HALFEN HZA-PS POWER SOLUTION

Technical Product Information

Seismic C1/ C2 assessment


NEW report and ETA-17/0728
for HZA-PS 53/34

HZA-PS 20
We are one team.
We are Leviat.
Leviat is the new name of
CRH’s construction accessories
companies worldwide.
Under the Leviat brand, we are uniting the
expertise, skills and resources of HALFEN and its
sister companies to create a world leader in fixing,
connecting and anchoring technology.

The products you know and trust, including the


HALFEN HZA-PS Power Solution, will remain an
integral part of Leviat’s comprehensive brand and
product portfolio. As Leviat, we can offer you an
extended range of specialist products and services,
greater technical expertise, a larger and more agile
supply chain and better, faster innovation.

By bringing together CRH’s construction


accessories family as one global organisation,
we are better equipped to meet the needs of our
customers, and the demands of construction
projects, of any scale, anywhere in the world.

This is an exciting change. Join us on our journey.

Read more about Leviat at Leviat.com


Our product brands include:

sales in

60 30+ 3000
locations countries people worldwide

Imagine. Model. Make. Leviat.com


HALFEN HZA-PS POWER SOLUTION
HALFEN Cast-in Channels for Power Plants

Standard application Safety relevant applications


HALFEN HTA-CE and HZA Channels are officially approved Higher safety requirements for exterior (EVA) or interior
and recommended for applications in normal concrete (EVI) impact loads must be considered in safety relevant
projects; office buildings, schools, industrial buildings or areas e.g. in nuclear power plants or other nuclear facilities.
in non-critical areas of nuclear power plants. The suitability of the HZA-PS Channels for extraordinary
In these applications the maximum crack width in the impact loads has been verified in simulated application tests.
concrete is 0.3 mm. For more information please see the All these tests were done in concrete with opening and clos-
Technical Product Information for HALFEN Cast-in channels. ing cracks varying from 1.0 mm up to 1.5 mm. The results are
Free download at: summarized in evaluation report 09.05.18-E (see also pages
www.halfen.com/brochures/construction/fixing systems/ 8 and 9).
HTA Cast-in channels

Concrete cracks Larger concrete cracks


max. 0.3 mm up to 1.5 mm

HALFEN HTA-CE and HALFEN HZA-PS


HZA Cast-in channels Cast-in channel
annel

Approvals/European Expert Report/


R
Technical Assessments European
uropea Technical
Eu
Assessment
Assessm

Nuclear power plant under construction

4 © 2020 · HZA-PS 20-E · www.halfen.com


HALFEN HZA-PS POWER SOLUTION
HALFEN Cast-in Channels for Power Plants

Approvals
HALFEN Cast-in channels are available in Cast-in channels are embedded in HTA-CE: ETA-09/0339
hot-dip galvanized or in stainless steel. the concrete, flush with the surface. HZA 41/22: App. no. Z-21.4-145
Building authority approved by the Ger- HALFEN T-bolts or serrated t-bolts, nuts HZA Dynagrip: App. no. Z-21.4-1691
man Institute of Construction Engineering and washers are used to reliably attach
(DIBt, Deutsches Institut für Bautechnik). structural elements to the channels.

c ia
l ly HZA-PS 53/34: ETA-17/0728
Z-21.4-... ffi
...

o
European European -
1.4
Technical Technical
Z -2
No
Assessment Assessment
ETA - 09/0339 ETA - 17/0728 p.
Ap

ed
ov
appr

Evaluation Report
HALFEN HZA-PS Cast-in channels are evaluated by the: HZA-PS 53/34; HZA-PS 38/23;
suitable for applications in safety rele- HZA-PS 29/20
vant areas of nuclear power plants and Evaluation Report
Technical University
other nuclear facilities.
Faculty for Architecture and Building of Dortmund 09.05.18-E
HALFEN HZA-PS Cast-in channels meet Engineering
the high requirements for extraordinary Concrete structures – Connection technology
impacts from external (EVA) and inter- HZA-PS 53/34
nal (EVI) loads e.g. earthquakes, plane Seismic C1/C2 assessment
crash or explosions. report, Technical University
of Kaiserslautern, see page 5

Fire Protection
HALFEN HTA and HZA Cast-in chan- The anchor channels have a fire rating
nels, in combination with HALFEN of up to 120 minutes for concrete
Channel bolts, have been certified for structures if installed according to the
use in fire-exposed structural elements. approvals stated above.

Sustainability 
   
     
 

An EPD® (Environmental Product The new HPD (Health Product Decla- 
(""
""
, (-.$$
"
 !"#$%$& !'
 !"#$%$& !'
()*)
, )
$ $ /

+ ) , )

01 2$ $

Declaration) provides transparent and ration) for hot-dip galvanized HALFEN


*34"5),&5'6

*30"

comparable ecological data which Cast-in channels helps to achieve addi-  !!"#$%$ 

helps to evaluate the sustainability tional points in the Leed-v4-system.


of a building.

BIM
We already have considerable experi- Examples of previous projects devel-
ence as a BIM partner and we success- oped using BIM can be found at
fully completed various projects using www.halfen.com/Service/BIM/BIM
the BIM methodology. references.
BIM
Quality
Our subsidiaries are Quality Management certi-
The approvals can be found at:
fied according to ISO 9001:2015, Certificate no. www.halfen.com/downloads/brochures
202384-2016-AQ-GER-DAkkS.

Cert.-no. QS-281 HH

© 2020 · HZA-PS 20-E · www.halfen.com 5


HALFEN HZA-PS POWER SOLUTION
HALFEN Cast-in Channels for Power Plants

The anchor head


The wide, almost parallel anchor head when used in concrete designed for
is a positively interlock connection and possible wide cracks. With the minor
results in very effective load transmis- movement of the anchorage system
sion due to the low bearing pressure during opening and closing of cracks,
under the head. Furthermore, there a reliable fixing with low deformation
is an additional enormous advantage can be guaranteed.

Anchoring depth
Deep anchorage guarantees high load ideal load distribution into the rein-
capacity and compensates for weak- forcement. Simultaneously the chan-
ness in the concrete caused by larger nels (maximum height is 44 mm) are
cracks. Concrete elements designed easily installed in the standard concrete
for safety relevant areas are generally cover which is about 45–60 mm.
densely reinforced. The increase in
anchorage depth helps to ensure an

Channel profile
The manufacturing process for hot- profile into the concrete structure. The
rolled channels has allowed a more hot-roll process also prevents deforma-
efficient design of the channel cross tion over the channel length caused
section. This results in thicker chan- during production and improving the
nel lips which are stronger than the connection of components. Dynamic
channel backs or sides. This feature loads can also be better transmitted as
prevents lip deformation while pro- the hot-rolled material has low internal
viding reliable and efficient transfer stresses.
of impact loads through the channel

Serrated channel lips


A hard-wearing inner serration is The serrated anchor channels are very Type HZS
formed in the channel lip material beneficial for application in seismic
during the rolling process. The serrated zones or other load cases applications;
HALFEN Channel bolts engage with explosion collision loads or similar.
the matching 3.0 mm pitch of the To achieve full load capacities in the
channel serration allowing non-slip, longitudinal direction of the anchor
reliable transfer of loads in the longitu- channels the specified torque has to be
dinal direction of the channel. observed (see installation instructions).
Serration

6 © 2020 · HZA-PS 20-E · www.halfen.com


HALFEN HZA-PS POWER SOLUTION
HALFEN Cast-in Channels for Power Plants

The anchor foot


The anchor foot is welded on all four The extensive weld length is an addi-
edges to the back of the channel. tional safety feature. This is improved
This ensures efficient and even transfer on with regular, selective ultimate load
of static loads and critical dynamic tests of welded anchors in our quality
loads from the channel into the anchor. assurance programme.

HALFEN Channel bolts (serrated) A specified torque is applied to ensure a


Without exception all HZS Channel positive lock between the bolt and the
bolts for the HZA-PS Systems are only serration in the channel. The specified
available in high strength grade 8.8. torque is critical to ensure full load capacity
This ensures reliable transfer of loads in the longitudinal channel direction.
into the channel, even if an additional It is important that the torques specified in
moment acts on the bolt. the installation instructions are observed.

Seismic performance categories C1/C2


assessment report for HZA-PS 53/34 R0k,eq ,steel for each direction and for
The seismic assessment and expert performance category C1 and C2.
reports for the HALFEN anchor
load [kN]

channel HZA-PS 53/34 cover the HALFEN Anchor Channels HZA-PS


technical specifications of the AFCEN 53/34 fulfil the high requirements of
code RCC-CW, which corresponds to seismic performance category C2 with
the demands of ETAG 001 Annex E excellent ductile behaviour, no anchor
(replaced by TR 049). The report pro- failure and low displacements.
vides characteristic seismic resistance displacement [mm]

Quality
Our production facilities are Chemical, mechanical and geometric
EN ISO 9001 certified. The certifica- material properties are also checked.
tion requires regular maintenance of All products are subject to random
all machines and continual inspections quality testing during production
of all processes at the facilities. The which includes ultimate tensile
production facilities are certified for testing. The zinc layer is regularly
welding processes according to inter- checked for thickness to ensure good
national standard EN ISO 3834-2 and quality corrosion protection.
EN 1090. All incoming material must
be certified acc. to EN 10204.

Certification
According to DIN EN 10204 the the delivered product (inspection 3.1
following documents may be certificate).
requested: The customer can request a 3.1 certifi-
Acceptance certificates based on non- cate when placing an order.
specific test (production 2.1 certificate A 3.1 certificate issued by a manu-
and production 2.2 certificate [a more facturer confirms the test results of the
detailed description]) and acceptance delivered products fulfil the specified
certificates based on specific tests on requirements.

© 2020 · HZA-PS 20-E · www.halfen.com 7


HALFEN HZA-PS POWER SOLUTION
HALFEN Cast-in Channels for Power Plants

With more than 90 years of experience A logical complement to the serrated This additional research and the tests
we became a world leader in providing hot rolled channel range, the HZA-PS assume extreme interior and
adjustable anchoring systems. product range allows application in exterior load-effects caused by earth-
safety relevant areas of nuclear power quakes, explosions and plane impacts.
HALFEN Cold-rolled cast-in channels ful- stations and facilities.
fil all basic requirements for an adjusta-
ble, user-friendly and reliable anchoring A dedicated test-programme carried
system. The product family includes out at the Technical University of
hot-rolled channels with optimal charac- Dortmund/Germany confirms suita-
teristics for reliable transfer of dynamic bility of HALFEN Channels HZA-PS
loads. The hot-rolled serrated HALFEN 53/34, HZA-PS 38/23 and HZA-PS
Channels are also suitable for transfer 29/20 for exceptional loads.
of loads in its longitudinal direction.

Hot-rolled channels and Hot-rolled serrated


Cold-rolled channels
hot-rolled serrated channels channels HZA-PS

Main features: Additional features: Additional features:

 safety  suitable for dynamic loads  suitable for safety relevant areas
 reliability  flush with the concrete surface and extraordinary loads
 efficiency with non-deformed channel lips  stringent quality management
 adjustable bolt connection  suitable for loads in all directions and inspections
(serrated channels)
 no damage to concrete or
reinforcement  certified for seismic loads
(serrated channels)
 suitable for cracked or
non-cracked concrete
 approved for fire-resistant
structural elements
©Vattenfall AB
©Vattenfall AB

Fuel element cooling Turbine block in a nuclear power plant

8 © 2020 · HZA-PS 20-E · www.halfen.com


HALFEN HZA-PS POWER SOLUTION
HALFEN Cast-in Channels for Power Plants

HZA -PS Cast-in channels

HZA-PS 29/20 HZA-PS 38/23 38


29

20

23
166 *
163 *
35 ≤ 250 35

140
35 ≤ 200 35

140 5.7 18
5.7 12

40
40

HZA-PS 53/34 52.5 HZA-PS 64/44


64
34

44
177 *

187*
35 ≤ 250 35
35 ≤ 250 35
140

140
5.7 30 5.7 40

40 40
*calculated with tolerance
Available lengths (made to order) and anchor spacing

HZA-PS 38/23, 53/34, 64/44 – Standard lengths HZA-PS 29/20 – Standard lengths
Length [mm] / Number of anchors Length [mm] / Number of anchors
200 / 2 350 / 3 550 / 3 800 / 4 200 / 2 350 / 3 550 / 4 800 / 5
1050 / 5 3030 / 13 6070 / 25 1050 / 6 3030 / 16 6070 / 31

HZA-PS 38/23, 53/34, 64/44 – Fixed standard lengths HZA-PS 29/20 – Fixed standard lengths
Length [mm] / Number of anchors Length [mm] / Number of anchors
- 1300 / 6 1550 / 7 1800/ 8 1250/ 7 1450/ 8 1650/ 9 1850/ 10
2050 / 9 2300/ 10 2550/ 11 2800/ 12 2050/ 11 2250/ 12 2450/ 13 2650/ 14
- 3300/ 14 3550/ 15 3800/ 16 2850/ 15 - 3250/ 17 3450/ 18

4050/ 17 4300/ 18 4550/ 19 4800/ 20 3650/ 19 3850/ 20 4050/ 21 4250/ 22

5050/ 21 5300/ 22 5550/ 23 5800/ 24 4450/ 23 4650/ 24 4850/ 25 5050/ 26


5250/ 27 5450/ 28 5650/ 29 5850/ 30
3 ≤ 3
3 ≤ 3

© 2020 · HZA-PS 20-E · www.halfen.com 9


HALFEN HZA-PS POWER SOLUTION
HALFEN Cast-in Channels for Power Plants

Various specifications taken from different certifications and


categories apply in nuclear power plants and nuclear facilities
(see DIN 25449):

Category A3: Load cases which may occur only once during
the lifetime of the facility:

• earthquake 1.0 mm/1.5 mm


• plane crash
• exterior explosion
• interior explosion 1.0 and 1.5 mm concrete cracks in the location of the anchor
• differential pressure
• supporting forces etc. Load

Category A2: Load cases which are likely to occur less than
ten times during the lifetime of the facility.

Category A1: Load cases which are likely to occur more than
ten times during the lifetime of the facility.

As a result of the higher demands of category A3 and A2


wider concrete cracks must be considered. Therefore, the Deformation
behaviour of the anchoring system is examined in additional Load-deformation diagram of a pull-out test showing the constant load
increase with low deformation until maximum load is achieved.
suitability tests with larger crack widths.
The existing guidelines set by the (DIBt) German Institute
of Building Technology for use of post installed anchors in
nuclear power plants was the basis used for specification
of the additional tests.

Examples of tests include:

1. Pull-out test; the anchor was tested in a 1.0 mm


wide
wideconcrete
concretecrack
crack

2. Pull-out test; the anchor was tested in a 1.5 mm


wide concrete crack

Test setup; pull-out test

10 © 2020 · HZA-PS 20-E · www.halfen.com


HALFEN HZA-PS POWER SOLUTION
HALFEN Cast-in Channels for Power Plants

3. Performance test in an opening and closing


4. Cyclic load change in a wide concrete crack
concrete crack

For this purpose, 10 oscillations were applied with a frequency In this test, cracks in the concrete were opened to 1.5 mm
of 0.2 Hz; the concrete crack varying between 1.0 and 1.5 and a tension load applied to the cast-in channel.
mm, while the cast-in channel was subjected to a constant The load was then completely removed from the cast-in
tension load. A pull-out test was subsequently carried out channel. In this test 15 load cycles with a frequency F < 1 Hz
in the widest concrete crack of 1.5 mm. were applied. A pull-out test was subsequently carried out in
the widest (1.5 mm) concrete crack.

Load

Deformation

Anchor position directly in an opening and closing concrete crack. Load-displacement diagram - even after the cyclic load test the final
pull-out test shows a steady increase with only low deformation.

Crack width Adjustment Apply Test of residual


1.5 mm
to 1,5 mm of crack preload to load capacity
anchor
1.6

1.4

1.2
Crack width [mm]

0.8 crack widths


varied
0.6

0.4

0.2

0
0 500 1000 1500 2000
Time [s]

Chronological test procedure

Load

Deformation
Load-displacement diagram: shows ductile behaviour during the final
pull-out test. Test setup for cyclic load test

© 2020 · HZA-PS 20-E · www.halfen.com 11


HALFEN HZA-PS POWER SOLUTION
HALFEN Cast-in Channels for Power Plants

HZS bolts — available lengths

HZS 29/20 HZS 38/23 HZS 53/34 HZS 64/44 Product identification
M12 M16 M20 M24
Nomenclature on bolt head:

Manufacturer
HALFEN
H 4.6
8.8 Strength grade 8.8
(electroplated with addi-
tional special coating )
 equivalent to HDG coating for interior applications
H Z S T- B o l t l e n g t h s

Bolt type/ Grade 8.8


Bolt diameter (mm)
channel profile Bolt length (mm) 2 notches on the tip of
HZS 64/44 M24 80, 150 the shank. Used to verify
HZS 53/34 M20 65, 100 correct installation in the channel.
HZS 38/23 M16 40, 60, 80
HZS 29/20 M12 60, 80
For bolts in other lengths and diameters please contact
us (→ see page 19).

Example order for bolts: Example order for channels:


HZS 53/34 M20x100 GV-S8.8 HZA -PS 53/34-FV-1050-KF
Bolt prefix Channel prefix
Channel profile Channel profile
Bolt diameter Material/finish (FV)
Length (mm) Length (mm)
Finish and grade (GVs 8.8) Combination strip filler
(GVs = electroplated with additional special coating) (FV = hot-dip galvanized)

Tender specifications- Examples

1. HALFEN Cast-in channels


1.1 HALFEN HZA-PS Channel type – Power Solution
HALFEN HZA-PS Cast-in channel , hot-dip galvanized (FV) with strip filler (KF),
suitable for adjustable connections to concrete in safety relevant areas of nuclear
plants or other nuclear installations, channel length mm, design resistance FRd =
kN in all directions, up to kN dynamic loading, delivery and installation according
to the installation instructions.

2. HALFEN Bolts
2.1 HALFEN Bolts type HZS
HALFEN HZS serrated bolt suitable for the corresponding HALFEN HZA-PS
Cast-in channel, electroplated with special coating, including nut, delivery and instal-
lation according to the installation instructions.

12 © 2020 · HZA-PS 20-E · www.halfen.com


HALFEN HZA-PS POWER SOLUTION
HALFEN Cast-in Channels for Power Plants

Load capacities, HZA-PS 53/34 acc. to ETA-17/0728

The HZA-PS 53/34 (ETA-17/0728) design is based on EOTA Verification will account for specific boundary conditions and
TR 047 (EN 1992-4). differentiates between steel and concrete failure modes.

Profile load capacity* HZA-PS 53/34


HZA-PS 53/34 acc. to ETA-17/0728

N0Rd, s, l [kN] 43.7 * Concrete load capacity has to be verified for each individual case
V0Rd, s, l,y [kN] 43.7 (taking the geometric boundary conditions into account).

VRd, s, l,x [kN]/inst 27.3 N0Rd,s,l = channel lip load capacity (tension)
V0Rd,s,l,y = channel lip load capacity (shear perpendicular)
MRd, s, flex [Nm] 3538 VRd,s,l,x = channel lip load capacity (shear longitudinal)

Seismic performance categories C1 and C2

HALFEN HZA-PS 53/34 Cast-in channels have been tested


under simulated seismic tension and shear loads according to The Support team is available to help with
EOTA TR 049 for seismic performance categories C1 and C2. planning. Contact Information can be found
The assessment of the test results was done by the Techni- at the back of the catalogue or go to:
cal University of Kaiserslautern and can be found in the test www.halfen.com
report. Available on request.
l ly
c ia

.
- ..

o
Load capacities of HZA-PS according to Z-21.4-1691 No
Z -2
1.4

p.
Ap

ed
ov
appr

Loads where:
All the values shown are design resistance capacities and G = partial factor for permanent loads
should therefore be compared against fully factored loads. Gk = characteristic value of permanent loads (dead load)
q = partial factor for variable loads
e.g. FEd = G Gk + Q Qk Qk = characteristic value of variable loads (imposed or live load)

Design steel resistance FRd s = anchor spacing see page 7

FRd with simultaneous loading in all directions Single loads Load pairs

s s

y x
F F F F F F F

To check:  b1 b2 p1 b1 p2
bi ≥ 250 bi ≤ 250
A FEd = NEd2 + VxEd2 + VyEd2 < FRd
FRd [kN] FRd [kN] 
B Vx,Ed ≤ 0.8 x FRd (single load)
z bi ≥ 250 pi = 50 pi = 100 pi = 150 pi = 200 pi = 250

64/44 37.8 - 23.6 27.0 31.5 37.8

53/34 30.8 - 19.25 22.0 25.7 30.8


HZA-PS profile 
38/23 16.8 9.4 10.5 12.0 14.0 16.8

29/20 11.2 6.3 7.5 9.0 11.2 11.2

 Check B is only necessary if there are 2 or more bolts connecting one component.
 Intermediate values may be linearly interpolated.
Sufficient concrete resistances are provided if the boundary conditions are in accordance with the approval Z-21.4-1691 and the
Technical Product Information for HALFEN Cast-in channels.
Extraordinary impact loads from external (EVA) or internal (EVI) forces are given in the Evaluation Report TU Dortmund.
Available on request. Also see page 3.

© 2020 · HZA-PS 20-E · www.halfen.com 13


HALFEN HZA-PS POWER SOLUTION
System Solutions/Application Examples

Planning with our products provides a wide range of possible More than 90 Years of experience is packed into our products.
design solutions: Nuclear power plants (EVA and Contact the our support team to design and effectively dimen-
EVI impact load requirements); sewage plants with larger sion a project.
pipe sizes; very long cable runs; pipe supply lines in utillity See the back of the catalogue for contact addresses or go to
or other types of tunnels; various other fixings, even to www.halfen.com
curved or slanted surfaces.

Stacked cable trays fixed to vertical serrated channels

Pipe support fixed to vertical cast-in serrated channel

Cantilever fixed to a vertical serrated channel for pipe support

Pipe fixed to anchor channels cast into a ceiling slab Cantilever fixed to vertical serrated channel for pipe support

14 © 2020 · HZA-PS 20-E · www.halfen.com


HALFEN HZA-PS POWER SOLUTION
HALFEN System Solutions/Channel ring

Example: designing with the our Engineering Support Team

Our technical support team starts with outline drawings, Standard and custom elements are combined when
which should include some basic information. designing a pipe support system; this ensures the best
and most economical solution for a specific project.
Our Engineering Support Team always strive
From your drawings... to achieve the best balance between safety and economy.
Always working in close cooperation with the customer
throughout the design process to find the best connections
for a project.
See the back of the catalogue for contact addresses or go
to www.halfen.com

..to a detailed design and a


successful
project

Example of a medium duty


framing channel ring HCS–SRI.
DN 2
DN 250
50
0 Available in hot-dip galvanized
Available in stainless steel

DN
DN 200
20
00
00
0
90

Serrated framing
R=

channel 1300

DN 3
DN 30
300
00
00 DN 250
~ 450 to center

1000

D
DNN 20
00
00
200 DN 300

Alternative:
Serrated anchor
channel

Example for a
hinged support
Example for a hinged beam

© 2020 · HZA-PS 20-E · www.halfen.com 15


HALFEN HZA-PS POWER SOLUTION
HALFEN HTA-CE/HZA Cast-in Channels

HTA-CE 72/48 HZA 64/44 HTA-CE 55/42 HZA 53/34 HTA-CE 52/34

187
191

161
185

177
hot-rolled

72
64
54.5
52.5
52.5
48.5

44

33.5
42

34
33 26 22.5
26 22.5

Bolt: Bolt:
HS 72/48 Bolt: Bolt: Bolt: HS 50/30
HSR 72/48 HZS 64/44 HS 50/30 HZS 53/34 HSR 50/30

Material: Material: Material: Material: Material:

HTA-CE 54/33 HTA-CE 49/30


HALFEN Cast-in channels are available in cold-
rolled or hot-rolled designs, with serrated or
non-serrated channel lips. Other Information not
included here; calculation notes, installation and
further application examples can be found in
the HALFEN Cast-in channels, Technical Product
161

Information:
Free download at: www.halfen.com
54
103
cold-rolled

100

53.5
50
33

30

22 22

FV = steel, hot-dip galvanized suitable for


dynamic loads Bolt: Bolt:
A4 = stainless steel
HS 50/30 HS 50/30
HCR = high corrosion resistant
steel Material: Material:
serrated channel

16 © 2020 · HZA-PS 20-E · www.halfen.com


HALFEN HZA-PS POWER SOLUTION
HALFEN HTA-CE/HZA Cast-in Channels

HTA-CE 50/30-P HZA 38/23 HTA-CE 40/22-P HZA 29/20


100
112

99

87
97

87
49 38 39.5 29
30

23
23

20
18 18 14
22.5

Bolt: Bolt:
HS 50/30 Bolt: HS 40/22 Bolt:
HSR 50/30 HZS 38/23 HSR 40/22 HZS 29/20

Material: Material: Material: Material:

HTA-CE 40/25 HZA 41/22 HTA-CE 38/17 HTA-CE 28/15

40*
89

75

81
85

41.3 38 28
50
20.5
25

15.25
17.5

18 22.3 18 12

Bolt: Bolt: Bolt: Bolt:


HS 40/22 HZS 41/22 HS 38/17 HS 28/15
Material: Material: Material: Material:
* 40
* 39.5

© 2020 · HZA-PS 20-E · www.halfen.com 17


HALFEN HZA-PS POWER SOLUTION
System Solutions/Application Examples

Air ventilation duct


supported with a welded
steel frame anchored to
a concrete slab with a
pair of serrated channels

Air ventilation duct


support
suspended as a light
weight system
bolted to a concrete slab
using a serrated channel

Air ventilation duct


support
a HALFEN Framing system
suspended from a
concrete slab with a pair
of serrated channels

Cable tray support


cantilever brackets
fixed to a vertical
serrated channel

18 © 2020 · HZA-PS 20-E · www.halfen.com


HALFEN HZA-PS POWER SOLUTION
System Solutions/Application Examples

A revolution in pipe support in


tunnels! The HALFEN Adjustable
cantilever combines the acclaimed
high load bearing capacity of the
medium duty system with a much
faster installation. Specially design-
ed for use in tunnels or other app-
lications with curved or slanted
surfaces. It is not necessary to know
the cantilever angles at planning.
One part for all fixings, dramatically
reduces complexity.
No custom cantilevers required, HALFEN Adjustable cantilever
no angles to measure. Angle and height adjustable

Suspended pipes and


cable trays with standard
cantilever brackets.
Height adjustable
using HALFEN Framing
HALFEN Cantilever
channels. height adjustable

The HALFEN Framing system product range


can be found in the following catalogues:
HALFEN Flexible bolt connections,
HALFEN Flexible framing connections
HALFEN Powerclick System.

Typical application of the HALFEN System: Anchor and framing channels with Powerclick and
framing fittings

© 2020 · HZA-PS 20-E · www.halfen.com 19


HALFEN HZA-PS POWER SOLUTION
System solutions/Application Examples

Example for standard cantilever with loads

HALFEN can supply standard cantilevers For higher loads with support bracket
with European Technical Approval from
stock. This brief extract from the main
catalogue illustrates just some of the Example:
HALFEN KON 42/2
available KON 52/2 cantilevers and the cantilever with bracing
corresponding working loads (allow.
load) i.e. the design resistances acc. to
Fixing to wall with T-head bolts to
Eurocode 3 (FRd). For more information a HALFEN Channel or with dowels
please see the MT-FFC Flexible Framing
Construction catalogue.
KON 52/2 Extract with sizes and load bearing capacities
F1 F1 F2 F2
Dimensions hot-dip stainless
galvanized steel A4
L
FV
Length Height Length
L/2 L/2 L L/3 L/3 L/3
L H LS
Order no. Order no.
[mm] [mm] [mm]
0310.080- 0310.080- F [kN] F1 F1 F2
H
30° allow. load 9.0 15.0 7.5
500 450 330 00001 00008
F Rd 12.6 21.0 10.5
allow. load 8.0 15.0 7.5
600 475 380 00002 00009
F Rd 11.2 21.0 10.5
allow. load 7.0 15.0 6.5
34
KON 52/2 700 500 430 00003 00010
F Rd 9.8 21.0 9.1
LS
allow. load 6.0 15.0 6.0
800 550 480 00004 00011
F Rd 8.4 21.0 8.4

Example for a custom cantilever solution

Cantilever for a safety relevant area


at the ITER fusion reactor (France).
Customized cantilevers for a cable
tray support, installed to a HALFEN
Cast-in channels.

Custom cantilever for a safety


relevant area:

 pre-assembled fixings provide fast


installation
 versatile and reliable support for
different types of cable trays

20 © 2020 · HZA-PS 20-E · www.halfen.com


Innovative engineered products and
construction solutions that allow
the industry to build safer,
stronger and faster.
Worldwide contacts for Leviat:

Australia Germany Poland


Leviat Leviat Leviat
98 Kurrajong Avenue, Liebigstrasse 14 Ul. Obornicka 287
Mount Druitt Sydney, NSW 2770 40764 Langenfeld 60-691 Poznań
Tel: +61 - 2 8808 3100 Tel: +49 - 2173 - 970 - 0 Tel: +48 - 61 - 622 14 14
Email: info.au@leviat.com Email: info.de@leviat.com Email: info.pl@leviat.com
Austria India Singapore
Leviat Leviat Leviat
Leonard-Bernstein-Str. 10 309, 3rd Floor, Orion Business Park 14 Benoi Crescent
Saturn Tower, 1220 Wien Ghodbunder Road, Kapurbawdi, Singapore 629977
Tel: +43 - 1 - 259 6770 Thane West, Thane, Tel: +65 - 6266 6802
Email: info.at@leviat.com Maharashtra 400607 Email: info.sg@leviat.com
Tel: +91 - 22 2589 2032
Belgium Spain
Email: info.in@leviat.com
Leviat Leviat
Borkelstraat 131 Italy Polígono Industrial Santa Ana
2900 Schoten Leviat c/ Ignacio Zuloaga, 20
Tel: +32 - 3 - 658 07 20 Via F.lli Bronzetti 28 28522 Rivas-Vaciamadrid
Email: info.be@leviat.com 24124 Bergamo Tel: +34 - 91 632 18 40
Tel: +39 - 035 - 0760711 Email: info.es@leviat.com
China
Email: info.it@leviat.com
Leviat Sweden
Room 601 Tower D, Vantone Centre Malaysia Leviat
No. A6 Chao Yang Men Wai Street Leviat Vädursgatan 5
Chaoyang District 28 Jalan Anggerik Mokara 31/59 412 50 Göteborg
Beijing · P.R. China 100020 Kota Kemuning, 40460 Shah Alam Tel: +46 - 31 - 98 58 00
Tel: +86 - 10 5907 3200 Selangor Email: info.se@leviat.com
Email: info.cn@leviat.com Tel: +603 - 5122 4182
Switzerland
Email: info.my@leviat.com
Czech Republic Leviat
Leviat Netherlands Hertistrasse 25
Business Center Šafránkova Leviat 8304 Wallisellen
Šafránkova 1238/1 Oostermaat 3 Tel: +41 - 44 - 849 78 78
155 00 Praha 5 7623 CS Borne Email: info.ch@leviat.com
Tel: +420 - 311 - 690 060 Tel: +31 - 74 - 267 14 49
United Kingdom
Email: info.cz@leviat.com Email: info.nl@leviat.com
Leviat
Finland New Zealand A1/A2 Portland Close
Leviat Leviat Houghton Regis LU5 5AW
Vädursgatan 5 2/19 Nuttall Drive, Hillsborough, Tel: +44 - 1582 - 470 300
412 50 Göteborg / Sweden Christchurch 8022 Email: info.uk@leviat.com
Tel: +358 (0)10 6338781 Tel: +64 - 3 376 5205
United States of America
Email: info.fi@leviat.com Email: info.nz@leviat.com
Leviat
France Norway 6467 S Falkenburg Rd.
Leviat Leviat Riverview, FL 33578
18, rue Goubet Vestre Svanholmen 5 Tel: (800) 423-9140
75019 Paris 4313 Sandnes Email: info.us@leviat.us
Tel: +33 - 1 - 44 52 31 00 Tel: +47 - 51 82 34 00
Email: info.fr@leviat.com Email: info.no@leviat.com
For countries not listed
Philippines Email: info@leviat.com
Leviat
2933 Regus, Joy Nostalg,
ADB Avenue
Ortigas Center
Pasig City
Tel: +63 - 2 7957 6381
Email: info.ph@leviat.com

Leviat.com
For information on certified management systems and standards see www.ancon.co.uk | www.aschwanden.com | www.halfen.com

Notes regarding this catalogue


© Protected by copyright. The construction applications and details provided in this publication are indicative only. In every case, project
working details should be entrusted to appropriately qualified and experienced persons. Whilst every care has been exercised in the preparation
of this publication to ensure that any advice, recommendations or information is accurate, no liability or responsibility of any kind is accepted
by Leviat for inaccuracies or printing errors. Technical and design changes are reserved. With a policy of continuous product development,
Leviat reserves the right to modify product design and specification at any time.
PDF 10/20
B-137-E – 02/20
© 2020

Imagine. Model. Make. Leviat.com