The document summarizes issues with various transmission equipment in the SWH zone of Tanzania and proposes replacements. It notes circuit breaker failures on 220kV transformers that are beyond repair. It also describes problems with aging 33kV oil circuit breakers and recommends replacing them. Additional upgrades are proposed for 33kV equipment at Kyela switch station to improve reliability. The engineer requests further action and submits the report for the manager's information.
Original Description:
Original Title
Report for Request 220kv & 33kv Circuit Breakers Swh Zone 2023
The document summarizes issues with various transmission equipment in the SWH zone of Tanzania and proposes replacements. It notes circuit breaker failures on 220kV transformers that are beyond repair. It also describes problems with aging 33kV oil circuit breakers and recommends replacing them. Additional upgrades are proposed for 33kV equipment at Kyela switch station to improve reliability. The engineer requests further action and submits the report for the manager's information.
The document summarizes issues with various transmission equipment in the SWH zone of Tanzania and proposes replacements. It notes circuit breaker failures on 220kV transformers that are beyond repair. It also describes problems with aging 33kV oil circuit breakers and recommends replacing them. Additional upgrades are proposed for 33kV equipment at Kyela switch station to improve reliability. The engineer requests further action and submits the report for the manager's information.
REPLACEMENT AND INSTALLING OF NEW 33KV EQUPMENTS Please refer to the above heading.
SN CIRCUIT DESCRIPTION REMARKS/ACTION/TASKS/IS
BREAKERS FAILURE/EVENTS SUES 1 2X23MVA,220/33KV Since 2010 these breaker has These breakers are single pole & Transformers(T1&T2) developed different problems. single mechanism. 220KV Operation failure during The breaking chambers and the Mufindi/Makambako the closing/opening. operating mechanism are totally Line and 220KV (Auto-Reclosing enclosed and assembled therefore it’s Iringa/Kidatu Line function operate). not accessible for the case of The C-O-C or O-C-O maintenance. Manufacture: Nuova Operations lead to have Magrini Galileo S.p.a Low SF6 Gas due to 2X23MVA,220/33kV Transformers at worn out of rings Tagamenda and 35MVA,220/33KV Type:SB6 245 Occasionally, tendency Transformer at Mufindi substation are to have partial in operation with these CB’s. Man Year:2002 closing/open Despite the fact it’s not recommended Frequency Burnt out of (technical) for the healthiness of our Electronics Card. equipment’s Fail to close all pole for the same time (Pole On 2022 year, we have already Discrepancy) due to the replace 2 Set for the same type with delaying of refilling air relative problems (1set for pressure 60MVA,220/33KV Transformer at All DC/AC INVERTERS Mwakibete substation and 1 Set on are defective and its 220KV Mufindi/Iringa Line at Mufindi substation) beyond repair Early 2019 220KV Pole Red Phase for (availability of spare 35MVA,220/33KV Transformer was parts). replaced due to the closing/opening failure.
Occasionally, we have replaced the
electronics card on the existing CB’s. (220kV Iringa/Kidatu line at Tagamenda substation and 35MVA,220/33KV Transformer at Mufindi substation)
The CB’s Type is very old technology
and no spare part in the market today.
These equipment’s are not included in
TTGUP project. 33kV Tunduma and The following problem was The 33/33kV Songwe switch station Kamsamba feeders developed since installation was constructed with old/aged Old Oil Circuit and commissioning equipment’s (Circuit breakers, breaker TAKAOKA Frequency oil Leakage Disconnector, CT’s, Gantries and Types at Songwe Frequency mechanism associated materials) and full of Switch station failure(Closing/Opening) fabrications Frequently burnt out of Since the commissioning of on 2019, Spring charging motors we have already replace the Burn of closing coil mechanism on 33kV Kamsamba It’s very old and oil type feeder and replace Red phase pole due to the oil leakage. Attending the failure of close/open operation
These equipment’s are not included in
TTGUP project. 33kV Equipment’s Since the commissioning early of (CB’s, Disconnector, 1990’s Kyela Switch station was CT’s and PT’s) for constructed with incoming bay (Only 33/33KV Kyela 33kV Disconnector) and one (1) 33kV Switch station outgoing Bulk oil circuit breaker.
Since 2019 we have succeeded to
improve the switch station by. Replace the Old Bulk oil 33kV circuit breaker with SF6 Type. Installing of new 33kV feeder for Kasumulu border. Installing of new 33kV Ipinda feeder. Addition of aggregate Requirement for the upgrading and maintaining the switch station equipment’s Installing of 33kV for incoming bay and new 33kV feeder for Ngonga Mwamnyange feeder. Switch station repainting Installing of these equipment’s will eliminate the power interruption to our customers (along the Kyela feeder from Tukuyu substation).
These equipment’s are not included in
TTGUP project.
Submitted for your information and further action.