Professional Documents
Culture Documents
SolarSpan & InsulRoof Patio Engineering Guide v4
SolarSpan & InsulRoof Patio Engineering Guide v4
SolarSpan & InsulRoof Patio Engineering Guide v4
Contents
Technical Data
Packing for Shipment
SolarSpan® & InsulRoof® sheets are packed to a maximum pack height of 1.2m
with the number of panels per pack dependant on panel thickness, length and
overall pack weight. SolarSpan® & InsulRoof® panels are manufactured with
2m Max
a protective film applied to the ceiling skin. SolarSpan® & InsulRoof® panels
can be marked externally on the insulated core with the panel number and/or
length, on request.
Delivery to Site
Panel packs should be secured using cargo straps spaced approximately Figure 1a Figure 1b
every 2m with 600mm plastic cargo angles under the straps (refer to Figure
1a). Long 600mm angles must be place on top and bottom of panel pack to
protect from straps. Do not overtighten straps, no depression in panel should
be seen, back off on strap tension, panel skin should be flat (refer to Figure
1b). Unloading remains the client’s responsibility. For lifting panels greater than
8m in length, use of a spreader bar is recommended (refer to Figures 1c & d).
Refer to Figures 1e & 1f for recommended steps to unload panels of less than
and greater than 8m in length. Panels should always be kept dry and if placed
on site, stored off the ground, slightly inclined, allowing adequate drainage and
ventilation of the panel pack.
Figure 1c Figure 1d
Figure 1e Figure 1f
Certification
Andrew Morrison
RPEQ 12942
19 Sept 2019
Certification
Andrew Morrison
RPEQ 12942
19 Sept 2019
Overview
The SolarSpan® & InsulRoof® Patio Engineering Guide and stamped local Building certification material has been provided for generic SolarSpan® & InsulRoof®
patio structures only which is based on the structural capacity determined through physical testing in accordance with the relevant Australian Standards. Other
products will perform differently due to differences in steel and core material selection, manufacturing methods and testing.
Introduction
This document is to be used in accordance with current Australian building standards. Please note, it is the licensed builder’s responsibility to ensure structural
adequacy of any existing structures are determined before attaching a SolarSpan® or InsulRoof® structure.
Please note for accurate capacity calculation, the formulas throughout this document must be completed and resulting values transposed to the Summary Table
of Engineering Calculations.
Below is an example of the formula calculation boxes you will find on most sections.
Example Only
STEP 4.1: Beam Load Width
A (patio roof span to beam) B (patio roof overhang)
Y
Load Width on beam = (0.5 x A) + B (mm)
L
A (0.5xA) B (mm) Load Width on beam (mm)
0.5 x Equals Plus Equals
N
(mm) (mm) Enter at Step 4 Enter at Step 4.1
E O 1250
P L
M
Summary of patio information selected
A
Step Step Page Figure from Formula Unit of Measurement
4.1
E X
Determine Load Width on beam 12
1250 mm
Certification
Andrew Morrison
RPEQ 12942
19 Sept 2019
Engineering Calculations
Summary of patio information selected
N1 C1
Wind Classification Determination N2 C2
1 (N1, N2, N3, N4, C1, C2, C3)
7
N3 C3
-
N4
SolarSpan®
2 Product & Panel Thickness 8/9
InsulRoof®
-
Case A
Case B
3 Case Type & Max Span 10/11 Case C mm
Case D
Case E
In Ground Footing
6.3 Post to Ground Connection Type 18/19 Footing with Slab Over -
On Slab Footing
For Metal Fascias (7.1)
For Timber Fascias (7.2)
7 Patio to House Connection Type 20/21 Offset Post (7.3) -
Andrew Morrison
RPEQ 12942
19 Sept 2019
50 0kmm
Smoothed
10 50k
1
km
Coastline
10 0km
m
(D)
0k
5
This section is a simplification of AS 4055:2012 (B)
Cairns (C)
Atherton (B)
Smoothed
Coastline
for the selection of a design Wind Classification Broome (C)
(B)
20˚ Townsville (C)
Exmouth (D)
Bundaberg (C) 25˚
Refer to AS 4055:2012 for more information. 25˚ Carnarvon (D)
Brisbane (B)
Toowoomba (A)
27˚
Refer to AS/NZS 1170.2:2012 for other application. 100km
100km
30˚
30˚ Geraldton (B) Kalgoorlie (A)
Geelong (A)
Launceston (A)
Location Classification
Shielded on flat terrain in suburban area Unshielded on gentle terrain in urban area Unshielded in suburban area.
REGION A - N1(W34), REGION B - N2 (W40) REGION A - N3 (W50), REGION B - N4 (W61) REGION A - N2 (W40), REGION B - N3 (W50) and
and REGION C - C1 (W50) and REGION C - C3 (W74) REGION C - C2 (W61)
Shielded on gentle terrain in suburban area Unshielded on steep terrain in urban Unshielded next to seafront
REGION A - N2 (W40), REGION B - N3 (W50) and on the crest of a hill REGION A - N3 (W50), REGION B - N4 (W61)
REGION C - C2 (W61) REGION A - N4 (W61) and REGION C - C3 (W74)
Wind Classification
Terrain Type
Wind Region Terrain Flat Gentle Steep
Shielded Not Shielded Shielded Not Shielded Shielded Not Shielded
Suburban N1 N1 N1 N2 N2 N2
A Rural N1 N2 N2 N3 N2 N3
Coastal N2 N2 N2 N3 N3 N3
Suburban N2 N3 N2 N3 N3 N4
B Rural N2 N3 N3 N4 N3 N4
Coastal N3 N4 N3 N4 N4 N4
Suburban C1 C2 C1 C3 C3 -
C Rural C1 C2 C2 - - -
Coastal C2 C3 C2 - - -
Suburban C2 C3 C2 - - -
D Rural C3 - C3 - - -
Coastal C3 - - - - -
Note: Suburban - Average spacing of surrounding houses or buildings 30m or less. Rural - Average spacing of surrounding houses or buildings greater than 30m. Coastal - Within 500mm of
the ocean or large body of water larger than 10km in any direction. Flat - less than 1:20 surrounding slopes. Gentle - Between 1:20 and 1:1 surrounding slopes. Steel - Between 1:10 and 1:7.5
surrounding slopes.
Andrew Morrison
RPEQ 12942
19 Sept 2019
Surfmist® Paperbark® Classic Cream™* Pale Eucalypt® Manor Red®** Dune® Shale Grey® Basalt®^ Woodland Grey®^**
Certification
Surfmist® Paperbark® Classic Cream™* Pale Eucalypt® Manor Red®** Dune® Shale Grey® Basalt®^ Woodland Grey®^** Zincalume™
Certification
STEP 3: SolarSpan ®
Max Roof Span Certification
STEP 3: InsulRoof ®
Max Roof Span Certification
Roof Fall:
• 2˚min SolarSpan®
Beam Span • 5˚min InsulRoof®
Case A Case B Case C Case D Case E Case A Case B Case C Case D Case E
3 Open 2 Open 1 Open Fully Free 3 Open 2 Open 1 Open Fully Free
Load Load
Wind Sides Sides Side Enclosed Standing Wind Sides Sides Side Enclosed Standing
Width Width
Category A A A A A Category A A A A A
(mm) (mm)
Max. Max. Max. Max. Max. Max. Max. Max. Max. Max.
Span Span Span Span Span Span Span Span Span Span
1500 0.91 1.73 2.07 2.23 0.91 1500 1.42 2.7 3.24 4.86 1.42
2100 1.28 2.42 2.9 3.12 1.28 2100 1.98 3.78 4.54 6.8 1.98
2700 1.64 3.11 3.73 4.02 1.64 2700 2.55 4.86 5.83 8.75 2.55
3300 2.01 3.8 4.56 4.91 2.01 3300 3.12 5.94 7.13 10.69 3.12
3900 2.37 4.49 5.39 5.8 2.37 3900 3.69 7.02 8.42 12.64 3.69
4500 2.73 5.18 6.22 6.7 2.73 4500 4.25 8.1 9.72 14.58 4.25
5100 3.1 5.88 7.05 7.59 3.1 5100 4.82 9.18 11.02 16.52 4.82
N1/N2 C1
5700 3.46 6.57 7.88 8.48 3.46 5700 5.39 10.26 12.31 18.47 5.39
(W55N) (W41C)
6300 3.83 7.26 8.71 9.37 3.83 6300 5.95 11.34 13.61 20.41 5.95
6900 4.19 7.95 9.54 10.27 4.19 6900 6.52 12.42 14.9 22.36 6.52
7500 4.56 8.64 10.37 11.16 4.56 7500 7.09 13.5 16.2 24.3 7.09
8100 4.92 9.33 11.2 12.05 4.92 8100 7.65 14.58 17.5 26.24 7.65
8700 5.29 10.02 12.03 12.95 5.29 8700 8.22 15.66 18.79 28.19 8.22
9000 5.47 10.37 12.44 13.39 5.47 9000 8.5 16.2 19.44 29.16 8.5
9600 5.83 11.06 13.27 14.28 5.83 9600 9.07 17.28 20.74 31.1 9.07
1500 1.42 2.7 3.24 3.49 1.42 1500 2.11 4.01 4.82 7.23 2.11
2100 1.99 3.78 4.54 4.88 1.99 2100 2.95 5.62 6.74 10.12 2.95
2700 2.56 4.86 5.83 6.28 2.56 2700 3.79 7.23 8.67 13.01 3.79
3300 3.13 5.94 7.13 7.67 3.13 3300 4.64 8.83 10.6 15.9 4.64
3900 3.7 7.02 8.42 9.07 3.7 3900 5.48 10.44 12.52 18.79 5.48
4500 4.27 8.1 9.72 10.46 4.27 4500 6.32 12.04 14.45 21.68 6.32
5100 4.84 9.18 11.02 11.86 4.84 5100 7.16 13.65 16.38 24.57 7.16
N3 C2
5700 5.41 10.26 12.31 13.25 5.41 5700 8.01 15.25 18.3 27.46 8.01
(W41N) (W50C)
6300 5.98 11.34 13.61 14.65 5.98 6300 8.85 16.86 20.23 30.35 8.85
6900 6.55 12.42 14.9 16.04 6.55 6900 9.69 18.46 22.16 33.24 9.69
7500 7.12 13.5 16.2 17.44 7.12 7500 10.54 20.07 24.08 36.13 10.54
8100 7.69 14.58 17.5 18.83 7.69 8100 11.38 21.68 26.01 39.02 11.38
8700 8.26 15.66 18.79 20.23 8.26 8700 12.22 23.28 27.94 41.91 12.22
9000 8.55 16.2 19.44 20.93 8.55 9000 12.64 24.08 28.9 43.35 12.64
9600 9.12 17.28 20.74 22.32 9.12 9600 13.49 25.69 30.83 46.24 13.49
1500 2.12 4.01 4.82 5.18 2.12 1500 3.1 5.9 7.08 10.63 3.1
2100 2.96 5.62 6.74 7.26 2.96 2100 4.34 8.27 9.92 14.88 4.34
2700 3.81 7.23 8.67 9.33 3.81 2700 5.58 10.63 12.75 19.13 5.58
3300 4.66 8.83 10.6 11.41 4.66 3300 6.82 12.99 15.59 23.38 6.82
3900 5.51 10.44 12.52 13.48 5.51 3900 8.06 15.35 18.42 27.63 8.06
4500 6.35 12.04 14.45 15.55 6.35 4500 9.3 17.71 21.25 31.88 9.3
5100 7.2 13.65 16.38 17.63 7.2 5100 10.54 20.07 24.09 36.13 10.54
N4 C3
5700 8.05 15.25 18.3 19.7 8.05 5700 11.78 22.44 26.92 40.38 11.78
(W50N) (W60C)
6300 8.89 16.86 20.23 21.78 8.89 6300 13.02 24.8 29.76 44.63 13.02
6900 9.74 18.46 22.16 23.85 9.74 6900 14.26 27.16 32.59 48.89 14.26
7500 10.59 20.07 24.08 25.92 10.59 7500 15.5 29.52 35.42 53.14 15.5
8100 11.43 21.68 26.01 28 11.43 8100 16.74 31.88 38.26 57.39 16.74
8700 12.28 23.28 27.94 30.07 12.28 8700 17.98 34.24 41.09 61.64 17.98
9000 12.7 24.08 28.9 31.11 12.7 9000 18.6 35.42 42.51 63.76 18.6
9600 13.55 25.69 30.83 33.18 13.55 9600 19.84 37.79 45.34 68.01 19.84
Notes:
1. Linear interpolation is permitted between Load Width values in the table.
2. Enclosure Case A, B, C & D are defined on sheet 1 (Patio Roof enclosure Case Table).
Wind Classification Load Width (mm) Case Equals Enter at Step 4.2
Andrew Morrison
RPEQ 12942
=
19 Sept 2019
Single Span
Multi-span
Andrew Morrison
RPEQ 12942
19 Sept 2019
Post Option B
- Multi-Span
End Post Beam Intermediate Post End Post with Beam Overhang
0.5 x =
Load Width on Intermediate Post (for Multi-Span only) = 0.5 x (A+B) (m)
Load Width on Intermediate Post (m)
A (m) Plus B (m) Equals (A+B) x 0.5 Equals
Enter at 6.1.2
+ = x 0.5 =
0.5 x = + =
Maximum Uplift on Post (kN) = Maximum Post Load Width (m) x Uplift Load on Beam (kN/m) from Step 4.2
6.1.3 Load Width
6.1.1 Load 6.1.2 Load Width Maximum Value Maximum Uplift
on End Post with
Maximum of Width on End or on Intermediate or Equals Post Load x from Equals on Post (kN)
Beam Overhang
Post (m) Post (m) Width Step 4.2 Enter at Step 6.1.4
(m)
MAX ( , , ) = x
Certification
Andrew Morrison
RPEQ 12942
19 Sept 2019
Steel G250 2 10 20 30 40
Andrew Morrison
RPEQ 12942
19 Sept 2019
(A) R.H.S. Post to R.H.S. Beam Joint (B) Timber Post to Beam Joint
Tek Screw Type 17 Tek Screw
with Cyclone Assembly with Cyclone Assembly
60
SolarSpan® / InsulRoof® Panel
Bolt (Refer Table)
50
4mm Steel Angle
Bolts (Refer Table)
Timber Beam
Steel Post (Min. 50x50x3) Timber Post
(Min. 90x90xF7)
(C) Notched Post to Roll Formed Beam Joint (D) Proprietary Systems
Tek Screw Tek Screw
with Cyclone Assembly with Cyclone Assembly
6mm Steel
50
50
50
100
300
300
“D”
“D”
200
200
W W
100
300
300
“D”
200
200
W W
Certification
Notes:
Hold down capacity applies to piers with an undercut into cohesive clay soils. Use post footings for sandy sites.
For footings with depth (D) greater than 500, reinforce the footing with 4/N12 vertical rods tied with R6 ligs at 500 CRS.
Concrete slab must be a minimum of 100mm thick, 20Mpa concrete reinforced with SL72 mesh and must extend for the full area covered by the
SolarSpan® or InsulRoof® roof.
IN GROUND FOOTING (CLAY SOIL) W = 450mm DIA. FOOTING WITH SLAB OVER (CLAY SOIL) W = 450mm DIA.
Hold Down Capacity (kN) Footing without Slab Over - Depth D (mm) Bolts/DIA. (mm) Hold Down Capacity (kN) Footing with Slab Over - Depth D (mm)
3.5 500 2/M10 or 1/M12 15.0 500
8.5 750 2/M12 or 1/M16 19.5 750
14.0 1000 2/M16 23.5 1000
22.0 1250 2/M20 27.0 1250
Certification
Notes: Sofit
A
3. The uplift capacity of the house fascia connections apply to the SolarSpan® &
InsulRoof® Receiver Channel connection only. The Load Capacity and suitability
of the members and connections below the rafter are to be assessed and
strengthened if required.
4. It is the responsibility of the builders and engineers to determine the capacity Beam
of the existing structures.
InsulRoof®
Existing Gutter Flashing to Panel
& Fasica Builders Details
Flashing
Existing Roof Rafter
M12 Bolt (Refer to
Table for spacing)
ø 4mm Rivets @ 300 Reciever Channel
CRS. Fix Reciever
7.2 For Timber Fascias Channel to InsulRoof®
or SolarSpan® Panel
Notes:
1. Refer to AS 1684 - Timber Framing Code for attaching pergola or
carport to house.
2. Connect SolarSpan & InsulRoof Receiver Channel as per carport/pergola
as shown in that publication. Certification
3. Alternatively, connect as for Metal Fascias above.
50x3.0 SHS
100 (Min.)
6mm Base Plate Fixed to Concrete Slab with 2/M12-75 Chemset Anchors
7.4 Removed Fascia & Soffit
Uplift Capacity of Receiver Channel
Rafter Spacing (mm)
to Rafter Connection (kN/m)
600 6 Rafter
900 4 InsulRoof® or
1200 3 SolarSpan® Panel
Flashing
Notes:
1. Cut back rafter tails as shown.
2. Fix new fascia to each rafter tail with 2-75mm batten screws.
3. Fix SolarSpan® & InsulRoof® Receiver Channel to fascia with No.14 Type 17 Fix Reciever Channel
screws at 300 CRS. to InsulRoof® or
SolarSpan® Panel via
ø 4mm Rivets
@ 300 CRS.
7.5 Brick / Masonry Wall
Uplift Capacity of Receiver Channel
Shuredrives Spacing (mm)
to Wall Connection (kN/m) 6mm Shuredrives 300 or 200 CRS
Min. 1.5m
300 2.5 InsulRoof® or
(Brickwork)
200 3.5 Flashing SolarSpan® Panel
Notes:
Do not attach brickwork with less than 1.5m of brickwork over unless brickwork
is positively tied down with anchor rods. Otherwise separate tie-down structure
is required. ø 4mm Rivets @ 300 CRS. Fix Reciever
Channel to InsulRoof® or SolarSpan® Panel
Certification
Andrew Morrison
RPEQ 12942
19 Sept 2019
50 125mm 125mm
75 150mm 150mm
Fixing Recommendations
SolarSpan® roofing side laps should be laid away from the prevailing wind and sit neatly on the preceding roof sheet. Refer to SolarSpan® Patio Engineering for
fixing details. Fascia gutter flashings should be fixed using sealed rivets in the valley.
Non Cyclonic Fixing - Through Each Rib* Screw with Cyclone Assembly Lapping
Side Lap Capillary Groove
Services Duct
up to 21.6 kN/m Screws as per (a) above, plus two screw with cyclone assembly per pan (between ribs)
Certification
Andrew Morrison
RPEQ 12942
19 Sept 2019
50 100mm 125mm
75 125mm 125mm
100 175mm 150mm
125 200mm 175mm
150 240mm 205mm
200 300mm 300mm
Side Lap
Services Duct Certification
Andrew Morrison
RPEQ 12942
19 Sept 2019
Slip Joint
Ridge Post
Ridge Beam
Roof Slope
Ridge Post
Post Inner Beam
Gable Beam
Outer Beam
Post Post
Ga th
ble eng
Wid leL
th Gab
Post
RF170x75
Ridge Combination Beam
M12 Bolt
Certification
Andrew Morrison
RPEQ 12942
19 Sept 2019
** Limited availability. ^ Darker colours warranted for use in limited regions. Metecno Pty Limited. ABN 44 096 402 934. The manufacturer reserves the right to change the specification without notice. Bondor®,
DesignerWall® and Metecno are trademarks of Metecno Pty Limited. BlueScope, Colorbond® and colour names are trademarks of BlueScope Steel Limited. The colours shown in this publication have been reproduced
to represent actual product colours as accurately as possible. However, given printing limitations, we recommend checking your chosen colour against an actual sample before placing orders. This advice is of a general
nature only. Designers must provide for adequate structural performance and other Building Code requirements. This information is subject to change. Refer to Bondor® website for latest version. Consult Bondor® for your
application. BON0509 SolarSpan & InsulRoof Patio Engineering Guide v4 18/09/2019