations.

7.5. Semi-rigid URM Loadbearing Wall Dynamic Equation of Motion

As discussed in Chapter 5, the real 'semi-rigid' non-linear F-Â relationship of a face


loaded URM wall results from the complicated interaction of gravity restoring moments,
the movement of vertical reactions with increasing mid-height displacement and p-A
overturning moments. The wall properties that therefore dictate the shape of the curve are
wall geometry, support conditions, overburden stress, material modulus and importantly
the condition of the morta¡ joint rotation points. As described in Section 6.4.5 theories
have been postulated by previous researchers to define this complex behaviour howeve¡
these were not found to correlate well with the experimental results as based on simple

and often unrealistic support conditions. Consequently a more empirically based method

was adopted in this study.

From the experimental study presented in Chapter 6 the real 'semi-rigid' non-linear F-À
relationship was found to approach that of the idealised rigid bi-linear relationship at
large mid-height displacements. This was due to the vertical reactions being pushed
nearly to the extreme compressive face of the wall. As the applied overburden was small
the influence of the hnite compressive stress blocks at vertical reactions was not
significant. Since the bi-linear F-A relationship is simply a function of geometry,
overburden and support conditions, this was used as a basis for development of an
approximation of the real non-linea¡ F-Â relationship.

A parametric study was undertaken to dete¡mine which of the non-linear F-Â relationship
properties governed the response behaviour. It was found that the initial stiffness, K¡o,
and 'semi-rigid threshold resistance' force plateau, R*(l), were critical. Thus to model
the non-linear F-A relationship at smaller mid-height displacements a tri-linear F-À

174
CHAPTER (7) - Non-Linear Time History
Analysis Development

approximation was selected (refer Figure 7.5.1). Since the rigid bi-linear relationship is
Â(1) *O
set the tri-linear approximation is defined by the displacements ratios ,
Lircøuitity

,L(z) , which govern Kn and zu(1) respectively. The value of , ^(t) -¿ -^(2)-
L;nsøtitity Linøaitity Linsnbitig

are therefore related to material properties, predominantly being the less stiff mortar, and

the state of degradation of the rotating mortar joints.

'semi-rigid threshold
resistance' force plateau Tri-linear F-Â
Approximation
R (1) =R"(1)+K(1)^(2)
Bi-linear F-A
Relationship
q)
o Real Semi-rigid
k
o Non-linea¡ F-Â
f¡r
cd
Relationship
k()
ct
r'l
!d)
È
È

Initial stiffness =
ç(1)
= R-11)+ICll)Â2)

^(1)

L(2) A¡n5¡aþ¡¡¡¡y
^(l)
Mid-height Displacement (Á)

Figure 7.5.1 TriJinear 'Semi-rigid' Non-linear F-A Relationship Approxinntion

Table 7.5.1 presents the empirically derived defining displacements of the tri-linear
approximation from the experimental static push tests presented in Chapter 6. Here the
support conditions considered included NLBSSCL and LBSSLL (refer Table 5.2.1), so

that ¡os¡n5¡¡ty wâs taken as the thickness of the wall. Since the materials used did not
change, an increase in degradation of the rotating mortar joints was related to an increase

175
CHAPTER (7) - Non-Lin¿ar Time History
Arulysß Developmcnt

in both displacement ratios t


^(t) -¿ --^Ø-.
Linsøuitiry
This represented
L;nsøuit;ty
( a decrease in Ki,r and

R*(1) and a corresponding flattening of the 'semi-rigid' non-linear F-A relationship (refer
Figure 7.5.2). The resulting decrease in the overall response frequencies also led to a
decrease in the instantaneous dynamic secant stiffness.

Table 7.5.1 Defining Displacenrents of the Tri-linear F-A Approxirmtion


State of Rotation Joint Degradation a(1) LA)
A^t"m.y 4-t UUtt
New 6Vo 28Vo
Moderate l37o 4O7o
Severe 2OVo 5O7o

10O7oR.( Tri-linea¡ F-Â


Approximation
Various Degradation
Bi-linear F-Â
Relationship

ú
(1)

èa
q) 727o
o
L New
o
f¡. 6O4o
ñt
c)
I I Moderaæ

s
5OVo
Severe
E(¡) /
Þr
Þr
I I
I K(1)

ñs s s
\OÈNN
ñòe
OA
.+ !ñ
l(X)7o \,65¡1,
Mid-height Displacement ( VoA¡", )
Figure 7.5.2 Tri-linear F-A Approximation for Various Wall Degradation

After adopting the tri-linear 'semi-rigid' F-A relationship approximation, the rocking
response was governed by three discrete equations of motion. At any given time the

176
CHAPTER (7) - Non-Linear Time History
Arnlysis Development

governing dynamic equation of motion is dependent on the instantaneous displacement.


In generic terms the three governing equations of motion are,

K"(I)L(2)
R"(1) + J
, (r) forl < < A(l)
2 ^(r)
^(1) (7.s.Ð

3
) (t ) for L(I) < Â(r) < L(2)
2

(7.s.2)

for L(2) < Â(r) < Lirctøitity

(7.s.3)

As each stiffness term is represented by the instantaneous dynamic secant stiffness the
overall generic dynamic equation of motion again takes the form of Equation 7.4.8.
Thus, by comparison with the basic linear SDOF equation of motion (F,quation 7.2.2) itis
observed that the required substitutions to allow the use of previously developed time-
stepping procedures highlighted in Section 7.4 are still applicable. This is provided that
the governing dynamic equation of motion at any time is dependent on the instantaneous
displacement.

By adopting the tri-linear F-A relationship approximation for the 'semi-rigid' rocking
response of URM walls allows an estimate of the frequency-displacement response to be

made. Since the approximate response is governed by the three dynamic equations of
motion, which are dependent on the instantaneous displacement, the frequency response
is also dependent on the instantaneous displacement. The relevant instantaneous dynamic
secant stiffness can therefore be used to determine the frequency-displacement

relationship in accordance with @ =21c, = Thus from Equation 7.5.1 to


W

177
CHAPTER (7) - Non-Linear Time Hßtory
Analysß Developmcnt

7.5.3 the generic 'semi-rigid' rocking frequency response can be approximated when
neglecting damping as,

1
2
r 2n
forï<^(f)<^(1) (7.s.4)

3 R,(1) + K (1)^(2)
2 L(t)M
r 2n
"
for L(t) < A(r) < L(2) (7.s.s)

3 R"(1) +K,(1)^(r)
2 L(t)M
f- 2n
" for L(2) < < L;rcøuinry Q .5.6)
^(/)

Figure 7 .5.3 to Figure 7.5.6 present a comparison of the analytical best fit/-^ relationship
without damping, each derived from Equation 7.5.4, Equation 7.5.5 and Equation 7.5.6
with the experimentally derivedf relationships as presented in Section 6.4.6.1.

6
î
il
O ExperirænøI ll0mm
5

o 4
É vo DELe)2Bvo
Ð
á
s3
l!
-oet1t¡6
2

I
0
o oaooooo
No<tnËÉ aooo
æO\c)
Midheight displacerrent (mm)

Figure 7.53 Analytical vs Experirnental F-Á- 110mrn, No Overburden

178
CHAPTER (7) - Non-Linear Timc History
Analysis Development

6 o Experiæntal 50mm
N 5

à4
a % DELe)zBEo
o
ø 3
-DEL(I)6
o
tL
2

0
onono
Êclôlm nono
o{sn
Midheigbt displacement (mm)

Figure 7.5.4 Analytical vs Experimental F-Á- 50mr¡t, No Overburden

I
I o
'N' Þçerlmental r.5
7
>' 6
o {r) zolo DEr-{22Ít96
EI 5
ru

d 4 -DE
c)
L 3
t\
2
I
0
o rO otôorootootoo
ÊÊcìN(l)Cl)++lo
Midherght dlÐlacem¡t ( mm)

Figure 7.5.5 Analytical vs Experirnental F-Á- 50mnr,0.û7MPa Overburden

9
8
o Experirental 50mm
ñ 7

6
o to% DFt (2)3oEo
É 5
o
õ -pgr(l)
o 4
È 3

2
I
0
o ononon ÊNCIOO
ono
ËTh
Midheight displacemont (mm)

Figure 7.5.6 Anatytical vs Experinrental F-A- 50mnt' 0.15MPa Overburden

t79
CHAPTER (7) - Non-Lineqr Tilne History
Analysis Development

7.6. Modelling of Non-Linear Damping

Although the F-Â relationship is the most critical factor for modeling of the rocking
frequency response, damping also has an influence on the f relationship. Due to the
complex physical nature of damping it is usually represented in a highly ideahzed fashion
as an equivalent viscous (velocity proportional) damping force with a similar decay rate
under free vibration conditions to that of the real system being modelled. Thus, the
proportional damping coefficient used in formulating the equation of motion (Equation
7.2.2) is selected so that the vibration energy dissipated is equivalent to the energy
dissipated in all of the damping mechanisms of the rocking system. For an URM wall
these mechanisms would include elastic, friction, impact and joint rotation energy losses.
Although not strictly an accurate representation of the system behaviour any
disadvantage of using this approximate method is far outweighed by the simplification
achieved in applying the equivalent viscous damper.

Commonly the damping in most structures can adequately be modelled by using Rayleigh
damping.

Rayleigh damping is a linear combination of both mass and stiffness proportional


damping so that,

C = ooM *Kcr,1 = cloM + crr(Mco2) = M(r,.,* a{2n1l2) (7.6.1)

= C/M = ob+ a[2úf2

By substituting C/l\4 = 4rf I the theoretical Rayleigh equivalent viscous damping


becomes,

ao
I +atÚ (7.6.2)

By comparison with experimental results presented in Section 6.4.6.3 and careful


selection of oo, and o,1, Rayleigh damping was found to best represent the physical nature

of the real non-linear system damping mechanisms. Figure 7.6.1 presents a compa¡ison

180
CHAPTER (7) - Non-Lineør Time History
Analysis Development

of the experimental equivalent viscous damping versus frequency with that calculated

using a theoretical Rayleigh damping (Equation 7.6.2) for a 50 mm thick wall specimen
having no applied overburden.

18.070
â
Ø oÐoeRIÀæNTALpSI
À 16.0lo
o . RAYLEIGHPSI
z
À
14.0%
toô o8 o
t2.o%
o o o
o a o
I
(-)
10.07o

8.O7o
o
F
7,
e ¡t'
(J 6.07o
F
zfIl 4.O%
(I¡ = 1.0
(J c[r = 0.002
ú 2.O%
f!
o.
0.ïVo
0 1 ) 3 4 5 6 7
FRBQIJENCY

Figure 7.6.1 Experimental I vs Rayleigh | - 50mm \üatl, No Àpplied Overburden

Although the mass and stiffness proportional damping coefficients were found to be
higher for both the 50 mm thick walls with overburden and the 110mm thick walls than
the coefficients shown in Figure 7.6.1 these provided a reasonable lower bound estimate
of the equivalent viscous damping. Thus to be conservative these coeff,rcients were
adopted for the parametric study presented in Chapter 8.

If system damping were truly of the linear viscous form then any set of m consecutive
cycles would give the same viscous damping ratio. For the case for rocking of URM
walls m consecutive cycles in a high amplitude response section will yield a different
damping ratio than that of m consecutive cycles in a lower amplitude section of free
response. The equivalent viscous damping ratio is therefore non-linear amplirude or
frequency dependent (refer Figure 7.6.1). Thus, we are unable to assume a linea¡ viscous
damping within the THA so that either an average proportional damping coefficient or an
iterative approach must be invoked into the THA.

181
CHAPTER (7) - Non-Lineør Time History
Analysis Development

While adopting an average proportional damping coefñcient method for the entte
response is the simplest and least intensive method the main disadvantage is that it
requires an average response frequency,f, to be estimated prior to the THA. From this an
estimate of c/lM is made from Equation7.6.l. The consequence of this is that the analysis

outcome can be subjective as it is related to the assumed average response frequency.

For the iterative approach an initial estimate of the proportional damping is made at the
colffnencement of each haH cycle of the response. The instantaneous frequency is then
determined at the completion of each half cycle and the resulting proportional damping
calculated. This is then tested against the estimated proportional damping at the
beginning of the cycle. If the estimate and resulting proportional damping coefficient
match then the next half cycle is considered. If not the THA returns to the beginning of
the half cycle under consideration and the initial conditions are reset. Another estimate of
the proportional damping coefficient is made and the iterative process continues. This
iterative process is shown in Figure 7 .6.2. The only disadvantage of the iterative method
is that the computing time is increased, however, this was not found to be significant for
the SDOF system. Comparison of anal¡ical and experimentally response showed that
the iterative procedure was the most effective and least sensitive to initial assumptions.

Estimate c1-+f¡
Final
()
'1' Prediction
ft--xn
C11)€St C1

È
Ê
Return to start of half cycle-new estimate
{q) Estimaæ cr4r{crr
2
&
ø Esttmaæ c2+f2
úc) Íz*.zt
ç21
C21(9St C2
Rehrrn to start of half cycle-new estimate

Time Estimate cs@


\acÍt 2
2
Estimate ca+fr
T^=ttf, fs--xst
2 C314St C3

LpÍ' Continue next half cycle


2

Figure 7.6.2 lterative Damping

r82
CHAPTER (7) - Non-Linear Tim¿ History
Atwlysis Development

7 .7 . Event Based Time-Stepping Analysis

Since at any time the dynamic response is dependent on the instantaneous displacement
an event based time-stepping analysis was required to distinguish between the governing

dynamic equation of motion. As part of the time-stepping procedure the dynamic

response was considered by conversion of the static non-linear F-Â curve into a 'pseudo

static' F-A relationship. This procedure was based on the constant acceleration

assumption between time steps and takes into account the proportional damping. By
adopting the tri-linear F-A model, the 'pseudo static' F-Â relationship was made up of the
three 'pseudo static' stiffness' being ktsl, ktsp and kts2 (refer Figure 7.7.1). To permit
the use of the time-stepping procedure as described in Section 7 .5 the conversion factor
of 312 was applied to both the input ground acceleration, ac(t) and the three 'pseudo
static' stiffness'.

Re(1)

Re( 1 )+Â(2)Ke( I )+Â( I )ktsp

Re(1ÌrÂ(2)Ke(1 a\

s1

L(2) Âioro¡lity
^(1) Mid-height Displacement, Â
c)
o
ct ktsp-4M +2p
Ø
at? ¿t
/
Ø
c)
ú where dt is the time
o increment
Trilinear'pseudo static' I o
h
o
l¡r
stiffness (d kts 1 =Re( 1 ÞÂ(2)Ke( 1 )+ktsp
È
O

rl ^(1)
kts2=ke(lþktsp

Figure 7.7.1 'Pseudo Static' F-A relationship

183
CHAPTER (7) - Non-Linear Time History
Annlysis Development

The time-stepping procedure is then applied to the 'pseudo static' system. The first step is
to convert the input excitation, 312(ar(t)), to an incremental'pseudo static' force (dps)
which takes into account the previous incremental acceleration. Once this has been
determined it is used to calculate the incremental 'pseudo static' force displacement using

the respective 'pseudo static' stiffness. If or is reached within the time


increment this is recognised
^(tl) ^(+2)
as an event and the dynamic equation of motion and the
'pseudo static' stiffness is updated. Any remaining 'pseudo static' resistance force is
then used to determine the remaining incremental displacement according to the new
'pseudo static' stiffness so that the displacement at the completion of the time increment

is determined. This process is continued until the incremental 'pseudo static' force and
thus the remaining system energy is reduced to zero. Alternatively, if the instability
displacemerìt, *¡s¡¿5¡¡ty, has been exceeded this indicates failure and the THA process is

terminated.

The Fortran 77 program developed to run the non-linear rocking LJRM wall THA is
presented in Appendix (G).

7.8. Comparison of Experimental and Analytical Results

Conhrmation of the non-linear time history analysis (THA) softwa¡e developed for the
'semi-rigid' rocking response of URM walls has been conducted by comparison of
analytical results with both pulse and earthquake excitation shaking table test results
(refer Chapter 6). Figure 7.8.1 presents an indicative comparison of an analytically and
experimentally derived response for a 110mm thick, 1.5m tall wall with no overburden
having been subjected to a lHz,37mm amplitude pulse excitation. Further details of the
parameters used within the THA are presented in Appendix (H). Figure 7.8.1 (a) provides

a comparison of the experimental mid-height displacement, MWD, relative to the shaking


table compared with the THA, (u). Figure 7.s.1 (b) provides a comparison of the
experimental mid-height acceleration, MrilA, compared with the absolute mid-height
acceleration derived through THA, (at). Figure 7.8.1 (c) provides a comparison of
experimental and anal¡ical hysteretic behaviour.

184
CHAPTER (7) - Non-Linear Timc History
Analysis Development

0.04
0.03 u(m)
0)
q)
0.02
()
(l
È
Ø
0.01 -MWD
0

Eèo -0.01 (\ c.l cô ú) c.) c1
0) -0.02

Ë
-0.03
À
-0.04
Time(secs)
(a)

5
4

c)
J
,, -at(m/Vs)
Ra Á -MIWA
<*
I

t9 0
I
-/\ t.t
ÒO ô ô ) I ) ( c
¡€
c) -1
IC ó Cñ

N
_1
à
I
\ V
-3 yqv
-4
Time(secs)
(b)

*at(m/s/s)
o +MwA
GI
Ê
o
()^
c)
O C.l

ðo o O OO(
OOO
3
0.)

Mi¿l [Ieioht T']isnlacement fmì

(c)

Figure 7.8.1 Comparison of Analyticat and Experimental Pulse Test Results

Figure 7.8.2 presents a comparison of the THA and experimental peak mid-height
displacements for a non-loadbearing simply supported 110mm thick, 1.5m tall LJRM

wall. For the THA the wall condition was assumed to be moderately degraded. Here it
is observed that the peak displacement response for the tested pulse frequencies and
amplitudes is well represented by the THA. It is observed that the maximum

185
CHAPTER (7) - Non-Linear Time History
Arnlysis Development

displacement amplification occurs for pulse frequencies of around lHz to 2Hz. Thus the
effective resonant frequency,fit, for the 110mm thick, 1.5m tall simply supported walls
with no applied overburden is also approximately lHz.

ll0
Amplified
100
displacements
E

\fl
90

gBo
I
Ë

Hzo
o
o I1

ô. o
É60
g THEOREICAL 0.5FIz Pulse
Eso
o oo - TI{EORETICAL lFIz Pulse
ú - TI{EORETCAL 2IIz Pr¡lse
Ë40
Ð
E
- THEORETCAL 3.0H2 R¡Ise
¿30
tr
-o Ð(P I IIz 1/2 Sine Disp pulse
o FXP 2llz 1/2 Sine Disp pulse
= tr
20 o EXP 3I{z 1/2 Sine Disp pulse
tro tr EXP 0.5 [Iz Gaussian R¡lse
l0 E Ð(P I tlz Gaussian Pulse
tr EXP R.¡lse
0
0 l0 20 30 4 50 60 70 80 90 r00 I
Peak Base Displacernent (mm)

Figure 7.8.2 THA and Experinrental Peak Pulse Mid-height Disp. Response

Figure 7.8.3 presents an indicative comparison of an analytically and experimentally


derived response for a 110mm thick, l.5m tall wall with no overburden having been
subjected to an earthquake excitation representin g 80Vo of the Pacoima Dam earthquake
(refer Table 6.4.9). Further details of the parameters used within the THA are presented
ln Appendix (Ð. Figure 7.8.3 (a), (b) and (c) provide comparisons of mid-height
displacement, acceleration and hysteretic behaviour respectively.

186
CHAPTER (7) - Non-Lincar Tim¿ History
Analysis Development

4
É?
€) -at(r/s/s)
E^
()
-MV/A
åq
1

o
-Èr

tr _1
oo Ê CO ìa¡ t,,- O\ Ê
O^
-c -L
ilt Ittt
lt t t It
rt'
t
4 Irme(secs)
-5
(a)

0.08
À
g u(ml
0.06
Ë
Ë 0.04

Ë o.o2
I ilt
-MWD
.Ä0
o, I

Ë -0.02
(a¡ O ìô I
bo al !a) ht--ol\-cl+\c)æO\-ú)
J:Êeì(.lNelN(.lcq(.)
E -o.o¿
E
> -0.06 uv Time(secs)
-0.08
(b)

*at(rn/s/s)
.9
c!
Ê
(,)
o
+MwA
r
o^
o e.¡

.Ëg
è0 (
O
c)
EI

-l
Mid Heisht l)isnlacement fm'
(c)

Figure 7.8.3 Comparison of Analyt¡cåt and Experimental Earthquake Test Resr¡lts

A representative cross section of analytical and experimental, pulse and earthquake

results is presented in Appendix (Ff¡. This shows that the THA is capable of accurately
predicting both the forced and free vibration rocking response provided that the non-
linear (F-À) and damping properties are adequately represented in the analytical model.

187 ,)
8. LINEARISED DISPLACBMENT-BASBD
(DB)ANALYSIS

8.L. Linearised DB Analysis Methodology

The displacement-based (DB) analysis methodology provides a rational means for


determining seismic design actions as an alternative to the more traditional 'quasi-static'
force-based approach. In the DB procedure the dynamic lateral capacity of a structure is

determined on the basis of a comparison of a pre-determined failure displacement with


the displacement demand imposed on the structure by a seismic event.

To simplify the DB analysis procedure for highly non-linear systems the 'substitute
structure' methodology, proposed by Shibata and Sozen (1976), is often adopted. This
involves the substitution of the real structure's stiffness and damping properties with the
linear properties of a characteristic elastic SDOF oscillator. Here the characterising
linear properties are selected so that the linear and real non-linear systems are ftkely to
reach the failure displacement under the same applied excitation. The elastic system's
response to failure, as can be determined from the elastic response spectrum, is therefore
representative of the displacement demand on the real structure.

For elastic perfectly plastic systems (refer Figure 8.1.1) the bi-linear F-À relationship to
the failure displacement is characterised by the elastic stiffness related to the real
structure's secant stiffness at the in-elastic failure displacement (Priestly 7996:1997 ,Iudi
et al 1998, Edwards et aI 1999). Thus, the characterising SDOF oscillator stiffness
component is approximated by the lowest secant stiffness analogous with the real
structure's dynamic response and is associated with the lowest feasible response

frequency. Using this characteristic 'substitute structure' property for elastic perfectly
plastic systems and an appropriate level of equivalent viscous damping during the non-

188
CHAPTER (8) - Linearised Displacement-based Analysis

linear response, the linea¡ised DB analysis has been found to provide a reasonable
prediction of these system's dynamic lateral capacity.

Failure
Displacement

c)
()
o
t¡r
ñt
k()
d ¡.- Elastic Perfectly
Ëq) \Plastic Non-linea¡

Þ.
F-^ \ 'Substiu¡te
SEuch¡re'

Kubgi¡¡æ or¡ua¡rc

A¡oitrrc
Mid-height Displacement ( A)

Figure 8.1.1 Lineadsed DB Analysis for Elastic perfectly plastic System

Unlike the more comprehensive non-linear time history analysis (THA), the linea¡ised
DB procedure does not provide an accurate representation of the complete dynamic
response but rather an indication of the excitation (load) required to reach the pre{efined
failure displacement. To illushate, during the elastic response phase the tangential
stiffrress is underestimated however during the in-elastic response phase the tangential
stiffness is overestimated. As a consequence of this a 'period lag' may deveþ between
the 'substitute structure' and the real system displacement response so that at the critical
response cycle the DB analysis initial conditions may not represent the real initial
conditions.

The DB analysis effectiveness is dependent on the probability that the 'substitute


structure' and real system will reach the predetermined failure displacement when
subjected to the same excitation. It is therefore evident that for the DB analysis to
provide a reasonable estimate of the excitation required to cause the structure to reach the
failure displacement an integral part of the procedure is the selection of the cha¡acteristic

189
CHAPTER (8) - Linearised Displacement-based Arnlysis

SDOF oscillator or 'substitute structure' Iinear stiffrress. To confirm that the selected
'substitute structure' properties represent the real system at the critical displacement for
any linearised DB analysis procedure an extensive comparison of the DB prediction with

experimental and THA results was required.

The following chapter presents a proposed linearised DB analysis procedure for the
ultimate limit state analysis of simply supported URM walls including a procedure for the
definition of the characterising linear SDOF oscillator stiffness. The displacement
capacity and damping properties of the simply supported walls are discussed in
conjunction with the implication on the modeling of the real structure as a characteristic
SDOF oscillator. An extensive comparison of the linearised DB analysis predictions of
dynamic lateral capacity with THA and experimental results is then presented to confirm
the procedure' s suitability.

Similar to the above, a comparison of THA predictions with the existing 'quasi-static'
rigid body and 'semi-rigid resistance threshold' force prediction of lateral capacity is also
conducted. This highlights the limitations of not considering 'dynamic stability' concepts
for the dynamic analysis of simply supported URM walls. He¡e the 'quasi-static'

analysis results are shown to often fall outside of the limiting tolerance assumed for the
DB anaþis.

8.2. Proposed Linearised DB Analysis

In accordance with the DB procedure, the 'substitute structure' displacement demand

relative to the top and bottom wall supports is determined from the response spectral
displacement (Aps¡), as obtained from the corresponding elastic displacement response
spectrum and characteristic 'substitute structure' frequency and damping. As is shown
by the typical relative elastic displacement response spectrum in Figure 8.2.1, for flexible
(low natural frequency) elastic systems the maximum relative displacement imposed by
an excitation is equal to the peak ground displacement (PGD). For elastic systems with
natural frequencies near to the excitations dominant frequency, displacement

190
CHAPTER (8 )
-' Linearised Displacement- based Analysis

amplification and resonant effects increase the Ânso to a maximum greater than the PGD.
The displacement amplification is thus defined as Ânso,/PGD. For elastic systems with
natural frequencies greater than the excitation's dominant frequency ¡þs ÂRsp and
displacement amplification is reduced. For rigid elastic systems with large natural
frequencies (i.e. infinite stiffness), Ânsp approaches zero.

(A) natural frequency < (C) nan¡ral frequency >


dominant excitation frequency dominant excitation frequency

(t
Ë
o
d)
Ê.
U)
o-,
(B ) RESONANsT FREQUENCY
É

o()"Tl
naû¡ral frequency = dominant excitation frequency
úÊ Maximum displacement amplification

ËË
€À
õ.9
úÀ

PGD

Elastic System Natural Frequency

.J rJ

In*l Hishf
f =fæ
Resonant
frequency

PGD > PGD PGD


Åns¡ = PGD ^RsD
Âqso = 0

Figure 8.2.1 Typical Elastic Displacenrent Response Spectrum

191
CHAPTER (8) - Lineørised Displacement-bøsed Arnlysis

This indicates that for ground motions where the dominant frequencies are much greater
than the elastic system's natural frequency the system will be safe from failure provided
that the PGD does not exceed Âinsrau¡iry. On the other hand should the dominant ground

motion frequency be nea¡ that of the natural resonant frequency, the Ans¡ may be
significantly amplified above that of the PGD depending on damping. In this case failure
may occur under excitations with much lower PGD.

THA and shaking table tests have shown the maximum relative mid-height displacement
amplification to be 1.5 to 3.3. This corresponds to a dynamic amplif,rcation of I to 2.2 at
the wall's effective mass, which is the point located at 213 of the free body height from
the point where the wall is stationary. This suggests that during ground motion with
dominant frequencies in the vicinity of the walls resonant frequency the wall will be safe
from overturning provided that the PGD does not exceed 0.3 of the wall thickness
(0.6612.2). For design, safefy factors would also need to be applied.

8.2.1. Derivation of Characteristic SDOF 6Substitute Structure' Stiffness


Provided that the selected SDOF 'substitute structure' stiffness, Kn (refer Figure 8.2.2)

linearly characterises the real structure for response at the incipient instability
displacement the real structure's displacement demand can be determined in accordance
with the relative elastic displacement response spectrum. The selection of Ç6 must

therefore be made so that it is probable that the 'substitute structure' and rocking wall

system will reach their respective displacement capacity under the same excitation.

Unlike the elastic perfectly plastic system presented in Section 8.1, where the lowest
secant stiffness analogous with the real structures dynamic response is used to
characterise the non-linear, this is not appropriate for rocking objects as at the failure or
instability displacement, ¡s65¡¡¡y, the secant stiffness is zero. It was therefore necessary
to develop an alternative procedure for deriving the characterising linear stiffness for
rocking simply supported URM walls.

192
CHAPTER (8) - Linearised Displacement-based Analysis

For same excitation the 2 systems


reach instability displacement
'Substiûlte
o
()
! SEuch¡re'
o
l¡.
ct
kí)
ct
EIt) Real Semi-rigid

Êr
Non-linear F-À
Relationship

A¡rr¡o6¡¡¿¡y
Mid-height Displacement ( A)

tr'igure 8.22 Linearised DB Analysis Characteristic StifÊress, K.¡

During the response of a simply supported URM wall subjected to a transient excitation,
it has been observed that incipient instability is most likely to be reached as a
consequence of the large displacement amplif,rcations associated with the effective
resonant frequency of the wall. This is because unrealistically large ground motions are
required at or near resonance to cause the wall response to reach incipient instability.
Consequently, the resonant behaviour of the simply supported URM walts should be
modelled by the linea¡ 'substitute structure' stiffness. Thus, the characteristic linear
stiffness that will most likely best model the real wall behaviour at instability is the real
structure's effective resonant frequency. As was discussed in Chapter 5, the effective
resonant frequency, ,Ên of a simply supported wall is associated with the aveÍage
incremental secant stiffrress, K"r", of the dynamic F-Â relationship. By again assuming

the tri-linear approximation of the static F-Â relationship K u"" is determined in generic
terms as,

Krou" =K" r+2LQ)- L(r) +


Liwøøniry - LQ) (8.2.1)
Â(2) + Â(1) Linsøbitiry + L(2)

Here Ç(1) is dehned by Table 5.2.1andÂ(l) and L(Z)by Tabte 7.5.1

t93
CHAPTER (8) - Linearised Displacement-based Arnlysis

As the average dynamic secant stiffness, & ou" = 312 K" un" (again assuming a triangular

acceleration response relative to the wall supports) an estimate of the effective resonant

frequency without considering damping is therefore derived in accordance with

a=2nf= âS'
M e

3 K,o,"
2 M"
lqr (8.2.2)
2n

Since this estimation of/.6 by Equation 8.2.2 does not consider the damping component,
the true effective resonant frequency is expected to be slightly higher than the estimation.
This is confirmed by comparison with THA in Section 8.3.1.

8.22. Simply Supported URM Walls Modelled as a SDOF Oscillator


Prior to DB analysis being applied to a simply supported URM wall the substitutions
required for the modeling of the rocking system as an SDOF oscillator must be
recognised. These substitutions are required as for SDOF oscillator it is assumed that
lÙOVo of the system mass is mobilized whereas for rocking bodies this is not the case. As
a result the effective mass location relative to the supports must be considered.

8.2.2.1. Modelled Displac eme nt Capacity

As discussed in Section 5.2.1, for rigid simply supported objects the instability mid-
height displacement, A¡r¡¿6i¡1y, is considered to have been reached when the resultant
vertical force above the mid-height crack, due to self weight and overburden, is displaced
outside of the back mid-height edge of the wall. The mid-height displacement at which
this occurs is dependent on the support conditions (Table 5.2.1). For simply supported
'semi-rigid' URM walls with relatively low levels of applied overburden the finite
vertical reaction stress blocks a¡e small atlarge mid-height displacements. Consequently,
the rigid incipient instability displacement, ¡s¡¿6i¡¡y, can also be assumed for the analysis
of 'semi-rigid' simply supported URM walls.

t94
CHAPTER (8 ) - Linearised Dßplacement-based Analysis

As was discussed in the development of the THA algorithm in Chapter 7, to represent a


simply supported rocking object as an SDOF oscillator a triangular acceleration response
is appropriate relative to the supports. Consequently, the effective masses of the two
rocking free bodies are located at the 213 of the free body heights as measured from the
supports. The effective displacement capacity of the modelled SDOF 'substitute
structure', 4r rsøuility, is therefore reduced to 2/3 of the wall's static mid-height
displacement capacity so that:

Anmstauitity = 2/3 A¡.¡¿5¡¡1,

8.2.2.2. Modelled Damping Appropriate During Rocking Response

To take into account the reduced response velocity at the effective mass the level of
damping associated with the elastic displacement response spectrum is taken as 213 that
determined experimentally from the mid-height response of the wall. As was presented in
Section 6.4.6.3, a lower bound mid-height experimental equivalent viscous damping,

€soo", of approximately 57o was observed for both the 50 mm and 110 mm thick wall
specimens (refer Figure 6.4.20 and Figure 6.4.21). For simplicity and to be slightly
conservative an equivalent viscous damping of 57o for all frequencies was adopted. The
proportional damping coeffltcient, c, therefore varies linearly with frequency. The
corresponding equivalent viscous damping assumed for the DB analysis to determine the
elastic RSD was therefore 3Vo (=2¡3 5Eo¡.

8.3. Effectiveness of the Linearised DB Analysis

To test the effectiveness of the proposed DB analysis for face loaded simply supported
URM walls an extensive analytical study was conducted using the non-linear THA
software ROWMANRY presented in Chapter 7. In this study wall configurations
selected for examination included simply supported URM walls l.5m tall, being
representative of the experimental study presented in Chapter 6, 3.3m tall, being a
common height found in Aust¡alian masonry construction and 4.0m tall, as permitted by
the South Australian Housing Code, 1996. For each wall height, wall thickness

195
CHAPTER (8) - Linearised Displacement-based Analysis

considered included 50mm, 110mm and 220mm. Iævels of applied overburden included

0MPa, 0.075MPa, 0.15MPa and 0.25MPa being representative of Australian masonry


construction. For all wall configurations having applied overburden, the top vertical
reaction was assumed to be pushed to the leeward face of the wall so that the mid-height

Ainstability was the thickness of the wall (refer Table 5.2.1) being representative of a

concrete slab above boundary condition. Finally, the three levels of mortar joint
degradation defined in Section 7 .5 were also examined for each of the wall configuration
considered. As the tri-linear F-A approximation is again used Table 7.5.1 presents the
defining displacements Â(1) and A(2) associated with each of the three levels of joint
degradation.

The first stage in testing the effectiveness of the proposed linearised DB analysis
procedure was to determine the estimated effective resonant frequency for each of the

wall configurations based on the average cycle secant stiffness to ¡r¡u6¡¡¡r, without

considering damping in accordance with Equation 8.2.1. Following this, an extensive


THA study using gaussian pulse input was conducted to confi¡m that the estimate of the
effective resonant frequency derived was appropriate. A linearised DB analysis was then
conducted on each of the simply supported wall configuration subjected to the transient
excitations as presented in Table 6.4.9. Here the percentage of the normalised transient
excitations required to cause instability of the simply supported URM wall under
consideration was predicted. As part of the linearised DB analysis procedure the derived
estimate of effective resonant frequency using Equation 8.2.2 was used as the
characteristic 'substitute structure' frequency. As discussed in Section 6.4.7.2 the
earthquake excitations used were selected to provide a representative cross section of
frequency and amplitude contents of plausible ground motions.

Comparison of the DB analysis is then made with results derived using the
comprehensive THA softwa¡e. The following sections present each stage of the study.

196
CHAPTER (8) - Linearised Displacement-based Analysis

8.3.1. Effective Resonant Frequency of simpry supported URM walls


The first stage of the study was to determine the effective resonant frequency of the
simply supported wall configurations selected. Initially an estimate of effective resonant
frequency based on the average static secant stiffness determined from Equation g.2.1
was made from Equation8.2.2.

A THA study was then conducted to confirm the effective resonant frequency for the
selected wall configurations. This was achieved by running a series of 500 gaussian
pulseTHA at frequencies ranging from 0.25Hzto l}Hz and amplitudes from 2.5mm to
11Omm for each of the wall configurations under consideration. From the resulting RSD

versus PGD plot the frequency associated with maximum displacement amplification was

identified as the effective resonant frequency. To illustrate, Figure 8.3.1 presents the
RSD versus PGD for a 500 gaussian point THA run for a non-loadbearing 3.3m tall,
l lOmm thick simply supported wall having moderately degraded rotation joints. From
this plot it is observed that the maximum mid-height displacement amplification of
lt0l40 = 2.75 is associated with gaussian pulse frequencies of between 0.75H2 and,
1.0H2. This is compared with the estimated effective resonant frequency derived in
accordance with Equation 8.2.2 for the 3.3m tall simply supported LIRM wall having
moderately degraded rotation joints of 0.81H2. For pulses with a much higher frequency
than the system natural frequency (>2.5H2) it can be seen that the plot converges to a
straight line where the PGD is equal to approximately 213 of the relative response mid-
height spectral displacement. Alternatively this line indicates where the pGD is
approximately equal to the Âns¡ measured at the 213 free body height being
representative of the effective mass location relative to the supports due to the triangular
acceleration response. This can be related to the lower part of zone (A) shown in Figure
8.2.1). For these higher frequencies it is evident that instability can only occur when the
PGD is equal to or greater than 213 of ¡or¡u6¡1, (measured at the mid-height).
Accordingly, much higher forces can be withstood by the wall at the higher excitation
frequencies than at frequencies near to the effective resonant frequency. This illustrates
the dependence of the walls dynamic reserve capacity on the dominant excitation
frequency.

r97
CHAPTER (8) - Linearised Dßplacement-bøsed Analysis

110
Maximum
I /
,{
rY
I
r00 Displacement/ I
Amplification )

90

€Í so
Poc!
EÊ PGD=2ß of
ó2io the relative
ËE mid-height
J
É8 ¿o disp. response
øá
o:

ãäso
E:
d¡3 )
*o.zsw, 0.5IIz *o.lsH"
åË 40 1 1n -#t.259" #t.5H"
Eå #2.5H"
e''4Hz À sl¡"
Ë' ,o
-l.75Hz3Hz
*:l- loHz -zHz
20

10
f âaãl Ðooê
Í Ðêê(; Ðoêê
froë'
0
0102030405060708090 100

PGD(mrn)

Figure 8.3.lGaussian Pulse; 33m Tall, 110mm Thicþ Moderate Degradation TIIA

As a result of this study it was determined that the effective resonant frequency of simply
supported URM walls derived using THA was approximately that predicted from the
average secant stiffness to A¡5¡¡5i¡¡y (refer Equation 8.2.1). A slight va.riation was

predicted to be due to the small influence of including damping in the THA increasing
the response frequency slightly. In summary, it was found that the frequency derived

using Equation 8.2.1 provided a good assessment of the estimate of effective resonant
frequency derived from the THA study which itself correlated well with the experimental
results (refer Figure 7.8.2). Consequently, it was postulated that the approximate
effective resonant frequency for simply supported URM walls determined in accordance
with Equatto¡ 8.2.2 for use as the characteristic 'substitute sffucture' frequency is
adequate considering the approximations made within the linearisation procedure.

The estimated effective resonant frequency (Equation 8.2.2) determined for the 1.5m,
3.3m and 4.0m height walls at various levels of overburden stress and joint degradation

198
CHAPTER (8) - Linearised Displacement-based Analysis

are presented in Table 8.4.1 to Table 8.4.12. In most cases the effective resonant
frequency is associated with the secant stiffness at instantaneous displacements at around
30 to 40Vo of the incipient instability displacement. The wall thickness was found to have
little influence on the effective resonant frequency (the reasons for this are discussed in
Section 5.2.1).

By comparison with experimental results it was also found that the analytically derived
effective resonant frequencies correlated well with frequencies observed experimentally
as the minimum asymptotic frequency, friroit.

8.32. Linearised DB Analysis


The second stage of the study was to conduct the linearised DB analysis on each of the
simply supported tlRM wall configurations subjected to the transient excitations
presented in Table 6.4.9 including Elcentro, Pacoima Dam, Nahanni and Taft earthquake.

Here the effective resonant frequency determined in the fîrst stage of the study, and the

elastic displacement response spectrum at 3Vo damping (=2l3x5%o) were used to


determine the displacement demand on each of the modelled wall configurations. Using
the effective resonant frequency as the cha¡acterising elastic SDOF stiffrress the percent
normalised earthquake excitation required for the modelled displacement demand to
equal the modelled displacement capacity was determined. This therefore represented the

excitation required for ultimate instability of the wall to be reached. For illustrative
purposes the linearised DB procedure for the 3.3m tall, 110mm thick wall with 0.075MPa

applied overburden stress having moderately degraded rotation joints and subjected to the

ElCentro earthquake is described.

Figure 8.3.2 presents the relative elastic displacement response specfum (3Vo damping)
for the Elcentro earthquake comprised of displacement-normaltzed spectrum ranging
from 25Vo to 500Vo in 25Vo increments. The horizontal line shown at 73mm (ll0x2l3)
displacement is representative of the displacement capacity of the elastic SDOF
'substitute structure' representing the 110mm thick wall both with and without

199
CHAPTER (8) - Linearised Displacement-based Analysis

overburden. The estimate of effective resonant frequency, determined in accordance with


Equation 8.2.1 (refer Table 8.4.2) is l.23Hz. As frequencies gteater than the assumed
characteristic SDOF oscillator frequency are relevant to the response, to be slightly
conservative the lowest percent displacement normalised ElCentro earthquake is adopted
from all frequencies greater than the estimated effective resonant frequency. Thus, using
the characteristic 'substitute structure' stiffness compatible with the l.23Hz resonant
frequency the percent displacement normalised ElCentro earthquake predicted to cause
instability of the wall is determined as 7OVo.

Results of the linearised DB analysis for all of the considered wall conf,rgurations are
presented in Table 8.4.1 to Table 8.4.12.

e 200
É I

ã a ïï
ft rzs * xt
.s

'ã rt t ¡
I
E t\
b
I
H lzs
1¿
¡

t
\ -+- +
E roo
8"

I
75
IY 7Qïo
1
1
50
¡ \ )aa A
I FT Lt i'l(
P( N
25 tf.
+ Ê
+. È
0
hhih6hNhhhóhhhthhhhñh
Jtìcl..jrìclñrì.ìGiìcl+lqvi
OÉÊddoOçth
'SUBSTITUTE STRUCTIJRE' FREQTJENCY

Figure 8.3.2 Relative ElCentro Earthquake Elastic Response Spectrum (37o damp¡ng)

8.33. TIIA for Various Transient Excitation


The next stage of the study to test the effectiveness of the DB criterion \ryas to predict the
percent displacement normalised earthquake to cause ultimate instability using the non-
linear THA software described in Chapter 7. For each wall under consideration a THA
was performed gradually increasing the displacement-normalised earthquake by l7o at a

200
CHAPTER (8) - Lineørised Dßplacernent-based Analysis

time. Figure 8.3.3, Figure 8.3.4 and Figure 8.3.5 present the peak mid-height
displacement result, relative to the supports, for the 1.5m, 3.3m and 4m wall respectively

at va¡ious overburden and with moderately degraded bed joints subjected to the ElCentro
earthquake. From Figure 8.3.4 it can be observed that for the 3.3m wall with 0.0Z5Mpa
applied overburden stess the THA prediction for ultimate instability is 85Vo of the
displacement normalised ElCentro earthquake. This compares reasonably well with the
DB analysis prediction of 70Vo ElCentro as described in Section 8.3.2. Damping
assumed for all THA was Rayleigh damping with the mass proportional coeff,rcient of 1.0
and stiffness proportional coefficient of 0.002 as these represented the lower bound of the
experimental results presented in Section 6.4.6.3.

ll0
100
E90 +0MPa
Y80
ts
{-0.075MPa
8zo 0.l5MPa
É
Jê0.25MPa
s60
Éso
 a
Ë40
Ð
'õ.
¡ 30
Ézo
0
0 50 100 150 200 250 300 350 400 450
7o Normalised Accelerogram

Figure 8.3.3 THA ElCentro Earthquake: 1.5m Tall, Moderate Degradation

110 vt t -"
100

Ee0 <-OMF¿
Yao {-0.075MPa
Ezo 0.15MPa
o
R60 ra -)ts0.25MPa
¡'t
ås0
åû r tJ
õ
830
þzo
0
0 25 50 75 100 t25 150 175 200 225 250
% Normalised Accelerogram

Figure 8.3.4 ElCentro Earthquake: 33m Tall, Moderate Degradation

201
CHAPTER (8) - Linearised Displacement-based Anølysis

110 'ìl" t^ 'I/ : -

^100 -#OMPa
Ëe0
, #0.075MPa
ãao
Ëro .fl
t i
0.l5MPa
-X-0.25MPa
-E
Þ.
É50
oo
t-
z,Æ
il
Eso
€ro
'' 10
0
0 15 30 45 60 75 90 r05 r20 135 150 165
% Normalised Accelerogram

Figure 8.3.5 ElCentro Earthquake: 4.0m Tall, Moderate Degradation

The analysis results for the THA study are presented in Table 8.4.1 to Table 8.4.12.

8.3.4. Comparison of Predictive Model Results

The final stage of the study to test the effectiveness of the DB criterion was to compale
the linearised DB and non-linear THA predictions of the percent displacement

normalised eafthquake to cause ultimate instability as derived in 8.3.2 and 8.3.3


respectively. Figure 8.3.6 graphically presents these comparisons where it is observed
that almost all of the results fall within the bounds of the 1507o tolerance lines. That is,
the linearised DB analysis, using the estimate of effective resonant frequency derived in
accordance with Equation8.2.2 as the characterising 'substitute structure' frequency, will
provide an ultimate instability prediction not more than 1.5 times and or less than2l3 of
that predicted by the more comprehensive non-linear THA. The scatter of results
observed is a function of the linearisation of the real non-linear stiffrress and damping
components of the real rocking wall system.

Further to this comparison, the more traditional 'quasi-static' rigid body prediction of
lateral resistance capacity and the 'semi-rigid resistance threshold' acceleration (refer
Table 8.4.1 to Table 5.4.12) are compared with the THA predictions.

202
CHAPTER (8) - Linearised Displacement-based Analysis

2.50

w
.ELCENTRO
d
2.25 15O4"'ît llønæI.i
IPACOIMADAM
,me
o TAFT
õ 2.00

-7
É ONAHANM
I 1.75
o o ô
o Un-conser ¡ativeDB nalysis
(
o a
r

Predicti@
È 1.50
H

/r
o
r.¡r
1.25

d
o r
l5Ocr'oTo terance Lir
J 1.00
rl
t a )/
0.75

Cons rvativÊ DI
0.50

0.25
I
0.00
o o o
Ò el n I o eì I rì o cl
o o o o el N N
THAG)

Figure 8.3.6 Comparison of DB Analysis and THA Ultirmte Instability Prediction

Figure 8.3.7 presents graphically the compa.rison of the 'semi-rigid resistance threshold'
acceleration with the THA ultimate instability prediction. Here it is observed that for the
transient excitations with lower dominant frequencies (Taft, ElCentro and Pacoima Dam)
near to the wall's effective resonant frequency the 'semi-rigid resistance threshold'
acceleration provides a good prediction of the lateral acceleration capacity of the wall.
This is because at these dominant excitation frequencies there is little benefit gained
through 'dynamic stability' concepts so that the URM wall's reserye capacity is small.
Thus, this 'quasi-static' analysis provides a reasonable prediction oflateral capacity. For
excitations having dominant frequencies greater than the effective resonant frequency
(Nahanni) the dynamic reserve capacity is far more significant. As this is not accounted
for by the 'quasi-static' analysis the ultimate instability prediction is conservative.

203
CHAPTER (8) - Linearised Displacement-based Analysis

2.50
d) aeI-cENTRo l50%oTol erance
o -imit
lpeconuRo¡r"t
T
2.25
b
ç¡.
o TAFT
s 2.00 oNRnnr.INI
I
?
.s Equ Line
.2
o
I I Lity

1.75
ú Un-col servative I RR
Ë analys s Predictio I
è0
d 1.50
Cons )rvative lredictic
E
o
ll
(t) t.25
a I
a I !^lt^--^^
1.00 ¡
a Limit
a T
0.75
ì TT o Cons :rvative Sl R
t.ì a¡al: ris Pr€dict )n
0.s0
I o o
âô ô
0.25
a o
e o oB ooo o (J

ô Ê
0.00
onÔnahonano
õñnrôNhroe{n
ððoo-'iôi ñõi
THAG)

Figure 8.3.7 R*(1) vs THA Ultirnatc Instability Prediction

Figure 8.3.8 presents graphically the comp¿ìrison of the 'quasi-static' rigid body ultimate
instability prediction. Here it is observed that for the transient excitations 'with lower
dominant frequencies near to the wall's effective resonant frequency the 'quasi-static'
rigid body analysis provides an un-conservative prediction of the lateral acceleration

capacity of the wall. This is attributed to the overestimation of the 'semi-rigid resistance
threshold' force by the rigid assumption and ths in-significant wall dynamic reserve
capacity. For transient excitations with higher dominant frequencies than the wall's
effective resonant frequency, like the 'semi-rigid resistance threshold' force prediction,
the 'quasi-static' rigid body analysis provides a conservative prediction of the lateral
acceleration capacify of the wall.

204
CHAPTER (8) - Lineørised Displacement-based Analysis

€9 2.50
.ELCENTRO 150%1 ollerance I {
õ 2.25 TPACOIMADAM
Ê
TAFT
at 2.00 ONAHANNI
o
É
Ë RB
^, ity Line

è0 1.75 AI
ú
-a a I t a I Io
s
u)
1.50
ßOqt Tolleranq
Limit
lt
a 1.25
a o
1.00
o
0.75
I
,) /l Cmserv¿ ive RB
,'l o anatysis Tediction
J o
0.50
o oo oo o
0.25 ô
o
o
o o" o
0.00 o
o
ô
o

o
Vl
o
¡l
o
a cl o
u] ì E
el
cl
e.l e{
THAG)

Figure 8.3.8 'Quasi-static' Rigid Body vs THA llltirnate Instability Prediction

8.4. Conclusion

Linearised DB analysis using the wall's effective resonant frequency as the 'substitute
structure' natural frequency provides predictions of ultimate instability \ryithin + 5OVo of
the more comprehensive THA. Equation 8.2.1, which represents the generic average
secant stiffness to the incipient instability displacement, has been found to provide a
reasonable estimate of the simply supported IJRM walls effective resonant frequency.

The linearised DB analysis therefore provides a rational and relatively straight forward
prediction of the dynamic lateral capacity for simply supported URM walls. Since this
takes into account the true dynamic behaviour of the rocking wall system, the dynamic
reserve capacity for excitations having dominant frequencies greater than the effective
resonant frequency is accounted for.

In conclusion the linearised DB analysis using the wall's effective resonant frequency
determined in accordance with Equation 8.2.1 as the 'substitute structure' characteristic

205
CHAPTER (8) - Linearised Dßpbcement-based Analysis

frequency provides predictions within limiting tolerances of + 50Vo of the more

comprehensive THA results. This method therefore provides the most rational and
simple approach for assessing the dynamic lateral capacity of simply supported URM
walls subjected to transient excitations.

Table 8.4.1 ElCentro Analysis Conrparison: 1.5m Height Wall

GEOMETRY OVER- WALL CONDITION RIGID SEMI THA DBA


(t) (h) BURDEN (refer ag) BODY RIGID ToEQ PGA &t (g)
l* >FREQ >FREQ
(mm) (m) (MPa) Figure A^ A* G) G) (Hz) ToEQ PGA
6.4.12) k)
50 1.5 0 NE}V 67o 287o 0.13 0.10 33Vo 0.11 1.45 307o 0. l0
50 1.5 0 MOD l37o 4OVo 0.13 0.08 197o 0.07 t.2t 25Vo 0.09

0.13 0.07 217o 0.07 1.04 20Vo 0.07


50 1.5 0 SEV 2O7o 5O7o
50 1.5 0.075 NEW 67o 28Vo 0.89 0.64 l3O7o 0.45 2.U l4OTo 0.49

50 1.5 0.075 MOD l3%o 4OVo 0.89 0.53 924o 0.32 2.X lOO9o 0.35

50 1.5 0.075 SEV 2O4o 5O7o 0.89 0.44 767o 0.26 LM 6OVo o.2t

50 1.5 0.15 NEW 6Vo 28Vo 1.64 1.18 5407o 1.14 t.74 2OOTo 0.70

50 1.5 0.15 MOD 13Vo 4OVo 1.64 0.99 LSO4o 0.52 3.r2 lSOTo 0.52

50 1.5 0.15 SEV 2OVo 5OVo 1.64 0.82 lXZ7o 0.42 2.69 ll57o 0.40

50 1.5 0.25 NE}V 6Vo 28Vo 2.65 1.91 NF NF 4.62 4001o 1.39

50 1.5 o.25 MOD l3Vo 4OVo 2.65 1.59 I{F NF 3.9 2OOVo 0.70

50 1.5 o.25 SEV 2OVo 5OVo 2.65 1.33 1939o 0.67 337 2NVo 0.70

110 1.5 0 NEV/ 6Vo 287o o.29 o.2l 80Vo 0.28 1.45 85Vo 0.30

ll0 1.5 0 MOD 13Vo 4OVo 0.29 0.18 457o 0.16 t2r 6OVo 0.21

0 SEV 0.29 0.15 457o 0.16 1.04 45Vo 0.16


110 1.5 2O7o 5O7o
110 1.5 0.075 NEW 67o 28Vo 1.95 l.4l 3757o t.3l 2.U 3tOVo 1. r5

110 1.5 0.075 MOD 13Vo 4O7o 1.95 t.t7 3257o 1.13 2.36 250Vo 0.87

110 1.5 0.075 SEV 2OVo 5OVo 1.95 0.98 2107o 0.73 2.M \23Vo 0.43

110 1.5 0.15


'
NEW 67o 287o 3.62 2.60 Nr. NF 1.74 425Vo 1.48

110 1.5 0.15 MOD 131o 4OVo 3.62 2.17 NF NF 3.12 3257o 1.13

110 1.5 0.15 SEV 2OVo 5OVo 3.62 l.8l 3854o 1.34 2.69 250/o 0.87

110 1.5 0.25 NEV/ 67o 28Vo 5.83 4.20 ¡m NF 4.62 NT' NF

110 1.5 0.25 MOD 137o 4OVo 5.83 3.50 NF NF 3.9 ASTo 1.48

r10 1.5 0.25 SEV 2O7o 5OVo 5.83 2.92 NF NF 337 4254o 1.48

NEW 0.59 o.42 1557o 0.54 1.45 lTOVo 0.59


220 1.5 0 6Vo 28Vo
220 1.5 0 MOD l3Vo 4OVo 0.59 0.35 85Vo 0.30 l.2l 125Vo 0.44

220 1.5 0 SEV ZOVo SOVo 0.59 0.29 N7o 0.28 1.04 85Vo 0.30

220 1.5 0.075 NEW 6Vo 284o 3.91 2.8r NF NF 2.U NT' NF

220 1.5 0.075 MOD I3Vo 404o 3.91 2.35 NF NF 236 NF NF

220 1.5 0.075 SEV 2OVo 5O1o 3.9t 1.95 4l5Vo 1.45 2.M 4707o t.&
l5 NEW 7.23 5.2r NF NF 3.74 NT' NF
220 1.5 0. 6Vo 28Vo
220 1.5 0.15 MOD 13Vo 4O7o 7.23 4.34 I\F NF 3.12 NT' NF

220 1.5 0.15 SEV 2OVo 5O7o 7.23 3.62 NF NF 2.69 NF

NEW 11.66 8.40 NF NF 4.62 NF NF


220 1.5 0.25 61o 28Vo
MOD l31o 11.66 7.00 NF NF 3.9 NT' NF
220 1.5 0.25 4OVo
1r.66 5.83 NF NF 3.37 NT' NF
220 1.5 0.25 SEV 2OVo SOVo

*NF
- No Fail within limits of study

206
CHAPTER (8) - Lineørised Displacernent-based Arnlysis

Table 8.4.2 ElCenho Analysis Conrparison: 3.3m Height Wall

GEOMETRY OVER. WALL CONDITION RIGID SEMI THA DBA


(r)
(mm)
(h)
(m)
BURDEN (refer a(1) BODY RIGID &I VoEQ PGA l"n >FREQ >FREQ
0\,rPa) Figure A^ 4^ G) G) G) (Hz) loEQ PGA
6.4.12) k)
50 3.3 0 NE\Y 67o 28Vo 0.06 0.04 2O7o 0.07 0.96 257o 0.09
50 3.3 0 MOD 13Vo 4OVo 0.06 0.04 tLVo 0.08 0,81 25Vo 0.(D
50 3.3 0 SEV 2OVo 5O7o 0.06 0.03 267o 0.09 t.7 25To 0.09
50 3.3 0.075 NEW 6Vo 28Vo o.22 0.r6 327o 0.1I t.46 3O7o 0. r0
50 3.3 0.075 MOD 13Vo 4OVo 0.22 0.13 27Vo 0.09 t.?.3 25y'o 0.09
50 3.3 0.075 SEV 2OVo 5OVo 0.22 0.11 2OVo 0.07 1.0ó 2OVo 0.07
50 3.3 0.15 NEW 6Vo 287o o.37 0.27 547o 0.19 1.82 45lo 0.16
50 3.3 0.15 MOD 13Vo 4OVo 0.37 0.22 377o 0.13 1.54 357o tJ.12
50 3.3 0.15 SEV 2OVo 5O7o 0.37 0.19 327o 0.11 r33 3O9o 0.r0
50 3.3 o.25 NEW 6Vo 28Vo 0.58 0.42 93Vo 0.32 2.72 TOVo 0.24
50 J.J 0.25 MOD l3Vo 4O7o 0.58 0.35 6Vo 0.23 SOVo o.t7
50 3.3 o.25 SEV 2O7o 5O7o 0.58 0.29 439o 0.15 L6¿ 4O7o 0.14
110 3.3 0 NEW 6Vo 28Vo 0. 13 0.10 457o 0.16 0.96 457o 0. ló
ll0 3.3 0 MOD l37o 4OVo 0.13 0.08 45Vo 0.16 0.81 451o 0.1ó
ll0 3.3 0 SEV 2OVo 50% 0.13 0.07 457o 0.16 0.7 457o 0. l6
110 3.3 0.075 NEW 6Vo 28Vo 0.48 0.34 üVo 0.28 1.46 EOVo 0.28
110 3.3 0.075 MOD 137o 4OVo 0.48 o.29 85Vo 0.30 t.?ß 7O7o 0.24
ll0 3.3 0.075 SEV ZOVo SOVo 0.48 o.24 5O7o 0.17 1.06 S54o 0.19
110 3.3 0.15 NEW 6Vo 28Vo 0.82 0.59 lffiVo 0.56 1.82 lOOTo 0.35
110 3.3 0.15 MOD l3Vo 4OVo o.82 0.49 l30Vo 0.45 1.54 917o 0.31
ll0 3.3 0.15 SEV ZOVo 5O7o 0.82 0.41 1257o o.44 1.33 EOVo 0.28
ll0 3.3 0.25 NEW 67o 28Vo 1.28 0.92 ttsvo 0.78 2.?:2 l5O7o 0.52
110 3.3 o.25 MOD l3Vo 4O7o 1.28 0.77 1757o 0.61 1.87 llïVo 0.38
110 3.3 0.25 SEV 2OVo 5OVo 1.28 o.& l45Vo 0.51 1.62 9O7o 0.31
220 3.3 0 NEW 6Vo 28Vo 0.27 0.19 7íVo 0.26 0;96 9OVo 0.3r
220 3.3 0 MOD 137o 4OVo 0.27 0.16 80Vo 0.28 0;81 9{Vo 0.31
220 3.3 0 SEV 2O7o 5O7o o.27 0.13 lA07o 0.35 0.7 9OVo 0.31
220 3.3 0.075 NEW 6Vo 28Vo 0.95 0.69 16OVo 0.56 1.46 16OVo 0.56
220 3.3 0.o75 MOD 13Vo 40Vo 0.95 0.57 lffiVo 0.56 1.23 l25lo 0.44
220 3.3 0.075 SEV 2OVo 5OVo 0.95 0.48 l05Vo 0.37 1:06 9X)7o 0.31
220 3.3 0. l5 NEW 67o 28Vo 1.64 1.18 3357o l.t7 1.82 2OOVo 0.70
220 3.3 0.15 MOD 13Vo 4OVo 1.64 0.98 2757o 0.96 1.54 17SVo 0.61
220 3.3 0.15 SEV 2OVo 5OVo 1.64 0.82 2357o 0.82 1.33 17SVo 0.ól
220 3.3 0.25 NEIW 6Vo 28Vo 2.55 1.84 4SSVo 1.58 2.X2 3507o 1.22
220 3.3 0.25 MOD 13Vo 4OVo 2.55 1.53 SOOVo 1.74 1.87 25O7o 0.87
220 3.3 o.25 SEV 2OVo 5OVo 2.s5 1.28 29n7o t.0r 1.62 17íVo 0.61

*NF
- No Fail within limits of study

207
CHAPTER (8) - Linearised Dßplacement-based Analysis

Table 8.4.3 ElCentro Analysis Comparison: 4.0m Height \üall

GEOMETRY OYER- WALL CONDITION RIGID SEMI THA DBA


(t) (h) BURDEN (refer 4ú) AG) BODY RIGID VoEQ PGA f*
(IIz)
>FREQ >FREQ
(mm) (m) (MPa) Figure A^ 4^ G) G) G) ToEQ PGA
6.4.12\ G)
50 4 0 NEW 6Vo 287o 0.05 o.04 32Vo 0.1r O.EE 254o 0.09

50 4 0 MOD 13Vo 4O7o 0.05 0.03 3O4o 0.10 o.74 259o 0.09

50 4 0 SEV 2O4o 5OVo 0.05 0.03 33Vo 0.n 0.64 25(o 0.09

50 4 0.075 NEW 6Vo 28Vo 0. 16 0.ll 32Vo 0.11 1.26 257o 0.09

50 4 0.075 MOD 137o 4OVo 0.1ó 0.09 L9Vo 0.07 1.06 22Vo 0.08

50 4 0.075 SEV 2OVo 5O7o 0. ló 0.08 2lVo 0.07 0.92 22(o 0.08

50 4 0.15 NEW 6Vo 287o o.26 0.19 5O7o o.t7 1.55 4O9o 0.14

50 4 0.15 MOD l37o 4O7o o.26 0. 16 347o o.t2 1.31 35Vo o.t2
50 4 0. 15 SEV 2OVo 5OVo [J.26 0.13 22Vo 0.08 1.13 251o 0.u,
50 4 o.25 NEW 6Vo 287o 0.4{) o.29 62Vo 0.22 1.01 5O7o 0. 17

50 4 o.25 MOD l3Vo 4OVo 0..!0 0.24 417o 0.14 l.5E 4OVo 0.14

50 4 0.25 SEV 2OVo 5O7o 0.40 o.zo 377o 0.13 1.36 35To 0.12

ll0 4 0 NEW 6Vo 28Vo 0.11 0.08 757o tJ.26 0.8E 45Vo 0. 16

110 4 0 MOD 13Vo 4OVo 0.il 0.07 45Vo 0. l6 0.74 45Vo 0.16

110 4 0 SEV 2OVo 5OVo 0.ll 0.06 55lo 0.19 0.64 457o 0. 16

110 4 0.075 NEW 6Vo 287o 0.34 0.25 757o 0.26 70Vo o.24

110 4 0.075 MOD l3Vo 4OVo 0.34 o.2t 55Vo 0.19 l;06 5O7o 0.17

110 4 0.075 SEV 2OVo 5OVo 0.34 0.17 457o 0.16 0,92 457o 0.16

110 4 0.15 NEW 67o 28Vo 0.5E o.42 lO5Vo 0.37 1.55 ESVo 0.30

ll0 4 0.15 MOD l3Vo 4O7o 0.58 0.35 757o o.26 131 lSVo 0.26

110 4 0. 15 SEV 2OVo 5OVo 0.s8 0.29 TOVo o.24 1.13 60?o 0.21

ll0 4 0.25 NEW 6Vo 287o 0.89 o.g lEïVo 0.63 1.01 IIOVo 0.38

110 4 o.25 MOD l3Vo 4OVo 0.89 0.53 l35Vo o.47 1.sE 9OVo 0.31

110 4 o.25 SEV ZOVo 5O7o 0.89 o.44 9Oio 0.31 136 9O7o 0.31

220 4 0 NE}V 6Vo 281o 0.22 0.16 t457o 0.51 0.8E 9nVo 0.3r
220 4 0 MOD 13Vo 4OVo o.22 0.13 too% 0.35 0.74 9OVo 0.3r
220 4 0 SEV 2OVo 5OVo o.22 0.11 llSVo 0.,1{J 0.64 9O4o 0.31

220 4 0.075 NEW 6Vo 287o 0.69 0.49 l25Vo o.44 1.2Íi lSOlo 0.52

220 4 0.075 MOD 13Vo 4O7o 0.69 0.41 160Vo 0.56 1.06 9OVo 0.31

220 4 0.075 SEV 2OVo 5OVo 0.69 o.34 9O9o 0.3r 0.92 90?o 0.31

220 4 0.15 NEW 6Vo 28Vo l 15 0.83 2to?o o.13 1.55 17SVo 0.61

220 4 0.15 MOD 137o 4OVo 1.15 0.69 2207o 0.77 131 16O7o 0.56

220 4 0. 15 SEV 2OVo 5O7o l.l5 0.58 l35Vo o.47 1.13 llSVo 0.,1O

220 4 o.25 NEW 6Vo 28Vo 1.78 1.28 370Vo 1.29 1.01 2lO7o 0.73

220 4 0.25 MOD 13Vo 4OVo l.7E r.07 2E07o 0.98 l5E IEOVo 0.63

220 4 o.25 SEV 2O7o SOVo 1.78 0.89 lEOTo 0.63 136 lTOVo 0.59

*NF
- No Fail within limits of study

208
CHAPTER (8) - Linearised Displacement-based Analysis

Table 8.4.4 Taft Analysis Conrparison: l.5m Height \ilall

GEOMETRY OYER. \ilALL CONDITION RIGID SEMI THA DBA


(r) (h) BURDEN (refer ag) AQT BODY RIGID TIEQ PGA .r"n >FREQ >FREQ
(MPa)
(mm) (m) Figure 4* 4^ G) G) G) (Hz) loEQ PGA
6.4.12) k)
50 1.5 o NEIW 6Vo 28Vo 0.13 0.10 72Vo 0.13 1.45 öo"h 0.14
50 1.5 0 MOD 13Vo 4OVo 0.13 0.08 58% o.10 1.21 55Uo 0. t0
50 1.5 0 SEV 20% 50Vo 0.13 0.07 4OUo 0.07 1.04 45% 0.08
50 1.5 o.o75 NEI9V 6Vo 28Vo 0.89 o.M NF NF 2.84 190% 0.34
50 1.5 0.075 MOD l3Vo 4OVo 0.89 0.53 1360/o o.24 2.36 180ch 0.32
50 1.5 0.075 SEV ZOVo 5OVo 0.89 0.44 IOZYo 0.18 2.O4 95"/" o.17
50 1.5 o.15 NE}V '1.64 1.18 NF 3.74
6Vo 28Vo NF 410% o.74
50 1.5 0.15 MOD 13Vo 4OVo 1.64 0.99 NF NF 3.12 21OUo 0.38
50 1.5 0.15 SEV 2OVo 50% 1.64 0.82 19170 0.34 2.69 190% 0.34
50 1.5 o.25 NE\ry 6% 28Vo 2.65 1.91 NF NF 4.62 s00% o.90
50 1.5 0.25 MOD l37o 4OVo 2.65 1.59 NF NF 3.9 455% 0.82
50 1.5 0.25 SEV 2O7o 5O7o 2.65 1.33 NF NF 3.37 31O"/" o.56
110 1.5 0 NEW 67o 28Vo 0.29 o.21 155"h 0.28 1.45 190To o.34
110 1.5 0 MOD l3Vo 4OVo 0.29 0.18 145Vo o.26 1.21 12OYo o.22
110 1.5 0 SEV ?-OVo 5OVo 0.29 0.15 1OO"/" 0.18 1.04 120% o.22
ll0 1.5 0.075 NEW 6Vo 28Vo 1.95 1.41 NF NF 2.84 42Ùo/o 0.75
ll0 1.5 0.o75 MOD l37o 4OVo 1.95 1-17 4OOUI 0.72 2.36 350% 0.63
110 1.5 0.075 SEV 20Vo 5O7o 1.95 0.98 38OYo 0.68 2.O4 2OOe/o 0.36
110 1.5 0.15 NE}V 67o 28Vo 3.62 2.60 NF NF 3.74 1000% 1.79
110 1.5 o.15 MOD l3Vo 4OVo 3.62 2.11 NF NF 3.12 550o/" o.99
ll0 1.5 0.15 SEV 2OVo 5OVo 3.62 1.81 600"h 1.08 2.69 45O7o 0.81
110 1.5 o.25 NE\ry 6Vo 28Vo 5.83 4.20 NF NF 4.62 NF NF
r10 't.5 0.25 MOD 137o 4OVo 5.83 3.50 NF NF 3.9 NF NF
110 1.5 o.25 SEV 2OVo 5OVo 5.83 2.92 NF NF 3.37 TOVo o.13
220 1.5 0 NEIW 6Vo 28Vo 0.59 o.42 31OYo 0.56 1.45 390% 0.70
220 1.5 0 MOD 13Vo 4OVo 0.59 0.35 290% o.52 1.21 260% 0.47
220 1.5 0 SEV 2OVo 50Vo 0.s9 0.29 ZOOYo 0.36 1.04 22O'/o 0.39
220 1.5 0.o75 NEW 6% 28% 3.91 2.81 NF NF 2.84 8OO"/" 1.43
220 1.5 0.075 MOD 13Vo 4OVo 3.91 2.35 1050% 1.88 2.36 650% 1.17
220 1.5 0.075 SEV 2O7o 5O4o 3.91 1.95 725Yo 1.30 2.O4 400% 0.72
220 't.5 o.15 NEW 6Vo 28Vo 7.23 5.21 NF NF 3.74 NF NF
220 1.5 0.15 MOD 13Vo 4OVo 7.23 4.34 NF NF 3.12 NF NF
220 't.5 o.15 7.23
SEV 2OVo 5OVo 3.62 NF NF 2.69 81OYo 1.45
220 'L5 o.25 NEW 11.66 8.40 NF 4.62
6Vo 28Vo NF NF NF
220 1.5 0.25 MOD 137o 4OVo 11.66 7.00 NF NF 3.9 NF NF
220 1.5 0.25 SEV 2O7o 5OVo 11.66 5.83 NF NF 3.37 NF NF

*NF
- No Fail within limits of study

209
CHAPTER (8) - Linearised Displncement-based Analysis

Table 8.4.5 Taft Analysis Comparison: 3.3m Height Wall

GEOMETRY OVER- WALL CONDITION RIGID SEMI THA DBA


(t) (h) BURDEN (refer Â(1) ae) BODY RIGID loEQ PGA f"n >FREQ >FREQ
(MPa) (Hz) PGA
(mm) (m) Figure A* A* G) G) G) VoßQ
6.4.12) k)
50 3.3 0 NEW 6% 28V" 0.ott 0.04 53Vo 0.10 o.96 SOYI 0.09
50 3.3 0 MOD 13% 40% 0.06 0.04 46"/" 0.08 0.81 SOYI 0.09
50 3.3 0 SEV 2O"/o 50% 0.06 0.03 41Yo 0.07 o.7 5O"/" 0.09
50 3.3 0.075 NEV/ 6"/o 24"/" 0.22 0.16 91"/o 0.16 1.46 95% 0.17
50 3.3 0.075 MOD 13"/" 4OYo 0.22 0.13 66% 0.'t2 1.23 95"/o 0.17
50 3.3 0.075 SEV 2O"/o 5Oo/" 0.22 0.11 SAYI 0.10 1.0ö 5OV" 0.09

50 3.3 0.'t5 NEV/ 6% 24"/o 0.37 0.27 91"h 0.16 1.42 95% 0.17
50 3.3 0.15 MOD 13"/o 40% 0.37 o.22 66% 0.12 1.54 95% 0.17
50 3.3 0.15 SEV 2O"/o 5OTo 0.37 0.19 TOYo 0.13 1.33 95"/" o.'17

50 3.3 0.25 NEVT 6% zAV" 0.58 0.42 115"/o o.21 2.22 ro0% 0.'t8
50 3.3 0.25 MOD 13% 40% 0.58 0.35 104?/" 0.19 1.87 95"/o 0.17
50 3.3 0.25 SEV 2O"/" 50% 0.58 0.29 88e/o 0.16 1,62 95"/" 0.17

110 3.3 0 NEW 6"/0 28Y" 0.13 0.10 1O2"/o 0.18 0.96 11Oo/o 0.20
110 3.3 0 MOD 13o/" 40% 0.13 0.08 95% 0.17 0:81 11OYo 0.20
ll0 3.3 0 SEV 2O"/o 50% 0.13 0.07 SOUo 0.16 1,00% 0.18

110 3.3 0.075 NEIW 6% 28"/o 0.48 0.34 17sVo 0.31 1.46 190% 0.34
110 3.3 o.o75 MOD 'l3o/" 40% 0.48 0.29 1750h 0.31 1.23 145Yo

110 3.3 0.075 SEV 20% 50% 0.48 o.24 11sYo 0.31 1.06 11OYo o.20

110 3.3 0.15 NEV/ 60/" 28% 0.82 0.59 21OYo 0.38 1.82 190% 0.34
110 3.3 0.15 MOD 13o/" 40% o.a2 0.49 21O"/o 0.38 1.54 190% 0.34
110 3.3 0.15 SEV 20% 50% 0.82 0.41 175"/o 0.31 1.33 190% 0.34

ll0 3.3 o.25 NEV/ 6o/o 28% 1.28 0.92 365% 0.65 2.22 1 907o 0.34
110 3.3 0.25 MOD 13% 4OVo 't.28 0.77 27sVo 0.49 1.At 190% 0.34
110 3.3 0.25 SEV 20o/" 50% 1.24 o.64 210% 0.38 1.02 190% 0.34

220 3.3 0 NEV/ 6"/o 28Y" o.27 o.19 20O/" 0.36 0.96 21OYo 0.38
220 3.3 0 MOD 13"h 4oo/o 0.27 0.16 189"h o.32 0.81 240% 0.43
220 3.3 0 SEV 2O"/o 50% 0.27 0.13 2OO"/o 0.36 o,t 200% 0.36
220 3.3 0.075 NEW 6o/" 28% o.95 0.69 325o/o 0.58 1.46 370"h 0.66
220 3.3 0.075 MOD 13" 40% 0.95 0.57 ßOU. 0.77 1.23 300% 0.54
220 3.3 0.075 SEV 2OVo SOVI 0.95 0.48 300% 0.54 l.06 230% 0.41

220 3.3 0.15 NEW 6o/" 28% 1.64 1.18 44OYe 0.79 1.42 390% 0.70
220 3.3 0.15 MOD 13"/" 40% 1.64 0.98 525o/o 0.94 1.54 390% 0.70
220 3.3 0.15 SEV 2O"/o 5O"/o 1.64 0.82 360% 0.65 1.33 210% 0.38

220 3.3 o.25 NEIù/ 6o/" 28"/" 2.55 1.84 73OYo 1.31 2.22 390% 0.70
220 3.3 0.25 MOD 13% 40% 2.55 1.53 6250/" 1.12 1.87 3907o 0.70
220 3.3 0.25 SEV 2O"/" 5Oo/" 2.55 1.28 41OYo o.74 1.62 390% 0.70

*NF
- No Fail within limits of study

2to
CHAPTER (8) - Linearised Displncement-bøsed Arnlysis

Table 8.4.6 Taft Analysis Comparison: 4.0m Height Wall

GEOMETRY OVER. WALLCONDITION RIGID SEMI THA DBA


(r) (h) BURDEN (refer BODY RIGID PGA >FREQ >FREQ
AG) ToEQ f.n
(mm) (MPa)
(m) Figure A^ ^Ql
A^ G) G) G) (Hz) ToEQ PGA
6.4.12) k)
50 4 0 NEW 6Vo 28Vo o.05 0.04 4ïo/o 0.07 o.88 50% 0.09
50 4 0 MOD I37o 4OVo 0.05 0.03 4270 0.08 o.74 SOY' 0.09
50 4 0 SEV 2OVo SOVo 0.05 0.03 58Uo 0.10 0:64 4g7o 0.07
50 4 0.075 NEW 67o 287o 0. t6 0.11 TOYo 0.13 1.2õ 60% 0.11
4 0.075 MOD l3Vo 40Vo 0.16 0.09 60% o.11 1.06 sOVò 0.09
50 4 0.075 SEV 2OVo 50Vo 0.16 0.o8 SAYI 0.10 0.92 50o/o 0.09
50 4 0.15 NEW 6Vo 28Vo 0.26 0.19 Ez"/o 0.15 1.55 9OYo 0.16
50 4 0.15 MOD l3Vo 4O7o o.26 0.16 73% o.t3 1.31 85Yo 0.15
50 4 0.15 SEV 2OVo 50Vo 0.26 0.13 6AUo o.12 f.13 5O"/o 0.09
50 4 0.25 NEW 6Vo 28Vo 0.40 0.29 86Uö 0.15 1.01 SOYo 0.09
50 4 0.25 MOD 13Vo 4OVo 0.40 o.24 9Oe/o 0.16 1.58 95o/" o.'17
50 4 0.25 SEV 2OVo 5OVo 0.40 o.20 76"/o 0.14 1.36 9OYo 0.16
110 4 0 NEW 6Vo 28Vo 0.11 0.08 100"h 0.18 O¡EE 11'gUo 0.20
110 4 o MOD l3Vo 4OVo o.11 0.07 f05% o.19 o.74 1O5e/o 0.19
110 4 0 SEV 2OVo 5OVo 0.11 0.06 lOge/o 0.18 O:64 80% 0.14
110 4 0.075 NEW 6Vo 28Vo 0.34 0.25 1il.O"/o 0.30 1.2e 11O7o o.20
110 4 0.075 MOD l3Vo 4OVo 0.34 o.21 lV5"/o 0.31 1.O6 11O7o 0.20
110 4 0.075 SEV 2O7o 5OVo 0.34 0.17 125o/o o.22 0.92 1,100h 0.20
ll0 4 0.15 NEW 6Vo 28Vo 0.58 0.42 17Oo/" o.30 1.55 1900h 0.34
110 4 0.15 MOD 13Vo 40Vo 0.58 0.35 185c/o 0.33 1.31 19070 0.34
110 4 o.15 SEV 2OVo 5OVo 0.58 0.29 145o/o o.26 1 .13 0.20
il0 4 o.25 NEW 6Vo 28Vo 0.89 0.64 23O/o o.41 1.01 1'1Oo/e 0.20
ll0 4 0.25 MOD l3Vo 4O7o 0.89 0.53 21OUo 0.38 1.58 19O'/o o.34
ll0 4 0.25 SEV 2OVo 5OVo o.89 o.44 185Yo 0.33 1.36 r90% 0.34
220 4 0 NEW 6Vo 28Vo o.22 0.16 2D5o/o 0.37 O;EE 22OYo 0.39
220 4 0 MOD 13Vo 4OVo o.22 0.13 lVSVo 0.31 o.74 21O7o 0.38
220 4 0 SEV 2OVo 5O7o 0.22 o.11 185% 0.33 0.64 15O'/o o.27
220 4 0.075 NEW 6Vo 287o 0.69 o.49 285e/o 0.51 1.26 25O'/o o.45
220 4 0.075 MOD 13Vo 40Vo 0.69 0.41 315"/" o.56 1.06 22OYo 0.39
220 4 0.075 SEV 2OVo 50Vo 0.69 0.34 25OYo 0.45 0.92 21Oo/" o.38
220 4 0.15 NEW 6Vo 28Vo 1.15 0.83 380% 0.68 f .55 3AO7o 0.68
220 4 0.15 MOD 13Vo 407o 1.15 0.69 385% 0.69 1.31 3SO"h 0.68
220 4 0.15 SEV 2OVo 5O7o 't. t5 0.58 300"h 0.54 1 .13 38096 o.68
220 4 0.25 NEW 6Vo 28Vo 1.78 1.24 47Dch 0.84 1.0t 6OO"/o 1.43
4 0.25 MOD 13Vo 4O7o 1.78 1.O7 550% o.99 1.58 3AOYI 0.68
220 4 0.25 SEV 2OVo 5OVo 1.78 0.89 365% 0.65 1.36 38O"/" 0.68

*NF
- No Fail within lirnits of study

2tr
CHAPTER (8) - Linearised Displacement-based Analysis

Table 8.4.7 Pacoima Dam Analysis Conrparison: l.5m Height Wall

GEOMETRY OVER- WALL CONDITION RIGID SEMI THÄ DBA


(t) (h) BURDEN (refer 4ú) ae) BODY RIGID VoßQ PGA Í.n
(Hz)
>FREQ >FREQ
(mm) (m) (MPa) Figure À." A* G) G) G) VoEQ PGA
6.4.12) (e)
50 1.5 0 NEW 6"/" 28o/" 0.13 0.10 43Yo 0.19 1.45 SgYo o.22
50 1.5 0 MOD 'l3Yo 4O"/o 0.13 o.08 33% 0.14 1.21 SOYo o.22
50 1.5 0 SEV 20% 50/. 0.13 0.07 48Yo o.21 1.04 35"/o 0.15
50 1.5 0.075 NEVT 6Vo 28o/" 0.89 0.64 118"h 0.51 2.4¿I 100% 0.43
50 1.5 0.075 MOD 13o/" 40% o.89 o.53 97% 0.42 2.36 7O7o 0.30
50 1.5 0.075 SEV 2Oo/" 50y. 0.89 0.44 67Uo o.29 2.O4 65"/c 0.28

50
'1.5 0.15 NEW 6"/o 28% 1.64 1.18 NF NF 3.74 25.O?/" 1.08

50 1.5 0.'t5 MOD 13% 40% 1.64 o.99 136% 0.59 3:12 140e/o 0.61

50 1.5 0.15 SEV 2Oo/" 50% 1.64 o.82 1sOYo 0.5tt 2.69 85"/" 0.37
't.5 2.65 't.91 NF 4.62 1.21
50 0.25 NEW 6% 28"/o NF zfJlJ7o
't.5 0.25 MOD 13% 2.65 1.59 NF NF 3:9 28OVo 1.21
50 4Oo/o

50 1.5 0.25 SEV 2O"/o 50o/o 2.65 1.33 163% 0.71 3.37 175'h 0.76
ll0 'L5 0 NEW 6"/" 28"/o 0.29 0.2'l 105% 0.46 1.45 115% 0.50
110 1.5 0 MOD 'lSYo 40% 0.29 o.18 I 057c 0.46 1.21 125Vo 0.54
110 '1.5 0 SEV 2Oo/" 50/" 0.29 0.15 7veh 0.30 1.04 75o/o 0.33
110 1.5 0.075 NEW 6"/o 28% 1.95 1.41 340"h 1.48 2.84 22O"/" 0.95
't.95 2.3õ 0.65
110 1.5 0.075 MOD 13"/o 4OVo 1.17 28O"/o 1.21

ll0 1.5 0.075 SEV 20% 50"/" 1.95 0.98 2154/o 0.93 2.O4 13OYo o.56

110 1.5 0.15 NEW 6% 28% 3.62 2.60 NF NF 3.74 NF NF

110 1.5 0.'t5 MOD 13"/" 4O"/o 3.62 2.17 460"/o 2.00 3.12 300% 1.30
110 1.5 o.15 SEV 20% 50"/ 3.62 1.81 430"/" 1.87 2.69 2OO"/o 0.87

110 1.5 o.25 NEW 6Y" 28% 5.83 4.20 NF NF 4,62 NF NF

110 1.5 0.25 MOD 13"/" 40o/o 5.83 3.50 NF NF 3.9 NF NF

ll0 1.5 o.25 SEV 20% 50% 5.83 2.92 NF NF 3.37 4OO7o 't.74

220 1.5 0 NEVT 6Yo 28% 0.59 o.42 325"/" 1.4',1 1.45 225"h 0.98
220 1.5 0 MOD 13% 4Ùo/o 0.59 0.35 225Yo 0.98 1.21 27s%o 1.19
't.5 0 50% 0.59 0.29 135% 0.59 1.O4 14O"/" 0.61
220 SEV 2O"/o
2.81 NF NF 2.44 425"/" 't.84
220 1.5 0.075 NEVT 6% 2A7o 3.91
220 1.5 0.075 MOD 13% 4Oo/o 3.91 2.35 500% 2.17 2.36 28OYo 1.21

220 1.5 0.075 SEV 2O"/o 50o/o 3.91 1.95 43O"/o 1.47 2.Ott 260% 1.13

220 1.5 0.15 NEW 6% 28"/o 7.23 5.2'l NF NF 3.74 NF NF

220 1.5 o.15 MOD 13% 40% 7.23 4.U NF NF 3.12 NF NF

220 1.5 0.15 SEV 2O"/o 500/" 7.23 3.62 600% 2.60 2.69 375"/" 1.63

220 1.5 0.25 NEW 6% 2fj"/o 11.66 8.40 NF NF 4.62 NF NF

220 1.5 o.25 MOD 13% 40% 11.66 7.OO NF NF 3.9 NF NF

220 1.5 0.25 SEV 2Oo/" 50% 11.66 5.83 NF NF 3.37 NF NF

*NF
- No Fail within limits of study

212
CHAPTER (8) - Lineørised Displacement-bøsed Analysis

Table E.4.8 Pacoirm Dam Analysis Conrparison: 3.3m Height Wall

GEOMETRY OVER- 1VALL CONDITION RIGID SEMI THA DBA


(t) ft) BURDEN (refer AG) BODY RIGID ToEQ PGA .f.n >FREQ >FREQ
(MPa)
(mm) (m) Figure 4* ^(2)
A^ G) G) G) (Hz) ToEQ PGA
6.4.12) k)
50 3.3 0 NEW 6Vo 28% 0.06 0.04 29"/o 0.13 o.96 35"/o 0.15
50 3.3 0 MOD 13o/o 4Oo/" 0.06 0.04 ¿ |"/c o.12 0.81 3Ùo/o 0.13
50 3.3 0 SEV 20% 50o/o 0.06 0.03 33Uo 0.14 o.7 SOUI 0.13
50 3.3 0.075 NEW 60/" 28"/" 0.22 0.16 4TYo 0.20 1.46 5O!/o 0.22
50 3.3 0.075 MOD 13% 4Oo/o o.22 0.13 36"/" o.16 1.23 50"/" o.22
50 3.3 o.075 SEV 2Oo/o 5O"/" o.22 0.11 33Yo 0.14 1¡06 35"h 0.15
50 3.3 0.15 NEW 6o/" zAVo 0.37 0.27 5BUo 0.25 1.82 6Ðolo 0.26
50 3.3 0.15 MOD 13% 40% 0.37 o.22 46"/o 0.20 1.54 55o/o 0.24
50 3.3 0.15 SEV 20% 5Oo/" o.37 0.19 49/" 0.21 1.33 50"/" o.22
50 3.3 o.25 NEW 6% 28% 0.58 0.42 ATUo 0.38 2.22 607o o.26
50 3.3 0.25 MOD 13% 40"/" 0.s8 0.35 63% o.27 1.87 6OVo 0.26
50 3.3 o.25 SEV 2oo/o SOVo 0.58 0.29 49"h 0.21 1.62 55"h o.24
110 3.3 0 NEW 6% 28% 0.13 0.10 6O."/o 0.35 0:96 7Oe/o 0.30
ll0 3.3 0 MOD 13Yo 4Oo/" 0.13 0.08 65% 0.28 o.81 TOYo 0.30
110 3.3 0 SEV 2Oo/" 5Oo/" 0.13 0.07 g7o o.22 o,7 70V" 0.30
ll0 3.3 o.075 NEV/ 6% 28o/" 0.48 0.34 Í05% 0.46 1.46 l:1Se./o 0.50
110 3.3 0.075 MOD 13o/" 40% 0.48 0.29 9.57o 0.41 1.23 1157o 0.50
ll0 3.3 0.075 SEV 20% 50% 0.48 o.24 75o/o 0.33 1:06 7Sc/o 0.33
110 3.3 0. t5 NEW 6% 28o/o 0.82 0.59 150% 0.69 1.42 135o/o 0.s9
110 3.3 0.15 MOD 13o/" 4oo/o 0.82 0.49 1zOYo 0.52 1.54 125Yo 0.54
ll0 3.3 0.15 SEV 2O"/o 5Oo/o 0.82 o.41 1OO7o 0.43 1.33 11iYo 0.50
110 3.3 0.25 NE}V 6% 28% 't.28 0.92 215o/o 0.93 2.22 135o/o 0.59
110 3.3 o.25 MOD 13% 4O"/o 1.28 o.77 ISOYo 0.78 1.87 f3O7o 0.56
ll0 3.3 o.25 SEV zOV" 50% 't.28 o.64 1sOUo 0.56 1.62 1sOYo 0.56
220 3.3 0 NEIù/ 6V" 284/o o.27 o.19 17O"/o 0.74 o.96 140c/c 0.61
220 3.3 0 MOD 13o/o 40o/o o.27 0.16 125o/o o.54 O:81 13Ùo/o o.56
220 3.3 0 SEV 20% 50% o.27 0.13 1OsYo 0.46 o.7 11sYo 0.50
220 3.3 0.075 NEW 6o/" zAV" 0.95 0.69 ZIOUo 0.91 1.46 220"h 0.95
220 3.3 0.075 MOD 13% 4Oo/" 0.95 0.57 2OOo/o 0.87 1.23 14Ùo/o 0.61
220 3.3 o.o75 sEv 20o/" 50"Â 0.95 0.48 15Ùo/o 0.65 1.06 150Y" 0.65
220 3.3 0.15 NEW 6o/o 28"/" 1.64 1. t8 325Yo 1.41 1.82 2607o 1.13
220 3.3 0.15 MOD 134/o 40o/o 1.64 o.98 29OUo 't.26 1.54 26OYo 1.13
220 3 o.15 SEV 2Oo/o SOVo 1.64 0.82 190U" o.82 1.33 26lJ7o 1.13
220 3.3 o.25 NEW 6/" zAVo 2.55 1.84 435?/o 1.89 2.22 275'/o 1.19
220 3.3 0.25 MOD 13"/" 4Oo/o 2.55 1.53 4257o 1.U 1.87 26OVo 1.13
220 3.3 0.25 SEV 2Oo/o 5O"/" 2.55 1.28 265% 1.15 1.62 26OYo 1.13

*NF
- No Fail wirhin limirs of study

213
CHAPTER (8) - Linearised Displacement-based AnøIysis

Table 8.4.9 Pacoinra Dam Analysis Conrparison: 4.0m Height Wall

GEOMETRY OVER- WALL CONDITION RIGID SEMI THA DBA


(t) (h) BURDEN (refer a(2) BODY RIGID ToEQ PGA f"n >FREQ >FREQ
(mm) (m) (MPa) Figure A^ 4^
^(1) G) G) G) (IIz) VoEQ PGA
6.4.12) (e)
50 4 0 NEW 6% 2a% o.05 0.04 36/" 0.16 0.88 SOYI 0.13
50 4 0 MOD 13o/" 40% 0.05 0.03 23"/o 0.10 o.74 zAYo o.12
50 4 0 SEV 2O"/o 50% 0.05 0.03 31% 0.13 0.64 28e/o 0.12
50 4 0.075 NEW 6"/0 28"/o o.1tt 0.11 40"/" 0.17 1.26 55Yo 0.24
50 4 o.075 MOD 13o/" 40% 0.16 0.09 32"/o 0.14 r.oõ 35"fo 0.1 5

50 4 0.075 SEV 2O"/" 50% 0.16 0.08 33"/" 0.14 0.92 3O"/o 0.13
50 4 0.15 NE\M 6"/o 28Y" o.2tt 0.19 53V" 0.23 1.55 55Yo o.24
50 4 o.15 MOD 13o/" 40% o.26 0.16 37Uo 0.1tt t.3t slJ"h 0.22
50 4 0.15 SEV 2O"/o s0% 0.26 0.13 47Vo 0.20 1.13 45Uo 0.20
50 4 0.25 NEVT 6"/" 28% o.40 0.29 60/" 0.26 t.0f 6O"/o 0.26
50 4 o.25 MOD 13"/" 40% 0.40 0.24 48Yo 0.21 1.58 55% 0.24
50 4 0.2s SEV 2O"/o 50% o.40 o.20 5O1" 0.22 1.36 50?/o 0.22
110 4 0 NEW 6% 28% o.11 0.08 70e/" 0.30 0.88 70% 0.30
110 4 0 MOD 13o/" 40% 0.11 0.07 50"h o.22 o.74 70% 0.30
110 4 0 SEV 2O"/o 50% 0.11 0.06 7Oe/o 0.30 0.64 7lJ"h 0.30
ll0 4 0.075 NEW 6o/o 28"/o 0.34 0.25 85"h 0.37 1.26 115"/o 0.50
110 4 0.075 MOD 13% 40% 0.34 o.21 lSYo 0.33 r.06 75% 0.33
110 4 0.075 SEV 2Oo/o 5O"/" 0.34 o.'t7 TQYo 0.30 0.92 TOYo 0.30
110 4 0.15 NEV/ 6Vo 28o/" 0.58 0.42 12O7o 0.52 1.55 125Yo 0.54
110 4 0.15 MOD 13"/" 40% o.58 o.35 99"/o 0.39 1.31 115"/o 0.50
110 4 0.15 SEV 2oo/o 5O"/o 0.58 0.29 80?/o 0.35 1 .13 100% 0.43
r10 4 0.25 NEW 6% 280/ 0.89 0.64 17sch 0.76 1.O1 130"/" 0.56
110 4 o.25 MOD 1sVo 4O"/" 0.89 0.53 130o/o 0.56 1.58 130% 0.56
110 4 o.25 SEV 20"/" 50% 0.89 o.44 105% o.4tt f .36 115% 0.50
220 4 0 NEW 60/" 28"/" o.22 0.16 135e/o 0.59 0.88 135e/o 0.59
220 4 0 MOD 13"/o 40% 0.22 0.13 125Vo 0.54 o.74 125Yo 0.54
220 4 0 SEV 2O"/o 50% o.22 0.11 13s% 0.s9 0.64 12O7o 0.52
220 4 0.075 NEIW 6Y" 2A% o.69 0.49 20O."/" 0.87 1.26 22OYo 0.95
220 4 0.075 MOD 13"/o 40% 0.69 0.41 155% 0.67 1.06 r50% 0.65
220 4 0.075 SEV 2O"/o 5O"/o o.ttg 0.34 135"/o 0.59 0.92 135% 0.59
220 4 0.15 NEV/ 6% 2A% 1.15 0.83 255"/" 1.'t 1 1.55 255% 1.11

220 4 0.15 MOD 13o/o 40o/o 1.15 0.69 225o/o 0.98 1.31 220"/" 0.95
220 4 0.15 SEV 2O"/o 5O"/o 1.15 0.58 165% 0.72 1.13 19OYo o.a2
1.18 345"/" 't.50 1.01 260% 1.13
220 4 o.25 NEW 6o/" 28"/" 1.24
4 o.25 MOD 13% 1.78 1.07 31Oo/o 't.34 1.58 260% 1.13
220 40o/o

220 4 0.25 SEV zOV" 50o/o 1.78 0.89 215V. 0.93 1.36 220"h 0.95

*NF No Fail within limits of study


-

2t4
CHAPTER (8) - Linearísed Displacement-based Analysis

Table 8.4.10 Nahanni Analysis Conrparison: l.Sm lleight Walt


GEOMETRY OVER. \ryALL CONDITION RIGID SEMI THA DBA
(r) (h) BURDEN (refer AG) AQ) BODY RIGID PGA
(MPa)
VoEQ l.n >FREQ >FREQ
(mm) (m) Figure 4^ 4^ G) G) G) (Hz) ToEQ PGA
6.4.12)
G)
50 1.5 o NEW 60/o 28Y" 0.13 0.10 24Ùe/o 0.55 1.45 400% 0.91
50 1.5 0 MOD 13"/õ 4OV" 0.13 0.08 41Oe/o 0.94 1.21 400?/o 0.91
50 1.5 0 SEV 2Oo/" S0o/o o.13 0.07 500% 1.14 1.04 400"h 0.91
50 1.5 0.075 NEW 6Yo 28T" 0.89 0.64 33O"/" 0.75 2.84 475"/o 1.09
1.5 0.075 MOD 13o/" 4Ùo/o 0.89 0.53 32OYo 0.73 236 420% 0.96
50 1.5 0.075 SEV 20% 50% 0.89 o.44 41och 0.94 2.W 41Oe/o 0.94
50 1.5 0.15 NEW 6% 28o/o 1.64 1.18 38OYo 0.87 3.74 6007o 1.37
50 1.5 0.15 MOD 13/' 4O"/" 1.64 0.99 360% o.a2 3.1,2 550e/" 1.26
50 1.5 0.15 SEV 20% 50% 1.64 o.82 3$OYo 0.78 2.69 420"h 0.96
50 1.5 o.25 NETW 6Y" 28o/" 2.65 1.91 4OO"/" 0.91 4:62 900% 2.06
50 1.5 0.25 MOD 13Vo 40% 2.65 1.59 NF NF 3.9 750eh 1.71
50 1.5 0.25 SEV 20% SOT' 2.65 1.33 NF NF 3.37 6007o 1.37
110 1.5 0 NEW 6a/o 28Yo o.29 o.21 55OYo 't.26 1.45 900% 2.06
't.5
110 0 MOD 13% 40e/o 0.29 0.18 900% 2.06 1.21 900% 2.06
110 1.5 0 SEV zOV" SOY" 0.29 o.15 1050% 2.40 1-04 900e/o 2.06
110 1.5 0.075 NEW 6% 28o/o 1.95 1.41 7íOVo 1.71 2.84 900% 2.06
't.5
110 o.075 MOD 13% 4Oo/" 1.95 1.17 9OO"/" 2.06 2.36 900% 2.06
ll0 1.5 0.075 SEV 2Oo/" 50% 1.95 0.98 7sOYo 1.7'l 2.O4 900% 2.06
ll0 1.5 0.f 5 NEW 6"/o 28% 3.62 2.60 NF NF 3.V4 1500% 3.43
't.5
110 0.15 MOD 13% 40Yo 3.62 2_'t7 950e/" 2.'t7 3.1.2 1200"/o 2.74
ll0 1.5 0.15 SEV 2O"/o s0% 3.62 1.81 E50% 1.94 2.69 lOOO7o 2.24
110 1.5 0.25 NEW 6Vo 28% 5.83 4.20 NF NF 4.62 NF NF
ll0 1.5 o.25 MOD 13% 4Oo/" 5.83 3.50 NF NF 3.9 16O0e/¿ 3.66
ll0 1.5 o.25 SEV 2Oo/" 50% s.83 2.92 NF NF 3.37 1300% 2.97
220 1.5 0 NEW 6% zAVo 0.59 o.42 11OO/" 2.51 1.45 l76Oo/" 4.02
220 1.5 0 MOD 13Vo 40% 0.s9 0.3s IAOOUo 4.'t 1 1.21 17öO7o 4.02
220 1.5 0 SEV 2Oo/" 5Oo/" 0.59 o.29 2200yo 5.03 r.04 176OUo 4.O2
220 1.5 0.075 NEW 6% 28o/" 3.91 2.81 14OOYI 3.20 2.Vt NF NF
220 1.5 0.075 MOD 13"/o 4oo/o 3.91 2.35 r3u¡% 2.97 2.36 1800% 4.11
220 1.5 0.075 SEV 20% 50% 3.91 't.95 1600% 3.66 2.O4 IAOOYI 4.11
220 1.5 0.15 NEW 6% 28% 7.23 5.21 NF NF 3.74 NF NF
220 1.5 0.15 MOD 13"/o 4OV" 7.23 4.U zOltOTo 4.57 3.12 NF NF
220 1.5 0.15 SEV 20% 50% 7.23 3.62 1700ch 3.88 2.69 19OOYI 4.34
220 1.5 0.25 NEW 6% 28% 11.66 8.40 NF NF 4.62 NF NF
220 1.5 o.25 MOD 13y" 4Ùo/o 1 1.66 7.00 NF NF 3.9 NF NF
220 1.5 0.25 SEV zOVo 50% 11.66 5.83 NF NF 3.37 NF NF

*NF
- No Fail within limits of study

215
CHAPTER (8) - Linearised Displacement-based Annlysis

Table E.4.11 Nahanni Analysis Conparison: 3.3m lleight \{all

GEOMETRY OYER- WALL CONDITION RIGII) SEMI THA DBA


(t) (h) BURDEN (refer A(Ð BODY RIGII) VoEQ PGA Í.n >FREQ >FREQ
(mm) (m) (MPa) Figure A^ ^3r
A* G) (e) G) (Hz) ToEQ PGA
6.4.12) G)
50 3.3 0 NEV/ 6o/o 28o/o 0.06 0.04 360% 0.82 0.96 4OO"/o 0.91
50 3.3 0 MOD 13"/o 4O"/o o.ott o.o4 500% 1.14 O;El 4OO7o 0.9'l
50 3.3 0 SEV 20% 50% 0.06 0.03 NF NF o.7 4OOYI 0.91
50 3.3 0.075 NEV/ 6Yo 28Yo o.22 0.16 360% 0.82 1.46 400"h 0.91
50 3.3 0.075 MOD 'l3Yo 40% o.22 0.13 42O/" 0.96 1.23 4OOe/" o.91
50 3.3 0.075 SEV 20% 50"/o o.22 0.11 44OYo 1.01 1.06 400?/o 0.91
50 3.3 0.15 NEW 6% 28T" 0.37 o.27 360% o.82 1.82 4OO"/o 0.91
50 3.3 0.15 MOD 131" 40% 0.37 0.22 340?/" 0.78 1.54 400% 0.91
50 3.3 0.15 SEV 2OVo 50% o.37 0.19 28o9h 0.64 1.33 4OOUo o.91
50 3.3 0.25 NEV/ 6Y" 28% 0.58 0.42 360% 0.82 2.22 41vch 0.94
50 3.3 0.25 MOD 13o/" 4Oo/" 0.58 0.35 NF NF 1.r 4OOo/o 0.91
50 3.3 0.25 SEV 20% 50% 0.58 0.29 360% 0.82 4OOe/o 0.91
110 3.3 0 NEW 6o/" 28% 0.13 0.10 1050e/o 2.40 t 900e/" 2.06
110 3.3 0 MOD 13"/o 4OYo 0.13 0.08 NF NF 90Oe/o 2.06
ll0 3.3 0 SEV 2O"/" 50% 0.13 0.07 NF NF o.7 900e/o 2.06
110 3.3 0.075 NEW 6% 28% 0.48 0.34 1O5OYI 2-40 1.¡ 9OO9/o 2.06
110 3.3 o.075 MOD 13% 40% 0.48 0.29 600% 1.37 2.06
110 3.3 0.075 SEV 2OV" 5O"/o o.48 o.24 ro00% 2.24 r.06 2.06
110 3.3 0.15 NEW 60/" 24" o.a2 0.59 1050% 2.40 9OOe/o 2.06
110 3.3 0.15 MOD 13% 40o/o 0.82 0.49 980% 2.24 1.54 900% 2.06
ll0 3.3 0.15 SEV 2O"/o 50% o.a2 o.41 1000% 2.28 Lr 9009/o 2.06
110 3.3 o.25 NEV/ 6Vo 24"/o 1.28 0.92 1050% 2.40 2.22 9OOe/" 2.06
110 3.3 0.25 MOD 13% 40% 1.28 0.77 75O"/o 1.71 1.87 900% 2.06
110 3.3 0.25 SEV 2O"/o 50"/" 1.28 0.64 1000% 2.28 1.1 2 2.06
220 3.3 0 NEW 6"/o 24"/o o.27 0.19 2O5O"/" 4.68 0.96 1.76070 4.O2
220 3.3 0 MOD '13"/o 40% o.27 0.16 2O5OVI 4.68 o.E1 1760% 4.02
220 3.3 0 SEV 2Oo/" 50% 0.27 0.13 NF NF o.7 176OUo 4.O2

2ZO 3.3 o.075 NEfW 6o/" 2Bo/" 0.95 0.69 2050% 4.68 L46 176OYo 4.O2
220 3.3 0.075 MOD 13% 40"/" o.95 o.57 1600e/o 3.66 1.23 176O0/" 4.O2
220 3.3 0.075 SEV 20% 50% 0.95 0.48 2OOO"/o 4.57 1.06 17607o 4-O2

220 3.3 0.15 NEV/ 6% 28"/o 1.64 1.18 2O5O"/o 4.68 1.82 1800% 4.11
220 3.3 0.15 MOD 13Vo 4O"/o 1.tt4 o.98 1800% 4.1'l f .54 1800% 4.'t1
220 3.3 0.15 SEV 2oo/o 50% 1.64 0.82 2000% 4.57 1.33 17607o 4.O2

220 3.3 0.25 NEW 6o/" 28% 2.55 1.84 2100% 4.80 2.22 1800% 4_11

220 3.3 o.25 MOD 13"/o 4O"/o 2.55 1.53 15007" 3.43 1.87 18000/" 4.'t1
220 3.3 0.25 SEV 20% 50% 2.55 1.28 2O5O"/o 4.68 1.62 1600% 4.',t1

*NF
- No Fail within limits of study

216
CHAPTER (8) - Linearised Displacement-based Annlysis

Table 8.4.12 Nahanni Analysis Comparison: 4.0m lleight rildl

GEOMETRY OVER. WALL CONDITION RIGID SEMI THA DBA


(t) (h) BURDEN (refer ag) BODY RIGID PGA >FREQ >FREQ
ToEQ f.n
(mm) (m) (MPa) Figure 4^ ^(2\
4^ G) G) G) (Hz) VoEQ PGA
6.4.12) G)
50 4 0 NEW 6% 28% 0.05 0.04 NF NF 0.88 4OOYI 0.91
50 4 0 MOD 13Y" 40% o.05 0.03 NF NF o.74 4OOYI 0.91
50 4 0 SEV zOVo 50% 0.05 0.03 24O'/o 0.55 0.il 4OO/o 0.91
50 4 0.075 NEW 6"/" 28% 0.16 0.11 3E096 o.87 1.26 4OO"/" 0.91
50 4 0.075 MOD 13% 4O/o 0.16 0.09 41OYo 0.94 1.06 4g0e/o 0.91
50 4 0.075 SEV 20% 50% 0.16 0.08 NF NF o92 4OOTI 0.91
50 4 0.15 NEV/ 60/o 28% o.26 0.19 SEO"/o 0.87 1.55 4OOYo 0.91
50 4 0.1s MOD 13o/" 4Oo/" 0.26 0.16 26O"/o 0.64 1.31 4OO"/o 0.91
50 4 0.15 SEV 20Io 50% o.26 0.13 420o/o o.96 1.13 4OOo/o 0.91
50 4 0.25 NEW 6"/o 28% 0.40 0.29 3E07ö o.87 1.01 4OOo/o 0.91
50 4 o.25 MOD 13Y" 40io 0.40 o.24 380o/o 0.87 1.58 4OO"/o 0.91
50 4 o.25 SEV 2Oo/" 5O"/" 0.40 0.20 3OOe/o 0.69 1.36 4OOo/o 0.91
ll0 4 0 NEV/ 6"/o 28"/o 0.11 0.08 fO5O7o 2.40 0.88 900% 2.06
110 4 0 MOD 13% 4Oo/" 0.11 o.o7 NF NF 0.74 900% 2.06
ll0 4 0 SEV 2Oo/" 5Oo/" 0.11 0.06 NF NF 0.õ4 900% 2.06
110 4 0.075 NEW 6/o zAVo 0.34 0.25 r050% 2.40 1.26 90O.e/o 2.06
ll0 4 0.075 MOD 13V" 40% 0.34 0.21 SOOYo 1.14 1.06 90070 2.06
110 4 0.075 SEV 20% 5Oo/" 0.34 o.17 1000e/o 2.28 o.g2 9POYo 2.06
ll0 4 0.'t5 NEIù/ 6o/o 28% o.58 o.42 1050e/o 2.40 r.55 90OYo 2.06
ll0 4 0.15 MOD 1sYo 40% 0.58 0.35 759'/o 1.71 1.31 9OO"/" 2.06
ll0 4 0. t5 SEV 2OYo 50% 0.58 o.29 55OYo 1.26 l.l3 900% 2.06
110 4 0.25 NEW 60/" 28% 0.89 o.64 1O5OYI 2.40 1.01 900% 2.06
ll0 4 0.25 MOD 13o/" 4OV" 0.89 0.53 11OOo/o 2.51 r.5E 90OYo 2.06
110 4 o.25 SEV 2OYo 50% 0.89 o.44 800% 1.83 1;36 900% 2.06
220 4 0 NEW 6% 28o/o 0.22 0. t6 NF NF 0.88 176OY" 4.O2
220 4 0 MOD 13% 4Oo/" Q.22 0.13 NF NF o.74 1760e/o 4.O2
220 4 0 SEV 2Oo/" 5Oo/" 0.22 0.11 NF NF 0.64 1760eh 4.O2
220 4 0.075 NErty 6"/o 28% 0.69 0.49 2000/" 4.57 1.26 176OYo 4.02
220 4 0.075 MOD 13o/o 40o/o 0.69 0.41 110070 2.51 r.0õ 17.6OU. 4.02
220 4 0.075 SEV 2Oo/" 50% 0.69 0.34 r950% 4.45 o.92 l76Ùyc 4.O2
220 4 0.15 NE\ry 6% 28o/" 1.15 0.83 2OOO/o 4.57 1.55 176o0/o 4.02
220 4 0.15 MOD 13% 4Oo/o 1.15 0.69 17OOYo 3.88 f .31 176lJ"h 4.O2
220 4 0.15 SEV 20% 50% 1.15 0.58 11OOo/c 2.51 1.13 176OYo 4.O2
220 4 o.25 NEW 60/" 28% 1-78 1.28 2OOOo/o 4.57 1.01 1800% 4.11
220 4 0.25 MOD 13% 4Oo/o 1.78 1.07 1600% 3.66 1.s8 176lJ"h 4.O2
220 4 o.25 SEV 2Qo/o 5Oo/" 1.78 0.89 1600% 3.66 1.36 176OYo 4.O2

*NF- No Fail within limits of study

217
9. SUMMARYAND CONCLUSIONS

This report has presented the findings of an investigation into the weak links in the
seismic load path of unreinforced masonry buildings specifically aimed at Australian
masoffy construction being:

(1) The limited force capacity of connections betvveen floors and walls, in particular the
friction dependent connections containing damp proof course (DPC) membranes and

(2) the out-of-plane failure of walls in the upper stories of URM buildings.

The two prime objectives of this investigation were thus to provide designers with the
appropriate tools to avoid these brittle 'weak link' failure modes in the design of new and

the assessment of existing URM buildings. Once adequate seismic load paths have been
developed and these 'weak links' successfully avoided it is expected that carefully
designed, detailed and constructed regular URM buildings will behave adequately during
moderate intensity earthquakes.

The first of the above objectives was fulfilled by an extensive series of shaking table tests
on URM connections containing DPC membrane typical found in Australian masonry
construction being aimed at providing data on the connections dynamic capacity
applicable (refer Chapter 4). The main purpose of these tests was therefore to evaluate
the connection performance under dynamic loading in order to assess their seismic
integrity. Dynamic friction coefficients determined from these tests were then compared
with quasi-static friction coefficients determined by previous research (Griffith et al
1998) to assess to what extent the quasi-statically determined friction coefficients
represented those which could be expected in seismic events. Here it was found that the

dynamic friction coefficients were not more than 20Vo less than those determined quasi-

218
CHAPTER (9) - Summary and Conclusions

statically. Further with the exception of greased galvanised sheets no connection had a
friction coefficient less than the 453700-1998 code prescribed design value of 0.3.
The second of the above objectives was achieved by the development of a simplistic
rational analysis procedure for face loaded simply supported IJRM walls for practical
applications which considers the essence of the true dynamic response behaviour. Since
the simplified procedure was required to be both user friendly and readily codified it was
developed from the increasingly popular linea¡ised 'Displacement-based' method.
Various boundary conditions for URM walls are often encountered which can
significantly impact on the \ryall's dynamic behaviour. The analysis procedure therefore
needed to have the ability of easily accounting for these conditions. Also, with poor
quality masonry, lack of maintenance and poor workmanship arising as major issues from
previous earthquake reconnaissance documentation, the analysis needed to have the
capability of allowing for rotation joint condition over the life of the wall. Both of these
requirements were taken into account by modifications to the modelled F-A relationship
(refer Chapter 8). The following paragraphs briefly describe the steps undertaken to
develop this procedure:

To gain a better understanding of the physical process governing the out-of-plane


behaviour of URM walls an extensive series of out-of-plane static and dynamic tests were
undertaken on one-way spanning wall panels as presented in Chapter 6. Test variables
included the level of overburden stress and wall aspect ratio, however, only one set of
boundary conditions was examined. Joint degradation was also examined as pa-rt of the
experimental phase.

A comprehensive THA program was then developed to accurately model the dynamic
wall behaviour, as presented in Chapter 7. Here the rocking wall was modelled as a single
degree of freedom (SDOÐ system having a non-linear spring and frequency dependent
damper. The relationships between the real and SDOF systems were determined by
comparison of the dynamic equations of motion. The modelled non-linear spring and
frequency dependent damper were then calibrated by comparison with experimentally

determined F-Â and /-Ç relationships. Results of the THA were then confirmed by

219
CHAPTER (9) - Summary and Conclusions

comparison with experimental results including free vibration tests, single pulse,

harmonic and transient excitation tests.


Following confirmation of the THA, results were used to undertake parametric studies to
further identify key properties of URM wall behaviour without the expense of continued
experimental testing. In total over two hundred thousand THA were completed as part of
this process.

The simplihed analysis procedure was based on the linearised 'Displacement-based'


procedure, used to predict the input excitation required to force the post-cracked URM
wall to incipient instability (refer Chapter 8). For the simplifred analysis, as most
realistic failures are associated with the large displacement amplifications associated with
resonance, the characteristic 'substitute structure' linear stiffness was related to the
effective resonant frequency of the simply supported wall to permit the wall's resonant
behaviour to be modelled. The effective resonant frequency was in turn related to the
average incremental secant stiffness of the failure half cycle. Damping was related to a
constant lowerbound observed during the experimental phase. As this method linearises
a highly non-linea¡ problem it has an inherent degree of inaccuracy for transient
excitations where a 'period lag' between the modelled linear SDOF oscillator and the real
system. Consequently, the suitability and accuracy of using the simplified method was
determined by comparison with THA and experimental results. Although, as expected
some result scatter was observed the correlation was substantially better than that of a

comparison with 'quasi-static' methods which are currently in use. Therefore, with the
provision of suitable safety factors it appears that the proposed linearised DB procedure
in conjunction with a 'quasi-statically' determined lowerbound force provides an
improved method for assessing the dynamic capacity for the design of new and the
assessment of existing URM buildings.

220
REFERENCES

ABK - A Joint Venture, "Methodology for the Mitigation of Seismic Hazards in Existing
Unreinforced Masonry Buildings: The Methodology", Topical Report 08, 1984
ABRAMS, D., DEMPSTER, 4., "Seismic Analysis of Masonry Buildings", Elsevier
Science Ltd., 1998, Paper reference T126-6
ABRAMS, D., P., " Effects of Scale and Loading Rate with tests of Concrete and
Masonry Structures", Earthquake Spectra, Journal of the Earthquake Engineering
Research Institute, Volume 12, No.l, 1996,pp.13-28.

ABRAMS, D., P., "A Lesson læarned From Loma Prieta on Vulnerability of URM
Construction East of the Rockies", Proceedings of the National earthquake Conference,
USA, 1993, pp. 143-151
ABRAMS, D., P., "Strength and Behaviour of Unreinforced Masonry Elements",
Proceedings of the 10th World Conference on Earthquake Engineering, Rotterdam, 1992,
pp.3475-3480.
ABRAMS, D., P., ANGEL, R., UZARSKI, J., "Out-of-Plane Strength of Unreinforced
Masonry Infill Panels", Earthquake Spectra, Vol. 12, No. 4, 1996, pp. 825-844
ABRAMS, D., P., PAVESE, 4., MAGENES, G., CALVI, G., M., "Large Scale Seismic
Testing of Unreinforced Brick Masonry Building", Proceedings of the 5th National
Conference on Earthquake Engineering, Vol. 1, 1994, pp.l37 -145
ABRAMS, D., P., TENA-COLUNGA, 4., "Seismic Behaviour of Structures with
Flexible Diaphragms", Journal of Structural Engineering, 1996, pp. 439 445.
ABRAMS, D., P., PAIJLSON, T., J.," Correlation between Static and Dynamic Response
of Model Masonry Structures", Earthquake Spectra, Journal of the Earthquake
Engineering Research Institute, Volume 6, No.3, 1990, pp.573-591
ABRAMS, P., D., "USA Masonry Today and Seismic Rehabilitation of Masonry
Buildings", Proceedings of the 4th Australasian Masonry Conference, Sydney, 1995,
pp.1-13
ADHAM, S., 4., "Static and Dynamic Out of Plane Response of Brick Masonry Walls",
Proceedings of the 7th International Brick Masonry Conference, Melbourne, 1985,
pp.1218-1224
ALCOCER, SERGIO, "June 1999 Mexico Earthquake", National Information Service for
Earthquake Engineering, University of California, Berkley,
http //www.eerc.berkley.edu/mexico/alcocer.htm, 1999
'Wall
ANDERSON, C., "Arching Action in Transverse Laterally l¡aded Masonry
Panels", The Structural Engineer, Vol. 628, No. 1, 1984, pp.12-23

221
REFERENCES

ANDERSON, C., "Transverse Laterally Loaded Tests on Single l,eaf and Cavity'Walls",
cIB 3'd International symposium on wâll structures, vol. l, w*ru*, 1984, pp. gz-tol
ANICIC, D., STEINMAN, v., "Tensile Strength of Masonry walls as a Factor of
Earthquake Resistance of Masonry Buildings", CIB 3"t International Symposium on Vy'all
Structures, YoL2,Warsaw, 1984, pp. 253-267
ANTHOINE,4., MAGONETTE, G., MAGENES, G., "shea¡-compression Testing and
Analysis of Brick Masonry Walls", Proceedings of the 10th European Conference on
Earthquake Engineering, Vol. 3, Rotterdam,1995, ppJ657 - 1662
Applied Technology Council "Tentative Provisions For The Development of Seismic
Regulations For Buildings", ACT 3-06
AS/NIZS 2904-1995, Damp-proof Courses and Flashings, Standards Australia, Sydney,
1995

ASTANEH-ASL, A., MODJTAHEDI, D., McMULLIN, K., SHEN, J., D'AMORE, E.,
"Stability of Damaged Steel Moment Frames in Los Angeles", Engineering Structures,
Vol.20, No 4-6, 1998, pp. 425432
ATC - Applied Technology Council 1988, ATC 3-3-06 "Tentative Provisions for the
Development of Seismic Provisions for Buildings", National Bureau of Standa¡ds,
Washington, DC
AUSTRALIAN GEOLOGICAL SURVEY ORGANISATION, Earthquake Information,
http ://www.bmr. pv.au/geohazards/quakes, 1999

BACHMANN, H., LINDE, P., WENK, T., "capacity Design and Nonrinear Dynamic
Analysis of Earthquake Resistant Structures", Proceedings of the lOth European
Conference on Earthquake Engineering, Vol. 1, Rotterdam, 1995, pp. lI
-20
BAKER, L., R., "Pre-cracking of Behaviour of Laterally Loaded Behaviour with In-Plane
Restraints", Proceedings of rhe British ceramic society, No.27, l97B,pp.r29-146
BAKER, L., R., "Structural Action of Brickwork Panels Subjected to Wind L,oads",
Journal of The Australian Ceramic Society, No. 1, Vol.9, 1973,pp.8-13
BAKER, L., R., "Variation in Flexural Strength of Brickwork With Beam and Span
L,oading", Journal of rhe Australian ceramic Society, }¡/.ay 1974, No. 2, vol.l0, pp.2g-
31

BARIOLA, J., GINoccHIo, J., F., QUINN, D., "out of Plane seismic Response of
Brick Walls", Proceedings of the 5th North American Masonry Conference, lgg},
pp.429-439
BASE, G., D., BAKER, L., R., "Fundamental Properties of structural Brickwork",
Journal of The Australian Ceramic Society, No. 1, Vol.9, 1973,pp.l-7
BEARD, R., DINNIE, 4., RICHARDS, R., "Movement of Brickwork", Transactions of
the British Ceramic Society, Vol. 68, No. 2, 1969, pp. 45-96
BEEBY, 4., W., CROOK, R., N., READ, J., 8., "Behaviour of Slender Concrete Block
Walls Under Vertical l-oads", CIB 3'd International Symposium on Wall Structures, Vol.
l, Warsaw, 1984, pp. 123-l3O

222
REFERENCES

BEER, F., P., JOHNSTON, E., R., "Mechanics for Engineers - Statics", McGraw Hill
Book Company, 1987
BELL, D., K., McNAUGHTON, H., DAVIDSON, 8., J., "Seismic Evaluation of an
Unreinforced Masonry Building", Proceedings of the 1998 Technical Seminar of the New
TnalandNational Society of Earthquake Engineering, t998, pp. 175-181
BENEDETTI, D, CARYDIS, P., PEZZOLI, P., I.ShaKing TAbIE TESTS ON 24 SiMPIC
Masonry Buildings", Earthquake Engineering and Structural Dynamics, Yol. 27, 1998,
pp.67-90
BENUSKA, K., L., " Loma Prieta Earthquake Reconnaissance Report", Earthquake
Spectra, Journal of the Earthquake Engineering Research Institute, Vol. 6, May 1990,
pp.l27-149.
BLAKIE, E., L., SPUR, D., D., "Earthquake Vulnerability of Existing Unreinforced
Masonry Buildings", EQC, Works Consultancy Services, Wellington, 1992
BLONG, R., J., "Domestic Insured l,osses and the Newcastle Earthquake", Proceedings
of the Australian Earthquake Engineering Society Conference, Sydney, Australia, 1992,
pp.70-83
BLONG, R., W., "Hazard Micronization of Melbourne", Proceedings of the Earthquake
Engineering and Disaster Reduction Seminar, Australian Earthquake Engineering
Society, Melbourne , 1993 , pp. 107 -ll7
BOLT, 8., 4., "Intraplate Seismicity and Zonation", Bulletin of the New 7'ealand
National Society for Earthquake Engineering, Yol.29, No.4, 1996, pp. 221-227
BOUSSABAH, L, BRUNEAU, M., "Review of the Seismic Performance of
Unreinforced Masonry Walls", Proceedings of the Tenth World Conference on
Earthquake Engineering, Madrid, Spain, 1992
BRITISH GEOLOGICAL GROUP (BGS), http ://www. gsrg.nmh.ac.uk, 1999
BROOKS, D., S., "strength and Stability of Brick Masonry'Walls", Research Report No.
R30, The University of Adelaide, Department of Civil and Environmental Engineering,
1980
BRUNEAU, M., "seismic Evaluation of Unreinforced Masonry Buildings - A State of
the Art Report", Canadian Journal of Civil Engineering, No. 21,1994,pp.512-539
BRUNEAU, M., "State-of+he-Art Report on Seismic Performance of Unreinforced
Masonry Buildings", American Society of Civil Engineers, Journal of Structural
Engineering, Vol. 120, No. 1,1994,pp.230-251
BRUNEAU, M., YOSHIMURA, K., "Damage to Masonry Buildings Caused by the 1995
Hyogo-ken (Kobe-Japan) Earthquake", Canadian Journal of Civil Engineerin g, Y ol. 23,
No.3, 1996,pp.797-807
BUBB, C., T., J., "Earthquake Engineering in Australia - Before Meckering and After
Newcastle", Bulletin of the New Zealand National Society for Earthquake Engineering,
Y ol. 32,No. 1, 1999, pp.l3-20

223
REFERENCES

BUBB, G., "Behaviour of structures - council Buildings", proceedings of the


Conference on the Newcastle Earthquake, Newcastle, Australia, t990,pp.26-27
BUCCINO, F., VITIELLO, E., "Experimental Behaviour and Design Criteria for
Anchorage Between Slabs and Brick 'Walls", Proceedings of the 10th European
Conference on Earthquake Engineering, Vol. 3, Rotterdam, 1995, pp. 2255 - 2260
CALVI, G., M., KINGSLEY, G., R., MAGENES, G., "Testing of Masonry structures for
Seismic Assessment", Earthquake Spectra, Volume 12, No.1, 1996.
CALVI, G., M., PAVESE, 4., "Application of Dynamic Identification Techniques to a
Brick Masonry Building Protot¡pe", Proceedings of the 10th European Conference on
Earthquake Engineering, Vol. 3, Rotterdam,1995, pp.2413 - 2418
CHOPRA, 4., K., "Dynamics of Structures - Theory and Applications to Earthquake
Engineering", Prentice-Hall, I995
CHRISTOPHSEN,4., "Magnitude and Catalogue Completeness Study'', Proceedings of
the 1999 Technical Seminar of the New Zealand National Society of Earthquake
Engineerin g, 1999, pp. 156-162
CLOUGH, R.,'W., GÜLKAN, P., MANOS, G., C., MAYES, R., L., "SEiSMiC TCStiNg Of
Single-Story Masonry Houses: Part 1", Journal of Structural Engineering, Vol. 116, No.
l, 1990, pp.235-256
cLouGH, R., W., GÜLKAN, p., MANOS, G., C., MAYES, R., L., .,Seismic Testing of
Single-Story Masonry Houses: Part 2", Journal of Structural Engineering, Vol. 116, No.
1,1990, pp.257-2274
cLouGH, R., w., PENZIAN, J., "D¡mamics of Structures", second Edition, McGraw-
Hill,Inc., 1993
coLE, w., LEV/IS, R., "A Note on the Moisture Expansion of unrestrained
Experimental Brick'Walls", Journal of the Australian Ceramic Society, November, No.3,
Vol.10, I974,pp.55
Concrete Masonry Association of Australia and South Australian Clay Brick Association
Incorporated, "A Guide to Masonry Construction", 1983
CORNELruSSEN, R., D., "Failure of Plastics", Hanser Publishers, 1986
CORTELL, R., "Numerical Analysis and Dynamic Problems with Negative Stiffness",
Computers and Structures, Vol.6l, No. 6,1996,pp. 1009-1011
CRANSTON, W., 8., ROBERTS, J., J., " The Structural Behaviour of Concrete Masonry
- Reinforced and Unreinforced", The Structural Engineer, No. I I, vol. 54,1976,pp.423-
436
CURTIN, W., G., SHAW, G., BECK, J., K., PARKINSON, G., I., "Masonry Fin Walls",
The Structural Engineer, Vol. 624, No. 7 , 1984, pp.203-2lO
CURTIN, W., G., SHAW, G., BECK, J., K., BRAY, W., 4., "structural Masonry
Designers Manual", Granada Publishing Limited, Great Britain, 1982

224
REFERENCES

DAVIDSON, 8., J., BRAMMER, D., R., "Cyclic Performance of Nominally Reinforced
Masonry 'Walls", Proceedings of the 1996 Technical Seminar of the New Zealand
National Society of Earthquake Engineering, New Plymouth, 1996, pp. t44-l5l
DE VEKEY, R., C., BRIGHT, N., J., LUCKIN, K., R., ARORA, S., K., "ThE RESiSTANCE
of Masonry to Lateral Inading - Research Results on Autoclaved Aerated Concrete
BlockworK', The Structural Engineer, Vol. 644, No. 11, 1986, pp. 332-340
DEANIN, R., D., "Polymer Structure, Properties and Applicationso', Cahners Publishing
Company,1972
DENHAM, D., "lntraplate Earthquakes rWhy?", Proceedings of the Australian
-
Eanhquake Engineering Society Conference, Sydney, Australia, 1992, pp. 3-6
DEPPE, K., "The Whittier Natrows, California Earthquake of October l, t987 -
Evaluation of Strengthened and Un-strengthened Unreinforced Masonry in Los Angelies
Citt'', Earthquake Spectra, Vol. 4, No. 1, 1988, pp. 157-180
DeVITIS, N., PAGE, A., 'W., LAIVRENCE, S., J., "Influence of Age on The
Development of Bond Strength", Proceedings of the 4th Australasian Masonry
Conference, Sydney, 1995, pp.299 -307
DHANASEKAR, M., "Effect of Central Queensland Sands on the Shear Capacity of
Concrete Masonry Containing Damp Proof Course", Proceedings of the 5ù Australasian
Masonry Conference, Gladstone, Queensland, 1 998, pp. 75-83
DHANASEKAR, M., PAGE, 4.,'W., KLEENMAN, P., 'W., "The Failure of Brick
Masonry Under Biaxial Stresses", Proceedings of The Institution of Civil Engineers, Part
2,1985, pp.295-313
DHANASEKAR, M., KLEENMAN, P., W., PAGE, 4.,W., "Biaxial Stress-Strain
Relationships for Brick Masonry'', American Society of Civil Engineers, Journal of
Structural Engineering, Vol.1 1 1, No.5, 1985, pp.1085-1 100
DOBBINS, J., J., "Problems of Chronology, Decoration, and Urban Design in the Forum
at Pompeii", Proceedings of the American Journal of Archeology, Vol. 98, No.4, 1994
'WILSON,
DOI{ERTY, K., LAM, N., GRIFFITH, M., J., "Investigation in the Weak
Links in the Seismic Load Path of Unreinforced Masonry Buildings", Proceedings of the
5th Australasian Masonry Conference, Gladstone, Queensland, 1998, pp.115-128
DOHERTY, K., LAM, N., GRIFTITH, M., WLSON, J., "The Modelling of Earthquake
Induced Collapse of Unreinforced Masonry'Walls Combining Force and Displacement
Principals", Pioceedings of the 12ù World Conference on Earthquake Engineering,
Auckland, New Zealand,2000, Paper 1645
DOHERTY, K., LAM, N., GRIFFITH, M., WILSON, J., "Modelling the Collapse
Behaviour of Unreinforced Masonry rWalls During the Newcastle Earthquake",
Proceedings of Australian Earthquake Engineering Society, Sydney, 1999
DONALDSON, R., J., "Behaviour of Structures - Patterns of Failure in Domestic
Buildings After the 1989 Newcastle Earthquake, Proceedings of the Conference on the
Newcastle Earthquake, Newcastle, Australia, 1990, pp.39 -43

225
REFERENCES

DOWRICK, D., J., RHOADES, D., A., "Magnitude of New z,ealandEarthquakes, l90l-
1993", Bulletin of the New Zealand National Society for Earthquake Engineering, Vol.
31, No.4, 1998, pp. 260-280
DRYSDALE, R., G., ESSAWY, 4., s., "out-of-Plane Bending of concrete Block
'Walls",
American Society of Civil Engineers, Journal of Structural Engineering, No. 1,
Vol. 114, 1988, pp.l2l-133
DRYSDALE, R., G., HAMID,4.,4., BAKER, L., R., "Masonry Structures - Behaviour
and Design", Prentice Hall,1994

EDWARDS, M., LAM, N., WIISON, J., HUTCHINSON, G., "The prediction of
Earthquake Induced Displacement Demand of Buildings in Australia : An Integrated
Approach", Proceedings of the 1999 Technical Semina¡ of the New Zealand National
Society of Earthquake Engineering, Rotorua, 1999, pp. 43 -50
ETTER, D., M., "Structured Fortran 77 -For Engineers and Scientists", Second Edition,
The Benjamin/Cummings Publishing Company, Inc., 1987
EWING, R., D., "Seismic Performance of [.ow Rise Concrete and Masonry Buildings",
Proceedings of the Workshop for the Seismic Performance of t ow Rise Buitdings, State-
of-the-art and Research Needs, Illinois, 1980, pp. 66-75
EWING, R., D., KARIOTIS, J., c., JOHNSON, 4., 'w'., "predictions of Stability for
Unreinforced Brick Masonry Walls Shaken By Earthquakes", Proceedings of the 7th
International Brick Masonry Conference, Melbourne, 1 985, pp. 1 1 75- 1 I 83.
EV/ING, R., D., KARIOTIS,I., C, JOHNSON, 4.,'W., "strength Determination and
Shear Failure Modes of Unreinforced Brick Masonry with L¡w Strength Mortar",
Proceedings of the 7th International Brick Masonry Conference, Melbourne, 1985,
pp.l327-1337
FAILLA, 4., La MENDOLA, L., PIRRorrA, 4., "Flexural cycric Behaviour of
Masonry Walls Subjected to Horizontal Forces", Proceedings of the 11ù Conference on
Earthquake Engineering, Balkema, Rotterdam, 1 998
FARDIS, M., N., "S.O.A. Lecture: læssons l-earnt in Past Earthquakes", Proceedings of
the 10th European Conference on Earthquake Engineering, Vol. 1, Rotterdam, 1995, pp.
779 -788
FATEMI, s., JAMES., c., "The [,ong Beach Earthquake of 1933", National Information
Service for Earthquake Engineering, University of California, Berkley,
http ://www.eerc.berkley.edu, 1999

GAD, E., DUFFIELD, C., "Investigation into Domestic Brick Veneer Structures When
Subjected to Lateral [-oading", Proceedings of the Australasian Structural Engineering
Conference, Sydney, 1994, pp. 67 3-67 8

GAMBAROTTA, L., LAGOMARSINO, s., "Damage Models for the Seismic Response
of Brick Masonry Shear Walls. Part I: The Mortar Joint Model and its Applications",
Earthquake Engineering and Structural Dynamics, Vol. 26, 1997, pp.423439

226
REFERENCES

GAMBAROTTA, L., LAGOMARSINO, S., "Damage Models for the Seismic Response
of Brick Masonry Shear Walls. Part II: The Continuum Model and its Applications",
Earthquake Engineering and Structural Dynamics, Vol. 26, 1997, pp.44l 462
GAMBAROTTA, L., LAGOMARSINO, S., MORBIDUCCI, R., "Brittle-Ductile
Response of In-plane Loaded Brick Masonry'!Y'alls", Proceedings of the 10th European
-
Conference on Earthquake Engineering, Vol. 3, Rotterdam, 1995, pp. 1663 1668
GERE, J., H., TIMONSHENCO, S., P., "Mechanics of Materials", PWS-Kent Publishing
Co., Boston, 1990
GHAZ/J-[ M.,2., RIDDINGTON, J., R., "Simple Test Method For Masonry Shear
Strength", Technical Note No. 505, Proceedings of The Institution of Civil Engineers
Part 2,Vo1.85, 1988, pp.567 -57 4
GIBSON, G., "An Introduction to Seismology", Proceedings of the Conference on the
Newcastle Earthquake, Newcastle, Australia, 1 990, pp.6-8
GLOGAU, O., 4., "Masonry Performance in Earthquakes", Bulletin of the New Zealand
National Society for Earthquake Engineering, Vol.7, No.4, 1974
GRAHAM, K., J., PAGE, 4., 'W., "Testing of Post-Tensioned Hollow Clay Masonry",
Proceedings of the 4th Australasian Masonry Conference, Sydney, 1995, pp.228-239
GRAPES, R., DOWNES, G., "The 1855 Vy'airarapa, New Zealand, Earthquake -
Analysis of Historical Data", Bulletin of the New Zealand National Society for
Earthquake Engineering, Vol. 30, No.4, 1997,pp.271-368
GRIFFITH, M., C., "Performance of Unreinforced Masonry Buildings During the
Newcastle Earthquake, Australia", Research Report No. R86, The University of
Adelaide, Department of Civil and Environmental Engineering,l99l
GRIFFpH, M., C., PAGE, A., W., "On the Seismic Capacity of Typical DPC and Slip
Joints in Unreinforced Masonry Buildings", Australian Journal of Structural Engineering,
Vol. SEl, No. 2,1998, pp.133-140
GUGGISBERG, R., THURLIMANN, 8., "Failure Criterion for Laterally Loaded
Masonry Walls", Proceedings of the 5th North American Masonry Conference, Urbana-
Champign, 1990, pp. 949-958
GUPTA, 4., K., "Response Spectrum Method in Seismic Analysis and Design of
Structures", B lackwell Scientific Publications, Boston Oxford, ISBN 0-8 6542- 1 1 5 -3
GURLEY, C., "Existing Structures Requirements and Repairs", Proceedings of the
-
Conference on the Newcastle Earthquake, Newcastle, Australia, 1990, pp.l07-113
HAMID, 4., DRYSDALE, R., G., "Flexural Tensile Strength of Concrete Block
Masonry", Journal of Structural Engineering, Vol. I 14, No. 1, 1988, pp. 50-66
HART, G., C., KARIOTIS, J., NOLAND, J.,L., "The Whittier Narrows, California
Earthquake of October 1, 1987 - Masonry Buildings Performance Survey'', Earthquake
Spectra, Vol.4, No. 1, 1988, pp. 181-195

227
REFERENCES

HASELTINE, 8., A., TUTT, J., N., "The Resistance of Masonry to Lateral Loading
-
Implications of Research on Design Implications", The Structural Engineer, Vol. 64A,
No. 11, 1986, pp. 341-350
HASELTINE,8.,4., WEST, H.,'w'., H., TUTT, J., N., " The Resistance of Brickwork to
Lateral Loading - Pa¡t 2 - Design of Walls to Resist Lateral L-oads", The Structural
Engineer, 1977, No. 10, Vol.55, pp. 422430
HENDRY, 4., W., "The Lateral Strength of Unreinforced Brickwork - Discussion",
Structural Engineer, No. 8, Volume 5l,lg73
HENDRY, 4., 'W., '"The Lateral Strength of Unreinforced Brickwork", Structural
Engineer, No. 2, Volume 5I,1973
HENDRY,4., W., "Structural Brickwork", The MacMillan press Ltd, lggl
HJELMSTAD, K., D., WILLIAMSON, E., 8., "D¡mamic stability of structural systems
subjected to Base Excitation", Engineering Structures, vol. 20, No. 4-6,lggg, pp. 425-
432,
HOGAN, S., J., "On the Dynamics of Rigid-Block Motion Under Harmonic Forcing",
Proceedings of the Royal Society of London, 1 989, pp. 44247 6
HOUSNER, G., W., "The Behaviour of ^425,
Inverted Pendulum Structures During
Earthquakes", Bulletin of the seismological society of America", vol. 53, No.2, 1963,
pp.403417
HUTCHINSON, G., WILSON, J., PHAM, L., BILLINGS, I., JURY, R., K[NG, A.,
"Developing a Common Australasian Earthquake L,oading Standard", Proceedings of the
Australasian Structural Engineering Conference, Sydney, 1994, pp. 853-857
IRISH, J., L., "Earthquake Damage Functions For Australian Houses and the Probable
Maximum Loss for an Insurance Portfolio", Proceedings of the Australian Earthquake
Engineering Society Conference, Sydney, Australia, 1992, pp. 6l -69
JAIN, S., K., MURTY, C., V., R., ARLECAR, J., SINHA, R., GOYAL, A., JAIN, C.,
"Some Observations on Engineering Aspects of the Jabalpur Earthquake of 22 May
1997 ", EERI S peci al Earthqu ake Report, http ://www.eeri. or g/Reconn/, I gg7

JAMES, C., I{ERNANDEZ,L., "Helena, Montana, 7935-, National Information Service


for Earthquake Engineering, university of california, Berkley,
http //www.eerc.berkle)¡.edu, 1999
JANKULOVSKI, E., PARSANEIAD, S., "Analytical Evaluation of In-Plane Resistance
of Unreinforced Masonry 'Walls", Proceedings of the 4th Australasian Masonry
Conference, Sydney, 1995, pp.65-70
JOHNSON, M., w., PIEREPIEKARZ, M., R., "seismic strengthening Methods for
Unreinforced CMU Partition and Infill Systems", Proceedings of the National Earthquake
Conference,1993
JONES, N., P., CROSS, W., B., "Floor and Wall Interaction in Unreinforced Masonry
Buildings", Proceedings of the National Earthquake Conference, vol. 1 l, lgg3, pp.2l5-
224.

228
REFERENCES

JORDAN, J.,'W., LUDLOW, J., N., TRUEMAN, E.,G., "The Newcastle Earthquake and
Heritage Structures", Proceedings of the 5ù National Conference on Engineering
Heritage, Perth, 1990
JUDI, H., DAVIDSON, 8., FENWICK, R., "A Comparison of Force and Displacement
Based Design", Proceedings of the 1998 Technical Seminar of the New Zealand National
Society of Earthquake Engineering, 1998, pp. 67 -7 4
KARIOTIS, J., C., EWING, R., D., JOHNSON, 4.,'W., ADHAM, S., 4., "MEthOdOIOgY
for Mitigation of Earthquake Hazards in Unreinforced Brick Masonry Buildings",
Proceedings of the 7th International Brick Masonry Conference, Melbourne, 1985,
pp.1339-1350
KAUTTO, J., PAGE, 4., W., "The Impact of The Earthquake Loading Code on Masonry
Housing", Proceedings of the 4th Australasian Masonry Conference, Sydney, 1995,
pp.160-170
KELLY, T., E., "Earthquake Resistance of Unreinforced Masonry Buildings",
Proceedings of New Zealand National Society for Earthquake Engineering, 1995, pp. 28-
35
KING, 4., "Earthquake Loads and Earthquake Resistant Design of Buildings",
Proceedings of the Australian Earthquake Engineering Conference, Perth, 1998
KLOPP, G., M., "seismic Design of Unreinforced Masonry Structures", Ph.D. Thesis,
Department of Civil and Environmental Engineering, The University of Adelaide,
Australia, 1996
KLOPP, G., M., GRIFtttH, M., C., "D¡mamic Characteristics of Existing Masonry
Buildings", Proceedings of the Pacific Conference on Earthquake Engineering, New
7.ealand, 199 1, pp1 87 -195.

KLOPP, G., M., GRIFFITH, M., C., "Earthquake Design Requirements for Unreinforced
Masonry Buildings in Australia - 2 Case Studies", Proceedings of the Australasian
Structural En gineerin g Conference, Sydney, 199 4, pp. 84 I -846
KLOPP, G., M., GRIffmH, M., C., "Seismic Analysis of Unreinforced Masonry
Buildings in Australia - 2 Case Studies", Australian Journal of Structural Engineering,
Vol. SEl, No.2, 1998,pp.lTl-131
KLOPP, G., M., Gruf'fftH, M., C., "Seismic Analysis of Unreinforced Masonry
Buildings", Australian Journal of Structural Engineering, VoL SEl, No. 2, 1998, pp.l2l-
131

KLOPP, G., M., GRIFFITH, M., C., "Shaking Table Tests of Unreinforced Masonry
Wall Panels", Australian Journal of Structural Engineering, Vol. SEl, No. 2,1998,pp.
1 l3-130

KLOPP, G.,M., GRIFFTTH, M., C., "The Design of Unreinforced Masonry Buildings for
Earthquake Induced Forces", Pacific Conference on Earthquake Engineering, Australia,
1995, pp.87-96

229
REFERENCES

KLOPP, G., M., GRIFFITH, M., c., "The Earthquake Design of unreinforced Masonry
Structures In Areas of Low Seismic Risk", Proceedings of the 3rd National Masonry
Seminar, Brisbane Australia, 7994, pp. 19.l -19.9
KLOPP, G., M., GRIFFTTH, M., c., "The Earthquake Design of unreinforced Masonry
Structures - Are Existing Period Formulae Suitable", Proceedings of the National
Earthquake Conference, 1993, pp. I 53 -162
KÖNIG, G., MANN, V/., ÖTES, A., "Experimental Investigations on the Behaviour of
Unreinforced Masonry Walls Under Seismically Induced t oads and læssons Derived",
Proceedings of the 9th World Conference on Earthquake Engineering, Tokyo-Kyoto,
1988, Vol.8, pp.1 1 l7 -1122
KOO, R., CT{ENG, M., LAM, N., WILSON, J., HUTCHINSON, G., GRIFFITH, M.,
"Modelling of the Earthquake Ground Motions Generated by the Newcastle Earthquake",
Proceedings of the 1999 Australian Earthquake Engineering Conference, Sydney, 1999
KRAV/INKLER, H, " Cyclic Loading Histories for Seismic Experimentation of
Structural Components", Earthquake Spectra, Journal of the Earthquake Engineering
Research Institute, Volume 12, No.l, 1996, pp.l-11
La MENDOLA, L., PAPIA, M., ZINGONE, G., "stability of Masonry \ilalls Subjected
to Seismic Transverse Forces", Journal of Structural Engineering, 1995, pp. l58l-15g7
LAFUENTE, M., GENATIOS, c., LORRAIN, M., "Anal5rtical studies of Masonry
Walls Subjected to Monotonic Lateral Loads", Proceedings of the 10th European
-
Conference on Earthquake Engineering, Vol. 3, Rotterdam, 1995, pp. 175l 1755
LAM, N., NURTUG, 4., wILsoN, J., "shaking Table Testing of parapet v/alls with
Periodic and Transient Excitations", Departmental of Civit and Environmental
Engineering, The University of Melbourne, Departmental Report No. RR/STRUCT/98,
1998

LAM, N., WILSON, J., "Eldmation of the Site Natural Period from a Borehole Record",
Australian Journal of Structural engineering, Vol. SEl, No. 3,1999,pp.179-200
LAM, N., WLSON, J., CHANDLER, 4., HUTCHISON, G., .,Response Spectrum
Modelling in Low and Moderate Seismicity Regions Combining Velocity, Displacement
and Acceleration Predictions", Earthquake Engineering and Structural Dynamics (under
review)
LAM, N., WILSON, J., EDWARDS, M., HUTCHISON, G., "A Displacement Based
Prediction of the Seismic Hazard for Australia", hoceedings of the 1998 Australian
Earthquake Engineering Conference, Perth, 1998, pp. 20.1-20.5
LAM, N., wILSoN, J., HUTCHINSON, G., "Building Ductility Demand: Interplate
Versus Intraplate Earthquakes", Earthquake Engineering and Structural Dynamics, Vol.
25,1996, pp. 965-985
LAM, N., wILSoN, J., HUTCHINSON, G., "Development of Intraplate Response
Spectra for Bedrock in Australia", Proceedings of the 1998 Technical Seminar of the
New Zealand National Society of Earthquake Engineering, 1998, pp. 137 -144

230
REFERENCES

LAM, N., WLSON, J., HUTCHINSON, G., "Modelling of an Unreinforced Masonry


Parapet Wall for Seismic Performance Evaluation Based on Dynamic Testing",
Departmental of Civil and Environmental Engineering, The University of Melbourne,
Departmental Report No. RR/STRUCT/03/95, 1995
LAM, N., WILSON, J., HUTCHINSON, G., "The Ductility Reduction Factor in the
Seismic Design of Buildings", Earthquake Engineering and Structural Dynamics, 27,
1998, pp. 749-769
LAM, N., WILSON, J., HUTCHINSON, G., "The Seismic Resistance of Unreinforced
Masonry Cantilever Walls in [,ow Seismicity Areas", Bulletin of The New Zealand
National Society of Earthquake Engineering, Vol. 28, no. 3,1995, pp. 79-195
LAM, N., WILSON, J., HUTCHINSON, G., "Time-History Analysis for Rocking of
Rigid Objects Subjected to Base Excitations", Proceedings of the 14th ACMSM, Hobart,
Vol. 1, 19958, pp.284-289
LAM, N., \VILSON, J., KOO, R., HUTCHINSON, G., "Determination of Earthquake
Response Spectra in Low and Moderate Seismicity Regions Using New Methodologies",
Proceedings of The Australian Earthquake Engineering Conference, Newcastle,
Australia, 1999
LAV/RENCE, S., J "Masonry codes and Regulations - Past, Present and Future",
Proceedings of the 5
rh
Australasian Masonry Conference, Gladstone, Queensland, 1 998,
pp.219-225
LAWRENCE, S., J., "The New 453700 Approach to Lateral Load", Proceedings of the
5ù Australasian Masonry Conference, Gladstone, Queensland, 1998, pp.227-237
LAV/RENCE, S., J., "Flexural Strength of Brickwork Normal to and Parallel to The Bed
Joints", Journal of The Australian Ceramic Society, No. 1, Vol. 1 l,1975, pp. 5-6
LAWRENCE, S., J., "Lateral Loading of Masonry - An Overview", Proceedings to the
2nd National Masonry Seminar, Brisbane Australia, 1994, pp.20.l -20.9
LAWRENCE, S., J., "Out of Plane Lateral Load Resistance of Clay Brick Panels",
Proceedings of the Australasian Structural Engineering Conference, Sydney, 1994, pp.
657 -663

LAWRENCE, S., J., PAGE, 4., W., "Mortar Bond - A Major Research Program",
Proceedings of the 4th Australasian Masonry Conference, Sydney,1995,pp.3l-37
LEEDS, D., "Report on Conference on 1971 San Fernando, Ca., Earthquake", American
Society of Civil Engineers, Civil Engineering, Environmental Design and Engineered
Construction, 197 2, pp. 58-60
LZUNDIA, 8., DONG, W., H., W., REITI{ERMAN, R., "LIRM Building Damage
Patterns in the l¡ma Prieta Earthquake: Implications for Improvements in l¡ss
Estimation Methodologies", Proceedings of the 5ù National Conference on Earthquake
Engineerin g, 199 4, pp.459468
LIZUNDIA, 8., HOLMES, W., T., "Development of Procedures to Enhance the
Performance of Rehabilitated URM Buildings: A Summary", Proceedings of the 6ù US
National Conference on Earthquake Engineering

231
REFERENCES

LOKE, J., Y., o., "Behaviour of Structures - Institutionar', proceedings of the


conference on the Newcastle Earthquake, Newcastle, Australia, r990, pp-28-32
LOLJRENCO, P., 8., "Computational Strategies for Masonry Structures", Ph.D. Thesis,
The Civil Engineering Department, Delft University of Technology, The Netherlands,
1996
LovEGRovE, R., "A Discussion of 'Yieldlines' in unreinforced Masonry", The
Structural Engineer, Vol. 66, No.22, 1988, pp. 371-375
MAGENES, G., cALvI, G., M., "cyclic Behaviour of Brick Masonry walls",
Proceedings of the 1Oth World Conference on Earthquake Engineering, Rotterdam, 1992,
pp.35t7-3522
MAGENES, G., cALvI, G., M., "In-plane seismic Response of Brick Masonry'walls",
Earthquake Engineering and structural Dynamics, vol. 26, 1997,pp. 109r-1 I 12
MAGENES, G., CALVI, G., M., "shaking Table Tests on Brick Masonry'walls",
Proceedings of the 10th European Conference on Earthquake Engineering, Vol. 3,
Rotterdam, 1995, pp. 2419 -2424
MAKRIS, N., Roussos, Y., "Rocking Response and overturning of Equipment under
Horizontal Pulse Type Motions", Pacific Earthquake Research Center, Berkley,
University of California, PEER-98/05
MANFREDT, G., MAZZOLANI, s., MASI, 4., "Review of Existing in Experimental
Testing of Masonry Structures Subjected to Horizontal Loads", Proceedings of the lOth
\vorld conference on Earthquake Engineerin g, Rotterdam, 1992, pp. 3 5 57 -j562
MARTINI, K., "Finite Element Studies in the Two-way Out of Plane Failure of
Un¡einforced Masonry", Proceedings of the 6ù US National Conference on Earthquake
Engineering
MARTIM, K., "Research in the Out-of-Plane Behaviour of Unreinforced Masonry",
Vir a.EI) 1997
MARTIM, K., "Finite Element Studies in the Out-of-Plane Failure of Unreinforced
Masonry", Proceedings on the International Conference on Computing in Civil and
Building Engineering, Vol. I, Korea, 1997
MARZAHN, G., "Dry-stacked Masonry in Comparison with Morta¡ Jointed Masomy",
I-eipng Annual Civil Engineering Report, No. 2, 1997,pp.353-365
MARZAHN, G., "shear Strength of Grout Dowelled Mason4y'', I-eipng Annual civil
Engineering Report, No. 2, 1997,pp.335-351
McCUE, K., "Seismicity and Earthquake Hazard in Australia", Proceedings of the
Earthquake Engineering and Disaster Reduction Seminar, Australian Earthquake
Engineering Society, Melbourne, 1993, pp. 9 -14
McCUE, K., "Seismological Aspects of the Newcastle NSV/ Earthquake of 28 December
1989", Proceedings of the Conference on the Newcastle Earthquake, Newcastle,
Australia, 1990, pp.9-13.

232
REFERENCES

McGINLEY, W'., M., BORCHELT, J., G., "Friction at the Supports of Clay Brick
Walls", Proceedings of the 5th North American Masonry Conference, 1990, pp.1053-
1066
McGINLEY, 'W., M., BORCIIELT, J., G., "Influence of Materials on the Friction
Developed at the Base of Clay Brick Walls", Proceedings of the 9th IBMAC, Berlin,
1991, pp. 292-3OO
MELCHERS, R., E., (Ed) "Newcastle Earthquake Study", The Institution of Engineers,
Australia, 1990
MELCHERS, R., E., "On Intra-plate Earthquakes and Existing Buildings", Transactions
of the Institution of Engineers, Civil Engineering, Vol. C836, No.4, 1994,pp.265-271
MELCHERS, R., MORISON, D., "Structural Response to Typical Intra-Plate Ground
Shaking", Research Report No. 107.02.1995, The University of Newcastle, 1995
MERCER, J., CROSS, W., "Simple, I¡w-Cost Retrofit Procedures for Historic
Unreinforced Masonry Buildings", Elsevier Science Ltd, 1998, Paper reference T126-5
..The Whittier NarrOwS,
MOORE, T., 4., KOBæTP, J., H., DIRI, J., ARNOLD, C.,
California Earthquake of October 1, 1987 - Prelimina¡yEvaluation of the Performance of
Strengthened Unreinforced Masonry Buildings", Earthquake Spectra, Vol. 4, No. 1,
1988, pp.197-215
MULLINS, P., J., O'CONNER, C., "{Jnreinforced Brick Shear'Walls", hoceedings of
the 4th Australasian Masonry Conference, Sydney, 1995, pp.7l-80
MUQTARIR, M., "slenderness Effects in Eccentrically Loaded Plain Masonry'Walls",
Proceedings of the 5th North American Masonry Conference, Urbana-Champign, 1990,
pp.1007-1015.
MURPHY, S., 4., STEWART, M., G., "Analysis of Public Buildings Damaged in the
1989 Newcastle Earthquake", Australian Civil Engineering Transactions, Vol. CE35, No.
3,1993, pp.187-201
NAWAR, G., ZOURTOS, K., "Planning and Control of Site Quality with Reference to
Special Masonry", Proceedings of the 3rd National Masonry Seminar, Brisbane
Australia, L994, pp.1 .l-7 .11.
NEHRP, "Recommended Provisions for the Development of Seismic Regulations for
New Buildings - Part 1 Provisions", National Hazards Reduction Program, Federal
Emergency Management Agency, Washington, DC, 1991
NEHRP, "Recommended Provisions for the Development of Seismic Regulations for
New Buildings - Pat 2 Commentary'', National Haza¡ds Reduction Program, Federal
Emergency Management Agency, Washington, DC, 1991
NICHOLS, J., M., TOTOEV, Y., Z., "Background to a Study of Damage Mechanics in
Masonry Panels Subjected to Cyclic [,oading", Proceedings of the 5ù Australasian
Masonry Conference, Gladstone, Queensland, 1 998, pp. 283 -292

233
REFERENCES

NURTUG, 4., DOHERTY, K., GRIFFITH, M., LAM, N., WILSON, J., ,,Research into
the Seismic Performance of Un¡einforced Masonry Walls", Proceedings of the Australian
Earthquake Engineering Conference, Brisbane, Australia,1997,p. l5-l - 154
OH, K., HARRIS, G., "Seismic Behaviour of Floor to 'Wall Horizontal Joints of Masonry
Buildings using 1/3 Scale Direct Models", Proceedings of the 5ù North American
Masonry Conference, Tllinois, 1990, pp. 8l-92
PAGE, A., W., "A Note on the Shear Capacity of Membrane Type Damp Proof Courses",
Research Report No. 097.05.1994,The University of Newcastle, 1992
PAGE, 4., W., "Behaviour of Structures - Patterns of Failure", Proceedings of the
conference on the Newcastle Earthquake, Newcastle, Australia, r990,pp.39-43
PAGE, A., W., "The Design, Detailing and Construction of Masonry - The læssons From
the Newcastle Earthquake", Research Report No. 073.03.1992, The University of
Newcastle, 1992
PAGE, 4., w., "The Design, Detailing and construction of Masonry The læssons
-
From the Newcastle Earthquake", Australian Civil Engineering Transactions, Vol. C834,
No.4, 1992,pp.343-353
PAGE, 4., \ry., "The New Australian Standard for Masonry Structures (A53700-1998)",
Proceedings of the 5ù Australasian Masonry Conferen"", bludrtone, Queensland, 1998,
pp.303-308
PAGE, 4., W., "Un¡einforced Masonry Structures - An Australian Overview",
Proceedings of the Pacific Conference on Earthquake Engineering, Australia, 1995, pp.
1-16.
PAGE, 4., W., KLEEMAN, P., 'W., STEWART, M., G., MELCI{ERS., R., 8.,
"Structural Aspects of the Newcastle Earthquake", The lnstitution of Engineers Australia
St¡uctural Engineering Conference, Adelaide, 1990, pp. 305-312
PAGE, 4., w., LAWRENCE, s., J., "An Integrated study of Masonry Bond Strength",
Proceedings of the 5ù Australasian Masonry Conference, Gladstone, Queensland, 1-998,
pp.309-317
PAGE, 4., 'w., "codes overview - connectors and Accessories For Masonry
Construction - Strengthening of Existing Buildings For Earthquakes", Proceedings of the
4th Australasian Masonry Conference, Sydney, 1995, pp.97-I02
PAGE, 4., w., "The shear capacity of Membrane Type Damp-proof courses in
Masonry'', Transactions of the Institution of Engineers, Civil Engineering, 1995, Vol.
C837, No.1, pp.29-39
PAGE, 4., w., GRIFFITH, M., c., "seismic Design of connections in unreinforced
Masonry Buildings', Proceedings of the 1998 Structural Engineers World Conference,
San Francisco, CA, USA, 1998
PAGE, 4., w., KLEENMAN, P., BRYANT, I., "The Effect of Foundation Hogging and
Sagging on Masonry Walls", Proceedings of the Australasian Structural Engineering
Conference, Sydney, 1994, pp. 665-67 I

234
REFERENCES

PAGE, A., W., LAV/RENCE, S., "Design of Clay Masonry for V/ind and Earthquake",
clay Brick and Paver Instifute, 1999,ISBN 0947160 03 5
PARSANEJAD, S., JANKLJLOVSKI, E., "Hysteresis Behaviour of Plain Brick Masonry
Walls: An Experimental Investigation", Proceedings of the Australasian Structural
Engineering Conference, Sydney, 1994, pp.679-683.
PAULAY, T., "Simplicity and Confidence in Seismic
Design", Proceedings of the
Australian Earthquake Engineering Society Conference, Brisbane, Australia, 1997, pp. 1-
| - t-12
PAULAY, T., PRIESTLY, M., J., N., "Seismic Design of Reinforced Concrete and
Masonry Buildings", J. Wiley, 1992
PEDERSEN, I., "Behaviour of Structures - Major Commercial Buildings", Proceedings
of the Conference on the Newcastle Earthquake, Newcastle, Australia, 1990,pp.21-25
PHAM, L., GRIFFITH, M., C., "Review of Building Performance in
Recent
Earthquakes", Proceedings of the 4th Australasian Masonry Conference, Sydney, 1995,
pp.14-20
PHAM, L., LI, C., Q., "Domestic Construction and Serviceability'', Proceedings of the
Australasian Structural Engineerin g Conference, Sydney, 199 4, pp. 847 -85 1
PHIPPS, M., "Diaphragm and Other Walls of Geometric Cross Section in the UK",
Proceedings to the 2nd National Masonry Seminar, Brisbane Australia, 1994, pp.24.1-
24.r0.
PHIPPS, M., E., "The Design of Slender Masonry Walls and Columns of Geometric
Cross-section to Carry Vertical Load", The Structural Engineer, Vol. 65A, No. 12,1987,
pp.443447
PHIPPS, M., E., PAGE, A., W., "Developments in Masonry Part 1 -'Walls of Geometric
Cross-Section", Australian Civil Engineering Transactions, Vol. CE37 .(2),1995, 159-165
PHIPPS, M., E., PAGE, 4., W., "Developments in Masonry Pafi 2 - Reinforced and
Prestressed Walling", Australian Civil Engineering Transactions, Vol. C837. (2), 1995,
167-174
POMONIS,4., SPENCE, R., J., S., COBURN,4., \V., "Shaking Table Tests on Strong
Motion Damageness Upon Reinforced Masonry", Proceedings of the 10th World
Conference on Earthquake Engineering, VoL 6, Rotterdam, 1992, pp. 3533-3538
POTTER, R, J, "Earthquake and Masonry - An Overview", Proceedings of the 3rd
National Masonry Semina¡, Brisbane Australia, 1 994, pp. 1 5. I -l 5. I 1 .
POULOS, H., G., "Relationship Between l¡cal Soil Conditions and Structural Damage
in the 1989 Newcastle Earthquake", Australian Civil Engineering Transactions, Vol.
C833, No. 3, 1991, pp.l81-188
PRIESTLEY, J., N., "seismic Behaviour of Unreinforced Masonry Walls", Bulletin of
the New Tnaland National Society for Earthquake Engineering, Vol. 18, No.2, 1985,
pp.191-205.

235
REFERENCES

PRIESTLEY, J., N., ROBINSON, L., M., "Discussion - seismic Behaviour of


Un¡einforced Masonry 'Walls", Bulletin of the New Zæaland National Society for
Earthquake Engineering, Vol. 19, No. 1, March 1986, pp.65-75.
PRIESTLY, M., J., N., CALVI, G., M., "concepts and procedures for Direct
Displacement-Based Design and Assessment", Workshop on Seismic Design Approaches
for the 21'r Century, Slovenia,lgg7
PRIESTLY, N., J., "Displacement-Based Seismic Assessment of Existing Reinforced
Concrete Buildings", Bulletin of the New Zealand National Society for Earthquake
Engineering, Vol.. 29, No.4, 1996,pp.256-271
PUJOL, S., RAMIREZ, J., SARRIA, 4., "Coffee Znne, Columbia, January 25
Earthquake, Observations on the Behaviour of L,ow Rise Reinforced Concrete
Buildings", http://www.eeri.org/Reconn/, 1999
RAJAKARUNA, M., P., "Effect of a Damp Proof Course on The Shear Strength of
Masonry", Proceedings of the 15th Australasian Conference on The Mechanics of
Structures and Materials, Melbourne, Victoria, Australia, lg97,pp. 633-637
RAMIREZ, J., PUGLESI, R., "The october 9, 1995 Magnitude 7 .6 Manzanillo, Mexico
Earthquake", EERI Special Earthquake Report, http://www.eeri.org/Reconn/,lg95
RANGAN, B., v., WARNER, R., F., "Large concrete Buildings", concrete Design and
Construction Series, Longman Group Limited, 1996
REITHERMAN, R., "The Borah Peak, Idaho Earthquake of october zg, lgg3 -
Performance of Unreinforced Masonry Buildings in Mackay,Idaho", Earthquake Spectra,
Yol.2, No. 1, 1985, pp. 205-224
Report by the Masonry Standards Joint Committee on Building Code Requirements for
Masonry Structures (ACI 530-92/ASCE 5-92ÆMS 402-92), Specification for Masonry
Süuctures (ACI 530.1-92|ASCE 6-92|TMS 602-92), Commentary on Building Code
Requirements for Masonry Structures (ACI 530-92/ASCE 5-92|TMS 402-92) and
Commentary on Specifications for Masonry Structures (ACI 530.1-921ASCE 6-92|TMS
602-92),USA, 1gg2
RIDDINGTON, J., R., ruKEs, P., "A Masonry Joint shear strength rest Method",
Proceedings of the Institution of Civil Engineers, 104,1994,pp.267-274
RIDDINGTON, J., R., GHAZALI, M, 2., "Hypothesis for shear Failure in Masonry
civil Engineers, part2,l990, pp.89-102
Joints", Proceedings of rhe Institution of
RODOLICO, 8., DOI{ERTY, K., LAM, N., GRTFFITH, M., WILSON, J., "SEiSMiC
Response Behaviour of Unreinforced Masonry Slender \ilalls Revealed By Shaking
Table Testings and Time-History Analyses", Proceedings of the 16ù Ausgalasian
Conference on Mechanics of Structures and Materials, Sydney,lggg
RoMANo, F., GANDUSCIO, s., zNGoNE, G., "Analysis of Masonry walls Subject
to Cyclic L-oads", Proceedings of the 10th European Conference on Earthquake
Engineering, Vol. 3, Rotterdam, 1995, pp. 1675 - 1680
ROSATO, Donald, V., MATTIA, D., P., ROSATO, Dominick, V., ..Designing with
Composites and Plastics: A Handbook", Van Nostrand Reinhold, l99l

236
REFERENCES

SAA Earthquake Loading Code, AS2l21, Standards Association of Australia, Sydney,


1979
SAA Loading Code, Minimum Design Loads on Structures - Part 4 - Earthquake [¡ads,
4S1170.4 - 1993, Standa¡ds Australia, Sydney 1993
SAA Masonry Code 453700-1988, Standa¡ds Australia, Sydney 1988
SAA Masonry Code 453700-1998, Standa¡ds Australia, Sydney 1998
SAA Masonry Code Commentary, 453700 Supplement l, Standards Australia, Sydney,
t99l
SAA Strengthening Existing Buildings for Earthquake, 453626 - 1998, Standards
Australia, Sydney 1998
SAMARASINGHE, W., LAWRENCE, S., J., PAGE,4., W., "Investigations of the Bond
'Wrench Method of Testing masonry", Proceedings of the 15th Australasian Conference
on The Mechanics of Structures and Materials, Melbourne, Victoria, Australia, 1997,
pp.651-656
SAÀ4AIù\SINGHE, W., LAWRENCE, S., J., PAGE,4.,'W., "Standardising the Bond
'Wrench", Proceedings of the 5th Australasian Masonry Conference, Gladstone,
Queensland, 1998, pp. 335-344
4., 'W., FIENDRY, 4., 'W., "Behaviour of Brick
SAÀ4AIL{SINGHE, W., PAGE,
Masonry Shear'Walls", The Structural Engineer, Vol. 59B, No. 3, 1981, pp. 4348
SCHWARTZ, J.,THURLIMANN, 8., "Design of Masonry'Walls Under Normal Force
with Swiss STD.SIA Y 17712", Proceedings of the 5th North American Masonry
Conference, Urbana-Champign, I 990, pp.959 -969
SCRIVENER, J., C., "Masonry Structures - Earthquake Resistant Design and
Construction", Proceedings of the Earthquake Engineering and Disaster Reduction
Seminar, Australian Earthquake Engineering Society, Melbourne,1993,pp'39-44
SEAOC - Structural Engineers Association of California, "Recommended Lateral Force
Requirements and Commentary'', Structural Engineers Association of California, Los
Angeles, Cahfornia, 197 7
SEISMOLOGY RESEARCH CENTER, Seismology Education, http://www.seis,com.au,
1999
SEISUN, M., PARSENEIAD, S., JANKULOVSKI, E., "Experimental Behaviour of Clay
Brick Masonry Subject to Compression and Shear", Proceedings of the Australasian
Structural Engineering Conference, Sydney, t994, pp.69 1 -695.
SHELTON, R., H., "Face t oaded Performance of Masonry Veneer Under Seismic
Action", Proceedings of the 4th Australasian Masonry Conference, Sydney, 1995,
pp.150-159
SHIBATA, 4., SOæN, M., 4., "substitute-Structure Method for Seismic Design in
R./C", Journal of the Structural Division, Proceedings of the American Society of Civil
Engineers, Vol. 102, No.ST1, 1976

237
REFERENCES

STAITFORD SMITH, B., s., CARTER, C., "Hlpothesis for the shear Failure of Brick
Work", American Society of Civil Engineers, Journal of Structural Engineering, Vol.
120, No. ST4, 1971, pp. 1055-1062

SOMERS, P., " Northridge Earthquake of January 17 1994: Reconnaissance Report, Vol.
2 Unreinforced Masonry Buildings", Earthquake Spectra, Journal of the Earthquake
Engineering Research lnstitute, Vol. I l, 1996, pp.l95 -217 .
SOMERVILLE, M., MccuE, K., SINADINOVSKI, c., "Response Spectra
Recommended for Australia", Proceedings of the 1998 Australian Earthquake
Engineering Conference, Perth, 1998, pp. 19.1 - 19.3
South Australian Housing Code 199ó, Department of Housing and Urban Development,
Building Standards and Policy Branch Planning Division, ISBN Number 0 7308 4662 g
SPENCE, R., D'AYALA, D., "Damage Assessment and Analysis of the 1997 umbria-
Marche Earthquakes", Journal of the International Association for Bridge and Structural
Engineering, SEI Vol.9, No. 3, 1999
suH, N., P., TURNER, 4., P., L., "Elements of the Mechanical Behaviour of solids",
Scripta Book Comp any, I97 5
SUTER, G., T., IBRAHIM, K., S., "Shear Resistance of Damp Proof Course Materials in
Brick Morta¡ Joints", Proceedings of the 6th Canadian Masonry Symposium, Canada,
1992,pp.1 19-130.
TAYLOR-FIRTH, 4., TAYLOR, L, "A Bond Tensile Strength Test for use in Assessing
the Compatibility of Brick/l4ortar Interfaces", Construction and Building Materials, Vol.
4, No.2, 1990, pp. 58-63
TENA-COLUNGA, 4., "seismic Evaluation of Unreinforced Masonry Structured with
Flexible Diaphragms", Earthquake Spectra, Vol. 8, No 2, 1992, pp305-320.
TERCELI, s., SHEPPARD, P., TURNSEK, v., "The Influence of Frequency on the
Shear Strength and Ductility of Masonry Walls in Dynamic loading Tests", Proceedings
of the lOth World Conference on Earthquake Engineering, Rotterdam, 1992, pp.2ggr-
2997
TMOSHENKO, s., V/OINOV/SKY-KRIEGER, s., "Theory of plares and shells",
Second Edition, McGraw-Hill Book Company, 1959
TOMAZEVIC, M., "Seismic Design of Masonry Structures", Progress in Structural
Engineering and Materials, Vol. I (l),1997,pp. 88-95
TOMAZEVIC, M., "Simulation of Seismic Behaviour of Masonry Walls and Buildings
by Laboratory Testing", Proceedings of the 10th European Conference on Earthquake
Engineering, Vol. 3, Rotterdam, 1995, pp.2425 -2434
TOMAZEVIC, M., LUTMAN, M., \ryEISS, P., "The Influence of rying the walls with
Steel Ties on the Seismic Behaviour of Historical Stone and Brick Masonry Buildings",
Proceedings of the 10th European Conference on Earthquake Engineering, Vol. 3,
Rotterdam, 1995, pp. 2249 -2254

238
REFENZNCES

TOMAZEVIC, M., WEISS, P., "Seismic Behaviour of Plain- and Reinforced-Masonry


Buildings", American Society of Civil Engineers, Journal of Structural Engineering, Vol.
120, No. 2, 1994, pp. 323-338

UBC, "Uniform Building Code", International Conference of Building Officials,


Whinier, California, 1976
VAN DEN BOOM, Th., J., "Experimental Research into Flexural Strength of Masoffy",
CIB 3"1International Symposium on Wall Structures, Vol. 1, Warsaw, 1984, pp.9-18
VINTZILEOU, E., "Eurocode 8 - Specific Rules for Masonry Buildings :

Presentation/comments", Proceedings of the 10th European Conference on Earthquake


Engineering, Vol.4, Rotterdam, 1995, pp. 2963 - 2961
WEST, H., W., H., HODGKINSON, H., R., HASELTINE, 8., 4., DE VEKEY, R., C.,
"The Resistance of Masonry to Lateral Loading - Research Results on Brickwork and
Aggregate Blockwork Since 1977", The Structural Engineer, Vol. 644, No. 11, 1986, pp.
320-331
WEST, H., W., H., HODGINSKON, H., R., HASELTINE, 8., 4., " The Resistance of
Brickwork to Lateral Loading - Part 1 - Experimental Methods and Results of Tests on
Small Specimens and Full Sized Walls", The Structural Engineer, No. 10, Vol. 55, 1977,
pp.4ll42t
HODGKINSON, H., R., WEST, W., H., "The Shear Resistance of Some Damp Proof
Course Materials", Proceedings of the British Ceramic Society, No.30, 1982,pp.13-22
V/EST, 'W., H., HODGKINSON, H., R., WEBB, W., F., "The Resistance of Brick Walls
to Lateral Loading", Proceedings of the British Ceramic Society, No.21, t973, pp.l4l-
t64
WILI{ELM, P., "Earthquake Repairs to the Christ Church Cathedral, Newcastle NSW",
Australian Journal of Structural Engineering, Vol. 1, No.1, 1998
WILSON, J., LAM, N., HUTCJINSON, G., "The Capacity of Unreinforced Masonry
Parapet 'Walls in Domestic Buildings to Withstand Earthquake Induced Loading",
Australian Civil Engineering Transactions, Vol. CE.37 , No. 1, 1995, pp.4149
'WYAT"[, K., "Restrained Moisture Expansion of Clay Masomy", Journal of the
Australian Ceramic Society, November, No.2, Vol.l2, 1976,pp34-36
WYLLIE, L., "seismic Strengthening of Historic Churches", Proceedings of the 6ú US
National Conference on Earthquake Engineering
YIM, C-S., CHOPRA, 4., K., PENZIAN, J., "Rocking Response of Rigid Blocks to
Earthquakes", Earthquake Engineering and Structural Dlmamics', Vol. 8, 1980, pp. 565-
587
YOKEL, F., Y., DICKERS, R., D., "Strength of l¡adbearing Masonry Walls", American
Society of Civil Engineers, Journal of Structural Engineering, Vol. 120, No. ST5, 1971,
pp. 1593-1608

239
REFERENCES

YOKEL, F., Y., FATTAL, G., "Failure Hypothesis for Masonry Shear'walls", American
Society of Civil Engineers, Journal of Structural Engineering, vol. 120, No. ST3, 1976,
pp.5l5-532
YouNG, D., T., soLTAN, E., I., "optimum Design of concrete Masonry Loadbearing
and Non-l¡adbearing 'Walls", Proceedings of the 5th North American Masonry
Conference, Urbana-Champign, I 990, pp.93 7 -9 4g

YTTRUP, P., J., "Design of Earth Masonry rilalls For Lateral L,oads and The hoposed
New Zealand Earth Building Standard", Proceedings of the 4th Australasian Masonry
Conference, Sydney, 1995,pp.l I 3-1 I 8
YIIXIAN, IfU., "Some Engineering Features of the Tangshan Earthquake", Proceedings
of the 2od US National Conference ón Earthquake Engineãnng,1979
ZOUTENBIER, J., "Seisdúc Response of Unreinforced Masonry Buildings", Masters
Thesis, The University of Canterbury, Christchurch, New Znaland,lgg6
ZSEMBERY, s., McNEILLY, T., scRfvENER, J., "A Method for Accurately Batching
Mortar", hoceedings of the 4th Australasian Masonry Conference, Sydney, 1995,
pp.134-140

240
APPENDIX (A): Band Pass Filter Program ForttanTT
Code

PROGRAM filtl
C Fourier Transform of single real function
INTEGER n, no, isign
REAL del, botd, ûopd
REAL a(0: I 63 84), ai(O: I 63 84), afdu(O: I 6384), afdf(O: 1 6384)
REAL freq(O:16384)
REAL del(0:16384)
CHARACTER *50 IG[¡, OFIIß
C

'Write(*,*) " BAND PASS FILTER PROGRAM"


\Vrite(*,*) " FILTI.
Write(*,*) " FILTERS I COLUMN OF DATA"
V/riæ(*,*)
V/riæ(+,x) "Type filename of input time domain data file (.csv)"
Read(*,'(a)') )GILE
V/rite(*,*) "Type filename for filtered data output (.csv)"
Read(*,(a)') OFII¡
Write(*,*) "Type input data time increment (secs)"
Read(*,*) del
rWrite(*,*) "Type bottom band pass filter frequency"
Read(*,*) botd
Write(*,*) "Type top band pass filter frequency @isplacements)"
Read(+,+) topd
Open(30,file=XFllE,staûrs='old',err= I I 0)
no=O
C
C Here the data array is read from external file XFILE
Do 1k=1,16384
Read(30,*,END=2) a(k)
ai(k)=a(k)
no=no+1
I Continue
c
Close(30)
2 Continue
n=1
3 Continue
If(no.gLn)then
n=2*n
goto 3
end if
C Anays are augmented with zeros to get a function of 2
Do 4 k=netl, n
a(k)=O-0
ai(k){.0

241
APPENDD( (A)-Band Pass Filter Forrran hogram

4 Continue
C Transform to frequency domain compleæd giving data(n) array
isign=l
call realft(a,n,isþ)
Do 5 k=l,n
afdu(k)=¿(þ)
5 Continue
C Frequencies a¡e calculated
Do 6 j-l,n/2
Freq$=y'(n*del)
6 Continue
C Frequency domain daø is filæred
C acceleration band pass filær frequencies
call genfil(a,freq,n,botd,topd)
Do 7 k=l,n
afdf(k)=a(k)
7 Continue
C Realft is called to perform the inverse
C Eansform of the filtered data
isign = -1
ca-ll realft(a,n,isign)
Do 8 k=l,n
dell(k)-del*k
a(k)=2+¿1¡¡7n
8 Continue
C Data ouput
Open(35,file=OFILE,staüls='new',en= 1 20)
Write(35,*) "INPUT FILENAME : ",XFILE
Write(35,9) del
9 Format ('SAMPIÆ RATE USED IS =',F6.3,'seconds')
Write(35, l0) botd, topd
10 Format (tsand pass filter range',F5.2,' Hz -'
+,F5.2,TI2')
Wriæ135,*¡ "'
Write(3 5, *) "FREQUENCY DOMAIN,,,,,TIME DOMAIN"
Writ€(35, *) "No.,Frequency,Data,Data,,Time,Data"Data"
Write(35,*) ",,unfilt filt,,,unfilt filt"
Write(35, l2) afdu(1),afdf(l ),del( 1),ai( 1),a( l)
l2 Format ('1,0,'"F15.3,',',F15.3,',,',F15.3,',',F15.3,',',F15.3)
rWrite(35, I 3) freq(n2),afdu(2),afdf(2),detJ¡(2),u(2),a(2)
l3 Format (2,',F15.3,',',F15.3,','"Fl 5.3,',,',F15.3,',',F15.3
+,',',Fll.3)
Do 14 k=3,n-1,2
Write(3 5, I 5) Þ,,freq(kÍ2- I l2),afdu(k),afdf(k),del(k), ai(k), a(k)
rffrite(35, I 5) k+l,freq(V2- 1/Z),afdu(k+l
),afdf(k+ I ),denG+l )
+ ,ai(k+l),a(k+l)
15 Format (I4,',',F15.3,',',F15.3,',',F15.3,',,',F15.3,',',F15.3,',
+ ',F15.3)
14 Continue
lù[rite1*,*¡ " "
Wriæ(*,16) no
16 Forma('Number of inputdata lines =',I10)
Write(*,17) n
17 Format('Number of ouþut data lines = ',I10)
lVriæ(*, *) "PROGRAM RIJN COMPLETED"
100 Stop

242
APPENDD( (A) - Band Pass Filter Fortran Program

110 Vtrire(*,*) 'ERROR OPENING INPUT FILE"


105 Stop
120 Wriæ(*,*) "ERROR OPENING OUTPUT FILE"
END

PROGRAM filtls
C Fourier Transform of single real function
INTEGER n, no, isign
REAL del, botd, topd, æmp
REAL a(0: 1 63 84), ai(O: I 63 84), afdu(0: I 6384), afdf(O: 1 6384)
REAL freq(0:16384)
REAL dell(O:16384)
CHARACTER *50)CITIF, OFTÍ F, TEXT
C
ìVriæ1*,x¡ " "
Wriæ(*,*) ¡---------------
Write(t,*) " BAND PASS FILTERPROGRAM"
Write(*,*) " FILTI"
Write(*,*) " FILTERS I COLUMN OFDATA"
Write(*,*)
Write(*,*) "Type filename of input time domain data file (.csv)"
Read(*,'(a)') )GILE
\Yrite(*,*) "Type filename for filæred data output (.csv)"
Read(*,'(a)') OFILE
Write(*,*) "Type input daø time increment (secs)"
Read(*,*) del
Wriæ(*,*) "Type bottom band pass filter frequency"
Read(*,*) botd
Write(*,*) "Type top band pass filter frequency (Displacemens)"
Read(*,*) topd
Open(30,file=XFILE,staülrs='old',err= I 10)
no=0
C
C Here the data array is read from external file )GILE
Do 20 i=I,8
read(*,*) TEXT
write(*,*) TEXT
20 Continue
Do I k=1,16384
Read(30,*,END=2) temP, a(k)
ai(k)=a(k)
no=noll
I Continue
C
Close(30)
2 Continue
n=l
3 Continue
If(no.gt.n)then
n=2*n
goto 3
end if

243
APPENDX (A) - Band Pass Filær Forrran Program

C Arrays are augmented with zeros to get a function of 2


Do 4 k=noll, n
a(k)=0.0
ai(k){.0
4 Continue
C Transform to frequency domain completed giving data(n) array
isign=l
call realft(a,n,isign)
Do 5 k=l,n
afdu(k)=¿(ft)
5 Continue
C Frequencies are calculated
Do 6 j-l,nl2
Freq()=j(n*del)
6 Continue
C Frequency domain data is filæred
C acceleration band pass filter frequencies
call genfil(a,freq,n,botd,topd)
Do 7 k=l,n
afdf(k)=¿1¡¡
7 Continue
C Realft is called to perform the inverse
C hansform of the filtered data
isign = -1
call realft(a,n,isigrr)
Do 8 k=l,n
dell(k)del*k
a(k)=2*¿1¡¡¡n
8 Continue
C Data ouÞut
Open(35,fiIe=OFILE,stah¡s='new',err= I 20)
Write(35,*) "INPUT FILENAME : ",XFILE
Wriæ(35,9) del
9 Format ('SAMPll RATE USED IS =',F6.3,'seconds')
Vfriþ(35, l0) botd, topd
10 Format (tsand pass frlter range',Fí.2,'Hz -'
+,F5.2,TI2',)
Wriæ(35,*)'"
Write(35,+) "FREQIJENCY DOMAIN,,,,,TIME DOMAIN"
Write(35, *) "No.,Frequency,Data,Data,,Time,Daa,Daø"
Write(35,*) ",,unfilt filt,,,unfilt filt"
Write(35, l2) afdu(l),afdf(l ),dell(l ),ai( l),a(l)
l2 Format ('1,0,'¡l 5.3,',',Fl 5.3,',,',F15.3,',',Fl 5.3,',',Fl 5.3)
Write(35,13)freq(nl2),afdu(2),af df (2)dell(2),ai(2),a(2)
l3 Format (2,',F15.3,',',F15.3,','"F15.3,',,',F15.3,',',F15.3
+,""F11.3)
Do 14 k=3,n-1,2
Write(35, I 5) k,frq(H2-l 12),afdu(k),afdf(k),dell(k),ai(k),a(k)
Write(35, l5) k+l,freq(lc/2- l/2),afdu(k+l ),afdf(k+l ),dell(k+ I )
+ ,ai(k+l),a(k+l)
l5 Format (I4,',',F15.3,',',F15.3,',',F15.3,',,',F15.3,',',F15.3,',
+
',F15.3)
14 Continue
Wriæ1*'*¡ " "
Wriæ(*,16) no
16 Format('Number of input data lines =',I10)

244
APPENDD( (A) - Band Pass Filær Fortran Program

Write(*,17) n
17 Format('Number of ouþut data lines =',I10)
Write(*,*) "PROGRAM RUN COMPLETED"
100 Stop
ll0 rWrite(*,*) "ERROR OPENING INPUT FILE"
105 Stop
l20Write(*,*) "ERROR OPENING OUTPUT FILE'
END

SIJBROUTINE genfilt(data,freq,n,bot"top)
INTEGER n
REAL daø(n), freq(n/2)
C Data in the frequency domain is filtered
Do22i=3,¡-1,2
IF (Freq(i2- I /2).LT.bot- 1.0) TmN
data(i)=0.0
daø(i+1)=0.0
ELSEIF (keq(l2-I l2).LT.bot-0.5) THEN
data(i)=(2.0* (Freq(tl2- U2)-bot+ 1.0) * *2) *data(i)
data(i+l )=(2.0*(Freq(i/2- l/2)-bot+1.0)**2)*data(i+1)
ELSEIF (Freq(tl2-I lZ).LT.bot) TI{EN
* *2)+ I
d ata(i)=((-2.0* (Fteq(il2- I l2)-boÐ )*data(Ð
data(i+ I )=((-2.O*(Freq(i/2 - | l2)-bot)**2)+ I )*data(i+l )
ELSEIF (Frcq(il2-l lL).LT.top) TmN
data(i)=data(i)
data(i+1)dara(i+1)
ELSEIF (Fteq(rl2-l l2).LT.top+0.5) TIIEN
data(i)=((-2.0*(Frcq(rl2- I l2)-top)**2)+1 )*data(Ð
data(i+ I )=((- 2.0* (Freq(il2- I 12) -top)**2)+ 1 ) *data(i+ I )
ELSEIF (Freq(ú2-l l2)IT.topr 1.0) TIIEN
data(i)=(2.0* (Frcqbfz- il2)-toÞ 1.0)* *2)*data(i)
data(i+l )=(2.0*(Freq(i/2- 1/2)+op- 1.0)**2)*data(i+l )
ELSE
data(i)=0.0
data(i+l)=0.0
ENDIF
Data(l)=0.0
Data(2){.0
22 Continue
END

245
APPENDD( (A) - Band Pass Filter Fortran Program

SUBROUTINE realf(daø,n,isþ)
INTEGER isign,n
REAL data(n)
CU USES fourl
INTEGER i,it,i2,i3,i4,n2p3
REAL cl,c2,hli,hlr,h2i,h2r,wis,wrs
DOUBTE PRECISION theta,wi,\4,pi,r4,pr,wr,wremp
rhera=3. 1 4I59 265 3 5897 93 dO/dble(n/2)
c1{.5
if (isign.eq.l) then
c2=-0.5
call four I (daø,n12,+ l)
else
c2=0.5
theta=-theta
endif
wpr=-2.0d0*sin(O.5d0*the6)* *f
wpi=sin(theta)
wr=l.OdGrwpr
wi=wpi
n2p3=n+3
do ll i=2,n14
i1=2*i-1
i2=il+1
i3=n2p3-i2
i4=i3+1
wfs=sngl(wr)
wis=sngl(wi)
h lr+ I *(dara(i1 Þdata(i3))
h 1i+ I *(data(i2)-data(i4))
h2r =- c2* (data(i2lrd ata(i4 ) )
h2i<,2+ (daø(i I )- data(i3 ))
data(i I )=h I r+wrs *h2r-wis *h2i
data(i2)=h I i+wrs*h2i+wis *h2r
data(i3 )=h I r-wrs *h2r+wis *h2i
data(i4)=-h I i+wrs*h2i+wis*h2r
wtÊmP=wr
wewr*wpr-wi*wpi+wr
wi=wi*wpr+wtemp *wpi+wi
1l continue
if (isign.eq.l) then
hlrdaa(l)
data(l)=hlr+data(2)
data(2)=hl¡-¿¿¡¿12¡
else
hlrdaø(1)
data( I )=c I *(h lr+daa(2))
daø(2)=c I *(h lr-daø(2))
call four I (data,nn,- l)
endif
feturn
END
C (C) Copr. 1986-92 Numerical Recþs Softn'are 5lP.

246
APPENDX (B): Representative DPC Connection
Test Results

Direction of Shaking: Out-of-plane


Normal Stress at Slip Face: 0.164MPa (31.9k1.I)

'E
o
É
o
Ea
åÉ
Þo
o
v

=
MiGheigÞt Dirylacement (m)

a(slÞ) Jûst Añer Flrst S[p Ys Tlme


ave amax (after first slþ) = kv = Q.{.{g
Flftcrcd
0.ó

0.4
ào

0.2
E
O
o
0
\o

cl
q æ\}
oo¡ + nì
\o cl æ çô
ON \o
a
ô¡æ
qì9
E 4.2
d
{
N
r; ç;
o¡êì cl ô.¡ ô¡
oq

ôl
\o\C'ôl
ô¡
\o
ôl
\o
ol
\o
ôl
4.4
4.6
Ilme (secs)

Hystercdc Bebavlour
Ff(mx) = 14kì¡
f,Ilte¡ed
20
215
g
Ët0
o<
åo
f¡.

çt) q e
-5
É o
\o
-10
-15
:20
Rebtlve Jolnt Dbpl¡cement (mm)

Figure B I - Stândsrd DPC Connection One Layer of Standard Alcor

247
APPENDD( (B) - Representative DPC Connection Test Resuks

Direction of Shaking: Outof-plane


Normal Stress at Slip Face: 0.164MPa (31.9kN)

0.08
0.06 u(m)
a
É
0.04
- MWD
c) 0.02
E
6)
C)
GI 0
È
ø rô ìn
-0.02
â
è0
-0.04
c)
-0.06
rt
à -0.08
Time(secs)
-0.1

¡(sllp) Jûst After Flrst Slp V'r Tlme


Illtcrcd
ave amax (afr€r 6rs¡ sùp) = kv - 0.a7g
0.ó

0.4

e o.z
ê
E 0
ú o
o
o
E 4.2
\\o
êl
09
€ r
c!
r
þ

r F-
æ
IF ú
ñ
\o
('

N
æ
Ë
æ

4.4

{.6
Thc (secs)

Eysteredc Behavlour
Fllt¿rcd
15 kN

20
15

10
2
é5
!o
o

lz
o-5
ô _10

-15
:20

Rehlve Jol¡t Dbplacement (mm)

Figure B 2 - Ståndard DPC Connection One Layer of Super Alcor

248
APPENDD( (B) - Representative DPIC Connection Test Results

Direction of Shaking: Out-of-plane


Normal Stress at Slip Face: 0.164MPa (31.9k1Ð

Absolute Dlsplacerents
BebwC.mnectim
First slip bas ocorcd at ll.7
socs tAboveCm€ction

50
,10

î30
;20
Er0
o

Ëo
o
Él
X æ \o æ \o q
-lo çI
!i o\
ó Y;
-20
-30
40
Thc (secs)

a(slþ) Jus .lfter trlrst Sllp Y's Tlme


Itttercd ave amx (after frst sùp) = kv - 0.37g
0.5
04
0.3

eé o.2
ê 0.1
f 0
o
o
I

4.3
4.4
{.5
The (secs)

Eystereüc Behavlour
Illte¡ed
Ff(mx) = 12UV

z
ëo
q
ê
f¡(
Êì.

Relalve Jolnt Dþlacement (mn)

Figure B 3 - Standard DPC Connection One Layer of Polyfiash

249
APPENDD( (B) - Represenrarive DPC Connection Test Results

Direction of Shaking: Out-of-plane


Normal Stess at Slip Face: 0.164MPa (31.9k1Ð

Abeoluúe ltlsplacements
tBelowCo¡neciol
t Above Connection
q
â20
€o
o t
Ë
Ê
o
-zo
ô¡
e
ó *
6) \É
æ
q
\o
I t
ct
a
940
â{0

First slip has ooored at 16.4
{0 socs

-100

Tlme (secs)

a(slþ) Just mer X'lrct S[p Y's llme


Illtercd Aryliur& of actntor c¡as d€€r€asd
ave arnx (afrer first slip) = þy - 9.36* fu these cycles

0.5
0.4
0.3
19 0.2
ê 0.1
E 0
o €
r {.1 g æ
ô¡
!.1 ë n
r IÉ
4.2
\o t- €
{.3
4.4
4.5
llme (secs)

E¡rtereüc Bebavlour
Illtered = 12kN

l5

10

z5
,¡a
o
Ên
fa
È
=-5

-10

-15

Rehüve Jolnt Dþlacement (mm)

Figure B 4 - standard DPC connection one Layer of Dry-cor (Embossed polythene)

250
APPENDIX (C): Representative Slip Joint
Connection Test Results

Direction of Shaking: In-Plane


Normal Stress at Slip Face: 0.18 MPa (N=17.81ò[)

Absolute Dlsplacements tbelow cmnection


aboveænædion
40

à20
go
É o o
cl
Ê¿o æ
*N

N
c-
d
340
ôl

Êt
ã60 /
First slip bas ocqrcd at 24.5 secs
-80
I¡me (secs)

a(sllp) Jost Aftcr trlrst Sllp Y's Tlre (aft€r first slip) = kv = 0.,169
X'lltered
0.6

o.4

3É 0.2

E 0
\o c¡
O
o q
æ
tl
\f,
o\ a
E 4.2 scì (;

c;
cl
\o

4.4

4.6
Tlme (secs)

Hystereüc Bebavlour
tr'lltered Ftuax=7.7kN=amax N
10
7.5

z 5

éo 2.s
Ëo
è
I -r( n
r
É! N
çt -5
:7.5
_10
Rel¡lve Jotnt Dbpl¡cement (mm)

Figure C 1- Slip Joint Two layers of Standard Alcor

25t
APPENDD( (C) - Representative Slip Joint Connection Test Results

Direction of Shaking: Out-of-Plane


Normal Stress at Slip Face: 0.18 MPa (N=17.8k19

Absolute Dþlæements tBelowComectim


tAboveCmrection
40
30

Ãn
€ro
Ëo o o o o o
-to fo o
E it oq !t
ñ e e
o
09
tt N t
-20
È
Ê -30
I
40 First stip oq¡¡red at 1255 smnds
-50
the (cccs)

s(slþ) Ju6t After Ftrst Sllp V's Tlme


Ftlt€r€d ave amx (afrer firs slip) - kv - 0.439
0.5
04
ú 0.3

o 0.2
6
o 0.r
o 0
E
e o o o û
4.1 æ I
o
og
çE
\o
4.2
Õ¡ e s \f

{.3
4.4
4.5
Ilme (secs)

Hystercdc Behavlour F(mx) = 7.7 kll


Xïltercd
10
8
Ã
z
é4
o
?,2
o
þ_v
(À :¿
o ccl ee
\oæ
4
4
-8
_10

Relaüve Jol¡t Dbplacement (rm)

Figure C 2 Slip Jt¡int One layer of Standard Alcor

252
Acceleradon (Ð Displacement (mm)
Sltp Force ftN)
Ò^Þ e^ I
95bì5
Hu(fr(¡Oliu
ñõ Sp 8üåüot,ätts zv
oË'
22.08
g IJO
â, EL
=
ÞÉ.
22.1 6 a9
€, I
rtt 6
E ãs
m n 19.80 È 8u)
\ô 22.32 Þ o
ä EI ll ã
El
o ãR a rzt î.
(¡ Fø ô
a I
22.48 E
t,oa"
v) Èt ¡I1
EF
&lg
22.56 E e Þ
E 1 ô
tr I ø g e FÉ
9. t 22.64 FI |!
c 8. 20.80 fll
ri É z
È N) U
d lJr 22.80 !..)
o æE X
Þ 21.20
N) fi <g
¡úo o
L,I ô
ã
(, q 22.96 sl I
o F
23.04 o
o
zil E
ã 21.80 (l
ô \ 23.12 a
Þ
ø -¡ o
(! 'æ
À tl Þ
ä r,
Þ
o
Ë 23.28 z o
B E v)
È ð ð YY Þ
a
ô
E il 23.44 q
I
,84 o
å Elì gH
È 6
b, Þ
v) 23.52 ø
g E, ø ô
.D EE o
aà 23.60 I EI
I il Þ
23.20 ô
()
* ã' FT q,
il
Ë 23.76 88 o
E È
¡l ¡l
E o
q

* F åB
I
23.92
98 F
g ô
{9 2
ø
APPENDD( (C) - Representative Slip Joint Connection Test Results

Direction of Shaking: Out-of-Plane


Normal Stress at Slip Face: 0.18 MPa (N=17.8kN)

AhohcDl$æm r{boræCæcim
Behn,Crrecio
30

Én
Ë10
6)

EU
ð
.â -10
â
-n
-30
sqt
Th

{slip) Jr¡st After flrst Sllp \Is llræ aæ amax (aftef frst dip) = kv = Q.{,{g
fflter€d
0.6

èo 0.4
E
0.2
ol
c)
d)
0
è¡ o n
(,)
4.2 n
û oi
F-. E
o(i o\ o\
c¡ N ôl ôl c.l
{.4
4.6
Ilnrc (secs)

HysferUflcBehvirur
ryrmx)=14k|¡ Illtcred

2
!
û)
IE
ê
?
È {.5 -5 0.5
v)
l0

Reldive Joiú Dþhernt (m)

Figure C 4- Slip Joint Orrc layer of Embossed Polythene (Dry-Cor)

254
APPENDIX (D): Rigid F-A - Various Boundary
Conditions
o
R1

Ht4

I
w12

w4
O+W12

^
w4

co kN/m

O+W

Figure D 1 - Concrete Slab with DPC Connection Above

Taking moments about (A) to determine horizontal reaction forces

255
APPENDX (D) - Rigid P-Á - Va¡ious Top C-onnection Types

o=ùh -wlr-Al-^"0
2 [2 2) ¿

R" =ry-Yú-¡)
'22h')
n, =4*w lr-¡)
'22h"
Taking moments about (B) top free body

0
ah2
o(, - t)+\(t i) :(i -*n-
8
^,
Rearranging

,=#(o.T\,.o,
Maximum resistance occurs when Å=0

8rf w
= lrllO+
'^* 2

\ryith the rigid body assumption static instability occurs at a mid height displacement
which causes the mid height reaction to move outside of the thickness of the wall. At this
point or=0

w
O+ t -Âr^)
2
)
Rearranging

o+Y
2
,ß _T
^ o+Y
2

256
APPENDX (D)- Rigid P-Å - Various Top Connection Types

CONCRETE SLAB \ryITH DPC CONNECTION ABOVE - STATIC INSTABILITY


STATIC FORCE-DISPLACEMENT RELATIONSHIP

w
a^ =f,
8r
O+
2

zJ¿ Bi-linea¡ rigid force - displacement


{ relationship
!(g
o
Real non-linear semi-rigid force
ے)
P displacement relationship
=
-o
¡r
(t) (50-907o) ro"-.
â Depending on wall
material and condition
of rotation joints

Mid-height displacement, ÂAi^ = f

Figure D 2 - Rigid F-A Relationship Top Vertical Reaction at Leeward Face

257
APPENDX (D)- Rigid P-Å - Various Top Connection Types

R1

w4
w

O+W12 Hl4
(B )

w4

Hl4

ol kN/m (A) R2

Figure D 3 - Tlmber Top Plate Above

258
APPENDX (D) - Rigid P-A - Various Top Connection Types

Taking moments about (A) to determine horizontal reaction forces

o=ùh -o' -w (i-+)-.*


22
(Ðlt Ot W
(r-¡)
2 2h2h
R2

(Dh Ot W, .\
À1 =_+_+_(r_^,1
2 2h 2h'
Taking moments about (B) top free body

@h2
ol*{11 - Al-¿ eth _Ot _W (r-¡)
* o( !--
8 [2 ) 212 2) 2 2 2h2h
o =

Rearranging

,=þl*r'-^) +o(T+2^)]

Maximum resistance occurs when A=0

0-* =#l*.,},of
With the rigid body assumption static instability occurs at a mid height displacement
which causes the mid height reaction to move outside of the thickness of the wall. At this
point co=O

o=
þl*rt - L,^) + o(T+ za,^ l]
Rearranging

w+92
Â,^ =
(w -2o)

259
APPENDD( (D) - Rigid P-Â - Various Top Connection T¡res

TMBER TOP PLATE - STATIC INSTABILITY


STATIC FORCE-DISPLACEMENT RELATIONSHIP

@-* =
#lrur,.orT',f

z.\4 Bi-linea¡ rigid force - displacement


€(! relationship
o
€c)
-o
E.t) Real non-linear semi-rigid force
A di splacement relationship

(50-907o) ol,,--
depends on wall
material and
condition

Mid-height displacement, Â 2
^
IA
(w -2o)

Figure D 4 - Rigid F-a Relationship Top vertical Reaction at centerline

260
APPENDIX (E): Material Test Results

450
a
J't
400
LOAD = 0.3372 MICRO STRAIN /

z
350
300 -r
250
â _{
200
o /S
/f
Fl
150
100
50
/'
0
á'
OOOOOOO
oooooÕo
c.ìs\ooooc.ì$
MICRO STRAIN

Figure E I - Bond \ilrench Calibration Plot 110mm Brick Specinren Bond \ilrench

225
LOAD -- 0.46II MICRO STRAIN
200 -¿
175
å
150
á
z Ã
125
â
o
È
100 -tF
75
50
4
25
0
/F
OOOOOOOOO
\nOl.)O\nO\nOln
ri Ê C.ì C.ì C.¡ C.¡ É sl'
MICRO STRAIN

Figure E 2- Bond Wrench Calibration Plot 50mmBrick Specimen Bond Wrench

261
APPENDD( (E) - Maærial Test Results

RESULTS OF BOND WRENCH TESTS

llOmm TwO BRICK PRISMS TESTED MARCH 1998 (SERIES l)


Brick thickress ll0 mm
Brick length 230 mm
Mass bond wrench 4.043 kg
Mass at lever arm
Brick and mortar mass above interface
Front brick face to center of gravity 250 mm
Front brick face to notch 't65 mm
Elastic modulus 463833 Illm-
1

Bedded a¡ea 2s300 mm2


Total compressive force on bedded area

F"o =9.81(m"r+ fth+ %)

lT;l Bending moment about rhe cenrroid of the bedded a¡ea

=o.zw,(a,-'/)*n tt^(a,-'ú)
trt
¡rI
"r
Flexural sEength of the specimen

f*=*'/o-'"ú,

Specimen TEST IIucro m" m" fsp MP f"p Ave StDev


No. NO. strain kg ke N Nmm MPa MPa MPa
I I 23.5 3.3 302.57 t7t4t3.9t 0.36
2 14.3 3.17 ztt.o4 to't334.99 0.22 0.28 0.07
3 17.t 3.62 242.93 126837.27 o.26
2 I 27.2 3.09 336.81 t97184.78 0.41
2 24.4 3.05 308.95 177682.50 o.37 0.36 0.06
3 19.7 3.11 269.31 1M946.53 0.30
3 I 19.3 3 258.42 t42160.49 0.30
2 32.1 3.06 384.58 231313.77 0.48 0.40 0.10
3 28 2.99 343.67 202756.86 o.42
4 I 22.9 3.14 295.|t 167234.85 0.3s
2 28.8 3.5 356.52 208328.94 0.44 o.42 o.o7
3 32.1t 3.54 389.39 231383.42 0.48

oVERALL AVERAGE F.p FOR N-r- 4 BATCI{ES 0.37


OVERALL ST DEV FOR ALL 4 BATCITES D.08
LOWEST BOND VALI.JE 0.22
HIG}IEST BOND VALI.]E 0.48

262
APPENDD( (E) - Maærial TestResults

l10mm PRE-DYNAMICALLY TESTED WALLS TESTED MARCH 1998 (SERIES 1)

Brick thickress 110 Illm


I Brick length 230 mtn
Mass bond wrench 4.M3 kg
Mass at lever arm
Brick and mortar mass above inærface
Front brick face to center of gravþ 250 mm
Front brick face to notch 765 mm
1
Elastic modulus 463833 mm-
Bedded area 2$AO mm'
fsp Total compressive force on bedded area

F"o =9.81(mr+ nb+m!)

Bending moment about the centroid of the bedded a¡ea


lT;l
M,p = ssm,(a, -' ú). o .z rrn,(a, -' ú)
lTl Flexural süength of the specimen

F"o/
Í,0=M'/,0-
/Ao

Specimen TEST micro m2 lll3 Fsp [rfsp fP Ave St Dev


No. NO. sÍain ke ke N Nmm MPa MPa MPa
I I 48.01 3.8 347.92 342128.51 0.72
2 35.17 3.64 420.39 252696.62 0.53 o.g 0.10
3 44.34 3.18 505.90 316566.59 0.66
2 1 25.99 3.8 331.90 188757.01 0.39
2 31.09 3.5 378.99 224279.02 0.47 0.47 0.07
3 36.19 4.O3 434.22 259801.03 0.54
3 I 35.t',l 3.5 419.01 252696.62 0.53
2 28.03 3.t4 345.44 202965.81 o.42 0.47 0.05
3 31.09 3.97 383.60 224279.02 o.47
4 I 56.57 3.763 631.53 401749.76 0.84
2 40.27 3.72 471.20 288218.63 0.60 0.6r 0.22
3 25.99 3.925 333.r3 188757.01 0.39

OVERALL AVERAGE F"P FOR ALL 4 BATCIIES 0.55


OVERALL ST DEV FOR ALL 4 BATCTIES 0.14
LOWEST BOND VALUE 0.39
HIGIIEST BOND VALI]E D.E4

263
APPENDX (E) - Material Tesr Results

l lOmm TWO BRICK PRISMS TESTED JUNE 1998 (SERIES 2)

Brick thickness 110 fllm


Brick length 230 fltm
Mass bond wrench 5.36 kg
Mass at lever arm
Brick and mofar mass above interface
Frontbrick face to center ofgravity 2W mm
Front brick face to notch 765 flrm
Elastic modulus 463833 mm'
Bedded area 25300 mm2
Total compressive force on bedded a¡ea

F"r=9.9I(mr+m2+m3)

li4-;l Bending moment about the centroid of the bedded area

¡'I =o.um,(a,-'/)*, tt (0,-'ú)


t-_l
"r
Flexural strength of the specimen

r,o=*'/,0-''/n

Specimen TEST nucfo m" m' Fsp Mp fP Ave StDev


No. NO. sEain kq ke N Nmm MPa MPa MPa
5 I 750 25.78 2.984 334.75 187183.33 0.39
2 1260 43.31 3.058 507.45 309283.45 0.65 0.s8 0.16
3 1360 46.75 3.551 546.01 333224.65 o.70
6 I 770 26.47 2.982 341.48 t9r9'n.57 0.40
2 770 26.47 2.985 341.51 191971.57 0.40 0.42 0.oÍ
3 900 30.94 2.974 385.24 223095-13 o.47
7 I t200 41.2s 2.982 486.48 294918.73 o.62
) 1300 44.69 2.984 520.21 318859.93 o.67 0.59 0.09
3 950 32.65 35W 407.28 23565.73 o.49
8 I 700 24.06 2.977 317.83 175212.73 o.37
2 1050 36.09 3.546 ut.43 259m6..93 0.54 0.44 0.09
3 800 27.50 3.013 351.90 199153.93 o.42

OVERALL AVERAGE F,P FOR ALL 4 BATC}IES 0.52


OVERALL STDEV FOR ALL4 BATCI{ES J.t2
LO\ryESTBOND VALI.JE ù.37
HIGITEST BOND VALI]E D.7t

264
APPENDD( (E) - Material Test Results

l10mm PRE-DYNAMICALLY TESTED TWALLS TESTED JUNE 1998 (SERIES 2)

t Brick thickness ll0 fllm


I Brick length 230 mm
lIll Mass bond wrench 5.36 kg
lll2 Mass at lever arm
IIì3 Brick and mortar mÍrss above interface
dr Front brick face to center of gravity 2N IIlm
dz Front brick face to notch 765 mm
Z¿ Elastic modulus 463833 mm3
A'd Bedded area 25300 mm2
Fsp Total compressive force on bedded area

F,o =9.81(mr+ mr+ m.)

l-ìrf-;l Bending moment about the centroid of the bedded a¡ea

¡1,'I
"r
= o .zw"(a, -' /)*, rr^(0, -''/)
t--ç-l Flexural sfrength of the specimen

f ,o=*'o/o '"/o,

Specimen TEST micro m' m' fsp Mp f"p Ave StDev


No. NO. strain ke ke N Nmm MPa MPa MPa
5 I 1050 36.91 2.984 443.92 2@693.30 0.55
2 1100 38.67 3.058 461.89 276934.68 0.58 0.71 o-25
3 1900 66.79 3.551 742.59 472796.75 0.99
6 1 1000 35.15 2.982 426.66 252451-92 o.53
2 1300 45.70 2.985 530.14 325W.t9 0.68 0.s6 0.11
3 900 3r.64 2.974 392.tO 227969.16 0.48
7 I 800 28.12 2.982 357.70 203486.40 0.42
.,
500 17.58 2.984 254.27 130038.13 o.n 0.41 0.13
3 1000 35.15 3.502 43t.76 25245r.92 0.53
8 1 1000 35.15 2.977 426.61 2s245t.92 0.s3
2 1200 42.18 3.546 501.16 301417.44 0.63 0.59 0.05
3 I 150 40.42 3.013 478.69 289t76.06 0.ó0

OVERALL AVERAGE FspFOR AJ-L4 BATCIIES D.57


OVERALL ST DEV FOR ALL 4 BATCTMS t. l7
LOWEST BOND VALIJE D.27
HIGI{EST BOND VALUE 0.99

265
APPENDIX (E) - Material Test Results

1l0mm TWO BRICK PRISMS TESTED SEPTEMBER 1998

Brick thiclness ll0 mm


Brick length 230 lItm
Mass bond wrench 5.36 kg
Mass at lever arm
Brick and mortar mass above interface
Front brick face to notch 2OO mm
Front brick face to center of gravity 765 mm
Elastic modulus 463833 mm3
Bedded a¡ea 253W mm2
Total compressive force on bedded area

F"o =9.81(mr+ nb+ m3)

f-M--l Bending moment about the centroid of the bedded area

¡vI
"e
=o.tua(a,-'/)., rt^(a,-'ú)
l--r'"-l Flexural strength of the specimen

M
r* "o/
F"o
'/
/Zo /Ao

Specimen TEST nucro m' m' psp Msp frP Ave StDev
No. NO. strain kg kg N Nmm MPa MPa MPa

rIIll I 300 10.55


I 2.984 185.30 8to72.61
IIo.l7
2 1050 36.91 3.058 444.65 264693.30 0.55 0.32 0.20
3 450 15.82 3.551 242.59 ltj't96.75 o.24

t2 I 600 2r.o9 2S82 288.73 154520.88 o.32


I 500 17.58 2.985 254.28 130038.13 0.27 0.30 0.03

rI r III
3 550 2.974

I
19.33 271.41 142279.50 0.30

l4 I 750 26.36 2.982 340.46 t9lu5.o2 0.40


2 450 t5.82 2.984

I
237.03 rt1796.75 o.24 0.29 0.10
3 400 14.06 3.052 220.45 10s555.37 o.22

OVERALL AVERAGE Fsp FOR 3 BATCIIES 0.30


OVERALL ST DEV FOR 3 BATCTIES ).1I
LOWESTBONDVALUE 0.tr
HIGIIEST BOND VALI.]E 0.55

266
APPENDIX (E) - Material Test Results

50mm TV/O BRICK PRISMS TESTED SEPTEMBER 1998

Brick thickness 50 nìm


Brick length 230 mm
Mass bond wrench 3.5 kg
Mass at lever arm
Brick and mortår mass above interface
Front brick face to notch 192 mm
Front brick face to center of gravity 592 nìm
Elastic modulus 95833 mm'
Bedded area 11500 mm2
Total compressive force on bedded area

F,o =9.81(mr+ nh+ m))

l-Çl Bending moment about the centroid of the bedded area

¡r = s.tw,(a, -' /)*, rt^(a, -' ú)


"n

t-?-t Flexural stength of the specimen

r,o=*'/o-''/n

Specimen TEST TruCfO IIl2 fIl3 Fsp 1ylsp f"p Ave St Dev
No. NO sfrain kg kg N Nmm MPa MPa MPa

10 I 300 14.3'.1 0.9 184.16 85680.95 0.88


2 300 14.37 0.9 184.16 85680.95 0.88 0.70 0.30
3 ll0 5.27 0.9 94.86 35047.85 0.36

t3 1 185 8.86 0.9 130.11 55034.60 0.56


2 295 14.r3 0.9 181.81 84348.50 0.86 0.76 o.r7
3 295 t4.13 0.9 181.81 84348.50 0.86

OVERALL AVERAGE F,P FOR 2 BATCTIES 0.73


OVERALL ST DEV FOR 2 BATCIIES 0.22
LOWEST BOND VALUE 0.36
HIGTIEST BOND VALUE D.88

267
APPENDIX (E) - Material Test Results

RESULTS OF MODULUS TESTS

SPECMEN No. (2) - 110mm THICK TESTED MARCH 1998


LOAD DEMEC (1) DEMEC (2) STRATN (l) STRATN (2) L(2) Â(comb) COMB STRESS
(N) brick bricl/morta¡ brick brick/mortar ^(1)
brick brick/morta¡ STRAIN MPa
0 782 943 0 0 0 0 0 0 0
25000 781 942 0.0000252 0.00001 0.00128 0.002032 0.Nr2457 0.0000072 0.99
7'.|9 930 0.00007s6 0.00013. 0.00384 0.0264t6 0.024057 0.0001398 l.98
7s000 775 926 0.0001764 0.0w17) 0.00896 0.034s44 0.029040 0.0001688 2.96
100000 767 920 0.000378 0.00023 0.0192 0.046736 0.034941 0.000203 3.95
125000 763 911 0.0004788 0.00032 0.02432 0.065024 0.050084 0.0002911 4.94
150000 758 900 0.0006048 0.00043 0.03072 0.o87376 0.0ó8554 0.0003982 5.93
332000 T]LTIMATE 57o ULTMATE 16,600 N 0.66
337o ULTIMATE l10,556 N 4.37
Estimate Modulus 15,000 MPa

SPECIMEN No. (3) - 110mm THICK TESTED MARCH 1998


LOAD DEMEC (I) DEMEC (2) STRATN (1) STRATN (2) L(2) A(comb) COMB STRESS
(N) brick bricl/morø¡ brick briclc/mortar ^(l)
brick bricl/morta¡ STRAIN MPa
0 988 911 0 0 0 0 0 0 0
25000 995 855 -0.0n01764 0.00056 -0.00896 0.113792 0.1t9295 0.0006935 0.99
994 846 -0.0001512 0.00065 -0.00768 0.13208 0.136797 0.0007953 1.98
993 827 -0.000126 0.0@84 -0.0064 0.170688 0.174619 0.0010152 2.96
100000 989 805 -0.0000252 0.00,101 -0.00128 0.215392 0.216178 0.001256 3.95
125000 986 780 0.0000504 0.00131 0.00256 0.266192 0.264619 0.00r538 4.94
150000 982 765 0.0001512 0.00146 0.00768 0.296672 0.29t954 0.00r697 5.93
336000 ULTIMATE SVoIJLTG,ÃATE 16,800 N 0.66
33VoULTIMATE 11 1 ,888 N 4.42
Estimate Modulus 3,300 MPa

268
SPECIMEN No. (a) - 110mm THICK TESTED MARCH 1998

LOAD DEMEC (1) DEMEC (2) STRAIN (1) STRATN (2) A(1) L(2) Â(comb) COMB STRESS
(N) brick brick/mortar brick bricl/mortar brick bricl/mortar STRAIN MPa
0 796 939 0 0 0 0 0 0 0
25000 795 910 0.0000252 0.00029 0.00128 0.058928 0.0581417 0.0003380 0.99
50000 794 887 0.0000504 0.00052 0.00256 0.105664 0.1040914 0.0006051 1.98
75000 792 864 0.0001008 0.00075 0.00512 0.1524 0.1492549 0.0008677 2.96
100000 789 843 0.0001764 0.00096 0.00896 0.195072 0. l 89568 0.001102 3.95
125000 786 820 0.w252 0.00119 0.0128 0.241808 0.2339452 0.001360 4.94
150000 782 791 0.0003528 0.00148 o.0r792 0.300736 0.289728 0.001684 5.93
333000 LILTIMATE 5VoULTIJ'VIATE 16,650 N 0.66
33VaULTIMATE 110,889 N 4.38
Estimate Modulus MPa

SPECMEN No. (5) - 110mm THICK TESTED JUNE 1998


LOAD DEMEC (I) DEMEC (2) STRAIN (1) STRAIN (2) A(l) L(2) Â(comb) COMB STRESS
(N) brick bricl/mortar brick brick/morør brick brick/mortar STRAIN MPa
0 797 812 0 0 0 0 0 0 0.00
25000 796 810 2.528-05 0.00002 0.0013 0.004064 o.æ3277726 1.90565E-05 0.99
50000 795 808 5.04E-05 0.00004 0.0026 0.008128 0.006555451 3.81131E-05 1.98
75000 793 805 0.000101 0.00007 0.0051 0.014224 0.011078903 6.441228-05 2.96
100000 792 796 0.000126 0.00016 0.0064 0.032512 0.028580629 0.000166r66 3.9s
r25000 780 790 0.000428 0.ñ022 0.0218 0.0M704 0.03t337337 0.000182194 4.94
150000 778 781 0.000479 0.00031 0.0243 0.062992 0.048052789 0.w0279377 5.93
175000 777 772 0.000504 0.0004 0.0256 0.08128 0.065554515 0.00038113 r 6.92
200000 775 762 0.000554 0.m05 0.0282 0.10r6 0.084301966 0.000490128 7.91

360000 T.JLTIMATE 57o ULTIMATE 18,000 N o.7t


337o ULTMATE 119,880 N 4.74
Estimate 16,000 MPa

269
APPENDIX (E) - Maærial Test Results

SPECMEN No. (6) - 110mm THICK TESTED JUNE 1998


LOAD DEMEC (l) DEMEC (2) STRATN (l) STRATN (2) L(2) Â(comb) COMB STRESS
(N) brick bricl/mortar brick brick/mortar ^(l)
brick brick/mortar STRAIN MPa
0 911 918 0 0 0 0 0 0 0.00
25000 903 918 0.0æ202 0 0.0102 0 -0.00629019 -3.6571E-05 0.99
50000 902 916 0.0æ227 0.00002 0.0115 0.004064 -0.m.301247 -1.7514E-05 1.98
75000 9r6 0.000454 0.00002 0.023 0.004064 -0.01008894 -5.8657E-0s 2.96
100000 883 916 0.000706 0.00002 0.0358 0.004064 -0.01795168 -0.000r0437 3.95
125000 79t 915 o.æ3024 0.00003 0.1536 0.006096 -0.08825691 -0.00051312 4.94
150000 795 910 0.002923 0.00008 0.1485 0.016256 -0.07495182 -0.00043577 5.93
338,000 ULTIMATE 5VoIULTIJvIATE 16,900 N 0.67
33VoULTIJvIAT]E 1t2,554 N 4.45
Estimaæ Modulus Unreliable Data No Estimate

SPECIMEN No. (7) - 110mm THICK TESTED JUNE 1998


LOAD DEMEC (1) DEMEC (2) STRATN (r) STRAIN (2) L(2) Â(comb) COMB STRESS
(N) brick bricl/mortar brick brick/morør ^(1)
brick brick/mortar STRAIN MPa
0 8r2 95r 0 0 0 0 0 0 0.00
812 94'.1 0 0.00004 0 0.008128 0.008128 4.725588-05 0.99
50000 808 945 0.00010r 0.00006 0.0051 0.0t2192 0.009046903 5.25983E-05 1.98
75000 807 940 0.000126 0.000r I 0.0064 0.022352 0.018420629 0.000107097 2.96
100000 807 933 0.000126 0.00018 0.0064 0.036576 0.032644629 0.000189794 3.9s
125000 804 927 0.000202 0.00024 0.0102 0.048768 0.042477806 0.000246964 4.94
150000 802 918 0.000252 0.00033 0.0128 0.067056 0.059193257 0.w03Mt47 5.93
175000 799 907 0.000328 0.00044 0.0166 0.089408 0.079186434 0.000460386 6.92
200000 797 897 0.000378 0.00054 0.0192 0.109728 0.097933886 0.000569383 7.9t
313000 ULTIMATE 57o IJLTIMATE 15,650 N 0.62
337o ULTMATE t04,229 N 4.12
Estimate Modulus 13,900 MPa

2',to
SPECIMEN No. (8) - 110mm THICK TESTED JUNE 1998
LOAD DEMEC (l) DEMEC (2) STRAIN (I) STRAIN (2) L(2) Â(comb) COMB STRESS
(N) brick brick/mortar brick briclc/monar ^(l)
brick briclc/morta¡ STRAIN MPa
0 840 9r8 0 0 0 0 0 0 0.00
25000 83s 907 0.000126 0.00011 0.0064 0.022352 0.018420629 0.000107097 0.99
50000 831 893 0.@0227 0.00025 0.01l5 0.0508 0.043723532 0.000254207 1.98
75000 830 880 o.o0f252 0.00038 0.0128 o.o77216 o.069353257 o.ooo4032r7 2.96
100000 829 866 o.æ0277 0.00052 0.0141 0.105664 0.097014983 0.000564041 3.95
125000 827 849 0.000328 0.00069 0.0r66 0.140208 0.129986434 0.000755735 4.94
150000 826 830 0.000353 0.00088 0.0179 0.178816 0.16780816 0.w0975629 5.93
175000 823 809 0.000428 0.00109 0.0218 0.22t488 0.208121337 0.001210008 6.92
200000 819 786 0.000529 0.00132 0.0269 o.268224 0.25t71224 0.o01463443 7.91
245000 ULTIMATE 57o ULTMATE t2,250 N 0.48
3370 ULTMATE 81,585 N 3.22
Estimaæ Modulus 5,400 MPa

SPECIMEN No. (10) - 50mm THICK TESTED SEPTEMBER 1998


LOAD DEMEC (1) STRATN (l) DEMEC (1) STRAIN (I) DEMEC (1) STRAIN (1) DEMEC (I) STRAIN (1) Stress
(N) brick/mortar brick/morør brick/mortar brick/mortar brick/mortar bricl:/mortar briclJmortar brick/mortar MPa
0 898 0 901 0 895 0.000000 898 0.000000 0.00
15000 897.5 0.0000r26 898 0.0000756 888 0.000176 895 0.000076 1.30
30000 890 0.0002016 892 0.0002268 884 0.000277 889 0.040227 2.6r
45000 884 0.0003528 886 0.000378 882 0.000328 882 0.000403 3.9r
60000 880 0.0004536 878 0.000s796 872 0.000580 877 0.000529 s.22

I
0.000756 868 0.000756 6.52

I
75000 874 0.0006048 873 0.0007056 865
90000 870.5 0.000693 864 0.0009324 865 0.000756 864 0.000857 7.83
Iest I Modulus 11,300MPa Iest 2 Modulus 8,400MPa Test 3 Modulus 10,400MPa Test 4 Modulus 9,l00MPa
Estimate Estimate Estimate Estimate
307000 ULTIMATE 57oULTIMATE 15,350 N 1.33
33% ULTIMATE toz,23r N 8.89
Average Modulus 9,800 MPa

271
APPENDIX (E) - Material Test Results

SPECMEN No. (11) - 110mm THICK TESTED SEPTEMBER 1998


LOAD DEMEC (I) DEMEC (2) STRATN (r) STRAIN (2) L(2) Â(comb) COMB STRESS
(N) brick bricVmorør brick bricl/mortar ^(l)
brick brick/mortar STRAIN MPa
0 812 901 0 0 0.000000 0.000000 0.000000 0.000000 0.00
25000 811 887 0.0m,0252 0.00014 0.001280 0.028448 0.027662 0.00016r 0.99
809.5 871 0.000063 0.0003 0.003200 0.060960 0.058994 0.000343 1.98
808 857 0.0001008 0.00044 0.005121 0.089408 0.086263 0.000502 2.96
100000 806 844 0.0001512 0.00057 0.007681 0.115824 0.1 1 1 106 0.000646 3.95
125000 805 831 0.0001764 0.0007 0.008961 o.t42240 0.136736 0.000795 4.94
r50000 801.5 820 0.w2646 0.00081 0.013442 0.164592 0.156336 0.000909 5.93
359000 I.JLTIMATE 5% ULTIMATE 17,950 N 0.7r
S3ToIJLTIMATE 119,547 N 4.73
Estimate Modulus 6,600 MPa

SPECMEN No. (12) - 110mm THICK TESTED SEPTEMBER 1998


LOAD DEMEC (l) DEMEC (2) STRATN (t) STRATN (2) L(2) Â(comb) COMB STRESS
(N) brick briclc/mortar brick bricl/morør ^(1)
brick briclc/mortar STRAIN MPa
0 807.5 914 0 0 0.000000 0.000000 0.000000 0.000000 0.00
25000 805 908.5 0.000063 0.000055 0.003200 0.0r r 176 0.009210 0.000054 0.99
50000 802.5 900.5 0.000126 0.000135 0.006401 0.027432 0.023501 0.000137 1.98
75000 800 892 0.000189 0.0nn.22 0.00960r o.ou704 0.038807 0.0ú226 2.96
I 795.5 883 0.ñ030u 0.00031 0.015362 0.062992 0.0535s7 0.00031r 3.95
I 793 875 0.0003654 0.00039 0.018562 0.079248 0.067847 0.000394 4.94
150000 788 866 0.0004914 0.00048 0.024963 0.097536 0.082204 0.000478 5.93
397000 ULTIMATE 57o ULTMATE 19,8s0 N 0.78
33/oULTIJvLAI]E 132,200 N 5.23
Estimate Modulus 11,600 MPa

).7)
SPECIMEN No. (13) - 110mm THICK TESTED SEPTEMBER 1998
LOAD DEMEC (I) DEMEC (2) STRATN (1) srRArN (2) L(2) À(comb) COMB STRESS
(N) brick brick/mortar brick brick/mortar ^(1)
brick brick/mortar STRAIN MPa
0 900 9t6 0 0 0.000000 0.000000 0.000000 0.000000 0.00
25000 894 9t6 0.0001512 0 0.007681 0.000000 -0.004718 -0.000027 0.99
50000 887.5 915 0.000315 0.00001 0.016002 0.002032 -0.007796 -0.000045 1.98
7s000 884 912 0.0004032 0.00004 0.020483 0.008128 -o.oo44s2 -0.000026 2.96
100000 880.5 908 0.0004914 0.00008 0.024963 0.016256 0.M924 0.000005 3.95
125000 877 902 0.0005796 0.00014 0.029444 o.028448 0.010364 0.000060 4.94
397000 ULTIMATE 57o ULTIMATE 19,850 N 0.78
33ToIJLTIvIATE r32,2@ N 5.23
Estimate Modulus Unreliable Data No Estimate

SPECIMEN No. (10) - 50mm THICK TESTED SEPTEMBER 1998


LOAD DEMEC (I) STRAIN (1) DEMEC (I) STRAIN (1) DBMEC (1) STRATN (1) DEMEC (1) STRATN (1) Stress
N) briclc/mortar bricVmortar brick/mortar brick/mort¿r bricL/mort¿r brick/mortar bricL/mort¿r brick/mortar MPa
0 873 0 811 0 867 0.000000 803 0.000000 0.00
15000 858 0.000378 808 0.0000756 845 0.000554 802 0.000025 1.30
30000 844 0.0007308 802 0.0402268 825 0.001058 801 0.000050 2.61
45000 825 0.0012096 799 0.0403024 814 0.001336 797 0.000151 3.91
60000 818 0.001386 794.5 0.0004158 802 0.001638 794 0.0cp227 5.22
75000 811 o.oot5624 786 0.00063 795 0.001814 790 0.000328 6.52
90000 805 0.0017136 782 0.0007308 788 0.001991 787 0.000403 7.83
105000 794 0.0019908 780 0.0007812 773 0.a02369 785 0.000454 9.13
120000 779 0.0023688 776 0.000882 763 0.002621 782 0.000529 10.43

Test 1 Modulus 4,400MPa Test 2 Modulus 11,800MPa Test 3 Modulus 4,000MPa Iest 4 Modulus Unreliable
Estimate Estimate Estimate Estimate Data
303000 ULTIMATE 5VoIJLTNIATE r5,150 N 1.32
33VoUI-TIIúATE 100,900 N 8.77
Average Modulus 6,700 MPa

273
APPENDX (E) - Maærial Test Results

RESULTS OF COMPRESSTVE MORTAR CI]BE TESTS

Series Specimen Specimen Cube Number Compressive


No. Thickness (l00xl00x100mm) Strength
(mm) (MPa)
Marchl998 1 ll0 I 5.20
2 5.02
J 6.82
Marchl998 2 110 I 5.88
2 6.18
3 5.62
Marchl998 J 110 I 7.16
1 6.84
J 6.42
March1998 4 ll0 I 7.16
2 6.34
3 6.r4
June 1998 5 ll0 1 6.02
2 4.30
June 1998 6 110 I 6.06
2 4.O4
June 1998 7 ll0 I 4.02
2 4.98
June 1998 8 110 I 5.06
2 4.32
3 4.16
September 1998 l0 50 I 5.00
2 5.20
3 s.48
September 1998 l1 ll0 I 4.68
2 4.22
3 4.90
Sept€mber 1998 t2 lt0 I 5.28
2 4.94
3 5.08
Sepæmber 1998 t3 ll0 I 3.76
2 4.M
3 3.84
September 1998 t4 50 I 4.08
2 3.56
3 4.44
AVERAGE 5.17

274
APPENDIX (F): Simply Supported \ü/all Test Results
MARCH 98 Height 1.485[m Applied Overburden 0 MPa
SPECIMEN 3 fhiclmess I10hr,m Flexural Tensile Süength, f, 460 kPa
Længttr 9501l¡,¡Ít Linear Elastic Analysis Prediction 2.ø4 KN
Density 1800 Rieid Bodv Analysis P¡ediction 0.406 KN

STATIC PUSH TEST _ MID HEIGTIT FOINT IOAD


35

3.18
I
3

! r.t ---i
E
9,
rcRCE (kN)
-FEXPERTMENTAL
'#RIGIDBoDY (kl.t)
Þ.1

É - 'tr - LINEAR ELA.STIC ßN)


3 r.s
d
Ir

0.5

0
0 20 Q 60 80 100
MIDHEIGHT DEFI-ECTION (lvilvÍ)

Figure F 1- Static Push Test - Un-cracked, 110mn¡ No Overburden

JUNE 98 Height t.485tm Applied Overburden 0.15lMPa


SPECIMEN t Ihiclness 110bnm Flexural Tensile SEength, f, 46|kPa
Lensttr 95rlmm Linea¡ Elastic Analysis Prediction 4.S212lkr{
Density I80?t/r;ghl¡i Risid Bodv Analvsis Prediction 5.3Iólkl.I
STATIC PUSH TEST. MID HEIGHT POINT LOAD
1

FORCE (kN)
'-TRIGIDBODY (kÐ

I
6
_
- Ð LINEAR ELASTIC (KN)

2
ð 5
F
5
zf¡l 4
ú
F.
¡
Ø
3
¿
ADDITIONAL II IERAL STRENGTF ABOVETHATOF
I
l¡l
ruUU UUÞ IV ü !¡@ùÐ ùIAITL utrELlrvlì ur
OVERBT]RDEN S IRINGS FOUND TC BE SICNIFICANT
lhD rt^--úr^T tc
1

0
0 20 44 60 80 100
MID.HEIGHT DBFLECTION (MM)

'Figure F 2-
Static Push Test - Un-cracked, L10mrn' 0.15MPa Overburden

2t5
APPENDD( F : Out-of-plane Simply &tpported WaIl Test Results

JUNE 98 ÉIeight l.485lm Applied Overburden 0.15 MPa


SPECIMEN 8 Ihickness lI0lr.urr Flexural Tensile Stengú" f, 0 kPa
ænsth 950 Linea¡ Elastic An¿¡lysis Pr,ediction 2.322 KN
Density 1800[rslm' Rigid Body Analysis P¡ediction 5.it6 KN

STATIC PUSH TEST - MID HEIGIIT FOINT LOAI)

EXPERJMENTAL K)RCE (KN)


5
.+RIGIDBODY (kN)
2
*
è9
4
ü
z
t¡l
&
F 3

¡
U)
/
ADDITIONI LLATERAL STRI NGTTIABOVE
d 2

f
H t-
rlut vrà JIU DUE TL' IIìL] ENÐùIÂIIL
I DEFLECTIC !¡OFOVERBIIRX ]N SPRINGS
FOTJNDTO ¡ESIGNIFICANT 0R f lOnm
I WALLS

0 20 40 60 80 100 120
MID-HEIGIIT DEFLECTION (MM)

Figure F 3. Static Push Test - Cracked, 110mm,O.l5Mpa (Þerbu¡den

SEPIEMBER9S Heieht Applied Overburden 0lMPa


SPECIMEN 10 Ihichess 50 Flexural Tensile SEength, f, 0[rPa
Lengtlr Linear El¿stic Analysis Prediction 0.07[lkN
2300 lieid Body Analysis Prediction 0.1071kr{
STATIC PUSH TEST.MID HEIGITT FOINTI,OAD
0.r2

0.1

2
t9
0.08
,/ FORG (kN)
F
o RIGIDBODY (IN)
zB]
ú
F 0.06
\,
6
-l
ú
l¡l 0.04
f
F

0.o2

0
0 5 l0 l5 20 25 30 35 q 45
MIDHEIGIIT DEFLECTTON (MM)

Figure F 4- Static Push Test - Cracked" 50mnD No Overburden

276
APPENDIX F: Out-of-plane Simply Supponed Woll Test Results

SEPIEMBER9S Heisht 1.485 m Applied Overburden 0.075llvlPa


SPECIMEN 10 Thiclness 50 rnm Flexural Tensile Stensth, f, 750kPa
Lænsth 950 mm Linear Elastic Analysis Prediction I.07Ilkl.I
Density n0a ks/Íf Risid Bodv Analysis Prediction Ø.587lklr

STATIC PUSHTEST - MID MIGI{T POINT LOAD


1.1
F--- --i.
1
z ! 0.9s ÐGERIMENTALFORCE (KN)
J 0.9
+RIGIDBODY (KN)
h 0.8 _ I _ LINEAR ELASTTC (KN)
zlI] 0.7
ú 0.6 .-a\
F
U) 0.5
J
0.4
ú L
la 0.3
F
J o.2
0.1
0
0510152025 30 35 40 45 50
MID-MIGI{T DEFLECTION

Figure F 5 - Static Push Test - Urcracked, 50mnu 0.Û75MPa Overburden

SEPTEMBER93 Heieht 1.485 m Aoolied Overburden 0.075lMPa


SPECIMEN 10 Ihiclness 50 mm Flexural Tensile Srength, f, 0[rPa
Leneth 950 mm Lineár Elastic Analvsis Prediction Ø.28ólkl.I
ÞnsiW 2300 ks/n: Rigid Bodv Analysis Prediction 0.órSlktI
STATIC PUSH TEST - MID HEIGIIT POINT IJOAD
0.7

L
0.6

2
g
F
o.s FORG (kl.I)
-tsEXPERIMENTAL

f
F
-+RTGTDBODY (kl.t)
V o.+
ú
F
(t) $\.
c
f
0'3

fi
<
J
0.2
r
¡

0.1

0
0 5 t0 l5 20 25 30 35 40 45 50
MID.HEIGTIT DEFLECTION (MM)

Figure F G Static Push Test - Cracked, 50mq 0.075 Overburden

277
APPENDIX F: Out-of-plane Simply Supponed Wall Test Results

SEPTEMBER93 Height 1.48s m Applied Overburden 0lMPa


SPECIMEN 11 Thickness 1r0 mm Flexural Tensile Sfrength, f, 0[Pa
ængth 950 nm Linear Elastic Analysis Prediction o.27rlkl.l
DensiW 1800 ks/m' Rigid Body Analysis Prediction 0.4061k1:{
STATIC PUSH TEST - MID HEIGIIT POINT I]OAD
0.45

0.4

-{tsEXPERIMENTAL FORCE (H{)


z^
,4
0.35
--+RIGIDBODY (kN)
IF 0.3
o
Á o.zs
ú
F r
/ \* -\
fr o.rs
Fl o.l
MORTARDR )POUTREDUCIN( THE
\-\
EFFECTTVB \ .IDTHOFTHE RIC DBODY
0.05

0
0 20 40 60 E0 100
MID-ITEIGHT DEFLECTION (MM)

Figure F 7- Static Push Test - Cracked, lfOmnr, No Overburden

SEPTEMBER93 ÉIeieht 1.485 m Applied Overburden 0.IíllvfPa


SPECIMEN 11 Ihiclness 110 mm Flexural Tensile Strength, f, 460lWa
læneth 950 film Linea¡ Elastic Analysis Prediction 4.82121kt{
Density I 800 ks/m' Rigid Bodv Analysis Prediction 5.3rólkt¡
STATIC PUSH TEST - MID IIEIGIIT POINT LOAD
6

.Hh\¡r
5 -$r:!.-:
2
FORCE (kN)
F
4 --#RTGTDBODY (kN)
zf¡ì r' - LINEAR ELASTIC

É J
Ø
FI
ú
\

F
s ÏTIAT OF RIGtr DUE TO INCREAS] D STATIC
DEFLECTION C FOVERBT]RDEN SI RINGS FOTJND
I

0 20 40 60 80 100

MID-HEIGHT DEFLECTION (MM)

Figure F E - Static Push Test - Urrcracked, 110mnr, 0.l5Mpa Overburden

278
APPENDIX F : Out- of-plnne Simply Supported Wall Test Results

SEPIEMBER98 Heisht t.48slm epplied Overburden 0 MPa


SPECIMEN 12 Thickress 110k¡l'm Flexural Tensile Srength, f, 460 kPa
tænsttl 950hnm Linear Elastic Analysis Prediction 2.ø4 KN
Density 18007ù;s,lm Rieid Bodv Analysis hediction 0.406 KN

STATIC PUSH TEST - MID HEIGTIT POINT LOAD

t.5

2
€ 2.s
l-----' ---l
E
F
ZJ
t¡.]
É
F
FORCE (kN)
a) -ì-E)GERJMENTAL
---{-RTGTDBODY (kN)
¡ 1.5
ú - €- LINEAR ELASTTC (kÐ
tq
t-< I
J

0.5
t-ù--L*
0
0 20 40 ó0 80 100
MID-HBIGHI DEFLECTION G/rvf)

Figure F 9 - Static Push Test- UN-cracke{ 110mm' No Overburden

SEPTEMBER9S Heisht 1.485 Aoolied Overburden a MPa


SPECIMEN 12 Ihicloess lIlln¡rî Flexural Tensile Strength, f, a kPa
Længth 9501l¡¡Ít Linear Elastic Analysis Prediction 0.271 KN
I Risid Bodv AnalYsis Prediction 0.40ó KN

STATIC PUSH TEST - MID HEIGÍIT POINT LOAD

0.45

o.4 (kN)
-^:I-Ð0ERIMENTAL FORCE
0.35
\-, --!-RTGTDBODY (kÐ
2
ú 0.3
t-
(, I
zt¡¡ o.25
d
Fr
o o.2
,l
d 0.15

f
ti
0.1

0.05

0
0 20 40 60 80 100

MID-TIEIGTIT DEFLECTION (MM)

Figure F 10- Static Push Test - Cracked, llûmrn, No Overburden

279
APPENDIX F : Out- of-plane Simply Supponed WaII Test Results

SEPTEMBER93 Heieht l.485lm Applied Overburden 0lMPa


SPECIMEN 13 fhickress ll?h¡tm Flexural Tensile Srengú, f, 460Wa
ængth 950 Linea¡ Flestic Analysis Prediction 2.64418N
Density I80Ìks,lm' Rigid Body Analysis P¡ediction 0.'l06lkl-I
STATIC PTJSH TEST - MID HEIGTTT FOINT T.OAI)
5

F------
2.5

2
é l : TEST (I) - I]NCRACKED E}PERIMENTAL FoRG (kN)
F<
(J
zl¡J -{I-RIGIDBODY (kN)
Í

r.s
- rr - LINEAR EIASTTC (kN)
-.¡

É,
f
0.5

=ÞH--

0
0 2A 4 60 80 100

MIDHEIGTIT DEFLECTION (MM)

Figure F 11- Static Push Test - Uncracked, f10mn, No Overburden

SEPTEMBER93 Height 0lMPa


SPECIMEN 13 Ihichess 110 Flexural Tensile Strengü, ft 0[rPa
L,engtlr 950 Linear Elastic Analysis P¡ediction 0.27lkl:{
Density I Rigid Body Analysis Prediction 0.4MlkÌ,t
STATIC PUSH TEST - MID HEIGÍTT POINT LOAI)
0.5
(l) 90úm TIYSTERESIS EKPERIMENTAL FORCE (KÐ
0.45 -ôTEST
+TEST (2) TOmm IIYSTERESIS ÐPBRIMENTAL FORCE (kN)

o.4
'+TEST (3) sonm I{YSTERESIS Ð{PERIMENTAL FORCE (kN)
(4) 3onn HYSTERESIS EXPERIMENTAL FoRCE (kN)
2 o.ts o TEST(5) 10m IIÍSTERESISEXPERIMENTALFORCE (kÐ
TJ +.RIGIDBODY
H o,
2 o
po.zs a

i ,f
F
Ø
cd 0.2

I
H o.rs

0
-rbì
ñ.Ì
I
0.05
."tìiìl
-.\
0
0 20 40 60 80 100
MII}HEIGHT DEFT.ECTION (MM)

Figure F 12- Static Push Test (Hysteretic) - Cracked, ll0rrun, No Overburden

280
AP PENDIX F : Out- of-plane Simply Supp oned Wall Te st Re s ults

SEPIEMBER9E SPECIMEN 13 - RF,SONANT ENERGY LOSS PER CYCLE

INPUTDATA

Euz ENERGY DTSIPATED IN HAIF CYCLE OF ACTUAL STRUCTURE


E¿ ENERGY DISIPATED IN FULL CYCLE OF ACTUAL STRUCTLIRE
A ACTUAL MAX VIBRATION AMPLITIJDE

DEFIN]TION OF EFFECTTVE STIFFNESS

Àr EFFECTTVE MAX YIBRATIONAL AMPLITUDE


F"r EFFECTIVE MAX RESISTANCE FORCE
Çn EFFECTTVE CYCLE STIFFNESS
Ero STRAINENERGY
Pti DAMPING RATIO FORMAX VIBRATIONAL AMPLITUDE

DESCRIPTION E¿¡2 E¿ 4n Fn IÇn E- P*i A


N N IItm N N/mm Nmm mm
MAXDISP.90 8213.61 16ø'27.23 40.00 220.4O 5.50 44{n.00 29.717o 90
MAXDISP. TO 4026.40 wsz.79 35.00 2110.00 6.57 402s.00 15.X27o 70
MAXDISP.50 2946.6 5893.32 32.00 2s0.00 7.8r 4{n0.00 l!.72?o 50
MAXDISP.30 t761.6 3523.3t 18.50 285.00 15.41 2ß6.?,5 10.Ø7o 30
MAXDISP.lO 68835 1376.70 6.00 3z).00 53.33 960.00 ll^.4lVo l0

DAMPING RATIO USING RESONANCE ENERGY LOSS PER CYCLE METHOD

35.07o

30.O7o

À 25.01o
o
F 2O.07o
,/
ú
(5
zF _/
* 15.0%

H 10.0%

5.0%

0.07o
0 l0 20 30 40 50 ó0 70 80 90 r00
MÆ(MIJM CYCLE DISPLACEMENT (nm)

Figure F 13- September9S Specirnen 13 - Resonant Energy Loss Per Cycle

281
APPENDIX F : Out of-plane Simply Supported Wall Test Results

SEPITMBER9S Heieht 1.485 m Applied Overburden 0lMPa


SPECIMEN 14 Ihickness 50 mm Flexural Tensile Strensth, f, 0kPa
.eneth 950 nm Linear Elastic Analysis Prediction 0.0711k1.1
Density x0a kslm' Rigid BodV Analysis Prediction 0.t07lkt'I
SÎATIC PUSH TEST. MID HEIGTIT POINT I-OAI)
o.t2
0.11 -f-EXPERIMENTAL FORCE (KN)

0.r -. - AI.TEtrI DINAII,ÍIC E,PERIMENTAL FIoRcE (kÐ


2 0.@ +FRIGIDBODY (KÐ
é
, 0.0E

0.07
a
4 0.06
F
Ø
,l 0.05
d TO DYNAMIC TESTING
t¡¡ 0.04

f
H
0.03

0.02

0,01

0
0 5 10 15 20 25 30 35û4550
MID,HEIGIIT DEFLECTION (MM)

Figure F 14 - Static Push Test- Un-cracked, 110mn, No Overburden

SEPTEMBER9E Heisht L485 m Applied Overburden 0.15lMPa


SPECIMEN 14 lhiclness 50 mm Flexural Tensile SEength, f, o[<Pa
ængth 950 mm Linear Elastic Analvsis Prediction 0.47rlkl:{
Density 2300 ksÍn' Rigid Bodv Analysis Prediction 1.M^kl,I
STATIC PUSH TEST - MID IIEIGTIT POINT LOAD
t.2

t.-.
I (1) - AFTER DYNAMIC ÐGERIMENTAL
2 _ FORCE (kN)
?-RIGIDBODY (kN
Éot
(']
zr¡¡
É
Ø
o.ø -F
È-

ft
-t
tF o.t
Å -\
,l
0.2
*\
0
0 5 10 l5 20 25 30 35 40 45 50

MID-MIGIIT DEFLECNON (MM)

Figure F 15 - Static Push Test - Cracked, 50mrq 0.15MP¡ Overburden

282
APPENDIX F : Out- of-planc Simply S upported Wall Te st Re sults

SIMPLY STJPPORTED URM WALL RELEASE ÏEST RESTJLT PLOTS

SEPIEMBER 98 -Specimen (10) - Release Test (1)


MIDIIEIGHT RESPONSE DISPLACEMENT
50
40
\
30
f\
ê20 ^
9ro /t
F
Zo ^ Ân^^ I
^
l\^^.--
É -to
/{ bl"r- c'' ìo Bv-'ê - o 'l ohov l"U{"-:n q n q,
(J I
<
È -20

Ø¿o
â I
40
-50
F- l"-. TIME (Secs)
60

MII>HEIGHT RESPONSE ACCELERATION

0.2

0.r5
lr . . I r À¡ À I r, À I

d) 0.1
I I I I tlil
ll v
z I /\- I
o 0.05
F-
0
Itlllllllfltñl I ilil il ilIil i, ". .- I ililt iililt H

ú 4 o
t¡l
J {.05 a J
t!
I
U 4.1
ñ

I
,lilll ! ,llll I
lf
415
I I' fr l"
'
4.2
TIME (S€cs)
4.25

MIDHEIGTIT }IYSTERESIS

z DI'E TO ANGLE OFWALL


o OFFSET Æ,RO
F- INFLIJENCE ON ACCELEROMETER
ú
f¡l
J
t¡l
(J
?o
F

f!
,{,
H

MIDHEICTIT DISPLACEMENT (mn)

Figure F 16 - Release Test (1) - 50mnu No Overburden

283
APPENDIX F : Out-of-plnnz Simply Supported WaII Test Results

SEPTEMBER 98 -Soecimen (1) - Release Test (2)

MIDIIEIGIIT RESPONSE DISPLACEMENT

60
50
â40
à
>30
Ito
Ëto lt^ I .Âl^^-. . . . . . . . .r. . . .
a

üo €\ çllJll6'ä o ; .i æ ,J K" cìO\\ON ¡v


. -Â-e"--
r r
S æ
À
-ro
OF ÑVÑ ç*n€ I
r
'tt--.
qr(þ 6
-a o
É o
È ol N
*
vn€r"UL
â"0 V
-30
40
-50
60 TIME (Secs)

MIDI#IGHT RESFONSE ACCELERATION


0.25

l.,L
0.2
015 I I l,,L t¡ I ¡
i
o0

z 0.1
I I I illt a

I ililt
I
F
F 0.05
^r.
d 0 \+ A rt Å¡. I +
lK"ä
f¡l
J t ar\ .(

(.)
U {.1
4.05
I'il I I II |'iil
ÊÉÈ É
til fF
I I
4.r5 ,,tll
ll
t' r | , IT I
4.2
TïME (Secs)
4.25

MIDHEIGIIT TIYSTERESIS

g
zo
l4*
F
d
t¡l
t¡¡
WN
f/ \Y..
U
(J
/
-
t¡l
ts -
é

MIDHEIGHT DISPLACMENT (mTq)

Figure F 17 - Release Test (2) - 50run, No Overburden

284
APPENDIX F : Out- of-plane Simply Stryported WaII Test Results

SEPTEMBER 9E -'Snecimen (1ì - Release Test (3)


MIDHEIGIIT RESPONSE DISPLACEMENT
60

\
50
ê¿o
\
930 ^
F lì
Zzo
H
¡ I
ãro
?o
J
r+ A + .lh^-.
lJ,i
à-r0 oÈÈ eì to$hhrr ææ N (r çr Y Fd
a_20
-30
40
-50
TIME (Secs)
60

MIDHEIGHT RESPONSE ACCELERATION


I
0.8
O o.o
rl I ¡l
l,
3
F
o.o
I I ¡

1 0.2
I I I ¡ I

ú
Bo
Í!
I4.2
< 4.4 t--. I lËËdtdt

4.6
I
I I
-0.8 I
I TIME (S€cs)
-t

MIDHEIGIIT ITYSTERESIS

IzF ltr
tr?\
&
f!
J
r{
9a
O

ti


L
H :-É?-
//D-
//flr^: MIDHEIGHT DISPLACEMETNT (MM)

Figure F 18 - Release Test (3) - 50mn,0.t75MPa Overburden

285
APPENDD( F : Out of-plnne S imply Supp orted WaIl Te s t Re s ults

SEPfEMBER 98 - Specimen (111 - Release Test (4)

MIDHETGHT RESPONSE DISPLACEMENT


90
80
70
g 60
50
F
2 40
30
Ë It
t¡l 20
U ^ l ^
10 n
J
À
.t) 0 .+
â -10 L----9
v
-20
-30
40
-50
v v
50 TTMF ISFI.SI

MIDHEIGHT RESPONSE ACCF'Í FR{TION


0.4

lr lr ¡
0.3
6
> 0.2 I I 1l1
o
ã o.t
/ I ! I . r... J
d
3o
ql
t+
I
fV

(J v 6 I

r ïl'
? 4.r
I

¡rtl
4.2
Fl
{.3 I
TIME (SECS)
4.4

MIDIIEIGHT ITYSTERESIS

z
L
k
ú
t¡¡
J
fIJ
U
?o
F-
(5 40 -20 20 40 60 80

=
MIDHEIGIIT DISAACEMENT (rnn)

Figure F 19 - Release Test (4) - 110mn, No Overburden

286
APPENDD( F : Out- of-plme Simply Supported Wall Test Results

SEPTEMBER 9E -Specimen (111 - Release Test (51


MIDI{EIGITT RESFONSE DISPLACEMENT
50
,t0
Â
30 ^ ^
€zo
910
zo
tr
f¡ì ra
I .lI¡.^-..... .... ..J
oæl- ü
I .Ân..-..... - -1 .......
ô¡€
t.t
> n
f¡l
_10
;a
c c.¡
T--E---Y-
þr , c¡ ct
220
d-30
?4
H
-50
60
-70 I t
-80
_90 TIME(SECS)

MIDIIETGTÍT RESPONSE ACCELERATION


0.4

0.3
¡ln i, l"

ô
e o.2
il il1,. I t l,l l¡
zo
F o.r
á i
3o ll,
lì".
tI] óær
I II t V¡

f
8 ¡.r It.'\ -,i+ I ll äd r
l \
I
I
I

r
I
4.2

{.3
I IY II' vt
I u lf '
TIME (SECS)
4.4

MIDIIEIGHT ITYSTERESIS

\
zo

U
-l
t-
d
t¡l
J
t¡¡
U I
?o ^1
I
ts 0 -10 t0 30 50
()
\ Ã /Æ
&W
H
.{
H
\Z
MID'HEIGHT DISPLACEMENT (m)

Figure F 20 - Release Test (5) - 110mrn, No Overburden

287
APPENDD( F : Out-of-plnne Simply Supported Wøll Test Results

SEPIEMBER 98 -,Snecimen (11) - Release Test (6)


MIDHEIGIIT RESPONSE DISPI-ACEMENT
50
40
â30
E
920 /\
210
go
à
I4¿o
-r0 O\C
:-YT
oc
ol
i5 o
ôô¡aæ-
úT<--tl
+*qidJ ,d '\Ë
¿vx.æææ Ë r

à¿o
ã¿o
-50
60
-70 ü
TrME(SECS)
-80

MIDHEIGTIT RESFONSE ACCELERAIION


o.4

0.3 I
I 0.2
V

0.1 rl t
0 + + r! -h ç t- r¡T -\ tT
4.1
o\o ¡: o
^1
o\ o¡
f r û
q1 !
!t
r I a I6
F-
(

4.2 I IV'l liU


^
iltr '
4.3
'/V \J
il
TIME (SECS
4.4

MIDIIEIGHT ITYSTERESIS

IfrFT
o
z

(r/
F ^
å
r¡l
FI
f¡.1
(J
U a
t<
(,
H
Á
E

MIDHEIGHT DISPLACEMENT (nrn)

Figure F 21 - Release Test (6) , lfOmrn, No Overburden

288
APPENDIX F: Out-of-planc Simply Supported Wall Test Results

SIMPLY SUPPORTED I]RM \ryALL PULSE TF.ST RESI]LT PLOTS


SEPIEMBER 9E - Specimen (L0l - 05IIz Half Sine Displacement Pulse

55
50
-INSTRON
45
40
35

eil
30

Írs
2to I /t
Es tl I tt,t
Éo /li\^ I VIn^,- -^-J .l

9-5
j -r0 O\n;ó
I
É1, ll Vi Q I dì l;Å: ^il l^i tL :IJU
à -ts -lt- |
tt
ã -zo ttt
I

_25
tt t
-30
:35
lt
40
45
-50
-55
60

WALL ACCELERATIONS BWA


0.6 -TWA
0.5
o 0.4
z
o 0.3
t- o.2
á
¡
0.1
f¡l
0
E
(J 4.1
r â
4.2
-0.3
4.4 rrr'¡! \vLvul

4.5

0.3
-TABLEA
o.25
g 0.2
I
v
F 0.15
F
I
á
gl 0.1
J
fI¡ 0.0s
(J
(J ¡^- -.1 .l t^ I I
iprx.*ilt
I

{.05
0 f
e{9 cì
I u lK q ö'l H i,--*. s q
oÈÈN oËhh c- r oo ?'-l = -¡lrw li
4.r TIME (SECS)
4.15

Figure F 22 - OSHz Half Sine Displacenænt Pulse, 50mm, No Overburden

289
APPENDIX F: Out-of-pløw Simply SupponedWallTest Results

SEPTEMBER 98 - specimen (10) - 1.0H2 Half sine Disolacement pulse

50
45
40
35
30
9zs
¿20
F15 rl
ì¡
lr
l¡l
ãto
à{ I lt t. tl
I

lllr. Iilr.
?9
t¡¡

d-)
Ia -10
l[l tvl !,

Ï
-ts U tv v
I
:20
_25
I
-30
-f5
40
45
-50

WALL ACCELERAIIONS G)
BWA
0.3
0.25

c9 0.2
2 0.15 ¡ I

F
H 0.1
á
t¡l
0.0s
tJ.
,.1 0
l¡J .ll'
U 4.05
U
{.1 a.ï ,tt
FNæO\OÊd
H-ÈÉe^¡olN
4.15 J
4.2
4.25 TIME (SECS)

INPIj"T ACCELERATIONS

0.25

0.2
-TABLEA
è¡)
I
tl
I
z 015
F 0.1
F
ú 0.05
f{
J -t I^ I ...t lL-
H 0
c.)
() {05 o¡ r t- t
o cì
-0 1

{.15 T
TIME (SECS)
42

Figure ß 23- l.0Hz Half Sine Displacenrent pulse, 50mÍ¡ No Overburden

290
APPEND IX F : Out- of-plane Simply Supp oned Wøll Te s t Re sults

SEPTEMBER 98 - Soecimen ((10) - 2.0H2 Half Sine Displacement Pulse

DISPLACEMENTS

25
-INSTRON
20
I
l5
I ^ rl
10
â
àJ
I I lt
à ^
YO t- +
2< Ë
Yñ r;
q
;ld \o (
þ Ê
ñ -10
? -rs
v I
v
V lt
J -20
à
ã¿s V
-30 U U
:35
40
45
-50
TIME (SECS)
-55

WALL ACCELERATIONS BWA


0.4

0.3
è0

z 0.2

F ft
k 0.1
d
fI¡
J 0
f¡ì
(J
æ I e^¡ o\

U -0.1
T
4.2
TIME (SECS)
4.3

INPT]T ACCEIÆ,RATIONS A
0.5
0.4
-TABLE
I
Ð 0.3
zo 0.2
I l. I

F 0.1
Ir I
ú
Í¡l
Jqì
U
0
4.r
o\ *
O
4.2 I
{.3 I
4.4
I Tnvß(sgcs)
-0.5

Figure fA - z,OHz Half Sine Displacerrænt Pulse,50mn¡ No Overburden

291
APPENDIX F : Out- of-plane Simply Supported Wall Test Results

SEPTEMBER 98 - specimen (101 - 05Hz Hatf sine Dispracement pulse

15
10
-INSTRON
5
0

^-5 cq
ã -ro
ô -ts
L
2 -20
B -rt
Fì -30
<
J--
-?5
ù40
ã45
-50
-55
50
{5
:7O
-75
-80 TIME

WALL ACCELERATIONS
_.ITVA BWA
I
0.8
ä)

á 0.6
Jr Ll,
H
I

0.4
F
;lSü
â 0.2
3o 'sl
u

() 4.2
eloh
e9 r a1':
Ê d,r
É
rll o
4.6
I I
{.8
I
-l

INPUT ACCELERATIONS

0.5
-TABLEA -FRAMFA
è0 0.4
z

0.3
F
F
0.2
d
t¡ì
J 0.r
tI]
U
(J 0
I t L ) I
L-

É æ
-0.1 ó
4.2
TIME (SECS)
4.3

Figure F 25 - 05Hz Half sirc Displacenrent pulse,50mnu 0.û75Mpa overburden

292
APPENDIX F : Out- of-plane Simply Supp orted WaIl Te st Re sults

SEPIEMBER 98 - Specimen (10) - 1.0H2 llalf Sine Displacement Pulse

- - TWD

J5 -INSTRON
30
25
i
20
^15
ãro I
¿ ll t I I lt L I
:)
h

g-5
à
tJl -lo
(J
< _15
d -zo
â -30
-rt
-35
40
45
-50
-55 rrMË, (sbr.-s)
ó0

WALL ACCELERATIONS BWA


I
0.8
^ o.e
€9
z
o 0.4
E 0.,
fio
d o.z
,.

cl
H.o
{.6
{.8
-l
-1.2

INPUT ACCELERATIONS .-FRAMEA


0.6 -TABLEA
I
0.4
d) I
rl
z 0.2
I I I

F 0
d \o
H 4.2
J
ç¡¡
I 4.4
O
-0.6

{.8
TIME (SECS)
-1

Figure ß 2çl.OHzHalf Sine Displacenænt Pulse, 50mnu 0.075MP4 Overburden

293
AP PEND IX F : Out- of-p Inne Simply Supp oned WaIl Te st Re sults

SEPTEMBER 98 - Specimen (101 - 2.0H2 Hatf Sine Disolacement Pulse

-' - TWDm
45
40
-MWDmm -INSTRONT¡n
35
30
^î<
¿
>20
¡- 15
Éto
à<
?0
Í¡¡

d-5 F
2 -10
ê -ts
-20
-25
-30
-35
40
45

WALL ACCEr-ERATTONS G)
BWAg
I
-TWAg -MwAg
@os
z
o
Eo
ú ôl ææ\o
vl.jeìo\ oqqñq
tlc.¡€æ
oo
rI¡
J ÊN di-1n
.+* \orr
8{5
(.)

-l
TIME(SECS)
-l 5

INPUT ACCFT F'RATIONS

0.ó -TABLEA -FRAMEA


I I

ll
è0 0.4
z o.2 I
F
H
ú 0
I
hl'u^ - -. ^^.rl t
Í¡l u
J il \o
t¡ì
(J
U
4.2

4.4
r ï'

{.6 I
TIME(SECS)
4.8

Figure ß 27-2.OHz Half Sine Displacennnt Pulse, 50mnr,0.075Mpa Overburden

294
APPEND IX F : Out- of-plane Simply Supp orted Wøll Te st Re s ults

SEPIEMBER 98 - Specimen (10) - 3.0H2 Half Sine Displacement Pulse

'_ __TWDm
45 -MWDm -INSTRONnm
40
35
30
^25
3ro
ãrs
ãro t\^ n
t! tl /\.n l t\l\^^.
?0
J-5 It d
^
6 6
alñnYrti!
6 LII"V;"
Fì\¡QI
¿ i
E!
Iâ -ro
Â.
V
++! lh h h 6

-ts
-20
:25
-30
-35
'40 v

45

WALL ACCET.ERATIONS BWAg


I
-TWAg -MWAg
o
0.8
0.6 ^ I ¡ il

v 0.4

ft
Ä

'ìt
I

F I

'\
;': ¡
À-
to
o.z
,{
fIì
it
a .¡l
Â

il rd¿
'it ,'-v I a j.¿ V"v]--
Eì 4.2
H ¡.¿ I
j'l/i¿ N
I
"{ ;i oçç.
"\,t
Y ¡.u
-0.8
l/
-l TIME (SECS)
-1.2

INPUT ACCEIÆRATIONS
Ag
0.8 -TABLEAg
I
-FRAME
0.6
¡t
o o-4

a
A
o'2
t<^ *ç-.-'e -s-'i" ll,-n^^¡a,¡a^,^-,
d l4'ç ï ï"e- ü :
vs 'q
ã 4.2
K LU
J ôoo ôlcìoo o{É hhhn\o
8
(J
q.4

I
4.8 TIME (SECS)
-1

Figure F 2& 3.0 Hz Half Sine Displacenrent Pulse, S0mrr¡ 0.075MPa Overburden

295
APPENDIX F: Out-of-planc Simply SupportedWall Test Results

SEPTEMBER 98 - specimen (101 - L.0H2 Hatf sine Displacement pulse


DISPLACEMENTS _--ITID mr
25
20
-MWDm -INSTRONm
l5 ,l
10
rÀ Âil
ln,[^
5 I ¡t ¡l¡t
Àr ^Ì.n
Ul.n . _lln ..
;-\
à I l1n I
Jlv- ;-fvI
0
i"
Ì1

F. -5
H, t' r V ô llÁl/ -
-'^.\ v.
F
2 'õjü ...¡ ...:
:, r.
cìjcl
r:
N
o
c ç{!tq
-.
ô9\O
I -:
-
-10
tv
14
à
Irl
(J -15
-20
J
À
(h -t{
â -30
35
40
45
-50
-55
{0
45

WALL ACCELERATIONS
BWA
1.5

I
g
é
F
o.t
F
4
d0
t¡l
J a) ql
lll o
I4.5 o

-t
TIME(SECS)
-1.5

INPUT ACCELERATIONS
Ag Ag
0.8
-I'ABIÆ -FRAME
0.6
o 0.4
2
t
z o.2 t
k
d 0 l
t¡l
J
ql 4.2
of 'ð-o .; ..': .j¡f ñ cr
t
U or \o<j't rrood
U 4.4
4.ó
I
T
4.8
TIME (SECS)
-1

Figure ß 29- osHz Half sine Displacenænt hrlse, 50mnr,O.l5Mpa overburden

296
APPENDIX F : Out- of-plnne Simply Supp orted Wall Te st Re sults

SEPIEMBER 98 - Specimen (1.01 - 1.0H2 llalf Sine Displacement Pulse

*_*_TWDm
45
40 -MWDm -INSTRONm
35
30
25
a2o
¿1< tt
310 tttì
t-s Jla l n^
^ n I I Il r
ãó r ILllt/\^e
l-s -I-yÑ].=*-Y.E".ai
O\cìnaÒ Ê lk Att r o õ
I
(
t
.ltlÍr-
I I't' t,
ô õ
E -ro ,(r v F- tf
< -r5 v
d -zo
2:25
â -¡o
-35
40
45
-50
-55
50 ù
45
-70
-75

WALL ACCELERATIONS
BWAg
1.5 -TWAg -MWAg
€9 I
v
Fr 0.5
I ¡ A¡ /1 i tt t I ¡ il flh I /1i i
á il/ I

t4
J 0 ti-+ lr
E ìl h 6

ïli
(J l:
{.5
I'lrT { I !
rv
r
-1 'l
r
TIME (SECS)
-1.5

INPIJT ACCELERATIONS
Ag
0.6
I
-TABLEAg -FRAME
0.4
@ o.z
,l il I À

z ,1.
9o
F llr
Àr I ¡

WI fI
¡.

q.z
á,
f¡l lr(P tf cl'+¡"- o o ç {l f $f lüi r'n n t{ ? !$." ræ0(
d.o
ú ¡.0
v

4.8 I I I
-1
TIME (SECS)
-1.2

Figure F 30- f.0Hz IIaIf Sine Displacenrcnt Pulse, sOrrun,0.15MPa Overburden

297
APPENDN F : Out- of-plnne Simply Supported WølI Te s t Re sults

SEPTEMBER 98 - specimen (10ì - 2.0H2 Half sine Dispracement putse


DISPLACEMENTS
_INSTRONnn --._, .TWDmm
25 -MWDmm
20

15

e 10
2
I
fl
5
F
z
^/t
rJ;;; Â^
I
g
,ul
A ^l I
,l{- F;
0
E ñl dit-
d
N :ì// Ë ^-dj
;V r Ét c.¡ €
' ''
-5 di d,Á
v
J
CL
Ø -10
11 l
o \
-15

-20

-25
Vr

-30
TIME (SECS)
-35

WALL ACCELERATIONS
BWAg
1.5
-TWAg -MWAg
I
c9
v
F 0.5
ts
ú
r¡l 0
J
f¡l
(J
hôt
r n r
o
tt
r \o h
(J 4.5 \ô

-l
TIME (SECS)
-1.5

INPIIT ACCEIÆRATIONS

0.6
-TABIÆAg -FRAMEAg
o.4

o¡ nrt
r
ç
C
O N R o fn I

O
{ {.0 f, I

-0.8
TIME (SECS)
-1

Figure F 31 - 2.0H2 HaIf sine Displacenrcnt pulse, 50mrr,0.15Mpa overburden

298
AP PENDIX F : Out- oJ-pløne Simply Supp orte d Wall Te st Re s ults

SEPTEMBER 98 - Soecimen (11.1 - 2.0H2 Half Sine Displacement Pulse

30 -II\¡STRONmm
25
2n
t5
^10
ão
F.
z -s
r
E -10
É -rs
2-?0
d-ã
2-n
Ê -35
4
45
-50
-55
a
65
:70

WALL ACCELERATIONS
'-MWAg BWAg
0.5
-TWAg
0.4

o 0.3

v 0.2
ã o.l
Éo r
d
(J
4.1
r
? 4.2
{.3
4.4
TIME(SECS)
4.5

INPUT ACCELERATIONS Ag Ag
0.6
-TABIÆ -FRAME
o.4
€9
z 0.2
o
t<
0
ú æ N \o Éo q æ
f¡¡
J 42 € ¡- r ô¡
f¡l I
C)
44 )
I
-06
TIME (SECS)
48

Figure F 35- 2.0H2 Half Sine Displacenrent Pulse, 110mrn' No Overburden

302
APPENDIX F : Out- of-pløne Simply Supported WaII Test Results

SEPTEMBER 98 - specimen (11) - 1.0H2 Hatf sine Displacement Pulse

DISPLACEMENTS

90
80
-MWDm -INSTRONm
70
60
^50
!no ^
;30
ãro t
lr
Ero t ¡
ft ,l

?0
^
t-t-

dl0
? -20 -
ô I ill
-30
40
ry v
I
-50
{0
:7O

s0
-90
TIME

WAII ACCELERATIONS
BWAg
0.8
-TlYAg -MWAg
0.6
€9
z 0.4

F< 0.2
o¿
0
3 æ
r¡l
4.2
| *r t{yFrN
ïf
C)
(J
4.4
I
4.6
TIME(SECS)
{.8

INPUTACCEITRATIONS
--FRAMEAg
0.5
-TABLEAg
OA
g 0.3 l,
z
0.2
Fr
ú 0.1
I i
f4
F.l
r¡ 0 ,t ¡ . -.-' --. .,.d ¿d"-^ .t.,....il
U tr o\ ô
= -ì : :ì :'
c) 4.1 {
4.2
é clT
t È- oif ià ñdòì

I
4.3
4.4
I rnm(srcs)

Figure F 34- 1.0H2 Half Sirrc Displacenænt Pulse, 110mn, No Overburden

301
APPENDDI F : Outof-plane Simply Supported Wall Test Results

SEPIEMBER 98 - Specimen (11) - 1.0H2 rralf Sine Displacement Pulse


DIS

55
50
-NfwDllm -INSTRONm
45
û
35
9¡o
äzs
t- 2ß
Ás
ãto
(J5
Íó
Ø-\
â -lo r
-15
-?T
-25
-30
-35
4
45

WALL ACCELERATIONS BWAg


0.4
-TWAg -MWAg
t,,
irr
0.3
o l¡ I
z
I3
o.2 f-
r.l ¡
0.1
á I
fIl
J
0 I H{
t¡l
U -0.1
U
4.2
{.3
f' lf I |Nrl r! 1 Í! TI
TIME (SECS)
4.4

INPTJT ACCEIÆRATIONS

0.3
I
-TI\BLEAg I
-FRAMEAg
à0
0.25
0.2
rl I
zo ll
0.15
t- 0.1
d
¡
Í¡l
t¡ì
0.05
0
1

U tl
U 4.05 'lü' .ì ñ ì l&; + .r r;' --r di oil HF(I

4.1
lll
4.r5 TIME(SECS)
4.2

Figure F 33- 1.0H2 HaIf Sine Displacenænt Pulse' llûmn¡ No Overburden

300
AP PENDIX F : Out- of-plnne Simply Supp orted Wøll Te st Re sults

SEPTEMBER 98 - specimen (10) - 2.0H2 Hatf sine Displacement pulse


DISPI-ACEMENTS
-- .. -TWDmn
15
-MWDm -INSTRONrm
10

i i
5
ll  il it fi ,A

0
À elhæ 1l oc.l9q ¿ -1 Aì\oGl vl0q
t< -5
óoo I nnh\o rr
zf¡l ll
l/
à -10 t
l¡,¡
C) I
J -15
À
(t)
H -20

-25

-30
I
:35
.: TIME (SECS)
-40

WALL ACCELERATIONS
BWAg
15
-TWAg -MWAg
O1
2
9
F
o.s ¡Å il ¡fl t
I'
á
f{0 I
t-
t!
(J
næ d!9q ld 1¡ì\o noq
ooo lr rr
?¿s I I ¡
I I
f

ìj
U r T

I
TIME (SECS)
-15

INPUT ACCELERATIONS

I
0.8
-TABLEAg -FRAMEAg
0.6 I
è0
¡l
zo
I
0.4
I
,k 0.2
t rlìA¡4,¡.¡"rÀ ¡1'1À.4 .-.- flt ¡r-aÅo .^ --..¡.i f,.|\ .n ¡,
; ;-"JTI
¡r l1

ï_\'ïg
I m
ú 0 ^"Â
sl
J 4.2
iY
a ç
Jtt",rl'¡i'; oO

t¡)
I Nr N ! Ì1 \Ô l, p r r r
Q 4.4
C)
4.6
-0.8
ì I
-1
-1.2
TIME (SECS)

Figure ß 32- z.OHz Half Sine Dis¡¡lacenrcnt Pulse, sùrun, 0.l5Mpa Overburden

299
AP PENDD( F : Out- of-plane Simply Supp orted WøII Te s t Re sult s

SEPIEMBER 98 - Specimen (1.3) - 1.0IIz Gaussian Displacement Pulse

DISPLACEMENTS *--=-TWDrm

25 -MWDmm -INSTRONm
20

^15
äro I
F
2
f¡¡ 5
il I
a
t tlh i
?0
r¡l I
J T a t- oqçq æ
É d
Ø-)
À iNO \ci

â I
_10 fl
!l
-15 ¡

}
-20
TIME(SECS)
-25

WAII ACCELERATIONS
Bv/Ag
0.5
-TWAg -MWAg
0.4
I I
O o.¡
I

é o.z
¡

<
L¡ I
0.1
ú
5o
ôl
t:r
lft
I l. Ër
1'.

lr \
I4' ¡.r
f¡ì , l,
|

F- lô¡ ñ
4.2
il I I
4.3 l¡ rnm, lsncs¡r'I
4.4

INPUT ACCELERATIONS

0.r5 -TABLEAg -FRAÀ,IEAg


0.1
'l I I
@ o.os
v h¡^--. JI
Fi
4.05
0
l{l: o\e{É ;-i flrll"r
-!ñ OræO\ç.
Ft

ú -elóçn\oc- 000\È ÈÈôìclclc ô{ (\ e.l


{).1
B
Íll
U 4.15
(J
4.2
4.25
4.3
TIME(SECS)
{.35

Figure F 36- 1.0H2 Gaussian Displacenrcnt Pulse, 110nur¡ No Overburden

303
APPENDIX F : Out- of-plane S imply Supported WalI Te st Re s ults

SEPTTDMBER 98 - specimen (131 - 1.0H2 Gaussian Displacement pulse

-----TWDm
45
û -MWDmm -INSTRONm
35
30
â25
À
¿n
F15
ãro
ã5
3:
Fr -J
F
H
-ro
-15
-m
_25

-30
_35
4
45

\ryALL ACCELERATIONS
BV/Ag
0.5
-TWAg -MWAg
0.4
èo
0.3
Irl I rl I I ,. I
2
o
F
F
o.2
I I
0.1
&
0 -^.i1.'i
tf
3
f¡l
c) 4.1
(-)
4.2 I NôIeìôIN
I
4.3
4.4
ll ' ln' Ir"' I lr ' I TIME (srcs)
4.5

INPUT ACCELER,A^TIONS
C
0.2 -FRAMEAg
o 0.1
¡l ¡l tl
z lL^.
9o
F
I l¿^,
{r¡\o 'l tr.r
O\OÊ
r1 r

ôì
¡ l^.1 /
^-, Õçn\o
d 4.1
cl c.¡ ô¡ N
3
IU ¡.2
< 4.3

4.4
TTME(SECS)
{.5

Figure F 37- 1.0H2 Gaussian Displacenrent Pulse, 110mrr, No Overburden

304
APPEND IX F : Out of-plnne Simply Supp orted WaIl Te st Re sult s

SEPTEMBER 98 - Soecimen (13) - 1.0IIz Gaussian Displacement Pulse

_M.WDmn _INSTRONnn -____TWDmm


70
65
60
55
50
45
È40
e35
F. 30
q2ñ
Z1<

ñ15
Yl0
J5
ào
ã-s
- -10
-15
-20
-25
-30
-35
40
45
-50

V/AII ACGT.ERATIONS
BWAg
0.4 -TWAg -MWAg
0.3
rl t l[' lr I t
o 0.2 I I
z
o
t
I
I
I I
I I
o.t
E
I

ßo
,l € \o
t¡l
g {.r
'n.2
I
{.3
TIME(SECS)
4.4

INPUT ACCEI.ERATIONS

0.3 -TABLEAg -FRAMEAC


I
0.2
4 0.r I
¡
I I i
z !-..
i-l rlT {
0 TF "
tr c- il t
ú 4.1 re.,¡o{nFæ O\ÈÊÈid e{ ôì e.l cì c.¡ ê.¡ cl o d
sr¡l 4.2
c)
O 4.3
I
4.4
I
{.5 ì
TIME(SECS)
{.6

Figure F 38' 1.0H2 Gaussian Displacenænt Pulse, 110mÍL No Overburden

305
APPENDIX F : Out- of-plane Simply Supp orted WalI Te st Re sults

SEPTEMBER 98 - specimen (13) - 1.0H2 Gaussian Disolacement Pulse

_INSTRONmm ____-_T.WDmm

60
55
-MWDmm
50
45
40
^35
ãro
ázs
s20
zt5
Ero
f¡l J
OO
d -ro
? -ts
Å -20
_25
-30
-35
40
45
-50
-55
50

WALL ACCELERATIONS
BWAg
0.5
-TWAg -MWAg
0.4
e9 0.3
¡ t" rl I L
z
o 0.2
F 0.1
ú
f¡l 0
F- o\
fJl
'-.1
(J {.1
(J s
4.2
4.3 'lI lllJl' rl
I U t', it liU
4.4
I I
TIME(SECS)
{).5

INPUT ACCELERATIONS

0.6 -TABLEAg -FRAIT,EAg


o0¿
I I ,J t
á
tr
0.,

¿o
3 o\ tr- T 9
1..
c- o\
E o.z
U
<4t
4.6
ïïME (SECS)
4.8

X'igure F 39- 1.0H2 Gaussian Displacenænt Pulse, llùûr¡ No Overburden

306
APPENDIX F : Out- of-plane Simply Supported WalI Test Re sults

SEPIEMBER 98 - Soecimen (1.3) - 05Hz Gaussian Displacement Pulse


DISPLACEMENTS _MWD mm mm -.- -TlyD mm
60 -INSTRON I
50
40
e30
I
âto l
2to
go l¡. lllflh
I
lilth. i. t.
I
.1ilf11". ,, . ,

E -ro tq
---1---F IK 9d f ¡{t';
9:Srr)
o{ ;;I r lHll';
lñ r
ød
æ o
rl
r.
il
þ
Í -zo
:t n æ' ñ cì lhr d d o o Ì1

2
ctr

â---c¡ _40

-50
I
{0
:70
-80 I
-90
TIME

WAIIACCEI-ERATIONS
BWAg

0.4 -TWAg -MWAg


0.3
rl I i

6 I I I I
Z o.z
ì
F
¡ì
0.1

*o
Fl
I
o o\
IO ¡.r ô.t cì ôl
< 4.2 il' fl"'

{.3 ll
rnrlSnCS¡l I

4.4

INPUT ACCELERATIONS

0.3 -T'ABI.EAC -FRAMEAg


0.2
6 I
á
o
o.t
I I

È-O ,{tr,,
\o el
r-.'9
sf
'llr!l-.....''.''.''',.'
Èho!+o ôt€o
/i -.,: cì
æeì F- F
;io*'^
ü"o".
E o.t
-i--..:Èi,
v
t¡l
8 {.2 f
I
4.3

4.4
TIME(SECS)
4.5

Figure F 40- 0.5H2 Gaussian Displacenænt Pulse, 11ùûn' No Overburden

307
AP PEND IX F : Out- of-planc Simply Supported Wall Te s t Re s ults

SEPTEMBER 98 - specimen (13) - 05Hz Gaussian Displacement pulse

mm mm ---'--TWD mm
100
90
-MWD -INSTRON
80
't0
^60
Ès0
3n
230
Ëro
t¡¡ l0
Vo
d -ro
â -30
-ro

40
-50
{0
:7O
-80
-90

WAII ACCELERATIONS
BV/Ag
0.5
-TWAg -Mlg
€9
0.4
0.3
lrr I rl ¡, I
z
o 0.2 ll I I
H
0.1
ú
0
3
t¡l
O 4.1
O F-
4.2
I q I
{).3
I ì{
trr l,

4.4
4.5

INPUT ACCELEKA*TIONS

0.3
I
-TABLEAg -FRAMEAg
0.2
ô 0.1 ¡ ¡ ,l
z
o 0 å.\1a., ,, ,J I E¡Lh,¡¡ . .lil l¡-' .
r'lf-.F.r''
¡-
,

ts 4.1 R' 09sc¡9c¡ æ È- H K''äi' =Êc¡o çtn\o


'

ú el(îr\oræ Èôlelô¡e ô¡c¡e.¡ct


f4 4.2
È
t¡l
U 4.3
U
4.4 I
{.5 f
I
4.6
TItr4E (SECS)
4.7

Figure F 4f- 05IIz Gaussian Displacenænt Pulse, llùrun, No Overburden

308
APPENDD( F : Out-of-plane Simply Supported WalI Test Results

SEPIT,MBER 9E - Specimen (13) - 05Hz Gaussian Displacement Pulse

-__TWDmm
90
80
-MWDmn -INSTRONmn
70
60
50
e 40
É 30
ã
z 20
l0
trl 0
(J -r0
J -20
r
o"
9 -30
H 40
-50
{0
-70
-80
-90
-100
-r r0

V/ALL ACCELERATIONS
BWAg
o.4
rl. l
-TWAg -lvIWAg
tut
0.3
€9 I I

zo 0.2
1 i.l i,ì
0.1
Fr
0
,1
I ! i ,.11. ü
t:

d
5 {.1 æo\
E¡ c-
C)
(J 4.2
{.3
4.4
4.5
TIt\tE (SECS)
4.6

INPUT ACCEI-ERATIONS
FRAMEAg
0.4
0.3
-TABI-EA
6 0.2
rl
I

it J
I
rl,
I

zo 0.1
ts 0
tut ¡.L-L ù-tl.

\o æ
F+

ú 4.1
È( N v I r q
icìaìddôldôl(
t¡l ^aÈdosn9r
Þl
rd 4.2
O
(J 4.3
4.4
4.5
I I
4.6
TIME (SECS)
4.7

Figure f 42- O.sHz Gaussian Displacenrent Pulse, 110nnn, No Overburden

309
APPENDIX F : Out- of-plane Simply Supported WalI Test Results

SIMPLY SUPPORTTD IIRM WALL TRANSIENT EXCITATION TEST S

_--_-TWDmn
t20
ll0 -MWDmm -INSTRONnn
100
90
80
â 70
60
É, 50
t< 40
z
t¡¡
30
20
Ë
(J 10
0
.l -10
tu
Ø -20
-30
40
-50
-60
-70
-80
-90 WALLMID-IIEIGI{T HIT STJPPORT.INSTABILITY
-r00
-1 10

WALL ACCELERATIONS
g g BWAg
0.8
-TIVA -MWA
0.6
e 0.4
z
0.2
E
ú 0
r¡l
È 4.2
t¡J
U
(J 4.4
4.6
4.8
TIME (SECS)
-1

ACCELERATIONS

0.3 -TABIÆAg -FRAMEAg


I
0.25
O o.z
Z o:s
ã I lr r t
d
I¡t
o.r
0.05
l¡ tl f I lt I t h ¡ ¡ I t.

Bo
J

? o.os
ol-i í ìf -{l
{
4.1
I r
4.15 I
t
TIME (SECS)
4.2

Figure F 4! Transient Excitation Test - 667o E;lcentro, 110nrn, No overburden

310
APPENDIX F: Out-of-plane Simply Supported WaIl Test Results

DISPLACEMENTS
mm mm mm

t2.5 -ìr[WD -INSTRON -TWD


l0
e 7.5
i
á
F
z 5

t il {r
f¡ì
(J 2.5
J
À 0
?
H
ç {
I ô€d
Erìoq
-2.5 \(/
-5

-7.5
TIME (SECS)
-10

WALL ACCELERATIONS
BWAg

0.4 -TWAg -MWAg


I
0.3
6 0.2
¡

z
o 0.1
F 0 l
¿ Èrr
4.1
Li

3
t¡¡
oo t- c- F-
O 4.2 I
(J I
4.3
4.4
I
4.5
TIME(SECS)
4.6

INPUT ACCELERATIONS
F Ag Ag
0.4 -TARr -FRAlvfE
0.3
.:9 0.2
z I I
0.1
F
. .it l¡ I
d 0
S {).1 no\h |ll'l
fr¡
Q c)È
I
ç Sh\Ot'.€O\ÉÊ
(J
4.2
4.3
4.4 I TTME(SECS)
{.5

X'igure F 44 - Transient Excitation Test - 1ü)7o Nahanni' 110mrrD No Overburden

311
APPENDD( F : Out- of-pluc Simply Supported Wall Test Results

_MWDmm _INSTRONnn ___..TWDm


25
22.5
20
L7.5

I 15
12.5 I

r0
z
F.

g 1.5
f¡¡ 5
U
J
o.
2.5
/¡t
^./\&-
0
?
H -2.5 pr
-5
ci ¡(}
-7.5
I
-10
-r2.5
I
-15
TIME (SECS)
-17.5

WAIIACCELERATTONS
BWAg
0.6
-TVlAg -MWAg
o 0.4

0.2

c)È
4.2

4.4
TIME(SECS)
4.6

INPUT ACCELERATIONS

--FRAIvfEAg
0.8 -TABLEAg
0.6
e 0.4
z I

It- 0.2
I I ll
d ilr *... n. Jl¡1. a
,slsrK
. ì llll-'r,,À^..Jì -
3 0 rl, 'v r rl ll tuF ^
lll f h ó hl ¿\.t' h Ého\ho\ËæmF.c.¡
ÈÈÉÉ-
EI
() 4.2 ¡-i æ çi È-l i\o dir¡ç^'::jj^i
(J o cì I s v I tr æ o\
I
4.4
I
4.6
TrME(SECS)
{.8

Figure F 45- Transient Excit¡tion Test- 2NVo Nahonn¡, lllhrrnr, No Overburden

312
APPENDIX F : Out- of-pløne Simply Supported WølI Test Results

mm _INSTRONnn -"_-_TWDmm
30
25
20

9ts [,
3ro
f-
l1 ¡ fi

Ás ilft

ño
(J
ì Jo
+

S-s v,
r r
o. oôÊÈ
'iI ,x
n ls
\/
o1, lo\t-
\/¡
æ Ø q

É -to
-15
-20
_25
I
-30
TrME (SECS)
-35

WALL ACCF'I FRATIONS


BWAg
0.8 -TWAg -MWAg
0.6
oo

zo 0.4

t- 0.2
ú
5 0
r¡l o¡ eì
o\
C)
c) 4.2
4.4
{).6
TIME(SECS)
4.8

INPUT ACCELERATIONS

0.8
-TABLEAg -FRAMEAg
I
^€9 0.6
ll,
é o-q
F
F
S o.z
I il
f4
! .
E0 O\næ
^nilll
I
c.)
< 4.2 odl-j ur

I
4.4
ll' TIME(SECS)
{.6

Figure F 46 - Transient Excitation Tæt - 3û07o Nahanni, 110mn, No Overburden

313
APPENDIX F : Out- of-pløne Simply Supp orte d Wall Te st Re sults

_MWDmm _INSTRONnm .. '-_,TWD-m


30

25

20
ll
^15
äro I iT l
F / \ I
ãs :'j''
{1,
''-lll'ifl
\ t A

I
fro
l-s
or
høhæ

"
d "l/"il
, ,lr
',f+ .U
I ø r

É-r0 llv
-15

-20
-25

-30
I
TIME (SECS)
-35

WALL ACCELERATIONS
BWAg
0.6
-TWAg -M\ryAg
o 0'4
z
9
F
o.z

ú
140
J
t¡¡
U
? o.z
{).4
TIME (SECS)
4.6

INPUT ACCELERATIONS

0.8
-TABLEAg -FRAMEAg
0.6
6 It
¿0A
F o.z ¡ I ,l
d i, À¡r.,-,
30 M
O\hO\rf,æo r
ï
i:J c.¡

8 4.2
lïl " r
rl) æ q

4.4 lt,
{.6
TIME (SECS)
{.8

Figure F 47 - Transient Excitation TesJ - 4007o Naharmi, 110mn, No Overburden

374
APPENDIX F: Outof-plane Simply Supported Wall Test Results

DISPLACEMENTS
--TVfDmm
130
120 -MWDmm -INSTRONnn
ll0
100
90 l.
80
G.
70
Ê 60
ã 50
il it
z 40
E
2 30
r¡l 20
(J ¡l i
,¡ l0
ÉL 0
Ø -10
o a( ¡\ l@ l\
-20 -U-'
-30
40
-50
{0
-70
-80
-90
-100

WALL ACCEIÈR,ATIONS
BWAg
0.6 -TV/Ag -MWAg
0.4
€9
z 0.2
trL,- ,hrl ttär, lt,..lÅ., ¡l I

ts 0
d
ÍÐ 4.2
J
t¡l
U
(J 4.4
4.6
4.8
TIME (SECS)
-l

INPUTACCELERATIONS

0.3 -TABLEAC -FRAMEAg


I
^19 0.2
z
9
F
o.r

Éo
f¡l I
(.)
? o.r
I
tll
[' 'l
4.2
I TTME (SECS)
{.3

Figure F ¿|8 - Traruient Excitation Test - 67o E;lCentro, 110mn¡ No Overburden

315
APPENDD( F : Out- of-plnne Simply Supported Wall Te st Re s ults

80
-MWDmm -INSTRONñm -TWDmm
70
60
11il
50
È¿o ¡
è . rA
-30
2
il

H20 I Il/
2
Bro
lo I {t 1,1iltÀrN,
lllil{I'.ä\*^ä';/''
AJ

þ p -,.{q
-' ñ K
â¡ rf oq r'\.¡ /
:
æ t¿¡l
: F -\Þ
;t

r-" Ë 3
d
-t0
É Êdo*
t{il/ fllFì = = = = Ft--6Fã
-20
-30
I I
-40
-50
v
-60
TIME (SECS)
-70

WALL ACCELERATIONS
BWAg
0.4
-TWAg -MWAg
0.3
t¡Jl I I t
o
zo 0.2
it I rllll
F 0.1 I

ú I |l
t¡l 0
d
U {.1
(J s õ
4.2
i I 'I
N

\ I
I I

{.3
tl f Til i,

TIME (SECS)
4.4

INPUT ACCELERATIONS

0.4 -TABLEAg -FRAMEAg


0.3
€9
z 0.2
o 0.1
I

ù.¡
H
ilt
d 0
rll
J {.1 <æôl\o ç m

(J c.ìmt r
? 4.2 I
{.3
4.4
TIME(SECS)
4.5

Figure F 49- Transient Excitation Tæt - 667o Pacoirm Daq 110mnU No Overburden

3t6
APPENDIX F : Out- of-plnne Simply Supponed Vlall Te st Results

mm mm mm

80 -MWD -INSTRON -TWD


70
60
50
¡ A
40
å 30
,t I t/1 t
2
ã 20
I
ill ït ¡

z lt
¡¡l
U
sÞr
10
0
/t ilt ht lh,\
Fll+ì : 16= Y F ì.TuÞffi tì Ë ëì-
Ø -10
o ÊNo{ Þ1
àà ¡i
-20
-30
lv
v
-40
-50
-60
TIME (SECS)
-70

WALL ACCELERATIONS
BWAs
0¿
I I
-TWAg -MWAg
il¡
0.3

o o.z
¡l
z
v 0.1

fo
F-
I
f¡¡ I
d
(J
¿.r
? ¡.2
{.3
il
I I

4.4
TIME(SECS)
4.5

trNPIJT ACCELERATIONS Ag Ag
0.3
-TABIß -FRAME
o.2
I
LQ j
zo 0.1
t-
á 0
1 \o o
rq
J r êì
E 4.1
U
4.2
I
4.3
TIME (SECS)
4.4

Figure F 50- Transient Excitation Test - 807o Pacclirm Darn, 110mn¡, No Overburden

317
APPENDIX F : Out-of-plane Simply Supported WqlI Test Results

mm mm mm
100
-MWD -INSTRON -ÎYy'D
90
80 í\ WALLMID-IIEIGI{T TIIT STJPPORT - INSTABILITY
70
9oo
t
ã50
ã¿o A

l'ì 30 rì

iro
c. il I illl
I I
iÉLO
! It/ I |+{t Itl, \. .\
lq-q 4 ç ç'L'ö/-''bi;"/'i";
0
t9Qer_E iJ
"t - "q -\. Na \L/
-10
_20
iNñç
tþl
r ; J\r¡l\zãv/?r ñ = \.r àì ¡ä

^r-.,è-
t
-30 yv
40
TIME (SECS)
-50

WALL ACCELERATIONS
BWAg
0.5
-TWAg -MWAg
0.4
llr
o 0.3 'l
6
F
o.z
I tl

Id 0.1
rq0
!
E
(J
¡.r
< 4.2
-0.3
lll'
4.4
TIME (SECS)
4.5

INPLTT ACCELERATIONS
Ag
0.4
I
-TABLE
0.3
Iz o.z
IF o.t
¡ lr
So I
ñ nhhh
El 4.1
(J
4.2 1 ddN ddd

2
4.3
4.4
TIME (SECS)
4.5

Figure F 51 - Traruient Excitation Test - 1fi)7o Pacoinra Dan¡ 110mn¡ No Overburden

318
APPENDIX (G): Non-linear Time History Analysis
ROWMANRY FortranTT Code
Program rowrnanry
c lilriüen February 1999
c Program "ROWMANRY" was derived from the original progr¿ìm "romain"
c to determine the rocking behaviour of both rigid and semi rigid
c objects making allowance for various support conditions
c The main program drive subroutine is "Row-ray" which
c determines the displ. time-history of a rocking model
c using a tri-linear dynamic force displacement profile approximation
c Rayleigh damping is assumed with an iterative half cycle process used
c to ensure the proportional damping assumed at the start of each half cycle is appropriate
c at the end of the half cycle (where the instantaneous frequency is known)
c An initial damping coefficient of 3 is adopted however with the iterative process
c generally is not critical to the successful running of the program
c Uniform wall properties are assumed
c The acceleration data filename ACTIVE, time-step dt and the analysis time
c segment ta are required as input.
c The program will produce time-history arrays of the relative
c displacement u, relative velocity v, and total acceleration at
c at the top of a free standing object or mid height of a propped cantilever.
c Maximum u, v and at will be displayed on screen at run time.
c There is an option to writ€ the time-history series to a new file
c with the filename designaæd by the user (char variable ofile)-
character *50 ACTIVE,TEXT,ofile,type
character *1 yesno
character *60 code
integer NN,NTP,NT,NK,k
inæger IOS,ERL,X,Y,L
real ts(O: I 2000),as(0: I 2000)
real alpha, dt, ta, ag(0:16384)
real u(0: 16384), v(0: 16384), at(O: 16384)
real agmax,umax,vmax, aÍnax
real ke(-l: l), re(-1: l),ulirnit(-l: l),uy(-2:2),pi,g
real scale
real h,t,m
real HEFFR,ÌIEFFS, gam,PC
real a0, al, aOm, alm
c real EM,rd
real PCF
real PDM
real ulim¡b
parameter(pi=3.1 41 59265 4)
paramet€r(g=g.806)
c Rocking is independent of the mass of the object. Thus, a
c unit mass (l.Okg) has been assumed in subroutine roïvray.
m=I.0
c
writel*,*¡"*********************tc************r.*t<t *r.r.******r<*****rr
writel*,*¡" hogram ROTWMANRY"
wriæ1*,x¡" For time history rocking analysis of'

3r9
APPENDD( G: N0n-linear Time History Arutysis ROWMANRy FortranTT Code

write(*,*)" Free Standing or Simply Supporæd Objecs"


write(*,*)" LatestVersion: FEBRUARy1999"
wfitel*,*¡******************************************************n
wriæ1*,*¡" Units in length - rL time - secs, "
write(*,*)" Force - N, Density - kd^t "
write(*,*)" Stress - MPa unless shown otherwise "
write(*,*¡" "
c Inpuaing accelerogram daø into ag(t) array
write(*,*)"fype filename for accel. data [<= 8 Characters]:"
read (*,'(a)')ACTIVE
L=INDEX(ACTIVE,')
ACTIVE(L:L+4)='.csv'
c wrir€(*,2000) ACTIVE(1:L+4)
write(*,*¡ " "
write(*,*)" --- FORDEFAIJLT VALUES I I TYPE 0 ---"
writelr',*¡ " "
write(*,*)"Type scaling factor for ground accel. [1.0]:"
read(*,*)scale
if(scale .eq.0.O)then
scale=1.0
writel*'x¡ " "
writelx,*¡"-- DEFAIJLT SCALINGFACTOR [1.0] ADOPTED -- "
writel*,*¡ " '
end if
5 write(*,*)"Type time step interval dt [0.01]:"
read(*,*þt
if(dt.eq.0.O)then
dt{.01
write(*,*) " "
write(*,*) "-- DEFAIJLT TIME INCREMENT [0.01] SECS ADOPTED --"
wriæ1*'*¡ " "
end if
open(25,file=ACTIVE,staü¡s='old',iostaFIOS,ere I 000)
c Go passed 8 header lines in datafile
ERL=l
do l0 k=I,8
read(25,'(a)',iostat=IOS,err= I0I O)TEXT
ERL=ERL+1
l0 continue
c read (25,*,iostat=IOS,en=101O)NN
c ERL=ERL+I
NN=O
do 20 k=0,16384
read(25, *,iostat=Ios,er=l 0l 0,END=3) ts(k),as(k)
NN=NN+l
as(k)=5salls*asg¡
ERI=ERL+l
20 continue
3 continue
close(25)
wriæ1*'*¡ " "
wriæ(*,45) NN
45 format("NUMBER OF DATA POINTS IN INPUT prI F = ",lJ)
writel*,*¡ " "
c Data inærpolation
call linter(NN, ts,as,dt"NTP,ag)

320
APPENDIX G: Nùn-Iinear Time History Analysis ROWMANRY FortanTT Code

write(*, *) "Record time is ",rea(NTP)*dt, " seconds"


wriæ(*,*)"Type analysis time [Record time]:"
read(*,*)ta
if(ta.eq.0.0)then
ta=eal(NTP)*dt
wriæ(*,2010) ta
writel*,*¡ " "
2010 forma('-- DEFAULT : IRECORD TIME',F6.3,'secs] ADOPTED -')
writelx,x¡ " "
end if
NT=in(taldt)
if (NT.gr16384)then
write(*,x)"Required no. of time steps exceed limit of 16384"
write(*,*)"Retype longer time step or shorter analysis time"
goto 5
else
end if
if(NT.gt.NTP)then
c Augment ag(k>=NTP) with zeros
do 30 k=NTP,NT-l
ag(k)=0
30 continue
else
end if
4l continue
writel*,*¡"---
wriæ1*',*¡" OBJECTRIGIDITYCLASSIFICATION"
write(*,*)' Is the object to be analysed either :"
writc(*,*)" (Typecorrespondingnumber)"
write(x,*¡" "
writ€(*,*)"(l) RIGID eg steel library bookshelves"
write(*,*)"(2) SEMI RIGID eg simply supported URM wall"
wriæ(*,*)" parapetURM wall"
writelx,*¡"---
read(*,*) X
if(X.ne. 1.AND.X.ne.2)goto 4 1
4 continue
c Definition of support conditions
wriæ1*,x¡"
WTitC(*,*)" DEFINTTION OFVERTICAL SI.JPPORT CONDITIONS"
wriæ1*,*¡" V/hat support conditions exist:"
write(*,*)" (Type corresponding number)"
writel*,*¡" "
write(*,*)"(l) Free standing object, base reaction at LF"
write(*,*)"(2) SS non loadbearing, base reaction at LF"
write(*,*)"(l) SS loadbearing, top & bottom reactions at CL"
wriæ(*,*)"(4) SS loadbearing, top reaction at CL, bottom reaction
+ atthe LF"
write(*,*)"(5) SS loadbearing, top & bottom reaction at LF"
writel*,*¡" "
write(*,*)"where SS = simply supported"
write(*,*)" LF = leeward face of object"
wriæ1*,*¡" CL = center line of object"

read(*,*) Y
if(Y.ne. l.AND.Y.ne.2.AND.Y.ne.3.AND.Y.ne.4.AND.Y.ne.5)goto 4

32t
APPENDIX G: Nùn-linear Time History Anatysis RowMANRy FortranT7 code

c
c Inputing structural parameters
gam=O.0
c
wriæ(*,*)"Type total height of the object (m) :"
read(*,*)h
wriæ(*,*¡"Type total thickness of the object (mm) :"
read(*,*)t
t=t/1m0.0
c
if(Y.ge.3)then
c Loadbearing simply supported requires overburden sfress and density
wriæ(*,*)"Type the overburden stress at top of object (Mpa),'
read(*,*)PC
write(*,*)"Type object densiry [1800 kg/m3] :"
write(+,x)"[Masonry density approximarely 1500 - 2500 kg/m3]"
read(*,*) gam
if(gam.eq.0.0)then
gam=1800.0
wriûe1x,x¡ ' "
writelx,*¡"-- DEFAIJLT OBJECT DENSITY [l800kg/m3] ADOPTED --"
wriæ1*'*¡ " "
end if
c Calculation ofoverburden stress facûo¡
pCF=2.0*pC* lE6(h*gam+g)
else
PC{.0
PCF{.0
end if
c
if(Y.eq.1)then
type="Free standing object base reaction at LF"
c Stiffness and resistance acceleration conversion factors
ÍIEFFS=1.0
HEFFR=I.0
writel*,x¡ " "
write(*,1)HEFFS
write(*,2)ruFFR
writelr"*¡ " "
I forma(" Stiffness coefficient (IIEFFS) = ",fl 3)
2 forma(" Resistance coefficient (IIEFFR) - ",n 3)
end if
if(Y.eq.2)then
type="Ss non loadbearing G,F)"
ÍIEFFS=4.0
HEFFR=4.0
write(*'r'¡ " "
write(*,1)IIEFFS
write(*,2)IIEFFR
writel*'*¡ " "
end if
if(Y.eq.3)then
type="Ss loadbearing top & bocom (CL)"
ÍIEFFS=4.0*(t+pCF)
IßFFR=2.0*(1+PCF)
wriæ1*'*¡ " "

322
APPENDIX G: N)n-linearTime History Analysis ROWMANRY Fortøn77 Code

write(*,1)HEFFS
wriæ(*,2)IIEFFR
writelx,x¡ " "
end if
if(Y.eq.4)then
type="Ss loadbearing top (CL) bouom (LF)"
IIEFFS=4.O*(l+PCF)
I{EFFR=4.0*( 1+0.7 5 *PCF)
write(*'*¡ " "
write(*,1)IIEFFS
write(*,2)HEFFR
wriæ1*'x¡ " "
end if
if(Y.eq.5)then
type=" SS loadbearinC top & bottom (LF)"
IIEFFS=4.0*(l+PCF)
ffiFFR=4.0*(1+PCF)
wriæ1*'x¡ " "
wriæ(*,1)IIEFFS
writo(*,2)I{EFFR
writelx'*¡ " "
end if
c Apply SDOF conversion fac0or to ag which does not include the factor
do 60 k=O,NTP-1
ag(k)=1'5x¿t1¡¡
60 continue
c
3000 Continue
c Set first half cycle iteration approx proportional damping
alpha=3.0
c Set the propofional damping experimental to SDOF conversion factor
PDM=2.0ß.0
write(*, +) "Type mass proportional damping coefficienl : "
read(*,*)a0
c Modify a0 to fit SDOF model
aOm=PDM*a0
write(*, *) "Type stiffnes s proportional damping coefficient. "
:

read(*,*)al
c Modify al to frt SDOF model
alm=PDM*al
c
c Rigid body complete instability displacement (mm)
ulimrb=t* 1 000.0*IIEFFR/I{EFFS
c Side eccenEicities are t/2 as uniform properties assumed
c Calculation of the rigid body resistance acceleration
re( I )= I 5 *[IEFFR* g*t/tt
.

re(- 1)=- 1.O*re(1 )


c Calculation of the rigid body negative stiffness
ke(1)=- 1.5*tfrFFS*c/h
ke(-l)=ke(1)
c
c
c Completely rigid objecs
if(X.eq.1)then
c Setting the rocking displacements to a nominally small value (>0)
uY(l)=l.E-4

323
APPENDIX G: N0n-linearTirne History Analysis RowMANRy FortanTT code

uy(-l)=l.E-4
uY(2)=t.f,-4
uy(-2)=l.E-4
ulimi(l)=ulimrb
ulimi(- I )=- | *ulimit( I )
end if
c
c Semi rigid objocts
if(X.eq.2)tben
wriæ1*'*¡ " "
write(*,*)"Type disp.rocking expected to commence (mm)"
writ€(*,*)"(This disp. dictates the initial rocking stiffness"
writelx,*¡" and must be greîrur than zero)"
read(+,*)uy(l)
uy(l)=uy(1)/1000'0
uy(-l)=-1.O*uy(l)
write(*'*¡ " "
wriæ(*,*)"Type disp. at start negative stiffness (mm)"
wriæ(*,*)"(1his disp. dictates the peak rocking resistance',
wriæ(*,*)" plateau as it is the point of inærsection of'
wriæ1*,*¡" the semi rigid and rigid body force disp profiles)"
read(*,*)uy(2)
uY(2)=uY(2)/1000.0
uY(-2)=- I .0*uY(2)
write(*,*)"Type complere insøbiliry disp (mm) IRIGIDI"
u'dte(*,71) ulimrb
7l Format("I-ess than or equal to 'f6.2," (mm) - RIGID -")
read(*,*) ulimi(l)
if(ulimit( I ).eq.0.O)then
ulimit(l)=ulimrb
wriæ1x,*¡ " "
\4,rite(*,72) ulimrb
72 forma('--DEFAULT INSTABILITY DISP|,F6.2,'I mml ADOPTED--')
wriæ1*,*¡ " "
end if
ulimi( I )=ulimi( I Yl 000.0
ulimi(- I )=- | *ulimit( I )
end if
c
c Doing the achral computations
call rowray( l .0, alpha,re, uy,ke,ulimit NTdÇ ag,u, v,at code, aOm
+,alm)
c Finding the maximum out of each array
call fndmax(NT, I 6384,ag,agmax)
call fndmax(NT, I 63 84,u, umax)
call fndmax(NT, I 6384,v,vmax)
call fndmax(NT, I 6384,at,aunax)
c
c Oupuning the key results ûo screen(system output)
write(*,*¡' "
wnte(*,22þúe
22 format("ANALYSIS CONCLUSION : ",a60)
c If the code message does not begin with "M" for "Model"
c go straight to the end of the program.
if(icha(code(l : l)).ne.77)goûo I 100
write(*,*)"Analysis results summary: "

324
APPENDIX G: N0n-linear Time History Arulysis ROWMANRY FonranTT Code

write(*,21)"Max. rel. displ. = ",umax


write(*,21)"Max. rel. velocity = ",\'max
write(x,21¡"tax. total accel. = ",atmax
2l format(a21,1x,f9.6)
c
c Setting effective parameters back to original
uy(1)=1000.0*uy(1)
uy(2)=1000.0*uY(2)
t=t*1000.0
c
c Reporting the time-history ouÞut
wriæ(*,*)"Time-history results can be written to a file"
write(*,*)"Type y/n to indicaæ if hle is wanûed:"
read(*,'(a)')yesno
if(ichar(yesno).eq. 1 1O)goto 30 10
write(*,*)"Specify output filename [<= 8 characters]:"
read(*,'(a)')OFTÍ F
ÞINDEX(OFil-E,' ')
OFILE(L:L+4)='.csv'
c wdte(*, *) OFILE( 1 :L+4)
open( I 5,file=ofile,iostat=IOS,ERR=l 020)
write(*,*)"Type no. of time steps for every reported results"
read(*,*)NK
write(15,*)'***t *4c**********ll****r<*****'F**************d'**t'********
¡** ***** * ** **** * *r. ** * n
write(ls,*)" ProgramROWMANRY"
*,rite(15,*)" For ti¡ne hisûory rocking analysis of'
wriÞ(I5,*)" Free Sønding or Simply Supported Objects"
wriæ(15,*)" Latest Version : FEBRUARY 1999"
wriæ115,*¡"*t t<*** ****t<*******r<****t*****************t<****t *r.***1.1c
¡****** **i<* ** * ** * rc * * *rr
wriæ(15,+)"Ouþut filename : ",ofile
wriæ( 15, l7)"Accelerogram data from : ",ACTIVE
I7 format(a23,lx,al3)
wriæ(15,18)scale
18 format("Accelerogram scaling factor selected - ',f7.3)
write(15,t)'"
c Echo input data
write(15,*)"INPUT DATA SUMMARY FOR: "
write(15,*)type
write(Is,*)" "
write(15,11)h
ll format("Height of object = ",f7.3," m")
wriæ(15,13)t
l3 format("Object width = ",f7.3," mrn")
write(15,9)PC
9 forma("Overburden sEess at top of objec¡ = " ,f7 .3," MPa")
write(15,*)" "
write( I 5, *) "Tri-linear force disp profile data"
wriæ(15,16)uy(l)
l6 format("Disp I selected for initial stiffness = ",f5.2," mm")
write(15,26)uy(2)
26 format("Disp 2 selecæd for maximum force plateau = ",f5.2," mm")
wriæ(15,1)HEFFS
write(15,2)IIEFFR
write(15,*) " "

325
APPENDIX G: N0n-linearTime History Analysis ROWMANRY Fortran7T Code

wriæ( I 5, *) "Proportional damping data"


wriæ(15,27)a0
27 format(" Mass proportional damping coeff. = ",f7.4)
write(15,28)a1
28 format(" Stiffness proportional damping coeff. = ",17.4)
wriæ1t5,*¡" "
write(15,*)" "
wrire(15,22þode
wriæ(15,12) ø, dt
12 forma('Analysis time =',f7.4,'secs time inc =',f5.4,'secs')
write( 1 5, *) "Iæ gend :, ag = input ground acceleration "
write( I 5, *) ",u = relative displacement"
write(I 5,*)",v = relative velocity"
write( I 5, *) ",at = total acceleration"
write(15,*)" "
write( I 5, *)"Time,ag(m/s/s)
+,u(m),v(m/s),at(m/s/s)"
c Printing the maximum out of each array
wriæ( 15,42)"Maxim :",agmax,umax,vmax,aÍnax
42 format(a6,',',f7 .3,',',f9 .6,',',fl .3,',',f8.4)
write( I 5, *) "Tirne, ag(m/s/s)
+,u(m),v(m/s),a(m/s/s),experimental u(m)"
c Printing the time-history ¡urays
do 40 k{,NT-l,NK
wriæ( I 5,5 1 )rea(k) *dt"ag(k),u(k),v(k), at(k)
5I forma(f6.3,',',f7.3,',',f9.6,',',f7.3,',',f8.4)
40 continue
close(15)
3010 write(+,*)"Type y/n to continue analysis:"
read(*,'(a)')yesno
if(ichar(yesno).eq. 1 I O)then
goro 100
else
c Re-Setting effective parameters
t=t/1000.0
goto 3000
end if
100 wdte(*,*)"Program completed"
stop
c
c Error messages
10O0 write(*,1001)"opening file ",ACTWE
l00l format("Error in ",al3,al2)
goro ll00
I0I 0 wriæ(*, I OO2)"reading fiIe",ACTIVE,ERL
goto I100
1002 format("Error in ",al3,al2,"atline ", i5)
1020 wriæ(*,I001)"opening hle ",ofile
goto ll00
I 100 \r,rite(*,*)"Program aborted"
stop
end

326
APPENDIX G: N0n-Iinear Time History Analysis ROWMANRY FortranTT Code

Subroutine rowray(mrpcrreruyrkerulimrNTrdtragrufrvratrcoderaOm
+,alm)
c Rowray was originally derived from Rotha including a
c trilinear static force displacement relationship
c Iterative half cycle procedure to determine Rayleigh damping
c coefficient for current instantaneous frequency
c uy(1) is the initial positive rocking displacement
c uy(-l) is the initial negative rocking displacement
c uy(2) is the secondary positive rocking displacement
c uy(-2) is the secondary negative rocking displacement
c re(l) is the completely rigid positive rocking resistance
c re(-1) is the completely rigid negative rocking resistance
c ke(l) is the rigid body stiffness for +ve rocking
c ke(-l) is the rigid body stiffness for -ve rocking
ulim(l) is the +ve ultimate displacement
c ulim(-l) is the -ve ultimate displacement
c
c Declaration of parameters
character*60 code
integer NT
real m, pc
real ke(-l:1), re(-1:1), W(2:2), ulim(-l:l)
real ag(0:16384),dt
real u(0: 16384), uf(O:16384)
real v(0: ló384),at(O: I 6384)
c Decla¡ation of local variables
integer Jevenq k, j, p, e, d, X, Y
inæger f, I, I, px
real ry(-1:1)
real du, dv, da, a, dag, dps
real ktsl, ktsp, kts2
real fl,f2,f3
rcal t0,tl,AJj,t4
real pi, pl
real alm, aOm
real dpsx, dpsy, nc, jx, jy
real ay, ax
parameter(pi=3 . I 41 59265 4)
c
c Initialise conditions
u(0)=0.
uf(0)=0.
v(0)=0.
a{.
ag(O)=0.
at(O)=0.
Jevent=0
UYY=O.0
tO=O.0
tl=0.0
t2=0.O
ß=0.0
t4d).0
j{
e=0
d=0

327
APPENDIX G: NÙn-linear Time History Analysis ROWMANRY FortranT7 Code

P=O
xd)
y{
f{
I=1
px=O
code="Model did not rock"
c
5 continue
if(e.eq.l)then
c Reset time st€p at start of iteration
I=y
end if
if(d.eq.l)then
c Reset time step at start of iteration
I=x
end if
c
c open(unit= l,file='out. dat',status='new')
c write(I,*) "NT I(=x) pc"
c write(I,*) NT, I, pc
c u(k) is the displ. obtained at the end of each time sæp, and
c uyy is the displ. calculated and updated within the time step.
c Time history computation do-loop
c
do 10 k=I,NT-l
if(f.ne.l)then
c Determine pseudo-static force for each time-step except
c on iteration where returned ûo previous zeroed conditions
dag=¿g1¡¡- ag(k-l)
fl = m*dag
f2 = m*((4.*v(k-l)/dt)+2.*a)
f3 =2. * pc * v(k-l)
dps = f2+f3-f1
uyy=u(k-l)
else
c Reset flag for refurned ûo previous zeroed conditions
f{
end if
c Time sæp counter for time between zero crossings
t0=0+dt
if(dps.eq.0.0)then
u(k)=uYY
goto 25
end if
c BEGINEVENT ITERATION:
c
c Determine the dynamic stiffness profile for the
c particular proportional damping coefficient
c
c Determine pseudo-static stiffness (Jevent I rocking stiffness)
ktsp=(4. *nr(d t* * 2.))+ (2.* pc I dt)
c Rocking threshold acceleration
ry( I )=re( I )+ke( I )*uy(2)+kæp*uy( I )
ry(-l)=re( l)+ke(- I )*uy(-2)+ktsp*uy(- l)
c Determine Jevent 0 rocking stiffness

328
APPENDIX G: N0n-Iinear Time History Anølysis ROWMANRY FortranTT Code

ktsl=ry(l)/uy(1)
c Determine Jevent 2 rocking stiffness
kts2=ktsprke(1)
c write( l,*)"kts
1 ktsp kts2"
c wriæ(1,*) ktsl, ktsp,kts2
c
15 continue
c NON ROCKING (DISP INCREASING ORDECREASING)
if(Jevent.eq.0)then
du=dps/ktsl
UYY=uyy+du
c POSITIVE DIRECTION
if(dps.gt.0.0)then
c ROCKING NOT COMMENCED-NO EVENT
if(uyy.lt.uy( I ))then
u(k)=r¡YY
c STAGE I ROCKING LEVEL REAC}IED-WITH EVENT
else
dps=kts1*(uyy-uy(l))
uyy=uy(1)
Jevent=1
code="Model rocked within limits"
goto 15
end if
c NEGATIVE DIRECTION
else
U ROCKING NOT COMMENCED-NO EVENT
if(uyy. gt.uy(- 1 ))then
u(k)=uYY
c STAGE I ROCKING I-EVEL REACMD-ìWITH EVENT
else
dps=kts I *(uyy-uy(- I ))
uyy=uy(-l)
Jevent=-1
code="Model rocked within limits"
goto 15
end if
end if
else
c POSITTVE STAGE 1 ROCKING
if(Jevenleq.l)then
dudps/ktsp
uYY=uYY+du
c INCREASING DISPLACEMENT
if(dps.gt.0.0)then
c STAGE 2 ROCKING LEVEL NOT YET REACMD
if(uyy.lt.uy(2))then
u(k)=¡Yt
else
c STAGE 2 ROCKIN LEVEL REAC}IED
dps=ktsp*(uyy-uy(2))
uyy=uy(2)
Ievent=2
code="Model rocked within limits"
goto 15
end if

329
APPENDIX G: N0n-linearTirne Hístory Analysis ROWMANRY FortranTT Code

else
c DECREASING DISPLACEMENT
c NOEVENT
if(uyy.gt.uy(l))then
u(k)=uYY
else
c WTTH EVENT
dps=ktsp*(uyy-uy(l))
uyy=uy(l)
Jevent{
code="Model rocked within limits"
goto 15
end if
end if
end if
c NEGATIVE STAGE I ROCKING
if(Jevent.eq.- 1)then
du_Jps/ktsp
uYY=uYY+du
c INCREASING DISPLACEMENT
if(dps.lr0.0)then
c STAGE 2 ROCKING I.EVEL NOT YET REACTIED
if(uyy.gt.uy(-2))then
u(k)=¡Yt
else
c STAGE 2 ROCKING LEVEL REACMD
dps=ktsp*(uyy-uy(- 2))
uyy=uy(-2)
Jevent=-2
code="Model rocked within limis"
goto 15
end if
else
c DECREASING DISPLACEMENT
c NOEVENT
if(uyy.ltuy(-l))then
u(k)=¡YY
else
c \ryTTH EYENT
dps=ktsp*(uyy-uy(- I ))
uyy=uy(-l)
Jevent=O
code="Model rocked within limits"
goto 15
end if
end if
end if
c POSITIVE STAGE 2 ROCKING
if(Jeventeq.2)then
if(kts2.le.0.0)goro I 000
dudps/kts2
uYY=uYY+du
c INCREASING DISPLACEMENT
if(dps.gt.0.0)then
c COMPI-ETE INSTABILITY NOT REACHED
if(uyy.lt.ulim( 1))then

330
APPENDIX G: N)n-IinearTime History Analysis ROWMANRY FortranTT Code

u(k)=uYt
else
c COMPLETE INSTABILITY REACÍIED
c Update pc and return to initial conditions
if(px.eq.0)then
pl=pc
end if
c Vary proponional damping to try and achieve convergence
if(px.lt.5O)then
pç=pl -real(px)*O.02+p1
end if
if(px.eq.50)then
pc=pl
end if
if(px.gt.50)then
pc=pl +(real(px)-50.0) *0.02*p I
end if
if(px.eq.101)then
write(*, *) " Iteration limit reached- NO CONVERGENGE "
u(k)=uYY
v(k)=O'0
at(k)=0'0
do 38 l=I'k
uf(l)=u(l)
38 continue
c Set remaining final displacement store to zero
do 41 l=k+l,NT-l
uf(l)=0'0
v(l)=0'0
a(Ð=0'0
4l continue
goto 1000
end if
dps=dpsx
j=jx
a=ax
uYY=o'0
jevent=O
px=px*1
d=1
f=1
c write(1,*)"dpsx initial cond at"
s write(I,*) dpsx, x
c Resta¡t iteration with new predicted proportional damping coefficient
goto 5
end if
c DECREASING DISPLACEMENT
else
c NOEVENT
if(uyy.gt.uy(2))then
u(k)=uYY
c WTTHEVENT
else
dps=kts2*(uyy-uy(2))
uyy=uy(2)
Jevent=l

331
APPENDIX G: N)n-linear Tíme History Analysis RowMANRy Fortran7T code

code="Model rocked within limits"


goto 15
end if
end if
end if
c NEGATWE STAGE 2 ROCKING
if(Jevent.eq.-2)then
if(ks2.Ie.0.0)goro I 000
dudps/kts2
uyy=uyy+du
c INCREASINGDISPLACEMENT
if(dps.lt.0.0)then
c COMPLETE INSTABILITY NOT REACIIED
if(uyy.gt.ulim(- I ))then
u(k)=uYY
else
c COMPI-ETE INSTABILITY REACTIED
c Update pc and return to initial conditions
if(px.eq.0)then
pl=pc
end if
if(px.lt.5O)then
pç=p1 -real(px)*0.02 *p I
end if
if(px.eq.5O)rhen
pc=p1
end if
if(px.gt.50)then
pç=p 1+(real(px)-50.0)*0.02*pl
end if
c write(1,*)"Complete instability"
if(px.eq.l0l )then
wrire(*,*)"Ireration limit reached-NO CONVERGENGE"
u(k)=uYY
v(k){.0
at(k)=O'0
do 35 l=I,k
uf(l)=r¡(l¡
35 continue
c Set remaining final displacement store to zero
do 42I=k+l,NT-l
uf(l)=Q'9
v(l)=O'0
a(l){.0
42 continue
goto 1000
end if
dps=dpsy
j=jv
a=ay
uyy{.0
jeventd)
px=px+l
e=l
f=1
c write(1,*)"dpsy initial cond at"

332
APPENDIX G: Nln-Iinear Time History Analysis ROWMANRY Fortrøn77 Code

c write(l,*) dpsy, y
c Restart iteration with new predicted proportional damping coefficient
goto 5
end if
c DECREASINGDISPLACEMENT
else
c NOEVENT
if(uyy.lt. uy(- 2))then
u(k)-uyy
c WITHEVENT
else
dps=ks2*(uyy-uy(-2))
uyy=uy(-2)
Jevent=-l
code="Model rocked within limits"
goto 15
if
end
end if
end if
end if
c
c Zero crossings, instantaneous frequency and
c Rayleigh damping
c
c Identify zero crossing from neg to pos
if(tO.ne.t2)then
if(u(k).gt.0.0.AND.u(k- I ).1e.0.0)then
c write(1,*) "neg pos zero cross"
tl =dt*u(k- I )(u(k- I )-u(k))
t2dt*u(k)/(u(k)-u(k- 1 ))
tO=t0-dt+tl
j=j+l
if(.gt.l)then
if(d.ne.1)then
c Provided not prior to first half cycle or reiteration determines
c Rayleigh damping of compleæd half cycle response
nc=(aOm+a I m*pi*pil(tO* *2))
c Setting the maximum proportional damping coefficient for
c Frequency range of interest
if(nc .gt. 10.0)then
nc=10.0
end if
c wriæ(1,*) "period outcome predicted iteration k"
c wriæ(1,*) t0, nc, pc, p, k
if(nc.gt. 1. I *pc.OR.nc.lt.0.9*pc.AND.p.lt. 1O(Ð)then
c Limit on iterations t0 1000
c Compares Rayleigh damping with initial prediction
c ff out of
the specified bounds a reiteration is required
c with new predicæd proportional damping coefficient predicted below
c wriæ(I,*) "REITERATE - new pc"
pc=0.5*nc+0.5*pc
c write(1,*) pc
c Reset the initial conditions to the start of the current cycle
dps=dpsy
j=jy
a=ay

333
APPENDIX G: Nhn-linear Time History Anolysis RowMANRy FortranTT code

c write(1,*)"dps j a"
c wrire(l,*) dps, j, a
uyy=O'0
jevent{
c Iteration number
p=pll
e=l
f=l
c Restart iteration with new predicæd proportional damping coefficient
goto 5
else
c write(I,*) "PC-NC within limis"
if(p.gt.99)then
c write(*,*)"Iteration limit exceeded"
end if
P=0
px=0
e=0
c Setting the predicted proportional damping for the next half cycle
c to the successful proportional damping of the current half cycle
pc=3.0
c Transfer successful iteration to final displacement store
do 20I=I,k-l
uf(l)=r¡11¡
20 continue
end if
end if
else
c Transfer displacements prior to first half cycle to final disp store
do 2l l=I,k-l
uf(l)=¡1¡¡
2l continue
end if
û=A
c Set the initial conditions for the next half cycle
c The zero value for the dps depend on the new u(k) location
if(u(k).lt.uy( I ))then
dps=ktsl*u(k)
else
if(u(k). lt. uy(2)) then
dps=uy( I )*krs t+(u(k)-uy( I ))*ktsp
else
dps=uy( I )*kts I +(uy(2)-uy( I ))*ktspr(u(k)-uy(2))
end if
end if
uyy=O'0
Jevent=0
c Store the initial conditions for the next half cycle
dpsx=dps
jx=j-l
ax=a
x=k
c write(l,*) "dpsx jx x k u(k)"
c write(I,*) dpsx, jx, x, k, u(k)
goto 15
end if

334
APPENDIX G: N0n-linearTime History Analysis ROWMANRY FortanT7 Code

end if
c
c Identify zero crossings from pos to neg
if(t0.ne.t4)then
if(u(k).lt.0.0.AND.u(k- I ).ge.0.O)then
c write(1,*) "pos neg zero crossing"
t3dt*u(k- 1)(u(k- 1)-u(k))
t4{r*u(k)(u(k)-u(k- 1 ))
t0=t0-dt+B
j=j+1
if(.gt.l)then
if(e.ne.l)then
c Provided not prior to fftst half cycle or reiteration determines
c Rayleigh damping of compleûed half cycle response
nc=(a0m+a I m*pi*pi(t0* *2))
if(nc.gt.10.O)then
nc=10.0
end if
c write(1,*)"t0 nc pc p k"
c write(l,*) t0, nc, pc, p, k
if(nc. gt. I . I *pc.OR.nc.lt.0.9 *pc.AND.p.lt. I 000)then
c Limit on iterations to 1000
c Compares Rayleigh damping with initial prediction
c If out of the specified bounds a reiteration is required
ç with new predicæd proportional damping coefficient predicæd below
c wriæ(l,*) "REITERATE - new pc"
pc=0.5*nc+O.5*pc
c write(1,*) pc
c Reset the initial conditions to the start of the current cycle
dps=dpsx
jjx
a=ax
c write(1,*)"dps j a"
c write(l,*) dps, j, a
uyy{.0
jevent=O
c Iteration number
p=pt_l
d=l
f=1
c write(1,*) "new dps j x d f"
c write(1,*) dps, j, x, d, f
c Resørt iæration with new predicted proportional damping coefficient
goto 5
else
c write(1,*) "PC-NC within limits"
if(p.eq.100)then
, w¡iæ(*,*)"Iteration li¡nit exceeded"
end if
P=0
px4
d{
c The successful predicted proportional damping for the current halfcycle
c becomes the fnst approximation for the next haH cycle
pc=3.0
c Transfer successful iteration to final displacement store

335
APPENDIY G: N)n-linearTime History Analysis RowMANRy FortranT7 code

do22l-\k-l
uf(l)=u0)
22 continue
end if
end if
else
c Transfer displacements prior to first half cycle to final disp store
do 23 l=I,k-l
uf(l)=u(l)
23 continue
end if
t0=t4
c Set the initial conditions for the next half cycle
c The zero value for the dps depend on the new u(k) location
if(u(k).gt.uy(- I ))then
dps=ktsl*u(k)
else
if(u(k). gt.uy(-2))rhen
dps=uy(- I )*lfs I +(u(k)-uy(- I ))*ktsp
else
dps=uy(- I )*kts 1 +(uy(-2)-uy(- I ))*ktspr(u(k)-uyC2))
end if
end if
uyy=o'0
Jevent=0
c Store the initial conditions for the next half cycle
dPsY=dPs
jy=j-l
îY=a
Y=k
goto 15
end if
end if
c
c Sub-step iteration ends
25 du =u(k)-u(k-l)
dv = 2.*(du/dt) - 2.*v(k-l)
v(k)=v1¡-1¡*¿'tt
da=-2.*a+(2.*dv/dt)
a =a+da
at(k)= ¿g(lç¡ .r u
c
c if(k.lt.NT)then
c write(1,*)'Jpku(k)"
c wrire(I,*) j, p, k, u(k)
c end if
c
10 continue
return
1000 code="Model beyond timits - possible iterative instability"
feturn
I100 code="Invalid results, dtûoo large"
feturn
end

336
APPENDIX G: N)n-linearTirne History Analysis ROWMANRY FortranT7 Code

subroutine frrdnnx(Nrdin¡x,max)
c Subroutine to hnd the absolute max. value of a
c single dimension ilray x
c decla¡ation of parameters
inæger N,dim
real x(O:dim),max
c decla¡ation of local va¡iables
integer I
maxd).
do l0 I=0,N-l
if(ab s(x(I)). ge.abs(max))then
max=abs(x(t))
else
end if
10 continue
return
end

subroutine linter(NNTTTA,DT,NG'G)
c This subroutine interpolates linearly between uneven sample points.
c The interpolated data are then generated at a specified sample inærval
c
c declaration of parameters
inægerNN,NG
real T(0: 1 2000),4(0: 12000),DT,G(0: 163 84)
c declaration of local variables
integer J,K
real S

NG=int((T(NN- 1 )-T(0))/DT)+ I
G(0)=A(0)
J{
do 50 K=l,NG-1
55 if(K*DT.lt.T(J+1))then
s=K*DT_T(J)
G(K)=A(J)+S*(A(J+ I )-A(J))(T(J+ 1 )-T(J))
else
Jd+l
goto55
end if
50 continue
rehlfn
end

JJI
338
APPENDIX (H): Non-linear Time History Analysis Experimental Confirmation
t *t(**********{c*r!*t ***t :ß:ß********{.**********************
0.02
Program ROWMANRY .

For time history rocking analysis of 0.015


Free Standing or Simply Supported Objects o 0.01
_MWD
-u(m)
Latest Version : FEBRUARY 1999 o
*********************1.***r<* o 0.005
***********r<**:1.:t<***********t d
è
Accelerogram data from I Hz 16mm Amplitude Pulse t-¡
0
Accelerogram scaling factor selected = 1.000
èo
-0.00s o o
INPUT DATA SUMMARY FOR: o
Ê
SS non- loadbearing base reaction at LF
€ -0.01
v \y
À -0 015
Height ofobject = 1.500 m Time(secs)
Object width = 110.000 mm -0.02
Overburden stress at top of object = 0.000 MPa
4
t\Á
Trilinear force disp profile data 3
I
Â(1) selecæd for initial stiffness = 7.00 mm Ot
Â(2) selected for mædmum force plateau = 33.00 mm l¿1 I -at(trì/VÐ
O^^
-MWA

Qd
u -J_
Stiffness coefficient (IIEI'FS) = 4.0
Resistance coefficient (ÌIEFFR) = 4.0 .$
o
-l ;doooo, N ó
€-t
Prooortional damping data \
= -J
V
Mass proportional damping coeff. = 1.5000 Time(secs)
-4
Stiffness proportional damping coeff. = 0.0050

ANALYSIS CONCLUSION : Model rocked within limits


Analysis time = 4.0l00secs time inc =.0100secs ô
+-at(m/Js)
_+MrilA r
r
d
Ð
I-egend: o^
!t ñ'
aB = input ground acceleration u = relative displacement ã< /
v = relative velocity at = total acceleration EV
è0

¡
o
J
Time q(t) (m/s2) (m) v(t) (m/s) a(t) (m/s2)
À
Maximum 3.545 ^(t)
0.038978 0.471 3.6385
Mid Height Displacement (m)

339
AP PENDIX H : N on- Iine ar Time History Analy sis Exp erime ntal C onfirmation

*** *** * **** **** ***** ******* ***d< **** *** ** **** *** ****** **
Program ROWMANRY 0.05
For time history rocking analysis of ë 0.04
Free Standing or Simply Supported Objects o 0.03
Latest Version : FEBRUARY 1999 o
o 0.02 _MWD
-u(m)
*********+****:ß********+***********t ********+t***{.*t(*** d
o. 0.01
Accelerogram data from I Hz 24mm Amplitude Pulse H
0
Accelerogram scaling factor selected = 1.000 2
è¡)
-0.01
INPUT DATA SUMMARY FOR: el m o
SS non- loadbearing base reaction at LF -0.02
à
Heightofobject= 1.500m -0.03
Time(secs)
Object widrh = 110.000 mm -0.04
Overburden stress at ûop of object = 0.000 MPa
5

Trilinear force disp orofilé data 4 ar(Íilvs)


Â(1) selected for initial stiffness = 7.00 mm ÔJ
-
Eo
À(2) selecæd for maximum force plateau = 33.00 mm
õ^
AL
Á
-MWA
8gl
Stiffness coefficient (IIE¡PS) =
Resistance coefficient (IIEI,¡'R) =
4.0
4.0
;s
d )hohoh
/\
bn 3h >h 3V
o -l
-=
Ôì N( ¡cl lmooomom
Proportional damoine data >-L
-3
Mass proportional damping coeff. = 1.4000 vJv
^, Time(secs)
-4
Stiffness proportional damping coeff. = 0.0040

ANALYSIS CONCLUSION : Model rocked within limits


Analysis time = 4.0l00secs
time inc =.0100secs +at(m/Vs)
+MWA
tr
.5
Iægend: d

aB = input ground acceleration u = relative displacement õ-


o

v = relative velocity at = ùotal acceleration <* ?.¡'

Áv
è¡! oooo(
Time ar(t) (m/s2) (m) v(t) (m/Ð a(Ð (m/s2)
o oooo(
-iâ-iA
Maximum 3.545 ^(t)
0.038978 0.471 3.638s
MidHeight Displacement (m'

340
*****************:ß******:le*****d.**'r*************+*i.{.**t {.
0.08
Program ROWMANRY
For time history rocking analysis of 0.06
Free Sønding or Simply Supported Objects 0.04 -¡(m)
Latest Version : FEBRUARY 1999 o
**'r **** * *** ** *** * **** *** * **** * *** ********* ***{c *<*{.** **t<:1. o
0.02
-MV|/D
0
Accelerogram data from
(g
I Hz37nm Amplitude Pulse
;JðèèÌr"f
Þ.
-0.02
Accelerogram scaling factor selected = 1.000 f-l ÊÊ ÉelClô.¡Ncleloomóooo
-0,04
INPUT DATA SUMMARY FOR:
SS non- loadbearing base reaction at LF
Ò0
o -0.06 \\/
Heightofobject= 1.500m À -0.08 Time(secs)
Object width = 110.000 mm -0.1
Overburden sEess at top of object = 0.000 MPa
5
4 at(mj/si/s)
Trilinear force diso orofile data OJ
Â(1) selected for initial stiffness = J.50 mm -
t\
d1
Â(2) selecæd for maximum force plateau = 25.00 mm
BL
o^l
ON
tt I -MWA
åÉ 0
Stiffness coefficient (IIEFFS) = 4.0 Ëë

4
-t l.¿
)o\ T
Resistance coefficient (IIEFFR) = 4.0 -) ì

Prooonional dampine data -4


-5
Mass proportional damping coeff. = 1.5000
Stiffness proportional damping coeff. = 0.00s0
+at(m/ds)
ANALYSIS CONCLUSION: Model rocked within limits ----+-M\ilA
4.0100secs
Analysis time = time inc =.0100secs
i
d
ö
o^ I
!ì ñ'
Legend: ì*
u = relative displacement
JÈ¡

ag = input ground acceleration ot)


v = relative velocity at = total acceleration ¡o
Time ar(t) (m/s2) (m) v(r) (m/s ) a(Ð (m/s2)
Maximum 7.516 ^(t)
0.073902 0.613 4.0328 MidHeigbt Dsplacement (m)

34r
APPENDIX H: Non-linear Time History Analysis Experimental Confirmation

*** ***** *** * *************+*** ***:r:ß******+* **** **** ***** 0.006


0.005
Program ROWMANRY 0.004
For time history rocking analysis of g _
0.003 -(m) MWD
Free Standing or Simply Supported Objects
nllÍ\
ts 0.002
Latest Version : FEBRUARY 1999 e 0.00r ^
.r l\
*'ß* *t<.** ********:ß**************t* ******
o 0
** ***** **** **** **
Accelerogram data fromYzHz 4Ùmm Amplitude Pulse -é
o
à0
-0.00r
-0.002 -lr v-
Accelerogram scaling factor selected 1.000 = -0.003 I v
INPUT DATA SUMMARY FOR: 5 -0.004
SS loadbearing top & bottom reaction at LF -0.00s
Height of object = 1.500 m -0.006
Object width = 50.000 mrn
10
Overburden stress at úop of object = 0.075 MPa
8 at(m/srs)

Trilinear force diso profile data 8o -


Â(1) selecæd for initial stiffness = 5.00 mrn Ë¿ -MWA
Â(2) selected for mærimum force plateau = 15.00 mm Ea
o6 o

-iËlì \AA..A il\t l


Stiffness coefficient(IlE¡fs) = 21.735 'Þ
o¡)
-2
Resistance coefficient (HEFFR) = 21.735
È-4
el el

-6
Proportional damoine data v Time(secs)
Mass proportional damping coeff. = -8
3.0000
Stiffness proportional damping coeff. = 0.0060

AÀIALYSIS CONCLUSION : Model rscked within limits


Analysis time = 3.0l00secs
time inc =.0100secs é
o

Iægend: o
o^
qd
ag = input ground acceleration u = relative displacement 9u)
v = relative velocity at = total acceleration c¡
o
Time as(t) (m/s2) (m) v(t) (m/s) a(t) (m/s2) À
Maximum 4.78 ^(t)
0.005211 0.202 7.6747 Mid-heigþt Displacement (m)

142
*********{.*******{c***'1.************1.*,1.{.*******{<*t<t **1.*r.d. 0.008
Program ROWMANRY 0.006 _(m)
For time history rocking analysis of 1' 0.004
Free Standing or Simply Suppoted Objects o
0.002
Latest Version : FEBRUARY 1999 e A Â rrr-- -MWD
0
**¡lc*¡lc**t(******t *********rl.**+*****{.******{<*{<*1!***1 1.****:tc o
& -0.002
JI \1,ì\Évu qF (r q¡ r-
Y
Accelerogram data from r/zHz 60mm Amplitude Pulse
d) -0.004
ooo -ieiõiÕiõiõiñú;riri
Accelerogram scaling factor selected = 1.000 o
,é -0.00ó {
INPUT DATA SUMMARY FOR: À -0.008
SS loadbearing top & bottom reaction at LF -0.01
Heightofobject= 1.500m -o.012
Time(secs)

Object width = 50.000 mm


Overburden sEess at top of object = 0.075 MPa l0
8
É
Trilinear force disp Eofile data €6 -at(m/Ys)
Å(1) selecæd for initial stiffness = J.00 mm b4
d

Â(2) selecæd for maximum force plaûeau = 15.00 mrn Ec 2


l f\ ,r II A -MWA
Íè o

IññÀñi¡ñã¿à¡
d
Stiffness coefficient (HEFFS) = 2r.735
Resistance coefficient (HEffR) = 21.735
.É oôoo
il t/
YU
Prooortional dampine data -8 rr Time(secs)
Mass proportional damping coeff. = 3.0000 _10
Stiffness proportional damping coeff. = 0.0060

: Model rocked within limits


Analysis time = 3.5100secs
' time inc =.0100secs
É
'5
d
o
O^
od
Legend:
aB = input ground acceleration u = relative displacement

Ë.,11

v = relative velocity at = total acceleration o
É
Time ar(Ð (m/s2) (m) v(r) (m/s) a(t) (m/s2)
Maximum 6.398 ^(t)
0.007558 0.285 8.3396 Mid-height Dsplacement (m)

343
APPENDIX H: Non-linear Time History Analysis Eryerimental Confirmation

'1.**********1ê**************t **{<*************************
Program ROWMANRY 0.01
For time history rocking analysis of Þ 0.008
Freæ Sønding or Simply Supported Objects c(l) 0.006
Latest Version : FEBRUARY 1999 E 0.004 -u(m)
fvfvvD

*** ***** *** **:N.** ******** ********* +**X:N.* *** ******** *****
o)
() -
Accelerogram data from I Hz 30mrn Amplitude Pulse

o-
0.002
tl //\ I ^
Accelerogram scaling factor selected =
.a
o
0
l() ^ o å,
rb// ) o rO

INPUTDATA SUMMARYFOR:
1.000
.9)
q)
-0.002
-0.004
o c &ð"¡ o r - \¿r-;
SS loadbea¡ing top & bottom reaction at LF p -0.00ó
I
Heightofobject= t.500m -0.008
Object width = 50.000 mm -0.01
Tine(secs)
Overburden shess at top of object = 0.075 MPa
10
8
Trilinea¡ force disp orofile data at(mirs/s)
q6
Â(1) selected for initial stiffness = 415 nrnrt 'ã4 _MWA
-
Â(2) selected for maximum force plateau = 14.00 mm
s^
8g
2

^.
lll
0
Å[
r

Stiffness coefficient (IIEFPS) = 2t.735 Íè'2


Resistance coefficient (I{EFFR) = 21.735 B-4
€-6 V
Proportional damoine data Ë-8 I
Mass proportional damping coeff. = _10 V
3.0000
Time(secs)
Stiffness proportional damping coeff. = 0.0060 -12

ANALYSIS CONCLUSION : Model rocked within limits


Analysis time = 2.0100secs time inc =.0100secs
5d
Ð
Iægend:

ag = input ground acceleration u = relative displacement åç
v = relative velocity at = ûotal acceleration
Þ
e
E
Time ae(t) (rn/s2) (m) v(t) (m/s) a(Ð (m/s2) à
Maximum 5.839 ^(t)
0.0087r8 0.283 9.4s62

14¿.
******t **1.*******+******t *+t<************t<******'F*têrêt ***
0.04
Program ROWMANRY
For time history rocking analysis of ë 0.03
Free Standing or Simply Supported Objects Ë
-(m)
Latest Version : FEBRUARY 1999
Ê
o
o.o2
,1.'1.***t(********{.**d<***{<**t<**t *******'1.***r!*{<*******1.***** E
o
o.ol
-MWD
Accelerogram data from I Hz 50mm Amplitude Pulse
Accelerogram scaling factor selected = 1.000 äo
Á
À n, ^,-
Ð æ
èo
INPUT DATA SIJMMARY FOR: -0.01
SS loadbearing top & bottom reaction at LF
Heightofobject= 1.500m =
-0.02
Time(secs)
Object width = 50.000 mm -0.03
Overburden stress at top of object = O.075 MPa
l0
Trilinear force disp orofile data
c6
8
\ tl
À(1) selected for initial stiffness = 4.75 mm
(€'
5^ il
-at(m/Ys)
Â(2) selecæd for maximum force plateau = 13.50 mm -Þz lt V
-MWA
8g â.l,
O^

<l Ëës+
0
Stiffness coefficient (HEFFS) = 21.735 '-ë -¿ a__] L

B-4
NI rl ñ
Resistance coefficient (IIEfpR) = 21.735 'j,
1
€-6
Prooortional damoine data E-8
-10
Mass propofional damping coeff. = 3.0000
-12
Stiffness proportional damping coeff. = 0.0025

ANALYSIS CONCLUSION : Model rocked within limits


Analysis time = 3.9400secs time inc =.0l00secs
o
Iægend: d
{)
aB = input ground acceleration u = relative displacement o^
ON
a) .ò
v = relative velocity at = total acceleration
èD

Time ar(Ð (m/s2) (m)


v(Ð (m/s) a(t) (m/s2) Éo
Maximum 8.531 ^(Ð
0.030496 0.575 9.2466 À

345
APPEN DIX H : Non- linear Tirne History Analy sis Exp e rtmcntal C onfirmation

*** **** *+** ************* ********* ***** +*** **** **** ***** 0.02
Program ROTWMANRY
For time history rocking analysis of
â 0.0r5
0.01
Free Standing or Simply Supported Objects ø
o
0.005
-(n)
Latest Version : FEBRUARY 1999 o
o 0
t -MWD
*** ****:t*** *** ** ** ** ***+ ***** ******** *******'ßi. **** * **** G
È -0.005
Accelerogram data from 2Hz l5mm Amplitude Pulse â o c-l
2 -0.0r
Accelerogram scaling factor selected = 1.000 è¡)
o -0.0r5
INPUT DATA SUMMARY FOR:
SS loadbearing top & bottom reaction at LF
-0 02
-0.025
v
Heightofobject = 1.500 m Time(secs)
-0.03
Object width = 50.000 mm
Overburden stress at top of object = 0.075 MPa 10
8
Trilinear force disp profile data a6 _MWA
Â(1) selected for initial stiffness = {.75 mm 'iã4 -at(m/Vs)
b?
6

Â(2) selected for manimum force plateau = 13.50 mm A


8S
O^

<t 0
.*.\ I I
Stiffness coefficient (IIEFFS) = 21.735 \ E
.30 -4
Resistance coefficient (IIEnfR) = 21.735 o
€-6
Prooortional damoing data =-8 -10
Mass proportional damping coeff. = 3.0000 -12
I ime(secs)
Stiffness proportional damping coeff. = 0.0060

ANALYSIS CONCLUSION : Model rocked within limits


Analysis time = 2.2100secs time inc =.0100secs
Ð
Iægend: o^
AN
input ground acceleration 9u)
aB = u = relative displacement
v = relative velocity at = ûotal acceleration c)
o
ã
t
Time ar(t) (m/s2) (m) v(t) (m/s) a(Ð (m/s2) À
Maximum 6.972 ^(t)
0.023191 0.479 10.1605

?46
*** **{r* ***{. * *{<** *** * **{. *1.*r<** +*** ** ** ***** **** *ts:lc * ***ic*
0.01
Program ROWMANRY
For time history rocking analysis of 0.008
Free Standing or Simply Supported Objects 0.006 _MWD
-(m)
o
Latest Version : FEBRUARY 1999 o
0.004
\\/\
o
**********:*:1.**:1.:1.*rß**t(**********¡1.*r¡**t
Accelerogram data from
,1.*****+********r<t * d
o.
0.002
\ /lt
I Hz 30mm Amplitude Pulse 0
.l ) \ tJ/ u
Accelerogram scaling factor selected =
INPUT DATA SUMMARY FOR:
1.000
è0
-0.002
o -0.004
3ä oo 3I
\\
SS loadbearing top & bottom reaction at LF -0.006
V
À
!

Heightofobject= 1.500m -0.008


Time(secs)
Object width = 50.000 mm -0.01
Overburden shess at top of object = 0.15 MPa
t4
l2 at(m/s/s)
Trilinear force diso nrofile data r0
Â(1) selecæd for initial stiffness = 7 mm 88
'Ë6 -
Â(2) selecæd for maximwn force plateau = 2l mm b4
O^
-MWA
()d t

Stiffness coefficient (HEFFS) = 39.47t


Resistance coefficient (IIEFFR) = 39.47r 'õ
d
-1
¿= -O

Propgrtional dampine data


È-B
Á -lo
Mass proportional damping coeff. = 2.0000 -12
Stiffness proportional damping coeff. = 0.00s0 -14

ANALYSIS CONCLUSION : Model rocked within limits


Analysis time = 1.6600secs time inc =.0l00secs
ô
o I z
Iægend: O^
a ô^¡
aB = input ground acceleration
v = relative velocity
u = relative displacement
at = total acceleration

àt)
o
Time ar(Ð (m/s2) (m) v(t) (m/s) a(t) (m/s2)
Maximum 6.266 ^(Ð
0.008301 0.306 12.0173
id-heidit Llisolacemen fml

347
AP P EN D IX H : N on- line ør Time H i s t ory Analy s i s Exp e rime nt al C onfirmat ion

*1.t ************{.********************:F******************
0.02
Program ROWMANRY
0.015
For time history rocking analysis of g
Free Standing or Sirnply Supported Objects É
0.0r
-u(m)
Latest Version: FEBRUARY 1999
************:F************:¡:t i.***************+***{.***,tc*,ß*
ts
o
o
0.005
/At -MWD
o l-l
6t 0
è
Accelerogram data from
rÍèl;
(
I Hz 50mm Amplitude Pulse H
-0.00s
; c;\/d v¿
Accelerogram scaling factor selected =
)
1.000 cl -0.01
IMUT DATA SUMMARY FOR: o
I

-0.015
SS loadbearing top & bottom reaction at LF
-0.02
Heightofobject= 1.500m
-0.02s
Time(secs)
object width = 50.000 mm
Overburden shess at top of object = 0.15 MPa 12.5
l0 ar(m/Vs)
Trilinea¡ force diso profile data
'!o
7.5
_MWA
Â(l) selecæd for initial stiffness = 8 mm d 5 -
o 2.5
Â(2) selected for maximum force plateau = 23 nrn O^ t*\
\L -Jt
9N
<t 0
-2.5 Y\\ ,Jl
Stiffness coefficient (IIEFFS) = 39.471 c) -5
Resistance coefficient (IIEFFR) = 39.471 o
,4 V
€ -7.5
À -10 \
Proportional damoine datå I Ãt
-12.5
Mass proportional damping coeff. = 2.0000 -15
Stiffness proportional damping coeff. = 0.0050

ANALYSIS CONCLUSION : Model rocked within limits


Analysis time = 2.0500secs time inc =.0100secs
G
Iægend: o
O^
a
<l
c.¡
aB = input ground acceleration u = relative displacement
v = relative velocity at = total acceleration
.$
C)

Time ag(t) (m/s') (m) v(Ð (m/s) a(0 (m/s2) À


Maximum 7.487 ^(t)
0.020974 0.535 12.966
--Fos:ËÈJf+tÚz Mid-heigþt Displacement (m

?4R
****{.*!.1.'**{<r.*************t ******************************
Program ROV/MANRY 0.025
For time hisory rocking analysis of 0.02
0.015
Free Standing or Simply Supporæd Objects -¡(m)
Latest Version : FEBRUARY 1999 o 0.01
********:t ***********{.r.************dc*****ds****:1.*¡lc***t :k** õ
o 0.005
-MWD
d
Accelerogram data from 2Hzã0rll.n Amplitude Pulse À 0
A
Accelerogram scaling factor selected =
INPUT DATA SUMMARY FOR:
1.000
¡
o0
-0.005
-0.0r
o
SS loadbea¡ing top & bottom reaction at LF -0.0r5
Height ofobject = 1.500 m -0.02
Object widrh = 50.000 mm -0.025
Overburden súess at top of object = 0.15 MPa
15
12.5 at(rrils/s)
Trilinear force disp profile data 10
É
Â(1) selecæd for initial stiffness = 7.2 mm 7.5 -
d
Â(2) selected for maximum force plateau = 23 mm o 5
II -MWA
O^
oñ 2.5

Stiffness coefficient (IIEFFS) = 39.471 <è


Oøi
0 ^U
-2.5
Resistance coefficient (IIEFFR) = 39.47t .9
o -5

E T
-'7.5
hooortional dampine data À -10
Mass proportional damping coeff. = 2.0000 -12.5
Stiffness proportional damping coeff. = 0.0060 -15

ANALYSIS CONCLUSION: Model rocked within lirnits


Analysis time = 1.7600secs time inc =.0100secs
d
Iægend: o
O^
aB = input grouqd acceleration u = relative displacement 8g

v = relative velocity at = total acceleration E-
c)
o
Time ae(t) (m/st) (m) (m/s)
v(t) a(Ð (m/s'?)


À
Maximum 7.605 ^(t)
0.020093 0.567 12.532

349
APPENDIX H: Non-linear Time History Analysis Eryerimental Confinnntion

*************************r.*'*:t *:t *********1.**'F****+*t****


Program ROWMANRY 0.08
For time history rocking analysis of g 0.06
Free Standing or Simply Supporæd Objects
Latest Version : FEBRUARY 1999
o
Á
0.04 -(m)
{.****¡ß*+********************************:**.***t<**t t ***** o
o
ñ
0.02 -MWD
I
Accelerogram data from 807o Pacioma Dam E/Q = 0
Accelerogram scaling factor selected =
1.000 H
-0.02
cî iô €ÀÉ çra¡È-æ
INPUT DATA STJMMARY FOR: è¡)
o -0.04 Èel e.¡ (\ Cl C^l om
SS non- loadbearing base reaction at LF €
Heightofobject= 1.500m À -0.06
Time(secs)
Object width = 110.000 mm -0.08
Overburden stress at top of object = 0.000 MPa
4
Trilinear force diso nrofile data É
3 at(m.i/Vs)
o1
Â(1) selecæd for initial stiffness = 15.00 mm d -
Â(2) selecæd for maximum force plateau = 35.00 mm bl -MWA
8S n-
O^


Stiffness coefficient (HEFFS) = 4.0 :s-1
à0
Resistance coefficient (IIEFFR) = 4.0 O^

hoportional damoine daø


-4
Mass proportional damping coeff. = 1.000 T
Stiffness proportional damping coeff. = 0.0030 -5

ANALYSIS CONCLUSION : Model rocked within limits


a(n/Vs)
Analysis tirne = 34.9600secs tirne inc =.0l00secs é ---r-MWA
'.É
d
Ð
t,
lægend: o^
aB = input ground acceleration
v = relative velocity
u = relative displacement
at = total acceleration
<*
!ì ñ'
!v
c) (
ão
Time ag(t) (m/s2) (m) v(t) (m/s) a(t) (m/s2)
À
Maximum 3.545 ^(t)
0.038978 0.471 3.6385
Mid Height Displacement (m.

?sfl
******.i;ffiiåüffiåi*++' ***1'*"'F{<*¡
0.05
0.04
For time history rocking analysis of 0.03
Free Standing or Simply Supponed Objects o
É 0.02
-u(m)
Latest Version : FEBRUARY 1999 o
o
d 0.01 -M\ryD
*,1ê******{<*****,1.*******{<**:*:N<{.***********{<**t rlÊ*******'tr(X{< o 0
Accelerogram data from 507o Pacioma Dam E/Q t-l -0.01
Accelerogram scaling factor selected =

1.000 qf) -0.02
o
INPUT DATA SIJMMARY FOR: É -0.03
SS non- loadbearing base reaction at LF -0.04
Heightofobject= 1.500m -0.05
Time(secs)
Object width = 110.000 mm -0.06

Overburden sfress at top of object = 0.000 MPa -4


3
Trilinear force disp profile dat¿
oa
A(1) selected for initial stiffness = 12.00 mm d -at(m/Vs)
Â(2) selected for maximum force plateau = 35.00 mm Ðl
O^ -MWA

Stiffness coefficient (IIEFFS) = 4.0


åÉ o
d-t
Resistance coefficient (HEFFR) = FA t- ó
4.0 Eo icì ôl m
rJ _,,
à
Prooortional damoins data -3
Time(secs)
Mass proportional damping coeff. = 1.500 -4
Stiffness proportional damping coeff. = 0.0050

ANALYSIS CONCLUSION : Model rocked within limits +at(n¡lJs)


Analysis time = 34.9600secs time inc =.0100secs o _r-MWA
Ë*
o
Legend: e^
üçl
ag = input ground acceleration
v = relative velocity
u = relative displacement
at = total acceleration

¡v
c)
o
l= oooo (
É
Time ar(t) (m/s2) (m) v(t) (n/s) a(t) (m/s2)
À
Maximum 3.059 ^(t)
0.044787 0.453 3.52r MidHeight Displacement (m,

351
APPENDIX H: Non-linear Time History Analysis Experimentøl Confirmation

*** ******* ***** {< **** *{.*********** **** *****:ß*** *********

hogram RO\ryMANRY 0.t2


For time history rocking analysis of ? 0.1

Free Standing or Simply Supported Objects É


o
0.08
0.06
_MU¡D
-u(m)
Latest Version : FEBRUARY 1999 o 0.04
*** ******** ************* o
***.*:t **** **** ***** **t(* ********* d
0.02
ô. ll a ^ - r
Accelerogram data from
I t ñ
667o ElCentro E/Q o 0 ^l
u ^
Accelerogram scaling factor.selected = ' 1.000 -0.02
cl l?
èo
INPUT DATA SUMMARYFOR: o -0.04
É -0.06
v-
SS non- loadbearing base reaction at LF
À -0.08
Heightofobject= 1.500m -0.1 t._ Specimen Failure
r rme(socs,
Object widrh = 110.000 rnm -0.12
Overburden súess at top of object = 0.000 MPa
6
. at(m/vs)
*Trilinear force diso orofile data 4 _MWA
Â(l) selected for initial stiffness = 15.00 mm
Ê
5
d 2
Â(2) selected for maximum force plateau = 35.00 mm Ò
o
o ñ0 .l T rl I t.. -u,.1
o -T
Stiffness coefficient (HEffS) = 4.0 Lz
rd
rc ir ( ìI II t It
Resistance coefficient (IIEFFR) =
E
r
(

7 Tr,rf ll|rï *|fl fsvf! : 3r:'=


ô
3 R
4.O ,1¡
É
o
-4 = N

hooortional dampine data À


-6
Mass proportional damping coeff. = 1.750 I Time(secs)
Stiffness p,roportional damping coeff. = 0.0060 -8

ANALYSIS CONCLUSION : Model rocked beyond limits


Analysis time = 22.4600sæ,s time inc =.0100secs
+at(n/Vs) )
Ê --¡-MWA I
6 J.
Iægend: o
e^
48 = input ground acceleration
v = relative velocity
u = relative displacement
at = total acceleration
<*
EçI
¡v
èo
o
Time ag(t) (n/s2)
tf
(m) v(t) (m/s) a(t) (m/s2) -1

r
Maximum 3.986 ^(t)
Failed 0.706 4.0053 Å
Mid Heigþt Displacement (m)

a\t
*t<***{e*************:***t :***:1.******{<*******************rc*
Program ROWMANRY 0.0r2
I
For time history rocking analysis of 5 0.01
0.008
Free Standing or Simply Supported Objects
Latest Version : FEBRUARY 1999
o
E 0.006 -(m)
o
o
**rr***1.*:{ê*:1.***rs***t t {.*******r<r<******t+**{<*r<t!**********+ (Ë
0.004
I -M\IrD
0.002
Accelerogram data from 1007o Nahanni Aftershock rJü
¡ 0
H
Accelerogram scaling factor selected = 1.000 -0.002
èf)
INPUT DATA SUMMARY FOR: o
É -0.004
SS non- loadbearing base reaction at LF À -0.006
Heightofobject= 1.500m -0.008 Time(secs)
Object width = 110.000 mm -0.01
I
Overburden stress at top of object = 0.000 MPa
4
3
Trilinear force diso orofile data
é^
Å(1) selected for initial stiffness = J.00 mm aL -at(Inj/Vs)
Â(2) selecæd for maximum force plateau = 25.00 mm Ër ¡¡
t
lf ra
[iI¡.Il$l -MWA
Eç o
til lr [,r -¡r¡ - ô

Stiffness coefficient (IIEITS) =


(HEffR) =
4.0 Íè-r
.9 F- f--
Resistance coefficient 4.0 a-L

Proportional damoine data E-3 -4


Mass proportional damping coeff. = 4.000
-5
Stiffness proportional damping coeff. = 0.0060

ANALYSIS CONCLUSION: Model rocked within limits at(m/Vs)


D
Analysis time = 12.4200secs time inc =.0100secs É
.5 --r-MWA
ñ
o
Iægend:
Ha
aB = input ground acceleration u = relative displacement l*
v = relative velocity at = total acceleration !v
d
o
É
Time ae(t) (Ír/s2) (m) v(r) (m/s) a(t) (m/s2)
J

Maximum 6.413 ^(t)


0.012088 0.248 4.6692
Mid Heigþt Displacement (m)

353
354

You might also like