Sealed Combustion
Hot Water Gas Boiler
Logano GA244
CAUTION!
Before putting the boiler into operation
read this manual carefully.
WARNING !
Improper installation, adjustment,
alteration, service or maintenance can
cause injury, loss of life or property
damage. Refer to this manual. For
assistance or additional information
consult a qualified installer, service
agency or the gas supplier.
CAUTION !
The operating manual is part of the
documentation that is delivered to the
installation's operator. Go through the
information in this manual with the
owner/operator and make sure that he
or she is familiar with all the necessary
operating instructions.
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
2 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Table of Contents
1 Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.1 Application purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.2 Guideline of Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.3 Observe the following symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2 Regulations and Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
7 Electrical Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8 Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
8.1 Gas Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
8.2 Installation at Higher Elevations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
9 Combustion Air and Ventilation Openings . . . . . . . . . . . . . . . . . . . . . . . . 15
12 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
15 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 3
1 Safety Considerations
1 Safety Considerations
Please observe the following safety instructions. 1.3 Observe the following symbols
DANGER
1.1 Application purpose
due to explosion of gas.
The GA244 gas boiler is designed for use as a hot water WARNING! z Work only on gas components when
heating boiler to heat water for space heating purposes you have a license to do so.
for a single and multi family houses.
z Note that the assembly of gas and vent
connections, the initial start-up, the
electrical connections, the
1.2 Guideline of Notices maintenance and service can only be
performed by a licensed service
Two levels of danger are identified by the following contractor or technician.
warning labels:
DANGER
DANGER
due to electricity.
Denotes a possible severely dangerous
WARNING!
situation where, without proper caution, WARNING! z Prior to doing any work on the heating
bodily injury or loss of life may result. system, disconnect all electrical power
to the boiler at the emergency switch.
CAUTION!
Denotes a possible dangerous situation
that can lead to mild to moderate bodily SYSTEM DAMAGE
injury or physical damage.
due to improper installation.
due to electricity.
WARNING!
SYSTEM DAMAGE
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
4 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Regulations and Guidelines 2
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 5
3 Dimensions and Boiler Connections
B
D
5 A
6
1
C
3
Boiler Heating Air intake Exhaust Min. Relief No. of Water- Dry
model capacity connection connection Valve Burners content weight
Table. 1 Dimensions
Boiler A B 7.25
C D
model Air intake Exhaust
Inches Inches Inches Inches 156/182 MBTu/h
(Size 37/44)
37 7 3/8 17 1/2 43 3/4 25 6/8
44 7 3/8 17 1/2 43 3/4 25 6/8
53 7.9 20.9 43.3 29.1
62 7.9 24.4 43.3 32.7 1.45
Pressure Drop in psi
Table. 2 Dimensions
0.1
1.8 17.6 68.2
Flow Rate in GPM
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
6 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Packaging and Components 4
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 7
5 Installation
5 Installation
2"
open. When the access door is closed, a minimum
clearance of 2 inches in front and on the sides of the
boiler from combustibles is required (Fig.3). Maintain a
minimum clearance from combustibles of 2 inches for
the exhaust vent pipe. A 20“ top clearance is
recommended for cleaning access and is strictly
required when the boiler is placed in a fully enclosed
closet. A 2“ rear clearance is required for horizontal vent
pipe installations. The gas boiler is certified for 1
2"
installation on combustible flooring. The boiler must not
be installed on carpeting.
33"
2" 2"
Provide 2“ clearance between vent pipe and 2
combustible construction.
Fig. 3 Minimum clearances from combustible construction
No clearance is required between wall terminal body
and combustible construction Item. 1: Access door closed
Item. 2: Access door open
Item. 3: Exhaust vent pipe
NOTICE !
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
8 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Installation 5
z Unpack all boxes and cartons and check that all parts
have been delivered using the packing list.
NOTICE !
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 9
6 Boiler Water Connections
BOILER DAMAGE !
due to moisture. 3
DANGER! z Install this boiler so that the gas ignition
system components are protected from
water (dripping, spraying, rain, etc.)
during appliance operation and service
(circulator replacement, control
replacement etc.).
SYSTEM DAMAGE ! 2
1
due to over heating during low water
DANGER!
conditions.
z If this boiler is installed above radiation
level it must be provided with a low 2 2
water cut-off device either as a part of
the boiler or at the time of installation
(see Fig. 5).
4
SYSTEM DAMAGE !
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
10 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Boiler Water Connections 6
FIRE DANGER !
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 11
7 Electrical Supply
7 Electrical Supply
NOTICE
CAUTION !
due to electricity.
WARNING! z Label all wires prior to disconnection
when servicing controls.
z Wiring errors can cause improper and
dangerous operation.
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
12 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Gas Supply 8
8 Gas Supply
EXPLOSION DANGER !
Fig. 7 Gas supply piping: rear view
The possibility for explosions exists due to
Item. 1: Gas supply piping
DANGER!
leaks in gas piping and connections.
Item. 2: Manual shut off valve
z All gas connections must be tested for
Item. 3: Sediment trap
leaks with a soap and water solution.
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 13
8 Gas Supply
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
14 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Combustion Air and Ventilation Openings 9
z Make sure that intake and exhaust z Avoid excessive dust formation and
openings are sufficiently sized and no build-up.
reduction or closure of openings takes
place. NOTICE !
z When the problem is not resolved, do
When one expects contaminated
not operate the boiler.
combustion air (near swimming pools,
z Please note these restrictions and its chemical cleaning operations and hair
dangers to the operator of the boiler. salons), sealed combustion operation is
recommended.
Provisions must be made for combustion air and
ventilation air in accordance with section 5.3 Air for FIRE DANGER !
Combustion and Ventilation, of the National Fuel Gas
Code, ANSI Z 223.1, or applicable provisions of the local due to flammable materials or liquids.
building code. DANGER! z Do not store flammable materials and
Canadian installations must comply with CSA/CGA- liquids in the immediate vicinity of the
B149.1 and .2 Installation Codes. boiler.
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 15
9 Combustion Air and Ventilation Openings
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
16 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Installation of the Exhaust and Air Intake System 10
APPLICATION NOTICE !
OPERATIONAL PROBLEMS !
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 17
10 Installation of the Exhaust and Air Intake System
1 2 3
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
18 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Installation of the Exhaust and Air Intake System 10
z Insert the vent pipe into the terminal body far enough
so that distance between the termination tee and the
wall is about 10" (Fig. 10).
z Secure both ends of the exhaust pipe through the 1
terminal body using the furnished locking collars.
(Fig. 10, Item. 1). Rotate collars downward and
secure set screw on locking collars (Fig. 11, Item. 2).
z Seal the space between vent pipe and locking collars
with silicone (Fig. 11, Item. 1).
1
A venting system that exits the structure through a
sidewall or the like, shall terminate at least 12 inches 2
above the ground.
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 19
10 Installation of the Exhaust and Air Intake System
NOTICE !
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
20 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Installation of the Exhaust and Air Intake System 10
NOTICE !
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 21
10 Installation of the Exhaust and Air Intake System
DANGER !
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
22 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Installation of the Exhaust and Air Intake System 10
DANGER !
NOTICE !
Manufacturer Typ 45° 90° 45° 90° 45° 90° 45° 90°
O-flex-L Star 34 5 10 5 10 5 10 5 10
NOTICE !
NOTICE! To increase overall vent length, use a
The follwing maximum equivalent length of couple of 45° elbows on air intake piping
exhaust pipe (Table 7, page 24 and and run the intake piping at an angle.
Table 9, page 25) represents the maximum
equivalent length of exhaust vent pipe or air
intake pipe only, without condensate drain
tee, vent piping within the termination body
and length of the termination tee. Note that
we only need to be concerned about the
longest run; do not combine intake and
exhaust piping.
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 23
10 Installation of the Exhaust and Air Intake System
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
24 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Installation of the Exhaust and Air Intake System 10
NOTICE ! 2
Do not exceed 10 ft concentric piping with
vertical termination.
Fig. 20 Vertical sealed combustion vent system
Item. 1: Exhaust vent pipe 3“ (models 37, 44 and 53)
Item. 2: Air intake pipe 4“
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 25
11 Placing the Boiler in Operation
DANGER 2
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
26 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Placing the Boiler in Operation 11
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 27
11 Placing the Boiler in Operation
11.1 Lighting Instructions C) Use only your hand to turn the gas control knob.
Never use tools. If the knob will not turn by hand,
For your safety, read these instructions before don't try to repair it, call a qualified service
lighting. technician. Force or attempted repair may result in
a fire or explosion.
WARNING ! D) Do not use this appliance if any part has been under
water. Immediately call a qualified service
due to not follow these instructions.
technician to inspect the appliance and to replace
WARNING! z If you do not follow these instructions any part of the control system and any gas control
exactly, a fire or explosion may result which has been under water.
causing property damage, personal in-
jury or loss of life.
z Follow these operating instructions.
DANGER !
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
28 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Placing the Boiler in Operation 11
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 29
11 Placing the Boiler in Operation
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
30 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Placing the Boiler in Operation 11
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 31
11 Placing the Boiler in Operation
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
32 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Placing the Boiler in Operation 11
4. Fill boiler with water and purge air from the system.
Owner: Signature:__________________
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 33
11 Placing the Boiler in Operation
Table. 13
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
34 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Maintenance 12
12 Maintenance
2. Inspect boiler
4. Clean boiler
Carbon monoxide content (CO), airfree ––––––––––––– ppm ––––––––––––– ppm ––––––––––––– ppm
(Signature)
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 35
12 Maintenance
––––––––––––– ppm ––––––––––––– ppm ––––––––––––– ppm ––––––––––––– ppm ––––––––––––– ppm
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
36 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Maintenance 12
DANGER !
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 37
12 Maintenance
DANGER
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
38 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Maintenance 12
DANGER !
1
2
3 1
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 39
12 Maintenance
Removal of inducer.
1. Remove both screws (Fig. 34, Item. 1) on top rear
jacket cover (Fig. 34, Item. 2).
2. Remove top rear jacket cover (Fig. 34, Item. 2).
2
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
40 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Maintenance 12
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 41
12 Maintenance
7. Remove the rest of the water by shaking the burner Fig. 38 Pilot burner assembly
tubes. Item. 1: Pilot burner assembly
8. When necessary, clean burner box housing and air Item. 2: Pilot gas orifice
intake hose. Item. 3: Pilot gas line
9. Check the burner perforations for free passages; Item. 4: Ignition cable
remove any water from the perforations. If any
perforations are damaged, the burner tray must be
replaced.
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
42 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Maintenance 12
10. Take flue measurements according to the procedure Item. 7: Gas valve
on section 11.5.1 "Taking flue gas measurements", Item. 8: Air intake hose
page 34. Item. 9: Gas control module
Item. 10: Aquastat
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 43
12 Maintenance
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
44 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Maintenance 12
Start
• Checking of aquastat and transformer.
Turn gas supply off. NO * Check for line voltage (120 V) at N and L at plug X1.
If no voltage present, check incoming line voltage.
Supply power to the boiler
LED light up on boiler • * Check if 120 V at L1/L2 and L1X/L2X on aquastat.
(aquastat). If no 120 V present, check wiring.
If wiring is fine, replace aquastat.
• * Check for 24 V between terminals C and R on aquastat
If no voltage present, check wiring.
If wiring is fine, replace transformer.
Turn thermostat to call for heat. • Checking thermostat and its wiring.
* Put jumper between R and W terminals of aquastat
(10 F above room
If boiler starts, check thermostat and thermostat wiring.
temperature).
• Performing self diagnostics on aquastat.
Turn thermostat on aquastat to * Check LED light on aquastat.
call for heat (min. 10 °F above Light blinks 2x: check aquastat sensor contacts S1 and S2 and sensor wiring. If
it all looks fine, replace aquastat sensor.
boiler temperature).
Light blinks 3x or 4x: internal aquastat failure, replace aquastat
LED light off: aquastat is RESET mode, wait 5 minutes for automatic reset
Does fan motor starts?
NO • Check for 24 V between terminals B1 and B2 of aquastat.
If no 24 V, replace aquastat.
• Checking the fan relay and the fan motor.
* Check for 24 V between terminals 1 and 4 of “terminal of boiler block“ strip
(“terminal strip“).
If no 120 V, check wiring between terminal strip and relay and between relay and
terminal plug X1 (incoming power).
If wiring is fine, replace relay.
If 120 V is present between terminals L3 and N of plug X3, check wiring of the fan
blower.
If wiring is fine: replace fan blower
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 45
12 Maintenance
Turn gas supply on. NO Checking gas valve and S 8600 module.
Pilot burners lights.
• Check that all manual gas valves are open, supply tubing and pressures
are good and pilot burner orifice is not blocked.
• Before first start-up, purge the air from gas supply pipe.
• Check electrical connections between module and pilot operator on gas
control.
• Check for 24 V across MV-MV/PV terminals on module. If voltage is fine,
replace gas control. If not, replace module.
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
46 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Maintenance 12
Call for heat ends, system shuts Checking gas valve and S 8600 module.
NO
off. • Check for proper thermostat (controller) operation.
• Remove MV lead at module.
• If valve closes, recheck temperature controller and wiring, replace module
• If valve does not close, replace gas control.
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 47
12 Maintenance
Stage 1
Spark generator powered
Trial for ignition • Pilot valve opens.
END
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
48 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Parts List 13
13 Parts List
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 49
13 Parts List
250
280
300
310
240
320 265
270
260
275
290
140
140
220 230
210 150 80
160
100 140
90
220 140
95 130
30
120
323 180
170
190
321
322
323 110 140
321 35
322
323 40
20
70
25
321
330
140
321
322
323 340
200
322 10
323
65
55
50
60
1021933-02-Kesselblock GA244 "US/CA"
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
50 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Parts List 13
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 51
13 Parts List
60
120
65
70 120
120 120
50
140
120
40
120
90
120
120
30
20 120
Bu
de
rus
GA
24
4
10
130
80 120
100
120
110 120
120 120
52 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Parts List 13
20 Pressure measuring orifice G1/8" (DIN288-1) 0548- 1194 1194 1194 1194
40 Hex.-nut G1/8" 2 2 2 2
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 53
13 Parts List
10
40
30
20
30
50
60 70
54 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Parts List 13
10 Control panel GAW 028 00 compl. "US" - 63026298 63026298 63026299 63026300
30 Sheet metal screw DIN7981 F ST3,5x6,5 A3 see mounting-material for GAW027/GAW028 „US“
50 Sheet meatl screw DIN7981 F ST3,5x16 A3K see mounting-material for GAW027/GAW028 „US“
100 Tooth lock washer DIN6797 A4,3 A3K see mounting-material for GAW027/GAW028 „US“
190 Sheet metal screw DIN7981 C ST3,5x25 A3K see mounting-material for GAW027/GAW028 „US“
210 Sheet metal screw DIN7981 C ST2,9x16 A3K see mounting-material for GAW027/GAW028 „US“
260 Sheet metal screw DIN7981 C ST2,9x25 A3K see mounting-material for GAW027/GAW028 „US“
280 Sheet metal screw DIN7981 F ST3,5x9,5A3K see mounting-material for GAW027/GAW028 „US“
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 55
13 Parts List
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
56 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Parts List 13
10
20
30
30
40
50
50
270
240 60
260
250
210 230
200 210 220
280
170
100
30
100 80
30
180 80 70
190 80
80
190
190 160
140
190 150
100
30 130
90
110
100
30
100
30
120
100
30
Fig. 43 Control panel GAW028
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 57
13 Parts List
10 Burner tray assembly CE244 compl. 6302- 5795 5795 5796 5797
70 Burner tray cover plate CE244 5Gld compl. "US" 6302- 5808 5808 5809 5810
130 Clue Elastosil E 41 in 90ml tube 6301- 1270 1270 1270 1270
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
58 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Parts List 13
100 10
40
50
90
90
20
30
100 60
80
110
70
120
90 20
90 130
80
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 59
13 Parts List
30 Gasket D27x38x2mm C4400 Klinger SIL, green 0548- 9356 9356 9356 9356
60 O-ring gasket 24, 2x3 PERBUNAN 6302- 5931 5931 5931 5931
90 Screw - Set gas valve VR8304 compl. 6302- 5928 5928 5928 5928
s. Screw Set
100 Screw 8x32x11/4 A3T
Gas valve VR8304
Table 19 Gas valve VR8304
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
60 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Parts List 13
10 20
30
20
30
50
50 40
60
60
50
60
70 80
100
80
100
50
90
Fig. 45 Gas valve VR8304
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 61
13 Parts List
40 Pilot gas orifice for natural gas 390686-37 6302- 4518 4518 4518 4518
40 Pilot gas orifice for propane gas 390686-61 6302- 6339 6339 6339 6339
110 Grommet Set CE244 compl. "US" 6302- 5823 5823 5823 5823
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
62 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Parts List 13
90
100
80
20
20
40 10
50
40
50
70
110
60 50
70
90
100
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 63
13 Parts List
20 Insulation CE244 5 section compl. "US" 6302- 5811 5811 5812 5813
30 Ceramic clue Thermofix Tube 115gr. 0203- 7312 7312 7312 7312
40 Manifold CE244 5 section compl. "US" 6302- 5814 5814 5815 5816
s. Screw Set
50 Screw 8x32x1/2
VR8304
s. Screw Set
60 Screw 8x32x11/4 A3T
VR8304
s. Grommet Set
70 Grommet D68/D60/D48/D22
CE244"US"
Screw DIN7500 CE M5x12 CombiTorx
80 6301- 0217 0217 0217 0217
15 pieces/set
110 Sight glas Tempax 30x30x3,3mm 0544- 5802 5803 5804 5804
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
64 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Parts List 13
10
20
30
110
100
90
80
80
40
70
60
50
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 65
13 Parts List
NOTICE!
10 Gas burner CE244 Gr.37/5 G20 compl. "US" 6302- 5798 5799 5800 5801
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
66 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Parts List 13
10
Leistung 37 kW
Ser.-Nr. 63023412-00-3253-000001
00000001
The rating label is placed on the left side of the burner box.
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 67
14 Orifice Tables for High Elevations and Propane
Table 23 Main orifice sizes and high elevations for natural gas
Table 24 Main orifice sizes and high elevations for propane gas
Main orifice 2,05mm 63029401 Vtolerance 2% Main orifice 3,10mm 63034472 Vtolerance 2%
SW16 SW16
Main orifice 2,10 mm 63030024 Length 16 mm Main orifice 3,15 mm 63029406 Length 16 mm
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
68 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Wiring diagrams 15
15 Wiring diagrams
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 69
15 Wiring diagrams
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
70 Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
Wiring diagrams 15
Fig. 51 Wiring diagram – GA244 with control panel Logamatic 2107 or Logamatic 2109
We reserve the right to make any changes due to technical modifications! Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004 71