Professional Documents
Culture Documents
New 30402
New 30402
New 30402
Software Release
After downloading:
Find the Programmer installation file in C:\4100ESProg
Find the BIN files in C:\4100ubin\Rev3-04-02
Find the documentation in C:\4100ESinfo
To Install the Programmer go to C:\4100ESProg and double click on ESProgrammer_3.04.02.exe
ES Programmer 3.04.02
DBF Revision = 173
Functional Changes:
4007 Enhancements: add network support on 4007ES
Symbolic Name: use symbolic names (SIGx-y) for NXNA points; channel moving (IDNet & IDNAC)
Fixed Defects:
677985 Select node window (Node, Name and Description box) does not refresh when a different
network path is selected.
678328 Suppression Release: RELSIG point type turns ON during the first alarm in NYC Abort Logic.
690699 Changing a public TrueAlertES device to a legacy TrueAlert device crashes the programmer
606678 Cannot connect to BNIC for when using ES version 3 programmer
700223 PUBLIC legacy TrueAlert device crash in the programmer
700420 Suppression release wizard is allowing verification type points in a cross-zone hazard area
704146 IDNet card disappears in the programmer when dragged on an IDNet card already present on
the EPS.
Other Changes:
684985 IDNet channel name should not update itself when a card is deleted.
699607 There are option cards that should be made available for the 4010ES
699608 The external point capacity on the 4010ES must be increased
699984 FUI should be made available for the 4010ES domestic on bay 1 unit 0
704167 Support phone number to be removed
Fixed Defects
717151 Pressing front panel keys for sig byp, elev byp, dh byp sometimes slow to respond and
sometimes no response at all and have to click multiple times.
Other Changes
None
Usage Notes
Requires revision 2.02.02 or greater of CPU Bootloader.
Revision 3.04.01 of the ESSupport tools should be used with this release.
Requires EPS revision 1.05.02 or later
Requires InfoAlarm revision 1.04 and InfoAlarm Bootloader revision 1.04.
idnet2_1.02.01.bin
Functional Changes
None
Fixed Defects
699649 SRP device does not release immediately when the countdown timer expired
Other Changes
None
mxdloop_2.01.03.bin
Functional Changes
557243 Create AusNZ build w/AusNZ 850 devices and algorithms.
574965 Added Disable Carbon Monoxide Algorithms
Fixed Defects
589690 Force Alarm does not work for 850 Heat and 850 PC, (Triple Sensor), devices
620779 Link errors when building MXDLoop.
678355 MX PC devices will not pass new UL requirements.
686982 801OH device with EN54A1R sensitivity and ULROR sensitivity did not satisfy conditions as per
the procedures to go into alarm.
Other Changes
599892 Increase the Earth Fault Filtering time to one second.
TIC2_1.01.bin
Initial Release.