2.13 Ex-certification number and the certifying Authority indicated on the drawing
2.14 Transformer HV winding terminal box details shown separately and suitable for top/bottom cable entry as per
specification/datasheet
2.15 Transformer LV winding terminal box details shown separately and suitable for top/bottom cable entry as per
specification/datasheet
2.16 If specified, transformer LV windiing terminals shows details for Busduct termination
2.17 Ensure LV winding terminal phase sequence is matching with the busduct phase arrangement
2.18 If specified. Surge/lightning arresters on HV winding terminals shown
2.19 Surge/Lightning arrester type/rating indicated per specification/datasheet
2.20 Appropriate cable gland type and size provided (if specified in vendor's scope) on both HV and LV terminal box suitable
for the cable type/size
2.21
If specified, transformer differential CT mounting arrangement/details shown on transformer LV winding terminal box
2.22 If specified, transformer LV neutral CT mounting arrangement/details shown on transformer LV winding neutral terminal
box
2.23 Transformer LV neutral CT details/parameters indicated per specification/datasheet
2.24 Transformer differential CT parameters/details indicated per specification/datasheet
2.25 Transformer grounding pad/terminal, 2nos on opposite sides provided and the terminal/bolt size suitable for the grounding
lug hole size
2.26 Transformer external colour finish indicated and conforms to specification/datasheet.
2.27 Any other specific checks required per project requirement (Specify)
Rev.0/28.06.2004
ABB