SALVAVIDAS SISTEMAS CONTRA INC

25m. NTE DE PEDREGAL


SAN ANTONIO DE BELEN HEREDIA
COSTARICA
(506) 22931248

Job Name : CEDIS COYOL COSTA RICA


Building : PCI-08
Location : ALAJUELA, SAN JOSE COSTA RICA
System : 28
Contract : N/A
Data File : COY-S28.WXF

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
SALVAVIDAS SISTEMAS CONTRA INC Page 1
CEDIS COYOL COSTA RICA Date AUG.2018

HYDRAULIC CALCULATIONS
for

Project name: CEDIS COYOL


Location: ALAJUELA, SAN JOSE COSTA RICA
Drawing no: PCI-08
Date: AUG. 2018

Design
Remote area number: 28
Remote area location: SYSTEM 28
Occupancy classification: UNCARTON EXPANDED PLASTIC
Density: 1.4167
Area of application: 1200
Coverage per sprinkler: 100
Type of sprinklers calculated: ESFR K22.4 165°F, PENDENT, 1"NPT
No. of sprinklers calculated: 12@40PSI
In-rack demand: N/A
Hose streams: 250
Total water required (including hose streams): 1955.310 - GPM @ 114.272
Type of system: WET
Volume of dry or preaction system: N/A - Gal

Water supply information


Date: AUG.2018
Location: ALAJUELA COSTA RICA
Source: FIRE PUMP 2500GPM@145PSI, 290,000 GAL SUCTION TANK

Name of contractor: SALVAVIDAS SISTEMAS CONTRA INCENDIOS


Address: 75m NTE DE PEDREGAL, SAN ANTONIO DE BELEN HEREDIA COSTA RICA
Phone number: (506) 22931248
Name of designer: ING. MAURICIO MENESES
Authority having jurisdiction: FIRE DEPARTMENT OF COSTA RICA
Notes: (Include peaking information or gridded systems here.) FLOW AND PRESSURE SHOWN HERE
WERE CALCULATED AT THE PUMP'S DISCHARGE FLANGE

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
SALVAVIDAS SISTEMAS CONTRA INC Page 2
CEDIS COYOL COSTA RICA Date AUG.2018

Pump Data: Demand:


P1 - Pump Churn Pressure : 174 D1 - Elevation : 29.485
P2 - Pump Rated Pressure : 145 D2 - System Flow : 1705.31
P2 - Pump Rated Flow : 2500 D2 - System Pressure : 114.272
P3 - Pump Pressure @ Max Flow : 94.25 Hose ( Demand ) : 250
P3 - Pump Max Flow : 3750 D3 - System Demand : 1955.31
Safety Margin : 44.165

180 P1

168

156
P2
P 144

R 132

E 120 D2

S 108 D3 P3
S 96

U 84

R 72

E 60
48

36
D1
24

12

400 800 1200 1600 2000 2400 2800 3200 3600


FLOW ( N ^ 1.85 )

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
SALVAVIDAS SISTEMAS CONTRA INC Page 3
CEDIS COYOL COSTA RICA Date AUG.2018

Fitting Legend
Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24

Aty Alarm Tyco AV-1 14 23 24 23


E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
S NFPA 13 Swing Check Valve 4 5 5 7 9 11 14 16 19 22 27 32 45 55 65 76 87 98 109 130
T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121

Units Summary

Diameter Units Inches


Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch

Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
SALVAVIDAS SISTEMAS CONTRA INC Page 4
CEDIS COYOL COSTA RICA Date AUG.2018

Node Elevation K-Fact Pt Pn Flow Density Area Press


No. Actual Actual Req.

01 64.773 54.78 na
02 67.011 52.26 na
03 60.08 22.4 40.0 na 141.67 1.4167 100 40.0
04 59.595 22.4 40.03 na 141.72 1.4167 100 40.0
05 59.112 22.4 40.23 na 142.09 1.4167 100 40.0
06 58.624 22.4 40.64 na 142.8 1.4167 100 40.0
07 51.406 64.34 na
09 64.773 54.8 na
10 67.011 52.28 na
11 60.08 22.4 40.01 na 141.69 1.4167 100 40.0
12 59.595 22.4 40.04 na 141.74 1.4167 100 40.0
13 59.112 22.4 40.25 na 142.11 1.4167 100 40.0
14 58.624 22.4 40.65 na 142.82 1.4167 100 40.0
15 51.406 64.35 na
17 64.773 54.9 na
18 67.011 52.37 na
19 60.08 22.4 40.06 na 141.77 1.4167 100 40.0
20 59.595 22.4 40.08 na 141.82 1.4167 100 40.0
21 59.112 22.4 40.29 na 142.19 1.4167 100 40.0
22 58.624 22.4 40.7 na 142.9 1.4167 100 40.0
23 51.406 64.38 na
25 64.773 55.08 na
26 67.011 54.31 na
27 51.406 65.84 na
29 64.773 55.24 na
30 67.011 54.46 na
31 51.406 65.91 na
33 64.773 55.36 na
34 67.011 54.59 na
35 51.406 65.99 na
37 64.773 55.44 na
38 67.011 54.67 na
39 51.406 66.07 na
41 64.773 55.51 na
42 67.011 54.74 na
43 51.406 66.18 na
45 64.773 55.56 na
46 67.011 54.79 na
47 51.406 66.31 na
49 64.773 55.58 na
50 67.011 54.82 na
51 51.406 66.43 na
53 64.773 55.6 na
54 67.011 54.83 na
55 51.406 66.59 na
57 64.773 55.6 na
58 67.011 54.88 na
59 51.406 67.5 na
08 49.168 66.92 na
16 49.168 66.92 na
24 49.168 66.95 na
28 49.168 67.0 na
32 49.168 67.07 na
36 49.168 67.16 na
40 49.168 67.24 na
44 49.168 67.35 na
48 49.168 67.47 na
52 49.168 67.61 na
56 49.168 67.77 na
FMJ 49.168 68.72 na
T28 49.168 70.48 na
BR28 2.0 94.45 na

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Flow Summary - Standard
SALVAVIDAS SISTEMAS CONTRA INC Page 5
CEDIS COYOL COSTA RICA Date AUG.2018

Node Elevation K-Fact Pt Pn Flow Density Area Press


No. Actual Actual Req.

B28 2.0 94.45 na 250.0


UN23 -15.0 110.81 na
UN24 -15.0 110.81 na
UN25 -15.0 110.81 na
LI23 1.0 103.88 na
U23 -15.0 110.81 na
LI24 1.0 103.88 na
U24 -15.0 110.81 na
LI25 1.0 103.88 na
U25 -15.0 110.81 na
LI22 1.0 102.86 na
U22 -15.0 109.78 na
LI21 1.0 102.46 na
U21 -15.0 109.39 na
LI20 1.0 102.1 na
U20 -15.0 109.03 na
LI17 1.0 99.25 na
U17 -15.0 106.18 na
LI15 1.0 96.61 na
U15 -15.0 103.54 na
LI14 1.0 96.26 na
U14 -15.0 103.19 na
LI13 1.0 94.91 na
U13 -15.0 102.18 na
LI12 1.0 96.12 na
U12 -15.0 103.05 na
LI11 1.0 96.2 na
U11 -15.0 103.13 na
LI9 1.0 96.83 na
U9 -15.0 103.76 na
UN2 -15.0 112.48 na
UN26 -15.0 110.81 na
UN22 -15.0 109.78 na
UN21 -15.0 109.39 na
UN20 -15.0 109.03 na
UN19 -15.0 108.06 na
UN18 -15.0 106.8 na
UN17 -15.0 106.18 na
UN16 -15.0 103.93 na
UN15 -15.0 103.54 na
UN14 -15.0 103.19 na
UN13 -15.0 102.82 na
UN12 -15.0 103.05 na
UN11 -15.0 103.13 na
UN10 -15.0 103.52 na
UN9 -15.0 103.76 na
UN8 -15.0 105.57 na
UN7 -15.0 108.29 na
UN6 -15.0 109.35 na
UN5 -15.0 110.09 na
UN4 -15.0 110.84 na
UN3 -15.0 111.47 na
UN1 -15.0 114.46 na
LI1 -9.0 111.9 na
PH2 -1.0 108.75 na
PH1 -1.0 110.18 na
DSCH -8.0 113.56 na
FP -8.0 114.27 na

The maximum velocity is 11.74 and it occurs in the pipe between nodes B28 and LI13

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 6
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

*REMOTE LINES
*REMOTE LINE 1
01 -281.32 3.26 T 20.159 2.238 54.778
to 120.0 0.0 20.159 -0.969
02 -281.32 -0.0693 0.0 22.397 -1.551 Vel = 10.81
02 0.0 3.26 T 20.159 125.000 52.258
to 120.0 8E 75.261 95.420 3.002
03 -281.32 -0.0692 0.0 220.420 -15.260 Vel = 10.81
03 141.67 3.26 0.0 9.731 40.000 K Factor = 22.40
to 120.0 0.0 0.0 0.210
04 -139.65 -0.0189 0.0 9.731 -0.184 Vel = 5.37
04 141.72 3.26 0.0 9.719 40.026 K Factor = 22.40
to 120.0 0.0 0.0 0.209
05 2.07 0.0 0.0 9.719 0.0 Vel = 0.08
05 142.09 3.26 0.0 9.739 40.235 K Factor = 22.40
to 120.0 0.0 0.0 0.211
06 144.16 0.0201 0.0 9.739 0.196 Vel = 5.54
06 142.80 3.26 T 20.159 191.000 40.642 K Factor = 22.40
to 120.0 8E 75.261 95.420 3.126
07 286.96 0.0718 0.0 286.420 20.571 Vel = 11.03
07 0.0 3.26 T 20.159 2.238 64.339
to 120.0 0.0 20.159 0.969
08 286.96 0.0718 0.0 22.397 1.609 Vel = 11.03
0.0
286.96 66.917 K Factor = 35.08
*REMOTE LINE 2
09 -281.43 3.26 T 20.159 2.238 54.803
to 120.0 0.0 20.159 -0.969
10 -281.43 -0.0693 0.0 22.397 -1.552 Vel = 10.82
10 0.0 3.26 T 20.159 125.000 52.282
to 120.0 8E 75.261 95.420 3.002
11 -281.43 -0.0693 0.0 220.420 -15.272 Vel = 10.82
11 141.69 3.26 0.0 9.731 40.012 K Factor = 22.40
to 120.0 0.0 0.0 0.210
12 -139.74 -0.0189 0.0 9.731 -0.184 Vel = 5.37
12 141.74 3.26 0.0 9.719 40.038 K Factor = 22.40
to 120.0 0.0 0.0 0.209
13 2.0 0.0 0.0 9.719 0.0 Vel = 0.08
13 142.10 3.26 0.0 9.739 40.247 K Factor = 22.40
to 120.0 0.0 0.0 0.211
14 144.1 0.0201 0.0 9.739 0.196 Vel = 5.54
14 142.83 3.26 T 20.159 191.000 40.654 K Factor = 22.40
to 120.0 8E 75.261 95.420 3.126
15 286.93 0.0718 0.0 286.420 20.567 Vel = 11.03
15 0.0 3.26 T 20.159 2.238 64.347
to 120.0 0.0 20.159 0.969
16 286.93 0.0718 0.0 22.397 1.608 Vel = 11.03

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 7
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

0.0
286.93 66.924 K Factor = 35.07
*REMOTE LINE 3
17 -281.87 3.26 T 20.159 2.238 54.897
to 120.0 0.0 20.159 -0.969
18 -281.87 -0.0695 0.0 22.397 -1.557 Vel = 10.83
18 0.0 3.26 T 20.159 125.000 52.371
to 120.0 8E 75.261 95.420 3.002
19 -281.87 -0.0695 0.0 220.420 -15.315 Vel = 10.83
19 141.77 3.26 0.0 9.731 40.058 K Factor = 22.40
to 120.0 0.0 0.0 0.210
20 -140.1 -0.0190 0.0 9.731 -0.185 Vel = 5.39
20 141.82 3.26 0.0 9.719 40.083 K Factor = 22.40
to 120.0 0.0 0.0 0.209
21 1.72 0.0 0.0 9.719 0.0 Vel = 0.07
21 142.19 3.26 0.0 9.739 40.292 K Factor = 22.40
to 120.0 0.0 0.0 0.211
22 143.91 0.0200 0.0 9.739 0.195 Vel = 5.53
22 142.90 3.26 T 20.159 191.000 40.698 K Factor = 22.40
to 120.0 8E 75.261 95.420 3.126
23 286.81 0.0718 0.0 286.420 20.551 Vel = 11.02
23 0.0 3.26 T 20.159 2.238 64.375
to 120.0 0.0 20.159 0.969
24 286.81 0.0718 0.0 22.397 1.608 Vel = 11.02
0.0
286.81 66.952 K Factor = 35.05
*NON REMOTE LINES
25 92.75 3.26 T 20.159 2.238 55.077
to 120.0 0.0 20.159 -0.969
26 92.75 0.0089 0.0 22.397 0.199 Vel = 3.57
26 0.0 3.26 2T 40.319 345.890 54.307
to 120.0 16E 150.523 190.842 6.759
27 92.75 0.0089 0.0 536.732 4.770 Vel = 3.57
27 0.0 3.26 T 20.159 2.238 65.836
to 120.0 0.0 20.159 0.969
28 92.75 0.0089 0.0 22.397 0.199 Vel = 3.57
0.0
92.75 67.004 K Factor = 11.33
29 91.87 3.26 T 20.159 2.238 55.238
to 120.0 0.0 20.159 -0.969
30 91.87 0.0087 0.0 22.397 0.195 Vel = 3.53
30 0.0 3.26 2T 40.319 345.890 54.464
to 120.0 16E 150.523 190.842 6.759
31 91.87 0.0087 0.0 536.732 4.686 Vel = 3.53
31 0.0 3.26 T 20.159 2.238 65.909
to 120.0 0.0 20.159 0.969
32 91.87 0.0088 0.0 22.397 0.196 Vel = 3.53

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 8
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

0.0
91.87 67.074 K Factor = 11.22
33 91.45 3.26 T 20.159 2.238 55.361
to 120.0 0.0 20.159 -0.969
34 91.45 0.0087 0.0 22.397 0.194 Vel = 3.52
34 0.0 3.26 2T 40.319 345.890 54.586
to 120.0 16E 150.523 190.842 6.759
35 91.45 0.0087 0.0 536.732 4.647 Vel = 3.52
35 0.0 3.26 T 20.159 2.238 65.992
to 120.0 0.0 20.159 0.969
36 91.45 0.0087 0.0 22.397 0.195 Vel = 3.52
0.0
91.45 67.156 K Factor = 11.16
37 91.46 3.26 T 20.159 2.238 55.442
to 120.0 0.0 20.159 -0.969
38 91.46 0.0086 0.0 22.397 0.193 Vel = 3.52
38 0.0 3.26 2T 40.319 345.890 54.666
to 120.0 16E 150.523 190.842 6.759
39 91.46 0.0087 0.0 536.732 4.649 Vel = 3.52
39 0.0 3.26 T 20.159 2.238 66.074
to 120.0 0.0 20.159 0.969
40 91.46 0.0087 0.0 22.397 0.194 Vel = 3.52
0.0
91.46 67.237 K Factor = 11.15
41 91.88 3.26 T 20.159 2.238 55.510
to 120.0 0.0 20.159 -0.969
42 91.88 0.0087 0.0 22.397 0.195 Vel = 3.53
42 0.0 3.26 2T 40.319 345.890 54.736
to 120.0 16E 150.523 190.842 6.759
43 91.88 0.0087 0.0 536.732 4.688 Vel = 3.53
43 0.0 3.26 T 20.159 2.238 66.183
to 120.0 0.0 20.159 0.969
44 91.88 0.0088 0.0 22.397 0.196 Vel = 3.53
0.0
91.88 67.348 K Factor = 11.20
45 92.67 3.26 T 20.159 2.238 55.556
to 120.0 0.0 20.159 -0.969
46 92.67 0.0089 0.0 22.397 0.199 Vel = 3.56
46 0.0 3.26 2T 40.319 345.890 54.786
to 120.0 16E 150.523 190.842 6.759
47 92.67 0.0089 0.0 536.732 4.762 Vel = 3.56
47 0.0 3.26 T 20.159 2.238 66.307
to 120.0 0.0 20.159 0.969
48 92.67 0.0089 0.0 22.397 0.199 Vel = 3.56
0.0
92.67 67.475 K Factor = 11.28
49 93.69 3.26 T 20.159 2.238 55.582
to 120.0 0.0 20.159 -0.969
50 93.69 0.0090 0.0 22.397 0.202 Vel = 3.60

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 9
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

50 0.0 3.26 2T 40.319 345.890 54.815


to 120.0 16E 150.523 190.842 6.759
51 93.69 0.0091 0.0 536.732 4.860 Vel = 3.60
51 0.0 3.26 T 20.159 2.238 66.434
to 120.0 0.0 20.159 0.969
52 93.69 0.0091 0.0 22.397 0.203 Vel = 3.60
0.0
93.69 67.606 K Factor = 11.39
53 95.12 3.26 T 20.159 2.238 55.596
to 120.0 0.0 20.159 -0.969
54 95.12 0.0093 0.0 22.397 0.208 Vel = 3.66
54 0.0 3.26 2T 40.319 345.890 54.835
to 120.0 16E 150.523 190.842 6.759
55 95.12 0.0093 0.0 536.732 4.998 Vel = 3.66
55 0.0 3.26 T 20.159 2.238 66.592
to 120.0 0.0 20.159 0.969
56 95.12 0.0093 0.0 22.397 0.209 Vel = 3.66
0.0
95.12 67.770 K Factor = 11.55
57 103.74 3.26 T 20.159 2.238 55.600
to 120.0 0.0 20.159 -0.969
58 103.74 0.0109 0.0 22.397 0.244 Vel = 3.99
58 0.0 3.26 2T 40.319 345.890 54.875
to 120.0 16E 150.523 190.842 6.759
59 103.74 0.0109 0.0 536.732 5.868 Vel = 3.99
59 0.0 3.26 T 20.159 2.238 67.502
to 120.0 0.0 20.159 21.975
60 103.74 0.0109 0.0 22.397 0.245 Vel = 3.99
0.0
103.74 89.722 K Factor = 10.95
*BACK MAIN
01 281.32 6.357 0.0 9.615 54.778
to 120.0 0.0 0.0 0.0
09 281.32 0.0026 0.0 9.615 0.025 Vel = 2.84
09 281.43 6.357 0.0 9.679 54.803
to 120.0 0.0 0.0 0.0
17 562.75 0.0097 0.0 9.679 0.094 Vel = 5.69
17 281.87 6.357 0.0 8.806 54.897
to 120.0 0.0 0.0 0.0
25 844.62 0.0204 0.0 8.806 0.180 Vel = 8.54
25 -92.75 6.357 0.0 9.729 55.077
to 120.0 0.0 0.0 0.0
29 751.87 0.0165 0.0 9.729 0.161 Vel = 7.60
29 -91.87 6.357 0.0 9.523 55.238
to 120.0 0.0 0.0 0.0
33 660.0 0.0129 0.0 9.523 0.123 Vel = 6.67
33 -91.45 6.357 0.0 8.178 55.361
to 120.0 0.0 0.0 0.0
37 568.55 0.0099 0.0 8.178 0.081 Vel = 5.75

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 10
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

37 -91.47 6.357 0.0 9.615 55.442


to 120.0 0.0 0.0 0.0
41 477.08 0.0071 0.0 9.615 0.068 Vel = 4.82
41 -91.87 6.357 0.0 9.679 55.510
to 120.0 0.0 0.0 0.0
45 385.21 0.0048 0.0 9.679 0.046 Vel = 3.89
45 -92.67 6.357 0.0 8.806 55.556
to 120.0 0.0 0.0 0.0
49 292.54 0.0030 0.0 8.806 0.026 Vel = 2.96
49 -93.69 6.357 0.0 9.729 55.582
to 120.0 0.0 0.0 0.0
53 198.85 0.0014 0.0 9.729 0.014 Vel = 2.01
53 -95.11 6.357 0.0 9.523 55.596
to 120.0 0.0 0.0 0.0
57 103.74 0.0004 0.0 9.523 0.004 Vel = 1.05
0.0
103.74 55.600 K Factor = 13.91
*FRONT MAIN
08 286.96 8.249 0.0 9.615 66.917
to 120.0 0.0 0.0 0.0
16 286.96 0.0007 0.0 9.615 0.007 Vel = 1.72
16 286.92 8.249 0.0 9.679 66.924
to 120.0 0.0 0.0 0.0
24 573.88 0.0029 0.0 9.679 0.028 Vel = 3.45
24 286.81 8.249 0.0 8.806 66.952
to 120.0 0.0 0.0 0.0
28 860.69 0.0059 0.0 8.806 0.052 Vel = 5.17
28 92.75 8.249 0.0 9.729 67.004
to 120.0 0.0 0.0 0.0
32 953.44 0.0072 0.0 9.729 0.070 Vel = 5.72
32 91.87 8.249 0.0 9.523 67.074
to 120.0 0.0 0.0 0.0
36 1045.31 0.0086 0.0 9.523 0.082 Vel = 6.28
36 91.45 8.249 0.0 8.178 67.156
to 120.0 0.0 0.0 0.0
40 1136.76 0.0099 0.0 8.178 0.081 Vel = 6.82
40 91.46 8.249 0.0 9.615 67.237
to 120.0 0.0 0.0 0.0
44 1228.22 0.0115 0.0 9.615 0.111 Vel = 7.37
44 91.88 8.249 0.0 9.679 67.348
to 120.0 0.0 0.0 0.0
48 1320.1 0.0131 0.0 9.679 0.127 Vel = 7.92
48 92.67 8.249 0.0 8.806 67.475
to 120.0 0.0 0.0 0.0
52 1412.77 0.0149 0.0 8.806 0.131 Vel = 8.48
52 93.69 8.249 0.0 9.729 67.606
to 120.0 0.0 0.0 0.0
56 1506.46 0.0169 0.0 9.729 0.164 Vel = 9.04

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 11
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

56 95.11 8.249 T 41.108 9.524 67.770


to 120.0 0.0 41.108 0.0
FMJ 1601.57 0.0188 0.0 50.632 0.952 Vel = 9.61
FMJ -1705.31 8.249 T 41.108 4.762 68.722
to 120.0 0.0 41.108 21.006
60 -103.74 -0.0001 0.0 45.870 -0.006 Vel = 0.62
0.0
-103.74 89.722 K Factor = -10.95
*FEED
FMJ 1705.31 8.249 3E 63.423 20.000 68.722
to 120.0 0.0 63.423 0.0
T28 1705.31 0.0211 0.0 83.423 1.761 Vel = 10.24
0.0
1705.31 70.483 K Factor = 203.12
*RISER
T28 1705.31 8.249 T 41.108 47.168 70.483
to 120.0 G 4.698 72.820 21.428 * * Fixed Loss = 1
B28 1705.31 0.0211 Aty 27.014 119.988 2.534 Vel = 10.24
Fsp 0.0
0.0
1705.31 94.445 K Factor = 175.47
*MANIFOLD DE RISERS
BR28 0.0 8.249 T 41.108 3.000 94.445
to 120.0 0.0 41.108 0.0
B28 0.0 0.0 0.0 44.108 0.0 Vel = 0
B28 1955.31 8.249 0.0 1.000 94.445 Qa = 250
to 120.0 0.0 0.0 0.433
LI13 1955.31 0.0280 0.0 1.000 0.028 Vel = 11.74
0.0
1955.31 94.906 K Factor = 200.71
*LED-IN SITEMAS 21, 23 Y 25
UN23 0.0 9.42 G 5.593 64.000 110.809
to 150.0 0.0 5.593 0.0
UN24 0.0 0.0 0.0 69.593 0.0 Vel = 0
UN24 0.0 9.42 0.0 30.000 110.809
to 150.0 0.0 0.0 0.0
UN25 0.0 0.0 0.0 30.000 0.0 Vel = 0
UN25 0.0 9.42 T 55.931 337.000 110.809
to 150.0 0.0 55.931 0.0
UN26 0.0 0.0 0.0 392.931 0.0 Vel = 0
0.0
0.0 110.809 K Factor = 0
*LED-IN SISTEMA 21
LI23 0.0 10.28 E 33.148 16.000 103.880
to 140.0 0.0 33.148 6.930
U23 0.0 0.0 0.0 49.148 -0.001 Vel = 0
U23 0.0 9.42 T 55.931 50.000 110.809
to 150.0 G 5.593 61.524 0.0
UN23 0.0 0.0 0.0 111.524 0.0 Vel = 0

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 12
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

0.0
0.0 110.809 K Factor = 0
*LED-IN SISTEMA 23
LI24 0.0 10.28 E 33.148 16.000 103.880
to 140.0 0.0 33.148 6.930
U24 0.0 0.0 0.0 49.148 -0.001 Vel = 0
U24 0.0 9.42 T 55.931 50.000 110.809
to 150.0 G 5.593 61.524 0.0
UN24 0.0 0.0 0.0 111.524 0.0 Vel = 0
0.0
0.0 110.809 K Factor = 0
*LED-IN SISTEMA 25
LI25 0.0 10.28 E 33.148 16.000 103.880
to 140.0 0.0 33.148 6.930
U25 0.0 0.0 0.0 49.148 -0.001 Vel = 0
U25 0.0 9.42 T 55.931 50.000 110.809
to 150.0 G 5.593 61.524 0.0
UN25 0.0 0.0 0.0 111.524 0.0 Vel = 0
0.0
0.0 110.809 K Factor = 0
*LED-IN SISTEMA 27
LI22 0.0 10.28 E 33.148 16.000 102.855
to 140.0 0.0 33.148 6.930
U22 0.0 0.0 0.0 49.148 -0.001 Vel = 0
U22 0.0 9.42 T 55.931 391.000 109.784
to 150.0 G 5.593 61.524 0.0
UN22 0.0 0.0 0.0 452.524 0.0 Vel = 0
0.0
0.0 109.784 K Factor = 0
*LED-IN SISTEMA 29
LI21 0.0 10.28 E 33.148 16.000 102.456
to 140.0 0.0 33.148 6.930
U21 0.0 0.0 0.0 49.148 0.0 Vel = 0
U21 0.0 9.42 T 55.931 391.000 109.386
to 150.0 G 5.593 61.524 0.0
UN21 0.0 0.0 0.0 452.524 0.0 Vel = 0
0.0
0.0 109.386 K Factor = 0
*LED-IN SISTEMA 31
LI20 0.0 10.28 E 33.148 16.000 102.101
to 140.0 0.0 33.148 6.930
U20 0.0 0.0 0.0 49.148 0.0 Vel = 0
U20 0.0 9.42 T 55.931 391.000 109.031
to 150.0 G 5.593 61.524 0.0
UN20 0.0 0.0 0.0 452.524 0.0 Vel = 0
0.0
0.0 109.031 K Factor = 0

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 13
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

*LED-IN SISTEMA 33
LI17 0.0 10.28 E 33.148 16.000 99.248
to 140.0 0.0 33.148 6.930
U17 0.0 0.0 0.0 49.148 0.0 Vel = 0
U17 0.0 9.42 T 55.931 10.000 106.178
to 150.0 G 5.593 61.524 0.0
UN17 0.0 0.0 0.0 71.524 0.0 Vel = 0
0.0
0.0 106.178 K Factor = 0
*LED-IN SISTEMA 32
LI15 0.0 10.28 E 33.148 16.000 96.611
to 140.0 0.0 33.148 6.930
U15 0.0 0.0 0.0 49.148 0.0 Vel = 0
U15 0.0 9.42 T 55.931 6.000 103.541
to 150.0 G 5.593 61.524 0.0
UN15 0.0 0.0 0.0 67.524 0.0 Vel = 0
0.0
0.0 103.541 K Factor = 0
*LED-IN SISTEMA 30
LI14 0.0 10.28 E 33.148 16.000 96.259
to 140.0 0.0 33.148 6.930
U14 0.0 0.0 0.0 49.148 0.0 Vel = 0
U14 0.0 9.42 T 55.931 6.000 103.189
to 150.0 G 5.593 61.524 0.0
UN14 0.0 0.0 0.0 67.524 0.0 Vel = 0
0.0
0.0 103.189 K Factor = 0
*LED-IN SISTEMA 28
LI13 1955.31 10.28 E 33.148 16.000 94.906
to 140.0 0.0 33.148 6.930
U13 1955.31 0.0070 0.0 49.148 0.343 Vel = 7.56
U13 0.0 9.42 T 55.931 6.000 102.179
to 150.0 G 5.593 61.524 0.0
UN13 1955.31 0.0094 0.0 67.524 0.637 Vel = 9.00
0.0
1955.31 102.816 K Factor = 192.83
*LED-IN SISTEMA 26
LI12 0.0 10.28 E 33.148 16.000 96.120
to 140.0 0.0 33.148 6.930
U12 0.0 0.0 0.0 49.148 0.0 Vel = 0
U12 0.0 9.42 T 55.931 6.000 103.050
to 150.0 G 5.593 61.524 0.0
UN12 0.0 0.0 0.0 67.524 0.0 Vel = 0
0.0
0.0 103.050 K Factor = 0
*LED-IN SISTEMA 24

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 14
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

LI11 0.0 10.28 E 33.148 16.000 96.205


to 140.0 0.0 33.148 6.930
U11 0.0 0.0 0.0 49.148 -0.001 Vel = 0
U11 0.0 9.42 T 55.931 6.000 103.134
to 150.0 G 5.593 61.524 0.0
UN11 0.0 0.0 0.0 67.524 0.0 Vel = 0
0.0
0.0 103.134 K Factor = 0
*LED-IN SISTEMA 22
LI9 0.0 10.28 E 33.148 16.000 96.829
to 140.0 0.0 33.148 6.930
U9 0.0 0.0 0.0 49.148 -0.001 Vel = 0
U9 0.0 9.42 2T 111.863 230.000 103.758
to 150.0 E 24.61 142.065 0.0
UN9 0.0 0.0 G 5.593 372.065 0.0 Vel = 0
0.0
0.0 103.758 K Factor = 0
*UNDERGROUND
UN2 -1085.07 9.42 2T 111.863 361.000 112.483
to 150.0 2E 49.22 166.676 0.0
UN26 -1085.07 -0.0032 G 5.593 527.676 -1.674 Vel = 5.00
UN26 0.0 9.42 2E 49.22 218.000 110.809
to 150.0 T 55.931 105.151 0.0
UN22 -1085.07 -0.0032 0.0 323.151 -1.025 Vel = 5.00
UN22 0.0 9.42 G 5.593 120.000 109.784
to 150.0 0.0 5.593 0.0
UN21 -1085.07 -0.0032 0.0 125.593 -0.398 Vel = 5.00
UN21 0.0 9.42 0.0 112.000 109.386
to 150.0 0.0 0.0 0.0
UN20 -1085.07 -0.0032 0.0 112.000 -0.355 Vel = 5.00
UN20 0.0 9.42 E 24.61 283.000 109.031
to 150.0 0.0 24.609 0.0
UN19 -1085.07 -0.0032 0.0 307.609 -0.976 Vel = 5.00
UN19 0.0 9.42 G 5.593 390.000 108.055
to 150.0 0.0 5.593 0.0
UN18 -1085.07 -0.0032 0.0 395.593 -1.255 Vel = 5.00
UN18 0.0 9.42 2E 49.22 147.000 106.800
to 150.0 0.0 49.220 0.0
UN17 -1085.07 -0.0032 0.0 196.220 -0.622 Vel = 5.00
UN17 0.0 9.42 E 24.61 685.000 106.178
to 150.0 0.0 24.609 0.0
UN16 -1085.07 -0.0032 0.0 709.609 -2.251 Vel = 5.00
UN16 0.0 9.42 G 5.593 116.000 103.927
to 150.0 0.0 5.593 0.0
UN15 -1085.07 -0.0032 0.0 121.593 -0.386 Vel = 5.00
UN15 0.0 9.42 0.0 111.000 103.541
to 150.0 0.0 0.0 0.0
UN14 -1085.07 -0.0032 0.0 111.000 -0.352 Vel = 5.00

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 15
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

UN14 0.0 9.42 G 5.593 112.000 103.189


to 150.0 0.0 5.593 0.0
UN13 -1085.07 -0.0032 0.0 117.593 -0.373 Vel = 5.00
UN13 1955.31 9.42 0.0 111.000 102.816
to 150.0 0.0 0.0 0.0
UN12 870.24 0.0021 0.0 111.000 0.234 Vel = 4.01
UN12 0.0 9.42 0.0 40.000 103.050
to 150.0 0.0 0.0 0.0
UN11 870.24 0.0021 0.0 40.000 0.084 Vel = 4.01
UN11 0.0 9.42 2E 49.22 126.000 103.134
to 150.0 G 5.593 54.813 0.0
UN10 870.24 0.0021 0.0 180.813 0.382 Vel = 4.01
UN10 0.0 9.42 0.0 115.000 103.516
to 150.0 0.0 0.0 0.0
UN9 870.24 0.0021 0.0 115.000 0.242 Vel = 4.01
UN9 0.0 9.42 3E 73.829 780.000 103.758
to 150.0 G 5.593 79.422 0.0
UN8 870.24 0.0021 0.0 859.422 1.813 Vel = 4.01
UN8 0.0 9.42 18E 442.977 835.000 105.571
to 150.0 2G 11.186 454.163 0.0
UN7 870.24 0.0021 0.0 1289.163 2.719 Vel = 4.01
UN7 0.0 9.42 5E 123.049 381.000 108.290
to 150.0 0.0 123.049 0.0
UN6 870.24 0.0021 0.0 504.049 1.063 Vel = 4.01
UN6 0.0 9.42 2E 49.22 301.000 109.353
to 150.0 0.0 49.220 0.0
UN5 870.24 0.0021 0.0 350.220 0.738 Vel = 4.01
UN5 0.0 9.42 2E 49.22 299.000 110.091
to 150.0 G 5.593 54.813 0.0
UN4 870.24 0.0021 0.0 353.813 0.746 Vel = 4.01
UN4 0.0 9.42 2E 49.22 249.000 110.837
to 150.0 0.0 49.220 0.0
UN3 870.24 0.0021 0.0 298.220 0.629 Vel = 4.01
UN3 0.0 9.42 E 24.61 396.000 111.466
to 150.0 T 55.931 86.133 0.0
UN2 870.24 0.0021 G 5.593 482.133 1.017 Vel = 4.01
0.0
870.24 112.483 K Factor = 82.05
*LED-IN PUMP ROOM
UN2 1955.31 9.42 2E 49.22 160.000 112.483
to 150.0 0.0 49.220 0.0
UN1 1955.31 0.0094 0.0 209.220 1.973 Vel = 9.00
UN1 0.0 10.28 0.0 6.000 114.456
to 140.0 0.0 0.0 -2.599
LI1 1955.31 0.0070 0.0 6.000 0.042 Vel = 7.56
LI1 0.0 10.02 E 22.0 8.000 111.899
to 120.0 0.0 22.000 -3.465
PH2 1955.31 0.0106 0.0 30.000 0.317 Vel = 7.96

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
SALVAVIDAS SISTEMAS CONTRA INC Page 16
CEDIS COYOL COSTA RICA Date AUG.2018

Hyd. Qa Dia. Fitting Pipe Pt Pt


Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn

PH2 0.0 10.02 4E 88.0 47.000 108.751


to 120.0 0.0 88.000 0.0
PH1 1955.31 0.0105 0.0 135.000 1.424 Vel = 7.96
PH1 0.0 10.02 E 22.0 7.000 110.175
to 120.0 G 5.0 27.000 3.032
DSCH 1955.31 0.0105 0.0 34.000 0.358 Vel = 7.96
DSCH 0.0 10.02 S 55.0 12.000 113.565
to 120.0 0.0 55.000 0.0
FP 1955.31 0.0106 0.0 67.000 0.707 Vel = 7.96
0.0
1955.31 114.272 K Factor = 182.91

Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087