Equipment Selection
Tabulation of Air Handling Unit Load Data
Tabulation of Air Handling Unit Data Selected
Chilled and cooling water flow in gpm
Schematic diagram of Air Handling Unit/s
High-lighted selected data of AHUs (brochure)
High-lighted Specification of AHUs
3
AHU Selection Data and Chilled Water Flow
AIR-HANDLING UNIT
ITEM
AHU S21 (Zone 2) AHU S22 (Zone 2)
Capacity in Tons (Grand Total Heat or Total 10.49 10.49
Capacity) TC in Tons and BTU/HR 125858.3845 125858.3845
Sensible Capacity (Room Sensible Heat + 6.98 6.98
Outdoor Air Heat) SC in Tons and BTU/HR 83755.1595 83755.1595
Chilled Water Flow in gallons per minute 24.96 gpm 24.96 gpm
(12,000)(10.49)
Chilled Water Flow =
(500)(55 − 45)
4
AHU Selected Data
ITEM AHU (East Ground) AHU (East Ground)
Unit Model/Size LPC-AF 6-E-N LPC-AF 6-E-N
SIZE 6 SIZE 6
Fan CFM (with reference to
3300 3300
DCFM)
Type of Fan (Forward,
FAN
Backward, or Aerofoil Curve FORWARD FORWARD
Blades)
Selected Motor Brake
2.0 2.0
Horsepower
Shift Revolution per Minute 1050 1050
External Static Pressure
(Air Distribution Losses in 0.4643 0.4643
inch water gage)
Internal Static Pressure
(Losses in the AHU in inch 0.9689 0.9689
TOTAL STATIC water gage)
PRESSURE
• Mixing Box 0.1202 0.1202
• Angle Filter 0.1483 0.1483
• Cooling Coil (Air
0.7004 0.7004
Side)
Total Static Pressure 1.4332 1.4332
Cooling Coil Model SIZE 6 SIZE 6
Cooling Coil Capacity in
126495.1132 256274.38
BTU/hr
Face Area in Square Feet 5.6 5.6
Face Velocity in Feet per
554.8192 554.8192
Minute
AIR SIDE Number of Rows per Coil 8 8
Cooling Coil Entering Dry
and Wet Bulb Air 80℉/67℉ 80℉/67℉
COOLING Temperature in F
COIL Cooling Coil Leaving Dry
53.96℉/53.76℉ 53.96℉/53.76℉
and Wet Bulb Air
(53.39℉/52℉) (53.39℉/52℉)
Temperature in F
Cooling Coil Chilled Water
25.31 25.31
Flow in GPM
Cooling Coil Entering and
WATER
Leaving Chilled Water 45℉/55℉ 45℉/55℉
SIDE
Temperature in F
Cooling Coil Chilled Water
4.34 4.34
Pressure Drop in Feet
5
Interpolation:
Mixing Box
𝐌𝐒 ∆𝐏 = 𝟎. 𝟏𝟐𝟎𝟐 𝐢𝐧. 𝐖𝐆
Angle Filter
𝐀𝐅 ∆𝐏 = 𝟎. 𝟏𝟒𝟖𝟑 𝐢𝐧. 𝐖𝐆
6
SELECTED:
2.0 BHP
1.4332 in. WG 1050 RPM
3121.2178 CFM
7
Interpolation:
𝐂𝐂 ∆𝐏 = 𝟎. 𝟕𝟎𝟎𝟒 𝐢𝐧. 𝐖𝐆
8
Interpolation:
Total Capacity
BTU
3000 − 3121.2178 123.0 − TC 1000
= → TC = 126.4951132 MBh × hr
3000 − 3600 123.0 − 840.3 1 MBh
𝐁𝐓𝐔
𝐓𝐂 = 𝟏𝟐𝟔𝟒𝟗𝟓. 𝟏𝟏𝟑𝟐
𝐡𝐫
9
Sensible Capacity
BTU
3000 − 3121.2178 68 − SC 1000
= → SC = 89.6486183 MBh × hr
3000 − 3600 68 − 79.8 1 MBh
𝐁𝐓𝐔
𝐒𝐂 = 𝟖𝟗𝟔𝟒𝟖. 𝟔𝟏𝟖𝟑
𝐡𝐫
LDB
LWB
GPM
WPD
10
11
12
13
14
15
16
17
18
19