SECTION 2 – SYSTEM COMPONENTS SAPPHIRE PLUS Total Flood

UL EX4510 Fire Suppression System with FK-5-1-12 Agent


PAGE 2-46 REV. 00 2022-JUL-06 (Part No. 451539)

DISCHARGE NOZZLES
(Part number, See Table 2-31)
FK-5-1-12 agent distributes within the protected area by the
discharge nozzle which is sized to ensure the correct flow
of agent for the risk. Nozzles are available with seven port
(180°) or sixteen port (360°) horizontal discharge patterns.
Ports are drilled in 0.1 mm increments by the manufacturer to
the specified system design. Nozzles are supplied in brass or
stainless steel. Table 2-31 lists the discharge nozzle details.

Location on system
The discharge nozzles are fitted at the end of the discharge
pipework.

Technical specification
Material: Aluminum, brass, or stainless steel 180° nozzle pattern (7 PORTS)

Thread type: BSPT or NPT Female


(NPT thread is denoted by v-groove
around knurling)
Sizes: 15 mm, (1/2 in.), 20 mm (3/4 in.),
25 mm (1 in.), 32 mm (1 1/4 in.),
40 mm (1 1/2 in.), and 50 mm (2 in.)
Drilling increments: 0.1 mm
Nozzle types: 16 port (360°) or 7 port (180°)
Nozzle coverage radius: See Table 2-31
Maximum protection 4.3 m (14.1 ft)
height:
Minimum protection 0.3 m (1.0 ft)
height:
Maximum distance from 0.3 m (1.0 ft)
ceiling:
Minimum / Maximum 0.05 m to 0.3 m
distance from wall to (0.2 ft to 1.0 ft)
360° nozzle pattern (16 PORTS)
center of 180° nozzle:
Maximum coverage See Table 2-30 FIGURE 2-38
area per nozzle: 7 AND 16 PORT NOZZLES - BRASS CONFIGURATION
010466 / 010467 / 010468 / 010469
Minimum nozzle 6.33 bar (91.8 psi)
pressure:
Note: The nozzles are drilled and marked in metric (mm) only.
Working temperature -20 °C to 50 °C (-4 °F to 122 °F)
range: (LPCB standard coverage area)
-18 °C to 50 °C (0 °F to 122 °F)
(UL and FM standard coverage
area)
0 °C to 50 °C (32 °F to 122 °F)
(LPCB extended coverage area)
0 °C to 65 °C (32 °F to 149 °F)
(UL and FM extended coverage
area)
Orientation: Pendant / Upright
Approvals and listings: LPCB, UL and FM
Marking requirements: Manufacturer's mark, serial number,
part number, and drill size in mm