Professional Documents
Culture Documents
Energy & Buildings: Sultan Alfraidi, Abdelhakim Mesloub, Mohammad Alshenaifi, Emad Noaime, Atef Ahriz, R. Boukhanouf
Energy & Buildings: Sultan Alfraidi, Abdelhakim Mesloub, Mohammad Alshenaifi, Emad Noaime, Atef Ahriz, R. Boukhanouf
A R T I C L E I N F O A B S T R A C T
Keywords: Space cooling of buildings using evaporative cooling is a passive strategy that can provide thermal comfort for
Evaporative cooling occupants and conserve energy. In this paper, an innovative evaporative cooling wet media material in the form
Experiment of synthetic grass fibre mat was introduced to evaluate experimentally its effectiveness in Direct Evaporative
Wet media
Cooling (DEC), Indirect Evaporative Cooling (IEC), and Dew point evaporative cooling (DPEC). A laboratory
Synthetic grass
evaporative cooling module was constructed and tested using a fully instrumented test rig and was subject to
Hot climate
environmentally controlled conditions of air temperature and relative humidity (RH) commensurate to those
prevailing in hot and dry climates like the Middle East. The wet bulb effectiveness and cooling capacity of
evaporative coolers equipped with the new wet media material were evaluated experimentally. The results show
that these evaporative coolers performance correlate well with current technology. For instance, the ambient air
temperature is reduced by as much as 12.9 ◦ C, 10.2 ◦ C, and 10.3 ◦ C for direct, indirect, and dew point modes,
respectively. It was also shown that DEC achieved effectiveness 20 % higher than indirect evaporative coolers.
The work demonstrated that the new wet media can be a viable alternative to organic and non-organic
counterparts.
1. Introduction consumption and the equivalent of 33 % of the carbon emitted into the
environment [5]. Therefore, in many parts of the world there is renewed
The decoupling of buildings indoor climate from the surrounding awareness to address the high energy demands, through for example
environment to deliver essential thermal comfort for occupants con integration of passive cooling techniques in sustainable architectural
sumes substantial amounts of energy and is one of the major contribu designs [6].
tors to climate change [1]. Today, increasing demand for buildings in Indeed, for many centuries, in regions of the world with hot and dry
many parts of the world has caused surges of electrical power demand climates, traditional cooling methods such as evaporative cooling were
particularly for space air conditioning. This is aggravated by heavy exclusively used to keep buildings cool in summer temperatures. For
dependence on cheap and inefficient energy intensive mechanical air example, across countries in the Middle East evaporative cooling in
conditioning systems for thermal comfort. Therefore, the current focus is building using porous water jars in wind catchers was widely practiced
to develop thermal comfort solutions in buildings that can deliver net [7]. Moreover, evaporative cooling has the potential to maintain effec
zero emission of greenhouse gases and other pollutants including high tively favourable comfort levels in modern buildings and dispense full
global warming potential refrigerants [2,3]. Current mechanical air requirement of fresh air. Being low intensive energy process, evapora
conditioning systems are expected to remain dominant while new and tive cooling can reduce peak electricity demand, save as much as 75 %
more sustainable solutions are being identified and developed [4]. The on energy consumption and reduce carbon emission by 44 % compared
building sector worldwide contributes 40 % of the total primary energy to vapour-compression air-conditioning [8,9]. The drawback of
* Corresponding author.
E-mail address: s.alfraidi@uoh.edu.sa (S. Alfraidi).
https://doi.org/10.1016/j.enbuild.2024.113956
Received 24 September 2023; Received in revised form 22 January 2024; Accepted 24 January 2024
Available online 28 January 2024
0378-7788/© 2024 Elsevier B.V. All rights reserved.
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
Table 1 Table 2
Comparison between some air-conditioning systems [25–27]. Types and properties of evaporative coolers wet media materials [7,8,29].
System type VMC cooling Evaporative cooling Material type characteristics structure
Property
Organic fibres • made from shredded
COP 2 to 3 5 to 27 (Randomly organic matter fibres
Power consumption High Medium/Low packed wet have good water
Refrigerants CFCs, HFCs Water pads) absorption properties
Environmental Impact High Low low thermal
conductivity
high porosity
evaporative cooling, however, resides in cooling performance being (>50 %)
strongly dependant on the ambient conditions of temperature and hu
midity, limiting the application scope of the technology [10–13].
Previous research has addressed the design and performance chal
lenges of evaporative cooling system both analytically and experimen
tally. For instance, Kumar and his team [14] investigated the
performance of an evaporative cooling unit for varying ambient condi
tions. The authors found that the unit performs better under dynamic
conditions than static conditions. Da Veiga, Güths, and Da Silva [15]
presented and experimentally tested a model to forecast the effective
ness of evaporative cooling as a method to limit excessive heat gain in
buildings’ roofs. In most tests, the model was able to forecast with high
precision the heat flux passing through the porous medium. Under
specific conditions, the performance of the wet porous media can exceed Cellulose (rigid • takes the form of
that of its dry counterpart. Kowalski and Kwiecie [16] investigated cardboard rigid or corrugated
box/kraft paper
evaporative cooling (EC) systems for an imaginary Polish industrial
paper) thermal properties
building using the TRNSYS 17 software in which it evaluated six systems can vary depending
in four Polish cities (Koszalin, Lublin, Suwalki and Wroclaw). By gen on the specific
eralising the results, EC systems may be able to conserve energy in material and packing
Poland’s climate. Lapisa and colleagues [17] discussed the layout of Offers enhanced
water evaporation
commercial building envelopes for low-rise structures. It presented a
Multi objective optimisation using the NSGA-II approach to determine
the ideal design parameters for passive cooling solutions such as cool
roofs and nighttime natural ventilation. Alshenaifi et al., [18] proposed
a creative setup with three air outlet disposition of a passive down
draught evaporative cooling (PDEC) tower to be investigated numeri
cally using CFD (Computational Fluid Dynamics) software; based on the
findings, the input velocity and temperature had a substantial impact on
the quality of the interior temperature. Furthermore, He, et al., [19]
discussed a solar-powered reel dehumidifying system for evaporative
cooling. Experimental tests showed that the system can decrease the
indoor temperature and maintain the relative humidity. Dhamneya,
Rajput and Singh [20] studied the performance of an evaporative
cooling window air conditioner. The proposed solution performs better,
saving 7.39 % of energy in April and 5.18 % in March. Boukhanouf et al.,
[21] proposed a heat pipe and porous ceramic tube regenerative evap
orative cooler prototype. It described the cooler’s construction and lab
findings. Experimental results show that the cooler air supply temper
ature can be 14 ◦ C lower than ambient air.
Standard • high strength, low
Moosavi, Zandi, and Bidi [22] explored the cooling performance of a randomly density, and thermal
naturally ventilated house with a solar chimney and hybrid evaporative packed metal conductivity
cooling. The hybrid evaporative cooling system and solar chimney fibre wet made from copper,
lowered the atrium centre zone’s air temperature by 0.7 ◦ C. Leroux pads aluminium, and steel
The porosities
et al., [23] presented an evaporative cooling system with a porous range from 30 to 95
evaporator wall. Using a mathematical model and an experimental % and depends on
setup, evaporator material properties and their effect on cooling system metal fibre length,
performance were determined. The calculated evaporator wall power fibre diameter, and
the density
ranges from 12 to 72 W/m2. Zhang et al., [24] examined the influence of
climatic factors on the evaporative cooling of porous building materials. Porous ceramic • Have high thermal
According to their findings, the factors that had the greatest influence on conductivity
Have large contact
the evaporative cooling process are the amount of solar radiation, the area and uniform
temperature of the air, the partial pressure of the water vapour, and the water distribution
speed of the wind. Durable and high
Many study have shown that Evaporative coolers offer higher overall water-retention ca
pacity
energy efficiency than Vapour Mechanical Compression (MVC) system,
Porosity depends
particularly when deployed in favourable climatic conditions. The VMC
(continued on next page)
2
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
Table 2 (continued ) separately [10]. One of the key components of an evaporative cooling
Material type characteristics structure system is the wet media material, which is usually made of a porous
structure of large surface area. The thermal properties of these materials
on production tem
peratures (at baking
are characterised by their affinity to absorb and hold liquid water; as
temperature of well as enable fast evaporation [21,28]. There are many types of ma
1250 ◦ C, a bulk terials used as wet media in evaporative coolers including metals foams,
porosity of 47 % was organic and synthetic fibres, and porous ceramics. Research works into
reported)
these types of materials and their properties are summarised in Table 2.
This paper introduces synthetic grass as wet media material in the
systems are effective in temperature and humidity control and stable form of flat mat sheets, commonly used in sport fields, landscaping,
operation, but suffer from low Coefficient of Performance (COP) and playgrounds, etc. These synthetic grass sheets are manufactured from
sever adverse environmental impact, compared to evaporative coolers plastics such as Polyethylene (PE) or Polypropylene (PP) and are
as shown in Table 1 [25–27]. structurally stable under wet conditions, high ambient temperatures,
The concept of evaporative cooling involves a complex process of and UV exposure [30,31].
heat and mass transfer between a wet surface and an air stream flowing The Synthetic grass fibres are implanted in a back support mat,
immediately over it. The air stream, often warm fresh air supply, loses its which is also made of a combination of polypropylene and polyethylene.
sensible heat in exchange for increased moisture content gained from The back mat is coated with latex to hold the grass fibres in place and
water evaporating off the wet surface. The cool air can be supplied provide rigidity. The synthetic grass fibres are then cut to required
directly to buildings (DEC) to displace warm air or used to cool indi height [32]. Fig. 1 shows the form of grass mats, the backing material
rectly (IEC) through a heat exchanger air supply to buildings [7]. The and the type of grass fibre shapes.
main advantage of IEC is that it supplies air humidity can be controlled
Fig. 2. Typical weather condition in city of Riyadh, KSA (a) Monthly Average and maximum air temperature (b) monthly mean RH.
3
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
1.1. Research gap and contribution climatic conditions. The experimental work made use of an environ
mental chamber, which enabled the precise control of the temperature
The adoption of synthetic grass mats in evaporative cooling systems and relative humidity (RH) of the air introduced into the prototype. The
can potentially contribute to increasing service-life span and minimising test conditions were set to span the wider outdoor temperature range
the requirement for maintenance. Synthetic grass fibres are made in prevailing in hot dry climates such as that of Middle East. To establish
various shapes to provide large wet surface area and air contact for full performance of the synthetic grass media material, three configu
enhanced evaporation process, are readily available and at low pro ration of evaporative cooling systems were considered namely Direct
duction cost. The synthetic grass mats can be installed in new or as Evaporative Cooling (DEC), Indirect Evaporative Cooling (IEC), and
replacement in evaporative cooling systems. Unlike organic wet media Dew Point Evaporative Cooling (DPEC). Fig. 3 gives an outline of the
materials used in evaporative cooling systems, synthetic grass mat rolls research methodology used to evaluate the performance of the experi
do not require water or fertilizers to cultivate and are recyclable [30]. mental coolers.
This work aims to evaluate experimentally this novel wet media material
which is produced as a synthetic grass mat in three types of evaporative
coolers: Direct Evaporative Cooling (DEC), Indirect Evaporative Cooling 2.1. Description of the evaporative cooling system configurations
(IEC), and Dew point evaporative cooling (DPEC). A comparative per
formance analysis, in terms of system effectiveness and cooling capacity, Each of the three configurations of evaporative cooling systems
with similar published data of evaporative coolers was also conducted. namely, Direct evaporative cooling (DEC), Indirect evaporative cooling
(IEC) and dew point evaporative cooling (DPEC) requires a different
mechanical arrangement and layout of the airflow channels. Fig. 4
1.2. Target climatic condition for evaporative cooling shows a schematic arrangement of the airflow channels of the three
evaporative cooling systems.
A further contribution of this research is to support the development
and adoption of evaporative cooling systems as a sustainable solution to 2.1.1. Direct evaporative cooling (DEC)
thermal comfort in buildings in hot and dry climate such as the arid and In the DEC mode, the hot dry ambient air inlet is located at the top
semi-arid regions of the world. These regions are characterised by opening of the tower that houses the synthetic grass media. The ambient
extreme conditions of long and hot summers with temperatures often air flows through the free- passages in the wet media and fully brought
exceeding 40◦ C, and minimal precipitation. The average atmospheric into contact with sprayed water at the top of the wet channel. The cool
temperatures has also been noticeably increasing due to climate change and saturated air is then supplied to the test room, which is cooled
[33]. For example, many cities across the Middle East (Riyadh, Baghdad, through displacement ventilation. The supply air temperature of this
Kuwait, etc.) routinely experience intense heat, with temperatures oc system is limited to the wet bulb temperature. The excess water (i.e., not
casionally surpassing 50◦ C. Fig. 2 illustrate prevailing average and evaporated) is collected in a sump below the wet channel and recircu
maximum temperature and mean relative humidity in the city of Riyadh, lated by a water pump, as shown in Fig. 4 (a).
KSA [34], where the deployment of air conditioning in buildings due to
high temperature and low relative humidity (RH) lasts from April to 2.1.2. Indirect evaporative cooling (DEC)
October. For the IEC mode, the airflow through the cooler is arranged into two
separate channels, the wet and dry channel, which shares a heat transfer
2. Methodology surface area. The ambient air is drawn into the wet and dry channels at
two separate inlets. The ambient air admitted into the wet channel un
The energy performance of a laboratory prototype evaporative dergoes cooling through direct evaporation and is rejected to outside as
cooler using synthetic grass fibres was evaluated under controlled warm and humid air. Concurrently, the ambient air drawn in through
4
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
the dry channel inlet is cooled by transferring its sensible heat to the cool 2.2. Laboratory rig set up
wet channel wall surface and is supplied into the test room for
displacement ventilation. This arrangement has the advantage of sup The core of the evaporative cooling system is the synthetic grass wet
plying cooled air, without increasing its humidity. Like the DEC media module, as shown in Fig. 5 (a). The module is made of multiple
arrangement, excess water leaving the wet channel is collected in the layers of grass mat backed by a thin aluminium plate for rigidity. The
sump and is recirculated by a water pump, as shown in Fig. 4 (b). synthetic grass mats were then stacked vertically and separated by an air
gap to allow airflow in between. Depending on the mode of operation of
2.1.3. Dew point evaporative cooling (DPEC) the evaporative cooling, the channels formed by the synthetic grass mats
The mechanical arrangement of airflow in the DPEC mode is similar and the Aluminium back plate were arranged to allow for water and air
to that of the IEC mode, as it employs separate dry and wet channels. direct contact (DEC) or wet and dry channels being separated to allow
However, in the DPEC mode, approximately 50 % of the airflow from the for indirect air cooling to take place, as explained previously. Table 3
outlet of the dry channel is redirected into the wet channel for the summarises the main dimension of the core module.
evaporation process as it comes into contact the wet synthetic grass The full test rig onto which the synthetic grass module is integrated
media. The remaining cool and dry air from the dry channel is supplied was then placed on a wheeled bench to be freely moveable into the
to the test room for displacement ventilation. This allows the air sup environmental chamber in the laboratory for testing under controlled
plied into the test room to be cooled to a temperature approaching the temperature and relative humidity conditions. Fig. 5 (b, c) shows the
ambient air dew point temperature without increasing its moisture back and front view of the test rig with the dummy cooled test room
content. To control the amount of cool and dry air supply to the test connected to the cooler using a flexible duct.
room, a damper was placed at the inlet of the wet channel. Fig. 4(c) Furthermore, the test rig was equipped with thermocouples to
shows the airflow arrangement of the DPEC mode. measure airflow temperatures, anemometer to measure airflow veloc
ities and hygrometer to measure air humidity at the inlets and outlets of
5
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
Fig. 5. Experimental set-up test rig a) synthetic grass fibres module (b) back view (c) front view.
the dry and wet channels. A data logging station was used to record
Table 3 measured parameters at fixed time intervals. A summary of the type of
Design parameters of the synthetic grass module. instrument and their specification used in the experiment is given in
Height Width Thickness Number of Separation Table 4.
(mm) (mm) (mm) layers gap
(-) (mm) 2.3. Performance indices
Synthetic grass 800 800 3 9 –
mat The measured operating parameters of the three evaporative coolers
Backing 200 200 1 5 –
were used to calculate the cooling performance in terms of cooling
aluminum
plate
effectiveness, potential cooling capacity and COP. These energy per
Dry channel 100 5 – – 5 formance indices can be used to compare and identify the most effective
inlet/outlet cooling solutions for a given application. The cooling effectiveness of the
Wet channel 100 5 – – 3 system was evaluated using the wet bulb effectiveness which is the ratio
inlet/outlet
of the difference between ambient air temperature and the supply air
temperature to the difference between the ambient air temperature and
its corresponding wet-bulb temperature. The wet bulb effectiveness is
expressed by the following formula:
6
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
Table 4 The COP is the ratio between the cooling capacity of a cooler and the
Type of instrument and data logging. power demand to operate the cooler, which in this case is represented by
Instrument type Description of use Illustration the power load of the water pump and air circulating fan. It can be
written as:
K-type thermocouples located in the centre of
Range: –75 to + the air flow passages to Qc
250◦ C measure the temperature COP = (3)
Pp + Pf
Accuracy: +/- 2.2◦
C
where, Qc (W) is the cooling capacity, Pw (W) and Pf (W) are the water
pump and fan power demand. However, in this study, the power de
mand of the auxiliary equipment (the water pump and ventilation fan)
were not optimised, and the COP calculation doesn’t provide a precise
RS-232 humidity and Used to measure air representation of the energy performance of evaporative coolers.
temperature meters temperature and However, in this work, the power demand of the auxiliary equipment
Temperature range: humidity of the inlet and
0 to 60◦ C outlet of the dry and wet
(the water pump and ventilation fan) were not optimised and the COP
RH range: 0–95 % channel calculation doesn’t give an accurate picture of the evaporative coolers
Accuracy: ±3% RH energy performance.
and ± 0.8 ◦ C The final important parameters measured in this work is the water
consumption rate of the evaporative coolers. The water consumption
rate of an evaporative cooler depends on mainly on airflow rate in
contact with the wet surface and the inlet and outlet moisture content of
the air. This can be calculated by the following equation [25]:
where; ε is the wet bulb effectiveness of cooler; Tin: the Inlet ambient dry 3.1. Direct evaporative cooling (DEC) Configuration
bulb temperature (◦ C), TS: the supply temperature (◦ C) and Twb: the inlet
wet-bulb temperature (◦ C). Similarly, the Cooling capacity, Qc, of the In a direct evaporative cooling mode, the supply of air into occupied
evaporative cooler is expressed as follows: space is channelled through a wet channel and cooled to near its mois
Qc = ṁcp (Tin − Ts ) (2) ture saturation wet bulb temperature. This mode of operation may be
necessary when the ambient air is very dry and the addition of moisture
where, ṁ is the mass flow rate (kg/s), cp is the specific heat capacity of into the occupied space is required. The thermal performance of the
air (J/kg⋅◦ C), Tin is the inlet dry bulb temperature (◦ C) and Ts is the laboratory synthetic grass fibres in direct cooling mode was evaluated at
supply dry bulb temperature(◦ C). The other important performance temperatures of 30, 35 and 40 ◦ C and at corresponding RH of 25, 35 and
index is the coefficient of performance (COP) of the evaporative cooler. 45 % with inlet air velocity of 2.85 m/s. The supply air is drawn in into
the test room through the cooler wet channels.
7
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
Fig. 6. Steady state DEC inlet and supply air temperature (RH: 30.9 %, airflow velocity: 2.85 m/s)).
Table 5
DEC mode operating parameters.
Velocity Inlet Air Mass flow rate RH Temp Temp Temp Temp RH Effectiveness COP Cooling capacity
Inlet Air Inlet Air Supply air DB Supply air WB Supply air DP Supply air
was recorded for inlet air of 30◦ C. Therefore, the temperature drop of
the inlet air through the cooler improved as the ambient air temperature
increased. This represents an advantage of evaporative coolers over
mechanical vapour compression cooling systems.
8
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
channels into the occupied space. Equally, the ambient air was circu 3.2.2. Effect of ambient air temperature and RH on supply air temperature
lated through the wet channel to perform water evaporation and cool and cooling effectiveness
the air. The airflow in the dry channel is then cooling indirectly by The temperature drop through the IEC at ambient air temperature of
transferring heat through the thin aluminium support plate separating 30, 35 and 40 ◦ C and corresponding RH of 25, 35 and 45 % while the
the two channels. The optimisation of heat transfer process between the airflow rate was maintained at 1.65 m/s are presented in Fig. 11.
two airflows was not the subject of this work. Likewise, this shows the highest temperature drops are yielded at higher
ambient temperature and lower air RH. For instance, at ambient air
3.2.1. Cooling performance temperature of 40◦ C and 25 % RH, the airflow temperature decreased
Fig. 10 show a selected steady state inlet and supply air temperature, by 10.2◦ C.
which shows the IEC cooler maintains a temperature difference of 10.2◦ In addition, Fig. 11 shows the effect on the effectiveness of the IEC
C. system follows a similar trend in that high effectiveness was achieved at
A summary of the measured steady state temperatures, calculated high ambient inlet temperature and lower RH. For instance, the effec
effectiveness and cooling capacity is also presented in Table 6. tiveness of the cooler increased from 0.56 to 0.85 for ambient inlet
temperature increase from 30◦ C to 45◦ C at constant RH of 45 % and
airflow velocity of 1.65 m/s.
9
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
Fig. 10. Steady state IEC inlet and supply air temperature (airflow RH: 29.1 % and velocity: 1.65 m/s).
Table 6
Measured steady state performance parameters in the IEC Configuration
Velocity RH Temp Temp Temp Temp Temp Temp RH Calculated COP Calculated cooling
Inlet Dry Inlet Dry Supply Inlet Inlet Inlet wet Outlet wet Outlet wet effectiveness capacity
Air channel Channel DB WB DP channel channel channel
m/s % ◦
C ◦
C ◦
C ◦
C ◦
C ◦
C % (-) (-) W
1.65 29.1 40.5 30.3 25.4 19.09 40.5 32.1 87.7 0.67 1.47 155.4
Fig. 11. IEC cooler Effectiveness and air temperature drop (airflow velocity: 1.65 m/s).
3.2.3. Effect of ambient inlet temperature and RH on cooling capacity 3.3. Dewpoint evaporative cooling operation mode
The influence of ambient air temperature and RH on the cooling
capacity of the cooler is shown in Fig. 12. This shows that the cooling DPEC coolers have the advantage of supplying cooled air at tem
capacity of the IEC increases with increasing ambient inlet-air temper perature below wet bulb temperature of ambient inlet air by sacrificing a
ature. Conversely, the cooling capacity decreases with increasing air RH. portion (up to 50 %) of the dry channel cool outlet air for doing the
For instance, at inlet air RH of 25 %, the cooling capacity increased from evaporation work in the wet channel.
49.4 to 69.39 W/m2 as inlet air temperature increased from 30 to 40 ◦ C.
In contrast, at ambient inlet temperature of 30◦ C, the cooling capacity 3.3.1. Cooling performance
decreased from 49.4 to 31.5 W/m2. Like in the previous cases, the steady state inlet and supply air
temperature of the DPEC was recorded, as shown in Fig. 13. The cooler
maintains an operating temperature difference of 10.3◦ C when the inlet
10
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
Fig. 13. Steady state DPEC inlet and supply air temperature (RH: 27.4 % and airflow velocity: 1.85 m/s).
Table 7
Dewpoint evaporative cooling mode operating parameters.
Velocity RH Temp Temp Temp Temp Temp Temp RH Calculated COP Calculated cooling
Inlet Dry Inlet Dry Supply Inlet Inlet Inlet wet Outlet wet Outlet wet effectiveness capacity
Air channel Channel DB WB DP channel channel channel
m/s % ◦
C ◦
C ◦
C ◦
C ◦
C ◦
C % (-) W
1.85 27.4 40.8 31.5 25.5 19.22 31.5 33.3 86.1 0.67 1.65 174.4
11
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
Fig. 14. Supply air temperature reduction (air velocity: 1.85 m/s).
media. The synthetic grass fibres mats used in this work are designed for √̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅
( )2 ( )2 ( )
outdoor sport surface that allow fast drainage of rainwater. e Qc
=
eTin
+
eTs
+
ev 2
(6)
Qc Tin Ts v
3.5. Uncertainty analysis
where e is the thermocouple accuracy error, T is the measured temper
The reliability of the presented experimental data was further ana ature, ev is the velocity reading accuracy error, and v is the measured
lysed considering the instruments and sensors individual precision and velocity.
combining them to estimate the overall uncertainty of the calculated key The results of the uncertainty calculation are given in Table 8. The
performance indices. This is critical for the consistency and reproduc results show that the relative uncertainty of effectiveness ranges from
ibility of measurements under identical conditions. The respective un 3.04 to 3.23 % indicating acceptable level of precision of the measured
certainty of the calculated effectiveness and cooling capacity can be results of the three evaporative coolers. The relative uncertainty of
expressed as [39]: calculating the cooling capacity was however slightly high ranging from
√̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅̅ 10.76 to 18.30 %. This is greatly influenced by the accuracy (±0.3 m/s)
eεwb
( )2 ( )2 (
eTin eTs eTwb
)2 of the instrument used to measure the airflow velocity in the air ducts
= + + (5) and the difficulty in obtaining a uniform airflow in narrow ducts.
εwb Tin Ts Twb
12
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
Fig. 17. Comparison of experimental results of capacity and temperature drop (ambient air temperature: 40◦ C and RH: 25%.
13
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
Fig. 18. Comparison results of water consumption and effectiveness (ambient air temperature: 35 ◦ C and RH: 35 %).
Table 8
Relative uncertainty calculation for the evaporative cooling modes.
Inlet Air Inlet Air Supply air DB Supply air WB Effectiveness Effectiveness relative Cooling Cooling capacity relative
Velocity Temp Temp Temp uncertainty capacity uncertainty
14
S. Alfraidi et al. Energy & Buildings 306 (2024) 113956
[14] S. Kumar, et al., Comparative performance analysis of a static & dynamic [26] M. Ali, et al., Performance enhancement of a cross flow dew point indirect
evaporative cooling pads for varied climatic conditions, Energy 233 (2021) evaporative cooler with circular finned channel geometry, J. Build. Eng. 35 (2021)
121136. 101980.
[15] A.P. da Veiga, S. Güths, A.K. da Silva, Evaporative cooling in building roofs: [27] J. Lin, et al., The counter-flow dew point evaporative cooler: analyzing its transient
theoretical modeling and experimental validation (Part-1), Sol. Energy 207 (2020) and steady-state behavior, Appl. Therm. Eng. 143 (2018) 34–47.
1122–1131. [28] A. Al-Mogbel, et al., Experimental investigations of evaporative cooling system for
[16] P. Kowalski, D. Kwiecień, Evaluation of simple evaporative cooling systems in an buildings under hot and dry environmental conditions, Heat Transfer Research 51
industrial building in Poland, J. Build. Eng. 32 (2020) 101555. (9) (2020).
[17] R. Lapisa, et al., Optimized design of low-rise commercial buildings under various [29] X. Zhao, S. Liu, S.B. Riffat, Comparative study of heat and mass exchanging
climates–energy performance and passive cooling strategies, Build. Environ. 132 materials for indirect evaporative cooling systems, Build. Environ. 43 (11) (2008)
(2018) 83–95. 1902–1911.
[18] M.A. Alshenaifi, et al., Numerical analysis of building cooling using new passive [30] J.R. Jastifer, et al., Synthetic turf: history, design, maintenance, and athlete safety,
downdraught evaporative tower configuration in an arid climate, Mathematics 10 Sports Health 11 (1) (2019) 84–90.
(19) (2022) 3616. [31] T.J. Serensits, A.S. McNitt, J.C. Sorochan, Synthetic turf, Turfgrass: Biology, Use,
[19] W. He, et al., Research of evaporative cooling experiment in summer of residential and Management 56 (2013) 179–217.
buildings in Xi’an, Energy Procedia 152 (2018) 928–934. [32] G. Schoukens, Developments in textile sports surfaces, in: Advances in Carpet
[20] A.K. Dhamneya, S. Rajput, A. Singh, Theoretical performance analysis of window Manufacture, Elsevier, 2009, pp. 101–133.
air conditioner combined with evaporative cooling for better indoor thermal [33] M. Almazroui, et al., Regional and seasonal variation of climate extremes over
comfort and energy saving, J. Build. Eng. 17 (2018) 52–64. Saudi Arabia: observed evidence for the period 1978–2021, Arab. J. Geosci. 15
[21] R. Boukhanouf, et al., Design and performance analysis of a regenerative (20) (2022) 1605.
evaporative cooler for cooling of buildings in arid climates, Build. Environ. 142 [34] T. Phillip, B. Lau. Passive downdraught evaporative cooling: The Applicability for
(2018) 1–10. residential space cooling in Riyadh , Saudi Arabia. 2013.
[22] L. Moosavi, M. Zandi, M. Bidi, Experimental study on the cooling performance of [35] M.A. Musa, Novel evaporative cooling systems for building applications, University
solar-assisted natural ventilation in a large building in a warm and humid climate, of Nottingham, 2009. PhD diss.
J. Build. Eng. 19 (2018) 228–241. [36] E. Ibrahim, L. Shao, S.B. Riffat, Performance of porous ceramic evaporators for
[23] G. Leroux, et al., Innovative low-energy evaporative cooling system for buildings: building cooling application, Energ. Buildings 35 (9) (2003) 941–949.
study of the porous evaporator wall, J. Build. Perform. Simul. 12 (2) (2019) [37] B. Ford, R. Schiano-Phan, E. Francis, The architecture and engineering of
208–223. downdraught cooling: a design source book. 2010: PHDC press.
[24] L. Zhang, et al., Impact of climatic factors on evaporative cooling of porous [38] M. Kanzari, R. Boukhanouf, H.G. Ibrahim, Mathematical modeling of a sub-wet
building materials, Energ. Buildings 173 (2018) 601–612. bulb temperature evaporative cooling using porous ceramic materials, Int. J. Ind.
[25] Z. Duan, et al., Indirect evaporative cooling: past, present and future potentials, Manuf. Eng. 7 (12) (2013) 900–906.
Renew. Sustain. Energy Rev. 16 (9) (2012) 6823–6850. [39] J. Lv, et al., Study on the performance of a unit dew-point evaporative cooler with
fibrous membrane and its application in typical regions, Case Stud. Therm. Eng. 24
(2021) 100881.
15
Downloaded on 3/12/2024 12:43:31
Journal Information
EDITION CATEGORY
Science Citation Index ENGINEERING, CIVIL - SCIE
Expanded (SCIE) ENERGY & FUELS - SCIE
CONSTRUCTION & BUILDING
TECHNOLOGY - SCIE
Publisher Information
PUBLISHER ADDRESS PUBLICATION FREQUENCY
ELSEVIER SCIENCE SA PO BOX 564, 1001 LAUSANNE, 24 issues/year
SWITZERLAND
2022 JOURNAL IMPACT FACTOR 2022 JOURNAL IMPACT FACTOR WITHOUT SELF CITATIONS
6.7 5.9
Journal Impact Factor without self cites is calculated using the following metrics
Showing 1-5 rows of 1,705 total (use export in the relevant section to download the full table)
ENERGIES 703
BUILDINGS 501
ENERGY 444
SUSTAINABILITY 438
Showing 1-20 rows of 1,008 total (use export in the relevant section to download the full table)
5 14 146
0 times cited
ARTICLES REVIEWS OTHER
87 0 9
The data included in this tile summarizes the items published in the journal in the JCR data year and
in the previous two years. This three-year set of published items is used to provide descriptive
analysis of the content and community of the journal.Learn more
Items
TOTAL CITABLE % OF CITABLE OA
2,490 16.02%
CITABLE NON-CITABLE
SUBSCRIPTION OR BRONZE
2,091 / 83.44%
Citations*
TOTAL CITABLE % OF CITABLE OA
12,552 15.31%
CITABLE NON-CITABLE
EDITION EDITION
Science Citation Index Expanded (SCIE) Science Citation Index Expanded (SCIE)
CATEGORY CATEGORY
CONSTRUCTION & BUILDING TECHNOLOGY ENERGY & FUELS
10/68 37/119
JCR JIF RANK QUART JIF PERCENTILE JCR JIF RANK QUART JIF PERCENTILE
YEAR ILE YEAR ILE
2022 10/68 Q1 86.0 2022 37/119 Q2 69.3
2021 8/68 Q1 88.97 2021 36/119 Q2 70.17
2020 9/67 Q1 87.31 2020 36/114 Q2 68.86
2019 7/63 Q1 89.68 2019 31/112 Q2 72.77
2018 7/63 Q1 89.68 2018 28/103 Q2 73.30
2017 5/62 Q1 92.74 2017 22/97 Q1 77.84
2016 5/61 Q1 92.62 2016 20/92 Q1 78.80
2015 6/61 Q1 90.98 2015 31/88 Q2 65.34
2014 5/59 Q1 92.37 2014 30/89 Q2 66.85
2013 6/58 Q1 90.52 2013 36/83 Q2 57.23
2012 4/57 Q1 93.86 2012 26/81 Q2 68.52
2011 6/56 Q1 90.18 2011 27/81 Q2 67.28
2010 4/53 Q1 93.40 2010 30/79 Q2 62.66
2009 6/49 Q1 88.78 2009 31/71 Q2 57.04
2008 3/38 Q1 93.42 2008 25/67 Q2 63.43
2007 7/34 Q1 80.88 2007 32/64 Q2 50.78
2006 6/33 Q1 83.33 2006 27/62 Q2 57.26
2005 6/31 Q1 82.26 2005 32/63 Q3 50.00
2004 5/31 Q1 85.48 2004 23/61 Q2 63.11
2003 9/29 Q2 70.69 2003 32/62 Q3 49.19
2002 10/29 Q2 67.24 2002 30/63 Q2 53.17
2001 13/27 Q2 53.70 2001 34/66 Q3 49.24
2000 11/28 Q2 62.50 2000 32/66 Q2 52.27
1999 19/26 Q3 28.85 1999 44/64 Q3 32.03
1998 9/25 Q2 66.00 1998 27/67 Q2 60.45
1997 14/20 Q3 32.50 1997 43/58 Q3 26.72
CATEGORY CATEGORY
CONSTRUCTION & BUILDING TECHNOLOGY ENERGY & FUELS
13/89 34/155
JCR JCI RANK QUART JCI PERCENTILE JCR JCI RANK QUART JCI PERCENTILE
YEAR ILE YEAR ILE
2022 13/89 Q1 85.96 2022 34/155 Q1 78.39
2021 12/89 Q1 87.08 2021 26/145 Q1 82.41
2020 13/87 Q1 85.63 2020 25/133 Q1 81.58
2019 9/87 Q1 90.23 2019 17/132 Q1 87.50
2018 8/85 Q1 91.18 2018 16/131 Q1 88.17
2017 8/82 Q1 90.85 2017 14/126 Q1 89.29
CATEGORY
ENGINEERING, CIVIL
25/179
JCR JCI RANK QUART JCI PERCENTILE
YEAR ILE
2022 25/179 Q1 86.31
2021 21/175 Q1 88.29
2020 21/172 Q1 88.08
2019 13/172 Q1 92.73
2018 10/170 Q1 94.41
2017 11/168 Q1 93.75
Previous years:
14,261 citations
3 Energies 3,484
4 Buildings 2,563
6 Sustainability 2,197
7 Energy 1,864
Showing 1 - 20 rows of 1318 total (use export in the relevant section to download the full table)
5 Energy 1,218
13 Energies 500
16 Sustainability 306
Showing 1 - 20 rows of 1147 total (use export in the relevant section to download the full table)
69.3
CONSTRUCTION & BUILDING
TECHNOLOGY
86.0
ENGINEERING, CIVIL
91.7
3 TONGJI UNIVERSITY 58
5 CHONGQING UNIVERSITY 54
6 HUNAN UNIVERSITY 52
8 TIANJIN UNIVERSITY 45
Showing 1 - 8 rows of 1975 total (use export in the relevant section to download the full table)
Contributions by country/region
Countries or Regions that have contributed the most papers to the journal in the most recent three-
year period. Learn more
2 USA 342
3 England 191
4 Canada 158
5 Italy 156
6 Spain 117
7 Australia 106
Showing 1 - 8 rows of 88 total (use export in the relevant section to download the full table)
Normalized Eigenfactor
7.67443
The Normalized Eigenfactor Score is the Eigenfactor score normalized, by rescaling the total number
of journals in the JCR each year, so that the average journal has a score of 1. Journals can then be
compared and influence measured by their score relative to 1. Learn more