OIL AND NATURAL GAS CORPORATION LTD. | Issue No: | Rev No: 00
WELL SERVICES, CAMBAY ASSET ol __ | Rev Date:
DOC NO: CBY/WS/QHSE/FORMAT/ MCR Issue Date: | NA
a (OISD-GDN-178) June-2018,
MANAGEMENT OF CHANGE (REQUEST FORM): Change of process/ technologies
DOCUMENT REFERENCE: CBY/CBA/SERVICES/WELL-SER/2020/AFDSS/665888
Detail of Change Requested:
DGMS in their audit report § 29018/K1/2020/NWZ(Mech)/ Baa MA/ACHGTAE 87/563 dated
10/02/2020 found contravention and recommended installation of an Automatic Fire Detection and
Suppression System (AFDSS) on Diesel engine (IC Engine) installed on rig carrier engine of Work
over rig ROM-50-VIL.
Reason For Change:
DGMS cited Technical Circular No. of 2019 regarding safe conduct of operations in Workover Oil/
Gas Mines for installation of AFDSS, in the interest of safety and especially in the wake of fatal
accident at an onshore work over oil mine.
Since the rig engine is in proximity of well and is much susceptible to act as source of fire in case of
engine overrun/electrical spark etc. in an environment surcharged with HC gas cloud created at the
site due to workover operations in abnormal working condition, which is very hazardous for
manpower and capital equipment installed on WORK OVER RIG.
The main purpose of AFDSS on diesel engine is to reduce human intervention in
mitigation/suppression of fire in case of fire hazards on or near diesel engine
Impact Change will have on Health, Operating Procedures, Safety and Environment (Hazard
Analysis):
AFDSS will automatically detect and suppress fire on or near the diesel engine at initial stage without
any human intervention. This technology induction will have a long lasting positive impact on health
and safety of manpower and capital. :
As CO> is used as extinguishing agent in AFDSS, it is not harmful for human beings (if inhaled),
engine (if sucked along with air), engine electrical/mechanical accessories.
Action Plan (if any):
During conceptualization phase, needful study of the engine for the installation of the new AFDSS,
and field visit by maintenance team as well as In-charge HSE, WS Cambay Asset was done in order
to figure out a working solution and plan a basic drawing of the same. Several enquiries were made
regarding supply and installation of CO. based AFDSS from many vendors, which were expert in
installing such systems and had installed AFDSS on enclosed electrical panels and fully/partially
enclosed diesel engines. s a