Battery voltage calibration SOP

Connect AC input and battery, then turn on, connect the PC and UPS with a USB to RS232
cable, open “UartAssist3.7.2” software, choose the correct COM port, check the setting like
below picture, click “open”

1、 Comparing the reading of multimeter and the reading of the display, you can adjust the
reading on display until it same as the real reading on multimeter,
2、 If send BAP+05, it will increase 0.1V; if send BAP-05, it will decrease 0.1V;
If send BAP+09, it will increase 0.2V; if send BAP-09, it will decrease 0.2V, then continue
send the command until same as the real reading on multimeter.
3、 finally, please press the middle and the right buttons at the same time, then
it will turn to bypass mode,then turn off the AC input breaker,waiting the
display and fans power down by itself

4、 reboot again and check the reading