Professional Documents
Culture Documents
Configuration UDC A12NO
Configuration UDC A12NO
GROUP PROMPT FUNCTION PROMPT FACTORY SETTING VALUE OR SELECTION GROUP PROMPT FUNCTION PROMPT FACTORY SETTING VALUE OR SELECTION
PB or GAIN 1.00 PIDSET ONE
RATE T 0.00 SW VAL 0
I MIN or I RPM 1.00 LSP'S ONE
MANRST 1.00 RSPRSC NONE
PB2 or GAIN 2 0.00 SP TRK NONE
RATE2 T 0.00 PWR UP AUTO
I2 MIN or I2 RPM 1.00 PWROUT FSAF
CYCT1 or CT1 20 SP HI 2400
TUNING X3 20 SP LO 0
CONTROL
CYCT2 or CT2 20 ACTION REV REV
X3 20 OUT HI 100 70
SECURE 0 OUT LO 0 30
LOCK NONE D BAND 2.0
AUTOMA ENAB HYST 0.5
A TUNE ENAB FAILSF 0.0 0.0
RN HLD ENAB FSMODE NOL
SP SEL ENAB PB or GN GAIN
SPRAMP DIS MINRPM MIN
T1 MIN 3 AUXOUT DIS OUT
FINLSP 1000 ARANGE 4-20 4-20
SPRATE DIS 0 PCT 0
SPRAMP EUHRUP 0 100 PCT 100
OPTION
EUHRDN 0 DIG IN 1 NONE MNFS
SPPROG DIS DIG1 COM DIS
DIG IN 2 NONE
DIG2 COM DIS
FUZZY DIS ComSTA Disable
TUNE TUNE ComADD 0
DUPLEX MAN SDENAB Enable
ATUNE
AT ERR IRENAB Enable
SHDTIM 0
BAUD 9600
CTRALG PIDA TX_DLY 30
COM
TIMER DIS WS_FLT FP_B
PERIOD 0:01 SDMODE Last
START KEY SHDSP LSP
ALGOR L DISP TREM UNITS PCT
RESET KEY CSRATO 1
INCRMT MIN CSP BI 0
LOOPBACK Disable
A1S1TY NONE IN 1
OUTALG (MOXL) CURRENT A1S1VA 90 1800
CRANGE 4-20 4-20 A1S1HL HIGH HIGH
RLY TY MECH A1S1EV BEGN
OUTALG
MTRTI 5 A1S2TY NONE
A1S2VA 90
A1S2HL HIGH
IN1TYP KH KH A1S2EV BEGN
XMITR1 LIN A2S1TY NONE
IN1 HI 2400 2400 A2S1VA 90
ALARMS
IN1 LO 0 0 A2S1HL HIGH
RATIO1 1.00 1.00 A2S1EV BEGN
INPUT1 BIAS 1 0.00 0.00 A2S2TY NONE
FILTR1 1.00 1.00 A2S2VA 90
BRNOUT UP UP A2S2HL HIGH
EMIS 1 0 A2S2EV BEGN
ALHYST 0.0
ALARM1 NOL
IN2TYP 1-5V DIS BLOCK DIS
XMITR2 LIN DIAGAL DIS
IN2 HI 2400 DECMAL NONE
IN2 LO 0 UNITS F
INPUT2 RATIO2 1.00 FREQ 60
BIAS 2 0.00 DISPLY DISPLY SP
FILTR2 1.00 LWRDSP ENAB
LNGUAG ENGL
TCDIAG ENAB