1 2 3 4 5 6 7 8 9 10 NOTES

THIS DRAWING SHOULD NOT BE USED FOR


*EXECUTION WITHOUT SIGNED.
DEVELOPMENT LENGTH * THIS DRAWING SHOULD NOT BE SCALED OFF ONLY
WRITTEN DIMENSIONSSHOULD BE FOLLOWED
SCHEDULE OF R.C.C. SLAB.
B1 B3 SLAB * THE RESPONSIBILITY OF THE DESIGNER SEIZES IF THE
THK BOTTOM REINFORCEMENT DISTRIBUTION REMARK DISTRIBUTION OF THE REINFORCEMENT IS NOT GOT CHECKED
NUMBERS
PRIOR TO CONCRETING.

B37

B42

B54
B31
S3 4nos 10mm S1
TERRACE
S1 5" # 8 @ 5" C/C ALT BENTUP #8 @ 5" C/C ALT BENTUP TWO WAY SLAB
S1
THIS DRAWING IS PROPERTY OF VASTUSTRUCT....
B4 B5 B6
* ENGINEER AND STRUCTURAL CONSULTANT AND
F S2 F
6" # 10 @ 5" C/C ALT BENTUP # 10 @ 5" C/C ALT BENTUP ONE WAY SLAB
C3 C2 C1 SHALL NOT BE REPRODUCED OR USED WITHOUT
ONE WAY SLAB EXPLICIT PERMISSION.
S1 S3 5" # 8 @ 5" C/C ALT BENTUP # 6 @ 6" C/C DIST
S1
STRUCTURAL CONSULTANT WILL NOT BE

B36

B38
B30

B53
S3
RESPONSIBLE FOR
B7 B8 B9
THE STABILITY OF STRUCTURE IF ANY CHANGES OR
C4
UP
C6
S2 C5 * MODIFICATIONS ARE MADE INTHIS DRAWING WITHOUT
S3

B35

B43

B52

B55
B29
WRITTEN / E-MAIL CONSENT
S2
S3
B10
S3
B11 B12
* DRAWING RELEASED FOR 'APPROVAL' IS USED ON
THE SITE FOR CONSTRUCTION PURPOSE WITH
C16 C18 C14
S1
ARCH. / BUILDERS PRIOR PERMISSION.
S1
B13 * SAFETY OF ANY ARCHITECTURAL PROJECTION

B51
B28
WHICH IS NOT FOLLOWED IN THIS DRAWING.

B44
B34

B47
S3
DUCT
4'0" X 2'6"
QUALITY OF CONCRETE, QUALITY OF MATERIALS
B14
* USED FOR CONSTRUCTION, POOR WORKMANSHIP,

B46
UP S3 S3 FAULTY CONSTRUCTION PROCEDURE.
B15 C15 B16 C10
ANY ACCIDIENT OCCURING DURING CONSTRUCTION
* OF

B41
B27

B50
S3 STRUCTURE / BUILDING.
B17 B18
E C13
S1
E * ANY ACCIDIENT DUE TO INSUFFICIENT AND
IMPROPER SHUTTERING AND CENTERING WORK

CUPBOARD
C7 C11
S1 STEEL DETAILING AT TYPICAL

B49
S3 STABILITY OF ADJOINING STRUCTURES

B40
UCOLUMN-BEAM CONNECTION

B33
* SETTELMENT OF BED CONCRETE.

B26
C12

B48
B19
(SECTIONAL PLAN) * CRACKS IN WALLS

B45
C8 S3 * CRACKS DUE TO SHRINKAGE OF CONCRETE
B21 B22 B20

B39
rcc paradi

BEAM SCHEDULE (M20 : Fe500 (MAIN) : Fe415 (SHEAR)) (LEVEL: SECOND) S3 C9 SETOUT OUR RESPONSIBLITY

B25

B32
14'7" X 3'0" B24
S3
S1

BEAM SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT SHEAR STIRRUPS B23


REMARKS
NUMBERS B D LEFT MID SPAN RIGHT LEFT MID SPAN RIGHT LEFT MID SPAN RIGHT
* THE DESIGNER'S RESPONSIBILITY LIMITED TO THE DRG. & DESIGN
B1 150 450 2-T12 2-T12 2-T12 2-T12 2-T12 2-T12 4-2L-T8@100 C/C 2-2L-T8@100 C/C 4-2L-T8@100 C/C CANTILEVERED
INDEX PLAN AT SECOND SLAB BEAM LEVEL ONLY & NOT FOR EXECUTION.
+ + +
2-T12 2-T12 2-T12

B2 150 450 2-T12 2-T12 2-T12 2-T12 2-T12 2-T12 12-2L-T8@100 C/C 10-2L-T8@100 C/C 12-2L-T8@100 C/C -
+
2-T12

B3 150 450 2-T12 2-T12 2-T12 2-T10 2-T10 2-T10 11-2L-T8@100 C/C 9-2L-T8@100 C/C 11-2L-T8@100 C/C -
+
2-T12

B4,B7 230 450 3-T12 3-T12 3-T12 3-T12 3-T12 3-T12 4-2L-T8@100 C/C 2-2L-T8@100 C/C 4-2L-T8@100 C/C CANTILEVERED
+ + +
2-T12 2-T12 2-T12

D B5 230 450 3-T12 3-T12 3-T12 3-T12 3-T12 3-T12 10-2L-T8@125 C/C 8-2L-T8@125 C/C 10-2L-T8@125 C/C - D
+
2-T12

B6,B51 230 450 3-T12 3-T12 3-T12 3-T12 3-T12 3-T12 9-2L-T8@125 C/C 7-2L-T8@125 C/C 9-2L-T8@125 C/C -

B8 230 450 3-T12 3-T12 3-T12 3-T12 3-T12 3-T12 11-2L-T8@125 C/C 9-2L-T8@125 C/C 11-2L-T8@125 C/C - LD+10db

LD+10db
+
2-T12

B9 230 450 3-T12 3-T12 3-T12 3-T12 3-T12 3-T12 7-2L-T8@125 C/C 4-2L-T8@150 C/C 6-2L-T8@150 C/C -
LD+10db LD GENERAL NOTES
B10 230 450 2-T12 2-T12 2-T12 3-T12 3-T12 3-T12 4-2L-T8@100 C/C 2-2L-T8@100 C/C 4-2L-T8@100 C/C CANTILEVERED
+ + +
2-T12 2-T12 2-T12

B11 230 450 2-T12 2-T12 2-T12 3-T12 3-T12 3-T12 11-2L-T8@125 C/C 7-2L-T8@150 C/C 11-2L-T8@125 C/C -
MIN. DEPTH OF EXCAVATION
+
2-T12 IN MEDIUM SOIL. 1.2M
LD = DEVELOPMENT LENGTH IN TENSION (50 X DIA. OF BAR)
B12 230 450 2-T12 2-T12 2-T12 3-T12 3-T12 3-T12 7-2L-T8@125 C/C 5-2L-T8@125 C/C 7-2L-T8@125 C/C -
db = DIAMETER OF BAR
B13 230 450 3-T12 3-T12 3-T12 2-T12 2-T12 2-T12 8-2L-T8@100 C/C 4-2L-T8@125 C/C 6-2L-T8@125 C/C -
ENVIRONMENTAL EXPOSURE
CONDITION:- MILD
B14 230 450 3-T12 3-T12 3-T12 2-T12 2-T12 2-T12 6-2L-T8@125 C/C 4-2L-T8@125 C/C 6-2L-T8@125 C/C -
COLUMN
B15 230 450 2-T16 2-T16 2-T16 3-T16 3-T16 3-T16 4-2L-T8@100 C/C 2-2L-T8@100 C/C 4-2L-T8@100 C/C CANTILEVERED S.B.C. - T/SQM
+ + +
2-T16 2-T16 2-T16

B16 230 450 2-T16 3-T16 3-T16 3-T16 3-T16 2-T16 18-2L-T8@125 C/C 16-2L-T8@125 C/C 18-2L-T8@125 C/C - ANCHORAGE OF BEAM BARS IN EXT. JOINT GRADE OF CONCRETE
+
3-T16
+
2-T16
+
2-T16 HOOP SPACING BEAM REINFORCEMENT
M20
B17 230 450 3-T12 3-T12 3-T12 3-T12 3-T12 3-T12 3-2L-T8@100 C/C 1-2L-T8@100 C/C 3-2L-T8@100 C/C CANTILEVERED GRADE OF STEEL FE 415
+
2-T12
+
2-T12
+
2-T12 <=d/4 AND 8 db
B18 230 450 3-T12 3-T12 3-T12
+
3-T12
2-T12
3-T12 3-T12 12-2L-T8@100 C/C 10-2L-T8@100 C/C 12-2L-T8@100 C/C - TOP EXTRA R1 . . .
B19 230 450 3-T12 3-T12 3-T12 2-T12 2-T12 2-T12 10-2L-T8@125 C/C 8-2L-T8@125 C/C 10-2L-T8@125 C/C -
C C
B20 230 450 2-T12 2-T12 2-T12 2-T12 2-T12 2-T12 6-2L-T8@125 C/C 4-2L-T8@125 C/C 5-2L-T8@150 C/C - R1 . . .
B21 230 450 2-T12 2-T12 2-T12 3-T12 3-T12 3-T12 4-2L-T8@100 C/C 2-2L-T8@100 C/C 4-2L-T8@100 C/C CANTILEVERED
+ + +
3-T12 3-T12 3-T12
0

R0 ISSUED FOR CONSTRUCTION 01.02.24 MMK


15

B22 230 450 2-T12 2-T12 2-T12 3-T12 3-T12 3-T12 10-2L-T8@125 C/C 8-2L-T8@125 C/C 10-2L-T8@125 C/C -
+
3-T12
REV. DESCRIPTION DATE NAME
B23 150 450 2-T12 2-T12 2-T12 2-T10 2-T10 2-T10 4-2L-T8@100 C/C 2-2L-T8@100 C/C 4-2L-T8@100 C/C CANTILEVERED

B24 150 450 2-T12 2-T12 2-T12 2-T10 2-T10 2-T10 12-2L-T8@100 C/C 7-2L-T8@150 C/C 12-2L-T8@100 C/C -
+
2-T12

B25 150 450 2-T12 2-T12 2-T12 2-T12 2-T12 2-T12 3-2L-T8@150 C/C 1-2L-T8@150 C/C 3-2L-T8@150 C/C - ARCHITECT :
B26 150 450 2-T12 2-T12 2-T12 2-T12 2-T12 2-T12 15-2L-T8@100 C/C 13-2L-T8@100 C/C 15-2L-T8@100 C/C -
+
2-T12

B27 150 450 2-T12 2-T12 2-T12 2-T10 2-T10 2-T10 4-2L-T8@150 C/C 2-2L-T8@150 C/C 4-2L-T8@150 C/C - PROJECT :
B28 150 450 2-T12 2-T12 2-T12 2-T10 2-T10 2-T10 14-2L-T8@100 C/C 8-2L-T8@150 C/C 14-2L-T8@100 C/C -
+
2-T12 TYPICAL DETAILS OF CURTAIL BAR FOR BEAMS
B29 150 450 2-T12 2-T12 2-T12 2-T10 2-T10 2-T10 7-2L-T8@100 C/C 3-2L-T8@150 C/C 7-2L-T8@100 C/C -

B30 150 450 2-T12 2-T12 2-T12 2-T10 2-T10 2-T10 12-2L-T8@100 C/C 7-2L-T8@150 C/C 12-2L-T8@100 C/C -

B31 150 450 2-T12 2-T12 2-T12 2-T10 2-T10 2-T10 7-2L-T8@100 C/C 5-2L-T8@100 C/C 7-2L-T8@100 C/C -

B32 230 450 2-T12 2-T12 2-T12 2-T12 2-T12 2-T12 3-2L-T8@100 C/C 1-2L-T8@100 C/C 3-2L-T8@100 C/C CANTILEVERED

B33 230 450 2-T12 2-T12 2-T12 2-T12 2-T12 2-T12 12-2L-T8@125 C/C 10-2L-T8@125 C/C 12-2L-T8@125 C/C -

B34 230 450 2-T16 2-T16 2-T16 2-T16 2-T16 2-T16 11-2L-T8@125 C/C 9-2L-T8@125 C/C 11-2L-T8@125 C/C -

B35 230 450 2-T16 2-T16 2-T16 2-T16 2-T16 2-T16 5-2L-T8@150 C/C 3-2L-T8@150 C/C 5-2L-T8@150 C/C - B CONSULTANTS:
B36 230 450 2-T16 2-T16 2-T16 2-T16 3-T16
+
3-T16
3-T16
8-2L-T8@150 C/C 7-2L-T8@125 C/C 9-2L-T8@125 C/C - DETAILS OF ST1
B37 230 450 3-T16 3-T16 2-T16 3-T16 3-T16 3-T16 6-2L-T8@100 C/C 4-2L-T8@100 C/C 6-2L-T8@100 C/C CANTILEVERED
Vastustruct....
+ + + +
3-T12 3-T16 3-T16 3-T16 Engineers & Structural Consultant
TYPICAL DETAILS OF BAR BENDING FOR SLABS & BEAM KARAD
B38 230 450 3-T12 3-T12 3-T12 2-T12 2-T12 2-T12 10-2L-T8@125 C/C 7-2L-T8@150 C/C 10-2L-T8@125 C/C -
+
2-T12

B39 230 450 2-T12 2-T12 2-T12 3-T16 3-T16 3-T16 6-2L-T8@100 C/C 5-2L-T8@100 C/C 7-2L-T8@100 C/C CANTILEVERED
+ + +
2-T12 2-T12 2-T12
1. USE M20 GRADE CONCRETE CONFIRMING I. S. CODE 456 NOTE:
B40 230 450 2-T12 2-T12 2-T12 3-T16 2-T16 3-T16 6-2L-T8@150 C/C 4-2L-T8@150 C/C 6-2L-T8@150 C/C - 2. USE Fe 500 GRADE STEEL CONFIRMING I.S. CODE 1786 EXCEPT
+
2-T12
+
3-T12
THE NUMBER OF PROPS LEFT UNDER,THEIR SIZES & DISPOSITION SHALL BE
6MM SHALL BE FE250 GRADE SUCH AS TO BE ABLE TO SAFELY CARRY THE FULL DEAD LOAD OF THE SLAB, BEAM
B41 230 450 2-T12 2-T12 2-T12 3-T16 3-T16 3-T16 6-2L-T8@125 C/C 4-2L-T8@125 C/C 7-2L-T8@100 C/C - 3. CENTERING DESIGN IS CONTRACTORS RESPONSIBILITY.
+ + OR ARCH AS THE CASE MAY BE TOGETHER WITH ANY LIVE LOAD LIKELY TO OCCUR
3-T12 2-T12
4. REFER THIS DRAWING WITH ARCHITECT’S DRAWING. DURING CURING OR FURTHER CONSTRUCTION. M. 09552514711.
B42 230 450 3-T12 3-T12 3-T12 3-T16 3-T16 3-T16 5-2L-T8@100 C/C 3-2L-T8@100 C/C 5-2L-T8@100 C/C CANTILEVERED
+ + + 5. CLEAR COVERS TO FOOTING =50MM, COLUMN = 40MM, BEAM = 25MM,
2-T16 2-T16 2-T16 email:vastustructkolhapur@gmail.com
SLAB = 20MM,LINTELS = 20MM 11. BEAMS HAVING SPAN MORE THAN 7M MUST SUPPORTED AT ITS MID.
B43 230 450 2-T12 2-T12 2-T12 2-T12 2-T12 2-T12 6-2L-T8@125 C/C 4-2L-T8@125 C/C 6-2L-T8@125 C/C -
6. FOR BEAMS HAVING DEPTH MORE THAN 750MM PROVIDE SIDE FACE 12. CONTRACTOR HAS TO TAKE CARER DURING WORKING WITH ANY ADJECENT
B44 230 450 3-T16 3-T16 3-T16 3-T12 3-T12 3-T12 11-2L-T8@125 C/C 9-2L-T8@125 C/C 11-2L-T8@125 C/C - REINFORCEMENT #8 @ 300 C/C ON BOTH FACES. STRUCTURE/BUILDING FOR ABUTTMENT, WE ARE NOT RESPONSIBLE FOR ANY
+
3-T12
7. LAPS TO COLUMN BAR = 45 X D. LAPS TO SLAB / BEAM = 69 X D. DAMAGE IF CAUSED TO ABUTTING BUILDINGS. DRAWING :
B45 230 450 2-T12 2-T12 2-T12 2-T12 2-T12 2-T12 3-2L-T8@100 C/C 1-2L-T8@100 C/C 3-2L-T8@100 C/C CANTILEVERED 8. FOR BEAMS HAVING WIDTH 150 MM OR LESS ONLY TWO 13. FOR CANTILIVER BEAMS, TOP REINFORCEMENT SHOULD BE ANCHORED BACK
B46 230 450 2-T12 2-T12 2-T12 2-T12 2-T12 2-T12 4-2L-T8@150 C/C 2-2L-T8@150 C/C 4-2L-T8@150 C/C - BARS TO BE PROVIDED IN ANY ONE LAYER. FOR 70XDIA OF BAR OR 1.5 X SPAN OF CANTILIVER WHICH EVER IS GREATER.
B47 230 450 2-T12 2-T12 2-T12 2-T12 2-T12 2-T12 3-2L-T8@125 C/C 1-2L-T8@125 C/C 3-2L-T8@125 C/C - 9. FOR BEAMS HAVING WIDTH 230 MM ONLY THREE
BARS TO BE PROVIDED IN ANY ONE LAYER.
14. STRATA SHOULD BE GOT APPROVED BEFORE CASTING OF FOUNDATION.
A
SECOND SLAB
B48 230 450 3-T12 3-T12 3-T12 3-T12 3-T12 3-T12 3-2L-T8@100 C/C 1-2L-T8@100 C/C 3-2L-T8@100 C/C CANTILEVERED
15. STEEL SHOULD BE GOT CHEKED BEFORE CONCRETING.
10. DESHUTTERING PEROID 16. ANY DISCREPANCY BETWEEN THIS DWG/ARCH DWG/SITE CONDITION
B49 230 450 3-T12 3-T12 3-T12 3-T12 3-T12 3-T12 4-2L-T8@150 C/C 2-2L-T8@150 C/C 4-2L-T8@150 C/C - a) VERTICAL FORMWORK TO COLUMN, WALL AND BEAMS IS 24 HRS SHOULD BE BROUGHT TO OUR NOTICE BEFORE EXECUTION. SCALE DRAWN DATE CHECKED
B50 230 450 3-T12 3-T12 3-T12 3-T12 3-T12 3-T12 7-2L-T8@125 C/C 5-2L-T8@125 C/C 7-2L-T8@125 C/C - b) SLAB (# - TOR SIGN, ST- STRAIGHT BAR, BT- BENT BAR.)
B52 230 450 3-T12 3-T12 3-T12 3-T12 3-T12 3-T12 5-2L-T8@150 C/C 3-2L-T8@150 C/C 5-2L-T8@150 C/C - i. SPANNING UPTO 4.5M = 7 DAYS 17. (TYP) #12 - 16 READ AS # BAR DIA - NO. BARS.
B53 230 450 3-T12 3-T12 3-T12 3-T12 3-T12 3-T12 8-2L-T8@150 C/C 8-2L-T8@125 C/C 10-2L-T8@125 C/C -
ii.SPANNING OVER 4.50M = 14DAYS 18. AT DISCONTINOUS EDGE OF THE SLAB PROVIDE #8 @ 300 C/C AS AN EXTRA TOP N.T.S. ASP 01.02.2024 MMK
+ c) BEAM AND ARCH
3-T12 REINFORCEMENT TO THE SLAB.
B54 230 450 3-T12 3-T12 3-T12
+
3-T12
3-T12
+
3-T12
3-T12
+
3-T12
3-T12
5-2L-T8@100 C/C 3-2L-T8@100 C/C 5-2L-T8@100 C/C CANTILEVERED TYP.STIRRUPS DETAIL i.SPANNING UPTO 6.00M = 14 DAYS
ii.SPANNING OVER 6.00M = 21 DAYS
19. ALL LAPS TO REINFORCMENT SHOULD BE STAGGERED ,SPLICING/LAPPING SHOULD
NOT MORE THAN 50%. BAR AT ANY SECTION
JOB No: DRAWING No. SHEET REVISION

B55 230 450 2-T12 2-T12 2-T12 2-T12 2-T12 2-T12 5-2L-T8@150 C/C 4-2L-T8@125 C/C 6-2L-T8@125 C/C -
2023 VS-111 A3 00