O&M Manual For Ms DAICEL SAFETY SYSTEM AHU CONTROL PANEL 17OCT2022 by Azbil India
O&M Manual For Ms DAICEL SAFETY SYSTEM AHU CONTROL PANEL 17OCT2022 by Azbil India
1|Page
Azbil India Private Limited
2|Page
Azbil India Private Limited
AHU-1/2 Retun Air Relative Humidity: 50%RH (14 C dew point) or lower
3|Page
Azbil India Private Limited
2. Inside the Panel, confirm if all the MCCBs & MCBs are ON;
4. Set and confirm AHU-1/2 Return Air Temperature & Humidity Set Point;
RL1-RL6
Then,
Return Air Constant Temperature & Constant Humidity Control must work;
4|Page
Azbil India Private Limited
But OFF Delay remains for 10 minutes in order to prevent Heater from Fire
Buzzer will sound and continue sounding till pushing the PB1 for a second
5|Page
Azbil India Private Limited
Procedure of Recovery from Forced shutdown due to Fire & EMG stop
Even if Fire signal is gone and Emergy Stop Button Latch is released, AHU-1/2
Push PB1 button for more than 10 seconds, and all the forced sutdown
Then,
6|Page
Azbil India Private Limited
TIC-1/2-1: AHU-1/2 Return Air Temperature Controller PXF9AEY2-1VM00
PV input: Duct Insertion Temperature& Humidity sensor (HTY7805T1P00)
PV Range: 0 to 150 °C (Pt100)
SP(SV) : 24°C or settable
Proportional Band: 2 K(1.3%); Integral Time: 300 sec
MV output: Reverse Action
Modbus Device ID: 1 and 5
HI-1/2: AHU-1/2 Return Air Humidity Controller PXF9AEY2-1VM00
PV input: Duct Insertion Temperature & Humidity sensor (HTY7805T1P00)
PV Range: 0 to 100 %RH (1 to 5 VDC)
SP(SV) : 50%RH or settable
Proportional Band: 5%RH(5%); Integral Time: 300 sec
MV output: Reverse Action
Modbus Device ID: 2 and 6
TIC-1/2-2: Supply Air Temperature Controller PXF9AEY2-1VM00
PV input: Duct Insertion Temperature& Dew Point Temp sensor (HTY7905T1P00)
PV Range: 0 to 150 °C (Pt100)
Set Point(SV): 15 to 25 degrees Celsius changeable due to TIC-1/2-1 MV value
Proportional Band: 5 degree Kelvin (3.3% of Range)
Integral Time: 120 seconds
MV output: Reverse Action (when temperature is higher than SP, MV is 0%)
MV:0-50% is Cooling; MV:50-100% is ReHeating
RUN/STANDBY Interlock is done by DDC Controller Judgement
RUN AND Conditions: AHU-1/2 ON; AHU-1/2 STS; AHU-1/2 No Alarm;
AHU-1/2 Velocity Pressure ON; AHU-1/2 Heater No Overheat; No Forced Shutdown
Modbus Device ID: 3 and 7
DIC-1/2: Supply Air Dew Point Temperature Controller PXF9AEY2-1VM00
PV input: Duct Insertion Dew Point Temperature & Temp sensor (HTY7905T1P00)
PV Range: -40 to 60 °CDP (1 to 5 VDC)
Set Point(SV): 10 to 14 degrees Celsius DP changeable due to HIC-1/2 MV value
Proportional Band: 5 degree Kelvin DP (5% of Range)
Integral Time: 120 seconds
MV output: Reverse Action (when Dew Point temperature is higher than SP, MV is 0%)
MV:0-50% is Dehumidifying
RUN/STANDBY Interlock is done by DDC Controller Judgement
RUN AND Conditions: AHU-1/2 ON; AHU-1/2 STS; AHU-1/2 No Alarm;
AHU-1/2 Velocity Pressure ON; No Forced Shutdown
7|Page
Azbil India Private Limited
Modbus Device ID: 4 and 8
8|Page
Azbil India Private Limited
9|Page
Azbil India Private Limited
10 | P a g e
Azbil India Private Limited
SETTINGS
11 | P a g e
Azbil India Private Limited
12 | P a g e
Azbil India Private Limited
13 | P a g e
Azbil India Private Limited
14 | P a g e
Azbil India Private Limited
KEY CONTACTS
(END)