Professional Documents
Culture Documents
5 Selection and Erection of Equipment
5 Selection and Erection of Equipment
r"'"\
i,, urennnv '"
125
CHAPTER 51
GOMMON RULES
CONTENTS
CHAPTER 5,I COMMON RULES
510 INTRODUCTION
510.'l General
510.2 /Vot used
511 COMPLIANCE WITH STANDARDS
5'.l2 OPERATIONAL CONDITIONS AND EXTERNAL INFLUENCES
5',12.1 Operational conditions
512.1.1 Voltage
512.1.2 Current
512.',t.3 Frequency
512.1.4 Power
5',t2.1.5 Compatibility
512.1.6 lmpulse withstand voltage
512.2 External influences
513 ACCESSIBILITY
514 IDENTIFICATION AND NOTICES
514.',| General
514.3 ldentification of conductors
5',14.4 ldentiflcation of conductors by colour
514.4.1 Neutral or midpoint conductor
s',t4.4.2 Protective conductor
514.4.3 PEN conductor
514.4.4 Other conductors
514,4.6 Bare conductors
5'14.5 ldentification of conductors by letters and/or numbers
514.5.2 Protective conductor
514.5.3 Alphanumeric
514.5.4 Numeric
514.6 Omission of identification by colour or marking
514.7 Not used
s14.8 ldentification of a protective device
514,9 Diagrams and documentation
514.10 Warning notice: voltage
514.11 Warning notice: isolation
514.12 Notices: periodic inspection and testing
5',t4.13 Warning notices: earthing and bonding connections
514.14 Warning notice: non-standard colours
514.15 Warning notice: alternative supplies
514.16 Notice: high protective conductor current
515 PREVENTION OF MUTUAL DETRIMENTAL INFLUENCE
515.1 Prevention of mutual detrimental influence
't26
CHAPTER 51
COMMON RULES
510 INTRODUCTION
s10.1 General
This chapter deals with the selection of equipment and its erection. lt provides common rules for compliance with
measures of protection for safety, requirements for proper functioning lor il]tel]ded use of the installation, and
requirements appropriate to the extenlal influences.
s10.3 Every item ofequipment shall be selected and erected so as to allow compliance with the regulations
stated in this chapter and the relevant regulations in other parts ofBS 7671 and shall take account ofmanufacturers'
instructions.
Altematively, ifequipment complying with a foreign national standard based on an IEC Standard is to be used, the
designer or other person responsible lor specifying the installation shall verify that any differences between that
stardard and the coffesponding British or Harmonized Standard will not result in a lesser degree of safety than that
afforded by compliance with the British or Hamonized Standard. Such use shall be recorded on the appropriate I
511.2 Where equipment to be used is not covered by a British or Harmonized Standard or is to be used I
outside the scope ofits standard, the designer or other person responsible for specifying the installation shall conlinr]
that the equipment provides at leasl thc samc dcgrcc of safcty as that affordcd by compliancc u,ith thc Rcgulations.
Such use shall be noted and appended to the appropriate documertation specifled in Pal1 6.
512.1.2 Current
Every ite[r ofequipment shall be suitable for:
(i) the design cun'ent, taking into account any capacitive and inductive effects, and
(ii) the current tikely to flow in abnormal conditions for such periods of time as are determined by the
characteristics olthe protective devices concemed.
512.1.3 Frequency
If frequencyhas an influence on the characteristics of the equipment, the rated frequency of the equipment shall
conespond to the nominal frequency ofthe supply to the circuit concerned.
512.1.4 Power
Every item of equipment selected on the basis of its power chamctedstics shall be suitable for the duty demanded
oI the equipment.
^-. 127
512.1.5 Compatibility
Every ite[r ofequipment shall be selected and erected so that it will neither cause harmful effects to other equipment
nol il1rpair the supply during normal service including switching operations.
Switchgear, protective devices, accessories and other types of equipment shall not be connected to conducton
intended to operate at a temperature exceeding 70 'C at the ecluipment in normal service unless the equipment
rnanufacturer has confinned that the equipment is suitable for such conditions, or the co[ductor size shall be chosen
based on the cu-rent ratings for 70 'C cables ofa similar construction. See also Regulation 523.1 and Table 4A3.
The designer ofthe fixed installatiol shall veri& that the installed fixed equipment, where releiant, is designed and
manufactur-ed in accordance with EMC Directive 2014/30/EU and, upon request, the responsible person for the
fixed installation shall provide the required documentation as specified by EMC Directive 2014/30/EU.
NOTE 1 : lnfomatioll on tl'lc para eters to be considered is given in Scction 4,14. The level of detail of the documeotation
may vary from very sinrple information to much more detailed documentation for complex irstallations involvilg
irDportant poterltial EMC aspects.
NOTE 2: Thc responsible person ret'elred to in tbis regulation is as defined in the relcvant national legislation implementing
EMC Directive 2014/3o/EU. In the UK, this is the Electromagnetic Compatibility Regulations 2016. The responsible
person is the installer.
NOTE 3: Where installations are cornposed solely ofCE-mar*ed equiprnent placed on the market in confonnity with the EMC
Directive, the responsible person satisfies the documentation requirements by being able to provide, on request, the
instructions for installation, use and rnaintenance plovided by the supplier ofeach item of equipmeltt.
NOTE 4: Where the current rating is to be based on 70 "C, cu(elt-carrying capacities given in Tables 4D1 to 4D5 or 4H I to
4H4 ofAppendix 4 rnay be used for 90 'C themosettirg insulated cables.
512,2.2 If
the equipment does not, by its construction, have the characteristics relevant to the extemal
influerces of its location, it may neveftheless be used on condition that it is provided with appropriate additional
protection in the erection ofthe installation. Such protection shall not adversely affect the operation ofthe equipment
thus protected.
512.2.3 Where different external influences occur simultaneously, they may have independent or mutual
effects and the degree ofprotection shall be provided accordingly.
512.2.4 The selection of equipment according to extemal influences is necessary not only for proper
functioning, but also for the reliability of the measures of protection for safety complying with these Regulations
generally. Measures ofprotection afforded by the construction ofequipment are valid only for the given conditions
of extemal influence if the coruesponding equipment speciflcation tests are made in these conditions of extemal
influence.
NOTE: For the purposc of these Reglrlations, the following classes of extemal influence are conventionally regardcd as
nonnal:
513 ACCESSIBILITY
513.1 Except for a joint in cables where Section 526 allo$,s such a joint to be inaccessible, evety item of
equiprrent shall be aflanged so as to facilitate its opemtio[, inspection and mai]rtenal.Ice and access to each connection.
Such t'acility shall not be signillcantly impaired by mounting equipment in an elclosure or a comparlment.
514 IDENTIFICATION AND NOTICES
514.',1 General
514.',t .1 Except where tltere is no possibility ofconfusion, a label or othcr suitable nrea[s ofidentiflcation s]rall
be provided to indicate the purpose ofeach item ofswitchgear and controlgear'. Where the operator camot obsenr'e
the operation of su,itchgear and contrclgear and where this might lead to danger. a suitable indicator complying,
where applicable, widr BS EN 60073 and BS EN 60447, shall be Iixed in a position visible to the operator.
514,1,2 So far as is reasonabiy practicable, u,iring shall be so aranged or marked that it can be identified for
inspectiol, testing, repair or alteration ofthe installatiol.
514.1.3 Except where there is no possibility of confusion, unambiguous marking shall be provided at the
interface between conductors identified in accordance with these Regulations and conductors idefltified to previous
versions olthe Regulations.
NOTE: Appendix 7 gives guidance on how this can be achieved.
514,3 ldentificationofconductors
5'14.3,1 Except where identification is not requircd by Regulation 514.6, cores ofcables shall be identified by:
(i) colour as required by Regulation 514.4 and/or
(ii) letters and/or numbers as required by Regulation 51,1.5.
514.3,2 Every core of a cable shall be identifiable at its terminations and preferably throughout its length.
Binding and sleeves for identification purposes shall comply with BS 3858 whele appropliate.
514.4.2 Protectiveconductor
The bi-colour combination green-and-yellow shall be used exclusively for identification ol a protective conductor
and this combination shall not be used for any other pur?ose. In this combination one of the colours shall cover at
least 30 % and at most 70 % ofthe surlace being coloured, while the other colour shall cover the remainder ofthe
surface.
Single-core cables identified by green-and-yellow throughouttheir length shall only be used as a protective conductor
and shall not be ovennar*ed at their teflninations, except as permitted by Regulation 514.4.3.
A bare couductor ol busbar used as a protective conductor shall be identified, where necessary, by equal green-and-
yellow stlipes, each not less than l5 mm a[d not more than 100 mlr wide, close together. either throughout the
length ofthe conductor or in each compafiment and unit and at each accessible position.
514.4.4 Otherconductors
Other conductors shail be identified by colour in accordance with Table 51.
514.4.5 The single colour green shall not be used for the identification ol I
(ii) protectiveconductors I
fFRIO,\
9l t"*oo ?
129
514.4.6 Bareconductors
A bare conductor shall be identified, where necessary, by the application oftape, sleeve or disc of the appropriate
colour prescribed in Table 5l or by painting with such a colour.
5'14.5.2 Protectiveconductor
Conductors with green-and-yellow colour identification shall not be numbered other than for the purpose of circuit
identification.
514.5.3 Alphanumeric
The prefened alphanurne c system is described in Table 51.
514.5.4 Numeric
Conductors may be identified by numbers, the number 0 being reserued lor the neutml or midpoint conductor.
130
TABLE 51 - ldentification of conductors
Function
Proteclive conductors Green-and-yellow
Functional earthing conductor Cream
AC power circuit(r)
Line of single-phase circuit L Brown
Neutral ofsingle- or three-phase circuit N Blue
Line 1 oftluee-phase AC circuit LI Brcwn
Line 2 oftltee-phase AC circuit L2 Black
Line 3 ofthree-phase AC circuit L3 Clcy
-Ihree-wire
DC power circuit
Outer positive of two-wire ctcuit derived fron
three-wire system
Outer negative of two-wire circuit derived from Grey
three-wire system
Positive of three-wire circuit Brcwn
Mid-wire of three-wire circuitrr)1r) Blue
Negative of three-wire circuit Grey
'rr M identifies either the mid-wire ofa three-wire DC circuit. or the eafthed conductor ofa two-wire eafthed DC circuit.
1r)Only the rniddle wire ofthree-wire circuits may be earthed.
1r)An earlhed PELV conductor is blue.
131
514.7 Not used
For simple installations the foregoing information may be given in a schedule. A durable copy of the schedule
relating to a distribution board shall be provided within or adjacent to each distribution board.
IMPORTANT
NOTE: Testing frequencies ofRCDs i1l temporary installations may need increasrng.
CAUTION
This installation has wiring colours to two versions of BS 7671.
Great care should be taken before undertaking extension,
alteration or repair that all conductors are correctly identified.
133
514.15 Warning notice: alternative supplies
5'14.15'1 Where an installation includes altemative or additional sources of supply, waming notices shall be
aJnxed at the lollowing locations in the installation:
(i) At the origin ofthe installation
(ii) At the meterposition, ifremote from the origin
(iii) At the consumer unit or distribution board to which the altemative or additional sources are connected
(iv) At all points ofisolation ofall sources ofsupply.
The waming notice shall be durably marked in legible type not smaller than that illustrated here and shall read as
follows:
s',t5.2 Where equipment carying cuffent of different types or at different voltages is grouped in a common
assembly (such as a switchboard, a cubicle or a control desk or box), all the equipment belonging to any one type of
curent or any one voltage shall be effectively segregated wherever necessary to avoid mutual detdmental influence.
The immunity levels of equipment shall be chosen taking into account the electromagnetic disturbances that can
occur when connected and erected as for normal use, and taking into account the intended level of continuity of
service necessary for the application. See the specilic equipment standard or the relevant pafi ofBS EN 61000 series.
134
CHAPTER 52
SELECTION AND ERECTION OF WIRING SYSTEMS
CONTENTS
520 INTRODUCTION
520.1 Scope
520.4 General
521 TYPES OF WRING SYSTEM
521.4 Busbar trunking systems and powertrack systems
521.5 AC circuits: electromagnetic effects
521 .5.1 Ferromagnetic enclosures: electromagnetic effects
521.5.201 Electromechanical stresses
521.6 Conduit, ducting, trunking, tray and ladder systems
521.7 Multicore cables: two or more circuits
521 .8 Circuit arrangements
521 .9 Use of flexible cables
521.10 lnstallation of cables
522 SELECTION AND ERECTION OF WIRING SYSTEMS IN RELATION TO EXTERNAL
INFLUENCES
522.1 Ambient temperature (AA)
522.2 External heat sources
Presence of water (AD) or high humidity (AB)
522.4 Presence of solid foreign bodies (AE)
522.5 Presence of corrosive or polluting substances (AF)
522.6 lmpact (AG)
522.7 Vibration (AH)
522.8 Other mechanical stresses (AJ)
522.9 Presence of flora and/or mould growth (AK)
522.10 Presence of fauna (AL)
522.11 Solar radiation (AN) and ultraviolet radiation
522.12 Seismic effects (AP)
522.13 Movement of air (AR)
522.14 Nature of processed or stored materials (BE)
522.15 Building design (CB)
523 CURRENT-CARRYING CAPACITIES OF CABLES
523.5 Groups containing more than one circuit
523.6 Number of loaded conductors
Conductors in parallel
523.8 Variation of installation conditions along a route
Era o Cables in thermal insulation
523.201 Armoured single-core cables
524 CROSS-SECTIONAL AREAS OF CONDUCTORS
524.2 Neutral conductors
525 VOLTAGE DROP IN CONSUMERS' INSTALLATIONS
526 ELECTRICAL CONNECTIONS
526.9 Connection of multiwire, fine wire and very fine wire conductors
527 SELECTION AND ERECTION OF WRING SYSTEMS TO MINIMIZE THE SPREAD OF FIRE
527.1 Precautions within a fi re-segregated compartment
527 .2 Sealing of wiring system penetrations
528 PROXIMITY OF WIRING SYSTEMS TO OTHER SERVICES
528.1 Proximity to electrical services
528.2 Proximity of communications cables
Proximity to non-electrical services
529 SELECTION AND ERECTION OF WIRING SYSTEMS IN RELATION TO
MAINTAINABILITY INCLUDING CLEANING.
135
CHAPTER 52
SELEGTION AND ERECTION OF WIRING SYSTEMS
520 INTRODUCTION
520.1 Scope
This chapter deals with the selection ard erection of wiring systems.
NOTE: These regulations also apply in geleral to protective conductors. Chapter 54 contains further rcquirements for those
conductols.
520.4 General
Considemtion shall be givel to the application ofthe funda[rental principles ofChapter 13 as it applies to:
(i) cables and conductors
(ii) their connections. teminations and/or jointing
(iii) their associated supports or suspensions, and
(iv) their enclosule or methods of protection against extemal influences.
The requirelnents of Regulations 521.1 to 521.201 do not apply to busbar and powertrack systems covered by
Regulation 521.4.
521.1 Tl're rnstallation rncthocl ofa u,iring system in relation to the type ofconductor or cablc uscd shall be
in accorclancc with'Iable 4A1 ofAppendix,l, provided the extemal influcnccs arc taken into accoult accordit'tg to
Section 522.
521.2 Thc ir'rstallation rnetlrod ofa wiring systcm in relation to the situation concemed shail be in accordance
with Table 4A2 ofAppcndix 4. Othel methods of installation ofcables and conductols no1 included in Table 4A2 are
pen]]itted provided that they fullil the requirements of this chapter.
521.3 Exanrplcs of wiring systems. excluding systcms coveled by Regulation 521.4. are shown in
Table 4A2. Table 4A2 gives examples of installation methods of cables including reference method for obtaining
curent-canJing capacity rvhere it is considered that the same cuffenlcarryi[g capacities can safely be used. It is
not implied that such methods must be ernployed or that other methods are prohibited.
521.201 Prefabricatcd wiling systems intended lor permanent connection in fixed installations incorporating
installation couplers corforming to BS EN 61535, shall comply with BS 8488.
The conductols ofan AC circuit installed in a feron.ngnetic enclosure shall be aranged so that all line conductors
and the neutral conductor, ifany. and the appropdate protective conductor are contajled within the same enclosure.
Whcre such couductors eflter a ferrous cnclosure, they shall be affanged such that the conducton are only collectively
sunouuded by f'cno[']agnetic Inaterial.
These requirements do not preclude the use of an additional protective conductor in parallel with the steel wire
amouting of a cable wlrerc such is required to comply with the requirements of the appropriate regulations in
Chapters 4l and 54. It is pemitted for such an additional protective corductor to enter the ferrous enclosure
individually.
136
521.5'2 Singie-core cables armoured with steel wire or steel tape shall nor be gsed lor an AC circuit.
NOTE: The steel wire or sleel tape atmour of a single-core cable is legarded as a iifomasneric enclosure. For single-core
armoured cables. the use ofalulrinium armour may be considered.
Cable conduits shall comply with the appropriate pafi of the BS EN 61386 series, cable trunking or ducting shall
comply with the appropriate part of the BS EN 50085 series and cabJe tray and ladder systems shall co1nply with
BS EN 6I537.
521.8 Circuitarrangements
521'8.'l Each part of a circuit shall be arrarged such that the conducton are not distributed over dillerent
multicore cables, conduits, ducting systems, hxnking systems or tray or ladder systems.
This requirement need not be met where a number of multicore cables, loming onc circuit, are installed in parallel.
Where multicore cables are installed in parallel each cable shall contain one conductor ofeach line.
52'l '8.2 The line and neutral conductors of each final circuit shall be elect cally separate fi om those of every
other final circuit, so as to prevent the i[direcl energizing ofa final circuit intelded to be isolated.
521.8.3 whe,e rrv. or more circuits arc ter inated in a singlc.iunctirin box this shall comply with
BS EN 60670-22.
521 .9.2 Equipment that is irtended to be moved in use shall be comected by flexiblc cables! except equipmenr
supplied by contact rails.
521.9.3 Stationary equipment which is movecl temporarily for the purposes of connecting. cleaning etc.,
e.g. cookers or flush-mounting units for installations in false floors, shall be connected with flexiblc cable. If the
equipment is not subject to vibration then non-flexible cables may be used.
\on-sheathed cables are pelmitted if the cable trunking system provides at lcast the dcgree olprotectjon TPXXD or
IP,lX. and ifthe cover can only be removed by means ofa tool or a deliberate action.
NOTE: For a cable trunking system to meet IP.lX requirements. IP,IX ttunking and relatecl system components would need to
be inslalled. lfa systetn includes sile-fabricated j oints the installer must confirln thc conlpietcd itenr rnccts at least thc
degree of protection IPXXD.
137
521.10.202 Widng systems shall be supported such that they will not be liable to premature collapse in the event
ofa fire.
NOTE 1: Wiring systems lranging across access or egress routes may hinder evacuation and firefighting activitics.
NOTE 2: Cables installed in or on steel cable containment systems are deemed to meet the rcquirements ofthis rcgulation.
NOTE 3: This regulation precludes, lor example, the use of non metallic cable clips or cable ties as the sole means of support
where cables are clipped direct to exposed surfaces or suspended under cable tra1,, and the use ofnon-metallic cable
trunking as the sole means of support ofthe cables therein.
NOTE 4: Suitably spaced steel or copper clips, saddles or ties are examples that will meet the requirements ofthis regulation.
The installation method selected shall be such that protection against the expected extemal influences is provided
in all appropriate parts ofthe widng systern. Particular care shall be taken at changes ir direction and where wiring
enters into equipmenl.
NOTE: The extemal influences categorized in Appendix 5 which are of signiflcance to wiring systems are included in this
section.
522.'1.2 Wirilg system components, including cables and wiring accessories, shall only be installed or
handled at tempemtures within the limits stated in the relevant product specification or as given by the manufactlrrer.
522.2.201 Parts of a cable within an accessory appliance or luminaire shall be suitable for the temperatures
Iikely to be encountered, as determined in accordance with Regulation 522.1.1, or sha11 be provided with additional
insulation suitable for those temperatures.
522.3.2 Where water may collect or condensation may form in a wiring system, provision shall be made for
its escape,
522.3.3 Where a wiring system may be subjected to waves (AD6), protection against mechanical damage
shatl be afforded by one or more ofthe methods ofRegulations 522.6 to 8.
138
522.4 Presence of solid foreign bodies (AE)
522.4.1 Awiring system shall be selected and erected so as to minimize the danger adsing from the ingress of
solid foreign bodies. The completed wiring system shall comply with the IP degree olprorection (see BS EN 60529)
relevant to the particular location.
522,4,2 In a location where dust in significant quantib/ is present (AE4), additional precautions shall be taken
to prevent the accumulation of dust or other substances in quantities which could adr,ersely affect heat dissipation
from the wiring system.
NOTE: Awiring system which facilitates the removal ofdust may be necessary (see Secrion 529).
522.5.2 Dissimilar metals liable to initiate electrol)'tic action shall not be placed in cortact with each other,
unless special arrangements axe made to avoid the consequences ofsuch contact.
522.5.3 Materials liable to cause mutual or individual detedoration or hazardous degradation shall rot be
placed in contact with each other.
522.6.2 In a fixed installation where impacts of medium severity (AG2) or high severity (AG3) can occur
protection shall be afforded by:
(i) the mechanical characteristics ofthe wiring system, or
(ii) the location selected, or
(iii) the provision of additional local or general protection against mechanical damage, or
(iv) any combination ofthe above.
NOTE: Examples are areas where the floor is likely to be penetrated and areas used by forklifi trucks.
522,6,4 The degree ofprotection of electrical equipment shall be maintained after installation ofthe cables
and conducto$.
522.6.201 A cable installed under a floor or above a ceiling shall be run in such a position thar it is not liable to
be damaged by contact with the floor or ceiling or their fixings.
A cable passing through a joist within a floor or ceiling construction or through a ceiling suppoft (e.g. under
floorboards), shall:
(i) be installed at least 50 mm measured vertically from the top, or bottom as appropriate, ofthejoist or batten,
OI
(ii) comply with Regslatior, 522.6.204.
522,6,202 A cable installed in a wall or partition at a depth of less than 50 mm from a surface of the wall or
paltition shall:
(i) be installed in a zone
within 150 mm from the top of the wall orpartition or within 150 mm ofan angle formed
by two adjoining walls or partitions. Where the cable is comected to a point, accessory or switchgear on any
surface of the wall or pafiition, the cable may be installed in a zone either ho zontally or vefiically, to the
point, accessory or switchgear Where the location ofthe accessory point or switchgear can be detennined
from the reverse side, a zone formed on one side of a wall of 100 mm thickness or less or pa ition of
100 mm thickness ol less extends to the reverse side, or
(ii) comply with Re glJarion 522.6.204.
Where indent (i) but not indent (ii) applies, the cable shall be provided with additional protection by means of an
RCD having the characteristics specified in Regulation 415.1.1.
139
522.6.203 Inespective of its buried depth, a cable concealed in a wall or partition, the intemal construction of
which includes metallic parts, other than metallic fixings such as nails, screws and the like, shall:
(i) be provided with additional protection by means ofan RCD having the characteristics specified in Regulation
415. l. 1, or
(ii) comply with Regulatior 522.6.204.
For a cable installed at a depth of less than 50 mm from the surface of a wall or partition the requirements of
Regulation 522.6.202(i) shall also apply.
522.6.204 For the purposes ofRegulation 522.6.201(ii), Regulation 522.6.202(ii) and Regulation 522.6.203(ii),
a cable shall:
(i) incorporate an eafihed metallic covering which complies with the requiremerts of these Regulations for
a protective conductor of the circuit concemed, the cable complying with BS 5467, BS 6724, BS 7846,
BS 8436 or BS EN 60702-1, or
(ii) be installed in eathed conduit complying with BS EN 61386-21 and satisfliing the requirements ofthese
Regulations for a protective conductor, or
(iii) be enclosed in eafihed hunking or ducting complyingwith BS EN 50085-2-l and satisfying the requirements
ofthese Regulations for a protective conductor, or
(iv) be provided with n.rechanical protection against damage sufncient to prevent penetration of the cable by
nails, screws and the like, or
(v) form part ol a SELV or PELV circuit meeting the requirements of Regulation 414.4.
522.7.2 For the fixed installation ofsuspended cuffent-using equipment, e.g. luminaires, connection shall be
made by cable with flexible cores. Where no vibration or movement can be expected, cable with non-flexible cores
may be used.
522.8.3 The radius of every bend in a wiring system shall be such that conductors or cables do not suffer
damage and terminations are not stressed.
522.8.4 Where conducto$ or cables are not supported continuously due to the method of installation, they
shall be suppoted by suitable means at approp ate intervals h such a manner that the conductors or cables do not
suffer damage by their own weight.
522.8.5 Every cable or conductor shall be supported in such a way that it is not exposed to undue mechanical
strain and so that there is no appreciable mechanical stain on the teminations of the conductors, account being
taken ofmechanical strain imposed by the supported weight ofthe cable or conductor itself.
NOTE: Consumer unit meter tails are included in the requirements ofthis regulation.
522,8.6 A widng system intended for the drawing in or out ofconductors or cables shall have adequate means
ofaccess to allow this opemtion.
522.8.7 A wiring system buried in a floor shall be sufnciently protected to prevent damage caused by the
intended use ofthe floor.
140
522.8.'10 Except where installed in a conduit or duct which provides equi\ alenr protection against mechanical
damage, a cable buried in the ground shall incorporate an earthed amour or metal sheath or both, suitable for use
as a protective conductor The location ofburied cables shall be marked by cable cor ers or a suitable marker tape.
Buried conduits and ducts shall be suitably identified. Buried cables, conduits and ducts shall be at a sufficient depth
to avoid being damaged by any reasonably foreseeable disturbance ofthe ground.
NOTE: BS EN 61386-24 is the standard for underground conduits.
522.8.11 Cable supports and enclosures shall not have sharp edges liable to damage the wiring system.
522.8.13 Cables, busbars and other electrical conductors which pass across expansion joints shall be so
selected or erected that anticipated movement does not cause damage to the electrical equipment.
522.8.14 No wiring system shall penetrate an element ofbuilding construction which is intended to be load
bearing unless the integrity ofthe load-bearing element can be assured after such penetration.
523.1 The cufient, including any hannonic current, to be carried by any conductor for sustained periods
during nomal operation shall be such that the appropriate temperature limit specified in Table 52.1 is not exceeded.
The value of cunent shall be selected in accordance with Regulation 523.2, or determined in accordance with
Regulation 523.3.
NOTE: For the telnperatrue linits for othe| types ofinsulation, refer to cable speciflcation or manufacturer
523.2 The requirement ol Regulatio[ 523. 1 is considered to be satisfied if tl']e curent fbr non-sheathcd and
sheathed cables does not exceed the appropriate values seleated from the tables of curent-canJing capacity given
in Appendix 4 with reference to Table 4A2, subject to any necessary mting factors.
NOTE: The curent-carying capacities given in the tables are provided for guidance. It is recognizcd that there will be some
tolerance in the current-calrying capacities depending on the environmental conditions and the precise construction of
the cables.
523.3 The applopliate value of curent-carrying capacity may also be detennined as described in BS 7769
series (some parts of the BS 7769 seies are now numbered BS IEC 60287 series, eventually all pats will be
renurbered). or by test. or by calculation usirg a recognized method, plovided that the method is stated. Where
appropriate. accolLnt shall be taken olthe characteristics ofthe load and, for buried cables, the eflective thermal
rcsistance ofthe soil.
523.4 The ambient temperature shall be considered to be the temperature ofthe surrounding medium when
the non-sheathed or sheathed cable(s) under consideration are not loaded.
For groups containing non-sheathed or sheathed cables having differ ent maximum operating temperatures, the
curent-canling capacity of all the non-sheathed or sheathed cables in the grcup shall be based on the lowest
maximum operating telrperature ofany cable in the group together with the appropdate group rating factol'.
Il,due to krown operating conditions, a non-sheathed or sheathed cable is expected to cary a current not greater
than 30 % of its grouped curent-caffyirg capacity, it may be ignored for the purpose of obtainirg the rating factor
for the rest ofthe group.
142
I
523.6.2 Where the neutral conductor in a multicore cable carries curreni Li a result of an imbalance in the
line cunents, the temperature se due to the neutml current is offset bl ihe reduciion in rhe heat generated by one or
more ofthe line conductors. In this case the conductor size shall be chosen on the basis olthe highest line current.
In all cases the neutral conductor shall have a cross-sectional area adequate to afford compliance with Regulation
523.t.
523.6.3 Where the neutal conductor carries curent without a corresponding reduction in load of the line
conductors, the neutual conductor shall be taken into account in ascertaining the cunent-canying capacity of the
circuit. Such currents may be caused by a significant harmonic curent iII three-phase circuits. If the total harmonic
distortion due to third harmonic current or multiples olthe third harmonic is greater than 15 % ofthe flindamental
line crurent the neutral conductor shall not be smaller than the line conductors. Thermal effects due to the presence
ofthird harmonic or multiples ofthird harmonic curents and the corresponding rating factors for higher harmonic
cunents are given in Appendix 4, section 5.5.
523.6.4 Conductors which serve the purpose of protective conductors only are not to be taken into
consideration. PEN conductors shall be taken into consideration in the same way as neutral conductors.
523.6.201 The tabulated current-carrying capacities in Appendix 4 are based on the fundamertal frequency
only and do not take account ofthe effect ofharmonics.
This requirement is considered to be fulIilled if the conductors are of the same material, have the same cross-
sectional area, are approximately the same length and have no branch circuits along their length, and either:
(a) the conductors in parallel are multicore cables or twisted single-core cables or non-sheathed cables, ot
(b) the conducton in parallel are non-twisted single-core cables or non-sheathed cables in trefoil or flat
formation and where the cross-sectional area is greater than 50 mmz in copper or 70 mnf in alun.rinium,
the special configuration necessary for such formations is adopted. These conigumtions consist ol
suitable groupings and spacings ofthe different lines or poles
or
(ii) special consideration shall be given to the load curent sha ng to meet the requirements of Regulation 523.1.
This regulation does not preclude the use of ring final circuits with or without spur connections.
Where adequate current sharing is not possible or where four or more conductors have to be connected in parallel
consideration shall be given to the use ofbusbar trunking.
For a cable installed in a themally insulated wall or above a themally insulated ceiling. the cable being in contact
with a thermally conductive surface on one side, curent-carrying capacities are tabulated in Appendix 4.
For a single cable likely to be totally surounded by themally insulating mate al o\'er a length of 0.5 11 or more,
the current-carrying capacity shall be taken, in the absence of more precise infonration. as 0.5 times the cun'e[t-
canying capacity for that cable clipped direct to a surface and open (Reference Method C).
Where a cable is to be totally surounded by thermal insulation for less than 0.5 n] the currenGcanl,ing capacity of
the cable shall be reduced appropriately depending on the size of cable, length in insulation and thetmal propenies
of the insulation. The derating factors in Table 52.2 are appropriate to conductor size: up to 10 mmr in thermal
insulation having a theflnal conductivity ().) greater than 0.04 Wm 1K '.
143
TABLE 52.2 - Cable surrounded by thermal insulation
524.1 The cross-sectional area ofeach conductor in a circuit shall be not less than the values given in Table
52.3, except as prcvided for extralow voltage lighting installations according to Regulation 715.524.201
524,2.3 For a polyphase circuit where each line conductor has a cross-sectional arca greatel than l6 mmr for
copper or 25 mmr for aluminium, the ueutral conductor is permitted to have a smaller cross-sectional area than that
ofthe line corductors provided that the followilg conditions are simultaneously fullllled:
(i) The expected maximum current including harmonics, if any, in the neutml conductor duting normal service
is not greater than the current-canying capacity olthe reduced cross-sectional area ofthe neutral conductor,
and
NOTE: The load carried by the circLLit under normal service conditions should be practicaily equally
distributed between the lines.
(i1) the 11eutra] colductor is protected against overcurlents according to Regulation '131.2, and
(ii0 the size ofthe neutral conductor is at least equal to 16 mmr fol copper or 25 mmr for aluminium, account
being taken ofRegulation 523.6.3.
Non sheathed and sheathed Lightillg circuits Copper 1.0 (sce Note ,1) I
cables
Aluminiurn l6 (see Note 3) I
Non-sheathed and sheathed For a specific appliarce Copper As specified in the product standard
flexible cables For any other application 0.75"
NOTE l: ln infonnation technology, signalling and control circuits intended for electronic equipment a minimum cross-
sectional area ofo.l mmr is permitted
NOTE 2: For special requiremerts for ELV liShting see Section 715.
NOTE 3: Connectors used to tenninate aluminium conductoN shall be tested a[d approved for this specific use.
NOTE 4l For lighting circuits and associated small items ofcurrent-using equipmert, slrch as a bathroom extmctor fan
seven or inore cores. Note I
525.1 In the absence ofany other consideration, under normal service conditions the voltage at the terminals
of any fined curent-using equipment shall be greater than the lower limit corresponding to the product standard
rclevant to the equipment.
525.20,1 Where fixed curent-using equipment is not the subject ol a product standard the Yoltage at the
terminals shall be such as not to impair the safe functioning ofthat equipment.
525.202 The above requirements are deemed to be satisfied if the voltage drop between the origin of the
installation (usually the supply terminals) and a socketoutlet or the te[minals offixed curent-using equipment does
not exceed that stated in Appendix 4, section 6.4.
525.203 A greater voltage drop than stated in Apperdix 4, section 6.4 may be accepted for a notor dudng
stafiing periods and for other equipment with high inrush currents, provided that it is verified that the voltage
Yariations are within the limits specifled in the relevant product standard for the equipment ot, in the absence of a
product standard, in accordance with the manufacturer's recommendations.
526.2 The selection ofthe means ofcoDnection shall take account of, as apprcp ate:
(t the material ofthe conductor and its insulation
(ii) the number and shape ofthe wires forming the conductor
- (iii) the cross-sectional area ofthe conductor
(iv) the number ofconductom to be connected together
(v) the temperature attained at the tenninals in normal service such that the effectiveness ofthe insulation ofthe
conducto$ colnected to them is not impaired
(\'i) the provision ofadequate locking arrangements in situations subject to vibration or thermal cycling
',i
here a soldered connection is used the design shall take account of creep, mechanical stress anci temperature rise
-:der fault conditions.
raOTE l: Applicable standards include BS EN 609'17-7, the BS EN 60998 series and BS EN 61535'
ITOTE 2: Terminals without rhe marking 'r'(only dgid conductor). 'f'(only flexible conductor), 's'or 'sol'(only solid conductor)
are suitable tbr the connection ofall tyPes ofconductors
:26.3 Every connection shallbe accessible for ir'rspection. testing andmaintenance, except for the following:
Ajoint designed to be buried in the ground
A cornpound-fi lled or encapsulatcdio,nt
--- 145
(jii) A connection beflveen a cold rail and the heating element as in ceiling heating, floor heating or a trace
heating system
(iv) A joint made by welding, soldering, brazing or appropriate compression tool
(v) Joints ot'connections made in equipment by the manufacturer ofthe product and not intended to be inspected
or maintained
(vi) Equipment complying with BS 5733 for a maintenance-free accessory and marked with the symbol
and installed in accordance with the manufacturer,s instructions. @
526.4 Where necessary precautions shall be taken so that the temperature attained by a connection in
normal service shall not impair the effectiveness ofthe insulation ofthe conductors connected to it or any insulating
material used to support the connection. Where a cable is to be connected to a bare conductor or busbar its type of
insulation and/or sheath shall be suitable for the maximum operating temperature of the bare conductor or busbar
526.5 Evely termination and joint in a live conductor or a pEN conductor shall be made within one ofthe
fo1lowing or a combination thereof:
(i) A suitable accessory complying with the appropriate product standard
(ii) An equipment enclosure complying with the appropriate product standard
(iii) An enclosure partially formed or completed with building material which is non-combustible when tested to
BS 4'76-4.
526.7 where a comection is made in an enclosure the enclosure shall provide adequate mechanical
protection and protection against relevant extemal influences.
526.8 Cores of sheathed cables from which the sheath has been removed and non-sheathed cables at the
tennination ofconduit, ducting or tluf<ing shall be enclosed as required by Regulation 526.5.
526.9 Connection of multiwire, fine wire and very fine wire conductors
526.9.1 ln order to avoid inappropriate separation or spreading of individual wires of multiwire, fine wire or
very fine wire conductors. suitable temlillals shall be used or the condlLctor ends shall be suitabiy treated.
526.9.2 Soldering (tinning) ofthe wholc conductor end of multiwire. fine wire and very fine wire conductors
is not permitted ifscrew terminals are used.
526.9.3 Soldered (tinned) conductor ends on line wire and very flne wire conducto$ are not permissible at
connection and junction points which are subject in seryice to a relative movement between the soldered and the
non-soldered part of the conductor.
527 .'l .2 A wiling system shall be installed so that the general building structural perfomance and fire safety
are not reduced.
527.1.3 Cables complying with, at least, the requirements BS EN 60332-1-2 may be instalted without special
precautions.
Where the fire-segregated compafiment provides a means of evacuation in an emergency then the cable shall meet
the requirements ofthe appropdate part ofBS EN 60332-3 series.
NOTE: Cables nlanufactured for the above application also need to satisfy the requirements of the CPR in respect of their
reaction ro 1lre. See Appendix 2, item 17.
527.1.4 Cables not complling with the cable requirements of Regulation 527.1.3 shall be limited to short
lengths fol connection of appliances to the pemanent wiring systerl and shall not pass frorri one fire-segregated
compaft mer]t to another.
146
527.1.5 Products harins rhe necessa4 resistance to flame propagation as spccificd in the BS EN 61386
series, thc approprjate pan ol BS EN 50085 series. BS EN 61439-6, tsS EN 6lill scrics. BS EN 61537 or
BS EN 60570 may be installed rvithout special precautions. Other products corlrplvin-s * ith standards haviug similar
requirements lor resistance to flame propagation may be installed without special precaurions.
527 ,1.6 Pafis of wiring systerns other than cables which do nor compl1.. as a ninimum. with the flame
propagation requirements as specified in the BS EN 61386 selies, the appropriate parr of BS EN 50085 selies,
BS EN 61439-6, BS EN 6153,1 series or BS EN 61537 but which comply in all other respects with the requirements
of their respectivc product standard shall, if used, be completely enclosed in suitable non-combustible building
materials.
This requireme)rt is satisfied if the sealing of the wiring system concemed has passed a relevant type test meeting
the requirements of Regutation 527.2.3.
527.2.1.1 During the erection of a wiring system tenporary sealing arangements shall be provided as
approp at
527.2.1.2 During altemtion work, sealing which has been disturbed shall be reinstated as soon as practicable.
527.2.2 A wiring system such as a conduit systerr, cable ducting systen, cable trunking system, busbar or
busbar trunking system which penetmtes elements of building construction having specified fire-resistance shall
be internally sealed to the degree of fire-resistance of the respective element before penetration as well as being
ertemally sealed as required by Regulation 521 .2.1.
This requirement is satisfied if the sealing ofthe wiring system concemed has passed a relevant type test meeting
the requirements of Regulation 527.2.3.
527 ,2.3 A conduit system, cable tmnking systera or cable ducting systenl classilied as non-flame propagating
lccording to the relevant product standard and having a maximum intemal cross-sectional area of710 mmr need not
b.' intemally sealed provided that:
(i) the system satisfies the test olBS EN 60529 for IP33, and
(ii) any telnrination of the system in one of the compartments, separated by the building construction being
penetrated, satisfies the test olBS EN 60529 for 1P33.
527.2.4 Any sealing an-angement intended to satisfy Regulation 527.2.1 or 527.2.1.1 shall resist external
rfluences to the same degree as the wi ng system with which it is used and, in addition, it shall n.reet all olthe
r.11os,in g requirements :
li) It shall be resistant to the products ofcombustion to the same extent asthe elements ofbuilding construction
rvhich have been penetrated
t ii) It shall provide the same degree of protection from water penetration as that required for the building
constmction element in which it has been installed
ll I It shall be compatible with the matedal ofthe widng system with which it is in contact
It shall permit thermal movement ofthe wiring systern without reduction ofthe sealing quality
It shall be of adequate mechanical stability to withstand the stresses which nlay a se through damage to the
suppofi ofthe wiring system due to fire.
:- .:iil and the \!iring system shall be plotected tiol]r drippirg r,r,ater utich may travel along the wiring system or
: ,:: maY otherwise collcct around the seal unless the n.iaterials used in the seal are all resistant to nloisture $,her]
- . '. rssembled for use.
\ f,TE: This regulation ma), be sarisf,ed ifi
either cable cleats, cable ties or cable supports are installed rvithin 750 mm ofthe seal, and are able to withstand
thc mechanical loads expected following the collapse ofthe supports on the fire side ofthe seal to the extent that
no strain is hansferred to the seal or
the design ofthe sealing syste itselfpr-olides adequate suppol1.
147
528 PROXIMITY OF WIRING SYSTEMS TO OTHER SERVICES
For SELV and PELV systems the requirements ofRegulation 414.4 shall apply.
NOTE 1: In the case of proximity of wiriflg systems and lightning prorection systems, BS EN 62305 should be considered.
NOTE 2; Recornmendations for separation and segregation in relation to safety ser,iices are given in BS 5266, BS 5g39 and
BS 8519.
In areas not specifically designed lor the installation of cables, e.g. service shafts and cavities, the cables shall be
laid so that they are not exposed to any harmful influence by the normal operation ofadjacent installations (e.g. gas,
water or steam [ines).
528.3.2 Where a wiring system is routed below services liable to cause condensation (such as water, steam
or gas services), precautions shall be taken to protect the wiring system from deleterious effects.
528.3.3 Where an electrical seryice is to be installed in proximity to one or more non-electrical services it
shall be so aranged that any foreseeable operation carried out on the other services will not cause damage to the
electrical service or the converse.
NOTE: This may be achieved by:
(i) suitable spaciflg between the services, or
(ii) the use of mechanical or themal shieldins.
528.3,4 Where an electrical service is located in close proximity to one or more non-electrical seruices, both
the following conditions shall be met:
(i) The wiring system shall be suitably protected against the hazards likely to arise fiom the presence ofthe
other services in nomal use
(ii) Fautt protection shall be afforded in accordance with the requirements of Section 4l 1 .
NOTE; The requirements for segregation between low pressure gas systems and electrical equipment are grven in BS 6891.
528.3.5 No cable shall be run in a lift or hoist well unless it forms part ofthe lift installation as defined in
BS EN 8l series.
_148 _
SELECTION AND ERECTION OF WRING SYSTEMS IN RELATION TO
MAINTAINABILITY, INCLUDING CLEANING
529,1 With regard to maintainabiliry reference shall be made to Regulation 1i2.12.
529.2 Where it is necessary to remove any protective measure in order to carry out maintenance, provision
shall be made so that the protective measure can be reinstated without rcduction ofthe degree ofprotection originally
intended.
529.3 Provision shall be made for safe and adequate access to all parts of a wi ng system which may
requlre marntenance.
NOTE: In some situations, it may be necessary to provide permanent means ofaccess by ladders, walkways, etc.
149
CHAPTER 53
PROTECTION, ISOLATION, SWITGHING, CONTROL
AND MONITORING
CONTENTS
530 INTRODUCTION
530.1 Scope
530.2 Not used
530.3 General and common requirements
530.4 Fixing of equipment
531 DEVICES FOR PROTECTION AGAINST ELECTRIC SHOCK BYAUTOMATIC
DISCONNECTION OF SUPPLY
cJt.t General
531 .2 Overcurrent protective devices
531.2.1 General
531 .2.2 TN systems
531.2.3 TT systems
531 .2.4 lT systems
531 .3 Residual current devices (RCDs)
531.3.1 General
531.3.2 Unwanted tripping
Types of RCD
531.3.4 Selection according to the accessibility to the installation
531.3.5 RCDs for fault protection
cJ t.J.o RCDs for additional protection
532 DEVICES FOR PROTECTION AGAINST THE RISK OF FIRE
532.1 General
532.2 Residual current devices (RCDs) for protection against the risk of flre
Residual current monitoring devices (RC[,4s) for protection against the risk of fire in lT
systems
532.4 lnsulation monitoring devices (lMDs) for protection against the risk of fire in lT systems
532.5 lnternal arc fault protection in a switchgear and controlgear assembly
532.6 Arc fault detection devices (AFDDs)
533 DEVICES FOR PROTECTION AGAINST OVERCURRENT
533.1 General requirements
533.1.1 Compliance with standards
533.1.2 Fuses
533.1.3 Circuit-breakers
533.2 Selection of devices for overload protection of wiring systems
533.2.2 Additional requirements for protection against overload when harmonic currents are present
533.3 Selection of devices for protection of wiring systems against fault current
534 DEVICES FOR PROTECTION AGAINST OVERVOLTAGE
534.1 General
534.4 Selection and erection of SPDs
534.4.1 SPD types and location
534.4.2 Connection modes of SPDs
534.4.3 Connection types
534.4.4 Selection of SPDs
534.4.5 Protection of the SPD against overcurrent
534.4.6 Fault protection
534.4.7 SPD installation ln conjunciion with RCDS
150 _ ._
534.4.8 Connection of SPDs I
AND MONITORING
530 INTRODUCTION
530.1 Scope
This chapter deals with general requirements for protection, isolation, switching, control and monitoring and with
the requirements for selection and erection ofthe devices provided to fulfil such functions.
NOTE: In Chapter 53, reference to short-circoit, where relevant, includes earth fault. Shoft-circuit Protective Device (SCPD),
where relevant, also means earth fauh curent protective device.
530.3.1 Every item ofequipment shall be selected and erected so as to allow compliance with the requirements
stated in the following regulations.
530.3.2 The noving contacts of multipole switching devices marked for the connection of the neutral or
midpoint may close before and open alter the other contacts.
530.3.3 A switching device shall not be inserted in the neutal conductor alone.
530.3.4 Devices embodying more than one function, as defined in the following regulations, shall comply
with the relevant requirements of this chapter approp ate to each separate function.
530.3.5 Equipment irtended for protection only shall not be provided for functional switching olcircuits.
NOTE: See Table 537.4 - Guidance on the selection ofprotective. isolatior amd switching devices.
530.4,2 Unelclosed equipnent shall be mounted in a suitable mounting box or enclosure in compliance with
the relevant part ofBS EN 60670, BS EN 62208 or other relevant standards such as BS EN 61439 series. Socket-
outlets, connectiol units, plate switches and similar accessories shall be fitted to a mounting box complying with
BS 4662 or BS 5733 and with the relevant pafi ofBS EN 60670.
530.4.3 Equipment such as circuit-bleakers, switches, socket-outlets, control equipment, etc. may be installed
on or in a cable tnlnking system complying with BS EN 50085 series. Wherever equipment is fixed on or in cable
trunkirg, skirting trunking or in mouldings it shall not be fixed on covers which can be removed inadvefiently.
531.1 General
531.1.1 Devices for protection against clectric shock by automatic disconnection ofsupply shall be suitable
1br isolation in accordance with Chapter 46 ard Section 537.
Automatic reclosing of devices for protection against elect c slrock by automatic disconnection of supply shall
only be installed in the associated part of the installation where access is rest cted to instructed persons or skilled
person\ onlY.
Awarning notice shall be clearly displayed nearthe point ofaccess to the associated part ofthe installation controlled
by the auto-reclosing device, indicating its automatic reclose function must be disengaged prior to entry.
NOTE: Automatic Reclosing Devices are intended to reclose circuit-breakers, RCBOs and RCCBs after tripping, in order to
r(-<.ldl_li-h ionlrnLri(y ol'ser1 ice.
diSconnection of supply
Requirements for the selection of devices fol plotection against electric shock b) automatic
are given in the regulations listed below.
531.2 Overcurrentprotectivedevices
531.2.1 General
I automatic disconnection of
where ovefcuTent protective devices are used for protection against electric shock by
supply they shall be selected in accordance with Section 533'
I
531.2.2 TN systems
531.2.3 TT systems
plovided that a suitably low value of
In TT systems, overcurrent protective devices may be used for fault protection
Z" is permanently and reliably assured (see Regulation 4l L5.4) so that in case ofa fault, tdpping ofthe overcurrent
times js achieved'
protective device in compliance with the required disconnection
InlTSystems,ifdisconnectionrequiredbyChapter4lintheeventofthesecondfaulttoearthcannotbeachieved
-o'. RCD'
by an overcurrent protective devici, on. o, used to provide the required fault protection within
'hul1be
the installation.
Refer.ence is also made to Regulation 419.3 where supplementary
protective equipotcrtial bo[ding is reqllired in those
NOTE:
cases where automatic disconnection accotdil1g to Regu]ation 41L3 2 I cannot be achieved'
Overcunent protective devices used in IT systems shall have line poles suitable
lor line-to-line voltage applications
and a neutrai pole, ilapplicable, suitable for the linelo-neutral voltage
for operation in case of a second insulation
fault.
153
In IT systems, in the event of a second fault. the operation of the overcunent protective device shall result in the
disconnection of all coresponding live conductors, including the neutral conductor, if any (see also Regulation
43 t.2.2).
Except where Regulation 53I.3. L201 applies, an RCD shall disconnect all live conducto$ olthe circuit protected.
The protective conductor shall not pass through the sensor ofthe RCD except where this is unavoidable, e.g. in the
case of armoured cables. In such exceptional cases, the protective conductor alone has to be passed again through
the sensor but ir the reverse direction. The protective conductor shall be insulated and shall not be earthed either at
the first or at the second passing through the sensor
A protective conductor current shall not contribute to the measurement ofthe residual current.
531.3.1.201 For protection against electric shock, there is no requirement to discomect/switch the neuhal in
TT or TN systems.
531.3.1.202 It is not pennissible to irtroduce an extemal connection for the puryose of intentionally creating a
residual curent to trip an RCD.
NOTE 1: This does not preclude the use ofan RCD with a functional earth conneclion.
NOTE 2: This does not preclude the use ofa test instrument in accordance with part 6.
53'|,.3.2 Unwantedtripping
Residual curent protective devices shall be selected and erected such as to limit the risk ofunwanted tripping. The
following shall be considered:
(i) subdivision ofcircuits with individual associated RCDs. RCDs shall be selected and the circuits subdivided
in such a way that any eafih leakage current likely to occur during normal opemtion ofthe connected load
will not cause unwanted tuipping of the device. See also Section 314
(ii) in order to avoid unwanted tripping by protective conductor culrents and/or earth leakage cu[ents, the
accumulation of such curents downstream of the RCD shall be not more than 30 % of the rated residual
operating current
NOTE :1 This will also allow a better selection of the g?e of RCDs according to the nature of the circuit or the load.
NOTE 2: RCDs may operate at any value ofresidual current in excess of50 oZ
ofthe mted residual current.
(iii) use of short time-delayed RCDs, provided the applicable requirements of Chapter 4l are met
NOTE3: ln the case oftransient effects,l pping ofthe RCD may occurby charging ofbypass capacitors orby other
electromagnetic disturbances_
(iv) coordination of general type RCDs, selective type RCDs and time-delayed RCDs (cBRs according to
BS EN 60947-2) as covered in Section 536
NOTE 4: CBR is a circuit-breaker incorporating residual current protection.
(v) coordination olRCDs with surge protective deyices (SpD) according to Regulation 534.4.7.
Different types ofRCD exist, depending on their behaviour in the presence ofDC components and frequencies. The
appropriate RCD shall be selected from the following:
(i) RCD Type AC: RCD tdpping on altemating sinusoidal residual current, suddenly applied or smoothly
increasing
(ii) RCD Type A: RCD tripping on altemating sinusoidal residual curent and on residual pulsating direct curent,
suddenly applied or smoothly increasing.
NOTE l: For RCD Type A, t pping is achieved for residual pulsating direct currents superimposed on a smooth direct
curent up to 6 mA.
(iii) RCD Type F: RCD for which tripping is achieved as for Type A and in addition:
(a) for composite residual curents, whether suddenly apptied or slowly rising, intended for circuit supplied
between line and neutral or line and earthed middle conductor
(b) for residual pulsating direct curents superimposed on smooth direct currenf.
154
l
NoTE2:FoTRCDT}}eF.rippingisachievedlorresidualpulsatingdileclcu(ents;upenmposedonaSmoothdirect
cunent uP to l0 mA.
(iv) RCD Type B: RCD for rvhich tripping is achieved as for Type F and in addition:
(a) for residual sinusoidal altemating currents up to 1 kHz
(b) for residual altemating currents superin.lposed on a smooth direct curent
(c) for residual pulsating direct currents superimposed on a smooth direct curent
(d) for residual pulsating rectified direct curent which rcsults from two or more phases
(e)forresidualsmoothdilectcurents,whethersuddenlyappliedorslowlyincreased,independentof
polarity.
NoTE3:FolRCDTypeB,trippirlgisachievedfolresidualpulsating<lirectcurentssuperirnposedonasmoothdirectcurent
up to 0.4 dm;s the rated residual cunent (lr',) or l0 nr-A, whjchever is the hiShest value'
531.3.4.201 Where an RCD may be opcmted by an ordinary person. it shall be designed or installed so thar it is
residual oper-ating current (11',) oI tirre dclay
not possible to modify or adjust the setting or the calibration ofits rated
or a tooi and in a inclication of
n.eciranism without a clcliberatc act invol"ving the use ofcither a key
'esulting 'isible
its setting or calibration.
persors or skilled
531.3.4.2 I[ AC installations having RCDs that are intended to be opemted by instructed
persons, the RCDs shall con.rply with:
- BS F.N 61008 scdes fot RCCBs. or
- BS EN 61009 series for RCBOs. or
BS EN 62423 fol Type F and Type B RCCBs and RCBOs, or
BS EN 60947-2 for CBRs and MRCDs
531.3.5.2 TN system
protected. The Iequilements for unwanted
RCDS shall be installed at the origin of that paft ofthe installation to be
tripping in accordance with Regulation 531.3.2 shall also be taken into account'
NoTE:Exceptwheleparticulalrestrictionforselectivityapplies,sevelalcircuitsn]aybeprotectedbythesamedevice'
The division of the PEN conductor into neutral conductol and protectiYe
conductol shall take place at the supply
! >ide olthe RCDs.
pemlitted'
, On the load side ofthe RCD, connection between the plotective and neufial conductors is not
531 .3.5.3.2 Selection of the rated residual operating current of the RCD
The rated residual operating curent value (16) of an RCD shall not exceed the Io"
corresponding to the maximum
value of the earth resistance RA to the exposed-conductive-parts, taking into account
the possible seasonal variations,
including soil lreezing and drying, ofthe part ofthe instaliation prote-cted by this device,
as shown in Tabte 53.1.
Rt is the sum of the resistances in ohms of the earth electode and the protectiye conductor
connecting it to the
exposed-conductive-parts.
Table 53.1 - Correlation between the maximum value of earth resistance RAand
the maximum rated residual operating current la.ofthe RCD
Maximum value of RA (O) Maximum Id" of the RCD
2.5 204
5 10A
l0 5A
t7 3A
50 1A
100 500 mA
t6'7 300 mA
500 100 m,A
t667 30 mA
531.3.5.4 lT system
531.3.5.4.1 General
In IT systems, protection of the neutral conductor by RCD is permitted provided that the requirements of
Regulation 431.2.2 are fulfll1ed.
531'3'5'4'2 Case of second fault on another live conductor when exposed-conductive-parts are
interconnected
where RCD' are used according to Regulation 411.6.3(v), one RCD per circuit shall be
used.
The operating characte stics of this RCD shall be selected according to Table
41 .1 of chapter 41.
531'3'5'4'3 Case of second fault on another live conductor when exposed-conductive-parts are not
interconnected
The conditions for detemining the characteristics ofthe RCD shall be those for TT systems
defined in Regulation
411.5:
- The rated residual operating curent IAn has to be selected according to Table 53.1.
156
- The disconnection time has to comply with the values given in Regulation J I 1.i. I
In addition, fault protection for every circuit located downstream ofthis RCD shali be provided in accordance with
the requircments of Regulation 411.6.3(v). [n this case every final circuit shal1 be indi\'idual)y protected by an RCD.
The use ofRCDs with a rated residual operating curert not exceeding 30 mA is recognized as additional protection
in compliance with Regulation 415.1. These RCDs shall be provided to comply u ith the requir ements ofRegulation
411.3.3.
Where installed at the origin of a final circuit or a group offinal circuits, an RCD with a rated residual current not
exceeding 30 mA may provide fault protection and additional protection simultaneously.
NOTE: Consideration shall be given to the division ofthe installation (see Regulations 531.3.2 and 314.2).
532.1 General
In locations where, in accordance with Chapter 42, a particular risk of fire exists, preventive protection measures
against the risk of fire are required. This may also apply to other locations ofthe electrical installation, depending
on a risk analysis.
NOTE: A suitable evaluation ofthe risk should be carried out by one ormore persons competent infue sk assessments.
The selection ofprotective and monitoring devices shall take into account the nature ofthe load and the likelihood
ofthe device to operate, e.g. fault curents ofhigher frequencies, DC fault currents or increased leakage curents.
(See also Regulation 331.1.)
532.2 Residual current devices (RCDs) for protection against the risk of fire
RCDs shall comply with Regulations 531.3.1 to 53 1.3.4 and with the applicable requirements ofRegulation 531.3.5.
RCDs with a rated residual opelating curent not exceeding 300 mA shall be used. RCDs shall be installed at the
origin ofthe circuit to be protected.
532.3 Residual current monitoring devices (RGMs) for protection against the risk of fire in
lT systems
In lT systems, RCMs may be used as an altemative to RCDs in accordance with Regulation 532.2, provided that the
location is supervised by one or more skilled or inshucted person(s).
RCMs shall be in accordance with BS EN 62020 and operate in conjunction with switchgear suitable for isolation.
RCMs shall be installed at the origin offinal circuits. The mted residual operating current shall not exceed 300 mA.
Audible and visual signals shall be provided by the RCMs.
532.4 Insulation monitoring devices (lMDs) for protection against the risk of fire in lT
systems
Insulation monitoring devices applied in IT systems for protection against the risk of fire shall comply with the
requirements of Section 538.
A fault location system in accordance with the requirement ofRegulation 538.2 able to locate the faulty circuit, may
also he used.
Where required for special applications, intemal arc fault protection (e.g. optical detection system) detecting a fault
arc together with a protection system can be selected in order to extinguish the arc.
Alternatively, an assembly with arc ignition protected zone(s) can be selected to minimise the risk ofan arcing fault.
(Arcing class I in accordance with PD IEC/TR 61641.)
NOTE: lntemal arc fault protection is typically associated \\ith a switchboard used in special applications. An asselnbly that
157
has been subject to an intemal arcing faul! can require maintenance or replacemeni.
A device for protection against overcu[ent shall cornply with one or more ofthe following:
- BS 88 series
- BS 646
- BS 1362
- BS 3036
- BS EN 60898 series
- BS EN 60947 series
- BS EN 61009 se es
- BS EN 62423.
The use ofanother device is not precluded provided that its time/cu[ent characteristics provide a level ofprotection
not less than that given by the devices listed above.
The following protective devices shall be used only for protection against short-circuit currelrt:
- instantaneous trip circuit-br eakers (lCB) in accordance with Annex O ofBS EN 60947-2
- aM and aR type hnes in accordance with BS HD 60269-2 or BS HD 60269-3.
For evety fuse ard circuit-breaker there shall be provided on or adjacenl to it an indication of its intended mted
cLlrrent as appropriate to the circuit it protects. For a semi-enclosed fuse, the intended ftrted cun'ent to be indicated
is the value to be selected in accordance with Regulation 533.1.2.3.
533.1.2 Fuses
533.1.2.1 A fuse base shall be aranged so as to exclude the possibility of the fuse carier making contact
between conductive pafis belonging to two adjacent fuse bases.
A fuse base using screw-in flises shall be connectedso that the centre contact is connected to tlre conductor ftom the
supply and the shell contact is connected to the conductor to the load.
533.1.2.2 Fuses having fuse links likely to be rernoved or replaced by an ordinary person shall be ol a type
which complies withBs 88-3, BS 3036 or BS 1362. Such a fuse link shall either:
(i) have marked on or adjacent to it an indication of the type of luse link intended to be used, or
(ii) be of a type such that there is no possibility of inadvertent replacement by a fuse link having the intended
rated curent but a higher fusing factor than that intended.
NOTE: In polyphase systems additional measules may be needed, e.g. al all-pole switch on ihe supply side. in ordertoprevent
thc risk of uDintentional contact with live par.ts on the load side.
Fuses or combination units having fuse links likely to be removed and replaced only by skilled or irstructed
person(s) shall be installed in such a manner that the fuse links can be removed or replaced without unintentional
contact with live pafis.
533.1 .2.3 A fuse shall prefembly be of the cartridge type. Where a serri-enclosed fuse is selected, it shall be
fitted with an element in accordance with the manufacturer's instructions. if any. In the absence of such instrucnons,
158
.-
it shall be fitted with a single element of tinned copper wire of the appropriare diamerer specified in Table 533.1.
TABLE 533.1 - Sizes of tinned copper wire for use in semi-enclosed fuses
533.1.3 Circuit-breakers
Where a circuit-breaker may be operated by an ordinary person, it shall be designed or installed so that it is not
possible to modif, the setting or the calibration ofits overcurrent release without a deliberate act involviue the use
ofeither a key or a tool and resulting in a visible indication ofits setting or calibration.
Where a screw-in type circuit-breaker is used in a fuse base, the requirements ofRegulation 533.1.2.1 also apply.
According to the requirements ofAnnex H of BS EN 60947-2, devices marked with the voltage value followed by
the :1 mbol ffi .hall nor be uced in lT 5) slems lor such r oltage.
\a_y
533.2 Selection of devices for overload protection of wiring systems
533.2.1 The rated curent (or cufient setting) of the protective device shall be chosen in accordance with
Regulation 433.1.
In certain cases, to avoid unintentional opemtion, the peak current values of the loads may have to be taken ilrto
consideration.
In the case ofa cyclic load, the values of I. and I2 shall be chosen on the basis ofvalues ofl6 and I. for the thermally
equivalent constant load
where:
16 is the curent for which the circuit is designed
I. current-catrying capacity of a cable for continuous service under the particular installation conditions
concemed
I, is the mted curent or cu[ent setting ofthe protective deyice
I
Ir is the curent causing effective operation ofthe overload protective device within the conventional time as
I
,tared in the producr standard.
NOTE: The current causing effective operation in the conventional time of protective dcvices may also bc naned It (for
circuit-bteakers) or If (for fuSes) according to the product standards. Both It and Il are lnultiples of ln and attention
should be given to the correct representation ofvalues and indexes.
533,2,2 Additional requirements for protection against overload when harmonic currents are
present
When selecting an overload protective device to comply with Regulation 433. l, account shall be taken of hamonic
curents in accordance with Regulation 431.2.3.
NOTE: See also Appendix 4 for fudher details on harmonics.
533.3 Selection of devices for protection of wiring systems against fault current
The application of the regulations of Chapter ,13 shall take into account both the minin.nn and maximum lault
I
current conditions, so ftat the highest energt let-rl'trough is taken itto accounr.
I
159
Where the standard covering a protective device specifies both a rated seruice short-circuit breaking capacity and
a rated ultimate short-circuit bleaking capacity, it is acceptable to select the protective device on the basis of the
ultimate short-circuit breaking capacity lor the maximum fault curent conditions. Operational circumstances may,
however, make it desimble to select the protective device on the seryice shoft-circuit breaking capacity, e.g. where
a protective device is placed at the origin ofthe installation.
Where the short-circuit breaking capacity of the protective device is lower than the maximum prospective short-
circuit or eath fault curent that is expected at its point olinstallation, it is necessary to comply with the requirements
ofthe last paragraph ofRegulation 536.1 and Regulation 536.5.
NOTE: To calculate the maximurn and mhimum faull cunents, see Technical Report PD CLC/TR 50480 'Determination of
cross-sectional area of conductors and selection ofprotective devices'. See also Appendix 4, paragraph 2.5.
534.1 General
This section contains provisions for the application olvoltage limitation in order to obtain insulation coordination
in the cases described in Section 443, BS EN 60664-1, BS EN 62305 series and BS EN 61643 series. This
section focuses mainly on the requirements lor the selection and erection of SPDs for protection against transient
ovenoltages where required by Section 443, the BS EN 62305 series, or as otherwise stated.
BS EN 62305-4 and BS EN 61643-12 series deal with the protection against the effects ofdirect lightning stokes
ol stuokes near to the supply system. Both documents desc be the selection and the application of suge protective
devices (SPDs) according to the Lightning Protection Zones (LPZ) concept. The LPZ concept descrii,es the
installation ofType 1, Type 2 and Type 3 SPDs. See Figr"rre 534.1 .
Low voliage
electr cal I\,4ast or
supply-cable railing
LPZ2
rm
ffi
Critical
equipment
@ toExtraneous-conductive-part
main earthing terminal
connected
'160
NOTE l: SPDs with more than one lype ofclassification are available, e.g. combined Tlle l l or combined Type 2+3.
Section 534 applies toAC power circuits. As far as it is applicable, the requirements ofSection 534 may be followed
for DC power circuits.
NOTE 3: Overvoltages ofatmospheric origin and electrical switching events can affect metallic data. signal and telecommunication
ljnes. Protection measures for these systems are detailed within PD CLC/TS 61643-22.
to specifically prevent danger-ous sparking which could lead to fire or electric shock hazards. In accordance with
BS EN 62305-4, a lightning protection system which only employs equipotential bonding SPDS provides no effective
protection against failure of sensitive electrical and electonic systems. Further SPDS (TWe 2 and Type 3) are
required to protect sensitive and critical equipment (for example, hospital equipment and fire/secu ty alarm systems)
downstream ofthe origin ofthe electrical installation.
534.4-1.2 In accordance with the LPZ concept, where a cable crosses the zonal interface, further SPDs shall be
installed to preserue the zone integrity.
534.4.1.3 where the installation of SPDs is required by Section 443 and the sfixcture is equipped with an
extemal lightning protection system or protection against the effects of direct lightning, Type 1 SPDs shall be
installed as close as possible to the odgin ofthe electrical installation.
534.4.1.4 Where the installation ofSPDs is required by Section 443 and the structure is not equipped with an
extemal lightning protectiofl system or does not require protection against the effects of direct lightning, Type 2
SPDs shall be installed as close as possible to the origin ofthe electrical installation.
534.4.1.5 Type 2 or Type 3 SPDs sha1l be located in the fixed electrical installation, for example, in sub-
dist bution boards or close to the equipment to be protected, to achieve the required voltage protection level; see
Figure 534.2. These SPDs shall be coordinated with Type I and/or Type 2 SPDs being installed at the origin ofthe
electrical installation (see Regulation 534.4.4.5).
-,"\
f^'"iuRY E
fl
Io '***
161
ryry T
Fig 534.2 - Example of insta ation of Type 1, Type 2 and Type 3 SpDs
534.4.1.6 Consideration shall be given to the provision of SPDs to protect from other sowces, such as:
(i) switching ovewoltages produced by curent-using equipment rocated withir the installation
(ii) ovel'voltages on other incoming services such as metallic telecommunication and signalling services
(iii) overwoltages on other seryices feeding other structures such as secondary buildings, extemal
installations/lighting, power lines feeding extemal sensors.
These SPDs shall be installed and located as close as possible to the origin of such events.
NOTE: For fufther inl-omation see BS EN 61643-12 series and BS EN 62305_4.
534'4'1 '7 The presence of SPDs installed downstream of a distribution board (e.g. in a socket-outlet)
shall be
permanently indicated (e.g. by a label) at or near the distdbution board.
An example ofconnection Type crl for application in a three-phase system is given in Figure 534.3.
162
Fig 534.3 - Connection Type CT1 (4+0-configuration) for a three+hase system with neutral
Ll L2 L3 N
An example ofconnection Type CT2 for application in a three-phase system is given in Figure 534.4.
Fig 534.4 - Connection Type CT2 (e.9. 3+1-configuration) for a three-phase system with neutral
L1 L2 L3 N
In installations operatrtg at 230/400V, the voltage protection level ofthe instaltecl SPD assembly shall not exceed
2.5 kV, as the SPD's connecting leads have additional inductive voltage drop across them (see Regulation 534.4.8).
It may, therefore, be necessary to select an SPD with a lower voltage protection level.
Ifthe distance between the SPD and equipment to be protected (protective distance) is greater than l0 m, oscillations
could lead to a voltage at the equipment terminals ofup to twice the SPD'S voltage protection level. Consideration
shall be given to the provision of additional coordinated SPDs, closer to the equipment, or the selection of SpDs
with a lower voltage protection level.
NOTE 2: It is recommended that the voltage protection level provided by SPDS does not exceed a safety margin of 80 % ofthe
required rated impulse voltage for equipment according to Table 443.2 and conesponding to overvoltage category Il.
This safety margin is not necessary where one ofthe foltowing cases applies:
- where the equipment is connected directly to the SpD terminals
- where a protection scheme according to Figure 534.9 is already applied
- where the voltage drop across the overcuaeflt protection in the SPD branch circuit is already taken into account
for the voltage protection level Up
- where protection accordi[g to overvoltage category II is provided but only over.r'oltage category III or IV
equipmenl is installed at this locatio[.
NOTE 3: DD CLC/TS 61643-12 gives additional infomalion about the mted impulse voltage of equipment and the given Up
for rhe SPD.
Table 534.2 - Minimum required uc of the sPD dependent on the supply system configuration
SPD connected bctween System configuration of distribution network
(as applicable)
TN system TT system lT system
Line conductor and neutral 1.1 U l.1u 1.1 U
conductor
.i3 i3 !3
or (0.64 x U) or (0.64 x U) or (0.64 x U)
r/: ri:
1.1 U
or (0.64 x U) or (0.64 x U)
or (0.64 x U)
Line conductors 1.1U 1.1U 1.1U
NOTE: U is the lineto-line voltage ofthe low voltage system.
a These values are related to worst-case fault conditions, therefore, the tolerance of 10 o/o
is not taken into
account.
164
impurse discharse
of spDs with resard to discharse currenr (r*oa) and
T *rr_ection
Atolneartheoriginoftheelectricalinstallation,SPDsshallcomplywithoneofthefollorvingcases.asapplicable:
-wherethebuildingisprotectedagainstdilectlightningstrike,SPDsattheoriginoftheelectricalinstallation
4 4 4 2 and Table 534 4
shall be selected according to Regulation 534
Regulatiot 534 4 4 4 l'
in other cases, SPDs shall be selected according to
also comply with the
near the oligin ofthe electrical installation shall
spDs installed downsfeam ofthe sPDs at oI
coordination requirements in Regulation 534 4
4'5 '
NorE:overvoltagesduetoswitchingcanbelorgerindurationandcancontainmoreenergythanthetransientovervoltages
discharge cuaent
origin. fnl, fri. io U. for the selection of SPDS with regard to nominal
of atmosphe c "oniidered
infomation DD CLC/TS 61643-12'
and impulse discharge cunent For tufiher
see
WhereType2SPDsarerequiredatornealtheodginoftheelecfficalinstallation,theilnominaldischargecurrent
(In.pa) shall be not less than that given in Table 534 3'
Table534'3-Nominaldischargecurrent(l""pd)dependingonsupplySystem
and connection TYPe
WhereTypelsPDsalelequiledatorneartheoriginoftheelectricaliastallation,oneofthefollowingcasesapplies:
(i)WherenoriskanalysisaccordingtoBsEN62305-2hasbeencarriedout'theimpulsedischargecurrent
(Ii,,p) shall be not less than as given in'fable 534 4'
NOTE
- Tht. r"f".,. t€htning prot""tion]t"1t (L!LI]lg:g IV
"b1"
be€n caried out' the impulse discharge current
(ii) Where the risk analysis according to BS Ef,61i91^1lis
{1,,"!l shall be detennined according to the BS
E\ 02105 series'
NOTE 2: This requirement does not apply to SPDS connected between the neutral conductor and PE in TN or TT systems, fbr
which this is already covered by the product standard BS EN 61643-l l.
For SPDs connected between the neutral conductor and PE in IT systems, the shofi-circuit current rating I"ccn ofthe
SPD shall not be lower than the maximum prospective short-circuit current at the connection points oithis SpD in
case ofa second fault.
534.4,4.7 Selection of SPDS with regard to the follow current interrupt rating (h)
In general, the follow current interrupt rating Ifi ofthe SPD, ifdeclared by the manufacturer, shall not be lower than
the maximum prospective short-circuit curent at the connection points ofthe SPD assembly. See Figure 534.5.
For SPDS connected between the neutral conductor aIId PE in IT systems, the follow cuffent interupt rating 16 ofthe
SPD, ifdeclared by the manufacturer, shall not be lower than the maximum prospective short-circuit current at the
connection points ofthis SPD in case ofa second fault.
Key
OCPD 1 overcu[ent protective device in the installation
OCPD 2 overcurrent protective device specified by the
SPD manufacturer
SPD surge protective device
SPDA SPD assembly
A&B connection points of SPD assembly
EIT equipment or installation to be protected.
534.4.5.1 General
SPD installations shall be protected against overcurent with respect to shorGcircuit curents.
This protection may be intemal and/or extemal to the SPD according to the manufacturer's instructions.
The ratings and chamcteristics ofextemal OCPDs for protecting the SPD assembly sha11 be selccted in accordance
with Section 434 and be the highest permissible rating to provide
a high surge curert capability for the complete
assembly whilst not exceeding the rutings and charactedstics as required in the SPD manufacturer's installation
instructions for the maximum overcurrent protection.
166
534.4.5.2 Arrangement of SPDs with relation to overcurrent protection
Incase of OCPD opemtion a sing from SPD failure, the continuit) of dre supph ro dre equipment is unaffected.
However, neither the installation nor the equipment is protected against pos:ible tunher over.,,oltages (see Figule
534.6). Il such an a[angement, the effective voltage protection ler el u ithin the insrallation is increased due to the
additional voltage drop at the extemal OCPD connected in series s ith the SPD.
K"y
OCPD overcurent protective device specified by the
SPD manufacturel
SPD suge protective device
SPDA SPD assembly
A&B connection points of SPD assembly
Efi equipment or installation to be protected.
534.4.5.3 SelectivitybetweenOCPDs
Where selectivity between OCPDs is necessary to prevent danger and where required for proper functioning ofthe
installation, the manufacturer's instructions shall be taken into accounl see Regulation 536.4.
534.4.6 Faultprotection
Fault protection, as defined in Chapter 4l, shall remain effective in the protected installation even in the event of
SPD failure.
NOTE; Additional requirements rnight apply for SPDs installed in the area of influence of applications such as railway
systems, HV power systems, mobile units, etc.
Where SPDs are installed in accordance with Regulation 534.4.1 and are on the load side of an RCD, an RCD
having an immunity to surge curents ofat least 3 kA 8/20 shall be used.
NOTE 1: Type S RCDs in accordance with BS EN 61008-1 and BS EN 61009-l satisly this requirement.
All conductors and interconnections to the relevant line to be protected, together with the connections between the
SPD and any extemal OCPD, shall be kept as shorl and as straight as possible and any unnecessary cable loops shall
be avoided.
The length ofthe connecting conductors is defined as the sum ofthe path length ofconductors used from the live
conductor 10 the PE in between connection points A and B as shown in Figure 534.8 (for example, a + b + c).
168
Fig 534.8 - Connection of the SPD
A Live conductor
Key
OCPD overculTent protective device
SPD surge protective device
PE conduqtor protective earthing conductor
A and B conlection points of SPD assembly.
NOTE: When the OCPD is not present, lergth b is cqual to 0.
Consideration shall be given to limit the total wiring length of conductors between connection points of the SPD
assembly, which should preferably not exceed 0.5 m and in no case exceed 1.0 m.
To meet these requirements, the main protective conductor shall be connected to the eafihing terminal located as
near as possible to the SPD by adding, if necessary, an intermediate earthing teminal (see Figure 534.9).
To determine the total lergth of the connecting conductors according to Figure 534.9, the lollowing conductor
rensths shall not be taken into account:
between the main eathing terminal and the intermediate earthing terminal
I
between the intermediate earthing terminal and the PE conductor.
The length (and therefore inductance) ofthe conductors betweer the SPDs and the main earthing teminal shall be
i.pt to a minimum. SPDS may be connected to the main eadhing tenninal or to the protective conductor via metallic
rafts. e.g. the metallic enclosures ofthe assembly (see Regulation 534.4.2), provided it is connected to PE and meets
--:r- requirements for a protective conductor in accordance with Chapter 54. Connection ofthe rclevant SPD(s) to the
:.ain earthing teminal, and in addition to the main protective conductor, may inprove the voltage protection level.
: ihe total wiring length (a +b +c) as defined in Figure 534.8 exceeds 0.5 m, at least one of the following options
be chosen:
':all
select an SPD with a lower voltage protection level U, (a I m length of rectilinear conductor carrying a
discharge curent of 10 kA (8/20) adds a voltage drop ofabout I 000 V)
install a second coordinated SPD ctose to the equipment to be protected so as to adapt the voltage protection
level U! to the rated impulse voltage ofthe equipment to be protected
rse the installation method as shown in Fisure 53,1.9.
169
Fig 534.9 - Example of installation of an SPD in order to decrease lead length
of SPD supply conductors
Key
OCPD overcurrent protective device
SPD surge protective device
PE conductor protective earthing
Elt equipment/installation to be protected
1 main earthing terminal
2 intemediate eaft hing terminal
3 length c (to be considered)
4 cable lengh need not be considered
5 cable length need not be considered
AandB connection points of SPD assembly.
l.
535 DEVICES FOR PROTECTION AGAINST UNDERVOLTAGE
comply with the relevant requirements ol Section'l-15'
Devices for protection against undervoltage shall
for protection against undervoltage mal- be required'
For protection ofpeEons and propedy, devices
are selected as follows:
Protective devices against undenoltage
(i) direct operating undervoltage release:
Iower value ofthe relay operating voltage
higher value ofthe relay operating voltage
- time delaY (ifrequired)
(i,) indirect opemting undervoltage release:
- lower value ofthe operating voltage
- higher value ofthe opemting voltage
- time delaY (ifrequired)
(ii0 automatic reclosing when the voltage is restored:
with reclosing Prevention
without reclosing Prevention'
Thecharacteristicsoftheprotectivedevicesagainstundervoltage-shallbecoordinatedwiththerequifementsinthe
offof the electrical equipment'
(in:rurrl op*u,lon aid switching
relevant standards for switching on "r'."*l
FOR PROTECTION' ISOLATION'
536 CO-ORDINATION OF ELECTRICAL EQUIPMENT
SWITCHING AND GONTROL
536.1 General
hissectiolcovelsco-ordinationinthecascofafaultandoverloadconditionsandalsotakesintoconsideration
as follows; deviccs
..p..it l"i..ti". L3 relevant to the co-ordination of electrical
- overculTcl.It protcctive device (OCPD)
(CPS)
control and protective switching device
- residual curent device (RCD)
- contactor and starter
- switch and disconnector'
\OTE 1: Co-ordination ofmonitoring devices is undel considemtion
\oTE2:Referencetothemeaningof.someoftheabbreviationsusedinthissectionmaybefoundinTableA53,linArrnexA53
located at the end ofthis chapter'
but provides requirements
the selection ofan electrical device alone'
-::.n 536 does not provide requireurents lor
' :'j,,:"
them'
co-ordilation between
selection ofelectrical devices to achieve electrical
. squilell]entsalsocoveraspectsofcontinuityofsupplyoftheinstallation'
provided
:.:6.2 Electrical devices considered and function
by different electrical devices'
\: -E: Table A53.I in Arnex A53 sho$'s the functions provided
1-',
Electrical devices shall be selected taking into account the co-ordination characteristics as givenby the m anu facturers.
536.4 Requirementsforselectivity
536.4.1 General
Selectivity between OCPDs is defined in Regulation 536.4.1.2 for overload conditions and in Regulation 536.4.1.3
for short-circuit conditions. Selectivity between RCDS is defined in Regulation 536.4.1.4 and selectivity between
OCPD and RCD is defined in Regulation 536.4.1.5.
In the case of a desk study, when time/current characteristics are used to veriry selectivity, account shall be taken
of the reference ambient temperature for which the tdpping curves are given and to load conditions before the
overcurTent.
o
c
P
D
1
o o
C c
P P
D D
21 22
In cases given in .{53.7 and 453.10 in Annex A53, selectivity will be obtained for shot-circuit currents up to a
specific value, the selectivity limit current. The value ofthis limit wili be given by the manufacturer In a pafiicular
installation selectivity may be total or partial.
NOTE: Generally, manufacturers provide tables giving information on selectivity in case of short-c ircuit.
536.4.1.4 SelectivitybetweenRCDS
(i) General requirements
Where selectivity is required (see Figure 536.2), verification shall be made either by:
desk study, taking into account the relevant product standard and the manufacturer's literatue, or
appropriate software tools where information is provided by the manufacturer for this specific use, or
tests in accordance with the applicable product standard (in order to achieve the correct test performances
and reproducibility), or
manufactwer's declaration.
NOTE 1: Generally, manufactuers provide information specifying selectivity between RCDS.
Selectivity in case ofresidual currents, as shown in Figure 536.2, is given under the following conditions:
the upsheam RCD is ofselective type (type S or time-delayed type with appropriate time delay setting), and
the mtio of the rated residual operating current of the upstream RCD to that of the downstream RCD is at
least 3:1,
In the case of RCDs with adjustable rated residual operating current and time delay, reference shall be made to
rnanufaclurer's in:.tructions lor selectivity.
NOTE2: RCD type S is in accordance with BS EN 61008 se esorBSEN61009series.
NOTE 3: A time-delay iype RCD ir accordance with BS EN 60947-2. Annex B or Annex M will be marked rvith thc symbol At
followed by the limiting non-actuating time in 1rrs or markcd with an [S]
L 173
Fig 536.3 - Selectivity between OCPD and RCD using RCBOS
o
c
D
1
R R
c c
B a
o o
21 22
In Figure 536.3, ifRCCBs are used instead ofRCBOs, selectivity cannot be guaranteed. In this case, ifthere
are OCPDs downstrcam olthe RCCB, as shown in Figure 536.4, selectivity may be achieved provided that the
requirements ofRegulation 536,4.1.2 and Regulation 536.4.1.3 are fulfilled. In addition, the connection between
the RCCB and the downstream OCPD shall be selected and erected so as to minimize the risk of earth faults.
NOTE: ln orderto minimize the risk offaults between RCCB and downstream OCPD, specific wir-ing accessories may be used
(e.g. .pecifi c bu.bars).
o
C
D
1
R
c c
c C
B B
21 22
o o o
C C C
D D D
31 32
R
c
c
B
I
R R
C C
B B
o o
21 22
This breaking technique allows the use of short-circuit protective devices with a lower breaking capacity than
required in Chapter 43. It is only applicable to short-circuit protective devices.
o
c
P
D
1
o
c
P
D
2
irc
_.31',1
'' Regulation 434.5.1 permits a device with a lower rated breaking capacity than the prospectiYe short-circuit curent
::l'lts
at its point of installation to be used in specific conditions.
When selecting two OCPDs for combined shod-circuit protection, reference shall be made ro rhe instmctions ofthe
manufacturer of the downsheam OCPD. These instructions are derived from tests peribrmed according to relelant
product standards, as applicable (e.g. BS EN 60947-2 andBS EN 60898-1). Where no iribrmatior is available from
the manufactruer, combined shofi-circuit protection of OCPDs shall not be used. and each OCPD shall har'e the
required short-circuit capabilily at the point ofinstallation.
Ifdeclared by the manufacturer ofboth devices, the combined short-circuit capability ofOCPDl and OCPD2 may
be higher than the breaking capacity of either OCPD. In this case, the connection between the two devices has to
minimize the risk of short-circuits and there shall not be any shofi-circuit contdbutions by other active equipment
in parallel to oCPD1.
NOTE 1 : Co-ordination of an OCPD with a separate curent limiter to increase the shon-circuit breaking capacil), of arl OCPD
may be used according to the manufactuer's instructions.
NOTE 2: Combined short-circuit protection may be used for manual motor stafier having a short-circuit capabilit\, ifl combination
with OCPD. when declared in the manufacturer documentation.
Contactors complying with BS EN 60947-4-1 or BS EN 61095 do not provide protection against short-circuit, thus
they shall be protected by an upstream overcurent protective device (OCPD).
NOTE 1: Contlol and Protective Switching Devices (CPS) provide protection against short-circuir. and therefore provide
intinsic co-ordination.
Figure 536.7 gives a typical schematic for co-ordination ofa contactor with a short-circuit protective device (OCPD).
Regutation 512.1.2 requires equipment to be selected for the design current which it has to carry in normal service
and the current likely to flow in abnormal conditions. In the event of shofi-circuit, the let-through energy and the
peak culTent may cause the contactor to open its contacts at a level of current beyond its making and breaking
capacity. Co-ordination ofthe contactor and the OCPD is needed to achieve safe operation in case ofshot-circuit.
Co-ordination between a contactor and an OCPD is verified by mandatory shod-circuit tests according to BS EN
60947-4-1or to BS EN 61095, as applicable.
Contactors shall be selected and erected in conjunction with the shorl-circuit protective device declared by the
manufactwer, such that the rated conditional shofi-circuit current is higher than the plospective short-circuit current
at the point ofinstallation.
The rated conditional shot-circuit curent can only be obtained by type-testing and thus the data for the selectiol'r
of the OCPD shall be obtained from the manufactuer of the contactot taking into account the rated operational
curent, rated operational voltage and the corresponding utilization category.
NOTE 2: This information is genemlly provided in co-ordination tables which summarize the combination ofdevices (OCPD.
contactor or motor starter) able to maintain a safe behaviour for a given rated conditional shofi-circuit.
In a motor circuit the overload curent protection may be provided by separate overload rclay electrically connected
with the contactor. In such a case protection ofthe overload relay shall also be achieved, since the overload relay
may be damaged by the letthrough energy (l':t) of the OCPD. This infomation is generally provided in the
manufactui'er's co-ordination tables.
176
536.4.2.3 Back-up protection of switches, Transfer Switching Equipment (TSE) or impulse
relays
Switches cornplying rvith BS EN 60947-l or BS EN 60669-2-4, Transi'er Sl irching Equipruent (TSE) corrplying
u'ith BS EN 60947-6-l and impulse telays complying with BS EN 60669-2-l are used to switch loads or circuirs
(e.g. distributior switchboard, lighting circuit, specific load). These devices do nor provide protection againsr shoft-
circuit. thus they shall be protected by an oyercun'ent protective device (OCPD).
NOTE: Fuse combinatior units to BS EN 60947-3 consist ofa sivitch and inte$ai liLse(s) and have a short-circuit capability
declared by thc nranut'actuler which does not lequile the use an upstrcaln OCPD.
Should a shot-circuit occur on the load side ol a switch, the curent will flou, through both devices (OCPD and
switch); therefore the let-through energy ancl the peak cuffent limited by the OCPD need to be compatible with the
shofi-circuit withstand ofthe switch, the TSE or the irrpulse relay.
Figure 536.9 gives a typical scllenatic for co-ordination of a switch with a short-circuit protective device (OCPD).
The OCPD may also be situated downstleam of the switch, TSE or impulse relay provided that the connection
letweerl tbe switch and the downstream OCPD is selectcd alrd erected so as to minimize the risk ofeafth faults and
.hort-circuits.
Silitches, Transt'er Switching Equiprrent and imptLlse relays shall be selected and erected in conjunction with the
.hort-circuit prctective device declared by the manufacturer in order that their mted conditional shorl-circuit cuffent
.: equal to or higher tl]an thc plospective sltoft-circuit cuffent at the point ofinstallatiou.
The rated conditional shoft-circuit cuuent of the switch can only be obtained by typc-testing and thus the data fbr'
::'ie selection of the OCPD shall be obtained from the nlanufacturer of the switch, taking into account the l?ted
:perational current and the rated operatiotal voltage.
.rr switches according to BS EN 60947-3, where the OCPD is not specified by the switch nrarufacturer, an
..ienrative nlethod lor co-ordination between the OCPD and the switch is as follows:
the rated short-circuit making capacity of the switch is higher than the peak value ofthe prospective shofi-
circuil culrent at the point of i[stallation, and
the OCPD time-cunent charactedstic is within the limits oflcw ofthe switch. as stated by the manufhcturer,
OI
the mted slloft-ci[cuit making capacity is higher than the peak value ofthe prospective sllorlcircuit cu[ent
at the point of installation, and
tl're mted shot time withstand cuffent is higher than the prospective shoft-circuit cu[ent at the point
of installation and the coffespondirg withstand time is longer than the operatiru time of the SCPD. if
applicable, or
ifat the prospective shofi-circuit cLnreDt" the protective device has an energy lerthrough (lrt) and cut-ot'f
currelt not exceeding the values for d]e s$,itch provided by the manufactLLrer.
177
_--.--
536.4.2.4 Back-up protection of RCCBS
In this regrilation. the OCPD cottld be replaced by an SCPD.
RCCBs complying u'irh BS EN 61008 serics are intended to protect persons against elect c shocks. They may
also be used to pl'o\, ide prolectiolr against fire hazards due to a persistent earth fault. These devices have a limited
siroft-circuit current rvithstand capability. thus they shall be protected by an upstream overcun ent protecti\ e device.
ShouLd a shorr-cilcuit occur. on the load side of a RCCB, the current will flow through both devices (OCPD and
RC CB): rheretbre tlrc lct,through energy and the peak curent limited by the OCPD need to be cornpatible with the
short-cil'cuit $ithstand capability of the RCCB.
Figure 536.10 gives a typical schenratic for co-ordination ofa RCCB with a short-circuit protective device.
RCCBs shall bc sclected and erected in conjunction with the OCPD declared by the manufacturer in order that their
rated conditional sltofi-circuit cu[ent is highcr than the prospective short-circuit cu-rent at the point ofinstallation.
Thc lated conditionai shoft-circuit curent of the RCCB with the OCPD, related to the relevant mted operational
cLrrrent and rated operational voltage. is given by the manufacturer based on tests results according to BS EN 61008
selies.
The OCPD rrlay also be situated downstream of the RCCB provided that the connection between RCCB and
dorvnstrearn OCPD is sclected and erected so as to minimize the risk ofcarlh faults and shofi-circuits.
Devices for overload protection are selected for the protectiol of cables. For overload protection of contactors or
SCPDs. the lated curlcnt of thc OCPD shall be selectcd according to manufacturers' information.
In cases rvhere Regulation 433.3 permits omission ofoverload protection, co-ordination in case ofoverload does not
apply
178
Regulation 43 3. I rcquires that devices for overload protection be selected lbr the proiection of cables. For overload
protection of RCCBs and switches, the rated cu-rent of the OCPD shall rake account of the manufaclurer's
information: in general, the OCPD is installed upstream olthe RCCB or the su itch.
The rated current ola switch or RCCB may also be based on the application ofdi\ ersity factors to the downstream
circuits according to Regulation 311.1, and the rated curent of the OCPD shall be selected according to the
manufacturer's instructions. See also Regulation 536.4.202.
NOTE: wllen usirg an RCBO instead of an RCCB, no f'ufiher consideration regarding orerload protection ofthe RCBO is
rleccssar].
Regulation 433.3 specifies conditions lor omission of overload protection. In such cases overload co-ordination
does not require verification.
536.4.4 Requirements for selectivity between OCPDs equipped with under voltage relay
lncase offault (short-circuit or eafth fault) a high fault cufient may generate a voltage drop through the installation.
Voltage drop may also occur i[ the installation for other reasons (for example, switchilg and reclosing of HV
switching device).
Wherc one undervoltage relay is installed in the OCPD on the supply side or elsewhere in the installation, possible
undewoltage rclay operation shall not impair selectivity achieved between OCPDs ard/or RCDs in series.
o
c
P
D
1
::_-ail: o o
C C
:: r)ll.
P P
:..l1al D D
r08 22
I .urcl
For selectivity, undervoltage rclay operation sha11 be time-delayed according to the maximum shoft-circuit or eartll
fault clearance time. ln all cases, instuctions plovided by the manufacturer shall be fulfilled in order not to irnpair'
the safety ofthc electrical iustallation.
:Srso11s The teflninology used to define the shofl-circuit rating ofan assenbly is given in the BS EN 61439 series as follows;
plyitg ratcd short-tilne withstand current. I.,,
..rne of
rated peak wilhstand curent. lur
t,-ctive
ratcd conditional sbort-circuit curent. I...
The assembly manut'actur-cr-'s ratings and instntctions shall be taken into accolul.
179
For ao installation with a 230 V silgle-phase supply rated up to 100 A that is under the contlol of ordinary persons,
switchgear and controlgear assemblies shall either comply with BS EN 61439-3 having a suitable fault cunent
(shofi-circuit) rating for the maximum prospective fault current at the point of connection to the systen or be a
consllfiter unit incorporating components and protective devices specified by the manufacturer complying with
BS EN 61439-3, including the 16kA conditional short-circuit test described in Annex ZB of the standard.
NOTE: When the single-phase PSCC value of 19.6 kA is cited from Engineering Recommendatior P25, the l6 lcA conditional
rating described in Annex ZB of BS EN 61439-3, for incoming service equipment, will satisfy design requirements
where the servicc cable is at least 2 mctres in length.
536.4.202 Currentratings
The relevant design current shall not exceed the rated cu[ent of an assembly (1,,A) or rated cu[ent of a circuit (I,,.)
ofthe associated assembly, having taken any applicable diversity/loading factors into account.
The teminology used to define the rating of an assembly in relation to load/design cunent used in BS EN 6l4jS
can be summarized as follows:
- Tlte rated current of an assembly (I",q) (A)o is the maximum load current that it is designed to manage and
distribute.
- The rated curent ofa circuit (I..) (A) is stated by the assembly manufacturer, taking into consideration the
mtings ofthe devices within the circuits, their disposition and application.
The cunent rating(s) of an assembly circuit may be lower than the rated current(s) of the device(s) according to
their respective device standald, when installed in the assembly; therefore, the assembly manufacturer's ratings and
instructions shall be taken into account.
Rated divenity (loading factor) can be stated by the assembly manufacturer, e.g. for goups ofcircuits.
The rated curent of a switch or RCCB (I,,.r and I,,,) shall be based upon:
the sum of6nal circuit current demard after any applicable load divl]Isity factors, or
thc sum offinal circuit culTellt dernand alicr any applicable load diversity thctors togclhcr with allou'ances
fol diversity betu,ccn final cilcr.rits. or
the sum ofthe downstream OCPDsT'circuit ratcd curaent multiplied by a diversity factor.
Howevel overload protection shall not solely be based on the use ofdiyersity factom ofthe downstream circuits.
To achieve overload protection of RCCBs or switches, the rated current ofthe OCPD shall be selected according to
the manufactuer's instructions.
The relevart part ofthe BS EN 61439 series shall be applied to the integration ofmechanical and electrical devices
and components, e.g. circuit-brcakers, control devices, busbars into an empty ellclosure or existing low voltage
assembly.
In low voltage assemblies to ttre BS EN 61439 series, e.g. consumer units, distribution boards, incorporated devices
and conponents shall only be those declared suitable according to the assembly manufacturer's instructions or
litemture.
NOTE 1: The use of ildividual componeDts complying with their respective product standard(s) does not indicate their
conpatibility when installed with other components in a low voltage switchgear and conffolgear asscnbly.
NOTE 2: Incorpomted components inside the assclrbly can be from different manufacturers. lt is essential that all incorporated
components shouidhavelrad their compatibility forthelinal enclosedarrangernents verifledbythe original manufachrrer
of the asscmbly and be assembled in accordance with their instructions e.g. the consumer uDit. distribution board
manufacturer. The original rnanufacturer is the organization that carried out the oiginal design and the associated
verification ofthe low voltage switchgear and controlgear assenlbly to the relevant part ofthe BS EN 61439 series.
lf an assembly deviates froln its original manufacturer's inshuctions, or includes components not included in the
original ver.ification, thc person introducing the deviation becomes the original manufacturer with lhe corresponding
obligations.
536.5 Documentation
The infonnatiol mentioned in the previous regulations for co-ordination of electrical devices may be found in
manufacturers'documentation (e.g. catalogue, instuuction sheets, calculation software).
Whe[ the initial verification is made, the documentation conceming the selection ofdevices for co-ordination shall
be addcd to the design documentation in accordance with the requirements ofRegulation 132.13
180
537 ISOLATION AND SWITCHING
537.1 General
::l This section provides requirements fbr:
(i) non-automatic local and temote isolation and switching neasurcs tbr the preventiolt or removal ofdangers
associated with electrical installations or electrically-powered equipment and machines, and
(ii) tunctional switching and control.
537 .1 .1 Any device foI isolation and switching accolding ro Sections 162 to 465 shall comply rvith the
lelevant requiremerrts included in this section.
i.) ln ceftain instances, additional requirefl]ents may be necessary lbr contbined functions.
NOTE 1: Tablc 517.,1 sLLmnlarizes the luDctions provided by the dcvices for isolation and s$itching, togcther with indicarion ol
'j9 rl,( r(lr\ anl product.ra ddrd*.
NOTE 2: Foi sorre applicatioDs such as nrotor contlol, the switcJ'ing device needs ro withstand the inrush curent.
lnd NOTE 3: Table 537.4 provides infonnation or sclection.
BS EN 60947-3
BS EN 609,17-s-1 No Yes \ts
ruits. (i)rltactor BS EN 60947-4-l
ing to BS EN 61095 No No Yes
C ircuit-breaker' BS EN 60898 Yes
BS EN 609,17-2 Yes .3)
181
BS l36l-l
BS 1363-2
Yesdr(Relnoval
of fuse li k)
Regulation 462.2.
(5)Circuit-breakcrs nnd RCDS are p marily cilcuit plotective devices and. as sr:ch. they arc not intended for frequent load
purposes ofisolation oI emergency switching
s\\,itching. Infrcquent switching of circuit-breakels on-load is admissible for the
ofoperations and load characte stics according to the manufactLuel's instructions shoLlld
FoI a mol.e liequent duty. the numbel
ftlnctional switching il] Table 537 4 should be
be taken into accol lt oL an altenlative device from tllose ]isted as suitable for
employecl.
ma*ed with the symbol fol on-load
NOTE : An entry of ( I,3 ) rreans that the devicc is suitabie for onJoad isolation only if it is
1
isolation ---lq-
and swjtching ale summarized, together with an
NOTE 2: Ir the abovs rable. the functions providcd by the devices fol isolation
indication o1' the rclc\ ant product standards.
10 more than
537 .,1 ,2 where at,] installation oI an iten of equjpment or enclosule contains live parts connected
that any person, before gaining access to live
one supply. a durable wanring notice shall be placei in such a position
the various supplies unless an interlocking arangement
ionr. i.iLiu. *u"r.d ofthe rieed ro isolate those parls from
is provided to isolate all the circuits concemed
Wherc an installation is supplied from more than one source of energy, one
of which requires a
537,1.5 provide that not more
means ofeatthing independent ofthe means ofearthing ofother sources and it is necessary to
than one means Jfeanili.g is applied at a,y time, a switching device may be inserted in the connection bet\'vee11the
neutml point and the ucatrs of earthing, provided that the device is:
(i)anrultipole.linkeds\\'itchillgdevicearrangedtodisconnectandconnecttheeafihingconductorforthe
''
nppropriut" ,ource at substantially the same time as the related live conductors' or
lelated live
(ii) a switchirg device iuterlocked with a multipole, linked switching device inserted in the
conductolssuchthattheearthingconductorfoltheapplopatesourceshallnotbeintenuptedbeforethe
the live conductols ale leconnected'
related live conductors al]cl shall-be re-established Ilot latel than when
of chapter 46 for a device
switching devices provided in accordance with (i) and (ii) shall meet the Iequilements
for isolation.
18?
537.2.3 Der.ices suitable tbr isolation shall be selected according to the requi:ei--:::. - :rri:r tr:3 r::.i t-]n the
overvoltage categories applicable at theil point ofinstallation.
Devices for isolation shall be designed for over voltage category III or lV except the plug ..; r p,ug and socket-outlet
cornbi[ation identilied in Table 537.4 as suitable for isolation
NOTE: Wher.e clectrically powcred equipment is witli[ the scope ol BS EN 6020.1. the requirem.nli l-or isolatiol of that
standard apply.
537.2,4 Devices lor isolation shall be selected and/or installed so as to pre\enl un\\anled or unintentional
closure (see Regulation 462.3).
This n.ray be achieved by locating the device in a lockable space or lockable enclosure or b}' padlocking or by other
suitable n'reans.
537.2.5 Provision strall be made for securing offJoad isolating devices agailrst un$'anted or uniutentional
opening.
This n]ay be achieved, for exanple, by locating the device ir a Iockable space or lockable enclosure ol by padlocking
Altematively. the off-load device may be interlocked with a load-breaking one.
537.2-6 Means ofisolation shall preferably be provided by a nrultipole switching device which disconnects
all applicable poles ofthe relevarrt supply but single-pole devices situated adjacert to each other are not excluded,
subject to the provisions ofRegulation 461.2.
oad
ing. 537.2.7 Each clevice userl fol isolation shall be cleally identified by position or durable marking to indicate
i\uld the installation or circuit it isolates.
dbell
537 .2.8 Where a link is inserted in the neutml conductor for isolating purposes, the link shall comply with the
following requilemerts:
- it cannot be removed without the use ofa tool, and
- it is accessible to one or more skilled persons only.
537.3.1.2 Furlctional switching devices shall be suitable tbr the most onerous duty thcy ae irtended to Perform.
: lor The chamcteristic ofthe load to be switched shall be considered (e.g. utilization category).
537,3.1.3 Functional switching devices may control the current without necessarily opening the correspondilg
poles.
NOTE: Semicoiductor switching devices and some control auxiliaries are exantples of devices capable of intempting the
cLur-ent in the circuit but not opening the conesponding poles.
:rr the NOTE: Wher.e elecflically powered cquipment is within the scope of BS EN 60204, the requircments for switching off for
mechanicai maintcnance ofthat standard apply
:: -i livc 537 .3.2.2 Devices for switchirg off for mechanical maintenance shall be inserled in the main supply circuit.
' ri the
','ited. Where a switclr is providcd 1br this purpose, it shall be capable of cutting off the full load current of the relevant
paft of the installation.
- -'rr ice
lnte[uption of a circnit tbr tl]e control of mechanical moverrent is permitted only where a condition equivalent to
the direct interruption olthe main supply is provided by one ofthe fo)lowing:
(i) Supplementary safeguards, such as mechanical retainers
' '\\ tbe (ii) Compliance with the requirements ofa British or Hamonized Standard specification for the cotttt'ol devices
used.
NOTE: Switching offfor rnechanical maintenance may be achieved, for example, by orre ofthe following:
- multipole su'itch
- cilcuit-breaker
- control and protective switching device (CPS)
- control switch operating a contactol
- plug and socket-outlet.
537 -3.2-3 Devices for switching off lor mechanical maintenance or control switches for such devices shall
require manual operation.
The open position ofthe contacts ofthe device shall be visible or be clearly and reliably indicated.
The indication required by this regulation may be achieved by the use ofthe symbols 'O' and'I'to indicate the open
and closed positions respectively.
537.3.2.4 Devices for switching off for mechanical maintenance shall be clearly identi{ied by position or
durable marking so as to be identifiable for their intended use.
NOTE: Etrergency switching off is an emergency operatio[ intended to switch offthe supply ofelectrical energy to all or part
ofan installation where a sk ofelectric shock or another isk ofelectrical origin is involved.
537,3.3.1 Selection and erection of devices for emergency switching off shall be in accordance with the
following regulations and shall comply with Regulation 537.2.
NOTE: Where electrically powered equipme]tt is within the scope ofBS EN 60204, the tequirements for enrergcncy s\vitching
offof that standard apply.
537.3.3.2 The devices for emergency switching off shall be capable of breaking the full load current of the
relevant parts ofthe installation taking into account stalled motor curents where appropriate.
Plugs al1d socket-outlets shall not be provided for use as means for emergency switching off.
537.3.3.4 Devices for emergency switching off shall provide the switching of the main circuit.
Hand-operated switching devices for direct intenuption ofthe main circuit shall be selected where practicable.
Remote control switching of circuit-breakers, control and protective switching devices or residual cu[ent devices
(RCD) shall be opened by de-energization of coils, or other equivalent failure-to-safety techniques/actuato$.
537.3.3.5 The means of opcrating (handles, push-buttons, etc.) devices for emergency switching off shall be
clearly identified, preferably by colour. [f a colour is used for identification, this shall be RED with a contrasting
background (e.g. yellow).
NOTE: The contrasting background rnay or may not include text.
537.3,3,6 The means of oper ating shall be readily accessible at places where a danger might occur and, where
appropriate, at any additional remote position from which that danger can be removed.
Devices for emergency switching offshall be so placed as to be readily identifiable and convenient for their intended use.
537.3.3.7 The means of operation ofa device for emergency switching off shall be capable of latching in the
'OFF'position, unless both the tneans ofopemtion for emergency switching off and for re-energizing are under the
contlol ofthe same person.
The rclease of an emergency switching device opemted remotely shall not re-energize the relevant pan of the
installation.
The oper.ation ofthe emergency switching device shatl have priority over any other function relative to safety and
shall not be inhibited by any other operation ofthe installation.
537.4 Firefighter'sswitches
537.4.1 Firefighter's su itches shall comply rvith BS EN 60669-2-6 or BS EN 60947-3.
184
537.4.2 A lirefighter's ss.itch sJrall be provided in rhe low volrage circuir .r;qi1 rng:
(i) outdool liglrting installatiorls operating at a voltage exceeding loir rcriiag;. rnd
(ii) indoor dischatge ligtrting installatiors operating ar a voltage exceedins lo\,. \ (rlrase.
'fhis requirtment does not apply to a portable discharge lighting hurinaire or to a sisn t irating not exceeding 100 W and
f'ed from an accessible socker-outlet
NOTE: Installations in certain prel)1ises subject to licensing conditioDs. such as perrrrl .raiion tbrecoufis, nray requir-e the
illstallation of a firelighter's switch.
537.4.2.1 Every outdool installation on each silgle premises should rvhererer practicable be controlled by a
sirgle lirefighter's switch. Sirnilarly, every intemal installation in each single prernises shoLrld be controlled by a
single firefighter's switch i[depcndent olthe switch for any outdoor installation.
537.4.2.2 Every firefightcr's switch should comply with the following requirements. r.r,here applicable:
(i) for an outdoor installation, the switch should be outside the building and adjacent ro the equipment, or
altematively a notice indicating the position ofthe switch should be placed adjacent to the equiprnent and a
notice should be fixed neat the switch so as to lendel it clearlv distinquishable
(ir) for an indoot installation. the switch should be in the main entrance to the building or in another position to
be agleed with the locai fire authority
(iii) the switch should be placed in a conspicuous position. reasonably accessible to firefighte$, at not more than
2.75 l.r fiorr the ground or the standirrg beneath the switch.
537.4.3 A lirefighte/s switch shall be easily visible, accessible and marked to indicate the installation or pafi
of the ilstallation u'hich it controls
537.4.4 The lbllowing infomation shall be distinctly and durably marked on the fireflghter's switch in a
position where it can be seen clearly by a person standing on the ground at tlte intended site. witl'rout openi[g the
enclosure and when the switch is installed;
'ON' and'OL-F' positiors" in lettels lrot less than 10 nrrr high:
letters reading 'I IREI- IGHTER'S SWITCH'or'L-IRE SWITCII' in letters nor less rhan 10 nm high.
Once installed, the handle offposition shall be up.
NOTE: The'ON'position nteans powered and dre 'OFF' position means unpower-ed.
An IMD is intended to permanently nronitor tlle iusulation resistance ofan lT system and provides an alam where
:- :.4 the insulation resistance R,.is below the response value R,.
R[is tl']e insulatiotr resistance between the system to which it is connected and either the eafih, the PE conr]ectiolr 01'
anothel reference point fot protective equipotential bonding.
Examples ofthese systeDs would bc an electrical installation, a mobile generator or a saf'ety service.
An IMD shall be installed in an lT systenl where selected to meet with the requirement of Regulation zll1.6.4.
IMDs shall be installed as close as practicable to the origin ofthe pafl ofthe installatio,r to be monirored.
lnstructions shall be provided indicating that when the iMD detects an insulatior fault to eanh. the ilsulation t'ault
shall be located and eliminated in order to restore normal operating conditions with dre shortest practicable delay.
Where the 1T systen is used for continuity of supply, the occuffence ofa first insulation thult shall be indicated at a
suitable locatior'r so it is audible and/or visible by instructed or skilled pe$on(s).
NOTE: This alaln may be relayed though a buLilding management system (BMS).
It is recommended to use an IMD that signals an intefuption of the ureasuremelr connections to the system
colducton and earth.
538.1.2 lnstallation of insulation monitoring devices
Where a ncutr.al cotductor is clistlibuted, an insulation monitoring device (lMD) may be connected to the neutral
conduclor. In tltis case. no overcunent protective device shall be inserted in the conductor connecting the IMD to
the neutlai.
An IMD shall be corutected symmetrically or unipolar-iy between the live conductors and earth or the PE connection
ot alother ret'ereuce point ibt protective equipotential bondilg.
Where the neutral conductor is not diStributed. the 'line' tenninal of the IMD may be connected:
(i) either to an adificial neutral point with thc three impedances connected to line conductors' or
(ii) to a line conductol.
whcre. in a polyplrase system. the IMD is connected between one line conductor and eal1h, it shall be suitahle to
withstancl at least the linc-to-lil,]e voltage between its 'line'teminal and its 'eafih'teminal'
NOTE: This Iolrage appears across these two tenninals ir the case ofa single insulation fault oD another line conductot
For DC installations. rhe 'line' terminal(s) of the IMD shall be connected either directly to the midpoint, if any' or
to one or all of the supply conducto$.
The supply circuit of IMD shall be connected either to the installation on the same circuit ofthe connecting
point of
the 'line'terminal antl as close as possible to the origin ofthe systern, or to an auxiliary source'
Thc corDecting point to tl're installatior shall be selected in such a way that the IMD is able to monitor the
insulation
ofthe installatior in all operating conditions.
Where the inslallation is supplied from r11ore thar one power supply, connected in parallel, one IMD pel supply shatl
be used, provicled t)iey are iiterlocked in such a way that only one IMD remains connected to the system.
All other
IMDs nonitor thc diicolnected power supply, enabling the reconnection of this supply without any pre-existing
insulation fault.
lMDs shall be able to lncasure the insulation resistance of the system if DC components caused by electronic
eqrlipment. e.g. rectiflers ol collvertols, are contajned in the fault curent.
The IMD shall have a selection ofsetting values and be adjusted to suit the respective installation.
When operating nonnally with the maximum ofloads connected, the IMD shall be set to a lower value con espolding
to the ool.11-Ial insulaliol-I of tlle system.
NOTE: A r,alue ol 100 A/V (300 OIV for pre wamirg) ofthe mted system voltage is an example oftypical setting vallles.
Whcre IMDs arc installed in locations where ordinary persons have access to their use they shall be selected
and/or installecl in such a way that it shall be impossible to modify the settings except by the use of a key, a
tool or
a passuord.
538.2 Equipment for insulation fault location in lT systems
Equipment for insulation t'ault location shall be in accordance with BS EN 61557-9. Where an [T system has
been
sclec-ted for contiluity of service. it is recommended to combine the IMD with devices enabling the fault location
on load. Their lunction is to indicate the faulty circuit when the IMD has detected an insulation fau1t.
activated. A prer.ccluisite tbr it is that tlte monitored electrical circuits are isolated fro[r all poles ofthe system.
NOTE: As an cxanrple. this can be applicabJe to a circuit comprising safety equipment which is nolnally de-energiTed such I
thrt the salily equipmcnt is allowed to lr'ork without intervention ofsupply du ng the emergency'
The reduction ofrhe insulation level shall be inrlicated locally by either a visual or an audible signal
with the optron I
of rcl'note indication.
Ilthe equipment from the installation during the off-load insulation measuring process, the insnlation
is disconnected
levcls ro be mcasurcd arc generally very high. The alam threshold should be above 300 kQ.
186
538.4 Residual current monitors (RCMs)
538.4.1 General
RCMs shall comply with BS EN 62020.
An RCM peuna[ently monitors leakage and fault cunents to earth of the do\ nsream insi"]laiion or pan ihere of
and is iltended to infom the usel about the level ofthese currents ofthat part ofthe insiailation being merniterred.
Where an RCD is installed upstream of the RCM, it is recommended that the RCI\l be set to a residual actuatin-s
curent no higher than halfofthe rated residual operating current (I1") of the RCD.
It is recomnended that RCMs ale installed at the origin ofthe outgoing circuits.
RCMs shall initiate an audible and/or visual signal, which shall continue as long as the fault persists.
In IT systerrs where interruption of the supply irr case ol a first insulation fault to earth is not required or not I
pemitted, RCMs rnay be installed to indicate the occurrence ofa first insulation fault from a live part to exposed- I
Where used in IT systems, it is recommended to use directionally discriminating RCMs, in order to avoid unwanted
signalling of leakage cuffent w]ren high leakage capacitances are liable to exist downstream lrom the point of
installation ol the RCM.
€^o'\
f",*3
187
Annex A53
(lnformative)
Device functions and coordination
Table A53.1 - Devices and associated functions
Devices FunctioIrs
Product OCPD(N SCPDA' RCDO) Standard Overload Short-circuit Residurl Switching
protection protection current only
protection
Circtit-breaker x BS EN 60947 2 Yes Yes No No
BS EN 60898 I
BS EN 60898-2
BS EN 62423
RCBO x X BS EN 61009 series Yes Yes Ycs No
BS EN 62423
CBR x x BS EN 60947-2, Yes Yes Ycs No
Annex B
BS EN 61095
BS EN 60669-2-4
rr) fuse combination units according to BS EN 60947-3 are considered in this row
1r) generic abbreviations used in this docunent for devices
rr) when associated with a circuit-breaker
188
A53.1 Basis of correct co-ordination
uJr.,:::.,-j .- i ,!.!ie1 e(ri]rbination oftheir'
The basjs ofthe co-oldiuation between e)ectrical ccluipment is to take
,.lectrical ,'ltat'uttet'i<lrr'. irl older llr\l 1,, ilnpllr:
the safety olan installation (i.e. to avoid equipment combustion due to an electrical iaull). Comblned shorr-
circuit pr.otection ofOCPDs and back-up plotection by an OCPD lelate to the sattn ofan instailation
the safety due to continuiry of service, ifneeded (i.e. to restrict discomrection to the taulty circuil in case of
overcurrent or thult to earlil).
Selectivity between electrical devices provides continuity of seNice and thus avoids dargers lilked to the loss of
supply of speciflc cilcuits.
As3.2 Parameters
The panleters lbr the corect co-ot'dination between electrical devices rtay be:
- design cufl'ent
prospective shoft-cit'cuit or l'ault current
operating timc of devices
system voltage
energy (tet-through lrt values)
peak let-through current.
TabteA53.2 shows the types ofcombinatiot ofdevices and cells to show how various tnodes ofco-ordination can
aft'ect safety.
\o
\o
\o
\o
Table 453.2 - Device co-ordination in a LV electrical installation
536.4. L3
Selectivity
536.,1. r.1 Between RCDs Yes
Sclcctivjty il1 casc ofoverload is vclificd by the con.rparison oftime/curert chamcteristics ofthe devices involved'
The naximum operating tirne of the device on the load side must be lower than the non{dpping tine
of the
in both the time and cunent axes provides
circuit-bteakel loi any ove oad currcnt. Separ-ation ofthe characteristics
seleclive opcraliol1 i0 this zonc.
sicle. Fuses to BS EN 60269-2 of the same utilization category (e.g. type gG) with rated curent
of l6 A and above
u.ill proviclc total selectivity ifthe ratio ofthe lated cunents is 1.6:1 or gleatel sepalation ofthe characteristics in
borh the time and current axes provides selective operation in this zone'
190
A53.7 Between circuit-breakers
Generally, reference should be n.rade to the manufacturers'docunentalion.
In principle, selectivity is assured up to the fault current level at which the peak current lerthough ofthe downstrean
ciriuit-bieaker is less than the peak value conesponding to the instantaneous tripping ler el ofthe upstream cjrcuit-
breaker. Where the upstream circuit-breaker has dedicated selective behai iour. lhe selectility lilrit might be higher.
Selectivity ilr case of shofi-citcuit is verilied by comparison of thc I:t values. The maximrur operating Irt value of
the fuse on tlte load side should be lower than the minimum pre-arcing []t value ofthe t'use on the supply side. Fuses
to BS EN 60269-1 of the same utilization categoly (e.g. type gG) with rated curett of l6 A and above will provide
total selectivity if the mtio ofthl3 rated currents is 1.6:1 or greater.
Data for peak values of fuses should be taken from the relevant standard or the manufacturers' documentation. If
data is taken 1ioru the lnanufactulet. this should be stated in the documentation olthe installation.
rd
Figure A53.'l - Possible fault currents in systems with semiconductors
Circuii diagram with fauh Shape of oad cuffent /L Shape of earlh fau I c!rent /F
RCD lripp ng
1 AC, A, F. B
2 AC. A. F. B
L1
L2
L3
3 lingle
bridge A,F.B
Circuil diagram wilh iault Shape of oad .!(ent /L Shape of earih fau l curent /F
RCD t pp ng
L
N
PE
L1
L2
L3
N
PE
L1
t2
N
PE
8 B
L1
L2
L3
N
PE
9 B
L1
t2
L3
N
PE
192
CHAPTER 54
EARTHING ARRANGEM ENTS AN D PROTECTIVE CON DUCTORS
CONTENTS
541 GENERAL
542 EARTHING ARRANGEMENTS
542.1 General requiremenls
542.1.2 Supply arrangements
542.1.3 lnstallation earthing arrangements
542.2 Earth electrodes
542.3 Earthing conductors
542.4 Main earthing terminals or bars
543 PROTECTIVE CONDUCTORS
543.1 Cross-sectional areas
543.2 Types of protective conductor
543.3 Preservation of electrical continuity of protective conductors
543.4 Combined protective and neutral (PEN) conductors
543.5 Earthing arrangements for combined protective and functional purposes
543.6 Earthing arrangements for protective purposes
543.7 Earthing requirements for the installation of equipment having high protective conductor
cuffents
543.7.'l General
543.7 .2 Socket-outlet final circuits
544 PROTECTIVE BONDING CONDUCTORS
544.1 Main protective bonding conductors
544.2 Supplementary bonding conductors
'193
CHAPTER 54
541 .2 Thc earthirg systern ofan installation may be subdivided, in which case each parl thus divided shall
conply with the reqLLitements ol tltis chapter
541 .3 Where there is also a lightning protection system, reference shall be made to BS EN 62305'
S4Z-1.201 The maill eafthjng teminal sha]l be connected with Eatlh by one of the methods described in
Regulations 542. .2. I to 542.1 .2.3 , as appropriate to the type of system ol which the installation is to
1
fom a pafi
and in corrpliarce with Regulations 542. I .3. I and 542. I .3.2.
NOTE: Reter to Pafi 2 and Appcrdix 9 lbr dellnitions ofsysten]s
542.1.2 Supplyarrangements
542.1.2-,1 For a TN-S system, rneans shall be provided for the main eatlhing terninal ofthe installation to be
colnectecl to the eafihed poillt ol the source of energy. Pafi of the connectiol rnay be fotmed by the distributor's
lires alld equipmerl.
542.1.2-2 TN,C-S systerr, wherc prcrective multipie earthilrg is ptovided, means shall be providcd lbr the
For a
main eafthing terminal oltlre installation to be connected by the distributol to the neutral ofthe source ofenergy'
For.a TT or IT systenl, the main eafthing temiual shall be connected via an eafthing conductor to
an
542.1-2.3
earth electrode corrplying with Regulation 542.2
542.1.2.4 Whcr.e the supply to an ilstallation is at high voltage, protection against faults between the high
voltage supply and earth shall be provided in accordalce with Section 442
542.1-3 lnstallationearthingarrangements
542/1.3.1 The earthing arangements slla1L be such that:
(i) the value of impeclance from the consrnner''s main earthing terminal to the earthed poil1t ofthe suppty tbr TN
systens" or Earlh tbr TT and tT systens, is in accordance with the protective and functional requirements
1()
S4Z-,1.3.2 plecautions shall be taken against the risk ofdamage to other rrctallic pafts through electlolysis.
542.1.3,3 Where a lumber of installations have separate eafthing arrangernents. any protective conducto$
to flow
conunou to aury of these installatiols shall eithel be capable of carrying the rnaxillnm fault cu[ent )ikely
through rhem or be ear.thecl withiD one installatiofl olly and insulated t'rom the eatlhilg an'angements of a1ly other
instaliation. I11 thc latter circumstances, if the plotective conductor fonls part ofa cable, the protective conductot
shall bc earthecl only in the installation containing the associated protectivc device
542.2.3 Where foundation earth electrodcs are installed. the materials and dinrensions ofthe earlh electrodes
shall be selected to withstand corrosion and to have adequate mechanical strength.
NOTE: lfa lighhiDg protection system (LPS) is present. BS EN 62305-l applies.
542.2.4 The type and embedded depth ofan earrh electrode shall be such that soil drying and freezing will
not increase its resistance above the required value.
rl 542.2.5 The usc. as al eatl}t electrode, ofthe lead sheath or other metal covering ofa cable shall be subject
to all ofthe following conditions:
(i) Adequate precar.rtions shall be taken to prcvent excessive deterioration by corrosion
(ii) The sheath or covering shall be in cft'ective contact with Earth
(iii) The consent ofthe ouner ofthe cable shall be obtained
(iv) Auangements shall exist fot the owner ofthe electrical installation to be wamed ofany proposed change to
the cable which rnight aft'ect its suitability as an eartlr electrode.
542.2.6 A metallic pipe for gases or flan.rmable liquids shall not be used as an earth electrode. The metallic
pipe ofa water utility supply shall not be used as an earth electrode. Other rnetallic water supply pipework shall not
be used as an earth electrode unless precautions are taken against its removal and it has been considered for such a use.
542.2.7 Ar carth electrode shall not consist ofa metal object immersed in water
542.2.8 Wherc an eanh electrode consists ofparts that mustbe connected together, connections shall be made
by rveldiug, pressule connectoN, c]amps or other stlitable mechanical connectors.
50 mnl: steel
542.3.2 The connectiol'l of an earthing conductor to an earth electrode or otlret means of earthing shall
--:nlge be soundly rlade and be electrically and mechanically satisfactory. and labelled in accordance with Regulation
s14.13.1(i). It shrll be suitahlr protccted aeainsl corro\ior. li
I
542.4 Main earthing terminals or bars
542.4.1 h eren installation a main earthi g rel.util1al shall be provided 10 connect the lbllowing to the
eafihing conductor:
(i) The cilcuit protective corlductols
(ii) The protective bonding conductols
(iii) Functionalearthingconductors(ifrequiled)
(iv) Lightnirg protection systern bondir)g cordLrclor. if any (see Rcguiatiorl 4l1.3.1.2).
542,4.2 To thcilitate rneasule[e|t oftlie fcsislancc ot the eafil]ing alrangements, nlealrs shall be provided in
an accessible position tbr alisconnecting the eafi[ring conductor'. Such means may conveniently be cornbined with
the main earthilg ternrinal or bar'. Any joint shall be capable of discorulection orrly by means ola tool.
Calculation in accoldance with Regulation 543. LJ is necessary iltlre choice olcross-sectional area olline conductors
has been dcteuined by consitlerations of shorrcircLrit cuu'ent and if the eath lhult cunent is expected to be less
thar the short-circr.rit curlelrt.
the cross-sectional area shall be oot less than 2.5 [un] copper equivalent ifprotection agairst rnechanical damage
is provided, ard 4 Drrur copper equivalcnt il'nrcchanical p|oteclioI is not plovided (see also Regulation 54i.3.I ).
For a protective conductor Lruried in the ground Rcguiation 542.1.1 fbr earthing conductors also applies. The cross-
sectional area of a protective bot]dillg co[dLrctol sha]l cornply with Section 544.
543,1.2 Where a protective conductol is comrlon to two ol mole cilcLlits. its closs-sectional arca shall be:
(i) calculated i[ accordalce with RcgulatioD 5u13, 1.3 fbl the r)rost onerous of the values of 1aLilt cunent alld
operating time encountered in each of the valior-ts circuits. ot'
(ii) selected in accodance with Rcgulntion 543.1,4 so as to correspond to the closs-sectiolal area ofthe Iargest
lire cordirclor ol'the cir(uil:.
543,1.3 The cross-sectional alea. whete calculated, sliall be not less than tlre valuc dctcrnined by the
followirg lbnlrula or shall be obtained by rel'er:ence to tsS 7454r
S: il{k
NOTE: Tltis equatio[ is aD adiabatic cquatioo .rntl rs applicable fbr disconneciion times not exceeding 5s.
where:
S ofthe corductol in nrml
is the nominal cross-sectiooal area
I is the value in amperes (rus tbr AC) of fault culrert lbr a thult ol negligible impeda[ce, which can
flow through the associatecl protective device- due account being taken of the cufferrt ]inliting elTect
ofthe circuit ill1pedances and tlre linriting capabi]it] (lrt) olthat protective device
t ofthe protective device in seconds corresponding to the t'ault cu el'rt I anperes
is the operating tilr're
k is a factor taking accoult oftl]e resistivity. teurpelatule coeflicient and heat capacity olthc conductor
lnaterial, and the appropriate initial and linal lenrperatrLres.
196
\hlues of k ior pr.rre.-rir e conductors in \ aliolls use or j-i.l
service are as given ln Tiibl.. 10 6. The vaiues are based
on d1c initial and final tempcralures indicated in each
table.
\\ here the applicatiotl ofthe formula produces a non-standard
size. a conrluclrrr harinr a larger. starldard closs-
iectionai area shall be used
TABLE 54.2 _
values of k for insulated protective conduclor not incorporated
in a cable and not bunched with cables,
or for seperate bare protective conductor in contact wiih
Jr" but not bunched with cables,
"ou"rinq
where the assumed initial temperature is 30 "C
TABLE 54.3
Values of k for protective conductor incorporated in a
-
cable or bunched with cables,
where the assumed initial temperature is 70.C or greater
Insulation material
\latcrial ol conductor
70 "c 90 .c 90.(
thermoplastic tl'rel.lnoplastjc thcfirosetting
L opp.'r' i t5/103'l 100/86* i43
llunrinium 76t68* 66!57* 94
lisuurcd initial tcnlperaturc .c
"c
70 90.(' 90
: rnal lenrrT er'anrre
160.C/t40.c* 160'C/140.C* 250 .C
* \bove 300 mm-l
TABLE 54.4 -
Values of k for for the sheath or armour of a cable as the protective
conductor
Insulatiolt l'natc.ial
\hr!'r'ial of conduclor
70 "c 90 .(' 90 "c
thennoplastic the]]noplastic thelntosellinc
-{lumtnlum 9i 85 85
Sreel
5t 46 16
Lead )6 23 23
\ssumcd iuitial tclrperaturc 60.c 80'c 80 "c
Final tcrnperatur-c 200 .c 200 "c 200.c
TABLE 54.5 -
Values of k for steel conduit, ducting and trunking as the protective
conductor
Irsulation nlatcrial
laterial olprotcctivc conductor
70 'c 90 "c 90.c
thermopiastic thermoplastic 1l'r!'rnroseltinq
: :-. ronduit. du!^ling and tr 47 ,+.1
5S
. - .:neLl tnitial lentpc ltuae .c
50 "c 60 60.c
:Clllocrlhr|i: 160 "C t60.c 250.C
TABLE 54.6 -
Values of k for bare conductor where there is
no risk of damage to any neighbouring material by the temperature indicated
NOTE: The telnpemtures indicated are valid only where they do not impair the quality ofthe connectioDs.
Conditiol1s
Material ofcotduclot Visible and in Normal conditions Fic risk
lcstl-ic1ed areas
543.1.4 Whele it is desired not to calculate the minimum cross-sectional area of a protective conductor in
accordance with Regulatir:n 543. L3, the cross-sectional area rnay be detennined in accordance with Table 54.7.
Where the application of Table 54.7 produces a non-standard size, a conductor having a larger standard cross-
sectional area shall be used.
. TABLE 54.7 -
Minimum cross-sectional area of protective conductor
in relation to the cross-sectional area of associated line conductor
s< 16
t6<s<35
s>35
where:
kl is the value of k lbr the line conductor, selected from Table 43.1 in Chapter 43 according to the
materials ofboth cor'rductor and insulation.
k, is the vaiue ofk lbl the protective conductor', selected fl'onr lables 54.2 to 54.6, as applicablc.
1qR
543.2 Types of protective conductor
one or nlore of th' tbiilr$ ing:
543.2,1 A protective conductor ma"v col]sist of
(i) A single-cote cable
(ii) A corductot in a cable
\a-ith insulated live conductors
(iii) An insulated or bare conductor in a common ellclosurc
(iv) Aiixed bare or insulated conducto
or amotu ing of a cable
(v) A nletai coYering, tbr exanrple' tile sheath' screen continuous suppofi
other encloswe or electrically
(vi) A rnetai conduit' metaliic cable managei'nent systelr ol
sYstem for condLlctors
543 2 6
(vii) an extaneous-conductive-pafi complying rvith Regulation
or controlgear assembly or busbar
enclosute ot frame of a lorv voltage switchgear
543,2.2 Whete a metal
truoking systefl is r.,,"d u' u p'ottci'i
t-0"*t' ii shall satisfy the.following three requirements: such a way as
in
construction or by suitable connection'
(i) Its electrical continuity shall be assured' eitherorbyelectrochcmical deterioration
to bc plotectcd agai"tt t"tf.'u'itui "f''trlical
(ii)Itscross-sectionalateashailbeatleastequaltotlratresultingfromtheapplicationofRegulation543.l,or
series
*i,f., ifr. apiropriate part ofBS EN 61439
verified by test in a..orOun"" tap-offpoint'
irr protective conducto$ at eveq/ predetemined
(iii)It shall pemlit the connection ofother
wires or other flexible metallic
pafis' or
oil pipe' flexible ol ptiable conduit' support
.l 543.2.3 A gas pipe, an
iti ,r",r*r service, shall not be selected
as a protective conductor'
constructional parts ,uu1..t to nr.Jilunl.'ut^.ir*r
543 2 1 and of cross-
described in items (i) to (iv) of Regulation
543.2.4 A protective conductor of the type s
be ofcoppet'
sectional arca [0 mtnr or less' shall
of a cable' in particular the sheath of
a
sheath ffare
543.2.5 Thc metal covering including the 1111r,*1ated'
purposes and metal conduit, may be used as a protectlve
,nineral insulated caur", t*nting iJ
Jrrcti,ig fol
"le"tri"al (ii) of Regulation 543 2.2'
corductor fbr the asro"iur.a .o.uir.irl;,
,"ii!n", u*r,, *orirernents of items 1i) and
extlaneous-conductive-pafi may
be used as a
prohibited by Regulation 54323':n
543.2.6 Except as
the follorving requitemerts:
ii"l"",ir. .""ar""r'if it s;tisflcs all connection' in such a way as to
assured' cither by construction or by suit:ble
(i) Electrical contrnuity shall be
be protccted agalnst
t}'"tical or electrociremical dcterioration
'"tt.'initut'
(ii)Thecross-Sectionata,.a,hullb"utleastequaltothatresultillgflolntheapplicationofRegulation54].1.1
its removal
shall be taken againsl
(iii) Unless compelsatory measures aIe providecl' precautiolls
suitably adapted'
(iu) t, hu. b..n aotsidered for such a ttse and' iflecessary'
tntnking or ducting or the metal sheath
plotective conductor is lbrmed by metal conduit'
543.2.7 Where the
ol each accessory shall be connected by
a separate protectlve
tenniral
a'd,,or amor,rr of a cable. tlre ."rtr.,irg
in the lssociated box or other enclosure'
conductot to atl eartf i"g t"'-l'ittoi intoiorated
I
543.3.201 A protective conductor havrlg a cross-sectiorlal area Llp to and including 6 rnurr shall be protected
throughout by a cove|ing at leasl equivalcut to that plovided by the insulation of a single cole rron-sheathed cable
ofappropriate size having a voltage latirlg ofat least 450/750 \2. except lbr the lbllowing:
(i) A protectiv(] conductor forning parl of a nlultiool e cable
(ii) A netal couduit. metallic cable malagenrert systelD or other elclosure or electrically co[tir]uous supporl
systerr tbr conductols. rvlrere lsecl rs a protective conductol.
Whele the sheath of a cablc' incorporatilg alt rurirtsirlated prolcctive corlductor of cross-sectional alea up to atrd
including 6 urnr is reuroved adjacent to.joiuts and ternilations. the protective colductol shall be pr-otected by
insulating sleeving complying with BS EN 60684 selies.
Switchilg devices provided in accordance with (i). (ii), (iii) and (iv) shall meet the requirerreuts olChapter 46 and
Section 537 fol a device tbr isolation.
Joints for test purposes that can be discoruected o11ly by the use ofa tool rray be insefied in a proteqtive conductor.
543"3,4 Where electrical eartll rnonitoring is used. rur dedicated devices (e.9. operatitrg sensors. coils) shall
be connected in series \\,ilh tlle protective cotductor (see BS 4444).
543.3.5 An exposed-conductive-part of eqLripment shall 1lot be used to lbrm a protectivc conductor fol other
equipment except as provided by Regulations 543.2.I . 543.2.2 and 543.2.5.
543,4,4 The outer conductor of a concentric cable shall rot be coluron to nrore than one cilcuit. This
requirernent does not preclude the use ola trviu or nulticr-rre cable to sel've a nu[]ber ofpoints contained withiu one
final circuit.
543.4.5 The conductance ofthe outer conductor ot a concentric cable (fleasuled at a ten]pelatue of20 "C) shall:
(i) for a single-corc cable. be not less thal that ofthe intenul conductor
(ii) fbr a multicore cable serving a r:urnber of points cortained withirr one linal circuit or having the intemal
conductors connected in parallel. bc no1 lcss than that ol the internal conductors connected in parallel.
200
543.4.6 At er er.l ioint ir't tl'te outcr conductor ola conccntt:; - -::.: 'il a rcrmination. the continuiq of
'-:--
by'' a conductot additional
lhat.joint shall be su1'rpletnented to an\ r'11.',:-' .':.: :.rr sealing arrd clalrping tl]e oritel'
corlductor. The corductatrce ofthe additiorlal conductot shall be noi l:., : .; specilied in Regulatiott 543.4.5
tin thc outer colductol.
543.4.7 No means ofisolatiol.t or switching shall be inserted in the outer conductor of a concentric cable.
543.4.8 Excepting a cable to BS EN 60702-1 installed in accordance \\'ith th!' manuthctlrer's instructiol]s.
the pEN conductor olevery cable shall be insulated or have ar insulating cor cring .uitable ibr the highest voltage
to which it uray be subjected.
I
543.4.201 For a fixed installation. aconductor ofa cabte not subject to flexing and har ing a cross-sectional area
not less than l0 mrrr lor copper or l6 mmr for aluminium may serve as a PEN conductor pro\ ided thal the part of
the installation concemed is not supplied through an RCD.
I 543,7.1.20'l Equipmcnt having a protective conductor curent exceeding 3.5 lllA bul l'Iot exceeding 10 mA- shall
bc L'ither penranently connected to the fixed wifitlg ofthe installation \\,itl']out the use ofa plug and socket-outlet
60309-2'
or
connccted by Ineans ofa plug and sockeloutlet complying with BS EN
543,7,1.202 Equiprrent having a plotcclivc conductol. current exceeding l0 rrA shall be collectcd to the supply
bl one olthc following tnethods:
(i) permal1ently corrnected to the wiring ofthe installation, with the protectivc colductor selected in accordancc
with Rcgulation 543.7.1 .203. The pemanent connection to the wiling lnay be by nrcans of a flexiblc cable
1ii) A flexible cablc wilh a plug and socket-outlet conplying with BS EN 60309-2. provided that either:
(a) the protective conductor ofthe associated flexible cable is ofa cross-sectional aleit not less than 2.5rrmr
for plugs rated at 16 A and llot less tllan 4 mmr fot plugs t'ated ah()vc l6 A- ot
(b) the protective conductor olthe associated flexible cable is of a cross-scctioltal area not less than that of
The lir're conductor
(iii) A protective conductor complying with Section 543 with an eadh lnonitoring system to BS 4444 installed
which, in the eYent ola continLrity 1ault occurring i1,] the plotective colductor. auto)natically disconnects d]e
supply to the equiPmert.
543.7.1.203 The rviring of every final circuit ard distribution circuit irtended to supply one or |nore items of
:quipment. such that the lotal protective conductor cunent is likely to excced l0 lnA. shall have a high inregrity
t' :iorective corlnection complying with o:re'or more ofthe lollowing:
(i) A sirgle protective condlLctol'having a cross-sectiolal area ofnot less tlran l0 tnn2. complying with the
requirerrents ofRegulations 543 2 and 543.3
i ii) A single copper protective conductol. having a ctoss-sectional area of not less than 4 tnmr. complyitlg
with ii,c r.equi.ements ofRegulations 543.2 and 543.3, the plotective conductor being enclosed to provide
additional protection against uechanical damage, for example. within a flexible conduit
iii) Two ildividual plotective conductols, each complying with the requiletnellts of section 543. The two
pr.otective conductors may bc ofditlerent types, e.g. a lnetal conduit togethel with an additional conductol'
of a cable enclosed in tlle same colduii.
.,.rire the two indivirtual protective conductors are both incoryorated in a uulticole cable. the total cross-sectioDal
l0 1nlr1r. One of the prote.'tivc
---'l of all the conducton including thc'live conductors shall be not less than
wire braid sclecn incorporatid in the const:uction of
- :,luctors may be fbrmed by th.,',',.tullia sheath, annour or
-. iable and couplying r,vith Regulation 5'13.2.5
201
(iv) An eafih monitoling systelr to BS 4444 may be installed which, in theeventofa continuity fault occurring
ilt the protective couductol, automatically disconnects the supply to the equipment
(v) Connection ofthe equipDrert to the supply by means ofa double-wound transformer ol equivalent unit, such
as a motor-altenator set. the prctective conductor ofthe illcoming supply being connected to the exposed-
condlLctive-parts ofthe equiprnent and fo a point ofthe secondary winding ofthe h?nsfoflner ol equivalent
device. The protecrive conductor(s) between the equipmeflt and the tr-anstbrmer or equivalent device shall
comply with one ofrhe an'argemerts described in (i) to (iv) above.
543,7,1,204 Where two protective conductors are used in accordance with Regulation 543.7.1.203(iii), the ends
ofthe protective conductors shall be terminated independently ofeach other at all connection poillts throughout the
circuit. e.g. the distlibution board, julction boxes and socket-outlets. This requires an accessory to be provided with
two sepamte carth teminals.
543.7.1-205 At the distribution boald inibmation shall be provided indicating those circuits having a high
protcctive conductor curent. This informatjon shall be positioned so as to be visible to a person who is modifying
or extendiug the circuit.
543.7 .2 Socket-outlet final circuits
543.7.2.201 For a tinal circuit with a number of socket-outlets or connection units intended to supply two or
nore items ofequipment, where it is know1l or reasonably to be expected that the total plotective conductor current
in uonnal service will exceed l0 urA. the circuit shall be provided with a high integrity protective conductor
courrection con'rplying with the requirements ofRegulation 543.7.1. The ibllowing arangements ofthe final circuit
are acceptable:
(i) A rfug final circuit with a ring protective conductor Spurs, if provided, require high integrity protective
conductor corulectiots complying with the requirements of Regulation 543.7.1
1ii) A radial final circLdt with a single protective conductol':
(a) the protective corductor being connected as a ring, or
(b) a separate protective conductor being provided at the final socket-outlet by connectiot'r to the netal
conduit ol ducting. or
(c) where two or moLe sinilar radial circuits supply socket-outlets i[ adjacent areas and are fed fiom thc
same distribution board, have identical means of short-circuit and overcurrelt protection and circuit
protective conductoLs of the same cross-sectional area, then a second protective conductor may be
provided at the final socket-outlet on one circuit by comection to the plotective conductor ofthe adjacent
cilcuit
(iii) Other circuits complyirg raitJr dre requirements of Regulation 543.7.1.
Except tbl highway power supplies and street funiture, where PME conditions apply the main protective bonding
conductor shall be selected in accordance with the PEN conductor ofthe supply and Table 54.8.
Where an ilstallation has lnore than one source ofsupply to which PME conditions apply, a main protective bonding
conductol shall be selected accor-ding to the largest PEN conductor ofthe supply.
202
TABLE 54.8 -
Minimum cross-sectional area of the main protectjve bonding conductor
in relation to the PEN conductor of the supply
Local distributor's lll]tlvork conditions may r-equie a largcr conducir,i
Copper equivalent cross-sectional ar.ea ofthe PEN Minimunr copper equir alent* cross-sectional area
conductor olthe main bonding conductor
35 mmr or less 10 mml
over 35 mmr up to 50 nrmr I 6 n.rm:
ovel 50 mnl] up to 95 mlnl 25 mrnl
over 95 mmr up to 150 mml 35 mn-rr
over 150 runl 50 mt'r:
* The l't'liniu'tuu copper equivalelt closs-sectional area is given by a copper bonding conductor ofthe tabulated
cross-scctioral arca or a bonding conductor ofanother metal affor.ding equivalent conductance.
544.'1.2 Tlre main protective bonding couection to any extraneous-conductive-paft such as gas, water or I
.:, othcr metallic pipework or service shall be rnade as near as practicable to the point of eDtry of that part into the
I
:_.1 premises. Where there is a meter, isoJation point or urion, the connection shall be made to the consumer's hard metal
I
!'f pipework and befote any branch pipework. Wherc pmcticable the connection shall be made within 600 mm ofthe
-.ll meter outlet union or at the point of enn), to the building ifthe meter is exterual.
544,2 Supplementarybondingconductors
544.2'1 A supplementary bonding conductor connecting two exposed-conductive-parts shalt have
a conductance, if sheathed ot otherwisc provided with mechanical protection, not less than that of the smaller
protective colductor connected to the exposed-conductive-parts. Ifmechanical protection is not provided, its cross-
sectional area shall be not less than ,1 mmr.
iiirl
544.2.2 A supplementaty bonding conductor connecting an exposed-conductive-pa1t to an exfaneous-
conductive-paft shall have a conductance, if sheathed or otherwise provided with mechanical protection, not less
ihe thal halfthat ofthe protective conductor conlrected to tlre exposcd-conductive-part. Ifmechanical protection is not
:;uit provided. its cross-sectional alea shall be uot less than 4 mmr.
: tre
raL'l]t 544.2.3 A supplelnentary bonding conductor connecting two extraneous-conductive-parts shall have a cross-
sectional area r'tot less tha[ 2.5 rnmr if sheathed or otherwise provided with mechanical protection or 4 nm, if
rrechanical protection is not provided, except that where one ofthe extraneous-conductive-pafts is connected to an
exposed-conductive-par1 ir colnpliance with Regulation 544.2.2. tl1at regulation shall apply also to the condrLctor
connecting the two c\ tra neous-conJ uc rive-pa m..
544.2.4 Except where Regr"rlation 544.2.5 applies, supplementary bonding shall be provided by a
supplementary cotlductor, a conductive part ofa pennalrent and reliable nature, or by a conrbination ofthese.
croSs-
n and 544'2.5 Where supplenrentary bonding is to be applied to a ilxed appliance which is supplied via a shorl
,.r or a length of flexible cable iiom an adjacent connection unit or other accessory, incorporating a flex outlet, the circuit
protective conductor within the flexible cablc shall be dcemed to provide the suppleme[tary bonding connection to
the exposed-conductive-pafis ofthe appliance. fiom the earthing terminal in the connection unit or other accessory.
L iLiing
CHAPTER 55
OTHER EQUIPMENT
CONTENTS
550.1 Scope
551 LOW VOLTAGE GENERATING SETS
551 .1 Scope
551 .2 General requirements
551.3 Protective measure: Extra-low voltage provided by SELV or PELV
c5 t .J. I Additional requirements for SELV and PELV
551.4 Fault protection
551.4.3 Protection by automatic disconnection of supply
551.4.4 Additional requirements for protection by automatic disconnection where
551.5 Protection against overcurreni
551.6 Additional requirements for installations where...
551 .7 Additional requirements for installations where...
551.8 Requirements for installations incorporaiing stationary batteries
552 ROTATING MACHINES
552.1 Rotating machines
553 ACCESSORIES
553.1 Plugs and socket-outlets
553.2 Cable couplers
554 CURRENT.USING EQUIPMENT
554.1 Electrode water heaters and boilers
554.2 Heaters for liquids or other substances having immersed heating elements
554.3 Water heaters having immersed and uninsulated heating elements
554.4 Heating conductors and cables
555 TRANSFORMERS
555.1 Autotransformers and step-up transformers
557 AUXILIARY CIRCUITS
557 .1 Scope
557 .3 Requirements for auxiliary circuits
557.3.1 General
557.3.201 Control circuits
557.3.2 Power supply for auxiliary circuits dependent on the main circuit
557.3.3 Auxiliary circuit supplied by an independent source
557.3.4 Auxiliary circuits with or without connection to earth
Power supplies for auxiliary circuits
557.3.6 Protective measures
557 .4 Characteristics of cables and conductors
557 .4.1 lvlinimum cross-sectional areas
Requirements for auxiliary circuits used for measurement
557.5.1 General
557.5.2 Auxiliary circuits for direct measurement of electrical quantiiies
557.5.3 Auxiliary circuits for measurement of electrical quantities via a transformer
557 .6 Functional considerations
557.6.1 Voltage supply
557 .6.2 Quality of signals depending on the cable characteristics
557.6.3 Measures to avoid the loss of functionality
557 .6.4 Current-limiting signal outputs
557.6.5 Connection to the main circuit
L-=-
557.6.6 Plug-in connections
551.1 Scope
This scction applies to low voltage and extra-low vo)tage installations which incorporate generating sets i[tended to
supply, either continuously or occasionally, all or part ofthe installation. Reqr.rirements are included 1br installations
with the following supply affargernerlts:
(i) Supply to an installatiol which is not conltected to a system for dist bution ofelectlicity to the public
(ii) Supply to an iustallation as an altemative to a system for distribution ofelectricity to the public
(iii) Supply to ao instaliation in palallel with a system for distributiou ofeleotricity to the public
(iv) Appropriate conbirrations ofthe above.
This section does not apply to sell'-contained items of extralow voltage electrical equiprnent which incorporate
both the source of erergy aud the e[ergy-using load and for which a specific product standard exists that includes
thc lequrreurenl. lbl elcctrrtal saletl.
NOTE: Whcre a gcncratiDg set with an output not exceedirg l6 A is to be connected in parallelwith a system fot distribution
ol electiicity to the public. procedures for infoflning the electricity distributor are given in the Electricity Sattty,
Quality and Continuity Rcgulations (ESQCR). tn addition to the ESQCR requirements, where a gelerating set with
an outpui cxceeding 16 A is to be connected in parallel with a system for distribution of electricity to the public,
requir-eDrents of the electricity distributor should be ascertained beforc thc generating set is connected. Requirernents
ofthe dishibutor for thc conncction ofunits ratcd up to 16 A are given in BS EN 50,138.
551.1.1 Generating sets with the fbllowing power sources are considered:
(i) Cornbustiolengines
(ii) Turbines
(iii) Electric Dotors
(iv) Photovoltaiccells
(v) Electrochemicalaccurnulato$
(vi) Other suitable sources.
551.1,2 Generating sets with the following electdcal chamcteristics are considered:
(i) Mains-excited and separatcly excited synclnonous generators
(ii) Mains-excited and self-excited asynchronous generators
(iii) Mains-commutated and sell'-conmutated static convefiors with or without bypass facilities.
551.1.3 The use of generating sets for the following purposes is considered:
(i) Supply to penlanent installations
{iit Supply lo tcnrporaq installations
(iii) Supply to mobile equiplnent which is not cornected to a permanert fixed installation
(iv) Supply to mobile units (Section 717 also applies).
551.2 General requirements
55'1,2,1 The means ofexcitation and commutation shall be appropriate for the intended use ofthe generating
set and thc salety and proper functioning of other sources of supply shall not be impaired by the generating set.
-lhe
551,2.2 prospective shofi-circuit cuuent and prospective eadh fault curent shall be assessed for each
source ofsupply or coflrbinatiorr ofsources which can operate independently ofother soulces ol combinations. The
shot-circuit mting of protective devices within the installatior.r and, where appropriate, connepted to a systen fot'
distribution ol electdcity to the prrblic, shall not be exceeded for any of the intended nethods of operation of the
sources.
206
551,2,3 Where the genercting set is intended to provide a suppl) Io an installaiion \\hich is not connected to
a systeln fordisi butiol of elcctt'icity to the public or to pl ovide a supp1l as a s"r :t;hed altemati\ e to such a system,
the capacity arld opemting characteristics of the generating set shall be .ucl ihri i:rger or darrage to equipment
cloes l-Iot arise aficr the couection or disconnectiolr of any intended load a. a re.u]i tiihe deriation ofthe voltage
or frequency frorn the intended operating range. Mears shall be prorided io automaiicall\ disconnect such pafts of
the installation as may be necessaly ifthe capacity ofthe generating sel i5 erceeded.
NOTE 1: Consicler.ation shoulcl be given to the intended duty cycle arld size ol indi\ iduai ;o:,r:cr:d loads as a proponion ofihe
capacity olthe generating set and to the startng cllamctelistics ofan\ conneci.d elsa:ic nlotors.
NOTE 2: Considelation slrould bc given to thc power f'actor speciied tbr protecti\ e de\ i..s ::r th. inslallation.
NOTE 3: The installalion ofa genemtil1g set rvithin an existing building or installation me. ;hange the conditioDs olextemal
inllucnce for-the installatior (see Part 3). for e\ample by the irltroduction ol Ino\ ing prni. parts at high te perature
or by the prescrce offlan rable fluids alrd noxious gascs. etc.
551 ,2,4 ision for isolation shall rneet tlre requir ernents of Chapter
Pr.ov .16 and Section 5 i 7 for each source or
combination of sources of supply.
Whete a SELV or PELV system may be supplied by more than one source, the requirements of Regulation '114.3
shall apply to each source. wlrere one or rnore of the sources is earthed, the requirements for PELV systenls in
Regulation 414.4 shall apply.
t If one or more of the sources does t'tot meet the requirerrents of Regulation 414.3, the system shall be treated as a
I
FELV system ard thc requiremcnts ofRegulation 411.7 shall apply.
I
.ll I
551.3.2 Whcre it is necessary to lnaintain thc supply to an extralow voltage system following the loss of
one or mot.e soLrrces of supply. each source of supply or cornbination of sources of supply which can operate
a.
independently of other sources or combinations shall be capable of supplying the intended load of the extra-low
voltage systen'1. Provisions shall bc rradc so that loss ofthe low voltagc supply to an extra-low voltage soutce does
not lead to dangcr or damage to other cxtra-low voltagc cquipment.
NOTE: Such provisions may bc lecessary in supplies for safety seNices (see Chapter 56).
TIte t'ault protective provisions shall be selected or precautiors shall be taken so that where fault protective provisions
are achieved in different ways within the same installation or pafi ofa[ ilstallation according to the active sources
of supply. no iufluence shall occul ol condjtions a se that could impair the effectiveness of the fault protective
plovisions.
NOTE: This rnight.lbl. example. requile the use ofa lmnsfbnnerproviding electrical separation bet\\'een palls ofthe irrstallalion
usirlg diflerent earthing systerl]s.
551-4.2 The generating set shall be connected so that any provision withir the installalion for protection by
RCDs in accotdance witb Chapter 41 remains effective 1br every intelded combination ofsources ofsupply.
NOTE: Conrlecliorl 01'livc parts ofthe generator u'ith Eallh may affect the protective measule
551.4.3.2 Additional requirements for installations where the generating set provides a
switched altemative to system for distribution ofelectricity to the public (standby systems)
551,4,3.2.1 Protectiol by autolnatic discornection of supply shall not rel] upon Ih. .-..nnection to tfie eanlI.d
point oftlte systenl lbr distr ibution ofelectricity to the public rvhen the gerlerator is optr:Irrg as e :$ itched aitenrriir e
:.. Tire to a TN systern. A suitable means ofearthing shall bc provided.
:.:l lot
: -.i tlre
,a
---
551.4.3.3 Additional requirements for installations incorporating static convertors
551'4.3,3,'l Wherc lault protectiol fot palts of thc installatior supplied by the static converlor relies upon the
aLLtoll]atic closureof the bypass srvitch and the operation of prolective devices on the supply side of thc bypass
switclr is not within the time required by Section 4ll, supplernentary equiporenlial bonding shall be proviclecl
between simultaleor"Lsly accessible exposed-cordrLctive-parts and extmrleous-conduclive-pafis otr the ]oad side of
the static couveflor in accordance rvith Regulatittn 4l 5.2.
The resistance (R) of the supplerlcntary proteclivc bondirg condLrctor- required betwecn simultaneously accessible
cxposed-collductive-parts altd extrancorrs-collducti\.c,l]afis shall f'ulfil the lbllowing condition:
R < 50/t"
where:
I" is the maxilr]uln eafh tlult currelt which can be supplied by the static convertol whelt the
bypass switch is closed.
NOTE: Where such equiprlcnr is intendcd to operute ir parallel wiril a systcrr tbr clistribution ofelectlicity to rhc public. the
requiremenls ofReglLlation 551.7 also a|p1y.
551.4.9.3.2 PrecalLtions shall be taken ot ecluipureut shall be selectecl so that the conect operatiolt olplotective
devices is not impaired by DC cuu-ents gclterared by a static convcfior or by the ptesence of filtcr.s.
551.4.3.3.3 A means ofisolation shall be installed ort both sides ofa static cotrveftor. This requirement does not
apply on the power source side ofa slatic converLor wlrich is intcgrated in the saure enclosul'e as the power source.
This regulation applies to poflable generatitg sets and to gel'rerating sets which are intended ro be tnoved to
unspecified locations 1br tempomry or sllort tcllll use. Such genelatilg sets rray be pafl of an ilstal]atiou which is
subject to sirrilar use. fhis regulation does not appl), to penltatlctll llxed itstallations.
NOTE: For suitablc conncctjon a -aogenenrs see IIS LN 60309
senes.
55'1.4.4.1 Between separate iterns of equrpnrent. protective conductols slrall be provided which are pan of a
suitable cable and which corrply with Table 54.7.
551.5,2 Where a generating set is iDtended to opelatc iu parallel rvith a system tbr distriburion of electricity
to the public, or wltere two or'nore gellcratilg sets ll1ay opctate in palallel, circulating harmonic curents shall be
linited so that the thennal rating ofconductors is rot exceeded.
The effects ofcirculating harmonic cuirents tnay be Iinited by one or morc ofthe fbllowing:
(i) The sclectiol ofgenerating sets with cornpensatcd wirdings
(ii) The provision ofa suirable irrpedance in thc connection to the generator star points
(iii) The plovisior oiswitches which inten'tipt the circulatory circuit but which are interlocked so rhat at all tinles
1'au1t protection is not intpaired
t
(ir flre p[ovisirrrr ol lill(rirc c,lllipr]re
(vt Othel srritable rncarr:.
NOTE: Consideration should bc given to the ntaximum voltase which may bc plodLrced across an irlpedance connected to
linlit circulaling hannonic curel]ls
248
551.6 Additional requirements for installations where the generating set provides a supply
as a switched alternative to the system for distribution of electricity to the public
(standby systems)
551.6.1 Precautions cornplying with the relevant requirements of Chapter 46 and Section 537 for isolation
shall be taken so that the generator camot opemte in parallel with the sysiem for distribution of electricity to the
public. Suitable precautions may include one or more olthe following:
(i) An electrical, mechanical or electromechanical interlock between the operating urechanisms or control
circuits ofthe changeover switching devices
(ii) A system of locks with a single transferable key
(iii) A three-positiqn break-before-make changeover switch
(iv) An automatic changeover switching device with a suitable interlock
(v) Other means providing equivalent security of operation.
551.6.2 For a TN-S system where the neutral is not isolated, any RCD shall be positioned to avoid incorrect
operation due to the existence of any parallel neutral-eardr path.
NOTE: It may be desirable in a TN system to disconnect the neutml ofthe installation front the neutml or PEN ofthe system
for distribution of electricity to the public to avoid disturbances such as induced voltage surges caused by lightning.
551.7 Additional requirements for installations where the generating set may operate in
parallel with other sources including systems for distribution of electricity to the
public
I 551 .7 .1 When a generating set is used as an additional source of supply in pamllel with a[other source, both
olthe following conditions shall be tutfilled:
(i) Protection against thermal effccts in accordance with Chapter 42 and protection against overcurrent in
accordance with Chapter 43 shall remain effective in all situations
I :a
(ii) Where an RCD is providing additional protection in accordance with Regulation 415.1 for a cilcuit
connectilg the generator set to the installation, the RCD shall disconnect all live conductors, including the
neutral conductor.
551.7 .2 A genentirg set used as an additional source of supply in parallel with another source shall be installed;
on the supply side ofall the overcurrent protective devices for the final circuits ofthe installation, or
on the load side olall the overcurent protective devices for a firal circuit ofthe iNtallation, but in this case all the
following additional requirements shall be fullilled:
(i) The conductors ofthe firal circuit shall meet the following requirement:
I.>1,,+ls
where:
[, is the cuffent-carrying capacity ofthe final circuit conductors
I,, is the lated cuffent ofthe protective device ofthe final circuit
Ig is the rated output cufl'ent ofthe generating set
(ir) A generating set shall not be connected to a flnal circuit by mcans ofa plug and socket-outlet
(iii) The line and neutral conductors of the fina1 circuit and ofthe generating set shall not be connected to
Earth
Unless the device providing automatic disconnection ofthe final circuit in accordance with Regulation
411.3.2 disconnects the line and neutral conducto$. it shall be verified that the combination of the
disconnection time ofthe protective device for the final circuit and the time taken for the output voltage
of the generating set to reduce to 50 V or less is not greater than the disconnection time required by
Regulation 4l 1.1.2 lor the final circuit.
-::.'gulationdoesnotapplytoanunintenuptiblepowersupplyprovidedtosupplyspecificitemsofcunent-using
-, .. :ment within the final circuit to which it is connected.
:5'1 .7.3 h selecting and using a gereratirg set to mn in parallel with the systerr lor distibution ofelectricity
: 'e public. care shall be taken to aYoid ad|erse effects 10 that system and to other jnstallations in respect of
.,. ir l'actor, voltage changes, harmonic distotjon. unbalance. stafting, synchronizinu or voltage fluctualion effects.
' iere synchlonization is necessaqr. the use of an alrtolnatic synchronizilg system \\ticlt considers frequency.
- -,.e and voltage is to be prefered.
551.7.4 Means ofautomatic switching shall be provided to disconnect the generating set from the system for
distribution ofelectdcity to the public in the event ofloss ofthat supply or deviation ofthe voltage or frequency at
the supply terminals from declared values.
For a genenting set with an output exceeding 16 A, the type of protection and the sensitivity and operating times
depend upon the protection ofthe system for distribution of electricity to the public and the number of generating
sets connected and sha1l be agreed by the distributor. For a generating set with an output not exceeding 16 A, the
settings shall conply with BS EN 50438.
In the case ol the presence of a static convefor, the meani of switching shall be provided on the load side of the
static convertor
551.7.5 Means shall be provided to prevent the connection ofa generating set to the system for distribution
of electricity to the public in the event of loss ofthat supply or deviation ofthe voltage or frequency at the supply
teminals from values required by Regulation 551.7.4.
NOTE: For a generating set with ail output not exceeding 16 A intended to opemte in parallel with a system for distributiorl of
electlicity to the public the requirements are given in BS EN 50438.
551.7.6 Means shall be provided to enable the generating set to be isolated from the system for distribution
of eleitricity to the public. For a generatingset with an output exceeding 16 A, the accessibility of this means of
isolation shall colnpty with national rules and distribution system operator requirements. For a generating set with
ar output not exceeding 16 A, the accessibility of this means of isolation shall comply with BS EN 50438.
551.7.7 Where a generating set may operate as a switched altemative to the system for distribution of
electricity to the public, the installation shall also comply with Regulation 551.6.
551-8.2 Batteryionnections shal) have basic protection by insulation or enclosutes or shall be arranged so that
two bare conductive pafis having between them a potentiat difference exceeding 120 volts cannot be inadvefiently
touched simultaneously.
552.1.2 Every elect c motor having a rating exceeding 0.37 kW shall be provided with control equipment
incorporating means of protection against overload of the motor This requirement does not apply to a motor
ircorpomted in an item ofcunent-using equipment complying as a whole with an appropdate British or Harmonized
Standard.
552.1.3 Except where failule to startafterab ef intemrption would be likely to cause greater danger, eYery
motor shall be provided with means to prevent automatic rcstarting after a stoppage due to a drop in voltage or
failure of supply, where unexpected restafting ofthe motor might cause danger This requirement does not preclude
arangenents for starting a motor at intervals by an automatic control device, where other adequate precautions are
taken against danger from unexpected restarting.
210
553 ACCESSORIES
553.1.2 Except for SELV or a special circuit frorr Regulation 553.1 .5, every plug and socket-outlet shall be
ofthe non-reversible type, with prcvision for the connection of a protective conductor
553.1.3 Except where Regulation 553.1.5 applies, in a low voltage circuit every plug and socket-outlet shall
rrl confomr with the applicable British Standard listed in Table 55.1.
TABLE 55.1 -
!)1',l
Plugs and socket-outlets for low voltage circuits
..i
nh Type of plug and socket-outlet Applicable British Standard
Fused plugs and shuttcred socket-outlets, BS I363 (tuses to BS 1362)
of 2-po1e and earth, fol AC
Plugs, fused or non-fused, and 2, 5, 15,30 BS 546 (fuses, ifany, to BS 646)
socket-outlets, 2-pole and ealth
and socket-outlets industrial t6,32, 63, 12s BS EN 60309-2
!rns.
553.1.201 Every socket-outlet for household and similar use shall be of the shuttered type and, for an AC
installation, shall preferably be ofa tlpe complying with BS 1363.
553.1.5 A plug and socket-outlet not complying with BS 1363, BS 546 or BS EN 60309-2, may be used in
single-phase AC or two-wire DC circuits operating at a nominal voltage not exceeding 250 volts for:
r that
.3nti-v (i) the connection of an electric clock, provided that the plug and socket-outlet are designed specifically for that
purpose, and that each plug incorporates a fuse of rating not exceeding 3 amperes complying with BS 646
or BS 1362 as appropriate
(ii) the connection of an electric shaver, provided that the socket-outlet is either incorporated in a shaver supply
unit complying with BS EN 61558-2-5 or is a type complying with BS 4573
(iii) a circuit having special characteristics such that danger would otherwise arise or it is necessary to distinguish
the function ofthe circuit.
[rrents
ared in 553,1.6 A socket-outlet on a wall or similar strxcture shall be mounted at a height above the floor or any
rvorking surface to miniurize the risk of mechanical damage to the socket-outlet or to an associated plug and its
nt duty
braking
flexible cable which might be caused during inserlion, use or with&awal ofthe plug.
553.1.7 Where mobile equipment is likely to be used, provision shall be made so that the equipment can
dpment be fed fiom an adjacent and conveniently accessible socket-outlet, taking account of the length of flexible cable
a motor nonnally fitted to poftable appliances and luminaires.
monized 553.2 Cable couplers
553-2.1 Except for a SELV or a Class II circuit, a cable coupler shall comply where appropriate with
Fr. every BS 6991 , BS EN 61535, BS EN 60309-2 or BS EN 60320- l, shall be non-reversible and shall have provision for the
oltage or . orlnection of a prolecli\e conductor.
preclude
rions are 553.2.2 A cable coupler shall be ananged so that the connector ofthe coupler is fitted at the end ofthe cable
remote from the supply.
211
554,'|,.2 The supplr te the clcctrodc watcr hcatcr or electrodc boiler shall bc controllcd by a linkcd
breaker ananged to disconnect the supply from all electrodes simultaneously and provided with an overcurrent
protective device in each conductor feeding an elecrode.
554.1.3 The earthing ofthe electrode water heater or electrode boiler shall comply with the requirements of
Chapter 54 and, in addition, the shell ofthe electrode water l'reater or electrode boiler shall be bonded to the metallic
sheath and armour, if any, ofthe incoming supply cable. The protective conductor shall be connected to the shell of
the electrode water heater or electrode boiler and shall comply with Regulation 543.1.1.
554.1.4 Where an electrode water heatel ot electrode boiler is iirectly connected to a supply at a voltage
exceeding low voltage, the installation shall include an RCD aranged to disconnect the supply tl'om the electodes
on the occurrence of a sustained earth leakage cuffent in excess of 10 % ofthe rated current ofthe electode water
heater or electrode boiler under normal conditions of operation. except that if in any instance a lrigher value is
essential for stability of operation of the electrode water heater or electrode boiler, the value may be increased to a
maximum of 15 %. A tirre delay may be incorporated in the device to prevent ulnecessary operation in the event of
imbalance of short duration.
554.1.5 Where an electrode water heater or electrode boiler is connected to a three-phase low voltage supply,
the shell ofthe electrode water heater or electrode boiler shall be connected to the neutral olthe supply as well as
to the earthing conductor. The current-carrying capacity of the neutral conductor shall be not less than that of the
largest line conductor connected to the equipment.
554.1 .6 Except as provided by Regulation 554. t.7. where the supply to an elechode water heater or electrode
boiler is single-phase and one electrode is connected to a neutral conductor earthed by the distributor, the shell of
the electrode water heater or elecffode boiler shall be connected to the neutral ofthe supply as well as 10 the earthing
conductor
554/1.7 Where the electrode water heater or electrode boiler is not piped to a water supply or in physical
contact with ar.ty earthed metal. and where the electrodes and the water in contact with the electrodes are so shielded
in insulating material that they cannot bc touched while the electrodes are live, a fuse in the Iine conductor may be
substituted for the circuit-breaker required under Regulation 554.1.2 and the shell of the electrode water heater or
electrode boiler need not be connected to the neutral olthe supply.
554.2 Heaters for liquids or other substances having immersed heating elements
554.2.1 Every heater for liquid or other substance shall incorporate or be provided with an aulomatic device
to prevent a dangerous se in temperature.
554.3.2 All metal parts ofthe heater or boiler which are in contact with the water (other than cunenlcarying
pats) shall be solidly and rnetallically connected to a metal water pipe through which the water supply to the heater
or boiler is provided, and that water pipe shall be connected to the main eafihing teminal by means independent of
the circuit protective conductor.
554.3.3 The heater or boiler shall be pennanertly connected to the electdcity supply thr-ough a double-pole
Iinked switch which is either separate from and r,"ithin easy reach ofthe heater or boilel or is incorporated therein,
and the wiring from the heater or boiler shall be connected directly to that switch without the use of a plug and
socket-outlet.
554.3.4 Before a heater or boiler ofthe type relered to in Regulation 554.3.1 is connected, the installer shall
confinn that no single-pole switch, non-linked circuitbreaker or fuse is fitted in the neufal conductor in any patl of
the circuit between the heater or boiler and the origin ofthe irstallation.
554.4.1 Where a )reatirrg cablc is required to pass through, or be il close proximity to. tr.raterial which
prescnts a fire hazard, the cable shallbe enclosed in material having the ignitability charactedstic 'P'as specified in
BS,176-12 and shall be adequately protected from any rnechanical damage reasonably foreseeable during installation
and use.
212
554.4.2 Aheating cable intended for laying directly in soil. concrete. cemenl screed or other material used for
road and buildirg construction shall be:
(i) capable olwithstanding mechanical damage under the conditions that can reasonably be expected to prevail
during its installation, and
ri (ii) constructed of mate al that will be resistant to damage from dampness and/or corosion under normal
i;
conditions of service.
554.4.3 A heating cable laid directly in soil, a road or the structure ofa building shall be installed so that it:
ae
(i) is co[ipletely embedded in the substance it is intended to heat, and
CS (ii) does not suffer damage in the event ofmovement nomally to be expected in it or the substance in whiclt it
:.7 is embedded. and
is (iii) complies in all respects with the manufacturer's instructions and recornmendations.
)a I
..f 554.4.4 The load of every floor-warming cable under operation shall be limited to a value such that the
tnanufacturer's stated colductor temperature is not exceeded. Other factors can limit the maximurn temperature at
rvhich the cable can be run, such as the tempemture rating ofany terminations or accessories, and any material with
,1)..
\\.hich it is in co[tact.
AS
e 555 TRANSFORMERS
557.1 Scope
:' lce
-ltis scction applies to auxiliary circuits, except thosc covcred by specific product or systern staldards. c.g. thc
,.'nstruction ofassemblics ofclcctrical equipment to the approp ate pafl olthc BS EN 61439 series.
:., ing Tbe power supply, AC ot'DC, for an auxiliary circuit may be either dependent or independent ofthe main circuit
:..':ltef .rccording to its required flrnction. Ifthe status ofthe main circuit has to be signalled, then the signalling circuit shall
.::rt of be able to operate independently ofthat main circuit.
.hall
557.3.2 Power supply for auxiliary circuits dependent on the main circuit
of
557.3.2.'l General
-\uxiliaty circuits with a power supply dependent on the main AC circuit sha11 be connected to the main circuit:
ti) directll tsee Figure 55.11. or
(ii) via a rectilier (see Figure 55.2), or
ir hiclt (iii) via a transformer (see Figure 55.3).
in
on It is recommended that auxilialy circuits supplying primarily electronic equipment or systems should not be supplied
directly but at least via simple separation from the main circuit.
ZIJ
Fig 55.1 - Auxiliary circuit supplied directly from the main circuit
L1
L2
L3
N
Fig 55.2 - Auxiliary circuit supplied from the main circuit via a rectifier
L1
L2
L3
N
Fig 55.3 -Auxiliary circuit supplied from the main circuit via a transformer
L1
L2
L3
N
NOTE: For an auxiliary circuit supplied from the main circuit. either directly or via a rectifier, the auxiliary circuit begins at
the connection point to the main circuit, see Figures 55.1 and 55.2. In the case ofa transformer supply, the auxiliary
circuit begins on the secondary side ofthe transfomer, see Figure 55.3.
557.3.2.2 Auxiliary circuit supplied from the main circuit via transformer
Where an auxiliary circuit is supplied by more than one transformel they shall be connected in pamllel both on the
pdmary and secondary sides.
557.3.3 Auxiliary circuit supplied by an independent source
Where an indcpendent source is used a loss of supply or undervoltage ofthe main circuit source shall be detected.
An independent auxilialy circuit shall not create a hazardous situation.
NOTE: Batteries and a power supply system independent ofthe mains are examples ofindependent sources.
214
557.3.4 Auxiliary circuits with or without connection to earth
557.3.4.1 General
An auxiliary circuit shall cornpll \\ith the .'arthing requirements ofBS 7671 except as modified by Regulation
55'7.3.4.2 or 551.3.4.3.
NOTE 1: lt depends on the requirements tbr an au:iilian circuit as to whether it is operated eathed or unearthed. For example,
in an earthed auxiliary circuit an eanh t'ault in a non-earthed conductor leads to disconnection ofthe power supply of
the auxiliary circuit; in an unearthed auxilian circuit. an canh fault in a conductor leads only to a signal from the IMD
(see Rcgr ation 557.3.4.3).
NOTE 2: The use of unearthed auxiliary circlrits should be considered \!here high reliability is required.
557.3.4.3 Unearthedauxiliarycircuit
Except in the case of a SELV or PELV circuit, if an auxiliary circuit is operated unearthed via a tmnsformcr,
an insulation monitoring device (IMD) according to BS EN 61557-8 shall be installed on the secondary side.
Consideration shall be given to the use ofdsk assessment to detennine whether the signal from the IMD is to initiate
an acoustic and/or a flash alam, or be transmitted to a monitodng system.
Account shall be taken of the effects ofvoltage drop on the electrical equipment ofthe auxiliary circuit, including
inrush and starting currents.
NOTE 2: Motors starting direct-on-1ire can draw a stafiing curent from the rnain circuit that will reduce the supply voltage to
an auxiliary cilcuit dependent on the main circuit, below the minimum operating yoltage ofthe associated switchgeaf.
557.3.5.3 AC supply
The nominal voltage ofcontrol circuits shall preferably not exceed:
(i) 230 V for circuits with 50 Hz nominal frequency
(ii) 277 V for circuits with 60 Hz nominal frequency
557.3.5.4 supply
DC
557.3"5.4.1 Supply by a power system
The nominal voltage of control circuits shall prefembly not exceed 220 V
557.3.5.4.2 Supply by batteries
Where batteries are used as a power supply for auxiliary circuits, the voltage fluctuation due to charging or
discharging shall not exceed voltage tolerances specified in BS EN 60038, untess the auxiliary circuit is specifically
designed to compensate for such voltage fluctuation.
557.3.6 Protectivemeasures
557.3.6.1 Protection of wiring systems
NOTE 1: In the case ofcxtencled auxiliary circuits it is necessary to check that the requircd operating currenl ol the protective
device will bc achier ed also al thc far end ofthe respective cables or conductors' Regulation '1ll' l '
Single-phase eathedAC auxiliary circuits supplied on the secondary side ofthe trauFfonner for an auxiliary supply I
and earthed DC auxiliary circuits are pennitted to be protected by single-pole devices. The protcctile devices shall I
In uneafihed AC or DC auxiliary circuits, shof-circuit protection shall be provided for all line conductors.
NOTE 2: Thc use ofprotecti!e devjces which disconnect all lines ofan unearthed auxiliary circuit will aid lault dlagnosis and
maintenance activities.
If the short-circuit protective device on the primary side ofthe transformer for an auxiliary circuit is selected so that
it also protects against short-circuit current on the secondary side, a protective device on the secondary side ofthe
tmnsfonner nlay be omitted.
NOTE 3: For a fault or the transfonner secondary side. thc magnitude ofthc short-circuit curaent on the pimary side depends
also o11 the impedarce ofthe transformer.
I11order to provide adequatc mecharrical strength. thc lollowing minimum cross-sectional areas indicated in Tahle
55.2 shall be mct. Ifthere are special nrcchanical strength requirencnts for cables or contluctors, then a Iarger ctoss-
sectional area ofconductor, sclccted ilr accordance with Chaptet 52, may be rcquired.
Type of cable
Application Single-core Two-core Multicore
Single-wire Strardcd Screened Unscreened Screenccl oI unscreeneal
" Othcr auxiliary circuits may teed a larget cross_sectional arcA ofcopper condr.tctor, e.g. for
NOTE; The cross-sectiotlal area ofcopper conductors is derived from Section 52'1'
216
(ii) Protective de\.ices interrupling the circuit shall not be used on the secoudary side ofthe rransibrmer
(iii) Conducton on the secondary side of the transfonner shall be insulated for the highest r oltage ol anl lir e
parts or shall be installed such that their insulation cannot come into contact n ith other li\e pafis. e.g.
.1
contact with busbars
(iv) Teruinals for temporary measurements shall be provided.
)l The above requirements do not apply to summation cunent tmnsfomers where'hazardous voltages do not occur,
l1 I
e.g. equipment for insulation fault location accordirg to BS EN 61557-9.
557.5.3.2 Voltagetransformer
I
The secondary side ola voltage transformer shall be protected by a shofl-circuit protective device.
The capacitance ofthe cable shall not impair the proper opemtion of an actuator in the auxiliary cilcuit. The cable
characteristics and length shall be taken into account for the selection of switchgear and controlgear or electronic
circuits.
NOTE: For an extensive auxiliary circuit. the use ofa DC power supply or bus-system is recommended.
eble
rOSS- 557.6.3 Measures to avoid the loss of functionality
An auxiliary circuit serving a special function where reliability is a concern will require additional design
considerations to lninimize the likelihood of wiring laults. These wiring faults could result in loss offunction and/
or loss of signal. Among the design considerations are:
(i) selection of appropriate installation methods for cables
(ii) selection of equipment where a fault from line to exposed-conductive-pafts is not possible, e.g. Class II
equipment
(iii) use of installation methods and equipment that are inherently short-circuit and earth fault proof.
For the design of installations and equipment that are inhelently short-circuit and earlh fault proof, the following
shall be considered:
(a) Arangemeflts ofsingle conductors with basic insulation, together with measures to prevent mutual contact
and contact with exposed-conductive-parts. This may be achieved by:
installation in (insulated) cable nunking systems, or
installation in (insulated) conduit
(b) Arrangements of:
siugle-core cables, or
.. here tlle
557.6.4 Current-limitingsignaloutputs
In eafihed or uneallhed auxiliary circuits with current-limiting signal outputs or electronically controlled protection
against short-circuit conditions. respectively, the signal circuit shall be disconnected within 5 s if the respective
measure operates. In special cases. a shorter disconnection time may be required.
For cunent-li[riting signal outputs or electronically controlled protection olthe signal output, respectively, automatic
disconnection of supply may be omitted if a hazardous situatior is not likely to occur.
Exception: Switching elements ofprotective relays, e.g. overcurent relays, may be installed between the eafihed or
the non-eaithed conductor and a coil, provided that:
(a) this co[rection is contained inside a comn]on enclosure, or
(b) it leads to
a simplification olextemal control devices, e.g. conductor bars, cable drums, multiple connectors,
and takes into account the requirements ofRegulation 557.3.6.2.
557.6.6 Plug-inconnections
Interchangeability between multiple plug-in connections is permitted only where it will not result in mechanical
damage or introduce a fisk of fir'e, electric shock or injury to pe$ons.
NOTE 1: These plug-in connections fonn a palt ofthe auxiliary circuit(s) and nray conduct different signals.
NOTE 2: Plotection against interchangeability may be achieved by marking. polarization, design or electronic interlocking.
559.1 Scope
This section applics to the selection and erection of luminaires and lighting installations intended to be pafi of the
fixed installation.
218
I
NOTE ,l: For outdoor lightilg insrallarions. exrra-lo\\ \ oltage lighting installalions and lighting inslalleiiLrn. i:r
j:F-.:.:- -N-:llLrns.
refer to Pat 7.
559.3.1 Every luminaire shall comply with the relevant standard for manufacture and test of that luminaire
and shall be selected and erected to take account ofthe manufacturer's instructions'
559.3.2 For the pulposes of this section, luminaires without transfomels or convello$ but which are
iitted with extfa-low voltage lamps connected in series to a low voltage suppty shall be consideled as low voltage
iquipment not exha-low voltage equipment. These luminaires shall be either class I oI class II equipment.
559.3.3 Where a luminaire is installed in a pelmet, there shall be no adverse effects due to the presence or
operation ofcurtains or blinds.
559.3.4 Atrack system for luminaires shall comply with the requirements ofBS EN 60570'
.1l each fixed lighting point one ofthe following shall be used for the tennination ofthe wiring system:
(i) A ceiling rose complying with BS 67
1ii) A lunrinaile supporting coupler (LSC) complying with BS 6972 or BS 7001
iii) A batten lampholder or a pendant set complying with BS EN 60598
r
,ir) A device for counecting a luminaire (DCL) outlet complying with BS IEC 61995-1
r\) An installation coupler couplying with BS EN 61535.
{oTE: In suspe[ded ceilings one plug-ir lighiing distribution unit rnay be used for a number ofluminaires.
559.5.1.201 A ceiling rose or lampholder shall not be installed in any circuit opemting at a voltage normally
..;;eeding 250 volts.
559.5.1.202 Aceilin-srose shall rlotbeused for the attachrnent ofmore than one outgoing flexible cable unless it
is specially designed for multiple pendants.
559.5.1.203 Luminaire supporting couplers and devices for the connection ofluminaires are designed specilically
for the elect cal connection of lulr]inaires and shall not be used for the connection of any other equipment.
559.5.1.204 Lighting circuits incolporating Bl5,822, E14, E27 or E40 lampholders shall be protected by an
overcurrent protective der.ice olrlaximum rating l6 A.
559.5.1.205 Bayonet lampholders 815 and 822 shall comply withBs EN 61184 and shall have the temperature
rating T2 desffibed in that standard.
559.5.1.206 In circuits ofa TN or TT system, except for E l4 and 827 lampholders complying with BS EN 60238,
the outer contact of every Edison screw or single centre bayonet cap type lampholder shall be comected to the
neutral conductor This regulation also applies to track mounted systems.
559.5.1.208 Considemtion shall be given to the provision of the neutral conductor, at each switch position, to
facilitate the installation of elechonic switching devices.
The fixing means may be mecharical accessories (e.g. hooks or screws), boxes or enclosures which are able to
support luminaires or supporling devices for connecting a luminairc.
Irt places u,here the fixing means is intended to supporl a luminaire, the fixing means shall be capable of carrying a
nass ofnot less than 5 kg. Ifthe mass ofthe lurninaire is greater than 5 kg, a fixing means capable ofsupporting the
mass ofthe luminaire shall be installed.
The installation ofthe fixing neans shall be in accordance with the manufacturer's instructions.
The weight of luminaires and their eventual accesso es, e.g. shades, shall be compatible with the mechanical
capability ofthe ceiling or suspended ceiling or suppoting structure where installed.
Any flexible cable between the fixing means and the luminaire shall be installed so that any expected stresses in
the conductors, terminals and teminations will not impair the safety of the installation. (See also Table 4F3A of
Appendir( 4.)
559.5.3.2 A cable for through wiring shall be selected in accordance with the temperature infonnation on the
luminaire or on the manufacturer's instruction sheet, ifany, as follows:
(i) For a luminaire complying with BS EN 60598 but with temperature marking, cables suitable for the marked
temperature shall be used
(ii) Unless specified in the manufacturer's inshxctions, for a luminaire complying with BS EN 60598 but with
no tempemture marking. heat-resistant cables are not required
(iii) In the absence of information, heat-resistant cables and/or insulated conductors of type H05S-U, H05S-K,
H05SJ-K, H05SS-K (BS EN 50525 series) or equivalent shall be used.
220
NOTE: For the installation of supply cables. see also Regulation 522.2.201.
559.8 Protection against electric shock for display stands for luminaires
Protection against electric shock lor circuits supplying display stands for luminaires shall be provided by either:
rIical (i) a SELV or PELV supply, or
(ii) a residual current deyice having a rated residual operating curent not exceeding 30 mA which provides
..'. in both automatic disconnection of supply according to Section 411 and additional protection according to
Regulatiolr 415.1.
l\trl
559.9 Stroboscopic effect
In the case of lighting for premises where machines with moving pafis are in operation, consideration shall be
given to sfoboscopic effects which can give a misleading impression ofmoving parts being stationary. Such effects
..r l'ot
may be avoided by selecting lLuninaires with suitable lamp controlgear, such as high frequency controlgear, or by
distributing lighting loads across all the phases ofa polyphase supply.
:r ille
559.10 Ground-recessedluminaires
::.:'k.-,'l For grould-recessed luminaires, the selection and erection shall take account ofthe guidance given in Table A.1 of
BS EN 60598-2- 13.
ri ith
bcl
TABLE 55.3 - Explanation of symbols used in luminaires, in controlgear for luminaires and in
the installation of luminaires
BS EN 60s98-l:2008
Recessed lurninaire not suitabie for direct mouflting
on normally flarrmable surfaces
(t'c(<'
/---...?,4 widng (number of conductors ofcable
is optional)
lamps that require an
extemal ignitor
Luminaire designed for use with bowl Luminaire lor use with
mirror lamps high pressure sodium
Iamps having an intemal
(BS EN 60598 series) stalting device
(BS EN 61558-2-6)
(BS EN 61347- 1)
Rough serr'ice luminaire Electoric convefior for
an extra-low voltage
(BS EN 60598 series) lighting installation
(BS EN 61347-r)
222
GHAPTER 56
SAFETY SERVICES
CONTENTS
560.1 SCOPE
560.4 CLASSIFICATION
560.5 GENERAL
560.6 ELECTRICAL SOURCES FOR SAFETY SERVICES
560.6.8 Special requirements for safety services having sources not capable of operation in
parallel
560.6.9 Special requirements for safety services having sources capable of operation in parallel
560.6.10 Central power supply sources
560.6.11 Low power supply sources
560.6.12 Uninterruptible power supply sources (UPS)
560.6.1 3 Generator sets for safety services
560.6.14 Monitoring of safety sources
560.7 CIRCUITS OF SAFETY SERVICES
560.8 WIRING SYSTEMS
s60.9 EMERGENCY LIGHTING SYSTEMS
s60.10 FIRE DETECTION AND FIRE ALARM SYSTEMS
560.11 LIFE SAFETY AND FIREFIGHTING APPLICATIONS
CHAPTER 56
SAFETY SERVICES
:6 0.1 SCOPE
:. chaptcr covers gereral requirements for safety services, selection and erection ofelect cal supply systenrs for
-:::r sen,ices and electrical safety soulces. Standby electrical supply systems are outside the scope.
r: .haptel does l]ot apply to installations in hazardous areas (BE3), for which requirements are given in BS EN
. -9_ l.l.
\tTE: Examples ofsafety scryices include (this list is not exhaustive):
- Errergency lighting
- Fire purnps
Fire rescue service litts
Fire detection and alann systems
CO detection and alann systcms
Fire evacuation systems
Srnoke ventilation systems
Fire services communication systelns
Essential medical systems
Industrial safety systcms.
,-
560.4 CLASSIFICATION
560.5 GENERAL
560.5.1 Safety services u.ny be reqr"rired to operate at all relevant times including during mains and local
supply failure and through fire conditions. To meet this rcquirement specilic sources, equipment, circuits and wiring
are necessary Some applications also have particular requirements, as in Regulations 560.5.2 and 560.5.3.
560.5.2 For safety services required to operate in fire conditions, the following two conditions shall be
fulfi11ed:
(i) An etectrical source for safety supply shall be so selected as to maintain a supply ofadequate dluation, and
(ii) all equipment ofsafety services shall be so provided, either by construction or by erection, with fire-resisting
proteclion ol adeqttate duration.
NOTE: The safety source is gencrally additional to the noflnal source. The normal source is, for example, the public supply
network.
560,5.3 Where automatic disconnection of supply is used as a protective measure against electdc shock,
non-disconnection on the first lault is preferred. ln lT systems, continuous insulation monitoring devices shall be
provided which give an audible and visual indication in the event ofa fint fault.
560.5.4 A failure in the control or bus system of a normal installation shall not adversely affect the function
of safety serices.
560.6.3 Safety sources shall be installed in a suitable location and be accessible only to skilled or instructed
pelsons (BA5 or BA4).
560.6,4 The location ofthe safety source shall be properly and adequately ventilated so that exhaust gases.
smoke or fumes from the safety sout'ce cannot penetrate areas occupied by one or more pemons.
560.6.5 Separated independent feeders from a dist butor's network shall not serve as electrical sources for
safety services unless assurance can be obtained that the two supplies are unlikely to fail concurrently.
560.6.6 The safety source shall have sulicient capability to supply its related safety service.
560.6.7 A safety source [ray, in addition, be used for purposes other than safety services, provided that the
availability for safety services is not thereby iurpaired. A fault occurring in a circuit for pruposes other than safet)
services shall not cause the iflten'uption olany circuit for saf'ety sen'ices.
224
-.I
560.6.8 Special requirements for safety services having sources not capable of operation in
parallel
560"6.8.2 Shoft-circuit protection and fault protection shall be pror ided for each source.
E 560.6.9 Special requirements for safety services having sources capable of operation in
parallel
Shofi-circuit protection and fault protectior shall be effective inespective of uhether the installation is supplied
separately by either olthe two sources or by both in parallel.
NOTE 1 : The Damllcl operatio[ofa pri\'alc source with the public supply network is subject to authorization by the distribution
nctwork opelator (DNO). This oray lequire special devices, for example to prevent reverse power. Refer also to Section
551. rhe DCode (Distributioo Code oflicensed distribution operators) and ENA Engjneering Recomtrendations G83/2
and G59/3.
Precautions may be necessary to limit curent circulation in the connection between the neutral points ofthe sources,
rn panlcul.rr thc cfl'cct ol I11plen lrarnronrcs.
560.7.2 Cilcuits of safety services shall rot pass through locations exposed to fire dsk (BE2) unless they are
iire-resista[t. The circuits shall not, in any case, pass through zones exposed to explosion risk (BE3).
NOTE: Whele placticablc. the passage ofcircuits through locations presenting a fire risk should be avoidcd-
- : r.rl d'. 560.7.3 In accordance with Regulation 433.3.3, protection against ovelload tnay be omitted where the loss
_ : :.1lal\ ofsupply may cause a greater hazard. Where protection against overload is omitted. the occulrence ofan overload
:hall be rnonitoled.
225
560,7,4 Overcurrent prorective devices shall be selected and erected so as to avoid an overcurrent in one
circuit impai ng the correct operation ofcircuits of safety services.
560.7.5 Switchgear and controlgear shall be clearly identified and grouped in locations accessible only to
skilled or instructed persons (B-\5 or BA4).
560.7.6 In equipmenr supplied by two different circuits, a fault occuring in one circuit shall not impair the
protection against elec!ic shock or the conect operation olthe other circuit. Such equipment shall be connected to
the protective conducto$ ofboth circuits, ifnecessary
560.7.7 Safety circuir cables, other than metallic screened, fire-resistant cables, shall be adequately and
reliably separated by distance or by barriers from other circuit cables, including other safety circuit cables.
NOTE: For battery cables. special lequirements may apply.
560,7.8 Circuits for safety services, with the exception ofwiring for fire and rescue selice lift supply cables
and wiring for Iifts with special requirements, shall not be installed in lift wells or other fluelike openings.
NOTE: while fre resistant cables rvill suwive most fires, if they are located in an unstopped vertical well the upward air
draught in a fire can generate cxcessive tempemtures above the capabilities ofthe cable so they should be avoided as
a route for safety systems.
560.7.9 In addition to a general schematic diagram, full details ofall electrical safety sources shall be given.
The inlbmation shall be maintair.red adjacent to the distribution board. A single-line diagram is sufficient.
560.7.10 A drawing or drawings of the electrical salety installations shall be available showing the exact
location of:
(i) all electrical equipment and distribution boards, with equipment designations
(ii) safety equiprnent with final circuit designation and particulars and pur?ose ofthe equipment
(iii) special switching and monitoring equipment for the safety power supply (e.g. area switches, visual or
acoustic w atr ing equipment).
560.7.11 A list ofall the cunent-using equipment permanently connected to the safety power supply, indicating
the nominal electrical power, rated nominal voltage, curent and starting cuffent, together with its duration, shall be
available.
NOTE: This information lnay be included in the circuit diagrams.
560.7.12 Operating instructions for safety equipment and electrical safety services shall be available. They
shall take into accor.mt all the particulars ofthe installation.
560.8.1 One or more olthe following wiring systems shall be utilised for safety services required to operate
in fire conditions:
(i) Mineral insulated cable systems complying with BS EN 60702-1 andBS EN 60702-2andBSEN 60332-1-2
(ii) Fire-resistant cables complying with IEC 60331- l, IEC 60331-2 or IEC 60331-3 and with BS EN 60332-l-2
(iii) Fire-resistant cables complying with test requirements ofBS EN 50200, BS 8434 or BS 8491, appropriate
for the cable size and with BS EN 60332-1-2
(iv) A wiring system maintaining the necessary fire and mechanical protection.
The wiring system selected shall tneet the requirements ofthe relevant code ofpractice appropdate to the application
aud shall be mounted and installed in such a way that the circuit integdty will not be impaired during a flre.
NOTE 1: BS 5266, BS 5839 and BS 8519 specify cables to BS EN 60702-1, BS 7629-1 and BS 7846 as being suitable
when appropridrel) sclccted tol the rpplication.
NOTE 2: Examples of a systern maintaining the necessary fire and mechanical protection could be:
(i) constructional enclosures to maintainflte and mechanical protection. or
(ii) wirirg systems in sepamte fire compatments.
560.8.2 Wiring lor cortrol and bus systems of safety services shall be in acaordance with the same
requirements as the wiring which is to be used for the safety services. This does not apply to circuits that do not
adversely aflect the operation ofthe safety equipment.
560.8.4 Circuits for safety services which can be supplied by direct current shall be provided with two-pole
overcurent protection mechanistls.
226
560.8.5 Srvitchgear and controlgeax used for both AC and DC supply- sources shall be suitable for both AC
and DC operation.
Emergency lighting systems shall comply with the relevant pafis ofBS 5266 series and BS EN 1838.
Fire detection and fire alam systems shall comply with the relevant parts ofBS 5839 series.
The selection and installation ol power and control cable systems which are required to maintain their circuit
integrity for life safety and firefighting applications shall comply with the relevant parts of BS 8519.
-l-l
-l-2
j - :.!