Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

IET Power Electronics

Research Article

Fast voltage detection method for grid-tied ISSN 1755-4535


Received on 14th September 2016
Revised 10th April 2017
renewable energy generation systems under Accepted on 25th April 2017
E-First on 24th July 2017
distorted grid voltage conditions doi: 10.1049/iet-pel.2016.0738
www.ietdl.org

Furong Xiao1, Lei Dong1 , Li Li2, Xiaozhong Liao1


1School of Automation, Beijing Institute of Technology, Beijing, People's Republic of China
2Faculty of Engineering and Information Technology, University of Technology, Sydney, Australia
E-mail: correspondent_dong@163.com

Abstract: A fast voltage detection method to assist with the low-voltage ride-through operation of grid-tied renewable energy
generation systems is proposed in this study. It is designed to detect every phase voltage, so that it can be applied in both three-
phase and single-phase applications. The whole voltage detection approach consists of two stages, the pre-filtering stage and
the voltage detection stage. In the pre-filtering stage, a cascaded delayed signal cancellation (CDSC) module and a low-pass
filter are connected in series to filter low-order harmonics and high-frequency noises. For eliminating the low-order harmonics of
interest, different types of CDSC methods are studied in detail. Subsequently, a new orthogonal signal generator is built to
calculate the voltage amplitude in the voltage detection stage. Finally, the proposed voltage detection method is verified by
experimental results.

1 Introduction Since the grid-tied converter is required to respond according to


the variation of either line voltage or phase voltage [7], the adopted
Along with the increasing penetration of distributed renewable voltage detection method should have the capability of detecting
energy generation systems, the grid stability and reliability are now each phase voltage. Consequently, conventional voltage detection
facing significant challenges [1]. Especially, during the grid fault approaches based on three-phase phase-locked loop (PLL) such as
period, the behaviours of grid-tied converters have a significant D axis and Q axis (DQ) transformation method [8] cannot satisfy
impact on the grid stability. For instance, sudden disconnection of the new requirements. Several other voltage detection methods
massive renewable power plants from the grid during voltage sag have been proposed in the literature, e.g. the root mean square
faults may trigger more severe problems than the initial event such (RMS) voltage detection [9], the peak voltage detection [10], and
as power outage and voltage flicker [2, 3]. Hence, many countries the discrete Fourier transform [11–13], whose detection speed is
have enacted their grid codes to guide the operation of grid-tied too slow for LVRT operation. The peak voltage detection method
renewable power systems [4, 5]. These new grid codes require maximally introduces half grid cycle delay, whereas both the RMS
grid-tied converters be capable of low-voltage ride-through and fast Fourier transform (FFT) related methods induce one grid
(LVRT) when suffering grid voltage sag. cycle delay [14]. Furthermore, for ensuring an accurate detection of
Fig. 1a shows the Chinese LVRT standard for large-capacity the grid voltage under distorted conditions, the low-order
grid-tied photovoltaic (PV) inverters. As shown, PV inverters harmonics and unbalanced variations of the grid voltage should be
should stay connected to the grid in the shaded area. Besides, they considered during the design. The current solutions are to either
are also required to provide reactive power for dynamic network insert a digital filter into the PLLs [15–17], or use the positive and
support during the fault period and in the recovery process [6]. The negative component separation methods [18, 19] to extract the
E.ON code shown in Fig. 1b defines the amount of the reactive fundamental voltage component for calculating the grid voltage.
current injected to the grid during LVRT. The injection of reactive Note that detecting each phase voltage separately with three
power should be sufficiently fast, e.g. the PV system should deliver independent single-phase PLLs is also valid for unbalanced voltage
the required reactive power within 30 ms [7]. Moreover, faster variations. However, as a matter of fact, the settling time of PLL-
detection of the voltage sag means that the grid-tied converter has related methods generally cannot be less than one grid cycle, so
more response time, which is beneficial for the converter safety. that PLLs are not suitable for detecting the grid voltage variation
Therefore, the voltage variation ratio should be detected as fast as ratio during LVRT operation. Ma et al. [14] present a new
possible.

Fig. 1 LVRT requirements


(a) China: company and grid state grid (Q/GDW) 617–2011, (b) E.ON code for LVRT

IET Power Electron., 2017, Vol. 10 Iss. 12, pp. 1487-1493 1487
© The Institution of Engineering and Technology 2017
17554543, 2017, 12, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0738 by Bangladesh Hinari NPL, Wiley Online Library on [11/03/2024]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 2 Phase voltage of the three-phase power grid
(a) Voltage detection approach for three-phase systems, (b) Proposed voltage detection method for each phase

detection method which is to detect both the maximum and zero the help of the proposed OSG and also the new DSC operators, the
voltage points. Its response time is affected by the position at grid voltage can be fast and accurately detected in this paper.
which the voltage variation occurs, and the largest time delay is
10.1 ms. 2 Proposed voltage detection method under ideal
In light of the above-mentioned issues, a new voltage detection
scheme, which can provide fast detection speed and also high
conditions
accuracy, is proposed in this paper. The presented method is not Given the same detection principle of each phase voltage in Fig. 2,
only applicable to single-phase power systems, but also can be only the phase a V a(t) = V ap sin(ωt), where V ap is the voltage
used for detecting every phase voltage of the three-phase power amplitude and ω is the angular frequency, is used for illustration in
grid as shown in Fig. 2. In this manner, the magnitude of each this paper. Generally, an orthogonal signal V β(t) with respect to the
phase voltage can be accurately obtained even if unbalanced grid original voltage signal V a(t) can be generated, so that the
faults happen in three-phase power systems. magnitude of the single-phase grid voltage can be given by
To facilitate the magnitude estimation of the single-phase
voltage, an extra orthogonal signal to the original single-phase V ap = V a2 + V β2 . To achieve this goal, a new OSG algorithm with
voltage is generally generated. In the literature, the second-order high-noise immunity and high accuracy in a wide range of
generalised integrator (SOGI) [20], the quarter-cycle delay [21], sampling frequencies is proposed in this section and can be
and the first-order differential method [22, 23] are the most popular expressed as (see (1)) in which T 1 is a predetermined delay time,
orthogonal signal generator (OSG) methods. SOGI provides low and λ1 and λ2 are functions of T 1 and the grid angular frequency ω.
computation burden and strong filtering capability. However, it Different from previous OSGs, the developed OSG creates an
exhibits a settling time of more than half of the fundamental period orthogonal frame of V ap sin(ωt − 0.5ωT 1) and V ap cos(ωt − 0.5ωT 1)
[24]. Although the quarter-cycle delay technique is easy to instead of V ap sin(ωt) and V ap cos(ωt). It is worth noting that (1) is
implement and also fast, it still introduces a time delay of one obtained by rigorous mathematical deduction without any
fourth of the fundamental period. Comparatively, the first-order approximation, so that the accuracy of the proposed OSG is
differential method may be the fastest OSG. However, higher independent of the sampling frequency (see Fig. 3). From (1), the
accuracy of the first-order differential method requires higher magnitude of the grid voltage can be achieved as V ap = V 12 + V 22.
sampling frequency, yet the high-frequency noise in the sampling
Note that T 1 is the only parameter which needs to be tuned in
process will be further amplified inevitably. To deal with these
the proposed OSG. In what follows, the design considerations of T 1
issues, a new OSG, which can provide fast dynamic response,
high-noise immunity, and also high accuracy, is first presented in are derived from the viewpoint of high-frequency noise
this paper. consideration. Considering the high-frequency random noise V x in
~
Nowadays, with more and more non-linear loads are connected the sampling process as V a(t) = V a(t) + V x(t), (1) can be rewritten
to modern power systems, low-order harmonics are inevitably as (see (2))
present in the grid voltage, especially in a weak power grid. To The physical quantities with superscript ∼ in this paper indicate
extend the developed OSG to distorted conditions, the delayed the existence of random noise. In (2) (see (3)) where k1 and k2 are
signal cancellation (DSC) technique, which has the advantages of the possible maximal noise amplification factors of the developed
easy implementation and less computational burden [25–27], is OSG in the worst condition. Since T 1 is designed below 0.25 grid
used as a pre-filter for common odd harmonics rejection periods for the sake of fast dynamic response, k1 is smaller than k2,
consideration. To be specific, a cascaded DSC (CDSC) module and so that k2 is mainly considered during the tuning of T 1. Obviously,
a low-pass filter are designed in the pre-filtering stage to eliminate k2 decreases remarkably and the response time increases linearly
the concerned low-order odd harmonics and high-frequency noise, with the increased T 1. Consequently, it is necessary to find a good
respectively. Different from previous DSC operators, a new DSC compromise between noise reduction and response speed.
operator, which can be designed more flexibly and has the potential Industrial experience suggests that a noise amplification factor of
to reduce the involved time delays, is introduced in this paper. With 10 can fully meet the precision requirement in most cases [28].

V a(t) + V a(t − T 1) V ap sin(ωt) + V ap sin(ωt − ωT 1)


V 1(t) = = = V ap sin(ωt − 0.5ωT 1)
λ1 2 cos(0.5ωT 1)
(1)
V a(t) − V a(t − T 1) V ap sin(ωt) − V ap sin(ωt − ωT 1)
V 2(t) = = = V ap cos(ωt − 0.5ωT 1)
λ2 2 sin(0.5ωT 1)
1488 IET Power Electron., 2017, Vol. 10 Iss. 12, pp. 1487-1493
© The Institution of Engineering and Technology 2017
17554543, 2017, 12, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0738 by Bangladesh Hinari NPL, Wiley Online Library on [11/03/2024]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
mentioned voltage detection. In practise, the allowable variation
range of the grid frequency is generally small in the normal
operation mode such as 0.2 Hz in China, which has negligible
influence on the accuracy of the developed voltage detection
method. Hence, this paper mainly focuses on the grid voltage
variation cases.

3 Proposed voltage detection method under


distorted conditions
To accurately detect the magnitude of grid voltage regardless of
low-order harmonics, a CDSC module-based pre-filtering stage is
used for filtering the sampled grid voltage signal before sending it
to the above-mentioned OSG. Similar to [14, 29], the low-order
harmonics 5th, 7th, 11th, and 13th are considered in this paper
because they are generally the dominant low-order harmonics in
the power grid. Although the developed pre-filtering stage is
designed for rejecting the low-order harmonics 5th, 7th, 11th, and
13th, it is not restrictive and can be easily extended to more
harmonics. In what follows, three different CDSC methods are
discussed and compared.

3.1 CDSC method I


The CDSC method I (see Fig. 4) based on the original DSC
(ODSC) [25–27] is used for eliminating the low-order harmonics
of interest. For the sake of simplicity, the grid voltage with only the
nth odd harmonic as V a(t) = V ap sin(ωt + θ1) + V n sin(nωt + θn) is
Fig. 3 Orthogonal signals constructed by the proposed OSG under assumed for illustrating the principle of the operator ODSCn. The
different sampling frequencies output signal ODSCno of the operator ODSCn is given by
(a) Generated Signal V 1, (b) Generated signal V 2
Tf
ODSCno(t) = V a(t) + V a(t − td) = V a(t) + V a t −
Considering the required fast detection of voltage sags during 2n
LVRT applications, T 1 is set as 1 ms, so that k1 = 1.01 and = V ap sin(ωt + θ1) + V n sin(nωt + θn)
k2 = 6.39. Namely, the response time of the designed OSG is 1 ms
π (4)
in this work. The possible high-frequency noises can be rejected by +V ap sin ωt + θ1 − + V n sin(nωt + θn − π)
a low-pass filter with 1 kHz cut-off frequency in the pre-filtering n
stage as shown in Fig. 2b. In addition to the above-mentioned high- π π
frequency noise, the rejection of the possible low-order voltage = 2V ap cos sin ωt + θ1 −
2n 2n
harmonics is also our concern. In this work, the proposed OSG is
mainly designed for fast generating the required orthogonal signals, in which T f is the fundamental period and td is the delay time. It is
while the rejection of low-order harmonics is conducted in the pre- clear that the output signal is free from the nth odd harmonic, while
filtering stage. the fundamental component suffers from fixed amplitude and phase
Note that (1) is derived on the premise of known grid frequency angle shifts. Note that, the nth odd harmonic can be removed by
ω. Generally, the grid frequency is often measured with a PLL in ODSCn only when td = T f /(2n). Moreover, each ODSC block can
grid-tied power converters. Therefore, it is reasonable to assume only remove one specific order odd harmonic, so that four ODSC
the grid frequency is known for implementing the proposed OSG. operators are required in the CDSC method I. The total delay time
The frequency ω for calculating λ1 and λ2 should only update after of the CDSC method I is 0.255T f , i.e. 5.1 ms for a 50 Hz power
the PLL settles to a new steady state. Consequently, the dynamic
system (the grid frequency is assumed to be always 50 Hz in the
process of the PLL in response to voltage variations (amplitude or
following discussion).
phase angle jump) does not affect the performance of the above-

~ ~
~ V a(t) + V a(t − T 1) [V ap sin(ωt) + V x(t)] + [V ap sin(ωt − ωT 1) + V x(t − T 1)]
V 1(t) = =
2 cos(0.5ωT 1) 2 cos(0.5ωT 1)
V x(t) + V x(t − T 1)
= V ap sin(ωt − 0.5ωT 1) +
2 cos(0.5ωT 1)
= V ap sin(ωt − 0.5ωT 1) + V 1n
~ ~ (2)
~ V a(t) − V a(t − T 1) [V ap sin(ωt) + V x(t)] − [V ap sin(ωt − ωT 1) + V x(t − T 1)]
V 2(t) = =
2 sin(0.5ωT 1) 2 sin(0.5ωT 1)
V x(t) − V x(t − T 1)
= V ap cos(ωt − 0.5ωT 1) +
2 sin(0.5ωT 1)
= V ap cos(ωt − 0.5ωT 1) + V 2n

|V x(t) + V x(t − T 1)| |V x(t) | + | V x(t − T 1)| |V x|


|V 1n| = ≤ ≤ = k1 | V x|
|2 cos(0.5ωT 1)| |2 cos(0.5ωT 1)| |cos(0.5ωT 1)|
(3)
|V x(t) − V x(t − T 1)| |V x(t) | + | V x(t − T 1)| |V x|
|V 2n| = ≤ ≤ = k2 | V x|
|2 sin(0.5ωT 1)| |2 sin(0.5ωT 1)| |sin(0.5ωT 1)|
IET Power Electron., 2017, Vol. 10 Iss. 12, pp. 1487-1493 1489
© The Institution of Engineering and Technology 2017
17554543, 2017, 12, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0738 by Bangladesh Hinari NPL, Wiley Online Library on [11/03/2024]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Fig. 4 Three types of CDSC methods for eliminating the 5th, 7th, 11th, and 13th harmonics

3.2 CDSC method II the CDSC method I. However, the possible maximal noise
amplification factor of such four PDSC blocks is 81, which may be
In addition to the ODSC operator, the proposed DSC (PDSC) not preferred in practise. Alternatively, the 5th and 7th harmonics
operator PDSCn for cancelling the nth odd harmonic is first are eliminated with PDSC5 and PDSC7, respectively, and the 11
discussed. Also, the input and 13th harmonics are removed with ODSC11 and ODSC13,
V a(t) = V ap sin(ωt + θ1) + V n sin(nωt + θn) is used to illustrate the
respectively, as shown in Fig. 4. This method provides 4 ms time
principle of the operator PDSCn as (see (5)) delay with the total noise amplification factor of 9, and is called the
It is obvious that the nth odd harmonic can be eliminated for CDSC method II.
any given td > 0. A close observation of (4) and (5) reveals that
ODSCn is a special case of PDSCn with td = T f /(2n). Next, how to 3.3 CDSC method III
design PDSCn for eliminating the nth odd harmonic with less time
delay is given in detail. Considering the high-frequency random In the above discussion, either ODSCn or PDSCn is designed to
~ eliminate only the nth odd harmonic, so that four cascaded
noise V x in the sampling process as V a(t) = V a(t) + V x(t), (5) can
be rewritten as (see (6)) operators are required for cancelling the 5th, 7th, 11th, and 13th
The ratio of the random noise to the amplitude of the harmonics. In this section, a new harmonic elimination operator
fundamental component in (6) is defined as PDSCn&m with specifically designed delay factor is introduced to
remove the nth and mth odd harmonics (m > n) simultaneously. As
|V x(t) + V x(t − td) − 2 cos(0.5nωtd)V x(t − 0.5td)| a result, the number of cascaded blocks can be reduced by half,
F(td, n) = thus reducing the computation and delay time. The principle of
|2[cos(0.5ωtd) − cos(0.5nωtd)]V ap|
(7) PDSCn&m is illustrated as (see (9))
|V x | + | V x | + | 2cos(0.5nωtd) | | V x| |V x| As mentioned above, the nth harmonic can be removed
≤ = k3(td, n)
|2[cos(0.5ωtd) − cos(0.5nωtd)]V ap| V ap regardless of td, whereas the mth harmonic can be eliminated only
if
where k3(td, n) is termed as the possible maximal noise
amplification factor of PDSCn in the worst case. While in ODSCn cos(0.5mωtd) − cos(0.5nωtd) = 0 (10)
(see (8))
Fig. 5 shows the relationship of the noise amplification factor From (10), to eliminate both the nth and mth harmonics within
versus the delay time. It is clear that the noise amplification factor the same operator PDSCn&m, the corresponding delay time can be
k3(td, n) of PDSCn decreases with the increased td in the shown derived as
range. In terms of LVRT operation, a faster detection of the grid
voltage variation ratio is preferred. Therefore, k3 is set to around 3, jT f jT f
td = or , m > n, j = 1, 2, 3, … (11)
so that the total delay time of four cascaded PDSCn (n = 5, 7, 11, 0.5(n + m) 0.5(m − n)
13) operators is 3.43 ms, which is 1.67 ms less than that (5.1 ms) of

PDSCno(t) = V a(t) + V a(t − td) − 2 cos(0.5nωtd)V a(t − 0.5td)


= V ap sin(ωt + θ1) + V n sin(nωt + θn)
+V ap sin(ωt + θ1 − ωtd) + V n sin(nωt + θn − nωtd)
(5)
−2cos(0.5nωtd)[V ap sin(ωt + θ1 − 0.5ωtd)
+V n sin(nωt + θn − 0.5nωtd)]
= 2[cos(0.5ωtd) − cos(0.5nωtd)]V ap sin(ωt + θ1 − 0.5ωtd)

~ ~ ~ ~
PDSCno(t) = V a(t) + V a(t − td) − 2 cos(0.5nωtd)V a(t − 0.5td)
= 2[cos(0.5ωtd) − cos(0.5nωtd)]V ap sin(ωt + θ1 − 0.5ωtd) (6)
+[V x(t) + V x(t − td) − 2cos(0.5nωtd)V x(t − 0.5td)]

~ ~ ~ Tf π π Tf
ODSCno(t) = V a(t) + V a t − = 2V ap cos sin ωt + θ1 − + Vx + Vx t −
2n 2n 2n 2n
(8)
Tf |V x + V x t − (T f /2n) | |V x| Tf |V x|
F ,n = ≤ = k3 ,n
2n |2 cos(π/2n)V ap| |cos(π/2n) | V ap 2n V ap
1490 IET Power Electron., 2017, Vol. 10 Iss. 12, pp. 1487-1493
© The Institution of Engineering and Technology 2017
17554543, 2017, 12, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0738 by Bangladesh Hinari NPL, Wiley Online Library on [11/03/2024]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
can reduce the computational load compared with the CDSC I and
II methods. In addition, the total delay time of the CDSC method
III is 4.4 ms which is 0.7 ms less than that of the CDSC method I.
From (7), the noise amplification factors of PDSC5&13 and
PDSC7&11 can be derived as

Tf (1 + | cos(0.5nωtd) | )
k3 ,5 =
9 |cos(0.5ωtd) − cos(0.5nωtd)|
(1 + | cos(5π/9) | )
= = 1.054, PDSC5&13
|cos(π/9) − cos(5π/9)|
(13)
Tf (1 + | cos(0.5nωtd) | )
k3 , 7 =
9 |cos(0.5ωtd) − cos(0.5nωtd)|
Fig. 5 Noise amplification factor versus the delay time
(1 + | cos(7π/9) | )
= = 1.035, PDSC7&11
|cos(π/9) − cos(7π/9)|

The noise amplification factors of the designed PDSC5&13 and


PDSC7&11 are close to one, which means the CDSC method III has
nearly the same noise rejection capability as the CDSC method I
according to Fig. 5.
Note that the operator PDSCn in the CDSC method II is used
for only eliminating the nth odd harmonic, so that the
corresponding delay time td can be selected flexibly. As mentioned
above, the nth odd harmonic can be eliminated for any given
td > 0. However, the operator PDSCn&m in the CDSC method III is
designed for eliminating both the nth and mth harmonics, so that
Fig. 6 Simulation results of PDSC5&13 and the cascaded block with the corresponding delay time cannot be selected free like that in the
PDSC5 and PDSC13 CDSC II method and must be td = 2T f /(n + m).
It follows from (4), (5), and (9) that the pre-filtering stage
For the purpose of short time delay, the delay time should be introduces a fixed magnitude shift on the fundamental component,
chosen as which can be entirely compensated by using a factor kamp as shown
in Fig. 2b. The compensating factors for different CDSC methods
2π Tf can be derived from (4), (5), and (9) and are given by (see (14))
td = = (12)
0.5(n + m)ω 0.5(n + m)
3.4 Comparison with previous voltage detection methods
Therefore, to eliminate the 5th and 13th harmonics, the delay
time of PDSC5&13 should be T f /9. The simulation results of The comparison results between previous voltage detection
methods and the proposed ones with different CDSC methods in
PDSC5&13 and the cascaded block with two separate operators
terms of the response time are listed in Table 1 for the condition of
PDSC5 and PDSC13 are given in Fig. 6. The delay times of PDSC5 three-phase unbalanced voltage drop with low-order harmonics.
and PDSC13 are chosen as T f /10 and T f /26, respectively. It can be The proposed method can estimate the magnitude of the grid
observed that these two methods can effectively eliminate the 5th voltage within 6.6 ms (CDSC I) or 5.5 ms (CDSC II) or 5.9 ms
and 13th harmonics, while holding different voltage gains for the (CDSC III) when considering the dominant low-order harmonics
fundamental components 5th, 7th, 11th, and 13th. It is worth noting that the response time
mentioned here is obtained considering both the pre-filtering stage
V α = sin(100πt) + 0.2 sin(500πt) + 0.1 sin(1300πt) and the voltage detection stage. In terms of the dynamic
performance, the proposed voltage detection methods perform
Similarly, PDSC7&11 with td = T f /9 can remove both the 7th better than most of the previous ones which can provide accurate
and 11th harmonics. Consequently, only two cascaded blocks, voltage measurement under distorted conditions.
PDSC5&13 and PDSC7&11, are enough for eliminating the 5th, 7th,
11th, and 13th harmonics, and this method is named as the CDSC
method III. With half number of cascaded blocks, this approach

V a(t) = V ap sin(ωt + θ1) + V n sin(nωt + θn) + V m sin(mωt + θm)


PDSCn&mo(t) = V a(t) + V a(t − td) − 2 cos(0.5nωtd)V a(t − 0.5td)
= V ap sin(ωt + θ1) + V n sin(nωt + θn) + V m sin(mωt + θm)
V ap sin(ωt + θ1 − ωtd) + V n sin(nωt + θn − nωtd)
+
+V m sin(mωt + θm − mωtd)
V ap sin(ωt + θ1 − 0.5ωtd) + V n sin(nωt + θn − 0.5nωtd)
−2 cos(0.5nωtd) (9)
+V m sin(mωt + θm − 0.5mωtd)
= 2 cos(0.5ωtd) − cos(0.5nωtd) V ap sin(ωt + θ1 − 0.5ωtd)
+2 cos(0.5nωtd) − cos(0.5nωtd) V n sin(nωt + θm − 0.5nωtd)
+2 cos(0.5mωtd) − cos(0.5nωtd) V m sin(mωt + θm − 0.5mωtd)
= 2 cos(0.5ωtd) − cos(0.5nωtd) V ap sin(ωt + θ1 − 0.5ωtd)
+2 cos(0.5mωtd) − cos(0.5nωtd) V m sin(mωt + θm − 0.5mωtd)
IET Power Electron., 2017, Vol. 10 Iss. 12, pp. 1487-1493 1491
© The Institution of Engineering and Technology 2017
17554543, 2017, 12, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0738 by Bangladesh Hinari NPL, Wiley Online Library on [11/03/2024]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
Table 1 Detection time comparison of different methods considering low-order harmonic distortion
Detection methods FFT-based methods [11–13] RMS method [9] Method [14] Proposed method
CDSC I CDSC II CDSC III
response times 20 ms 20 ms 5–10.1 ms 6.6 ms 5.5 ms 5.9 ms

Fig. 7 Experimental results of the proposed voltage detection method


(a) CDSC method I, (b) CDSC method II, (c) CDSC method III

4 Experimental results performance of the developed voltage detection method. All the
operations are conducted with 10 kHz sampling frequency. The
The proposed voltage detection method is verified experimentally corresponding experimental results are shown in Fig. 7. It can be
on a digital signal processor chip TMS30F28335-based platform. observed that the detection method with CDSC I, CDSC II, or
The normal voltage amplitude is 310 V and the dropped voltage CDSC III can fast detect the voltage amplitude under generally
amplitude is set to 200 V. Along with the voltage amplitude drop, distorted grid voltages. The response time of the approach with
the 5th (6%), 7th (4.8%), 11th (4%), and 13th (3.2%) voltage PDSC (CDSC II or CDSC III) is less compared with the one
harmonics are added for testing the harmonic rejection

1
kamp = = 0.0686, CDSCI
16 cos(π/10)cos(π/14)cos(π/22)cos(π/26)
1
kamp =
4[cos(7π/100) − cos(7π/20)][cos(9π/200) − cos(63π/200)]
(14)
1
× = 0.2021, CDSCII
4 cos(π/22)cos(π/26)
1
kamp = = 0.1316, CDSCIII
4[cos(π/9) − cos(5π/9)][cos(π/9) − cos(7π/9)]
1492 IET Power Electron., 2017, Vol. 10 Iss. 12, pp. 1487-1493
© The Institution of Engineering and Technology 2017
17554543, 2017, 12, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-pel.2016.0738 by Bangladesh Hinari NPL, Wiley Online Library on [11/03/2024]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
(CDSC I) based on ODSC. The achieved reduction of the delay [20] Ciobotaru, M., Teodorescu, R., Blaabjerg, F.: ‘A new single-phase PLL
structure based on second order generalized integrator’. Proc. 37th IEEE
time by using PDSC is limited in this paper; however, the freedom PESC, 2006, pp. 1511–1516
to design the time delay as well as the possibility to reduce the [21] Zhang, R., Cardinal, M., Szczesny, P., et al.: ‘A grid simulator with control of
number of cascaded modules makes PDSC interesting for single-phase power converters in D–Q rotating frame’. Proc. IEEE Power
applications related to harmonics cancellation. As shown in Fig. 7, Electronics Specialists Conf., 2002, pp. 1431–1436
[22] Luo, A., Chen, Y.D., Shuai, Z.K., et al.: ‘An improved reactive current
it can be guaranteed that the generated signals V1 and V2 are detection and power control method for single-phase photovoltaic grid-
mutually orthogonal and clear even if the input grid voltage connected DG system’, IEEE Trans. Energy Convers., 2013, 28, (4), pp. 823–
contains low-order harmonics. Note that V1 is not in phase with the 831
[23] Roshan, A., Burgos, R., Baisden, A.C., et al.: ‘A D-Q frame controller for a
fundamental component of the input signal due to the phase delays full-bridge single phase inverter used in small distributed power generation
caused by the pre-filtering stage and the proposed OSG. systems’. Proc. IEEE Applied Power Electronics Conf., 2007, pp. 641–647
[24] Kulkarni, A., John, V.: ‘A novel design method for SOGI-PLL for minimum
settling time and low unit vector distortion’. Industrial Electronics Society,
5 Conclusions IECON 2013-39th Annual Conf. of the IEEE, 2013, pp. 274–279
[25] Neves, F.A.S., Cavalcanti, M. C., de Souza, H. E. P., et al.: ‘A generalized
This paper presents a fast voltage detection method to assist with delayed signal cancellation method for detecting fundamental-frequency
the LVRT operation of grid-tied renewable energy generation positive-sequence three-phase signals’, IEEE Trans. Power Deliv., 2010, 25,
systems. With the proposed approach, the magnitude of each phase (3), pp. 1816–1825
voltage in three-phase power systems can be measured in a fast and [26] Svensson, J., Bongiorno, M., Sannino, A.: ‘Practical implementation of
delayed signal cancellation method for phase-sequence separation’, IEEE
accurate way regardless of unbalanced grid faults and low-order Trans. Power Deliv., 2007, 22, (1), pp. 18–26
odd harmonics. Also, the developed voltage detection method can [27] Wang, Y.F., Li, Y.W.: ‘Grid synchronization PLL based on cascaded delayed
be applicable to single-phase power systems. First, a new OSG signal cancellation’, IEEE Trans. Power Electron., 2011, 26, (7), pp. 1987–
with relatively fast response speed is analysed in detail. Second, 1997
[28] Xiong, L., Zhuo, F., Wang, F., et al.: ‘A fast orthogonal signal-generation
based on the concept of DSC, a novel harmonic cancellation block algorithm characterized by noise immunity and high accuracy for single-
is designed, so that both the delay time and number of the CDSC phase grid’, IEEE Trans. Power Electron., 2016, 31, (3), pp. 1847–1851
blocks required for eliminating the low-order odd harmonics of [29] Wang, Y.F., Li, Y.W.: ‘Three-phase cascaded delayed signal cancellation PLL
interest can be reduced. Finally, the presented voltage detection for fast selective harmonic detection’, IEEE Trans. Ind. Electron., 2013, 60,
(4), pp. 1452–1463
method is verified by experimental results.

6 References
[1] Yang, S., Lei, Q., Peng, F.Z., et al.: ‘A robust control scheme for grid-
connected voltage-source inverters’, IEEE Trans. Ind. Electron., 2011, 58, (1),
pp. 202–212
[2] Kovanen, K.O.: ‘Photovoltaics and power distribution’, Renew. Energy Focus,
2013, 14, (3), pp. 20–21
[3] Bae, Y., Vu, T.K., Kim, R.Y.: ‘Implemental control strategy for grid
stabilization of grid-connected PV system based on German grid code in
symmetrical low-to-medium voltage network’, IEEE Trans. Energy Convers.,
2013, 28, (3), pp. 619–631
[4] E.ON Netz GmbH: ‘Grid code high and extra high voltage Bayreuth’ (E.ON
Netz GmbH, Germany, 2006)
[5] Energinet: ‘Regulation TF 3.2.5 wind turbines connected to grids with
voltages above 100 kV’ (Denmark, 2010)
[6] Marinopoulos, A., Papandrea, F., Reza, M., et al.: ‘Grid integration aspects of
large solar PV installations: LVRT capability and reactive power/voltage
support requirements’. IEEE PowerTech Conf., Trondheim, 2011, pp. 1–8
[7] ‘Technical requirements for connecting photovoltaic power station to power
system’, Technical Report, GB/T 19964-2012, China, December 2012
[8] Kumsuwan, Y., Sillapawicharn, Y.: ‘A fast synchronously rotating reference
frame-based voltage sag detection under practical grid voltages for voltage
sag compensation systems’. Proc. Sixth IET Int. Conf. Power Electronics,
Machines, and Drives, 2012, pp. 1–5
[9] Styvaktakis, E., Bollen Seniorand, M.H.J., Gu, I.Y.J.: ‘Automatic
classification of power system events using rms voltage measurements’. Proc.
Power Engineering Society Summer Meeting, 2002, pp. 824–829
[10] Naidoo, R., Pillay, P.: ‘A new method of voltage sag and swell detection’,
IEEE Trans. Power Deliv., 2007, 22, (2), pp. 1056–1063
[11] Zou, W.H., Su, S.P.: ‘Voltage flicker detection based on wavelet Fourier
transform’. Proc. Int. Conf. Electrical and Control Engineering, 2011, pp.
4218–4220
[12] Jacobsen, E., Lyons, R.: ‘The sliding DFT’, IEEE Signal Process. Mag., 2003,
20, (2), pp. 74–80
[13] Jacobsen, E., Lyons, R.: ‘An update to the sliding DFT’, IEEE Signal Process.
Mag., 2004, 21, (1), pp. 110–111
[14] Ma, C., Gao, F., He, G, et al.: ‘A voltage detection method for the voltage
ride-through operation of renewable energy generation systems under grid
voltage distortion conditions’, IEEE Trans. Sustain. Energy, 2015, 6, (3), pp.
1131–1139
[15] Wang, Y.F., Li, Y.W.: ‘Analysis and digital implementation of cascaded
delayed-signal-cancellation PLL’, IEEE Trans. Power Electron., 2011, 26, (4),
pp. 1067–1080
[16] Lee, K.J., Lee, J.P., Shin, D., et al.: ‘A novel grid synchronization PLL
method based on adaptive low-pass notch filter for grid-connected PCS’,
IEEE Trans. Ind. Electron., 2014, 61, (1), pp. 292–301
[17] Golestan, S., Ramezani, M., Guerrero, J.M., et al.: ‘Moving average filter
based phase-locked loops: performance analysis and design guidelines’, IEEE
Trans. Power Electron., 2014, 29, (6), pp. 2750–2763
[18] Rodriguez, P., Pou, J., Bergas, J.: ‘Decoupled double synchronous reference
frame PLL for power converters control’, IEEE Trans. Power Electron., 2007,
22, (2), pp. 584–592
[19] Yazdani, D., Mojiri, M., Bakhshai, A., et al.: ‘A fast and accurate
synchronization technique for extraction of symmetrical components’, IEEE
Trans. Power Electron., 2009, 24, (3), pp. 674–684

IET Power Electron., 2017, Vol. 10 Iss. 12, pp. 1487-1493 1493
© The Institution of Engineering and Technology 2017

You might also like