Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Testing Department

SAGARDIGHI THERMAL POWER PROJECT


WEST BENGAL POWER DEVELOPMENT CORPORATION LIMITED

4011 CVT Tan δ and Capacitance Measurement (UST Mode) Date: 23/09/2021
Capacitive Voltage Transformer (R-Phase): Serial No: 00604003

 Insulation Resistance (IR) Value: (Instrument Used: 10 KV Digital I.R Tester Model: MI 3200, Make: METREL)
Before Tan δ Test After Tan δ Test Temp- 31°C
15 Sec 60 Sec 15 Sec 60 Sec
HV – Earth (By 5KV) 3.93 GΩ 5.01 GΩ 4.93 GΩ 5.11 GΩ
HV – Tan δ (By 5KV) 4.98 GΩ 8.10 GΩ 5.06 GΩ 8.25 GΩ
Tan δ - Earth (By 500V) 49.9 MΩ 59.8 MΩ 53.8 MΩ 61.1 MΩ
 Tan δ and Capacitance Measurement (by DELTA 2000, Make-MEGGER)
(5 KV) (10 KV)
V (KV) 4.91 9.97
I (mA) 6.824 13.88
W (W) 0.0070 0.1285
DF (%) 0.10 0.10
C (pF) 4429.4 4434.9
Capacitive Voltage Transformer (Y-Phase): Serial No: 00604002
 Insulation Resistance (IR) Value: (Instrument Used: 10 KV Digital I.R Tester Model: MI 3200, Make: METREL)
Before Tan δ Test After Tan δ Test
15 Sec 60 Sec 15 Sec 60 Sec
HV – Earth (By 5KV) 4.60 GΩ 6.22 GΩ 4.85 GΩ 6.30 GΩ
HV – Tan δ (By 5KV) 5.78 GΩ 7.42 GΩ 5.93 GΩ 7.53 GΩ
Tan δ - Earth (By 500V) 42.1 MΩ 46.2 MΩ 44.6 MΩ 49.8 MΩ
 Tan δ and Capacitance Measurement (by DELTA 2000, Make-MEGGER)
(5 KV) (10 KV)
V (KV) 5.00 9.97
I (mA) 6.946 13.90
W (W) 0.0336 0.1107
DF (%) 0.10 0.08
C (pF) 4421.2 4439.7
Capacitive Voltage Transformer (Y-Phase): Serial No: 00604001
 Insulation Resistance (IR) Value: (Instrument Used: 10 KV Digital I.R Tester Model: MI 3200, Make: METREL)
Before Tan δ Test After Tan δ Test
15 Sec 60 Sec 15 Sec 60 Sec
HV – Earth (By 5KV) 8.50 GΩ 18.98 GΩ 8.98 GΩ 19.65 GΩ
HV – Tan δ (By 5KV) 8.52 GΩ 19.80 GΩ 9.70 GΩ 20.05 GΩ
Tan δ - Earth (By 500V) 520 MΩ 542 MΩ 532 MΩ 548 MΩ
 Tan δ and Capacitance Measurement (by DELTA 2000, Make-MEGGER)
(5 KV) (10 KV)
V (KV) 4.98 9.95
I (mA) 6.912 13.86
W (W) 0.0350 0.1199
DF (%) 0.10 0.10
C (pF) 4417.4 4434.4

Page 1 of 1

You might also like