TANZANIA ELECTRIC SUPPLY COMPANY LIMITED

From: Zonal Principal Engineer To: Manager Transmission


Transmission – SWH Zone Substations

Our Ref: MTS/ZPTE/SWHZ/2023/02 Date: 26th Feb, 2023

RE: IMPROVEMENT OF POWER REALIBILITY IN SWH ZONE


REGIONALS (IRINGA, MBEYA AND SONGWE)

Sub: REPORT FOR PROPOSED 220kV CIRCUIT BREAKERS


REPLACEMENT AND INSTALLING OF NEW 33KV EQUPMENTS
Please refer to the above heading.

SN CIRCUIT DESCRIPTION REMARKS/ACTION/TASKS/IS


BREAKERS FAILURE/EVENTS SUES
1 2X23MVA,220/33KV Since 2010 these breaker has These breakers are single pole &
Transformers(T1&T2) developed different problems. single mechanism.
220KV  Operation failure during The breaking chambers and the
Mufindi/Makambako the closing/opening. operating mechanism are totally
Line and 220KV (Auto-Reclosing enclosed and assembled therefore it’s
Iringa/Kidatu Line function operate). not accessible for the case of
 The C-O-C or O-C-O maintenance.
Manufacture: Nuova Operations lead to have
Magrini Galileo S.p.a Low SF6 Gas due to 2X23MVA,220/33kV Transformers at
worn out of rings Tagamenda and 35MVA,220/33KV
Type:SB6 245  Occasionally, tendency Transformer at Mufindi substation are
to have partial in operation with these CB’s.
Man Year:2002 closing/open Despite the fact it’s not recommended
 Frequency Burnt out of (technical) for the healthiness of our
Electronics Card. equipment’s
 Fail to close all pole for
the same time (Pole On 2022 year, we have already
Discrepancy) due to the replace 2 Set for the same type with
delaying of refilling air relative problems (1set for
pressure 60MVA,220/33KV Transformer at
 All DC/AC INVERTERS Mwakibete substation and 1 Set on
are defective and its 220KV Mufindi/Iringa Line at Mufindi
substation)
beyond repair Early 2019 220KV Pole Red Phase for
(availability of spare 35MVA,220/33KV Transformer was
parts). replaced due to the closing/opening
failure.

Occasionally, we have replaced the


electronics card on the existing CB’s.
(220kV Iringa/Kidatu line at
Tagamenda substation and
35MVA,220/33KV Transformer at
Mufindi substation)

The CB’s Type is very old technology


and no spare part in the market today.

These equipment’s are not included in


TTGUP project.
33kV Tunduma and The following problem was The 33/33kV Songwe switch station
Kamsamba feeders developed since installation was constructed with old/aged
Old Oil Circuit and commissioning equipment’s (Circuit breakers,
breaker TAKAOKA  Frequency oil Leakage Disconnector, CT’s, Gantries and
Types at Songwe  Frequency mechanism associated materials) and full of
Switch station failure(Closing/Opening) fabrications
 Frequently burnt out of Since the commissioning of on 2019,
Spring charging motors we have already replace the
 Burn of closing coil mechanism on 33kV Kamsamba
 It’s very old and oil type feeder and replace Red phase pole
due to the oil leakage.
Attending the failure of close/open
operation

These equipment’s are not included in


TTGUP project.
33kV Equipment’s Since the commissioning early of
(CB’s, Disconnector, 1990’s Kyela Switch station was
CT’s and PT’s) for constructed with incoming bay (Only
33/33KV Kyela 33kV Disconnector) and one (1) 33kV
Switch station outgoing Bulk oil circuit breaker.

Since 2019 we have succeeded to


improve the switch station by.
 Replace the Old Bulk oil 33kV
circuit breaker with SF6 Type.
 Installing of new 33kV feeder
for Kasumulu border.
 Installing of new 33kV Ipinda
feeder.
 Addition of aggregate
Requirement for the upgrading and
maintaining the switch station
equipment’s
 Installing of 33kV for incoming
bay and new 33kV feeder for
Ngonga Mwamnyange feeder.
 Switch station repainting
Installing of these equipment’s will
eliminate the power interruption to our
customers (along the Kyela feeder
from Tukuyu substation).

These equipment’s are not included in


TTGUP project.

Submitted for your information and further action.

Eng. Nuru Twaha.


ZPTE – SWH Zone