Professional Documents
Culture Documents
Topic No. 3 Load Characteristics
Topic No. 3 Load Characteristics
Topic No. 3 Load Characteristics
SUBSTATION DESIGN
ENERGY DEMAND
100 KW 100 KW
80 KW 80 KW
40 KW 40 KW
10 KW 10 KW
0 6 AM 7 AM 8 AM 9 AM 0 2 hr 5 hr 11 hr 13 hr
The load duration curve can be daily, weekly, monthly or yearly. Sometimes the plots are
done in per unit values.
LOAD CURVES OF A GENERATING STATION
Peak load
KW
KW
Load curve Peak load Load-duration curve
TIME
The total load supplied by a generating station is
normally divided into three parts: The base load is the load below which the demand
never falls and is supplied 100% of the time. The Peak
✓ Base Load
load occurs for about 15% of the time. The
✓ Intermediate Load intermediate load represents the remaining load
✓ Peak Load region in the curve.
HOW TO DETERMINE LOAD CHARACTERISTICS
MAXIMUM DEMAND: It is the greatest Demand of the Load on the power station
during a given period .
DEMAND FACTOR: It is the ratio of the maximum demand on the power station to its
connected load
Maximum Demand ( KW )
Demand Factor =
Connected Load (KW )
The value of demand factor is usually less than 1. It is expected because maximum
demand on the power station is generally less than the connected load. If the
maximum demand on the power station is 80MW and the connected load is 100MW.
Then demand factor = 80/100 = 0.8 . The knowledge of demand factor is vital in
determining the capacity of the plant equipment.
AVERAGE LOAD: It is the average of loads occurring on the power station in a given
period ( day, month or year ) .
No. of units (kWh) generated in a day
Daily average Load (KW) =
24 hrs
PLANT USE FACTOR: It is the ratio of KWHR generated to the product of plant capacity
and the number of hours for which the plant was in operation
Average demand x T
=
Max. demand x T
Average demand x T
Plant Capacity