Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

GENERAL NOTES

GENERAL CONSTRUCTION NOTES


NOTES ON CONCRETE MIXES & PLACING
TABLE 'A'
TENSION BARS
TABLE OF LAP SPLICE & ANCHORAGE LENGTH (mm)
TABLE 'B'
COMPRESSION BARS
TABLE OF LAP SPLICE & ANCHORAGE LENGTH (mm)

CONF. REINF.
JOINT HOOP SPACE @ "2Sh" WHEN
1. ALL CONCRETE SHALL DEVELOP A MIN. COMPRESSIVE STRENGTH AT THE END OF TWENTY EIGHT 3. IF SLABS AR E REINFORCED BOTHWAYS BARS ALONG THE SHORTER SPAN SHALL BE PLACED BAR SIZES fc`= 20.7MPa(300psi) fc`= 27.6 MPa (4000psi) BAR SIZES fc`= 20.7MPa(300psi) fc`= 27.6 MPa (4000psi)
1.0 STANDARDS AND REFERENCES THERE ARE BEAMS HAVING WIDTH OF (DEFORMED MM) (DEFORMED MM)
(28) DAYS W/ CORRESPONDING MAXIMUM SIZE AGGREGATE & SLUMP AS FOLLOWS. BELOW THOSE ALONE THE LONG SPAN AT THE CENTER AND OVER THE LONGER SPAN FOR EMBEDMENT LAPPED EMBEDMENT LAPPED EMBEDMENT LAPPED EMBEDMENT LAPPED

D JOINT REINF. D
AT LEAST ONE-HALF THE COLUMN
THE FOLLOWING SHALL GOVERN THE DESIGN FABRICATION AND CONSTRUCTION OF THE PROJECT.
MAX. SIZE OF REINFORCING BARS NEAR THE SUPPORTS. THE SPACING OF THE BARS AT THE COLUMN STRIPS WIDTH & DEPTHS NOT LESS THAN Ø10 300 300 300 300 Ø10 225 300 200 300
1.1 NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (N.S.C.P 2015) VOL. 1, SEVENTH EDITION. LOCATION 28 DAYS STRENGTH MAX SLUMP SHALL NOT BE MORE THAN ONE AND A HALF ( 1 12 ) SLAB THICKNESS. THREE QUARTERS OF THE DEEPEST
AGGREGATE Ø12 300 300 300 300 Ø12 275 300 250 300
BEAM THAT FRAME INTO FOUR

CONF. REINF.
2.0 DESIGN CRITERIA ALL OTHERS, INCLUDING 20 mm 100mm 4. TEMPERATURE BARS FOR SLAB SHALL BE GENERALLY PLACED NEAR THE FACE IN TENSION AND SIDES OF THE COLUMN. ALL OTHER
Ø16 300 400 300 400 Ø16 350 400 325 400
4000 PSI (27.6 MPa) Ø20 400 550 350 500 Ø20 450 500 475 500
2.1 LOADINGS SUSPENDED SLABS SHALL NOT BE LESS THAN 0.0025 X GROSS-SECTIONAL AREA (Ag) OF THE SLAB. CONDITIONS USE HOOPS @ "Sh" CENTERS.

Sh
Ø25 600 800 550 750 Ø25 550 625 550 625
COLUMNS 4000 PSI (27.6 MPa) 20 mm 100mm ( SEE SCHEDULE BELOW)
A. DEAD LOAD
BEAMS 4000 PSI (27.6 MPa) 20 mm 100mm Ø28 750 1000 650 850 Ø28 625 675 625 675

COLUMN TIES AS
3

PER SCHEDULE
CONCRETE 23.56 kN/m 20 mm 100mm Ø32 950 1300 850 1100 Ø32 700 775 700 775
SLAB ON FILL 2500 PSI (17.5 MPa) SCHEDULE OF MINIMUM SLAB REINFORCEMENT FOR COL. BAR SPLICES SEE TABLE
STEEL 76.93 kN/m3
MINIMUM TEMPERATURE BARS OF MIN. LAP SPLICE LENGTH OF
150 mm THK. CHB WALL 2.73 kPa 2. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS. NOTES: NOTES:
COLUMN REINFORCEMENT 1. TOP PLAIN BARS, MULTIPLY VALUE BY 2 1. TOP PLAIN BARS, MULTIPLY VALUE BY 2
100 mm THK. CHB WALL 2.11 kPa SUSPENDED SLABS 20mm 100 mm 10mm Ø @ 250mm EACH WAY 2. NOT MORE THAN 33% OF THE BARS SHALL BE 2. NOT MORE THAN 33% OF THE BARS SHALL BE
40mm

CONF. REINF.
SPLICED WITHIN THE REQUIRED LAP LENGTH SPLICED WITHIN THE REQUIRED LAP LENGTH
B. LIVE LOAD SLAB ON GRADE 125 mm 10mm Ø @ 250mm EACH WAY 3. VALUES GIVEN ABOVE CAN ALSO BE USED FOR COLUMNS
WALLS ABOVE THE GRADE 25mm

Sh
ROOF 1.00 kPa 150 mm 10mm Ø @ 250mm EACH WAY

D JOINT REINF. D
BEAM STIRRUPS AND COLUMN TIES 40mm
CLASSROOMS 1.90 kPa 175 mm 10mm Ø @ 250mm EACH WAY NOTE:
WHERE CONCRETE IS EXPOSED TO
TOILETS 1.90 kPa 200 mm 10mm Ø @ 250mm EACH WAY ALL CONCRETE REINF. DETAIL SHOULD
EARTH BUT POURED AGAINST FORMS 50mm BE DONE IN ACCORDANCE WITH ACI 3. IF THE BEAM REINFORCING BARS END IN A WALL, THE CLEAR DISTANCE FROM THE BAR TO THE FARTHER FACE OF THE
CORRIDORS ABOVE, STAIRS 3.80 kPa
WHERE CONCRETE IS DEPOSITED DETAILING MANUAL (LATEST EDITION) WALL IS NOT LESS THAN 25mm. EMBEDMENT LENGTH SHALL BE SHOWN IN A TABLE 'A' FOR TENSION BARS AND TABLE 'B'

CONF. REINF.
CORRIDORS ON GROUND 4.80 kPa 75mm 5. UNLESS OTHERWISE NOTED IN THE PLANS ALL BEDDED SLABS SHALL BE REINFORCED WITH 10mm Ø
DIRECTLY AGAINST EARTH FOR COMPRESSION BARS UNLESS UNLESS SPECIFIED IN PLAN. TOP BARS AND SHALL NOT BE SPLICED WITHIN THE
C. WIND LOAD AT 250mm O.C. EACH WAY TO CENTER OF SLAB AND CONSTRUCTION JOINTS FOR SAME SHALL
COLUMN OR TWO STIRRUPS SHALL BE PROVED AT ALL SPLICES.
BUILDING CATEGORY = 1 (ESSENTIAL FACILITIES) NOT BE LESS THAN 3.65 METER APART.
3. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSISITON WITHOUT SEGREGATION. RE-HANDLING 4. IF THERE ARE TWO OR MORE LAYERS OF REINFORCING BARS, USED 25mm BAR SEPARATORS SPACED AT 1.0M ON
OPTION 1 OPTION 2 OR PLACING SHALL BE DONE PREFERABLY WITH BUGGIES , BUCKETS OR WHEELBARROWS, 6. PROVIDE EXTRA REINFORCEMENTS FOR CORNER SLAB ( TWO ADJACENT DISCONTINUOES EDGES) ON CENTER ON NO CASE SHALL THERE BE THAN TWO (2) SEPARATORS BETWEEN LAYERS OF BARS
EXPOSURE CAT. (FLAT UNOBSTRUCTED AREAS AND/OR (URBAN OR SUBURBAN AREAS WITH NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM HOPPERS TO BUIGGIES, AS SHOWN BELOW. TYPICAL COLUMN ELEV. SHOWING
D NEAR BODIES OF WATER) B NUMEROUS CLOSELY SPACED OBSTRUCTIONS) 5. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS OR STEEL SHAPES SHALL BE AS SHOWN IN FIGURE B-2
WHEELBARROWS OR BUCKETS IN WHICH CASE THEY SHALL NOT EXCEED SIX (6) METERS 7. CONCRETE SLAB REINFORCEMENT BE PROPERLY SUPPORTED WITH 10mm STEEL CHAIR
WIND VELOCITY V=340 KPH V=270 KPH DOWELS AND TIES SPACING UNLESS ELSEWHERE.
IN AGGREGATE LENGTH. OR APPROVED EQUIVALENT SPACED AT 1.0 METER ON CENTER BOTHWAYS.
P = qh [(GCpf)-(GCpi)] (DESIGN WIND PRESSURE) Ø12x1000 LONG AT
4. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS UNLESS MID-DEPTH OF SLAB
WHERE: qh = VELOCITY PRESSURE (kPa) AUTHORIZED IN WRITING DESIGNER AND ONLY FOR UNUSUAL CONDITIONS WHERE VIBRATIONS MAIN REINFORCEMENT MAIN REINFORCEMENT
GCpf = EXTERNAL PRESSURE COFFECIENT ARE EXTREMELY DIFFICULT TO ACCOMPLISH. LAP SPLICE LENGTH:
DOWN INTO EDGE BEAM. EXTENDED AT EACH CORNER

t OR 1/4 D

t OR 1/4 D
GCpf = INTERNAL PRESSURE COFFECIENT 4-Ø 12@ 1800 LONG TOP BARS BEND AT ANY LEVEL NO MORE THAN SLEEVES FOR UTILITY
5. ALL ANCHOR BOLTS, DOWELS, AND OTHER INSERTS SHALL BE PROPERLY POSITIONED & SECURED 1-Ø12 TOP & SLEEVES FOR UTILITY

t
BARS MIN. OF 1,200 (4'-0") INTO BARS. BOTT. BARS ALTERNATE BARS SHOULD BE PIPES MAX. 1/5 D PIPES MAX. 1/5 D

D
D. SEISMIC LOAD IN PLACE PRIOR TO PLACING OF CONCRETE. SPLICED. MIN. DISTANCE BET.
Cvl W 6. ALL CONCRETE SHALL BE KEPT MOST FOR A MINIMUM OF SEVEN CONSECUTIVE DAYS IMMEDIATELY 4-Ø12 BOTT. BARS TWO ADJACENT BARS SPLICES
V= (DESIGN BASE SHEAR) PROVIDE 3-Ø10 EXTRA STIRR. PROVIDE 3-Ø10 EXTRA STIRR.

400
RT AFTER POURING BY THE USE O WET BURLAP, FOG SPRAYING, CURING COMPOUNDS OR OTHER SHALL BE 600mm. EACH SIDE OF SLEEVES EACH SIDE OF SLEEVES

CONF. REINF. TIES LAT. TIES H (CLEAR HEIGHT OF COL.)


APPROVED METHODS.
Vmax = 2.50CaI W Vmin = 0.11 CalW 60
0
L
RT 7. STRIPPING OF FORMS AND SHORES: SLAB 38mm
TYP. DET. FOR SLEEVES TYP. DET. FOR SLEEVES
Vmin = 0.80 ZNvI W

0
CLEAR

WITHIN CENTER
(ZONE 4) 24 HOURS OPENING

60
FOUNDATION

HALF OF "H"
R THRU CONCRETE BEAM THRU CONCRETE BEAM
SUSPENDED SLAB EXCEPT WHEN 8 DAYS 0.25L
WHERE: W = TOTAL DEAD LOAD

400
ADDITIONAL LOADS ARE IMPOSED FIG. B-2 FIG. B-3
T = NATURAL PERIOD = Ct (h) 21 DAYS TOP BARS @ SUPPORT (CONT.)
WALLS
WHERE: C = NUMERICAL COEFFICIENT REQ'D. BOTT. BARS @ SUPPORT
BEAMS 14 DAYS IN TWO WAY SLAB EXTEND

JT. REINF.
h = BUILDING HEIGHT COLUMNS 21 DAYS 60 BARS UP TO BEAM SUPPORT
0
I = IMPORTANCE FACTOR = 1.50 6. WHEN A BEAM CROSSES A GIRDER , REST BEAM ON TOP OF GIRDER BARS, BEAM REINFORCING BARS SHALL BE
8. THE CONTRACTOR SHALL SUBMIT THE SCHEDULE OF POURING AND THE LOCATION OF THE OMIT TRIMMER BARS WHERE
R = NUMERICAL FACTOR = 8.50 OPENING IS FRAMED BY BEAM SYMMETRICAL ABOUT THE CENTER LINE WHENEVER POSSIBLE.
SEISMIC COEFFICIENT Cv = 0.44 Nv CONSTRUCTION JOINTS TO THE STRUCTURAL ENGINEER AT LEAST (4) DAYS PRIOR TO THE TYPICAL CORNER SLAB DETAIL 7. GENERALLY, NO SPLICES SHALL BE PERMITTED AT POINTS WHERE CRITICAL BENDING STRESSES OCCUR, SPLICES
Ca = 0.64 Nv POURING FOR APPROVAL. TYPICAL SLAB BOTTOM BARS WHERE SO PERMITTED SHALL BE INDICATED IN TABLE 'A' AND 'B'. WELDED SPLICES SHALL DEVELOP IN TENSION AT
0.165L SPLICE AT MID SPAN
NEAR SOURCE FACTOR (5 km) Nv = 1.6 9. THE CONTRACTOR SHALL FURNISH AND MAITAIN ADEQUATE FORMS AND SHORINGS UNTIL THE OPENING DET. EXTRA TOP BARS
LEAST 125% OF THE SPLICED YIELD STRENGTH OF THE BAR NOT MORE THAN 50% OF THE BARS AT ANY ONE SECTION
Na = 1.2 0.22L
CONCRETE MEMBERS HAVE ATTAINED THEIR WORKING CONDITION AND STRENGTH. NOTES ON COLUMNS @ SUPPORT IS ALLOWED TO BE SPLICED THEREIN.
Z = SEISMIC ZONE = 0.40 (ZONE 4)
S = SOIL TYPE = D 1. PROVIDE EXTRA SETS OF TIES AT 100 O.C. FOR TIED COLUMN REINFORCEMENT ABOVE
NOTES ON FOOTINGS AND BELOW BEAM-COLUMN CONNECTIONS FOR A DISTANCE FROM FACE OF CONNECTION
2.2 DESIGN STRESSES 1. FOOTINGS ARE DESIGNED FOR AN ALLOWANCE SOIL BEARING PRESSURE OF 96 KPa (2000psf). EQUAL TO GREATER OF THE OVERALL THICKNESS OF COLUMN, 1/6 THE CLEAR HEIGHT OF TYP. DETAIL OF COL. LAP SPLICE NOTES ON CONCRETE HOLLOW BLOCKS WALLS
A. CONCRETE COMPRESSIVE STRENGTH @ 28 DAYS: CONTRACTOR SHALL REPORT TO THE ENGINEER, IN WRITING ,THE ACTUAL SOIL CONDITIONS COLUMN OR 450mm.
a. FOOTINGS, COLUMNS, BEAMS AND SLABS f'c = 27.6 MPa (4,000 psi) UNCOVERED AND CONFIRM ACTUAL BEARING CAPACITY OF SOIL BEFORE DEPOSITING CONCRETE. COLUMN TIES SHALL BE PROTECTED EVERYWHERE BY A COVERING OF CONCRETE CAST
& EXT. GIRDER TO COL. CONNECT. 1. UNLESS OTHERWISE SHOWN IN PLANS ALL CONCRETE HOLLOW BLOCKS AND CERAMIC BLOCKS SHALL BE REINFORCED
2. FOOTING SHALL REST AT LEAST 1500mm BELOW NATURAL GRADE LINE UNLESS OTHERWISE AS SHOWN IN THE SCHEDULE OF CONCRETE HOLLOW BLOCKS AND CERAMIC BLOCK REINFORCEMENT.
b. SLAB ON FILL f'c = 17.5 MPa (2,500 psi) MONOLITHICALLY WIT HTHE CORE WITH A MINIMUM THICKNESS OF 40mm AND NOT LESS
C. SLAB f'c = 27.6 MPa (4,000 psi) INDICATED IN PLANS. NO FOOTING SHALL REST ON FILL 2. THAN 40 TIMES THE MAXIMUM SIZE OF COARSE AGGREGATE IN MILLIMETERS. NOTES ON BEAMS AND GIRDERS 2. PROVIDE 150mm x 300mm STIFFENER COLUMN REINFORCED WITH 4-12mm WITH 10mm Ø TIES AT 150mm ON CENTER
3. MINIMUM CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE 75mm CLEAR FOR CONCRETE WHERE CONCRETE HOLLOW BLOCK TERMINATES AND AT EVERY 3.0M LENGTH OF CONCRETE HOLLOW BLOCK
B. REINFORCING STEEL BARS WHERE COLUMNS CHANGE IN SIZE ,VERTICAL REINFORCEMENT SHALL BE OFFSET AT A 1. UNLESS, OTHERWISE NOTED IN PLANS , CAMBER ALL BEAMS AND GIRDER AT WALLS UNLESS NOTED IN STRUCTURAL PLANS.
DEPOSITED THE GROUND AND 50mm FOR CONCRETE DEPOSITED AGAINST A FORMWORK.
a. FOR BARS 16mm AND GREATER (INTERMEDIATE GRADE DEFORMED BAR) fy = 414 MPa (60,000 psi) SLOPE MONOLITHICALLY WITH THE CORE WITH MINIMUM THICKNESS OF 40mm AND LEAST 6mmØ FOR EVERY 4.5O M OF SPAN , EXCEPT CANTILEVERS FOR WHICH
4. IN CASES WHERE THE SOIL CONDITION IS SUCH THAT THE MINIMUM ALLOWABLE SOIL PRESSURE
b. FOR BARS LESS THAN 16mm (STRUCTURAL GRADE DEFORMED BAR) fy = 275 MPa (40,000 psi) 3. NOT LESS THAN 40 TIMES THE MAXIMUM SIZE COARSE AGGREGATE IN MILLIMETERS THE CAMBER SHALL BE AS NOTED IN PLANS OR AS ORDERED BY THE ENGINEER
OF 96KPa (2000 psf) CAN NOT BE ATTAINED AT A PRACTICAL DEPTHS THE USE OF MICROPILES ,
C. STRUCTURAL STEEL ASTM-A36 UNLESS OTHERWISE INDICATED IN THE PLANS, LAP SPLICES FOR VERTICAL COLUMN BUT IN NO CASE LESS THAN 20 mm FOR EVERY 3.0 M OF FREE SPAN.
BORED PILES, OR DRIVEN PILES MAY BE ADOPTED IN LIEU OF STANDARD ISOLATED FOOTINGS.
FOR TRUSSES, BRACINGS , & STRUTS fy = 248 MPa (36,000 psi) NOTES ON CONCRETE HOLLOW BLOCKS WALLS REINFORCEMENTS
REINFORCEMENT SHALL BE MADE WITHIN THE CENTER HALF OF COLUMN HEIGHT, AND 2. TYPICAL BARS BENDING AND CUTTING DETAILS FOR BEAMS SHALL BE AS
D. PURLINS 4. THE SPLICE LENGTH SHALL BE LESS THAN 40 BAR DIAMETERS. WELDING OR APPROVED SHOWN IN FIG. B-1 BLOCK THICKNESS REINFORCEMENT
COLD FORMED LIGHT fy = 248 MPa (36,000 psi) NOTES ON REINFORCEMENT MECHANICAL DEVICES MAY BE USED PROVIDED THAT NOT MORE THAN ALTERNATE BARS L1 L2
NOTES
E. MASONRY UNIT (CHB) HORIZONTAL LAPPED A. MINIMUM LAPS AT SPLICE= 0.25 M
1. UNLESS OTHERWISE NOTED IN PLANS, THE YIELD STRENGTH OF REINFORCING BARS SHALL BE: ARE WELDED OR MECHANICALLY SPLICED AT ANY LEVEL AND THE VERTICAL DISTANCES 1 1 1 1
NON - LOADING BEARING CHB WALLS fm' = 3.45 MPa (500 psi) fy = 414 MPa ( 60,000 psi ) L1 3 L1 3 L2 3 L2 3
A. FOOTINGS , FOOTING BEAMS AND GIRDERS BETWEEN THESE WELDS OR SPLICES OF ADJACENT BARS IS NOT LESS THAN 600mm. 75 mm 10mm Ø EVERY 3RD LEVEL 10mm Ø @ 600mm O.C. B. PROVIDE RIGHT ANGLED REINFORCEMENT
F. WELDS E - 60XX ELECTRODE fy = 414 MPa ( 60,000 psi ) AT CORNERS 0.92 m LONG
B. COLUMNS AND SHEAR WALLS 125 mm
G. STRUCTURAL BOLTS ASTM- A307 a. Ft = 96.60 mPa (14, 000 psi) 10mm Ø EVERY 3RD LEVEL 10mm Ø @ 600mm O.C.
C. BEAMS AND GIRDER fy = 414 MPa ( 60,000 psi ) C.WHERE CHB OR CER. BLK. WALL DOWELS
b. Fv= 69.00 mPa (10, 000 psi) 150mm 10mm Ø EVERY 3RD LEVEL 10mm Ø @ 600mm O.C. WITH THE SAME SIZE AS VER. OR HOR.
3.0 IN THE INTERPRETATION OF THE DRAWING, INDICATED DIMENSIONS SHALL GOVERN. D. NON-LOAD BEARING WALL PARTITIONS ,BEDDED SLABS , FLOOR & ROOF SLABS,
PARAPETS ,CATCH BASIN,SIDE WALK 4-Ø16 VERT. BARS REINFORCEMENT SHALL BE PROVIDED
fy = 275 MPa ( 40,000 psi ) 200 mm 12mm Ø EVERY 3RD LEVEL 10mm Ø @ 600mm O.C.
DISTANCES AND SIZES SHALL NOT BE SCALED FOR CONSTRUCTIONS PURPOSES 4-Ø16 VERT. BARS

550
2. ALL REINFORCING BARS SIZE 10mm OR LARGER SHALL BE DEFORMED IN ACCORDANCE WITH THE ASTM A-706 1 1 1 1

550
4.0 IN REFERENCES TO OTHER DRAWINGS, SEE ARCHITECTURAL DRAWINGS FOR DEPRESSIONS IN FLOOR BARS SMALLER THAN 10mm MAY BE PLAIN. L1 5 L1 5 L2 5
TOP BARS
L2 5

SLABS , OPENINGS IN THE WALLS AND SLABS , INTERIOR PARTITIONS , LOCATIONS OF DRAINS ETC. 3. SPLICES SHALL BE SECURELY WIRED TOGETHER & SHALL LAP OR EXTEND IN ACCORDANCE w/ TABLE B 2 Ø 12mm SIDE BARS WEB BARS SEE CONSTRUCTION NOTES
5.0 IN CASE OF DISCREPANCIES AS TO THE LAYOUT, DIMENSIONS AND ELEVATIONS BETWEEN THE (TABLE OF LAP SPLICE & ANCHORAGE LENGTH) UNLESS OTHERWISE SHOWNON DRAWINGS , SPLICES SHALL BE BOTTOM BARS FOR MASONRY WALL REIN-
STAGGERED WHENEVER POSSIBLE. 550 FORCEMENTS (TYPICAL)
STRUCTURAL PLANS AND ARCHITECTURAL DRAWINGS, THE CONTRACTORS SHALL NOTIFY BOTH THE 550
FIGURE B-1 FIN. FLR. LVL.

VARIES
6.0 ALL CONCRETE WORKS AND CONCRETE REINFORCEMENTS SHALL BE DONE IN ACCORDANCE WITH THE
ACI.318-14M BUILDING CODE REQUIREMENT AND ALL STRUCTURAL STEEL WORKS ACCORDING WITH THE NOTES ON CONCRETE SLABS TYPICAL CONNECTION DETAIL MAIN BAR END HOOKS NAT. GRD. LVL.
(ALL GRADES) DOWEL BARS TO MATCH
WITH THE AISC-05 IN SOFAR AS THEY DO NOT CONFLICT WITH THE LOCAL BUILDING CODE REQUIREMENT. 1. ALL SLAB REINFORCEMENTS SHALL BE 20mm CLEAR MINIMUM FROM BOTTOM AND FROM THE TOP OF SLAB. CHB VERTICAL BARS

600 (MIN.)
OF R.C. WALL AT CORNERS NOTES ON STIRUPS BAR SIZE DIAMETER 180° HOOK 90° HOOK
Ø10 BOTT. BARS
7.0 ACI REFERS TO AMERICAN CONCRETE INSTITUTE, AISC REFERS TO AMERICAN INSTITUTE OF STEEL 2. UNLESS OTHERWISE SHOWN, REINFORCEMENT IN CONTINUOUS ELEVETED SLAB SHALL BE CUT AS FOLLOWS: (DEFORMED) (mm) @ 300 O.C.
1. ALL REINFORCEMENT SHALL BE BENT COLD UNLESS

250
D+2db L L
CONSTRUCTION AND ASTM REFERS TO AMERICAN SOCIETY FOR TESTING MATERIALS. BENT BAR H 3-Ø10 BOTT. BARS
OTHERWISE PERMITTED BY THE STRUCTURAL ENGINEER. 10 mm Ø 60 75 125 150
8.0 CONSTURCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE SHOWN OR L1 L2 CROSS-TIE NOTES ON WELDS 2. AS SHOWN IN THE DESIGN DRAWINGS OR 12 mm Ø 75 100 150 200
NOTED. MODIFY TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL CONDITIONS. L1/4 L1/4 PERMITTED BY THE STRUCTURAL ENGINEER. 400
350mm. MAX.
L2/4 1. USE E60xx ELECTRODES FOR ALL MEMBERS WELDED. 16 mm Ø 95 125 175 250
TOP BAR 3. TIES & CLOSE STIRRUPS MUST BE AT 135.
9.0 SHOP DRAWING WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL STEELS, MISCELLANEOUS 2. WELDS SHALL DEVELOP THE FULL STRENGTH OF MEMBERS JOINED UNLESS 20 mm Ø 115 150 200 300
DOWEL TO MATCH
IRON, PRE-CAST CONCRETE, ETC. SHALL BE SUBMITTED FOR ENGINEERS APPROVAL BEFORE FABRICATION. OTHERWISE SHOWN OR DETAILED IN THE DRAWINGS.
180 DEG. HOOKS 25 mm Ø 150 200 230 450
CHB VERT. BARS
10

10. CONTRACTOR SHALL NOTE AND PROVIDE ALL MISCELLANEUOS CURBS, SILLS , STOOLS EQUIPMENT AND Dbar
dm

300

D+12db
28 mm Ø 240 300 350 550
NOTES ON STRUCTURAL STEEL
in.

MECHANICAL BASES THAT ARE REQUIRED BY THE ARCHITECTURAL , ELECTRICAL AND MECHANICAL DRAWINGS. (TYP.)

DOWEL
32 mm Ø 300 335 450 600

400
11. ALL RESULTS OF THE MATERIAL TESTING FOR CONCRETE, REINFORCING BARS & STRUCTURAL STEEL MUST BOTTOM BAR 1. STRUCTURAL STEEL TO BE USED FOR FABRICATION AND ERECTION OF THIS
FIN. FLR. LVL.
STRUCTURE SHALL COMPLY WITH ALL THE PERTINENT PROVISION OF AISC 4db OR 65mm
BE NOTED & APPROVED BY THE MATERIALS ENGINEER/STRUCTURAL DESIGNER. 135 DEG. HOOKS

250
SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL

VERIFY DEPRESSION
STIRRUP AND THE TIE HOOKS
STEEL FOR BUILDING LATEST EDITION. 90 DEG. HOOKS (ALL GRADES) 6-Ø10 BARS (AS SHOWN)
LE Ø10 BOTT. BARS @ 300 O.C.
2. ALL STRUCTURAL STEEL SHAPES SHALL CONFORM TO ASTM A36 STRUCTURAL Dbar
REINFORCING CONCRETE LINTEL BEAMS IN BAR SIZE DIAMETER
180° HOOK 90° HOOK 400
200 (MIN) 200 (MIN) STEEL UNLESS OTHERWISE INDICATED. 6d (DEFORMED) (mm)

D
D+2db L L
CONCRETE BLOCK WALLS DOWEL BARS TO b

L
12db
FLR. SLAB OR BEAM MATCH VERT. BARS 3. ALL WELDED CONNECTIONS SHALL DEVELOP THE FULL STRENGTH OF THE 10 mm Ø 40 125 85 100
MEMBERS CONNECTED. DOWEL TO MATCH
LINTELS IN BLOCK WALLS Ø10 STIRRUPS D 12 mm Ø 50 165 115 115
(DOWEL)

L1 CHB VERT. BARS


@ 150 O.C. 4. UNLESS OTHERWISE SPECIFIED ALL WELDING RODS SHALL CONFORM WITH
1. ALL JOINTS AND CELLS L
400

WHERE DEPRESSED
VERIFY ARCHITECTURAL

CLEAR TOTAL MIN. HEIGHT OF REINFORCEMENT 16 mm Ø 65 200 140 150


CONTAINING REINFORCING E60 ELECTRODES. 300 SLAB OCCURS
SPAN LENGTH fc' LINTEL
(L) (L+0.40M) (MPa) (mm) BOTTOM TOP STIRRUPS CHB WALL BARS SHALL BE FILLED 5. ALL BOLTS USED UNLESS OTHERWISE SPECIFIED SHALL BE ASTM A 307 BOLTS. 20 mm Ø 115 300 165 300
(TYP.)

DOWEL
FOR SIZE AND SPACING

400
OF HOR. & VERT. BARS WITH CONCRETE GROUT. 32 mm Ø 150 335 230 405
1.20 M 1.60 M 200 1-Ø10 1-Ø10 Ø6 mm @ 200mm SEE CONSTRUCTION NOTES 2. FOR REINFORCEMENTS SEE
OPENING 1-Ø16 VERT. NOTES ON EMBBED PIPES FIN. FLR. LVL.
(DOWEL)

1.50 M 1.90 M 14.0 200 1-Ø10 1-Ø10 Ø6 mm @ 200mm CONSTRUCTION NOTES.

250
BARS TYPICAL
400

1.80 M 2.20 M 200 1-Ø12 1-Ø10 Ø6 mm @ 200mm DOWEL BARS TO MATCH


CHB VERT. BARS 1. ALL EMBEDED PIPES FOR UTILITIES ETC. THAT PASS THRU BEAMS SHALL NOT
(DOWEL)

6-Ø10 BARS (AS SHOWN)


2-Ø12 TOP BARS 1-Ø16 CONT. HOR. BARS EXCEED 100mm IN DIAMETER OR 1/3 BEAM DETPH WHICHEVER IS LESS, UNLESS
400

2.10 M 2.50 M 250 1-Ø12 1-Ø10 Ø6 mm @ 200mm Ø10 BOTT. BARS @ 300 O.C.
FOR FLOOR SLAB ONLY OTHERWISE APPROVED IN WRITING BY THE STRUCTURAL ENGINEER. 400 TYPICAL CHB FOOTING DETAILS
200

2.40 M 2.90 M 17.0 250 1-Ø12 1-Ø10 Ø6 mm @ 200mm FIN. FLR. LVL.
2-Ø12 BOTT. BARS
NOTES ON CONCRETE WALLS
2.70 M 3.10 M 250 1-Ø16 1-Ø12 Ø10mm @ 200mm 2. NO PIPES SHALL BE ALLOWED TO PASS THRU BEAMS VERTICALLY. ( WHERE APPLICABLE )
3. NO PIPES SHALL BE EMBEDDED IN COLUMNS. 1. ALL WALLS SHALL BE REINFORCED ACCORDING TO THE FOLLOWING SCHEDULE OF WALL
3.00 M 3.40 M 300 1-Ø16 1-Ø12 Ø10mm @ 200mm
ELEVATION SECTION NOTE:
3.30 M 3.70 M 20.0 300 1-Ø16 1-Ø12 Ø10mm @ 200mm TYP. SECTION OF MASONRY REINFORCEMENT UNLESS OTHERWISE INDICATED IN THE PLANS.
Ø10mm @ 200mm
PROVIDE THESE ADDITIONAL BARS FOR
3.60 M 4.00 M 300 1-Ø20 1-Ø12
TYP. DET. OF LINTEL BEAM AT CHB WALL OPENING PARTITION REINFORCEMENTS NOTES ON CONSTRUCTION JOINTS IN CONCRETE ALL OPENINGS PLUS BARS (NOT
SHOWN) PARALLEL TO SIDE OF OPENING
WALL REINFORCEMENT VERTICAL
1. WHERE A CONSTRUCTION JOINT IS TO BE MADE, THE SURFACE OF CONCRETE THICKNESS EQUAL TO THE NUMBER OF TERMINATED
HORIZONTAL VERTICAL REMARKS SECTION BARS AT OPENING
SHALL BE CLEANED AND ALL LAITANCE AND STANDING WATER REMOVED SHEAR
TYPICAL CONNECTION DETAIL OF MASONRY WALL KEY SHALL BE PROVIDE AT THE JOINT. 100mm Ø10mm @ 250mm O.C. Ø10mm @ 300mm O.C. HORIZONTAL BARS
VER. BARS SEE ARCHITECTURAL & MECHANICAL
125mm Ø10mm @ 200mm O.C. Ø10mm @ 250mm O.C. AT CENTERS VERTICAL PLANS FOR SLAB OPENING LOCATION.
30 BAR DIA. 30 BAR DIA. MAIN REINFORCEMENTS TO BE
CONTINUOUS (TOP & BOTT. BARS) 150mm Ø12mm @ 250mm O.C. Ø12mm @ 300mm O.C. BARS STAGGED OUT HOR. BARS
(min.) (min.)
12 THK. EXPANSION JOINT
D=FOR BEAM
t=FOR SLAB

WITH MASTIC FILLER CHB WALL R.C. COLUMN OR WALL WHERE JOINTS IS AT POINT OF DOOR
MAIN REINFORCEMENTS
TO BE CONTINUOUS STRESS, PROVIDE SHEAR RODS REINFORCING BARS SHALL HAVE 25mm CLEAR CONCRETE COVER FROM FACE OF WALL EXCEPT FOR OPENING
1-Ø16 VERT. BARS DOWEL BARS TO MATCH WITH ENGINEERS APPROVAL
1-Ø16 VERT. BARS CHB HOR. BARS WALLS IN CONTACT WITH THE GROUND WHERE A MINIMUM OF 60mm SHALL BE PROVIDED AND FOR
Ø10x1000 LONG
(DOWEL)

12 THK. EXPANSION JOINT 12 THK. EXPANSION JOINT EXPOSED FACES OF FORMED WALLS WHERE THE MINIMUM SHALL BE 50mm CLEAR.
CHB WALL WITH MASTIC FILLER @ 300 O.C. 38mm CLEAR
400

WITH MASTIC FILLER 30Ø BAR 30Ø BAR WINDOW


1-Ø16 VERT. BARS 50
FOR SIZE AND SPACING (MIN.) (MIN.) 2. CARRY VERTICAL BARS AT LEAST 60mm ABOVE FLOOR LEVEL TO PROVIDE FOR SPLICES WHEN NECESSARY OPENING
OF HOR. & VERT. BARS 40
D=FOR BEAM STOP AT 50mm BELOW TOP SLAB OR SOLID BAND WHERE THE WALL ENDS VERTICAL AND HORIZONTAL BARS
D/3

SEE CONSTRUCTION NOTES.


(DOWEL)

2t=FOR SLAB
D/3
t/3 t/3

FOR SIZE AND SPACING SHALL BE SPLICED BY LAPPING A DISTANCE EQUAL TO 30 DIAMETERS AND WIRED SECURELY WITH 16 G.I. WIRE
D
t/3
400

OF HOR. & VERT. BARS


t

D/3

SEE CONSTRUCTION NOTES. 30 BAR DIA. (min.) PROVIDED THAT SPLICES IN ADJACENT BARS ARE STAGGERED AT LEAST 1.50M O.C.
FOR SIZE AND SPACING
OF HOR. & VERT. BARS SLAB BEAM
CHB WALL SEE CONSTRUCTION NOTES. 400 TYPICAL DETAIL FOR BEAM 3. UNLESS OTHERWISE NOTED IN THE PLANS, ALL OPENINGS IN WALLS 250mm OR THICKER SHALL BE REINFORCED
(DOWEL) AROUND WITH 2-20mmØ BARS. FOR 225mm, 200mm, 175mm, 150mm THICK WALLS, USE 2-16mmØ. FOR 125mm AND
OPENING OR END WALL OR SLAB CHANGE SOFFIT TYPICAL SLAB & BEAM TYP. EXTERIOR WDW. & DOOR OPENING
CORNER WALL INTERSECTION WALL INTERSECTING R.C. COLUMN OR WALL 100mm THICK WALLS, USE 2-12mmØ BARS. ALL WALLS SPANNING SHALL HAVE VERTICAL REINFORCEMENT BENT
CONSTRUCTION JOINT DET. A U-FORM LIKE STIRRUPS AND SPACED ACCORDING TO THE SCHEDULE UNLESS OTHERWISE NOTED.

PREPARED : PROJECT NAME AND LOCATION: SHEET CONTENTS : SUBMITTED BY : SUBMITTED TO : SET NO.: SHEET NO.

GENERAL NOTES

GROUP 5 - CE201 4 - STOREY EDUCATIONAL BUILDING CHRISTIAN KYLE S. BELTRAN MAE ALEXIS S. EMPERADOR SHIENA MARIE T. IGNACIO TEJAY F. MAWAL ANGELINE L. SEGUNDO ENGR. ARNULFO P. DELIMA S-1
PROJECT GROUP NO.
CAPSTONE 2 PROFESSOR
1 5
LOCATION: GUIMBAL NATIONAL HIGH SCHOOL, GUIMBAL, ILOILO

You might also like