2.ELECTRICAL TESTS
2.1 Function Test
ITEM DESCRIPTION CHECKED
1. Test switch/plug checked for correct function. OK
2. Case earthing checked. OK
3 Indications checked. OK
4 Alarm LED checked. OK
5 Trip contacts checked. OK
3. ELECTRICAL TEST:
3.1 CURRENT MEASUREMENT:
CT ratio: 600/5
Applied Expected Displayed Primary Value (A)
Current Value R Y B
(A) (A)
1.25 150 150 149 149
2.50 300 299 299 298
3.75 450 449 448 450
5.00 600 600 598 598
Limit: ± 0 – 5 %
4. PHASE OVERCURRENT
Setting Injected Expected tripping time (sec) Actual tripping time (sec)
Current Current Remarks
R Y B R Y B
FORMULA:
PICK UP CURRENT:
TRIP TIMING:
Injected 8.40 A in Sec
Injected Expected tripping time (sec) Actual tripping time (sec)
Current Remarks
R Y B R Y B
5. EARTHFAULT
Setting Injected Expected tripping time (sec) Actual tripping time (sec)
Current Current Remarks
R Y B R Y B
EXAMPLE:
t(d) = 0.440*0.140/((1.0/0.5)^0.02 – 1)
= 0.0616/0.01395
= 4.4127 Sec
PICK UP CURRENT:
TRIP TIMING:
Injected 2.10 A in Sec
Injected Expected tripping time (sec) Actual tripping time (sec)
Current Remarks
R Y B R Y B
6. UNDER VOLTAGE
TRIP TIMING:
Injected 45V in Sec
Injected Expected tripping time (sec) Actual tripping time (sec)
Voltage Remarks
RY YB BR RY YB BR
7. OVER VOLTAGE
A. OVERVOLTAGE :
Threshold = 110.0 % Un Delay = 3.0s
NOTE: Voltage applied by √3 conversion = 121/√3
= 69.86
PICK UP VOLTAGE:
8. TEST EQUIPMENT
EQUIPMENT MODEL SERIAL NUMBER CALIBRATION DUE
FREJA FREJA 1402737 02/07/2024