47-Division 16-Section 16650 Tag Numbering Convention-Version 2.0
47-Division 16-Section 16650 Tag Numbering Convention-Version 2.0
(ADSSC)
DIVISION 16 ELECTRICAL
TAG Numbering
ADSSC/GSEW Division 16 Section 16650 Rev: 02 Jan. 2011 Page 1 of 7
Convention
General Specification for Electrical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
03
04
05
06
07
08
09
10
TAG Numbering
ADSSC/GSEW Division 16 Section 16650 Rev: 02 Jan. 2011 Page 2 of 7
Convention
General Specification for Electrical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
TABLE OF CONTENTS
1. INTRODUCTION .......................................................................
2. SCOPE ..............................................................................
TAG Numbering
ADSSC/GSEW Division 16 Section 16650 Rev: 02 Jan. 2011 Page 3 of 7
Convention
General Specification for Electrical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
1. INTRODUCTION
2. SCOPE
3. VARIABLE DEFINITIONS
a) Variables are the most basic unit of information within a Citect system.
Every I/O device point monitored by the Citect run-time system must
have a variable tag defined for that point within Citect. Each I/O device
point is a memory location within an I/O device, and Citect exchanges
information with I/O devices by reading and writing variables.
b) Each I/O device point has a unique register address and the variable tag
definition within Citect is a label used to reference this register address.
The variable tag name should be a meaningful description of the point
being monitored. Citect variables are defined via the ‘Variable Tags’
form, accessible from the Citect Project Editor Development
environment.
c) Variable tags are used for performing the following tasks within Citect:
d) It should be noted that the variable tags are used during system
configuration. In the runtime system, the variable tag name is not
actually displayed, so the tag naming and structure is of no concern to a
normal operator. Users with higher privileges are able to determine
variable tag names at runtime to allow system debugging, if required.
TAG Numbering
ADSSC/GSEW Division 16 Section 16650 Rev: 02 Jan. 2011 Page 4 of 7
Convention
General Specification for Electrical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
a) The variable tag naming conventions shall follow the same conventions
used for the site electrical drawings, which are based on the following
Function Symbol Schedule.
TAG Numbering
ADSSC/GSEW Division 16 Section 16650 Rev: 02 Jan. 2011 Page 5 of 7
Convention
General Specification for Electrical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
Letter Measured Or Initiating Variable Modifier Readout Or Passive Output Function MODIFIER
Function
A ANALYSIS ALARM
B BURNER
C CONDUCTIVITY (ELECTRICAL) CONTROL CLOSE
DENSITY OR SPECIFIC
D DIFFERENTIAL
GRAVITY
E VOLTAGE (EMF) PRIMARY ELEMENT
F FLOWRATE RATIO (FRACTION)
G GAUGING GLASS
H HAND (MANUALLY INITIATED) HIGH
I CURRENT (ELECTRICAL) INDICATE
J POWER SCAN
K TIME OR TIME SCHEDULE TIME RATE OF CHANGE CONTROL STATION
L LEVEL LIGHT (PILOT) LOW
M MOTOR MOMENTARY MID
N IGNITER
O OPERATION OFFSET ORIFICE (RESTRICTION) OPEN
P PRESSURE OR VACUUM
INTEGRATE OR
Q QUANTITY OR EVENT
TOTALIZE
R RADIATION RECORD OR PRINT
S SPEED OR FREQUENCY SAFETY SWITCH
T TEMPERATURE THERMAL TRANSMIT
MULTI-
U MULTI-VARIABLE TREND MULTI-FUNCTION MULTI-FUNCTION
FUNCTION
V VIBRATION VALVE DAMPER OR LOUVER
W WEIGHT FORCE OR TORQUE WELL
X UNCLASSED VARIABLE SPECIAL
Y EVENT STATE OR PREGENCE RELAY OR COMPUTE
DRIVE ACTUATOR OR UNCLASSIFIED FINAL CONTROL
Z POSITION
ELEMENT
ADSSC/GSEW Division 16 Section 16650 TAG Numbering Convention Rev: 02 Jan. 2011 Page 6 of 7
General Specification for Electrical Works
Abu Dhabi Sewerage Services Company
(ADSSC)
END OF SECTION
TAG Numbering
ADSSC/GSEW Division 16 Section 16650 Rev: 02 Jan. 2011 Page 7 of 7
Convention